Vous êtes sur la page 1sur 68

1930-1990 MHz

Installation and Service Manual

OS-1900-SA(X)/SB(X) Outdoor Multi-Carrier Power Amplifier (MCPA) System G3S-1900-125 MCPA

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

2004 Powerwave Technologies Incorporated. All rights reserved. Powerwave Technologies, and the Powerwave logo are registered trademarks Powerwave Technologies, Inc. reserves the right to make changes to the documentation and equipment, including but not limited to component substitution and circuitry changes. Changes that impact this manual may subsequently be incorporated in a later revision of this manual. This Powerwave product is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges in this document may cause (1) spurious emissions that violate regulating body rules; (2) the equipment to be automatically removed from service when maximum thresholds are exceeded; or (3) the equipment to not perform in accordance with its specifications. It is the Operator's responsibility to ensure this equipment is properly installed and operated within Powerwave operating specifications to obtain proper performance from the equipment and to comply with regulating body rules.

June 2004

Powerwave Technologies, Inc. 1801 East St. Andrew Place Santa Ana, CA 92705

Tel: (714) 466-1000 (888) 797-9283


Fax: (714) 466-5800

Web Site: www.powerwave.com

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Warnings, Cautions, and Notes


Warnings, cautions, and notes are found throughout this manual where applicable. The associated icons are used to quickly identify a potential condition that could result in the consequences described below if precautions are not taken. Notes clarify and provide additional information to assist the user.

Warning This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical and RF circuitry and be familiar with standard practices for preventing accidents.

Caution

This caution symbol means reader be careful. In this situation, the user might do something that could result in equipment damage or loss of data.

Note

This note symbol means reader take note. Notes contain helpful suggestions or references to material not covered in the document. Procedures are not contained in notes.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

J une 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Revision Record
Revision Letter A B Date of Change December 2003 June 2004 Reason for Change Original version of product. Updated manual to add diversity antenna configuration and other miscellaneous changes.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

ii

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Table Of Contents
Paragraph Number 1-1 1-2 1-2.1 1-2.2 1-2.3 1-2.4 1-2.5 1-2.6 1-2.7 1-2.8 1-2.9

Section 1 Principles of Operation

Page Number

Introduction ......................................................................................................................... 1-1 General Description............................................................................................................ 1-1 SA(X) Models..................................................................................................................... 1-1 SB(X) Models..................................................................................................................... 1-2 Amplifiers ........................................................................................................................... 1-2 Universal Control Module .................................................................................................. 1-2 Rectifiers ............................................................................................................................ 1-2 Alarms................................................................................................................................ 1-2 Functional and Physical Specifications ............................................................................. 1-2 Equipment Changes .......................................................................................................... 1-2 System Components and Documents ...............................................................................1-3

Section 2 Installation
2-1 Introduction ......................................................................................................................... 2-1 2-2 Site Survey ......................................................................................................................... 2-1 2-3 Electrical Service Recommendations.................................................................................2-1 2-4 Heat Disipation ................................................................................................................... 2-2 2-5 Unpacking and Inspection ..................................................................................................2-3 2-6 Installation Instructions ....................................................................................................... 2-4 2-6.1 Chassis Mounting Examples ............................................................................................. 2-5 2-6.2 Wind Loading ..................................................................................................................... 2-6 2-6.3 RF Cable Connections....................................................................................................... 2-6 2-6.4 Alarm Cable Connections .................................................................................................. 2-8 2-6.5 Bias-T Connections .........................................................................................................2-10 2-6.6 AC Power Connections....................................................................................................2-10 2-6.7 125-Amp Rectifier Installation (930-00016-008)..............................................................2-11 2-6.8 148-Amp Rectifier Installation (930-00018-005)..............................................................2-12 2-6.9 Amplifier Installation.........................................................................................................2-13 2-6.10 Air Flow Panels..............................................................................................................2-13 2-6.11 DC Power Connections for OS-1900-SA(X) Three-Sector System ..............................2-13

Section 3 Operating Instructions


3-1 3-2 3-3 3-3.1 3-3.2 3-3.3 3-3.4 3-4 3-5 3-5.1 Introduction ......................................................................................................................... 3-1 Location and Function of Amplifier Module Controls and Indicators..................................3-1 Universal Control Module (UCM) Controls and Indicators .................................................3-3 UCM LED Indicators .......................................................................................................... 3-3 Pilot Tone Selections ......................................................................................................... 3-3 DIP Switch Functions......................................................................................................... 3-4 TX Gain Adjust................................................................................................................... 3-4 148-Amp Rectifier LED Indicators ......................................................................................3-5 Initial Start-Up and Operating Procedures ........................................................................ 3-5 Bypass Operation Check: ................................................................................................. 3-7

Section 4 Principles of Operation


4-1 4-2 4-3 4-4 4-5 4-5.1 4-5.2 Introduction ......................................................................................................................... 4-1 RF Input Signal ................................................................................................................... 4-1 RF Output Load .................................................................................................................. 4-1 System Functional Description ........................................................................................... 4-1 G3S-1900-125 Amplifier Module ........................................................................................ 4-3 Main Amplifier .................................................................................................................... 4-4 Error Amplifier .................................................................................................................... 4-4
Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

iii

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


4-5.3 Amplifier Monitoring ........................................................................................................... 4-4 4-5.4 Amplifier Module Cooling................................................................................................... 4-4 4-5.5 Power Distribution.............................................................................................................. 4-4 4-5.6 Intermodulation .................................................................................................................. 4-4 4-5.7 Two-Tone Intermodulation................................................................................................. 4-4 4-5.8 Multitone Intermodulation .................................................................................................. 4-5 4-5.9 Amplifier Monitoring ........................................................................................................... 4-5 4-5.10 Pilot Tone Control ............................................................................................................ 4-6 4-5.11 Alarm Interface ................................................................................................................ 4-7 4-5.12 Plug-In Rectifiers ............................................................................................................. 4-7

Section 5 Maintenance
5-1 Introduction ......................................................................................................................... 5-1 5-2 Periodic Maintenance ......................................................................................................... 5-1 5-3 Test Equipment Required for Test .....................................................................................5-1 5-4 Cleaning Air Inlets/Outlets/Filters .......................................................................................5-2 5-5 Performance Test ............................................................................................................... 5-2 5-6 Field Replaceable Parts and Modules................................................................................5-2 5-6.1 Power Amplifier Module..................................................................................................... 5-2 5-6.2 Amplifier Cooling Fans....................................................................................................... 5-3 5-6.3 Universal Control Module (UCM)....................................................................................... 5-3 5-6.4 125-Amp Rectifier (930-00016-008) .................................................................................. 5-3 5-6.4.1 Hot Swap in a Two-Rectifier System .............................................................................. 5-3 5-6.4.2 Replacement in a One-Rectifier System ........................................................................ 5-4 5-6.5 148-Amp Rectifier (930-00018-005) .................................................................................. 5-4 5-6.5.1 Hot Swap in a Two-Rectifier System .............................................................................. 5-4 5-6.5.2 Replacement in a One-Rectifier System ........................................................................ 5-5 5-6.6 Duplexer/Universal Input Attenuator (UIA) Tray................................................................ 5-5 5-6.7 Universal Input Attenuator (UIA) Cooling Fan Assembly .................................................. 5-5

Section 6 Troubleshooting
6-1 6-2 6-2.1 6-2.2 6-2.3 6-2.4 6-2.5 6-2.6 6-2.7 6-2.8 6-2.9 6-3 6-3.1 6-3.2 Introduction ......................................................................................................................... 6-1 Troubleshooting .................................................................................................................. 6-1 DC Voltage Indicators Not Illuminated ............................................................................... 6-1 OVER PWR Illuminated...................................................................................................... 6-2 HIGH TEMP Illuminated ..................................................................................................... 6-2 VSWR Illuminated............................................................................................................... 6-2 DC FAIL Illuminated ........................................................................................................... 6-3 FAN FAIL Illuminated ......................................................................................................... 6-3 LOOP FAIL Illuminated....................................................................................................... 6-3 LOW PWR Illuminated........................................................................................................ 6-3 LPA DISABLE Illuminated .................................................................................................. 6-3 Return for Service Procedures ........................................................................................... 6-4 Obtaining an RMA .............................................................................................................. 6-4 Repackaging for Shipment ................................................................................................. 6-4

List of Appendices
Appendix A Specifications ............................................................................................................A-1 A-1 OS-1900-SA(X)/SB(X) System Specifications ....................................................................A-1 A-2 Amplifier Model G3S-1900-125 Specifications ...................................................................A-2 A-3 125-Amp Rectifier Specifications ........................................................................................A-3 A-4 148-Amp Rectifier Specifications ........................................................................................A-4 Appendix B Power Setting Procedures.........................................................................................B-1 B-1 Power Setting Calculations .................................................................................................B-1 B-2 Power Setting Procedure ....................................................................................................B-2
Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

iv

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


Table Number 1-1 2-1 2-2 2-3 2-4 2-5 2-6 2-7 3-1 3-2 3-3 3-4 4-1 4-2 5-1 6-1 A-1 A-2 A-3 A-4 B-1 Page Number

List of Tables

OS-1900-SA(X)/SB(X) Major Components......................................................................... 1-3 Site Preparation................................................................................................................... 2-1 Averaged DC Current Load................................................................................................. 2-2 Averaged Heat Loading ......................................................................................................2-2 Materials Required for Installation but Not Supplied........................................................... 2-4 Tools Needed for Installation ..............................................................................................2-4 Form-C Alarm Terminal Block Relay Connections ............................................................. 2-8 Form-C Alarm Truth Table .................................................................................................. 2-9 Amplifier Module DC Indicators RF Switch Definitions ....................................................... 3-1 Amplifier Module RF Control and Indicators Definitions ..................................................... 3-2 UCM LED Descriptions .......................................................................................................3-3 Pilot Tone Switch Configuration Table ................................................................................ 3-3 G3S-1900-125 Interface Connector Pinouts ...................................................................... 4-5 Pilot Frequency Setting Based on PCS Frequency Block of Operation ............................. 4-6 Periodic Maintenance.......................................................................................................... 5-1 Amplifier Module DC and Logic Connector Definitions....................................................... 6-2 OS-1900-SA(X)/SB(X) System Specifications ....................................................................A-1 Amplifier Model G3S-1900-125 Functional Specifications..................................................A-2 125-Amp Rectifier Model 930-00016-008 Specifications....................................................A-3 148-Amp Rectifier Model 930-00018-005 Specifications....................................................A-4 OS-1900-SA(X)/SB(X) Gain Example.................................................................................B-1 Page Number

Figure Number 1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 1-12 1-13 1-14 1-15 1-16 1-17 1-18 1-19 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9

List of Figures

OS-1900-SA(X)/SB(X) Front Isometric View ...................................................................... 1-3 OS-1900-SA(X)/SB(X) Rear Isometric View ....................................................................... 1-4 OS-1900-SA(X)/SB(X) Front-View with Dimensions .......................................................... 1-4 OS-1900-SA(X)/SB(X) Rear-View with Dimensions ........................................................... 1-5 OS-1900-SA(X)/SB(X) Side-View with Mounting Dimensions............................................ 1-5 OS-1900-SA(X)/SB(X) Side-View with Panels and Dimensions......................................... 1-6 OS-1900-SA(X)/SB(X) Single (SA1) and Double-Sector(SA2) Front Panel Removed ...... 1-6 OS-1900-SA(X)/SB(X) Three-Sector (SA3) Front Panel Removed.................................... 1-7 OS-1900-SB1 Front Panel Removed.................................................................................. 1-7 OS-1900-SB2 Front Panel Removed.................................................................................. 1-8 OS-1900-SB3 Front Panel Removed.................................................................................. 1-8 G3S-1900-125 Multi-Carrier Power Amplifier Isometric View............................................. 1-9 G3S-1900-125 Multi-Carrier Power Amplifier Front, Side, and Rear Views ....................... 1-9 UCM Junction Board .........................................................................................................1-10 UCM Front Panel...............................................................................................................1-10 125-Amp Rectifier Front Panel..........................................................................................1-10 125-Amp Rectifier Subrack ...............................................................................................1-11 148-Amp Rectifier Isometric Views ...................................................................................1-12 148-Amp Rectifier Tray and Panel Views .........................................................................1-12 Mounting Bracket ................................................................................................................ 2-5 Outdoor Enclosure Mounting Examples .............................................................................2-5 OS-1900-SA(X) Rear Interface Panel.................................................................................2-7 OS-1900-SB(X) Rear Interface Panel.................................................................................2-7 Form-C Alarm Contacts Wiring Example ............................................................................ 2-8 Bias-T Terminal Block and Wiring Diagram ......................................................................2-10 AC Power Cable Connections (125-Amp Rectifier, 930-00016-008) ...............................2-10 AC Power Cable Connections (148-Amp Rectifier, 930-00018-005) ...............................2-11 148-Amp Rectifier (930-00018-005) Latching Example....................................................2-12
Copyright Powerwave Technologies, Inc., June 2004. All rights reserved

