SELECTION GUIDE
Characteristic
Controller tasks: Continuous Periodic Event
1769 CompactLogix
1769-L35x: 8 tasks 1769-L32x: 6 tasks 1769-L31: 4 tasks Event tasks: consumed tag and EVENT instruction triggers
1789-L10: 2 MB; 1 controller; no motion 1768-L43: 1768-L45: 2 MB 3 MB 1769-L31: 1769-L32x: 1769-L35x: 512 KB 750 KB 1.5 MB 1789-L30: 64 MB; 3 controllers 1789-L60: 64 MB; 6 controllers 1.5 MB
User memory
CompactFlash
CompactFlash
CompactFlash
None
CompactFlash
1769-L31: 2 RS-232 ports 1769-L32C, -L35CR: 1 ControlNet port and 1 RS- Depends on personal 232 serial port computer 1769-L32E, -L35E: 1 EtherNet/IP port and 1 RS232 serial port
Communication options
EtherNet/IP (standard and safety) ControlNet (standard and safety) DeviceNet (standard and safety) Data Highway Plus Remote I/O SynchLink ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic 250
ASCII DF1 full/half-duplex Serial port communication DF1 radio modem DH-485 Modbus via logic Controller connections 250 Per network module: 100 ControlNet (CN2/A) 40 ControlNet (CNB) 256 EtherNet/IP; 128 TCP (EN2x) 128 EtherNet/IP; 64 TCP (ENBT) Full support Stepper Servo via DeviceNet Analog ac drive SERCOS interface Analog options: Encoder input LDT input SSI input Relay ladder Structured text Function block SFC
ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic 250
ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic 100
ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic 100
Network connections
Per network module: 100 ControlNet (CN2/A) Per network module: 40 ControlNet (CNB) 48 ControlNet 256 EtherNet/IP; 128 64 EtherNet/IP; 32 TCP TCP (EN2x) 128 EtherNet/IP; 64 TCP (ENBT) None Stepper Servo via DeviceNet Analog ac drive SERCOS interface Analog options: Encoder input LDT input SSI input Relay ladder Structured text Function block SFC Backup via DeviceNet Stepper Servo via DeviceNet Analog ac drive
Per network module: Per network module: 48 ControlNet 32 ControlNet 128 EtherNet/IP; 64 TCP 32 EtherNet/IP; 32 TCP
NA Stepper Servo via DeviceNet Analog ac drive SERCOS interface Analog encoder input Relay ladder Structured text Function block SFC External routines (developed in C/C++)
NA Stepper Servo via DeviceNet Analog ac drive 1 full servo 1 feedback axis
Integrated motion
SERCOS interface
NA
Programming languages
Logix Platforms
Allen-Bradley Logix platforms provide a single integrated-control architecture for discrete, drives, motion, process, and safety control. The Logix platforms provide a common control engine, programming software environment, and communication support across multiple hardware platforms. All Logix controllers operate with a multitasking, multiprocessing operating system and support the same set of instructions in multiple programming languages. One RSLogix 5000 programming-software package programs all Logix controllers. And, as part of the Integrated Architecture, all Logix controllers offer the benefits of the Common Industrial Protocol (CIP) to communicate via EtherNet/IP, ControlNet, and DeviceNet networks.
Section CompactLogix System Overview CompactLogix Controllers Network Communication Motion Requirements 1769 I/O Modules Power Supplies Mounting View Products Software
Page 4 7 17 29 33 41 45 51 53
CompactLogix Systems
What's New in Version 16.03:
1768-L45 controller
CompactLogix is designed to provide a Logix solution for medium applications. Typically, these applications are machine-level control applications with I/O requirements, network connectivity, and motion control requirements. A simple system can consist of a standalone controller with a single bank of I/O modules and DeviceNet communication. In a more complex system, add other networks and motion control. Multiple controllers can communicate across networks and share data.
Using CompactLogix controllers on EtherNet/IP or ControlNet networks, you have the means to cost-effectively integrate a simple machine or application into a plant-wide control system. For example, you can use a CompactLogix 1769-L35E controller to connect a suite of scalable products, such as the Allen-Bradley PanelView Plus operator interface, POINT I/O, and the PowerFlex 70 drive, for a full-scale integrated solution. Both ends of the architecture provide a direct link from real-time production information to manufacturing quality or execution systems (and back again), providing a more accurate view of plant operations and more control options than ever before to achieve this integration.
The 1769 CompactLogix system provides a Logix solution for low-end to medium applications. Typically, these applications are machine-level control applications that require limited I/O quantities and limited communication capabilities. The 1769-L31 controller offers two serial ports. The 1769-L32C and 1769-L35CR controllers offer an integrated ControlNet port. The 1769-L32E and 1769-L35E controllers offer an integrated EtherNet/IP port.
The 1768 CompactLogix system combines a 1768 backplane for communication and motion support and a 1769 backplane for I/O support. The 1768 controller is designed for integrated motion applications and more complex communication requirements than the other CompactLogix controllers. The 1768 controller has one serial port. Add 1768 modules for motion control, EtherNet/IP communication, and ControlNet communication.
CompactLogix Selection Guide Follow these steps as you specify your CompactLogix system. See Select controllers. Controller specifications Determine memory requirements 1769-L3x controller placement 1768-L4x controller placement Compatibility Logix system connections page 7 page 8 page 9 page 10 page 12 page 14 page 17 page 19 page 22 page 24 page 26 page 28 page 27 page 27 page 28 page 32 page 39 page 40
Specify a System
Step 1
Select the appropriate controller based on: required controller tasks. number of I/O points needed. number of communication cards needed. required controller memory.
Network overview EtherNet/IP specifications 2 Select communication modules. ControlNet specifications DeviceNet specifications Add the number of communication modules to the system spreadsheet. Serial specifications DH-485 specifications 3 Select motion control and drives requirements. Motion overview Integrated motion Add the motion module to the system spreadsheet. Networked motion 4 Select I/O devices. Use a system spreadsheet to record: number of points needed. number of points available per module. number of modules. 5 Select power supplies. Calculate power requirements on the system spreadsheet. 6 Mount the system. Determine whether to panel mount or DIN-rail mount the CompactLogix system. 7 Select view products. I/O module specifications Wiring systems Place I/O modules
1769 power supply specifications 1768 power supply specifications 1769 CompactLogix dimensions 1768 CompactLogix dimensions RSView software PanelView Plus terminals PanelView CE industrial computers VersaView industrial computers Available software products Programming software Communication software Network configuration software Emulation software
page 41 page 43 page 45 page 48 page 51 page 52 page 52 page 52 page 53 page 55 page 56 page 58 page 60
Determine the visualization products that fit your operator interface needs. 8 Select software.
