company profile
SUPERIOR CABLES LTD., established in 1934, produces a wide range of copper and fiber optic cables for communication, power and electronics in its two divisions in Israel. The former "CVALIM" and "Cables of Zion" companies have merged January 1999 after they were acquired by the American cable manufacturer Superior TeleCom Inc., Atlanta. Superior TeleCom Inc. ranks as one of the 4 largest cable manufacturers in the world. The two divisions are: Telecommunication Division manufacturing mainly telephone copper conductors up to 2400 pairs, electronic wires and cables, fiber optic cables - single and multi mode fibers - up to 432 fibers. Power Division manufactures low, medium and high voltage power cables and also extra high voltage underground cables up to 161 kV as well as automotive and industrial cables such as control, flexible power and welding cables. The cables are manufactured according to the highest world standards and all the manufacturing facilities as well as the head quarters are ISO 9001/9002 approved. SUPERIOR CABLES LTD. is committed to offer our customers worldwide: Top quality World class service Technical expertise Reasonable prices Short delivery time These qualities have contributed to the growing number of satisfied customers and the intensive global activities in the cable business. The service, quality, price and short delivery time has given SUPERIOR CABLES LTD. the good reputation of a manufacturer who can develop and deliver a top quality cable at a shorter delivery time than many other cable manufacturers. Among the national and international standards with which our cables comply are: BS - British Standard, EC - Delta Electronics Testing, IBM, Motorola, UL - Underwriters Laboratory, EIA/TIA, VDE, Bellcore, Bezeq - Israel Telecom Company
Th e S ta
nd
ard
s I n s t it u t io
of
ty
ed A s s ur
Other available catalogs: Flexible Cables Fiber Optic Cables Telecommunication Cables Electronic Cables Automotive Cables Data Cables
Superior Cables Ltd. takes every precaution to ensure the information given in this publication is correct. E.&O.E. All information is subject to change without notice. Superior Cables Ltd. standard limited warranty, stated in its sales contract or order confirmation form is the only warranty offered by Superior Cables Ltd..
CVALIM - The Electric Wire & Cable Company of Israel Ltd. and Cables of Zion-United Works Ltd. have merged under the umbrella of the American Corporation Superior TeleCom Inc. Atlanta, USA. The company name was changed to Superior Cables Ltd. CVALIM is a brandname owned by Superior Cables Ltd.
Fi rm
Is r a e
i al Q u
table of contents
Installation Wires And Cables 3
Underground Power Cables - Low Voltage - 0.6/1kV PVC Insulated Non Armoured Underground Power Cables Low Voltage 0.6/1kV PVC Insulated Armoured Underground Power Cables Low Voltage 0.6/1kV XLPE Insulated Non Armoured Underground Power Cables Low Voltage 0.6/1kV XLPE Insulated Armoured
11
13
18
23
39
Power Cables
A Y 2Y 2X H HX C CW CE S SE
K F FE (F) (FL) R Go HX Y Y 2Y
2
Low Voltage
Thickness of insulation
Catalog Number
Approx. weight
mm2
mm
mm
mm
kg/km
Amperes
831011103 831011104 831011105 831011106 831011107 831012110 831012111 831012112 831012113 831013115 831013117 831013119 831014122 831014125 831014126 831015127 831015128
1x1.13 1x1.38 1x1.78 1x2.25 1x2.76 7x1.35 7x1.70 7x2.14 7x2.52 19x1.78 19x2.14 19x2.52 37x2.03 37x2.25 37x2.53 61x2.25 61x2.52
0.7 0.7 0.8 0.9 0.9 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4
2.6 2.9 3.5 4.2 4.8 6.7 7.5 9.3 10.5 12.5 14.5 17.0 18.5 20.5 23.0 26.0 28.5
15 20 30 50 70 115 170 270 365 500 700 960 1210 1480 1860 2450 3060
STANDARD DELIVERY LENGTHS : Up to 35 mm2 in coils of 100 m, 50 to 300 mm2 in coils of 50 metres. Longer delivery lengths on drums if requested.
