2006-4851 Rev. 1
A Input Data as per Specifications 1 2 3 4 5 6 Nominal System Voltage Highest System Voltage Short Circuit capacity Ground temperature Soil thermal resistivity Maximum depth of laying : : : : : : 3.3 kV 3.6 kV 25 kA for 1 second 40 C 2.5 C m/W 1.0 m
B Calculation B1 Required cross section of cable for short circuit withstanding capability The new cable shall withstand a Fault level of 25 kA for 1 sec. Cable cross section of 300 sq.mm is able to withstand the fault level = 42.9 kA for 1 sec. ( Refer cable catalogue in Attachment-1, sheet 3 ) For adequacy check of continuous current capacity & voltage drops, following steps are utilised ( Refer attached sheet for calculation ) B2 Derated current : Ic x TDF where Ic = Current rating of the proposed cable TDF = Total Derating factor for the cables laid in ground : ( 3 x I x (R cos + X sin ) x L / NR) where I = Full load current R = Per metre resistance of cable X = Per metre reactance of cable cos = 0.8 sin = 0.6 L = Length in metres NR = Number of cables run in parallel
B4 Allowable Voltage drop (as per clause 8.3.2 of QP Spec. ES.2.03.0001, rev.A) a) During normal operation = 5%
: Iflc / T.D.F Where Iflc = Full load current T.D.F = Total Derating factor for the cables laid in ground
C Result C1 3.3kV grade, 3C 300 sq.mm CU/XLPE/SWA/PVC cable is selected for the New MOL VSDS Input transformer.
I No. of runs
J Type of installation
N Current
Feeder details
Proposed rating of the cable size proposed cable (Sq.mm.) 300 (amps.) 481
SAFE
8.15
Cable data
Resistance Reactance Current rating in Ground (amps.)
LV CABLE SIZING
Derating factors : The following De-rating factors are considered for LV cable sizing.: Laid In Ground Ground Temperature @ 400C = Soil Thermal resistivity = 2.5 deg.C m/W Depth of installation @ 700 mm= Grouping of cables for 5 circuits Hence Total De-rating factor for Cables = 0.82 0.74 0.96 0.59
AxBxCxD 0.344
A B C
D
(refer Table 3 of Ducab catalogue in Attachment-2, sheet 3) (refer Table 4 of Ducab catalogue in Attachment-2, sheet 3) (refer Table 5 of Ducab catalogue in Attachment-2, sheet 4) (refer Table 7 of Ducab catalogue in Attachment-2, sheet 5)
Voltage Drop at steady State Voltage drop = mV x I x L/1000 in volts % Voltage drop = voltage drop x 100/ operating voltage Where, I = Full load current in Amps. L = Cable length in mtrs. mV = Approx. Voltage drop /amp/mtr
5% voltage drop is considered as the limit for the normal condition checks.
Voltage drop During motor Starting Voltage drop = SC x mV x I x L/1000 in volts in volts % Voltage drop = voltage drop x 100/ operating voltage Where, SC = Multiplying factor for starting current
20% voltage drop is considered as the limit for the starting condition checks.
Cable Current
Motor Rating
Cable Length
Full Load
Efficiency
(C) in kW
(F)
(G)
(H) in Amps
1113.00
(I)
(J) in Amps
3235.46 2154.07
(M) in Amps
1000 590
(N) in Mtrs
155 140
(O) in
mV/A/m
(P) in %
2.03 1.19
(Q) in %
5.0 5.0
(R) in x FL
NA NA
Current
Factor
Power
(S) in %
NA NA
0.344 0.344
0.195 0.190
0.80
0.90
741.00