Determine the software products you need to configure and program your application.
Step 1 - Select:
A controller with sufficient memory A 1784-CF64 CompactFlash card Replacement batteries for 1769-L3x controllers (no battery needed for 1768-L4x controllers)
CompactLogix Controllers
The CompactLogix platform brings together the benefits of the Logix platform common programming environment, common networks, common control engine in a small footprint with high performance. Combined with Compact I/O, the CompactLogix platform is perfect for tackling smaller, machine-level control applications, with or without simple motion, with unprecedented power and scalability. CompactLogix is ideal for systems that require standalone and system-connected control over EtherNet/IP, ControlNet, or DeviceNet networks.
Controller application
Controller tasks
User memory
Programming languages
Communication options
1769-L3x CompactLogix Controllers General purpose Single RPI for all modules 1769-L35x: 8 tasks 1769-L32x: 6 tasks 1769-L31: 4 tasks Only 1 continuous Event tasks: consumed tag and EVENT instruction triggers 1769-L31: 512 KB 1769-L32x: 750 KB 1769-L35x: 1.5 MB Relay ladder Function block diagram Structured text Sequential function block 1769-L31: 2 RS-232 ports (one DF1 only, other DF1 or ASCII) 1769-L32C, 1769-L35CR: 1 ControlNet port and 1 RS-232 serial port (DF1 or ASCII) 1769-L32E, 1769-L35E: 1 EtherNet/IP port and 1 RS-232 serial port (DF1 or ASCII) EtherNet/IP ControlNet DeviceNet ASCII DF1 full/half duplex DF1 radio modem DH-485 Modbus via logic
1768-L4 x CompactLogix Controllers Integrated motion Select individual RPI for each module 16 tasks (only 1 continuous) Event tasks: consumed tag, EVENT instruction, axis, and motion event triggers
1768-L43:2 MB 1768-L45:3 MB Relay ladder Function block diagram Structured text Sequential function block
EtherNet/IP ControlNet DeviceNet ASCII DF1 full/half duplex DF1 radio modem DH-485 Modbus via logic
CompactLogix Controllers
Characteristic
Available User Memory (Kbytes) CompactFlash Card Communication Ports
1769-L31
512 KB
1769-L32C
750 KB
1769-L32E
750 KB
1769-L35CR
1.5 MB
1769-L35E
1.5 MB
1768-L43
2 MB
1768-L45
3 MB
1784-CF64 64 MB 1784-CF64 64 MB 1784-CF64 64 MB 1784-CF64 64 MB 1784-CF64 64 MB 1784-CF64 64 MB 1784-CF64 64 MB 1784-CF128 128 MB 1784-CF128 128 MB 1784-CF128 128 MB 1784-CF128 128 MB 1784-CF128 128 MB 1784-CF128 128 MB 1784-CF128 128 MB 1 ControlNet port and 2 RS-232 ports (one DF1 only, other DF1 or 1 RS-232 serial port ASCII) (DF1 or ASCII) 1 EtherNet/IP port and 1 ControlNet port and 1 RS-232 serial port 1 RS-232 serial port (DF1 or ASCII) (DF1 or ASCII) 1 EtherNet/IP port and 1 RS-232 serial port 1 RS-232 port (DF1 or ASCII) 0A 1768 output 2.8 A @ 5.2V 1769 output 2.0 A @ 5.2V 1 RS-232 port 0A 1768 output 2.8 A @ 5.2V 1769 output 2.0 A @ 5.2V 1.3 A 1769 output 1.0 A @ 24V 6.3 W Four 1768 modules 30 1769 modules NA
330 mA
680 mA
660 mA
680 mA
660 mA
Backplane Current (mA) at 24V Power Dissipation Module Capacity Power Supply Distance Rating
40 mA 2.61 W
40 mA 4.36 W
1.3 A 1769 output 1.0 A @ 24V 6.3 W Two 1768 modules 16 1769 modules NA
_____ bytes _____ bytes _____ bytes _____ bytes _____ bytes _____ * 1000 = (per alarm) _____ bytes _____ * = 10000 (per subscriber)
When estimating memory use by communication modules, count all the communication modules in the system, not just those in the local chassis. This includes device connection modules, adapter modules, and ports on PanelView terminals.
CompactFlash Card
The CompactFlash card offers nonvolatile memory (flash) to permanently store a user program and tag data on a controller. 1784-CF64 has 64 MB of memory. 1784-CF128 has 128 MB of memory.
Controller Battery
The 1769 controller comes with one 1769-BA lithium battery. The 1768 controller does not require a battery. The controller uses internal flash memory to store its program during shutdown. Energy stored in the 1768 power supply maintains controller power long enough to store the program to internal flash memory (not the external CompactFlash card).
The controller and I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. The CompactLogix controller has a power supply distance rating of 4 modules. The controller must be the leftmost module in the first bank of the system. The maximum configuration for the first bank of a CompactLogix controller is the controller and 3 I/O modules to the left of the power supply and 8 I/O modules to the right of the power supply.
10
Specialty
You can always select an RPI that is slower than listed above. These considerations show how fast modules can be scanned - not how fast an application can use the data. The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput.
Follow these guidelines as you place modules in the 1768 backplane. The 1768 power supply must be the leftmost module in the 1768 backplane. The controller must be the rightmost module in the 1768 backplane.
11
Follow these guidelines as you place 1769 modules to the right of the 1768 backplane. As many as eight 1769 modules can be attached to the right of the 1768 system. The 1769 I/O connected directly to the 1768 backplane does not need a 1769 power supply. Never put a 1769 power supply in the 1768 system. Putting a 1769 power supply in the 1768 system causes the controller to generate a major fault that cannot be cleared until you remove the 1769 power supply. Additional 1769 modules must be in additional I/O banks. Each additional I/O bank must have its own 1769 power supply.
Configure an individual RPI for each local 1769 I/O module. Use the default RPI numbers that the software automatically assigns or select faster RPIs as fast as 1 millisecond. I/O update times do not affect overall 1768 bus performance, such as motion performance or controller performance. Use faster RPIs for time critical I/O without impacting overall 1769 I/O performance. Use Immediate Output (IOT) instructions for further reduction in I/O update times.
12
Compatibility
I/O Modules 1732 ArmorBlock 1734 POINT 1734D POINTBlock 1746 SLC 1756 ControlLogix 1769 Compact I/O 1771 PLC-5 1790 CompactBlock LDX 1791D CompactBlock 1792D ArmorBlock MaXum 1794 FLEX I/O 1797 FLEX Ex 1798 FLEX Armor 1799 Embedded
1769-SDN DeviceNet Yes Yes Yes No Yes Yes No Yes Yes Yes Yes No Yes Yes
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. To control I/O, use a 1769-SDN scanner to connect the controller to the DeviceNet network. Insert a 1797-BIC and 1797-CEC module pair to isolate the FLEX Ex I/O modules from the non-intrinsically safe portion of the system.