044-05140 Rev. B

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


2-10 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 3-9 4-1 4-2 4-3 4-4 6-1 OS-1900-SA3 Inter-Enclosure DC Wiring Interconnect Example.....................................2-14 Amplifier Module Controls and Indicators ........................................................................... 3-1 UCM Controls and Indicators .............................................................................................. 3-4 148-Amp Rectifier LED Indicators.......................................................................................3-5 Amplifier Front Panel........................................................................................................... 3-6 125-Amp Rectifier Power On/Off Switch Location .............................................................. 3-6 Bypass Path Mode .............................................................................................................. 3-7 Universal Control Module.................................................................................................... 3-8 OS-1900-SA(X) Interface Panel..........................................................................................3-9 OS-1900-SB(X) Interface Panel..........................................................................................3-9 OS-1900-SA(X) Single-Sector Configuration Example....................................................... 4-2 OS-1900-SB(X) Single-Sector Configuration Example....................................................... 4-2 G3S-1900-125 Power Amplifier Module Functional Block Diagram ................................... 4-3 G3S-1900-125 Interface Connector.................................................................................... 4-6 DC and Logic Connector (Male, on Rear of G3S-1900-125 Amplifier Module).................. 6-1

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

vi

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 1 General Description


1-1 Introduction
This manual contains information and procedures for the installation, operation, and maintenance of the Powerwave OS-1900-SA(X) and OS-1900-SB(X) Outdoor Multi-Carrier Power Amplifier (MCPA) System. The manual is organized into sections as follows: Section 1. Section 2. Section 3. Section 4. General Description Installation Operating Instructions Principles of Operation
Section 5. Section 6. Appendix A. Appendix B. Maintenance Troubleshooting Specifications Amplifier Power Setting Procedure

1-2 General Description


The OS-1900-SA(X)/SB(X) Multi-Carrier Power Amplifier (MCPA) system is an AC powered, linear, feedforward power amplifier system that operates in the 60 MHz frequency band from 1930 MHz to 1990 MHz with an instantaneous bandwidth of 25 MHz. It consists of: One or more outdoor enclosure assemblies. SA(X) Three Models: SA1 one enclosure, one sector SA2 one enclosure, two sectors SA3 two enclosures, three sectors SB(X) Three Models: SB1 one enclosure, one sector SB2 two enclosures, one sector each SB3 three enclosures, one sector each One or more model G3S-1900-125 amplifiers. One or more model 930-00016-008, 125-Amp or 930-00018-005, 148-Amp rectifiers.

Designed for outdoor use, the NEMA 3R rated enclosure has a sturdy aluminum case with removable front and rear lock-down ventilating panels as shown in figures 1-1 through 1-6. The enclosures has six mounting brackets (three on each side) used to secure it to its predetermined location. Access to the RF, power, and alarm cabling is located at the lower rear of the enclosure. The enclosure protects the Powerwave equipment from outdoor elements as well as housing the alarm summary board and the electrical interface for the 125-Amp rectifier (or 148-Amp rectifier) and G3S-1900-125 MCPA(s). The OS-1900-SA(X)/SB(X) system is shown in figures 1-7 and 1-8.

1-2.1 SA(X) Models


For a single-sector SA1 model, the enclosure houses one G3S-1900-125 MCPA module. Two modules are required for a two-sector solution (SA2 with two MCPAs). A three-sector solution consists of one two-sector (SA2) enclosure and an additional enclosure containing one MCPA module with DC power supplied from the two-sector enclosure that includes an additional rectifier. Each enclosure can contain the following: Up to two MCPA modules. Up to two 125-Amp or 148-Amp rectifiers (not mixed). Four input duplexers. Two universal input assemblies with DC fans.
Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


Two universal controllers. Two integrated output duplexer/RX filter assemblies. Four bypass transfer switches. Four Bias-T units.

1-2.2 SB(X) Models


The SB(X) models are the same as the SA1 models except a third antenna configuration is incorporated that includes an additional duplexer, 2:1 splitter for Rx1 and Rx3, bypass transfer
switch, and Bias-T. The interface panel also includes additional connections for the third antenna. Each enclosure is identical therefore, a one-sector system consists of one single-sector enclosure, two sectors consist of two single-sector enclosures, and three sectors consist of three single-sector enclosures.

1-2.3 Amplifiers
The all solid-state G3S-1900-125 plug-in amplifier module, shown in figures 1-9 and 1-10, is designed to produce high-peak output power. The modular construction and Light Emitting Diode (LED) based operational status and fault indicators help minimize downtime. The turn-on and turn-off sequence of voltages are fully automatic, as is overload protection and recycling. Inadvertent operator damage from front panel manipulation is virtually impossible. A nominal 52 Amps DC of current is required for the G3S-1900-125 amplifier.

1-2.4 Universal Control Module


A universal control module (UCM), one for each sector, is connected to one UCM junction board, shown in figures 1-11 and 1-12. Each UCM provides system status LED indicators, configuration switches, RS232 PC port, and gain adjustment potentiometer.

1-2.5 Rectifiers
The 125-Amp and 148-Amp rectifiers and associated subracks shown in figures 1-13 through 116, require a primary input power between 176 to 264 VAC. The rectifier converts the AC input power to the +27 VDC for use by the system. The 125-Amp rectifier is rated up to 24 Amps AC at full load at 176 VAC and the 148-Amp rectifier is rated up to 25.5 Amps AC at full load at 180 VAC. The system is expected to draw a typical 17 Amps AC during normal operation with two amplifiers. For circuit breaker protection, refer to section 2 and appendix A - Specifications.

1-2.6 Alarms
The OS-1900-SA(X)/SB(X) MCPA system also provides four Form-C dry contact alarms per sector to report system status when the optional alarm board is installed. See section 2.

1-2.7 Functional and Physical Specifications


Functional and physical specifications for the OS-1900-SA(X)/SB(X) system components are listed in appendix A. Section 4 of this manual contains a functional block diagram that illustrates the systems operational layout for one sector.

1-2.8 Equipment Changes


Powerwave Technologies, Inc. reserves the right to make changes to the subject equipment, including but not necessarily limited to component substitution and circuits. Changes that impact this manual may subsequently be incorporated in later revisions.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 1-2.9 System Components and Documents
Table 1-1 lists the model numbers and descriptions of major components that comprise the OS1900-SA(X)/SB(X) system and the document number of the manual related to each component. Table 1-1 OS-1900-SA(X)/SB(X) Major Components
Model 930-00016-008 * (128981-7) 930-00018-005 ** G3S-1900-125 800-00972-002 800-01075-003 800-07640-001 Manual Description 125-Amp Rectifier 148-Amp Rectifier 044-05122 125-Watt Amplifier Field-Replaceable Amplifier Cooling Fans Rear Fan Assembly Front Fan Assembly Universal Input Attenuator (UIA) Fan Assembly Quantity per system 1 or 2 1 or 2 1, 2, or 3 2/amplifier 2/amplifier 1 or 2

* Manufactured by Transistor Devices, Inc. ** Manufactured by Cherokee International (Rectifiers are not interchangeable)

Ventilating Panel, Front and Rear

Mounting Brackets, Three Each Side

Figure 1-1 OS-1900-SA(X)/SB(X) Front Isometric View

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

SA(X) Interface Panel

Figure 1-2 OS-1900-SA(X)/SB(X) Rear Isometric View

Figure 1-3 OS-1900-SA(X)/SB(X) Front-View with Dimensions

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

SA(X)

SB(X)

Figure 1-4 OS-1900-SA(X)/SB(X) Rear-View with Dimensions

Figure 1-5 OS-1900-SA(X)/SB(X) Side-View with Mounting Dimensions

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-5

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Figure 1-6 OS-1900-SA(X)/SB(X) Side View with Panels and Dimensions

SA1 Rectifier

SA2

Air Flow Panel Air Flow Panels UCM

MCPA

UIA Cooling Fan

(UCM Junction Board not Shown)

Figure 1-7 OS-1900-SA(X)/SB(X) Single (SA1) and Double-Sector (SA2) Front Panel Removed

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-6

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Rectifiers UCM
(UCM Junction Board not Shown)

MCPA

Air Flow Panels

UIA Cooling Fan

Figure 1-8 OS-1900-SA(X)/SB(X) Three-Sector (SA3) Front Panel Removed

Rectifier

UCM
(UCM Junction Board not Shown)

Air Flow Panels

MCPA

UIA Cooling Fan

Figure 1-9 OS-1900-SB1 Front Panel Removed

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-7

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Both sectors are identical

Figure 1-10 OS-1900-SB2 Front Panel Removed

*All three sectors are identical

Figure 1-11 OS-1900-SB3 Front Panel Removed

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-8

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Release Latch

Figure 1-12 G3S-1900-125 Multi-Carrier Power Amplifier Isometric View

Figure 1-13 G3S-1900-125 Multi-Carrier Power Amplifier- Front, Side and Rear Views

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-9

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Figure 1-14 UCM Junction Board

Voltage Adjust

Figure 1-15 UCM Front Panel Figure 1-16 125-Amp Rectifier Front Panel

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-10

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Rear

Figure 1-17 125-Amp Rectifier Subrack

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-11

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Front

Rear

Figure 1-18 148-Amp Rectifier Isometric Views

Rectifier

Front

Rear

Figure 1-19 148-Amp Rectifier Tray and Panel Views

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

1-12

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 2 Installation
2-1 Introduction
This section contains unpacking, inspection, installation instructions and recommendations for the OS-1900-SA(X) and OS-1900-SB(X) Outdoor Multi-Carrier Power Amplifier (MCPA) System. It is important to perform the following: 1. 2. 3. Carefully read all material in this section prior to equipment installation. Review any Federal Communications Commission (FCC) rules and local codes as they apply to your installation. Before operating, read the operating instructions in section 3.

2-2 Site Survey


Powerwave Technologies recommends that site surveys be performed by qualified individuals or firms prior to equipment ordering or installation. Performing a detailed site survey will reduce or eliminate installation and turn-up delays caused by oversights. Table 2-1 Site Preparation Description Measurement Width: 15.87 inches Height: 34 inches Depth: 34 inches Allow adequate clearances in the front and rear of the enclosure for cooling airflow. 120 lbs (without amplifiers) 231 lbs (45 lbs/amplifier, one 21 lb rectifier) 221.5 lbs (45 lbs/amplifier, one 13.5 lb rectifier)

Enclosure Dimensions

Enclosure Weight (shipping) Enclosure Weight (fully populated)

2-3 Electrical Service Recommendations


Powerwave Technologies recommends that proper AC line conditioning and surge suppression be provided on the primary AC input to the +27 VDC power source. All electrical service should be installed in accordance with the National Electrical Code, any applicable state or local codes, and good engineering practice. Special consideration should be given to lightning protection of all systems in view of the vulnerability of most transmitter sites to lightning. Lightning arrestors are recommended in the service entrance. Straight, short ground runs are recommended. The electrical service must be well grounded. Each amplifier system should have its own circuit breaker, so a failure in one does not shut off the whole installation. Circuit breakers should be capable of handling the anticipated inrush current, in a load center with a master switch. A 30-Amp AC circuit breaker using 10 AWG power cable for each rectifier is recommended for 220 VAC input service.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


According to the laws of probability used to formulate Erlang tables, rarely are all channels transmitting at the same time. We can use Erlang tables to predict typical maximum current usage. Table 2-2 describes the current load for a 3-sector (70%), 2-sector (80%), omni (90%), and typical (100%) site using G3S-1900-125 model amplifiers. Battery backup or UPS systems should be installed in remote sites or in sites which experience brownout conditions or generator switchovers. Adding this equipment should eliminate the need for site visits by technicians after brownouts or power outages. Battery backup systems also provide excellent DC filtering as a side benefit. Table 2-2 Averaged DC Current Load (Amperes; 125 Watt) (typical, based on % of output power @ 26 VDC) No. Of 3-Sector (70%) 2-Sector (80%) 1-Sector (90%) Amplifiers Averaged Current Averaged Current Averaged Current 142 3 94 99 102 2 47 49 51 1

