HV Cable Sizing Calculation (MOL) - Fahahil

2006-4851 Rev. 1

A Input Data as per Specifications 1 2 3 4 5 6 Nominal System Voltage Highest System Voltage Short Circuit capacity Ground temperature Soil thermal resistivity Maximum depth of laying : : : : : : 3.3 kV 3.6 kV 25 kA for 1 second 40 C 2.5 C m/W 1.0 m

B Calculation B1 Required cross section of cable for short circuit withstanding capability The new cable shall withstand a Fault level of 25 kA for 1 sec. Cable cross section of 300 sq.mm is able to withstand the fault level = 42.9 kA for 1 sec. ( Refer cable catalogue in Attachment-1, sheet 3 ) For adequacy check of continuous current capacity & voltage drops, following steps are utilised ( Refer attached sheet for calculation ) B2 Derated current : Ic x TDF where Ic = Current rating of the proposed cable TDF = Total Derating factor for the cables laid in ground : ( 3 x I x (R cos + X sin ) x L / NR) where I = Full load current R = Per metre resistance of cable X = Per metre reactance of cable cos = 0.8 sin = 0.6 L = Length in metres NR = Number of cables run in parallel

B3 Actual Voltage drop

B4 Allowable Voltage drop (as per clause 8.3.2 of QP Spec. ES.2.03.0001, rev.A) a) During normal operation = 5%

B5 Minimum required current rating

: Iflc / T.D.F Where Iflc = Full load current T.D.F = Total Derating factor for the cables laid in ground

C Result C1 3.3kV grade, 3C 300 sq.mm CU/XLPE/SWA/PVC cable is selected for the New MOL VSDS Input transformer.

2006-4851, rev 1 Attachment-1, Sheet 1

HV CABLE SIZING CALCULATION


A Sl. No. From To B C D E Cable Length (L) kVA 1 14SB-3003 VSDS Input transformer 1600 metres 150 279.9 F Full load Load current in Amps. (Iflc) G current (Ist) Iflcx6.5 YES 1 Ground 0.6208 H
(CU/XLPE/

I No. of runs

J Type of installation

K Total Derating factor TDF

L Min. reqd. cable current rating (F/K) 450.9

N Current

O Result for proposed cable size

P Voltage drop during running volts

Q % Volt-drop during running % 0.25

R Voltage drop during starting volts -

S % Volt-drop during starting % -

Feeder details

Starting Cable type in Amps. SWA/PVC)

Proposed rating of the cable size proposed cable (Sq.mm.) 300 (amps.) 481

SAFE

8.15

Manufacturer data ( refer attached DUCAB catalogue copies )


Derating Factors for cables laid in ground
Derating factor for ground temperature Derating factor for variation in thermal resistivity of soil 2.5 C M/W (Multicore) Derating factor for depth of laying ( upto 300 sq.mm. ) Derating factor for grouping two cables laid in horizontal formation touching TDF for cables laid in ground Notes: = = 0.8 0.6208 = 0.98 300 0.08 0.08 481 = 0.74 = 1.07 Cable size (Sq.mm) (ohms/km) (ohms/km)

Cable data
Resistance Reactance Current rating in Ground (amps.)

2006-4851, rev 1 Attachment-1, Sheet 2

LV CABLE SIZING
Derating factors : The following De-rating factors are considered for LV cable sizing.: Laid In Ground Ground Temperature @ 400C = Soil Thermal resistivity = 2.5 deg.C m/W Depth of installation @ 700 mm= Grouping of cables for 5 circuits Hence Total De-rating factor for Cables = 0.82 0.74 0.96 0.59
AxBxCxD 0.344

A B C
D

(refer Table 3 of Ducab catalogue in Attachment-2, sheet 3) (refer Table 4 of Ducab catalogue in Attachment-2, sheet 3) (refer Table 5 of Ducab catalogue in Attachment-2, sheet 4) (refer Table 7 of Ducab catalogue in Attachment-2, sheet 5)

Voltage Drop at steady State Voltage drop = mV x I x L/1000 in volts % Voltage drop = voltage drop x 100/ operating voltage Where, I = Full load current in Amps. L = Cable length in mtrs. mV = Approx. Voltage drop /amp/mtr
5% voltage drop is considered as the limit for the normal condition checks.

Voltage drop During motor Starting Voltage drop = SC x mV x I x L/1000 in volts in volts % Voltage drop = voltage drop x 100/ operating voltage Where, SC = Multiplying factor for starting current
20% voltage drop is considered as the limit for the starting condition checks.

2006-4851, rev 1, Attachment -2, sheet 1

2006-4851, rev 1, Attachment -2, sheet 1

LV CABLE SIZING CALCULATION TABLE


Operating Voltage Required Ampacity of Cable Rating of Current Feeder Rating Carrying Capacity Load Selected Cable Size Motor Starting Equipment Description / Tag Number To From (A) (B) in kVA
800 741

Cable Current

Motor Rating

Cable Length

Full Load

For Selected Cable

Voltage Drop Steady State Allowed

Efficiency

Overall Derating Factor

Voltage Drop During Motor Starting Selected Cable Allowed (T) in %


N.A N.A

(C) in kW

(D) (E) in in Amps Volts


415 415

(F)

(G)

(H) in Amps
1113.00

(I)

(J) in Amps
3235.46 2154.07

(K) (L) in Runs Sq.mm. per Ph


1C x 630 300 4 4

(M) in Amps
1000 590

(N) in Mtrs
155 140

(O) in
mV/A/m

(P) in %
2.03 1.19

(Q) in %
5.0 5.0

(R) in x FL
NA NA

Current

Factor

Power

(S) in %
NA NA

VSDS Trfe Secondary-1&2 VSDS Inverter-1/2&3

VSDS Panel Incomer Unit VSDS Motor

0.344 0.344

0.195 0.190

0.80

0.90

741.00

NOTES: H = B/(1.732xE) or (C/G)/(1.732xExF) or D; J = H/I; P = HxNxOx100/(Ex1000xL); S = PxR

2006-4851, rev 1, Attachment-2, sheet 2