Low Voltage
Thickness of insulation
Approx. weight
mm2
mm
mm
mm
kg/km
Amperes
831501103 831501203 831501303 831501403 831501503 831501104 831501204 831501304 831501404 831501504 831501105 831501205 831501305 831501405 831501505 831501106 831501206 831501306 831501406 831501506
4
1x1.0 2x1.0 3x1.0 4x1.0 5x1.0 1x1.5 2x1.5 3x1.5 4x1.5 5x1.5 1x2.5 2x2.5 3x2.5 4x2.5 5x2.5 1x4.0 2x4.0 3x4.0 4x4.0 5x4.0
1x1.13 1x1.13 1x1.13 1x1.13 1x1.13 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x2.25 1x2.25 1x2.25 1x2.25 1x2.25
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8
5.9 9.3 9.7 10.5 11.0 6.2 9.8 10.5 11.0 12.0 6.8 11.0 11.5 12.5 13.5 7.6 12.5 13.0 14.5 16.5
10 100 115 135 155 45 120 135 160 190 60 165 190 230 270 80 225 265 320 380
15 15 15 15 15 18 18 18 18 18 26 26 26 26 26 34 34 34 34 34
Low Voltage
control cables
USE: For indoor installation, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature: 90C Short circuit temperature (5 seconds max.): 250C SPECIFICATION: H.C. circular copper conductors, XLPE insulated, cores twisted together and wrapped with a non hygroscopic tape and PVC sheathed overall.
According to IS 1516 and IEC
60502/1.
designation.
mm2
mm
mm
mm
kg/km
Amperes Amperes
6x1.5 7x1.5 8x1.5 10x1.5 12x1.5 14x1.5 16x1.5 19x1.5 24x1.5 30x1.5 37x1.5
1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
11.5 11.5 12.5 14.0 15.0 15.5 16.5 17.0 20.0 21.5 23.0
180 200 215 270 310 350 400 450 570 700 840
16 15 14 12 12 11 11 10 9 7 8
22 21 19 17 17 16 16 14 12 11 10
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
5
NOTES:
1) If required, a flame retardant construction can be supplied. 2) If required, a 7-wire stranded conductor can be supplied. 3) Any specified number of cores in cable and special delivery lengths can be produced on request.
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper Conductors, XLPE Insulated PVC Sheathed
mm2
mm
mm
mm
kg/km
Amperes Amperes
831931604 831931609 831931614 831931624 831931634 831931644 831931654 831931669 831931694 831931724 831931754
6x2.5 7x2.5 8x2.5 10x2.5 12x2.5 14x2.5 16x2.5 19x2.5 24x2.5 30x2.5 37x2.5
1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
12.5 12.5 13.5 16.0 16.5 17.5 18.5 19.5 22.5 24.0 26.0
240 270 310 380 440 510 580 670 840 1050 1250
21 20 19 17 16 15 14 13 12 11 8
29 28 27 23 22 21 20 19 17 16 13
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Catalog Number
Approx. weight
Low Voltage
control cables
USE: For indoor installation, in cable ducts and in industrial plants or switching stations where mechanical damage is anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature: 90C Short circuit temperature (5 seconds max.): 250C SPECIFICATION: H.C. circular copper conductors, XLPE insulated, cores twisted together and wrapped with a non hygroscopic tape and PVC bedding protected by double steel tape armour and PVC sheathed overall. According to IS 1516 and IEC 60502/1.
Number and diameter of wires in conductor Number of cores and nominal section of conductor
designation.