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. For DeviceNet access, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). Use PLC/SLC mapping.
13
A non-EtherNet/IP controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. In the CompactLogix system, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). The Ethernet PLC-5 processor must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later. The 1785-CNET ControlNet communication interface module must be series A, firmware revision D or later. The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller. Use a 1747-L55x controller with firmware revision OS501 or later. The PLC-2 controller requires a 1771-KG module for serial (DF1) communication. The PLC-3 controller requires a 1775-KA module for serial (DF1) communication.
DH-485 Yes NA NA NA NA NA NA NA
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. For DeviceNet access, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module. Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN(R)15 ControlNet adapter module.
14
A Logix system uses a connection to establish a communication link between two devices. Connections can be: controller to local I/O modules or local communication modules. controller to remote I/O or remote communication modules. controller to remote I/O (rack-optimized) modules. produced and consumed tags. messages. You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system.
Method
Description A scheduled connection is unique to ControlNet communication. A scheduled connection lets you send and receive data repeatedly at a predetermined interval, which is the requested packet interval (RPI). For example, a connection to an I/O module is a scheduled connection because you repeatedly receive data from the module at a specified interval. Other scheduled connections include connections to: communication devices. produced/consumed tags. On a ControlNet network, you must use RSNetWorx for ControlNet software to enable all scheduled connections and establish a network update time (NUT). An unscheduled connection is a message transfer between controllers that is triggered by the requested packet interval (RPI) or the program (such as a MSG instruction). Unscheduled messaging lets you send and receive data when needed. All EtherNet/IP connections are unscheduled. An unconnected message is a message that does not require connection resources. An unconnected message is sent as a single request/response.
Unscheduled connection Deterministic Used by both ControlNet and EtherNet/IP networks Unconnected message Least deterministic
15
The total connection requirements for a 1769 CompactLogix system include both local and remote (distributed) connections. The controller supports 100 connections. The available remote connections depend on the network interface.
The total connection requirements for a 1768 CompactLogix system include both local and remote (distributed) connections. The controller supports 250 connections. The available remote connections depend on the network interface.
16
CompactLogix Selection Guide The total connection requirements for a CompactLogix system include both local and remote (distributed) connections. The 1769-L3x controller supports 100 connections; the 1768-L4x controller supports 250 connections. The available remote connections depends on the network interface. Connections per Total Device Quantity Device Connections 0 or 1 1 0 or 1 1 0 1 1 1 1 1
Connection Type Remote Ethernnet/IP communication module configured as a direct (none) connection configured as a rack-optimized connection Remote I/O module over EtherNet/IP network (direct connection) Remote ControlNet communication module configured as a direct (none) connection configured as a rack-optimized connection Remote I/O module over ControlNet network (direct connection) Remote device over DeviceNet network (accounted for in rack-optimized connection for local 1769-SDN module) Produced tag Each consumer Consumed tag Message RSLinx Enterprise subscriber (16 maximum) Total
17
Step 2 - Select:
Network Communications
NetLinx Open Network Architecture is the Rockwell Automation strategy of using open networking technology for seamless, top-floor to shop-floor integration. The NetLinxbased networks DeviceNet, ControlNet, and EtherNet/IP all use the Common Industrial Protocol (CIP), so they speak a common language and share a universal set of communication services. NetLinx architecture, part of the Integrated Architecture, seamlessly integrates all the components in an automation system from a few devices on one network to multiple devices on multiple networks including access to the Internet helping you to improve flexibility, reduce installation costs, and increase productivity. The EtherNet/IP network is an open industrial-networking standard that supports implicit and explicit messaging and uses commercial, off-the-shelf Ethernet equipment and physical media. The ControlNet network allows intelligent, high-speed control devices to share the information required for supervisory control, work-cell coordination, operator interface, remote device configuration, programming, and troubleshooting. The DeviceNet network offers low-cost, high-speed access to plant-floor data from a broad range of plant-floor devices and a significant reduction in wiring.
18
Available Networks
You can configure your system for information exchange between a range of devices and computing platforms and operating systems. Select a CompactLogix controller with integrated communication or the appropriate communication device for the networks that meet your needs. Use this network 1769-L3 x controller 1768-L4x controller
Plant management Configuration, data collection, and control on a single, high-speed network Time-critical applications with no established EtherNet/IP network schedule Data sent regularly Internet/Intranet connection Deterministic and repeatable data delivery Redundant media Intrinsic safety Internet/Intranet connection
ControlNet network
Connections of low-level devices directly to plant floor controllers, without interfacing them through I/O modules Data sent as needed DeviceNet network More diagnostics for improved data collection and fault detection Less wiring and reduced start-up time than a traditional, hard-wired system Modems Supervisory control and data acquisition (SCADA) Manipulate ASCII data Connections to existing DH-485 networks
Serial network
Built-in serial port on the controller 1769-ASCII module Built-in serial port with a 1761-NET-AIC
DH-485 network
19
EtherNet/IP Network
The Ethernet Industrial (EtherNet/IP) network protocol is an open industrial-networking standard that supports both real-time I/O messaging and message exchange. It emerged due to the high demand for using the Ethernet network for control applications. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media. The EtherNet/IP network provides excellent drive and I/O control performance along with HMI information processing and many commercial technologies.
If your application Controls I/O modules Requires an adapter for distributed I/O on EtherNet/IP links Communicates with other EtherNet/IP devices (messages) Bridges EtherNet/IP links to route messages to devices on other networks Requires remote access via an internet browser to tags in a local chassis Supports custom Web pages Bridges EtherNet/IP links to route messages to devices on other networks
NA
1768-EWEB
Power Dissipation p
4.38 W
4.74 W
660 mA
90 mA
4 modules
Certifications: c-UL-us (Class I, Division 2, Group A, B, C, D), CE, C-Tick See the Product Certifications link at http://ab.com for Declarations of Conformity, Certifications, and other certifications details. The 1768-L4x controllers support a maximum of two 1768 communication modules per controller.
20
21
22
ControlNet Network
The ControlNet network is an open, state-of-the-art control network that meets the demands of real-time, high-throughput applications. The ControlNet network uses the proven Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads and messaging.
Power Dissipation
5.14 W
32 connections
4.36 W
680 mA
40 mA
4 modules
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE, C-Tick See the Product Certifications link at http://ab.com for Declarations of Conformity, Certifications, and other certifications details.
23
24
DeviceNet Network
The DeviceNet network is an open, low-level network that provides connections between simple industrial devices (such as sensors and actuators) and higher-level devices (such as PLC controllers and computers). The DeviceNet network uses the proven Common Industrial Protocol (CIP) to provide the control, configure, and data collection capabilities for industrial devices.