Amplifier Power 125 125 125

100% Typical 155 104 52

2-4 Heat Disipation


Air conditioning of this Powerwave equipment is not required unless this equipment is installed in interior location (i.e. an equipment closet inside of a building). Each G3S-1900-125 amplifier generates 4364 BTUs typical (4364 BTUs max) of heat at full power. A fully populated OS-1900-SA2 enclosure (two-sectors) operating at full power generates 8,727 BTUs of heat typically. A single sector OS-1900-SB(X) enclosure operating at full power generates 4364 BTUs. Forced ambient air over the amplifier heat sinks dissipates the generated heat to the outside of the enclosure. To ensure the required airflow, the front and rear panel filter assemblies must be cleaned periodically (refer to section 6). Sufficient free space surrounding the enclosure is required to effectively cool the amplifiers (refer to table 2-1). In keeping with section 2-3, table 2-3 lists the heat loading for a 3-sector (70%), 2-sector (80%), omni (90%), and typical (100%) site using both G3S-1900-125 model amplifiers. Table 2-3 Averaged Heat Loading (British Thermal Units/hr; 125 Watt) (typical, based on % of output power @ 26 VDC) Amplifier Power 125 125 125 No. Of Amplifiers 3 2 1 3-Sector (70%) Averaged BTU's 12,127 8,084 4,042 2-Sector (80%) Averaged BTU's 8,403 4,202 1-Sector (90%) Averaged BTU's 8,648 4,324 100% Typical 13,091 8,727 4,364

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

2-5 Unpacking and Inspection


This equipment has been operated, tested and calibrated at the factory. Only in the event of severe shocks or other mistreatment should any substantial readjustment be required. Carefully unpack the enclosure, amplifier module, and rectifier after they have reached the installation site. Carefully open the several containers and remove the enclosure, amplifier module, and rectifier. Retain all packing material that can be reassembled in the event that the unit must be returned. Caution Exercise care in handling equipment during inspection to prevent damage caused by rough or careless handling.

Visually inspect the amplifier enclosure and associated equipment for damage that may have occurred during shipment. Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous packing material in the connectors or fans. Inspect male connectors on modules and harnesses for bent connector pins. If the equipment is damaged: The carrier is your first area of recourse. A claim should be filed with the carrier once the extent of any damage is assessed. We cannot stress too strongly the importance of IMMEDIATE careful inspection of the equipment and the subsequent IMMEDIATE filing of the necessary claims against the carrier if necessary. If possible, inspect the equipment in the presence of the delivery person. If the equipment is damaged and must be returned: Write or phone for a return authorization. Refer to section 6. Powerwave may not accept returns without a return authorization.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

2-6 Installation Instructions


The OS-1900-SA(X)/SB(X) Multi-Carrier Power Amplifier (MCPA) System is designed for installation in an interior or exterior location that permits access to the rear of the amplifier enclosure for connection of AC power, RF, and monitor cables. The installation must allow free movement of ambient air through the air intake and exhaust vents. Table 2-4 lists the materials that the installer will need and table 2-5 lists the tools. Refer to figures 2-1, 2-2, and 2-3 for mounting examples, mounting brackets, and interface panel connector locations. Table 2-4 Materials Required for Installation but not Supplied
Materials Needed AC Power Cable rated for 50A Tie wraps (6 or 8 inch) Unistrut Straps 3/8 x 1 x 16 TPI Hex Bolt 1/4 x 1 x 20 TPI Hex Bolt 3/8 Flat or Fender Washer 3/8 Lock Washer 1/4 Flat or Fender Washer 1/4 Lock Washer 0.5 inch foam semi-ridged coax (N male to N male) Weatherproofing materials 30 A AC breaker Where Used From AC breaker panel to OS-1900SA(X)/SB(X) Cable dressing OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting OS-1900-SA(X)/SB(X) Mounting RF input to OS-1900-SA(X)/SB(X) and RF Output from OS-1900-SA(X)/SB(X) to antenna jumper RF, DC/AC, and alarm connectors Rectifier Approximate Length (Each) As needed Quantity Per Enclosure 1 As needed As needed As needed 6 min / 12 max 6 min / 12 max 6 min / 12 max 6 min / 12 max 6 min / 12 max 6 min / 12 max 5-40 feet 2 As needed 1 per cabinet

Table 2-5 Tools Needed for Installation


Tools Needed Crimp tool Electricians knife Cable cutters Rotohammer 3/8 inch drill bit 5/16 open-end wrench 3/16 slotted screwdriver Wire cutters Digital power meter (up to 300 watts, 1800 to 2000 MHz) Spectrum analyzer (1800 to 2000 MHz) Dummy load (minimum 300 watts 1800 to 2000 MHz) 10, 20, 30 dB; 20- and 300-watt (min.) attenuators Digital volt-ohm meter Digital amp meter Where Used Ground cables Earth ground Ground cables unistrut or cabinet mounting unistrut or cabinet mounting Tightening and loosening SMA connectors Securing alarm cables Cut tie wraps Setting output power levels System performance checks Setting output power levels Spectrum analysis Verify power Verify power

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.1 Chassis Mounting Examples


The OS-1900-SA(X)/SB(X) enclosures can be installed in a variety of mounting configurations as shown in figure 2-2. Because of this, specific procedures are not provided herein. This general procedure assumes the enclosure is already sized and installed to accommodate the weight of the Powerwave and all other equipment contained therein. The following installation procedure assumes that you are using the rectifier supplied by Powerwave. If you choose to use your own rectifier system, do not connect the 220 VAC power to the Powerwave rectifier. Mount the enclosure onto its designated location. Verify that sufficient space to slide the modules in and out is available and that the air intake and exhaust vents are not blocked. The side located mounting bracket with bolt size requirements is shown in figure 2-1.

Figure 2-1 Mounting Bracket

Figure 2-2 Outdoor Enclosure Mounting Examples

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-5

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.2 Wind Loading


Wind resistance calculations are in accordance with the guidelines contained in Telecordia Technologies, Inc., Electronic Equipment Cabinets, Detailed Requirements Document GR-487-CORE, Issue 1, June 1996, and can be calculated using the following formula: P = 0.05 WH Where: P = force applied to cabinet, pounds W = cabinet width, inches H = cabinet height, inches The calculated wind loading on the OS 1900-SA(X)/SB(X) box with a wind speed of 100 mph and no form factor (FF) is the following: Side Load = 196 lbs. (392 lbs with FF) Frontal Load = 87 lbs. (174 lbs. with FF) When a form factor is accounted for, the worst case loading effectively doubles the above loadings. The form factor depends on mounting location, topography and drag coefficient of the equipment. According to the UBC (Uniform Building Code), the form factor must be accounted for.

2-6.3 RF Cable Connections


All cable connections are made on the bottom of the rear panel shown in figure 2-3. 1. 2. 3. 4. 5. 6. Connect the duplexed RF in (BTS - TX1/RX1) cable on the OS-1900-SA(X)/SB(X) to the duplexed output of the host equipment. Connect the diversity RF in (BTS - TX2/RX2) cable on the OS-1900-SA(X)/SB(X) to the diversity output of the host equipment. OS-1900-SB(X)) only: Connect the diversity RF in (BTS TX3/RX3) cable on the OS-1900SB(X) to the diversity output of the host equipment. Connect the duplexed ANT TX/RX1cable to the antenna. Connect the diversity ANT/RX2 cable to the antenna. OS-1900-SB(X)) only: Connect the diversity ANT/RX3 cable to the antenna.

Do not install weatherproofing materials to cables until the power setting procedure is completed.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-6

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


Sector 2 Sector 1

x 20 threaded ground studs

Figure 2-3 OS-1900-SA(X) Rear Interface Panel

One-Sector

x 20 threaded ground studs

Figure 2-4 OS-1900-SB(X) Rear Interface Panel

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-7

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.4 Alarm Cable Connections


The alarm status is reported via Form-C contacts. The four Form-C alarms are: Minor, Major, Critical and Bypass. Access to the alarm connections is made through the rear panels of the enclosures. With the rear panel removed, the Form-C alarm terminal block is mounted on an Lbracket along the right-hand side, about 10 inches from the top of the cabinet. Attach the alarm output cable from the terminal block to the appropriate host interface. Refer to figure 2-5 and table 2-6 for the alarm wiring and relay connections.

Figure 2-5 Form-C Alarm Contacts Wiring Example Table 2-6 Form-C Alarm Terminal Block Relay Connections
Relay Continuity Measurement - System Off Minor NO to Common (C) NC to Common (C) Closed Open Major NO to Common (C) NC to Common (C) Closed Open Critical NO to Common (C) NC to Common (C) Closed Open Bypass NO to Common (C) NC to Common (C) Closed Open

Relay Continuity Measurement - System On, Alarms Off Minor NO to Common (C) NC to Common (C) Open Closed Major NO to Common (C) NC to Common (C) Open Closed Critical NO to Common (C) NC to Common (C) Open Closed Bypass NO to Common (C) NC to Common (C) Open Closed

Relay Continuity Measurement - System On, Alarms On Minor NO to Common (C) NC to Common (C) Closed Open Major NO to Common (C) NC to Common (C) Closed Open Critical NO to Common (C) NC to Common (C) Closed Open Bypass NO to Common (C) NC to Common (C) Closed Open

NO = Normally Open, NC = Normally Closed, C = Common

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-8

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


The alarms are described as follows:
MINOR MAJOR Any fan fault, either from an MCPA or discrete tachometer inputs (up to three external fans). A major fault is asserted if: o Any active LNA/TMA faults. o One of two active rectifiers fault. A critical fault is asserted if: o o Any active LNA/TMA faults. Both of the active rectifiers fault. MCPA fault.

CRITICAL

o
BYPASS

Bypass fault is asserted any time the transmit portion of the system is in critical fault or bypass mode is forced via the configuration switches.

Table 2-7 Form-C Alarm Truth Table


Alarm Not Applicable Minor Critical Critical Critical Critical Not Applicable Minor Critical Critical Major Major Critical Bypass No No Yes Yes Yes Yes No No Yes Yes No No Yes MCPA Enabled Fan Fault Disabled Off FP Off CB Removed Reporting Off Fault Disabled Reporting Off Disabled Enabled Disabled Reporting Off Disabled Enabled Disabled Disabled FE Fan No Fault RECT0 Enabled RECT1 Enabled

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-9

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.5 Bias-T Connections


With the rear panel removed, the Bias-T voltage connections are made through the rear interface panel to the terminal block located on the left side of the enclosure directly below the Form-C terminal block. The terminal block with associated wiring is shown in figure 2-6.

Figure 2-6 Bias-T Terminal Block and Wiring Diagram

2-6.6 AC Power Connections


Install the AC circuit breaker in the circuit breaker panel as described by the manufacturers documentation. Ensure the circuit breaker is set to the OFF position. The AC cable from the base station is connected to the rectifier trays terminal posts as shown in figures 2-7 and 2-8. Use three 10 AWG conductors to connect to the rear of the rectifier tray (the terminal connection accepts 20 to 4 AWG wire). Attach the 10-guage line wires to the line terminals and the WHT 10-guage wire to the ground terminal. The AC cable should be protected with a 30-Amp AC minimum circuit breaker.
Line +27 VDC Load Sharing and Alarms Connector Line Ground

27V Return

Figure 2-7 AC Power Cable Connections (125-Amp Rectifier, 930-00016-008)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-10

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

+27 VDC 27V Return

+27 VDC

27V Return

Ground Line

Line

Load Sharing and Alarms Connector

Figure 2-8 AC Power Cable Connections (148-Amp Rectifier, 930-00018-005)

2-6.7 125-Amp Rectifier Installation (930-00016-008)


Warning Verify that the rectifier switch is in the off position. Turn off external primary AC power before connecting AC power cables.

1.

Insert the 125-Amp rectifier in the left rectifier slot. Secure the rectifier in place by latching the front panel lever on the lower front panel as shown in figure 2-9. This technique ensures that the locking mechanism catches against the enclosure frame. Check your work before applying AC voltage to the system. Make certain all connections are tight and correct. Turn on the AC power to the rectifier and measure the primary AC input voltage. AC input voltage should be 176 to 264 VAC, 24 Amps AC (when the rectifier is on). If the AC input voltage is above or below the limits, call and consult an electrician before you turn on your amplifier system. Turn on the rectifier and measure the primary DC output voltage for +27 VDC 1.0 VDC. If the DC output voltage is above or below the limits, use the front panel adjustment potentiometer to set the voltage (reference figure 1-13).