mm2
mm
mm
mm
kg/km
Amperes Amperes
833941603 833941608 833941613 833941623 833941633 833941643 833941653 833941668 833941693 833941723 833941753
6x1.5 7x1.5 8x1.5 10x1.5 12x1.5 14x1.5 16x1.5 19x1.5 24x1.5 30x1.5 37x1.5
1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
17.0 17.0 18.5 19.5 20.5 21.0 21.5 22.5 25.5 27.0 29.0
420 450 500 560 600 650 720 830 980 1150 1300
16 15 14 12 12 11 11 10 9 7 6
22 21 19 17 17 16 16 14 12 11 10
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
7
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper Conductors, XLPE Insulated, Armoured PVC Sheathed
Number and diameter of wires in conductor Number of cores and nominal section of conductor Max. Current rating at 30C in air Max. Current rating at 20C in ground
mm2
mm
mm
mm
kg/km
Amperes Amperes
833941604 833941609 833941614 833941624 833941634 833941644 833941654 833941669 833941694 833941724 833941754
6x2.5 7x2.5 8x2.5 10x2.5 12x2.5 14x2.5 16x2.5 19x2.5 24x2.5 30x2.5 37x2.5
1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
18.0 18.0 19.5 20.5 21.5 22.5 23.5 24.5 27.0 29.5 32.0
560 580 630 900 750 820 890 1000 1250 1510 1800
21 20 19 17 16 15 14 13 12 11 8
29 28 27 23 22 21 20 19 17 16 13
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Catalog Number
Approx. weight
Low Voltage
control cables
USE: For indoor installation, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Maximum permissible conductor temperature 70C. Short circuit temperature (5 seconds max. 160C) SPECIFICATION: H.C. circular copper conductor, PVC insulated, cores twisted together, lapped or extruded inner covering and PVC sheathed overall. According to IS 1516 and IEC 60502/1. Similar to NYY acc to VDE designation current rating based on VDEO298.
mm2
mm
mm
mm
kg/km
Amperes
831701603 831701608 831701613 831701623 831701633 831701643 831701653 831701668 831701693 831701723 831701753
6x1.5 7x1.5 8x1.5 10x1.5 12x1.5 14x1.5 16x1.5 19x1.5 24x1.5 30x1.5 37x1.5
1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38 1x1.38
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
13.0 13.0 14.0 15.0 16.0 16.0 16.5 17.0 20.0 21.0 22.5
255 275 310 365 410 385 425 490 605 730 875
14.0 13.0 12.0 10.0 10.0 9.5 9.5 8.5 8.0 7.0 6.0
Catalog Number
Approx. weight
500 500 500 500 500 500 500 500 500 500 500
9
Low Voltage
0.6/1 kV Circular Copper Conductor, PVC Insulated PVC Sheathed
Number and diameter of wires in conductor
mm2
mm
mm
mm
kg/km
Amperes
831701604 831701609 831701614 831701624 831701634 831701644 831701654 831701669 831701694 831701724 831701754
6x2.5 7x2.5 8x2.5 10x2.5 12x2.5 14x2.5 16x2.5 19x2.5 24x2.5 30x2.5 37x2.5
1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78 1x1.78
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
15.0 16.0 16.5 18.0 18.0 18.5 19.5 20.0 23.5 25.5 27.0
360 390 435 515 505 575 635 735 920 1135 1365
18.0 17.0 16.0 14.0 13.5 13.0 12.0 11.0 10.0 9.0 7.0
10
Catalog Number
Approx. weight
500 500 500 500 500 500 500 500 500 500 500
Low Voltage
mm2
Approx. weight
mm
mm
mm
kg/km
Amperes
Amperes
CU PVC PVC
831611304 831611305 831611404 831611405 831611406 831611407 831612410 831612411 831612012 831613013 831613015 831613017 831613019 831614022 831614025 831614026 831615027
3x1.5 3x2.5 4x1.5 4x2.5 4x4.0 4x6.0 4x10.0 4x16.0 3x25+16 3x35+16 3x50+25 3x70+35 3x95+50 3x120+70 3x150+70 3x185+95 3x240+120
1 1 1 1 1 1 6 6 6 6 6 12 15 18 18 30 34
0.6 0.7 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2
11.3 13.5 12.0 13.5 15.5 16.5 21.0 24.5 28.0 30.5 35.5 40.0 46.0 51.0 55.0 61.5 69.0
175 230 210 280 380 490 770 1150 1550 2000 2650 3600 4800 6100 7100 9100 12000
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 750 500 400 300 300 250 200
11
NOTES:
1) Any specified number of cores in cable and special delivery lengths can be produced on request. 2) If required a 7 wire stranded conductor can be supplied for 1.5 to 6 3) If required an aluminum round stranded conductor can be supplied for conductors with cross sectional areas 25mm2 and above. mm2
mm2.