If your application Communicates with other DeviceNet devices (I/O and messages) Requires explicit messaging Uses the controller as a master or slave Uses the controller serial port for other communication Requires higher performance than the 1769-NET-DNI interface Accesses as many as 30 remote Compact I/O modules Sends remote I/O data back to a scanner or controller
Select
Cat. No.
1769-SDN 1769-ADN/B 1769-ADN/A
Communication Rate
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE, C-Tick See the Product Certifications link at http://ab.com for Declarations of Conformity, Certifications, and other certifications details. The 1761-NET-DNI is a DeviceNet to serial linking device. The actual network performance depends on the maximum serial port connection speed. The series A 1769-ADN adapter does not support the 1769-OA16, 1769-OW16, 1769-IF4XOF2, or 1769-HSC modules.
25
L32C
CONTROLNET
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
26
Serial Network
Use this DF1 mode Point to point DF1 radio modem DF1 master DF1 slave User mode (ASCII)
The serial port is compatible with RS-232 serial communication. The serial port supports the DF1 protocol to communicate with other devices on the serial link. For Communication between a controller and other DF1-compatible devices using DF1 full-duplex protocol. SCADA applications where controllers exchange data via radio transmission. Control of polling and message transmission between the master and each slave using DF1 halfduplex polled protocol. Using the controller as a slave station in a master/slave serial network using DF1 half-duplex protocol. Communication between a controller and an ASCII device, such as a bar code reader. The controller you choose determines the number of serial ports that are available.
With this protocol DF1, DH-485, ASCII Channel 0: DF1, DH-485, ASCII Channel 1: DF1, DH-485
If you connect the controller to a non-isolated port (channel 1) on the controller to a programming workstation, modem, or ASCII device, install an isolator between the controller and the end device. One possible isolator is the 1761-NET-AIC interface converter.
27
Modbus Support
To use Logix5000 controllers on Modbus, you connect through the serial port and execute a specific ladder logic routine. The controller project is available with RSLogix 5000 Enterprise programming software. For more information, see Using Logix5000 Controllers as Masters or Slaves on Modbus Application Solution, publication CIG-AP129.
28
DH-485 Network
On the DH-485 network, the controller can send and receive messages to and from other controllers on the network. The DH-485 connection does support remote programming and monitoring via RSLogix 5000 software. However, excessive traffic over a DH-485 connection can adversely affect overall performance and can lead to timeouts and loss in RSLogix 5000 configuration performance. Important: Use Logix5000 controllers on DH-485 networks only when you want to add controllers to an existing DH-485 network. For new applications with Logix5000 controllers, networks in the NetLinx open architecture are the recommended networks. You need a 1761-NET-AIC converter for each controller you want to put on the DH-485 network. To connect to this port Port 1 DB-9 RS-232, DTE connection Port 2 mini-DIN 8 RS-232 connection Use this cable 1747-CP3 or 1761-CBL-AC00 1761-CBL-AP00 or 1761-CBL-PM02
29
Step 3 - Select:
Select a 1768-L4x controller if you have motion control requirements Size the motion application (use the Motion Analyzer) How you want to interface the controller and drives A SERCOS interface module Associated cables Select drives, motors, and accessories (use the Motion Analyzer)
Integrated Motion
The 1768-L4x controller supports integrated motion. You can communicate directly to a servo drive using a motion interface or over a network. With this controller 1768-L43 You can have Four axis Two feedback axis Six virtual axis Eight axis Four feedback axis Six virtual axis
1768-L45
The SERCOS interface modules can connect to these servo drives. 2099 Kinetix 7000 high-power servo drive 2098 Ultra3000 SERCOS servo drive 1394C SERCOS drive 8720MC spindle
Number of Modules per Cat. No. Controller Power Dissipation
1768-M04SE Two for 1768-L43 Four for 1768-L45 5.04 W
r Backplane Current (mA) Backplane Current (mA) at 24V SERCOS Data Rate at 5V
969 mA 0 mA 4 Mbits or 8 Mbits per second
30
Select one of these fiber optic cables to connect the SERCOS interface module to the drive. Cat. No. Description Plastic Fiber-optic Cables 1000 m plastic simplex fiber-optic cable Transmission range of 1...32 m (3.28...104.99 ft). Allen-Bradley offers plastic, fiber-optic cable assemblies that come in a variety of jackets: No jacket (chlorinated polyethylene) for use inside an electrical cabinet A standard jacket (polyvinyl chloride) for use outside of electrical cabinets A nylon jacket for use in harsh environments Glass Fiber-optic Cables 200 m glass fiber optic cable Transmission range of 1...200 m (3.28...656.17 ft). Allen-Bradley offers glass, fiber-optic cable assemblies that come with a standard jacket (polyvinyl chloride) for use in normal environments.
2090-SCVGx-x
The x-x determines the length in meters. Specify 0-1 for 0.1 m, 0-3 for 0.3 m, 1-0 for 1 m, 3-0 for 3 m, 5-0 for 5 m, 8-0 for 8 m, 10-0 for 10 m, 15-0 for 15 m, 20-0 for 20 m, 25-5 for 25 m, or 32-0 for 32 m. The x-x determines the length in meters. Specify 1-0 for 1 m, 5-0 for 5 m, 8-0 for 8 m, 10-0 for 10 m, 15-0 for 15 m, 20-0 for 20 m, 25-0 for 25 m, 32-0 for 32 m, 50-0 for 50 m, 100-0 for 100 m, 150-0 for 150 m, or 200-0 for 200 m.
Networked Motion
Drives 1394 GMC drive and control 2098 Ultra3000 DeviceNet servo drive 2098 Ultra5000 intelligent positioning EtherNet/IP No No No
Some servo drives are supported through communication interface modules. The controller can communicate with these servo drives over these networks. DeviceNet No Yes Yes RS-232 Serial Yes No Yes DH-485 Yes No No
Each drive has different options you order for its supported communication networks. See the appropriate catalog or selection information for a drive to make sure you select the appropriate option when specifying a drive for a specific network.
31
A 3-axis system with Kinetix drives supports: execution of 4 axes per 1 ms. velocity bandwidth > 400 Hz and current loop bandwidth > 1000 Hz. high resolution, unlimited travel, and absolute feedback features. two feedback ports per Kinetix drive.
32
Example Configuration - 4-axis Integrated Motion with Kinetix Drives and LIM Interface
A 4-axis system with Kinetix drives supports: execution of 4 axes per 1 ms. velocity bandwidth > 400 Hz and current loop bandwidth > 1000 Hz. high resolution, unlimited travel, and absolute feedback features. two feedback ports per Kinetix drive. optional 2094 Line Interface Module (LIM) as the incoming power source for an entire control panel.