2. 3.

4.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-11

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.8 148-Amp Rectifier Installation (930-00018-005)
Warning Turn off external primary AC power before connecting AC power cables and installing the rectifier unit into the OS-1900 enclosure.

1.

Before installing rectifier, use flat head screw driver and turn locking screw, located in the upper right-hand corner, fully clockwise, so the latch is pointing down, as shown in figure 28, Example A. With the latch pointing down, insert the 148-Amp rectifier in the rectifier slot until it seats into its mating connectors. Using the flat head screwdriver, turn the locking screw counterclockwise until latch is in the fully locked position as shown in figure 2-8, Example B. This ensures that the locking mechanism catches against the enclosure frame. Check your work before applying AC voltage to the system. Make certain all connections are tight and correct. Turn on the AC power circuit breaker to the rectifier and measure the primary AC input voltage. AC input voltage should be 176 to 264 VAC, 24 Amps AC (when the rectifier is on). If the AC input voltage is above or below the limits, call and consult an electrician before you turn on your amplifier system. Measure the rectifier primary DC output voltage for +27 VDC 1.0 VDC. If the DC output voltage is above or below the limits, contact Powerwave for assistance.

2.

3. 4.

5.

Slot

Example A

Latch in Down Position

Example B

Line up latch in slot, then continue turning CCW with screwdriver until tight. Latch in Locked Position

Figure 2-9 148-Amp Rectifier (930-00018-005) Latching Example

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-12

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 2-6.9 Amplifier Installation


1. 2. Turn off AC power to the enclosure. Inspect the 21-pin D-Sub male combo connector on the rear of the amplifier before installing it in the enclosure. Verify that all pins are straight, no pins are recessed, and that the alignment shield is not bent. Caution Do not slam the amplifier into the enclosure. Forcing the amplifier into the enclosure at too fast a rate may cause the pins on the 21-pin D-sub connector of the amplifier to become recessed or broken.

3.

After verifying that the front panel power RF OFF/ON/RESET switch is in the OFF position, gently install the plug-in amplifier module in the enclosure. Tighten top and bottom thumbscrews. Refer to section 3 of this manual for initial turn-on and checkout procedures. Do not install weatherproofing materials to the cables until after the power setting procedure is completed.

4. 5.

2-6.10 Air flow Panels


When removing or switching enclosure system components, ensure that the air flow panels shown in figure 1-8 and 1-9 are replaced or reinstalled in the empty spaces to maintain the proper cooling air flow for optimum system performance.

2-6.11 DC Power Connections for OS-1900-SA(X) Three-Sector System


Two examples of DC interconnections for a three-sector OS-1900-SA(X) system are shown in figure 2-9. Each example uses a different rectifier with the inch diameter +27 VDC and DC RETURN studs in different locations. It is recommended that a inch conduit be installed between enclosures and #6 AWG cable be used for the DC connections between enclosures. Each connection must be secured using the appropriate terminal lug and existing hardware. Also refer to figures 2-6 and 2-7 for location of the rectifier connections. When using two rectifiers in the same enclosure, the AC cable should be protected with a 50-Amp AC minimum circuit breaker. Caution The two rectifiers must be installed in the same enclosure that contains the two amplifiers (two sectors). Failure to do this could cause thermal problems resulting in system shutdown.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-13

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

AC Power Back of Rectifier Tray

Access holes sized for Conduit

Studs All Four Examples

Example Using 930-00016-008 Rectifier

Both rectifiers located in two-amplifier enclosure AC Power

Back of Rectifier Tray

Access holes sized for Conduit

Example Using 930-00018-005 Rectifier

Figure 2-10 OS-1900-SA3 Inter-Enclosure DC Wiring Interconnect Example

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

2-14

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 3 Operating Instructions


3-1 Introduction
This section contains operating instructions for the Powerwave OS-1900-SA(X) and OS-1900SB(X) Outdoor Multi-Carrier Power Amplifier (MCPA) Systems.

3-2 Location and Function of Amplifier Module Controls and Indicators


The location and function of the G3S-1900-125 plug-in amplifier module controls and indicators is shown in Figure 3-1 and listed and described in tables 3-1 and 3-2.

Figure 3-1. Amplifier Module Controls and Indicators Table 3-1 Amplifier Module DC Indicators RF Switch Definitions
Name +27 VDC Indicator +15 VDC Indicator +5 VDC Indicator -5 VDC Indicator Function Green LED - When lit indicates that the +27 VDC supply is greater than +21 VDC and less than +31 VDC. If the +27 VDC indicator goes out, the DC Fail indicator illuminates. This indicates that the +27 VDC voltage dropped below +21 VDC. Green LED - When lit indicates that the +15 VDC supply is greater than +12 VDC and less than +17 VDC. If the +15 VDC indicator goes out, the DC Fail indicator illuminates. This indicates that the +15 VDC voltage dropped below +12 VDC or increased above +17 VDC. Green LED - When lit indicates that the +5 VDC supply is greater than +2 VDC and less than +7 VDC. If the +5 VDC indicator goes out, the DC Fail indicator illuminates. This indicates that the +5 VDC voltage dropped below +2 VDC or increased above +7 VDC. Green LED - When lit indicates that the -5 VDC supply is greater than -7 VDC and less than -2 VDC. If the -5 VDC indicator goes out, the DC Fail indicator illuminates. This indicates that the -5 VDC voltage dropped below -7 VDC or increased above -2 VDC. Continued on next page

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


Name RF ON Switch Three-position switch: Off (down position) - Turns off amplifier module. On (center position) - Normal amplifier on position. Reset (up position) - When toggled to reset position, all red LED indicators turn on one at a time in sequence followed by all the green indicators one at a time in sequence; this also resets the fault latches. If the switch is held in the reset position, a microcontroller reset occurs and is verified by the LEDs toggling state again. When released, the spring-loaded switch returns to the normal ON position. If a fault occurs and the MCPA is disabled, a reset clears the alarms and enables the MCPA. The functions of the switch are disabled for five seconds after a power-up condition. Function

Table 3-2 Amplifier Module RF Control and Indicators Definitions


Amplifier Alarm Over PWR Fault Over PWR Fault High Temperature High Temperature VSWR
Latching

LED

MCPA Module Disable Disable Enable Disable

System Alarm (From Subrack) Major Major None Major

MCPA Disable signal

Condition

Auto-Recovery

Yes No No No

Red Red Red Red

High High Low High

No

Red

Enable

None

Low

VSWR DC Fail DC Fail (Over Voltage) DC Fail (Under Voltage) Fan Fail Loop Fail Low PWR

Yes No No No No Yes N/A

Red Red Red Red Red Red Red

Disable Disable Disable Disable Enable Disable Enable

Major Major Major Major Minor Major None

High High High High Low High Low

MCPA Module Pout > 52 dBm (Note 1) Pin > -6 dBm software; -5 dBm hardware Base plate temperature > 80 C Base plate temperature > 85 C Reflected and Forward Powers both exceed 40W. Condition exists for less than 1 minute Alarm set after alarm state on for more than 1 minute Average Internal voltage out of range. +27V DC input > 30.5 V +27VCD input < 21 V

None <-12 dBm Software <75C <75C Reflected or Forward Power < 38W None (Note 2) 30.0V 21.5V

Any fan fail (<70 Hz Speed) (>100 Hz Speed) Loop fail detected longer None than 2 min Indication shown base on NA rack RS 485 command.

MCPA Module Alarm Definition: Note 1: When Over Power detected at the output: a) MCPA Module will shut down (Disable). b) Turn on red Over Power lamp. c) Latch Over Power alarm d) The MCPA Module will use a RMS detector to determine the over power fault. Note 2: The Appropriate Status lamp will turn off, indicating which voltage is out of its range. (10% range for +15V, +5V, and -5V).

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

3-3 Universal Control Module (UCM) Controls and Indicators


The location and function of the UCM plug-in module controls and indicators is shown in Figure 3-2 and is described in detail in the paragraphs that follow.

3-3.1 UCM LED Indicators


There are eight bi-color LEDs located on the UCM controller (refer to figure 3-4). The indicators display disabled/enabled alarm reporting (configuration switch positions) and specific status of the individual external components. The LED functions and descriptions are listed in table 3-3. Table 3-3 UCM LED Descriptions
Color Off Green Blink System No DC Power Normal LNA0 S3-1 Off Enabled
High Current (+12 VDC above 300 mA) Low Current (+12 VDC below 75 mA)

LNA1 S3-2 Off Enabled


High Current (+12 VDC above 300 mA) Low Current (+12 VDC below 75 mA)

RECT0 S3-3 Off Enabled

RECT1 S3-4 Off Enabled

FAN0 S2-1 Off Enabled

FAN1 S2-2 Off Enabled

FAN2 S2-3 Off Enabled

Red

Fault

Fault

Fault

Fault

Fault

Fault

Red

1 Hz

3-3.2 Pilot Tone Selection


Refer to section 4, paragraph 4-9 for a complete description of the pilot tone function. Set the pilot tone to the nearest frequency outside of the base stations operating band. Refer to table 3-4 and figure 3-2. Caution Failure to set the Pilot Tone frequency properly may affect the amplifier performance.

Table 3-4 Pilot Tone Switch Configuration Table


Pilot (MHz) 1945.5 1950.5 1964.5 (default) 1965.5 1969.5 1970.5 1974.5 Band A D B E F E C Pilot 0 OFF ON OFF ON ON OFF OFF Pilot 1 OFF ON OFF OFF OFF ON ON Pilot 2 OFF OFF ON OFF ON ON OFF Pilot 3 OFF OFF OFF OFF OFF OFF OFF

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 3-3.3 Dip Switch Functions


The dip switches for the LNA, Fans, and Rectifier cause the UCM to monitor each of these components for fault alarms when the switch is in the On position (right-most position) See figure 3-2. In addition, the LNA switch controls whether the LNA port voltage is on or off. The LNA port can source either 12 or 15 VDC (factory programmed) and 150 mA of current. Note that third-party LNAs may be installed in the system, and are not monitored or controlled by the UCM. For this system, Fan0 and Fan1 switches are set to Off. The Bypass switch allows manual bypass of the MCPA when the switch is in the right-most position. When the switch is in the left-most position (Off), the UCM controls operational mode of the MCPA bypass relays, based on the MCPAs operational status.

3-3.4 TX Gain Adjust


The UCM controls the transmit gain of the system via the voltage variable attenuator in the UIA module. The UIA provides from 45 to 65 dB of attenuation to the applied signals, therefore, providing 20 dB of dynamic range. Transmit gain is at minimum when the front panel potentiometer is fully counter-clockwise.

Eight bicolor LEDs

Default switch positions shown

Figure 3-2. UCM Controls and Indicators

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

3-4 148-Amp Rectifier LED Indicators


The 148-Amp rectifier (930-00018-005) LED front panel indicators are shown in figure 3-3. All three indicators are illuminated during normal operation signifying the rectifier is operating within the specified ranges.
Green Amber Green

Figure 3-3. 148-Amp Rectifier LED Indicators

3-5 Initial Start-Up and Operating Procedures


Note The power amplifier must be warmed up for a minimum of 20 minutes prior to setting power levels. Failure to properly warm the amplifiers may result in inaccurate output power.

The amplifier module has two operating controls consisting of a power ON/OFF circuit breaker and the RF OFF/ON/RESET switch. Both are located on the front face of the module as shown in figure 3-4. Refer to manual 044-05122, G3S-1900-125 Multicarrier PCS Amplifier for a complete description of the amplifier module. Perform the initial start-up as follows: 1. Verify that all input and output cables are properly connected. Caution Before applying power, ensure that the system input and output is properly terminated at 50 ohms. Do not operate the system without a load attached. Refer to appendix A for input power requirements. Excessive input power may damage the amplifier.

Warning Never remove or install coaxial cables on either the input or output port when the power amplifier is turned on. Operating the power amplifier while disconnecting and connecting RF cables may damage the equipment and/or cause personal injury.

2. 3.

Verify that the amplifier front panel ON-OFF circuit breaker is in the OFF position and the RF OFF/ON/RESET switch is in the OFF (down) position. If the 125-Amp rectifier, P/N 930 00016-008, shown in figure 3-5 is used, turn on the rectifier by pressing the power button to the ON position. The 148-Amp rectifier, P/N 930-00018-005, is turned on when the OS-1900-SA(X)/SB(X) AC power switched is switched to On.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-5

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


RF OFF/ON/RESET Switch

ONOFF Circuit Breaker

Figure 3-4. Amplifier Front Panel 4. 5. 6. 7. Set the UCM TX Gain Adjust to minimum gain (fully counter-clockwise). Set the Pilot Tone frequency (see table 3-4). Set the UCM dip switches to their operating positions. See figure 3-2 for default configuration. Set the amplifier front panel ON-OFF circuit breaker to the ON position. Visually check the indicators on the amplifier module and verify that the following are on: A. B. 8. 9. LPA DISAB indicator (red). +27 VDC, +15 VDC, +5 VDC and -5 VDC indicators (green).