Low Voltage
mm2
mm
mm
mm
kg/km
Amperes Amperes
CU PVC PVC
6 6 12 15 18 18 30 34
831655027 3x240+120
NOTE:
1) Special delivery lengths can be produced on request. 2) If required an aluminum stranded shanded shaped conductor can be supplied
12
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper Conductors, PVC Insulated, Double Steel Tape Armoured, PVC Sheathed
mm2
mm
mm
mm
kg/km
Amperes Amperes
NOTE:
1) Any specified number of cores in cable and special delivery lengths can be produced on request. 2) If required a 7 wire stranded conductor can be supplied for 1.5 mm2 to 6 mm2. 3) If required an aluminum round stranded conductor can be supplied for conductors with cross sectional areas 25mm2 and above.
833011304 833011305 833011404 833011405 833011406 833011407 833012410 833012411 833012012 833013013 833013015 833013017 833013019 833014022 833014025 833014026 833015027
3x1.5 3x2.5 4x1.5 4x2.5 4x4.0 4x6.0 4x10.0 4x16.0 3x25+16 3x35+16 3x50+25 3x70+35 3x95+50 3x120+70 3x150+70 3x185+95 3x240+120
1 1 1 1 1 1 6 6 6 6 6 12 15 18 18 30 34
0.6 0.7 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2
13.0 14.0 14.0 15.5 17.5 18.5 23.5 28.0 31.0 33.5 40.0 44.5 51.5 56.0 60.0 66.0 74.0
300 370 330 420 550 660 1150 1600 2100 2500 3700 4700 6200 7500 8800 11000 14000
1000 1000 1000 1000 1000 1000 1000 1000 1000 750 500 400 300 250 200 200 150
13
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Shaped Copper Conductors, PVC Insulated, Double Steel Tape Armoured, PVC Sheathed
mm2
mm
mm
6 6 12 15 18 18 30 34
NOTE:
1) Special delivery lengths can be produced on request. 2) If required an aluminum stranded shanded shaped conductor can be supplied
833505027 3x240+120
14
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper Conductors, PVC Insulated, Steel Wire Armoured, PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
1 1 1 1 1 1 7 7
18 25 18 25 34 44 60 80
26 34 26 34 44 56 75 98
NOTES:
1) Any specified number of cores in cable and special delivery lengths can be produced on request. 2) If required a 7 wire stranded conductor can be supplied for 1.5 mm2 to 6 mm2.
Approx. weight
15
Low Voltage
0.6/1 kV Circular Copper Conductors, PVC Insulated Steel Strip Armoured PVC Sheathed
mm2
mm
mm
mm
833061407 833062410 833062411 833062012 833063013 833063015 833063017 833063019 833064022 833064025 833064026
4x6.0 4x10.0 4x16.0 3x25+16 3x35+16 3x50+25 3x70+35 3x95+50 3x120+70 3x150+70 3x185+95
1 6 6 6 6 6 12 15 18 18 30 34
0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2
19.5 23.5 27.5 30.5 33.0 38.5 43.0 50.0 54.0 58.0 64.5 72.5
900 1150 1600 2100 2450 3300 4250 5700 7000 8100 10100 12900
1000 1000 1000 1000 750 500 400 300 250 200 200 150
NOTE:
1) Any specified number of cores in cable and special delivery lengths can be produced on request. 2) If required an aluminum round stranded conductor can be supplied for conductors with cross sectional areas 25mm2 and above.