33
Step 1 - Select:
I/O modules 1492 wiring system (if you want to use a wiring system instead of the terminal block that comes with module) PanelConnect modules and cables if connecting input modules to sensors 1769-CRLx expansion cables for multiple banks of I/O modules
The 1769 Compact I/O modules can be used as local and distributed I/O for a CompactLogix controller. Each I/O module includes a built-in removable terminal block with finger-safe cover for connections to I/O sensors and actuators. The terminal block is behind a door at the front of the module. I/O wiring can be routed from beneath the module to the I/O terminals. When planning I/O requirements, consider: which Compact I/O modules to use. where to place Compact I/O modules. how Compact I/O modules operate.
Input module
Output module
34
Cat. No.
1769-IA8I
Number of Inputs
8 individually isolated
1769-IA16 16 1769-IM12 12
Cat. No.
1769-OA8
Number of Outputs
8
1769-OA16 16
100240V AC
85...265 ac @ 47...63Hz
8 modules
Recommended Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For 120V ac operation, use a 15 k, 2W resistor. For 240V ac operation use a 15 k, 5W resistor.
Cat. No.
1769-IG16
Number of Inputs
16
1769-IQ6XOW4 6
1769-IQ16
16
2 mA
1.5 mA
115 mA
8 modules
1769-IQ16F
16 high-speed
2 mA
1.5 mA
110 mA
8 modules
1769-IQ32
32
2 mA
1.5 mA
170 mA
8 modules
1769-IQ32T
32 terminated
3 mA
1.7 mA
170 mA
8 modules
TTL inputs are inverted (0.20.8V dc = logic low voltage = ON-state; 2.05.5V dc = logic high voltage = OFF-state).
35
1769-OB16
16
20.4...26.4V dc
1.0 mA @ 26.4V dc
200 mA
8 modules
1769-OB16P 16 protected
20.4...26.4V dc
1.0 mA @ 26.4V dc
160 mA
8 modules
1769-OB32
32
20.4...26.4V dc
1.0 mA @ 26.4V dc
300 mA
6 modules
1769-OB32T 32 terminated
10.2...26.4V dc
0.1 mA @ 26.4V dc
220 mA
8 modules
1769-OG16 16
4.5...5.5V dc
8 modules
1769-OV16
16
20.4...26.4V dc
1.0 mA @ 26.4V dc
200 mA
8 modules
1769-OV32T 32 terminated
10.2...26.4V dc
1.0 mA @ 26.4V dc
220 mA
8 modules
36
Cat. No.
Number of Outputs
Power Backplane Backplane Supply Current (mA) Current (mA) Distance at 5V at 24V Rating
105 mA 50 mA 8 modules
1769-IQ6XOW4 4
1769-OW8
24V dc
0 mA
125 mA
100 mA
8 modules
1769-OW8I
8 individually isolated 16
24V dc
0 mA
125 mA
100 mA
8 modules
1769-OW16
24V dc
0 mA
205 mA
180 mA
8 modules
Break
0.75 A 1.5 A
Voltamperes Make
1800 VA 28 VA 28 VA
Break
180 VA
IEC 947
AC15 DC13
Choose from a wide variety of analog, thermocouple, and RTS modules. Features include: Individually configurable channels On-board scaling Autocalibration of inputs Selectable input filters Over-range and under-range detection and indication Input modules offer both single-ended or differential inputs High accuracy rating
37
Cat. No.
Number of Inputs
Number of Outputs
Resolution, Bits
Signal Range
020 mA 420 mA 010V dc 10V dc 05V dc 15V dc 10.5V dc -0.510.5V dc -0.5...5.25V dc 0.55.25V dc 020 mA 420 mA 010V dc 10V dc 05V dc 15V dc 420 mA 020V mA -1010V dc 05V dc 0...10V dc 15V dc 020 mA 420 mA 10.5V dc -0.510.5V dc -0.5...5.25V dc 0.55.25V dc 010V dc 10V dc 05V dc 15V dc
Sensors Supported
1769-IF4
14 bits (unipolar)
105 mA
60 mA
8 modules
1769-IF4I
4 individually isolated
16 bits (unipolar)
145 mA
95 mA
8 modules
1769-IF8
16 bits (unipolar)
120 mA
70 mA
8 modules
1769-OF2 1769-OF4CI
120 mA 145 mA
120 mA 140 mA
8 modules 8 modules
1769-OF4VI
16 bits (unipolar)
145 mA
75 mA
8 modules
1769-OF8C
16 bits (unipolar)
145 mA
160 mA
8 modules
1769-OF8V
8 voltage
16 bits (unipolar)
145 mA
125 mA
8 modules
1769-IF4XOF2 4
2 individually isolated
120 mA
160 mA
8 modules
1769-IR6
100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 120 Nickel, alpha=618 10 Copper 604 Nickel-Iron 518 0150 0500 01000 03000
100 mA
45 mA
8 modules
1769-IT6
40 mA
8 modules
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA. Sign is always positive.
38
Cat. No.
1769-ASCII
Channel Configuration
RS-232, RS-422, or RS-485
Number of Inputs
8 real 8 virtual
Number of Outputs
4
Voltage Category/Type, Backplane Current (mA) Power Supply Distance Rating Input at 5V
24V dc, sinking input, sourcing output 220 mA 8 modules
Number of Inputs
Number of Outputs
4
1769-HSC 2
Number of Inputs
Number of Outputs
39
Description
Compact I/O to DPI/SCANport Module connects to PowerFlex 7-class drives, other DPIbased host devices, and SCANport-based host devices such as 1305 and 1336 PLUS II drives.
Communication Rate
DPI: 1925 Kbps or 250 Kbps SCANport: 125 Kbps
Compact I/O to DSI/Modbus Module connects to PowerFlex 4-class drives and to 1769-SM2 other Modbus RTU slave devices, such as PowerFlex 7-class drives with 20-COMM-H RS485 HVAC adapters.
350 mA
0 mA
4 modules
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of: interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.
A PanelConnect module and its sensor connection system connect sensors directly to I/O modules using convenient pre-built cables and connectors. The PanelConnect module mounts on the enclosure and creates the correct seal for the entry of the sensor connections. You do not need to seal the opening where the sensor cables enter the enclosure, create custom connectors, or wire to those custom connectors.
40
You can DIN-rail or panel mount the controller and I/O modules. The number of local I/O modules supported depends on the controller.