Set the amplifier front panel RF OFF/ON/RESET switch to the ON (center) position. All red LEDs should turn off after six seconds. Refer to appendix B for the power setting instructions.

10. Turn on external exciter/transceiver and apply RF input signals.

On/Off Switch

Figure 3-5. 125-Amp Rectifier Power On/Off Switch Location

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-6

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 3-5.1 Bypass Operation Check


Action: With the system in normal operation, set each amplifier RF OFF/ON/RESET switch, shown in figure 3-4, to OFF. Indication: The universal control module (UCM) SYSTEM LED, shown in figure 3-7, goes from green to red indicating the system is in bypass mode. When the system is in bypass mode, as shown in figure 3-6, the power level from BTS TX1/RX1 to ANT TX/RX1, BTS TX2/RX2 to ANT RX2 (figure 3-8 SAX model), and BTS TX3/RX3 to ANT RX3 (figure 3-9 SBX model) drops approximately 0.5 dB.

ANT TX1/ RX1 RX1

By-Pass Assembly

Switch Control -Bypass/Combiner

LA B-T

ANT TX/RX1

+47.51dBm (56.37W) 2 Composite Signals +51.72dBm (148.6W) Composite Max TX/RX1

2:1
1 2 3 4 5 6 7

RX1 IN

TX1

BTS TX1/RX1

Univ. Input Atten. (UIA)


Atten: -45 to -65 dB

Integrated Duplexer

S p l i t t e r

MCPA Control, Alarm

-40 dB TX Coupler MCPA Power: 125W Gain: 60dB TX

+27VDC

BTS TX2/RX2

TX2

Sense TX Gain From UCM 0-15V From UCM +24V From UCM

F A N

Integrated Filter Assy

RX2 ANT RX2

RX2 Out RX2 IN Switch Control -Bypass/Combiner

By-Pass Assembly

B-T LA B-T LA

ANT RX2 ANT RX3

BTS TX3/RX3 By-Pass Assembly

RX3 Integrated Duplexer Ground

50ohms +27VDC

TX3 ANT RX3

UCM Ctrl Signals - Sector 1


Sense B

Sense A

Output
+27VDC

Load Sharing /Battery Backup

220VAC

UCM Junction Block


-Bypass/Combiner -Bypass/Combiner RX Gain Adjust #1 RX Gain Adjust #2 Fan Control 1, 2, 3 Switch Control 2 Voltage monitor Fan Sense 1, 2, 3 Switch Control 1 Switch Control 3 Spare bypass

+27V Rectifier
Alarm
VDC Input MCPA Alarms

Load Sharing Battery Management Battery Management Sensor External DC Source

VDC LNA #1

RS-232

VDC LNA #2

Form C Alarm

TX Gain Adjust 0-15V

Universal Controller Module (UCM)

+27V Rectifier
03-0220B-B

Figure 3-6. Bypass Path Mode

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-7

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

System LED goes to red

Figure 3-7. Universal Control Module

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-8

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Figure 3-8. OS-1900-SA(X) Interface Panel

Figure 3-9. OS-1900-SB(X) Interface Panel

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-9

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

(This page intentionally left blank)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

3-10

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 4 Principles of Operation


4-1 Introduction
This section contains a functional description of the Powerwave OS-1900-SA(X)/SB(X) Indoor/Outdoor Multi-Carrier Power Amplifier (MCPA) System. Refer to figures 4-1, 4-2, and 4-3 for the system and amplifier module block diagrams. A complete OS-1900-SA(X)/SB(X) system consists of a one, two, or three-sector configuration that includes up to three G3S-1900-125 MCPA, 125-Watt amplifiers and up to two 125-Amp or 148-Amp, 220 VAC AC to +27 VDC rectifiers, and one or two indoor/outdoor enclosures. RF Input is from the BTS to the BDA Tx and Rx ports. Transmit is separated from receive, then all transmit signals are combined, amplified, duplexed, then transmit and receive are combined and provided to the antenna port. The control assembly monitors the MCPA, TMA, and rectifier, and reports alarms via the Form-C interface. The interface point for the RF IN, RF OUT, AC input power and monitor (I/O) cables are located at the enclosure bottom rear. The amplifier module is provided with a separate DC input line via an internal wiring harness. The rectifier requires a 30 Amp AC breaker (minimum), even though the rectifier is expected to draw 17 Amps AC nominal during normal operation with two 125-Watt amplifiers.

4-2 RF Input Signal


One to 10 CDMA carriers compliant with ANSI-J-STD-019. The maximum input power for all carrier frequencies should not exceed the limits specified in appendix A. The input VSWR should be 2:1 maximum (or better).

4-3 RF Output Load


The load impedance should be as good as possible (1.5:1 or better) in the working band for good power transfer to the load. If the amplifier is operated into a filter, it will maintain its distortion characteristics outside the signal band even if the VSWR is infinite, provided the reflected power does not exceed one watt. A parasitic signal of less than one-watt incident on the output will not cause distortion at a higher level than the normal forward distortion (i.e. -63 dBc).

4-4 System Functional Description


The G3S-1900-125 amplifier is a linear, feedforward power amplifier that operates in the 60 MHz frequency band from 1930 MHz to 1990 MHz. It is designed to operate in two continuous frequency blocks in the PCS band or an instantaneous bandwidth of 20 MHz. A typical one-sector system is shown in figure 4-1 and 4-2. The power output specification is listed in appendix A. Each amplifier is a self-contained plug-in module and is functionally independent of the other amplifier module. The amplifier modules are designed for parallel operation to achieve high peak power output, and for redundancy in unmanned remote locations. Each amplifier in the system can simultaneously transmit multiple carrier frequencies at 90 watts per sector Each amplifier output is an amplified composite signal of approximately 125 watts before losses. All phase and gain corrections are performed on the signal(s) in the individual amplifier modules. Each amplifier module has alarm and display LEDs that display the amplifier performance. If a failure or fault occurs in an amplifier module, it is displayed on the individual amplifier front panel.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


TX1/RX1
Switch Control -Bypass/Combiner

By-Pass Assembly

LA BT

ANT TX/RX1

BTS
RX1 TX1/RX1
+44.3dBm

RX
1 2 3 4 5 6 7

Input Duplexer #1

TX1

+43.3dBm

Universal Input Attenuator (UIA)


Pwr / Port: 45dBm Atten: -45 to -65dB
+5V From UCM
Splitter

MCPA Control, Alarm -9.03dBm Composite

Output Duplexer w/ Coupler TX/RX

Integrated Duplexer
+44.3dBm

TX2/RX2

Input Duplexer #2

TX2

+43.3dBm

F A N
Sense

MCPA Power: 125W Gain: 60dB

TX

TX Coupler Output

-40dB TX SAMPLE

+27VDC

TX Gain Setting 0-15V From UCM +24V From UCM

Integrated Filter Assembly


RX Receive Filter RX

RX2

BTS TX2/RX2 TX3/RX3


Switch Control -Bypass/Combiner

Switch Control -Bypass/Combiner

By-Pass Assembly

LA BT ANT RX3

ANT RX2

By-Pass Assembly

LA BT

BTS
RX3 TX3/RX3
+44.3dBm

Input Duplexer #3

TX3

Integrated Duplexer
+44.3dBm

TX4/RX4

Input Duplexer #4

TX4

RX4

BTS TX4/RX4 Universal Controller Module (UCM)


Form C Alarm
#1 #2 #1 #2 UCM Ctrl Signals - Sector 1

Switch Control -Bypass/Combiner

By-Pass Assembly

LA BT

ANT RX4

+27VDC

Ground

Sense B

Sense A OUTPUT LOADSHARING /BATTERY BACKUP 110VAC / 220VAC LOAD SHARING BATTERY MANAGEMENT BATTERY MANAGEMENT SENSOR

RS-232

+27VDC

UCM Junction Block


Alarm

+27V Rectifier

+27V Rectifier
03-0256B-A

Figure 4-1 OS-1900-SA(X) Functional Block Diagram

ANT TX1/ RX1 RX1

By-Pass Assembly

Switch Control -Bypass/Combiner

LA B-T
TX/RX1

ANT TX/RX1

2:1
1 2 3 4 5 6 7

RX1 IN

TX1

Univ. Input Atten. (UIA)


Atten: -45 to -65 dB

BTS TX1/RX1

Integrated Duplexer

S p li t t e r

MCPA Control, Alarm

-40 dB TX Coupler MCPA Power: 125W Gain: 60dB TX

+27VDC Sense TX Gain From UCM 0-15V From UCM +24V From UCM

TX2

BTS TX2/RX2
RX2 ANT RX2

F A N

Integrated Filter Assy

RX2 Out RX2 IN Switch Control -Bypass/Combiner

By-Pass Assembly

B-T LA B-T LA

ANT RX2 ANT RX3

BTS TX3/RX3
RX3 Integrated Duplexer +27VDC TX3 ANT RX3 Ground

By-Pass Assembly
50ohms

UCM Ctrl Signals - Sector 1


Sense B

Sense A

Output

Load Sharing /Battery Backup

+27VDC

UCM Junction Block


-Bypass/Combiner Fan Control 1, 2, 3 -Bypass/Combiner RX Gain Adjust #1 RX Gain Adjust #2 Fan Sense 1, 2, 3 Switch Control 1

+27V Rectifier
Alarm
VDC Input Voltage monitor MCPA Alarms

220VAC Load Sharing Battery Management Battery Management Sensor External DC Source

Switch Control 2

VDC LNA #1

RS-232

VDC LNA #2

Form C Alarm

Switch Control 3 Spare bypass

TX Gain Adjust 0-15V

Universal Controller Module (UCM)

+27V Rectifier
03-0220B-B

Figure 4-2 OS-1900-SB(X) Functional Block Diagram


Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

4-5 G3S-1900-125 Amplifier Module


The amplifier module, figure 4-3, has an average output of 125 watts power (1250 watts peak power) with intermodulation products suppressed to better than -63 dBc below carrier levels. The amplifier provides an amplified output signal with constant gain and phase by adding approximately 25 dB of distortion cancellation on the output signal. Continuously comparing active paths with passive references, and correcting for small variations through the RF feedback controls maintain constant gain and phase. All gain and phase variations, for example those due to temperature, are reduced to the passive reference variations. The amplifier module is comprised of: Preamplifiers: Two feedforward loops with phase-shift and gain controls

Main amplifier: DC/DC power regulator Error amplifier: Alarm monitoring, control, and display panel

The main amplifier employs class AB amplification for maximum efficiency. The error amplifier and feed forward loops correct signal nonlinearities introduced by the class AB main amplifier. The error amplifier also operates in class AB mode. The RF input signals are amplified by a preamp and coupled to an attenuator and phase shifter in the first feedforward loop. The main signal is phase shifted by 180 degrees and amplified in the premain amplifier. The output from the premain amplifier is fed to the class AB main amplifier. The output from the main amplifier is typically 180 watts. The signal is output to several couplers and a delay line.

Figure 4-3 G3S-1900-125 Power Amplifier Module Functional Block Diagram The signal output from the main amplifier is sampled using a coupler, and the sample signal is combined with the main input signal and input to the second feedforward loop. The error signal is attenuated, phase shifted 180 degrees, then fed to the error amplifier where it is amplified to a level identical to the sampled output from the main amplifier. The output from the error amplifier is then coupled back and added to the output from the main amplifier. The control loops continuously make adjustments to cancel out any distortion in the final output signals. The 2nd loop control section obtains a sample of the distortion added to the output signals by the main amplifiers, phase shifts the signals by 180 degrees, then feeds it to the error amplifier. There it is amplified to the same power level as the input sample and coupled onto the main output signal. The final output is monitored by the 2nd loop and adjusted to ensure that the signal distortion and IMD on the final output is canceled out.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 4-5.1 Main Amplifier


The input and output of the main amplifier employs two-stage, class AB amplifiers, to provide approximately 25 dB of gain in the 60 MHz frequency band from 1930 to 1990 MHz. The amplifier operates on +27 VDC, and is mounted directly on a heat sink, which is temperature monitored by a thermal sensor. If the heat sink temperature exceeds 85C, a high temperature fault occurs. The alarm logic that controls the transistor bias voltage, shuts down the amplifier.