833065027 3x240+120
16
Approx. weight
Low Voltage
0.6/1 kV Shaped Copper Conductors, PVC Insulated, Steel Strip Armoured, PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 6 12 15 18 18 30 34
NOTES:
1) Special delivery lengths can be produced on request. 2) If required an aluminum stranded sector shaped conductor can be supplied
833525027 3x240+120
Approx. weight
17
Low Voltage
0.6/1 kV Single Core Circular Copper Conductors, XLPE Insulated PVC Sheated
mm2
mm
mm
CU XLPE PVC
1x10 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300
7 7 7 7 6 12 15 18 18 30 34 34
0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8
9 10 13 14 15 18 19 22 24 27 30 32
180 210 310 410 530 750 970 1270 1550 1950 2560 3050
77 102 139 170 208 265 326 381 438 507 606 697
90 115 149 178 211 259 310 352 396 449 521 587
1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 500
NOTES:
1) Flame retardant construction can be supplied on request. 2) A compacted conductor can be supplied for 50 mm2 and above. 3) If required an aluminum round stranded conductor can be supplied for conductors with cross sectional areas 25mm2 and above.
18
Approx. weight
Low Voltage
mm2
mm
mm
kg/km
Amperes Amperes
CU XLPE PVC
6 6 6 12 15 15 15 30 30
NOTES:
1) Flame retardant construction can be supplied on request. 2) Special delivery lengths can be produced on request.
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Shaped Copper/ Aluminum Conductors, XLPE Insulated PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
AL XLPE PVC
6 6 6 12 15 15 15 30 30
20
Catalog Number
Approx. weight
Low Voltage
mm2
mm
mm
kg/km
Amperes Amperes
CU XLPE PVC
7 7 6 12 15 18 18 30 34
NOTES:
1) Flame retardant construction can be supplied on request. 2) A compacted conductor can be supplied for 50 mm2 and above on request.
831945027 3x240+120
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper/ Aluminum Conductors, XLPE Insulated PVC Sheathed
Number of cores and nominal section of conductor
mm2
mm
mm
kg/km
Amperes Amperes
AL XLPE PVC
6 6 6 12 15 15 15 30 30
841905027 3x240+120
22
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Shaped Copper Conductors, XLPE Insulated Double Steel Tape Armoured PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 6 6 12 15 15 15 30 30
NOTES:
1) Flame retardant construction can be supplied on request. 2) Special delivery lengths can be produced on request. 3) If required an aluminum stranded shanded shaped conductor can be supplied
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Circular Copper Conductors, XLPE Insulated, Double Steel Tape Armoured PVC Sheathed
designation.
mm2
mm
mm
kg/km
Amperes Amperes
6 6 6 12 15 18 18 30 34
833915027 3x240+120
24
Catalog Number
Approx. weight
Low Voltage
0.6/1 kV Shaped Copper Conductors, XLPE Insulated Steel Strip Armoured PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 6 6 12 15 15 15 30 30
NOTES:
1) Flame retardant construction can be supplied on request. 2) Special delivery lengths can be produced on request. 3) If required an aluminum stranded shanded shaped conductor can be supplied
Catalog Number
Approx. weight
25
Low Voltage
0.6/1 kV Circular Copper Conductors, XLPE Insulated Steel Strip Armoured PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
7 7 6 12 15 18 18 30 34
833955027 3x240+120
26
Catalog Number
Approx. weight
3.6/6 kV; 6/10 kV Circular Stranded Copper or Aluminum Conductors, XLPE Insulated PVC or PE Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 18 18 30 34 34
21 23 25 26 28 29 32 34
NOTES:
1) A special flame retardant construction can be supplied upon request. 2) A special moisture barrier construction can be supplied upon request. (type of cable N2XS(F)2Y)
Catalog Number
Approx. weight
27
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 15 15 30 30 30 53
24 26 28 29 31 33 36 38 43
6 12 15 18 18 30 34 34 53
24 26 28 29 31 33 36 38 43
832944122 1x120/16 832944125 1x150/25 832944126 1x185/25 832945127 1x240/25 832945128 1x300/25 832945129 1x400/35
28
Catalog Number
Approx. weight
3.6/6 kV; 6/10 kV Circular Stranded Copper or Aluminum Conductors, XLPE Insulated PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 18 18 30 34
44 48 51 55 59 63 68
NOTE:
A special flame retardant construction can be supplied upon request.