Considerations Each module uses a set amount of backplane memory, in addition to the data that the module stores or transfers. The additional banks are powered by standard 1769 power supplies and connect to the main rack by using standard 1769 expansion cables. As many as eight 1769 local modules can be attached to the 1768 backplane. The remaining modules can be in one or two additional I/O banks. The additional banks are powered by standard 1769 power supplies and connect to the main rack by using standard 1769 expansion cables.
16 local modules
3 separate banks
16 local modules
3 separate banks
1768-L45
30 local modules
3 separate banks
Each 1769 I/O module has a distance rating. In 1769 systems, the distance rating is the number of modules between the specific module and the 1769 power supply. In a 1768 system, the distance rating is the number of modules between the specific I/O module and the 1768 controller.
Expansion Cables
If you divide 1769 modules into multiple banks, make sure: each bank needs its own power supply. use expansion cables to connect the banks. the last I/O bank requires an end cap. How you orient I/O banks determines which expansion cables you need to connect the I/O banks. If you add a Second bank Third bank And connect the chassis Right to left Right to right Right to left Right to right Left to left Use this cable 1769-CRLx 1769-CRRx 1769-CRLx 1769CRRx 1769-CLLx
End Caps
The final I/O bank in the CompactLogix system needs an end cap on the end without the expansion cable. For a Right end cap Left end cap Order 1769-ECR 1769-ECL
41
For each 1768-Lx controller, one 1768 power supply For each 1769-Lx controller, one 1769 power supply Additional 1769 power supplies as needed
Power Supplies
Select power supplies based on the controller and the number of additional I/O banks. For a 1768-L4x controller 1769-L3x controller Select one 1768 power supply for the controller and 1768 modules one 1769 power supply for each additional bank of I/O modules one 1769 power supply for the controller and local I/O one 1769 power supply for each additional bank of I/O modules
Each 1769-L3x controller and additional bank of I/O modules requires a 1769 power supply. Place 1769 I/O modules to the left or the right of the 1769 power supply. As many as eight I/O modules can be placed on each side of the power supply. Each 1769 module also has a power supply distance rating (the number of modules from the power supply). Each module must be located within its distance rating. See the specifications for the module to determine its distance rating.
24V dc User Power w Capacity (0...55C)
250 mA
Cat. No.
Description
Current Capacity
2.0 A @ 5V 0.8 A @ 24V 2.0 A @ 5V 0.8 A @ 24V 4.0 A @ 5V 2.0 A @ 24V 4.0 A @ 5V 2.0 A @ 24V
Compact 124/240V 1769-PA2 ac Expansion Power Supply Compact 24V dc 1769-PB2 Expansion Power Supply Compact 124/240V 1769-PA4 ac Expansion Power Supply Compact 24V dc 1769-PB4 Expansion Power Supply
50 VA @ 24V dc
100 VA @ 24V dc
5 ms10 s
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE See the Product Certifications link at http://ab.com for Declarations of Conformity, Certifications, and other certifications details. 2000 mA @ 5V (055 C) 2000 mA @ 5V (5560 C) 800 mA @ 24V (055 C) 800 mA @ 24V (5560 C) 4000 mA @ 5V (055 C) 4000 mA @ 5V (5560 C) 2000 mA @ 24V (055 C) 1700 mA @ 24V (5560 C) 4000 mA @ 5V (055 C) 1700 mA @ 5V (5560 C) 2000 mA @ 24V (055 C) 2000 mA @ 24V (5560 C)
42
43
The 1768 backplane requires one 1768 power supply. The power supply is a dual input supply that operates in multiple ranges. The power supply also offers a 24V dc external power source. The CompactLogix power supply requires that a 1768 CompactLogix controller be installed to power the system. The power supply sends 24V dc to the controller located in slot 0. The controller converts the 24V dc to 5V dc and 24V dc and distributes it as needed. 5V and 24V power to 1769 I/O modules on the right side of the controller 24V power to 1768 modules on the left side of the controller
The 1768 modules do not have a distance rating to the 1768 power supply. For the 1769 I/O modules in the 1768 system, the distance rating is from the controller and not the 1768 power supply.
Power Consumption, Max.
118 W 112 W
Cat. No.
1768-PA3
Description
Backplane Current
Overvoltage Protection
for both +5V dc and for +24V dc
CompactLogix 5V/24V ac 85265V ac Input Non-Redundant 108132V dc Power Supply for 1768-PB3 CompactLogix Systems 16.8...31.2V dc
3.5A @ 24V dc 250 mA 24V dc to 1768 side 5V and 24V dc to 1769 side
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE, C-Tick See the Product Certifications link at http://ab.com for Declarations of Conformity, Certifications, and other certifications details.
44
45
Panel mount or DIN rail mount Appropriate number of panels or DIN rails based on the number of modules and the physical location One end cap per controller system
Mounting
You can panel mount or DIN-rail mount a CompactLogix system. The CompactLogix system must be mounted so that the modules are horizontal to each other. If you decide to use a DIN rail, use steel, 35 x 7.55mm DIN rails (A-B part number 199DR1; 46277-3; EN 50022). The DIN rails for all CompactLogix system components must be mounted on a common, conductive surface to be sure of proper electromagnetic interference (EMI) performance. Ground a CompactLogix system through the: non-coated, steel DIN rail. panel-mount screw hole containing the ground strap.
46
47
48
1768
Slot 1
Slot 2
Slot 2
Slot 1
Slot 0
1769
49
50
51
View Products
Visualization products, together with Logix for control and NetLinx architecture for communication, make up the RA Integrated Architecture strategy. The visualization strategy combines RA expertise in Allen-Bradley electronic operator interface and industrialized personal computer hardware with Rockwell Software supervisory control software. Current visualization products include: RSView Enterprise Series software. PanelView Plus operator interface. PanelView Plus CE operator interface. VersaView industrial computers and monitors.
RSView Enterprise Series software from Rockwell Software is a line of HMI software products designed with a common look, feel, and navigation to help speed HMI application development and training time. With RSView Enterprise Series 3.0, you can reference existing Logix data tags. Any changes made to these referenced tags are automatically inherited by RSView software. RSView Studio software lets you create applications in a single design environment. It configures RSView Supervisory Edition, RSView Machine Edition, VersaView CE, and PanelView Plus applications. It supports editing and reusing projects for improved portability between embedded machine and supervisory HMI systems. RSView Machine Edition (ME) software is a machine-level HMI product that supports both open and dedicated operator interface solutions. It provides a consistent operator interface across multiple platforms (including Microsoft Windows CE, Windows 2000/XP, and PanelView Plus solutions), and is ideal for monitoring and controlling individual machines or small processes. RSView Supervisory Edition (SE) software is an HMI software for supervisory-level monitoring and control applications. It has a distributed and scalable architecture that supports distributed-server/multi-user applications. This highly scalable architecture can be applied to a standalone, one-server/one-user application or to multiple users interfacing with multiple servers.