4-5.2 Error Amplifier


The main function of the error amplifier is to sample and amplify the signal distortion level generated by the main amplifier, to a level that cancels out the distortion and IMD when the error signal is coupled into the main signal at the amplifier output. The error amplifier is a balanced multistage class AB amplifier with 75 dB of gain to produce over 100-watts peak output. The amplifier operates on +27 VDC and is mounted directly on a heat sink.

4-5.3 Amplifier Monitoring


In the main and error amplifier modules, all normal variations are automatically compensated for by the feed forward loop control. However, when large variations occur beyond the adjustment range of the loop control, a loop fault occurs. The alarms are displayed on the front panel indicators and output via the 21-pin connector located on the rear of the module to the subrack summary board for subsequent remote monitoring via the ALARMS connector. Refer to section 2 for a description of the ALARMS connector.

4-5.4 Amplifier Module Cooling


Each amplifier module contains its own heat sink and heat is drawn out of the amplifier by cooler air flowing over the heat sink fins. Four fans provide forced air cooling and redundancy. The fans, which are field replaceable, are located on the front and rear of the amplifier module. Cooling air is drawn in through the front of the amplifier and the hot air is exhausted out the back of the module.

4-5.5 Power Distribution


The OS-1900-SA(X)/SB(X) enclosure uses an AC power source from the BTS. The AC powered enclosure contains either a 125-Amp or 148-Amp rectifier that supplies each amplifier module with a +27 VDC operating voltage. The amplifier module has an internal DC/DC converter that converts the +27 VDC to +15 VDC, +5 VDC and -5 VDC for use by other functions within the module.

4-5.6 Intermodulation
The G3S-1900-125 amplifier is designed to deliver a 125-watt composite average power, multicarrier signal, occupying a bandwidth less than or equal to 25 MHz, in the bandwidth from 1930 to 1990 MHz. The maximum average power for linear operation, and thus the amplifier efficiency, depends on the type of signal amplified.

4-5.7 Two-Tone Intermodulation


When measured with two equal CW tones spaced from 30 kHz to 20 MHz apart, and at any power level up to the average power, the 3rd order intermodulation products are below -63 dBc.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 4-5.8 Multitone Intermodulation


Adding more tones to the signal lowers individual intermodulation products. If the frequencies are not equally spaced, the level of intermodulation products gets very low. When the frequencies are equally spaced, those products fall on top of each other on the same frequency grid. The average power of all intermodulation beats falling on the same frequency is called the composite intermodulation; it is -63 dBc or better.

4-5.9 Amplifier Monitoring


In the main and error amplifier modules, all normal variations are automatically compensated for by the feedforward loop control. However, when large variations occur beyond the adjustment range of the loop control, a loop fault occurs. The alarms are displayed on the front panel indicators and output via the 21-pin connector located on the rear of the module to the subrack summary board for subsequent remote monitoring. Table 4-1 G3S-1900-125 Interface Connector Pinouts
Pin No. A1 A2 A3 A4 1 2 3 4 5 6 7 8 9 10 11 Function RF Input Power Input Ground RF Output Ground RS 485 +RxD RS 485 RxD RS 485 +TxD RS 485 TxD Address R3 Address R2 Fan Fail Forward Power Monitor Address R0 Average Power Input Description Coaxial Contact +27 VDC (Power Contact) Ground (Power Contact) Coaxial Contact Ground Serial Communication Data In Serial Communication Data In Serial Communication Data Out Serial Communication Data Out Rack Address R3; Ground for high, float for low Rack Address R2; Ground for high, float for low TTL signal normally low. A high level indicates that one or both of the fans have failed. An analog DC signal representing the RF output power of the MCPA. The voltage is 4 volts 100 mV at the maximum rated output power. Rack Address R0; Ground for high, float for low An analog DC voltage representing the average detected power of the MCPA in a subrack. This voltage is derived by dividing the sum of all the forward power voltages in a subrack by the number of enabled MCPAs. This voltage is used by the MCPA to determine a low power fault. Amp Address A0; Ground for high, float for low TTL signal normally low. A high level indicates that the MCPA has been disabled by a recurring alarm fault. Amp Address A1; Ground for high, float for low Ground potential. Informs the subrack that an MCPA is plugged in. TTL signal normally low for an enabled MCPA. A high level will disable the MCPA. TTL signal, low if the front panel switch is in the ON position. A high level indicates the front panel switch in the OFF position.

12 13 14 15 16 17

Address A0 Summary Fault Address A1 Module Detect Bias Input FP Disable Output

Note

Address R1 is internally tied high.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-5

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

2 3 4 5

6 7 8 9

A1

A2
10 11 12 13 14 15 16 17

A3

A4

Figure 4-4 G3S-1900-125 Interface Connector

4-5.10 Pilot Tone Control


For the OS-1900-SA(X)/SB(X) system G3S-1900-125 MCPAs, the pilot tone is preset at the factory to 1964.5 MHz. The pilot tone frequency selection is based on the intended operational band of the amplifiers as listed in table 4-2. Table 4-2 Pilot Frequency Setting Based on PCS Frequency Block of Operation
Block Designator Bandwidth Pilot (MHz) A 15 1945.5 (A) D 5 1950.5 (D) B 15 1965.5 (B) E 5 1964.5 (E) (default) 5 5 1970.5 (5) F 5 1969.5 (F) C 15 1974.5 (C) Block Pairs A-D 1930-1950 20 1950.5 (D) D-B 1945-1965 20 1965.5 (B) B-E 1950-1970 20 1970.5 (5) E-F 1965-1975 10 1964.5 (E) F-C 1970-1990 20 1969.5 (F) E-C Excluding F 1965-1990 Excluding: 1970-1975 25 1974.5 (C) (1) If the Block Designator has not been previously selected through serial communication, pilot defaults to 1964.5 on the G3S-1900-125 amplifier. (2) If the Block Designator is selected through serial interface, pilot frequency is moved to the appropriate spot and is stored permanently into the microprocessor until another band is changed. (3) 5 Pilot Frequency requires firmware update from rev. 3.C and greater. Transmit Frequency Band (MHz) Base Station 1930-1945 1945-1950 1950-1965 1965-1970 1965-1970 1970-1975 1975-1990

If the pilot tone is not moved and signals are transmitted in B-band, some traffic channels may transmit directly on the pilot tone. The pilot tone requires a guard band of 60 KHz for TDMA, 270 KHz for CDMA (IS-95), and 400 KHz for GSM. Transmitting on the pilot tone causes the amplifier to go into Loop Fail. This will not damage the MCPA. However, CDMA customers will experience a Loop Fail in every sector where the amplifiers are installed. TDMA and GSM customers will experience intermittent Loop Fails in the sectors that use these frequencies. On the other hand, if the pilot tone is not moved and signals are transmitted in A-band (19301945) or C-band (1975-1990), the instantaneous bandwidth of the amplifier will be exceeded. This will cause equipment operated in the outer bands of the PCS band to experience higher intermodulation distortion, which may in turn cause them to exceed FCC emission limits. The lower end of the PCS band presents the farthest frequency span from the default pilot tone, which begins at 1930 MHz, 34.5 MHz away from the pilot tone of the G3S-1900-125 amplifier. The amplifier may be operated in bandwidths wider than 20 MHz and still meet FCC rules, however the amplifier specifications are based on a 20 MHz bandwidth nearest the pilot tone. Refer to section 3-3.2 for actual Pilot frequency selection. The pilot frequency is set from the UCM, which also stores this setting in memory. If an amplifier fails, the UCM programs the pilot frequency of the replacement amplifier to that of the other installed amplifier.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-6

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 4-5.11 Alarm Interface


The amplifier has an RS-485 alarm port. The amplifier reports its status as faults occur, to the UCM. The alarm signals are converted to Form-C, then routed from the UCM to an internal terminal board mounted on the right side at the rear of the enclosure. The signals are then routed through the I/O port of the to the alarm monitor station (refer to section 2).

4-5.12 Plug-In Rectifiers


The system currently employees two different rectifiers (930-00016-008 or 930-00018-05) that are not interchangeable because of different subrack designs (refer to table 1-1). The function of the rectifier is to convert the AC voltage input from the BTS to the +27 VDC used by the OS-1900 system. In a one-rectifier system, if a failure occurs and replacement is required, the system would already be in bypass mode and the rectifier could be removed and replaced with the AC power still applied to the system. In a two-rectifier system, a failure of one rectifier would not place the system into bypass mode and the failed rectifier could be hot swapped with a new unit.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-7

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

(This page intentionally left blank)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

4-8

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 5 Maintenance
5-1 Introduction
This section contains periodic maintenance and performance test procedures for the Powerwave OS-1900-SA(X)/SB(X) Indoor/Outdoor Multi-Carrier Power Amplifier (MCPA) System. Note Check your sales order and equipment warranty before attempting to service or repair the OS-1900-SA(X)/SB(X) System. Do not break the seals on equipment under warranty or the warranty will be null and void. Do not return equipment for warranty or repair service until proper shipping instructions are received from the factory.

5-2 Periodic Maintenance


Periodic maintenance requirements are listed in table 5-1, as well as the intervals at which the tasks should be performed. Warning Wear proper eye protection to avoid eye injury when using compressed air.

Table 5-1 Periodic Maintenance Task Cleaning: Air Vents Inspection: Cables and Connectors Performance Tests 12 Months 12 Months 12 Months 12 Months Inspect signal and power cables for frayed insulation. Check RF connectors to be sure that they are tight. Perform annual tests in accordance with individual amplifier manuals. Check manual bypass switch for functionality. Antenna VSWR sweep. 180 Days* Inspect and clean per paragraph 5-4 Interval Action

* Dusty environment may require more frequent cleaning.

5-3 Test Equipment Required for Test


Test equipment required to test the amplifier system is listed in the individual manuals. Equivalent test equipment may be substituted for any item, keeping in mind that a thermistor type power meter is required. Note All RF test equipment must be calibrated to 0.05 dB resolution. Any deviation from the nominal attenuation must be accounted for and factored into all output readings.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

5-4 Cleaning Air Inlets/Outlets/Filters


The air inlets, outlets, and filter located on inside of the louvered enclosure front cover, should be cleaned every 180 days. If the equipment is operated in a severe dust environment, they should be cleaned more often as necessary. Turn off DC power source before cleaning fans. If dust and dirt are allowed to accumulate, the cooling efficiency may be diminished. Using either compressed air or a brush with soft bristles, loosen and remove accumulated dust and dirt from the air inlet/outlet panels.

5-5 Performance Test


Performance testing should be conducted every 12 months to ensure that the amplifier system meets the operational specifications listed in appendix A. Also verify system performance after any amplifier module is replaced in the field. Test equipment required for performing tests and test setups are listed in the amplifier manual (044-05122).

5-6 Field Replaceable Parts and Modules


The following parts and modules can be replaced in the field on site by a qualified technician with experience maintaining RF power amplifiers and similar equipment: Power Amplifier Module Amplifier Cooling Fans Universal Control Module (UCM) 125-Amp Rectifier Module 148-Amp Rectifier Module Duplexer/Universal Input Attenuator (UIA) Tray Universal Input Attenuator (UIA) Cooling Fan Assembly

Access panels on the OS-1900-SA(X)/SB(X) enclosure, front, rear, or both as appropriate, must be removed to perform the following maintenance operations.

5-6.1 Power Amplifier Module


To replace a power amplifier module, proceed as follows: 1. 2. Set the circuit breaker switch on the front panel of the amplifier module to Off. Loosen the two screws that secure the amplifier module to the amplifier subrack. Caution When removing the amplifier from the case, it is very important to support the amplifier such that the rear of the module does not suddenly drop when the guide rail disengages from the track. A drop such as this could damage the rear multipin connector. The amplifier weight is approximately 42 lbs.

3.

With steady even pressure, use the handle on the front of the amplifier to pull the module out of the enclosure. When the amplifier is halfway out, press on the release latch to completely remove the amplifier (see figure 1-9). Replace the amplifier module in the reverse order. Ensure that the mounting screws are tightened to seven (7) inch-pounds.

4.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 5-6.2 Amplifier Cooling Fans


To replace a cooling fan, proceed as follows: 1. 2. 3. There is no need to remove the amplifier module from the subrack to replace either fan. Pull out snap fasteners that secure fan to amplifier module. Disconnect fan power connector from amplifier module. Install replacement in reverse order of step 2.