832925327
Approx. weight
Catalog Number
29
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 15 15 30 30
49 53 57 61 66 70 76
6 12 15 18 18 30 34
49 53 57 61 66 70 76
30
Catalog Number
Approx. weight
3.6/6 kV; 6/10kV Circular Stranded Copper or Aluminum Conductors, XLPE Insulated Steel Strip Armoured PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
3.6/6 kV CU, XLPE, Individual CU Screening, PVC Bedding Armoured and PVC
6 12 15 18 18 30 34
47 51 54 58 63 66 72
NOTE:
A special flame retardant construction can be supplied upon request.
834928327
Catalog Number
Approx. weight
31
mm2
mm
mm
kg/km
Amperes Amperes
6/10 kV AL, XLPE, Individual CU Screening PVC Bedding Armoured and PVC
6 12 15 15 15 30 30
52 56 61 64 69 73 80
6/10 kV CU, XLPE, Individual CU Screening, PVC Bedding Armoured and PVC
6 12 15 18 18 30 34
52 56 61 64 69 73 80
32
Catalog Number
Approx. weight
12/20 kV; 18/30 kV; 26/45 kV Circular Stranded Copper or Aluminum Conductors, XLPE Insulated PVC or PE Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 18 18 30 34 34 53
28 29 31 33 34 36 39 41 47
832754125 1x150/25 832754126 1x185/25 832755127 1x240/25 832755128 1x300/25 832755129 1x400/25
Catalog Number
Approx. weight
mm2
mm
mm
kg/km
Amperes Amperes
832763115 832763117 832763119 832764122 832764125 832764126 832765127 832765128 832765129 832765130
1x50/16 1x70/16 1x95/16 1x120/16 1x150/25 1x185/25 1x240/25 1x300/25 1x400/35 1x500/50
6 12 15 18 18 30 34 34 53 53
8 8 8 8 8 8 8 8 8 8
33 35 37 38 40 42 44 47 52 54
1400 1650 2000 2250 2700 3100 3750 4400 5500 6450
241 299 362 416 469 536 630 717 823 929
226 276 329 373 415 468 541 608 684 762
15 18 18 30 34 34 53 53
43 45 46 48 51 53 58 62
34
Catalog Number
Approx. weight
1000 1000 1000 1000 1000 500 500 500 500 500
mm2
mm
mm
kg/km
Amperes Amperes
6 12 15 15 15 30 30 30 53
28 29 31 33 34 36 39 41 47
842763115 842763117 842763119 842764122 842764125 842764126 842765127 842765128 842765129 842765130
1x50/16 1x70/16 1x95/16 1x120/16 1x150/25 1x185/25 1x240/25 1x300/25 1x400/35 1x500/50
6 12 15 15 15 30 30 30 53 53
8 8 8 8 8 8 8 8 8 8
33 35 37 38 40 42 44 47 52 54
850 1200 1400 1500 1850 1900 2200 2500 2850 3300
187 232 281 323 365 418 494 564 654 747
175 214 256 290 324 366 426 479 545 614
1000 1000 1000 1000 1000 1000 1000 500 500 500
35
Catalog Number
Approx. weight
mm2
mm
mm
kg/km
Amperes Amperes
15 18 18 30 34 34 53 53
43 45 46 48 51 53 58 62
36
Catalog Number
Approx. weight
12/20 kV; 18/30 kV Circular Stranded Copper Conductors, XLPE Insulated Steel Strip Armoured PVC Sheathed
mm2
mm
mm
kg/km
Amperes Amperes
12/20 kV CU, XLPE, Individual CU Screening, PVC Bedding, Armoured and PVC NOTES:
1) A special flame retardant construction can be supplied upon request. 2) Cables protected by double steel tapes (type N2XSEYBY) are also available upon request. 3) It required an aluminum round stranded cunductor can be supplied
6 12 15 18 18 30 34
64 68 72 76 80 85 90
Catalog Number
Approx. weight
37
mm2
mm
mm
kg/km
Amperes Amperes
18/30 kV CU, XLPE, Individual CU Screening, PVC Bedding, Armoured and PVC
6 12 15 18 18 30 34
8 8 8 8 8 8 8
78 82 85 89 92 96 105
38
Catalog Number
Approx. weight
40/69kV (72.5kV), 64/110 (123kV), 76/132 (145kV), 87/150 (170kV) Single core, Copper conductor XLPE insulated, Lead sheath screen, PE outer sheathed
Type 2X(F)K2Y