Description
RSView Studio for RSView Enterprise Series RSView Studio for Machine Edition RSView ME Station runtime for Windows 2000, 15 displays RSView ME Station runtime for Windows 2000, 30 displays RSView ME Station runtime for Windows 2000, 75 displays RSView SE client RSView SE view client RSView SE server 25 displays RSView SE server 100 displays RSView SE server 250 displays RSView SE server unlimited display RSView SE station 25 displays RSView SE station 100 displays RSView SE station 250 displays RSView SE station unlimited display
52
The PanelView Plus terminal is ideal for applications that need to monitor, control, and display information graphically, allowing operators to quickly understand the status of their application. PanelView Plus terminals come with RSView Studio software and have embedded RSView Machine Edition software functionality. PanelView Plus terminals combine the best features from the popular Allen-Bradley PanelView Standard and PanelView e operator-interface products and adds new functionality. Multi-vendor communication Trending Expressions Data logging Animation RSView Studio software direct browsing of RSLogix 5000 addresses
PanelView Plus CE products offer open Windows CE terminals in Windows desktop environments, bringing together features of operator interfaces and industrial computers. It is a high performance computer with a CompactFlash drive and integrated RSView Machine Edition runtime (no activation required). Theres no hard disk, no fan, and no moving parts, which means maximum reliability on the plant floor. Easy to set up and maintain, PanelView Plus CE products provide an open system thats rugged and economical, offering high functionality in an easy to use package.
VersaView products are a family of industrial computer and monitor solutions, comprised of integrated display computers, workstations, non-display computers, and flat panel monitors. VersaView products offer effortless management of changing technology, a rugged but cost-effective design, and easier product configuration. All VersaView products provide the latest industrial solution available, optimized for visualization, control, information processing, and maintenance application.
53
Step 8 - Select:
The appropriate package of RSLogix 5000 Enterprise Series software and any options Other software packages for your application An appropriate operator interface
If you have CompactLogix controller SERCOS motion interface (1768 controller only)
Software
Your selection of modules and network configuration determines what software packages you need to configure and program your system. You need Order 9324 series (RSLogix 5000 Enterprise Series software) Use Lite Edition or higher to support motion. If no motion, you can use the Service Edition or Mini Edition. 9324 series (RSLogix 5000 Enterprise Series software) or 9324-RLD300NXENE (RSLogix 5000 Enterprise Series software plus RSNetWorx option)
RSLinx software or BOOTP/DHCP server utility to set IP addresses (RSLinx Lite and BOOTP server come with RSLogix 5000 Enterprise Series software)
optional RSNetWorx for EtherNet/IP optional 9357-ENETL3 (RSNetWorx for software EtherNet/IP) (comes with the standard/RSNetWorx option of RSLogix 5000 Enterprise Series software) 9324-RLD300NXENE (RSLogix 5000 Enterprise RSNetWorx for ControlNet software Series software plus RSNetWorx option) (comes with the standard/RSNetWorx option or of RSLogix 5000 Enterprise Series software) 9357-CNETL3 (RSNetWorx for ControlNet) 9324-RLD300NXENE (RSLogix 5000 RSNetWorx for DeviceNet software Enterprise Series software plus RSNetWorx (comes with the standard/RSNetWorx option option) of RSLogix 5000 Enterprise Series software) or 9357-DNETL3 (RSNetWorx for DeviceNet) RSLinx software 9324 series (RSLinx Lite comes with RSLogix 5000 (RSLogix 5000 Enterprise Series software) Enterprise Series software) RSLogix Emulate 5000 software 9310-WED200ENE
ControlNet interface
DeviceNet interface
54
Programming Software
RSLogix 5000 Enterprise Series software is designed to work with Logix5000 controller platforms. RSLogix 5000 Enterprise Series software is an IEC 61131-3 compliant software package that offers relay ladder, structured text, function block diagram, and sequential function chart editors for you to develop application programs. Create your own instructions by encapsulating a section of logic in any programming language into an add-on instruction. RSLogix 5000 Enterprise Series software also includes axis configuration and programming support for motion control. With RSLogix 5000 Enterprise Series software, you need only one software package for sequential, process, drive, motion control, and safety programming.
Value
Pentium II 450 MHz min Pentium III 733 MHz (or better) recommended Supported operating systems: Microsoft Windows XP Professional version 2002 (with Service Pack 1 or 2) or XP Home version 2002 Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3 Microsoft Windows Server 2003 128 MB of RAM min 256 MB of RAM recommended 100 MB of free hard disk space (or more based on application requirements) 256-color VGA graphics adapter 800 x 600 min resolution (True Color 1024 x 768 recommended)
Software requirements
55
Available Features
Logix5000 controllers supported Relay ladder diagram editor Function block diagram editor 9324-RLDFBDENE Sequential function chart editor 9324-RLDSFCE Structured text editor 9324-RLDSTXE PhaseManager 9324-RLDPME GuardLogix Safety 9324-RLDGLXE Highly integrated motion Graphical trending DriveExecutive Lite 9303-4DTE01ENE PIDE autotune 9323-ATUNEENE RSMACC audit support FuzzyDesigner 9324-RLDFZYENE RSLogix Emulate 5000 9310-WED200ENE Logix CPU security Routine source protection RSMACC (security server) client Standalone security server RSLinx Classic software RSNetWorx for ControlNet software RSNetWorx for DeviceNet software RSNetWorx for EtherNet/IP software RSLogix Architect 9326-LGXARCHENE FBD ActiveX faceplates Tag data upload/download RSLogix 5000 project compare Tag custom data monitor RSView demo (50 tags/2 hours)
Available separately Available separately Available separately Available separately Available separately Included Included NA Included Included Included Included Included
Available separately Available separately Available separately Available separately Available separately Available separately NA Included Included Included Included Lite included Available separately Available separately Available separately Included Included Included Included Included Lite included Included Included Included Included Lite included Included Included Included Included Lite included Included Included Included Included OEM included
Available separately NA Included Included Included Included Lite included Included Included Included Included Lite included
Available separately Available separately Available separately Available separately Available separately Available separately Included Included Included Included Included To Standard: 9324RLD0U3xxE To Full: 9324RLD0U6xxE To Professional: 9324-RLD0U7xxE Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included Included
Available separately Available separately Available separately Available separately Available separately Available separately Included To Standard: 9324RLD2U3xxE To Professional: 9324-RLD2U7xxE To Full: 9324RLD25U6xxE To Professional: 9324-RLD25U7xxE Node Locked to Concurrent License: 9324-RLD6U6FxxU To Professional: 9324-RLD6U7xxE
Upgrades
NA
NA
Replace xx in the catalog number with the appropriate language designation: ZH=Chinese, EN=English, FR=French, DE=German, IT=Italian, JP=Japanese, KO=Korean, PT=Portuguese, and ES=Spanish. Service Edition supports controllers running firmware revision 12 and later. Full Edition supports controllers running firmware revision 10 and later. A multiple language editor package is available as 9324-RLDMLPE. It contains the function block, sequential function chart, and structured text editors. RSNetWorx for ControlNet software is 9357-CNETL3. RSNetWorx for DeviceNet software is 9357-DNETL3. RSNetWorx for EtherNet/IP software is 9357-ENETL3. They are available together as 9357-ANETL3. The multiple language editor package (9324-RLDMLPE) is not the same as an upgrade, but it extends the programming languages to match those in a Full package. As of RSLogix 5000 programming software, version 15. As of RSLogix 5000 programming software, version 16.