5-6.3 Universal Control Module (UCM)


To replace a UCM, proceed as follows: 1. 2. 3. 4. At the main circuit breaker panel, turn off AC power to the OS-1900-SA(X)/SB(X). Remove the UCM from the subrack. Install replacement module in the reverse order. Readjust amplifier gain (refer to paragraph 3.3-5).

5-6.4 125-Amp Rectifier (930-00016-008)


To replace the rectifier, proceed as follows:

5-6.4.1 Hot Swap in a Two-Rectifier System


In a two-rectifier system, if one rectifier fails (as indicated by an alarm), the system does not go into bypass, and the failed rectifier may be removed from the enclosure and replaced with a good one as follows: 1. Loosen the thumbscrew that secures the rectifier module to the subrack. Caution When removing the rectifier from the subrack, it is very important to support the rectifier such that the rear of the module does not suddenly drop when removed from the subrack. A drop such as this could damage the rear multipin connector.

2. 3. 4. 5.

With steady even pressure, use the handle on the front of the rectifier to pull the module out of the subrack. Replace the rectifier module in the reverse order. Press the pushbutton On/Off switch on the front panel of the rectifier module to On. Once the rectifier voltage is in the normal operating range, the alarm will automatically clear. Note 1. If adding a second rectifier for redundancy, the UCM (RECTx) dipswitch must be set to ON for the additional rectifier to be monitored for alarms. See figure 3-2. 2. If a rectifier is permanently removed from a two-rectifier system, the UCM (RECTx) dipswitch must be set to OFF to clear the corresponding alarm. See figure 3-2.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 5-6.4.2 Replacement in a One-Rectifier System


In a one-rectifier system, if a rectifier fails, the amplifier shuts down and the system goes into bypass. Replace the rectifier as follows: 1. 2. 3. 4. Set the circuit breaker switch on the front panel of the amplifier module (s) to Off. At the main circuit breaker panel, turn off AC power to the OS-1900-SA(X)/SB(X). Press the pushbutton On/Off switch on the front panel of the rectifier module to Off. Loosen the thumbscrew that secures the rectifier module to the subrack. Caution When removing the rectifier from the subrack, it is very important to support the rectifier such that the rear of the module does not suddenly drop when removed from the subrack. A drop such as this could damage the rear multipin connector.

5. 6.

With steady even pressure, pull on the module handle to remove the module from the subrack. Replace the rectifier module in the reverse order.

5-6.5 148-Amp Rectifier (930-00018-005)


To replace the rectifier, proceed as follows:

5-6.5.1 Hot Swap in a Two-Rectifier System


In a two-rectifier system, if one rectifier fails (as indicated by an alarm), the system does not go into bypass, and the failed rectifier may be removed from the enclosure and replaced with a good one as follows: 1. Loosen the thumbscrew that secures the rectifier module to the subrack. Caution When removing the rectifier from the subrack, it is very important to support the rectifier such that the rear of the module does not suddenly drop when removed from the subrack. A drop such as this could damage the rear multipin connector.

2. 3. 4.

With steady even pressure, use the handle on the front of the rectifier to pull the module out of the subrack. Replace the rectifier module in the reverse order. Once the rectifier voltage is in the normal operating range, the alarm will automatically clear. Note 1. If adding a second rectifier for redundancy, the UCM (RECTx) dipswitch must be set to ON for the additional rectifier to be monitored for alarms. See figure 3-2. 2. If a rectifier is permanently removed from a two-rectifier system, the UCM (RECTx) dipswitch must be set to OFF to clear the corresponding alarm. See figure 3-2.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual 5-6.5.2 Replacement in a One-Rectifier System


In a one-rectifier system, if a rectifier fails, the amplifier shuts down and the system goes into bypass. Replace the rectifier as follows: 1. 2. 3. Set the circuit breaker switch on the front panel of the amplifier module (s) to Off. At the main circuit breaker panel, turn off AC power to the OS-1900-SA(X)/SB(X). Loosen the thumbscrew that secures the rectifier module to the subrack. Caution When removing the rectifier from the subrack, it is very important to support the rectifier such that the rear of the module does not suddenly drop when removed from the subrack. A drop such as this could damage the rear multipin connector.

4. 5.

With steady even pressure, use the handle on the front of the rectifier to pull the module out of the subrack. Replace the rectifier module in the reverse order.

5-6.6 Duplexer/Universal Input Attenuator (UIA) Tray


To replace a duplexer/universal input attenuator tray, proceed as follows: 1. 2. At the main circuit breaker panel, turn off AC power to the OS-1900-SA(X)/SB(X). Remove the rear panel. Caution The hard-line coaxial cables between the rear panel and the UIA are easily damaged. Care must be taken to avoid bending or forcing cables / connectors. Inspect connector solder points for cracks after connectors are reinstalled at the completion of this procedure.

3. 4. 5. 6.

Disconnect all RF input and output connections on the inside of the rear panel. Disconnect the fans Molex connector. Slide the duplexer/UIA drawer out. Install replacement module in the reverse order.

5-6.7 Universal Input Attenuator (UIA) Cooling Fan Assembly


To replace a UIA fan assembly, proceed as follows: 1. 2. 3. 4. At the main circuit breaker panel, turn off AC power to the OS-1900-SA(X)/SB(X). Refer to figure 1-8. Pull out on the fastener/plungers securing the fan assembly. Pull the fan out of the enclosure, disconnect the power connector, and completely remove the fan assembly. Install the replacement fan in reverse order of removal.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-5

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

(This page intentionally left blank)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

5-6

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Section 6 Troubleshooting
6-1 Introduction
This section contains problems based on the G3S-1900-125 front panel indicators and a few suggested actions that may correct these problems should they occur. If the suggested corrective action does not eliminate the problem, please contact your Powerwave field representative or the factory for further instructions. Note Check your sales order and equipment warranty before attempting to service or repair the unit. Do not break the seals on equipment under warranty or the warranty will be null and void. Do not return equipment for warranty or repair service until proper shipping instructions are received from the factory.

6-2

Troubleshooting

The OFF/ON/RESET switch can clear many alarm faults. It is located on the front panel of the faulted amplifier module. An attempt to reset the fault should be your first course of action. 24 Hour technical support service is available at our main phone number 888-797-9283 or 714-4661000; select the "System Operator Technical Support" option to receive assistance from Powerwave's Applications Support Group. The following are general guidelines established to aid Field Engineers or Cell Site Technicians in the proper method of Powerwave equipment fault resolution by fault mode.

6-2.1 DC Voltage Indicators Not Illuminated


1. 2. 3. Check the front panel ON/OFF switch. Check the power plant circuit breaker. Check for +27 + 1.0 VDC at the amplifier subrack input. A. B. If the voltage is low, verify that all DC connections between the power plant and the amplifier subrack are tight. If the voltage is correct, (1). Remove the amplifier from the subrack slot and move the amplifier to another amplifier subrack slot. (2). Check the voltage on the power pins of the mating amplifier and amplifier subrack connector. Verify that the amplifier DC connections are not damaged (see figure 61 and table 6-1). (3). If voltages are correct and connections are secure, return the amplifier to the factory for repair.

Figure 6-1 DC and Logic Connector (Male, on Rear of G3S-1900-125 Amplifier Module)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

6-1

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


Table 6-1 Amplifier Module DC and Logic Connector Definition PIN
A1 A2 A3 A4

Function
Power Input Power Input Ground Ground +27 VDC (Power Contact) +27 VDC (Power Contact) Ground (Power Contact) Ground (Power Contact)

Description

6-2.2 OVER PWR Illuminated


1. If all the amplifiers in a given amplifier enclosure are in Over Pwr and the LPA Disable LED is illuminated, then the input RF power level is too high and the amplifiers have been turned off. This could be the result of RF power being incorrectly set during equipment commissioning or a faulty jumper cable. Verify the amplifier enclosure output cables transmit filter, and directional coupler are in proper working order. The loss between the amplifier enclosure and the hatch plate is typically less than 2.0 dB. If the amplifier is in Over Pwr, then the input RF power level is too high. The amplifier is attempting to maintain a safe power output level. This could be the result of RF power being incorrectly set during equipment commissioning or a faulty jumper cable. Verify the amplifier output cables, duplexers, and attenuators are in proper working order.

2.

6-2.3 HIGH TEMP Illuminated


1. If an amplifier is in HIGH TEMP and the LPA Disable LED is illuminated, then the amplifier heat sink temperature is too high. This may be due to: A. B. C. 2. High ambient temperature. Fan failure. Insufficient air-volume capacity. Most of Powerwaves amplifiers require a certain amount of free-space to allow proper airflow.

Correct the heat problem, then reset the amplifier by momentarily pressing up on the amplifier front panel Off/On/Reset switch.

In hot climate environments, shading of the equipment cabinet is recommended to reduce the equipment cabinets heat load.

6-2.4 VSWR Illuminated


1. If the amplifier is in VSWR and the LPA Disable LED is illuminated, then the output RF reflected power level is too high and the amplifier has been turned off. This may be due to a faulty jumper cable or transmit filter. Verify the amplifier output cables, duplexers, and attenuators are in proper working order. This fault normally occurs during site or just following site power setting and normally takes about 10 to 15 minutes to appear. This fault may not occur at low power levels (i.e. when just one or two channels are up). If the amplifier is in VSWR and the LPA Disable LED is illuminated, then the output RF reflected power level is too high for that amplifier. This may be due to: A. B. A damaged or recessed amplifier RF output connector. Return the amplifier to the factory for repair. Mishandling of the amplifier can cause recessed pins. Before installing an amplifier, look at the D-sub connector to ensure none of the pins are recessed, bent, or that the outer connector shield is not damaged. When installing the amplifier, do not force the amplifier into the slot. Gentle even pressure is all that is needed to properly seat the amplifier.

2.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

6-2

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual


C. Improper seating of the amplifier. (1). Ensure the amplifier thumbscrews are properly tightened. (2). Try seating the amplifier in another slot. (3). Try seating the amplifier in another sector.

6-2.5 DC FAIL Illuminated


If an amplifier is in DC FAIL and the LPA Disable LED is illuminated, then one of the amplifier DC voltages is either out of tolerance or not present. Return the amplifier to the factory for repair.

6-2.6 FAN FAIL Illuminated


If an amplifier is in FAN FAIL, then an amplifiers cooling fans has failed. Replace the fan. In the G3 model amplifiers, fan failure does not cause the amplifier to shut down; this is determined by the heat sink temperature, as previously mentioned.

6-2.7 LOOP FAIL Illuminated


LPA Disable LED illuminated always accompanies Loop Fail. This may be due to: 1. 2. Inability of the amplifier to maintain a 180 phase shift between the first and second loops. A damaged error amplifier. This can be caused by: A. B. Out of band spurious or intermods being applied at too high of a level at the amplifier input port. An input band-pass filter may be necessary to correct this problem. Disconnecting amplifier RF output cables while the amplifier is still turned on. Always turn the amplifier off when moving output RF cables from the hatch plate to test equipment and back again.

3. 4.

Operating the Pilot tone within the base stations designated frequency band. Program the UCM for a Pilot tone in a neighboring frequency band. Refer to section 3, paragraph 3-3.2

6-2.8 LOW PWR Illuminated


The LPA Disable LED being illuminated always accompanies Low Power. This is due to the gain of either the internal preamplifier or main amplifier being 0.5 dB (typically) or more below the amplifier specification. The amplifier should be returned to the factory.

6-2.9 LPA DISABLE Illuminated


1. LPA Disable LED illuminated indicates that the amplifier RF section is turned off. This may be due to: A. B. 2. 3. 4. An accompanied alarm indicating a critical amplifier fault (i.e. Loop Fail fault). Improper seating of the amplifier in the enclosure.

Ensure the amplifier thumbscrews are properly tightened. Reset the amplifier by momentarily pressing up on the amplifier front panel Off/On/Reset switch. Try seating the amplifier in another enclosure slot. Try seating the amplifier in another enclosure, if available.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

6-3

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

6-3 Return for Service Procedures


When returning products to Powerwave, the following procedures will ensure optimum response.

6-3.1 Obtaining an RMA


A Return Material Authorization (RMA) number must be obtained prior to returning equipment to the factory for service. Please contact our Repair Department at (888) 797-9283 or (714) 4661000 to obtain this number, or FAX your request to (714) 466-5816. Failure to obtain this RMA number may result in delays in receiving repair service.

6-3.2 Repackaging for Shipment


To ensure safe shipment of the amplifier, it is recommended that the original shipping package designed for the amplifier be reused. If it is not available, contact our Repair Department for packing materials and information.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved 044-05140 Rev. B

6-4

June 2004

OS-1900-SA(X)/SB(X) Installation and Service Manual

Appendix A Specifications
A-1 OS-1900-SA(X)/SB(X) System Specifications
Table A-1 OS-1900-SA(X)/SB(X) System Specifications
Frequency Range Maximum Power Output Maximum Gain Gain Flatness Across Band IMD Performance Maximum RF Input Power without damage per port Primary Power: AC Model Current: 125-Amp Rectifier Current: 148-Amp Rectifier Operating Temperature Outdoor Enclosure Dimensions NEMA Rating Weight with amplifier subrack, one amplifier, and one rectifier Weight with amplifier subrack, two amplifiers, and one rectifier Weight with amplifier subrack, two amplifiers, and two rectifiers Weight with amplifier subrack and one amplifier 1930-1990 MHz, 25 MHz Instantaneous 90 Watts +12 dB 1.5 dB 0.75 dB Maximum See table A-2 below +47 dBm 176 to 264 VAC, 47-63 Hz, Single Phase See table A-3 See table A-4 -10 C to +50 C 34(H)x16(W)x34(D) inches 3R Approximately 186 Pounds Approximately 231 lbs (21 lb rectifier) Approximately 221.5 lbs (13.5 lb rectifier) Approximately 252 lbs with 21 lb rectifiers Approximately 235 lbs with 13.5 lb rectifiers Approximately 165 Pounds (-21 lb rectifier) Approximately 172.5 Pounds (-13.5 lb rectifier)

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. A-1 June 2004 044-05140 Rev. B

OS-1900-SA(X)/SB(X) Installation and Service Manual

A-2 Amplifier Model G3S-1900-125


Table A-2 Amplifier Model G3S-1900-125 Specifications
Frequency Range Total Maximum Input Power Total Output Power RF Gain at 1930 MHz Gain Flatness: Gain Variation Over Temperature: Output Protection: Input Port Return Loss: Output Port Return Loss: Second Harmonics: Duty Cycle: DC Input Power: Operating Temperature: Storage Temperature: Operating Humidity: Storage Humidity: RF Input / Output Connector Status / Alarm / Control / DC Input Connectors: Weight Dimensions: 1930-1990 MHz (Refer to table A-5) -4 dBm 125 Watts typical (1 Module) 60 dB 0.5 dB @ 27 VDC 1 VDC 0.5 dB from 24 to 30 VDC Mismatch Protected -14 dB (Max) -14 dB (Max) -13 dBm (Max) Continuous +27 1 VDC, 52 A DC typical. 60 A DC max @ 125 Watts; Operational +21.0 VDC to 30 VDC 0 C. to +50 C. -40 C. to +75 C. 0% - 80% Relative Humidity (No condensing) 0% - 95% Relative Humidity (No condensing) Radial BMA Female Blind Mate Connector 21-Pin D-Subminiature Combo Connector 45 lbs. 5.22 High, 16.97 Wide, 20.44 Deep

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. A-2 June 2004 044-05140 Rev. B

OS-1900-SA(X)/SB(X) Installation and Service Manual

A-3 125-Amp Rectifier Specifications


Table A-3 125-Amp Rectifier Model 930-00016-008 Specifications
Input Voltage Input Current 176 / 264 VAC, 47 / 63 Hz, Single phase 24 A AC@ 176 VAC 20 A AC @ 208 VAC 18 A AC @ 240 VAC 0.98 typical <5% total @ full load; <3% @ each harmonic 82% typical 15 ms, minimum at any input voltage within the operating range No damage will occur when operating below the minimum input voltage Meets IEEE-587-1980 +23.0 to +28.0 VDC (set to +27.0 for Powerwave) 125 A DC maximum 1350 Watts @ 220 VAC < 200 mV P-P measured with 20 MHz bandwidth <+0.25% <+0.5% from 10% to full load; +2% from no load to 10% load 2 seconds maximum 5% maximum May be connected to similar rectifiers for increased current output Isolation diode allows Hot Swap of failed units without disturbing load Shutdown occurs @ 30 VDC 125 +6 A DC, short circuit protected Shut down @ 70 C ambient; Thermostat controlled with auto recovery 0 to 50 C -30 to +85 C 0 to 95% non-condensing Radiated and conducted noise meets FCC Part 15, Subpart J, Class A, and VDE0871, Class A Meets UL1950, IEC950, and CSA 22.2 #234 100,000 21 pounds

Power Factor Harmonic Distortion Efficiency Hold-Up Time Under voltage Input transients Output Voltage Output Current Output Power Ripple & Noise Line Regulation Load Regulation Turn On Delay Turn On Overshoot Parallel Interface Hot Swap Over Voltage Protection Over Current Protection Over Temperature Protection Operating Temperature Storage Temperature Humidity EMI Safety MTBF Weight

Specifications as provided by Telecommunications Power Systems, Document Number 701396-15, Revision A, May 7, 1997

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. A-3 June 2004 044-05140 Rev. B

OS-1900-SA(X)/SB(X) Installation and Service Manual

A-4 148-Amp Rectifier Specifications


Table A-4 148-Amp Rectifier Model 930-00018-005 Specifications
Input Voltage Input Current Power Factor Inrush Current Harmonic Distortion Efficiency Hold-Up Time Output Voltage Range Line Regulation Load Regulation Output Ripple & Noise Transient Response Start-Up Time Hold-Up time Overshoot/Undershoot Temperature Coefficient Remote On/Off 180 / 264 VAC, 47 / 63 Hz, Single phase 25.5 A AC @ full load @180 VAC 0.99 typical 50 A AC maximum <5% total @ full load; <3% @ each harmonic 89% typical @ 230 VAC >20 ms @ low line +20.0 to +29.0 VDC (set to +27.0 for Powerwave)

0.5% using remote sense (5% on standby voltage) 0.5% using remote sense (5% on standby voltage) < 1% P-P 3 % max deviation. 0.50 ms recovery time for a 25% load change 2 Seconds >20 ms @ low line 1% at turn on/off 0.02% per C Logic 1(TTL high) or open enables unit (on), Logic 0 (TTL low) or short shuts unit down (Off) Power Fail Signal Signal goes low (TTL low) 2 ms before loss of output regulation Current Limit Protection 110-140% V1, 5VSB <2.5 amps automatic recovery Over Voltage Protection 29.5 to 30.5 V. Reset by cycling input power Over Temperature Protection Automatic shutdown with auto recovery. Thermal shutdown point @ 95 C MTBF 300,000 hours per Belcore standard Output Power Good TTL high = power good, TTL low = output out of limits LED Indicators DC good = green LED; temperature OK = green LED; AC good = amber LED Operating Temperature 0 to 50 C @ rated output power. Supply derates linearly from 50 C to 65 C @ 2.2% per C Cooling Self contained ball bearing fan Shock and Vibration Per MIL STD-810F, NEBS compliant to GR 63 Core EMI/EMC Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR1089-Core Safety Approvals Meets UL1950, CSA 22.2 #650, TUV EN60950 and CE Mark Weight 13.5 pounds Specifications as provided by Cherokee International, Document Number 97MS2101M, Revision A, Aug 1, 2003

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. A-4 June 2004 044-05140 Rev. B

OS-1900-SA(X)/SB(X) Installation and Service Manual

Appendix B. Power Setting Procedures


B-1 Power Setting Calculations:
1. 2. 3. Ensure the composite input power to the Powerwave amplifier is < -11 dBm. Determine the required output level at the hatch plate per carrier (Analog, Digital, CDPD, and Setup Channel). Determine the amount of loss between the amplifier output and the hatch plate. A. B. Either the calculated value, or Measure the loss: (1). Key one radio and make a measurement in dBm at the back of the amplifier with a HP EPM-441A or equivalent power meter. Write the value down: _____ dBm. (2). Unkey the radio and move the power meter to the hatch plate. (3). Key the same radio and make a measurement in dBm, and write it down: _____ dBm. The difference between the two measurements is the loss. 4. Determine the amount of power output at the rear of the amplifier per carrier. Multiply the number of carriers times the output power level per carrier at the rear of the amplifier. A blank worksheet is provided on page B4 for you to record your desired power levels. Table B-1 OS-1900-SA(X)/SB(X) Gain Example
Standard Gain OS-1900-SA(X)/SB(X) 1 MCPA 125W max Radio Input to OS-1900 Cable Loss to Bypass Bypass Loss Cable Loss to Duplexer Duplexer Loss Cable Loss to UIA UIA Loss Cable Loss to MCPA MCPA Gain Cable Loss to Duplexer Duplexer Loss Cable Loss to Bypass Bypass Loss Cable Loss to LA LA Loss Cable Loss to Antenna Antenna Gain / ERP System Gain: OS-1900SA(X)/SB(X) Number of Radios Single Carrier Power System Gain/ Loss -0.25 -0.2 -0.25 -1 -0.25 -57.8 -0.25 60 -0.25 -0.6 -0.25 -0.2 -0.25 -0.1 -1.5 13 -1.65 dBm 45 44.75 44.55 44.3 43.3 43.05 -14.75 -15 45 44.75 44.15 43.9 43.7 43.45 43.35 41.85 54.85 Watts 31.62 29.85 28.51 26.92 21.38 20.18 0.00 0.00 31.62 29.8538 26.0016 24.5471 23.4423 22.1309 21.6272 15.31 305.49 System Gain/ Loss -0.25 -0.2 -0.25 -1 -0.25 -57.8 -0.25 60 -0.25 -0.6 -0.25 -0.2 -0.25 -0.1 -1.5 13 -1.65 4 51.02059991 Composite Power dBm 51.02 50.77 50.57 50.32 49.32 49.07 -8.73 -8.98 51.02 50.77 50.17 49.92 49.72 49.47 49.37 47.87 60.87 Watts 126.49 119.42 114.04 107.66 85.52 80.73 0.00 0.00 126.49 119.42 104.01 98.19 93.77 88.52 86.51 61.24 1221.97 126.4911064

5.

If the total output power level at the back of the Powerwave amplifier exceeds the amplifiers specified capability: 1. Reduce the loss between the rear of the amplifier and the hatch plate, or
Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. B-1 June 2004 044-05140 Rev. B

OS-1900-SA(X)/SB(X) Installation and Service Manual


2. Reduce the number of input radios until the amplifier power rating is met. CDMA carriers are normally set with only pilot page and sync signals up. These represent approximately 15% of the overall maximum average channel power. Therefore, Powerwave normally multiplies CDMA power by a factor of 7 when CDMA power is given under 7 Watts.

B-2 Power Setting Procedure:


Note The amplifiers must be warmed up for a minimum of 20 minutes prior to setting power levels. Failure to properly warm the amplifiers may result in lower output power, once the amplifiers reach operating temperature.

1. 2. 3. 4. 5. 6. 7.

Set the UCM TX to minimum gain (fully counter-clockwise; factory default). Ensure all radios are unkeyed. Turn the amplifier off. Connect the power meter with appropriate attenuators as necessary to the duplexer output port of the OS-1900-SA(X)/SB(X). Turn the amplifier on. Set the base station radio output to +45 dBm. Set the OS-1900-SA(X)/SB(X) output power level using the TX gain potentiometer on the UCM. Key the same radio. Monitor the output power at the antenna port of the output duplexer and according to the calculations made in the first section above. Do not readjust the radio output level unless the gain adjust on the amplifier is set to fully clockwise (maximum gain) and the desired output power is still not attained. Unkey the radio. Key one radio at a time and set the power level of each individual radio at the hatch plate according to the calculations made in the first section above. Do not readjust the gain adjust on the UCM. All subsequent adjustments must be made at the radio.

8. 9.

10. Unkey all radios. 11. Key all the radios and measure the total maximum power. This power level should not exceed the rating for the amplifier. If the power rating for the amplifier is exceeded, the Inter Modulation Distortion performance of the amplifier suffers. Note Each amplifier will shut down at 158 W, which will cause the sector to be off the air.

12. Unkey all the radios. 13. Turn the amplifier off. 14. Reconnect the RF output coax cable to the Powerwave amplifier. 15. Install weatherproofing material on OS-1900-SA(X)/SB(X) external connections per the manufacturers instructions. 16. Turn the amplifier on. 17. Place the site in service.

Copyright Powerwave Technologies, Inc., June 2004. All rights reserved All specifications are subject to change without notice. Contact the factory for complete performance data. B-2 June 2004 044-05140 Rev. B

Vous aimerez peut-être aussi