56
CompactLogix Selection Guide RSLinx software is a complete communication server providing plant-floor device connectivity for a wide variety of software applications such as RSLogix 5, RSLogix 500, and RSLogix 5000, RSView32, RSView Enterprise Series, and RSSql/RSBizWare software. In addition, several open interfaces are provided for third-party HMI, data collection and analysis packages, and custom client-application software. RSLinx software can support multiple software applications simultaneously, communicating to a variety of devices on many different networks. RSLinx software, version 2.x, is now joined by RSLinx Enterprise software, a new product within the RSLinx family that provides unparalleled connectivity to Logix processors. RSLinx Enterprise software currently can support working as a data server for widely distributed RSView Supervisory Edition products, RSSql, RSBizWare Historian, and RSBizWare PlantMetrics applications, RSView Machine Edition software iincluding PanelView Plus and VersaView hardware platforms, and RSView Supervisory Edition Station software. You can communicate from anywhere to anywhere using RSLinx software.
RSLinx Software
Value
Pentium100 MHz processor (faster processors will improve performance) Supported operating systems: Microsoft Windows XP Microsoft Windows 2000 Microsoft Windows NT version 4.0 with Service Pack 3 or greater Microsoft Windows ME Microsoft Windows 98 32 MB of RAM min 64 MB or more of RAM recommended 35 Mbytes of free hard disk space (or more based on application requirements) 16-color VGA graphics display 800 x 600 or greater resolution
Operating system
In most cases, RSLinx Lite software comes bundled with controller programming software packages. You can also download RSLinx Lite for free from the Software Updates link on the Get Support Now website at http://support.rockwellautomation.com
57
58
RSNetWorx software is the configuration tool for your control network. With RSNetWorx software you can create a graphical representation of your network configuration and configure the parameters that define your network. Use RSNetWorx software for: ControlNet software to schedule network components. The software automatically calculates network bandwidth for the entire network, as well as the bandwidth used by each network component. You must have RSNetWorx software to configure and schedule ControlNet networks. DeviceNet software to configure DeviceNet I/O devices and create a scan list. The DeviceNet scanner stores the configuration information and scan list. EtherNet/IP software to configure EtherNet/IP devices using IP addresses or host names.
59
Personal computer Intel Pentium or Pentium-compatible computer Supported operating systems: Microsoft Windows XP Microsoft Windows 2000 Microsoft Windows 2000 Terminal Server Microsoft Windows NT version 4.0 with Service Pack 6 or later Microsoft Windows ME Microsoft Windows 98 32 MB of RAM min More memory is required for large networks Minimum: 108 MB (includes program and hardware files) Minimum: 115 MB (includes program and hardware files) Minimum: 190 MB (includes program and hardware files) Full support: 115...125 MB (includes program, online Full support: 168...193 MB (includes program, online Full support: 230...565 MB (includes program, online help, tutorial, and hardware files) help, tutorial, and hardware files) help, tutorial, and hardware files)
Operating system
RAM
16-color VGA graphics adapter Video requirements 640 x 480 resolution minimum 800 x 600 resolution recommended Other RSLinx Lite software, version 2.41 or later, to use RSNetWorx software online RSLinx Lite software, version 2.4 or later, to use RSNetWorx software online RSLinx Lite software, version 2.4 or later, to use RSNetWorx software online
In some cases, RSNetWorx software comes bundled with controller programming software packages.
60
CompactLogix Selection Guide RSLogix Emulate 5000 software (9310-WED200ENE) is the emulation package for the Logix5000 controllers. RSLogix Emulate 5000 software, used in conjunction with RSLogix 5000 software, lets you run and debug your application code while at your computer. In addition, RSLogix Emulate 5000 software lets you test HMI screens, developed in RSView software for example, without the need to connect to a real controller. You can set tracepoint and breakpoint instructions (ladder diagram only) in your application code, use traces, and also vary the execution speed of the emulator. RSLogix Emulate 5000 software supports all the programming languages (ladder diagram, function block diagram, structured text, and sequential function chart). RSLogix Emulate 5000 software does not allow for control of real I/O. Use RSLogix Emulate software for: troubleshooting. Stop the process whenever a selected rung goes true, effectively freezing the process at the instant that any error occurs. ladder logic scanning options. Scan your ladder logic continuously, one program scan at a time, rung-by-rung, or select a specific block of rungs to emulate. Selecting a block of rungs lets you isolate a particular section of the program for testing purposes. You can also set trace points to trace application program tags and set break points to halt program execution at predetermined locations.
Value
IBM-compatible Intel Pentium II 300 MHz or Celeron 300A (Pentium III 600 MHz recommended) Supported operating systems: Microsoft Windows XP with Service Pack 1or greater Microsoft Windows 2000 with Service Pack 2 or greater Microsoft Windows NT version 4.0 with Service Pack 6A or greater 128 MB of RAM min 50 MB of free hard disk space 16-color VGA graphics display 800 x 600 or greater resolution
Operating system
RSLogix Emulate 5000 software includes RSTestStand Lite software. RSTestStand Lite software lets you create virtual operator consoles that can help test your application code. RSTestStand Lite software can be upgraded to the standard version by ordering catalog number 9310-TSTNDENE. RSLogix Emulate 5000 and RSTestStand Lite software are included with RSLogix 5000 Professional software. 1769-SG001G-EN-P -- July 2007
Notes
Notes
Notes
CompactLogix, ControlLogix, FlexLogix, DriveLogix, PowerFlex, SoftLogix, MicroLogix, PLC-5, PLC-3, PLC-2, SLC, DH+, Allen-Bradley, FLEX Ex, PanelView, RSLinx, RSLogix, RSLogix, RSNetWorx, RSView, Rockwell Software, SERCOS, Ultraware, and VersaView are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1769-SG001G-EN-P July 2007 Supersedes 1768-SG001B-EN-P November 2006 and 1769-SG001F-EN-P November 2006
Copyright 2007 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.