CHARACTERISTICS: Max. continuous operating conductor temperature: 90C Max. conductor temperature during short circuit: 250C Max. one second short-circuit conductor current density 143.2 A/mm2 (acc to IEC 949) Initial temperature at short circuit)in metallic screen: 80C Final temperature at short circuit in metallic screen: 210C Max. one second short circuitn metallic screen current density: 24.3A/mm2 (acc to IEC949) CONSTRUCTION: Conductor: Stranded copper wires circular compacted or MILLIKEN, construction (segmental stranded for 800sq.mm and above conductor cross section area). Insulation: A triple extrusion of a thermosetting semiconducting material as a conductor screen, a XLPE insulating layer and a thermosetting semiconducting layer with an overlapped semiconducting swelling tape as an insulation screen. Metallic screen: An extruded lead alloy vibration resistant to provide an electrical screening, a radial water
40/69kV (72.5kV) Max discharge at 60kV: 5pC Impulse Valtafe Level 325kV
Insulation thickness Over all diameter (approx) mm Conductor Non cross section Diam over the insulation Lead sectional area Diam of cond. PE outer sheath thickness
mm2
mm
mm
mm
mm
mm2
mm
kg/km
50 54 60 63 66 71 77 81 87
proofing, an active conductor for the capacitive and homopolar short-circuit current and a contribution for a mechanical protection. Note: A special design for metallic screen to be suitable to carry higher fault currents can be perform and shall consist of
copper wires and a lead alloy sheath. Outer sheath: An extruded layer of PE with a semiconducting graphite coating to allow dielectric tests on sheath after installation. Tests of cables: According to IEC 840.
39
Diam of cond.
mm2
mm
mm
mm
mm
mm2
mm
kg/km
65 70 71 76 77 86 91 95
76/132kV (145kV) Max discharge at 114kV: 5pC Impulse Voltage Level 650kV
18 18 18 18 18 18 17.5 17.5
71 76 77 81 86 91 96 100
87/150kV (170kV) Max discharge at 130kV: 5pC Impulse Voltage Level 750kV
83 85 91 95 103 108
40
64/110 kV (123 kV) Single core, copper conductor XLPE insulated, Al-PE outer sheathed
Type 2XS(FL)2Y
CHARACTERISTICS: Max. continuous operating conductor temperature.: 90C Max. conductor temperatureF during short-circuit: 250C Max. one second short-circuito conductor current density: 143.2A/mm2 Initial temperature at short circuit in metallic screen: 80C Final temperature at short circuit in metallic screen: 210C Max. one second short circuith metallic screen current density: 133A/mm2 (acc to IEC949) CONSTRUCTION: Conductor: stranded copper wires circular compacted or Milliken construction (segmental stranded for 800sq.mm and above conductor cross section area). Insulation: A triple extrusion of thermosetting semiconducting material as a conductor screen, a XLPE insulating layer and a thermosetting semiconducting layer with an overlapped semiconducting swelling tape as an insulation screen. Metallic screen: Copper wires and copper tape embedded in a layer of swelling tape to form a longitudinal barrier against water.
Note: A larger metallic screen cross section area than indicated in the attached table can be designed to assure the cable usage in a system with higher fault currents. Outer sheath: Sheath consisting of a coated copolymer aluminum laminated tape bonded to a
black PE extruded layer to assure a radial water barrier and a high mechanical protection. A semiconducting graphite coating shall be applied on the PE sheath to allow diellectric tests on sheath after installation. Test of cables: According to IEC 840.
64/110kV (123kV) Max discharge at 96kV: 5pC Impulse Voltage Level 550kV
Insulation thickness Screen geometrical cross section Diam of conductor Over all diameter (approx)
mm2
mm2
mm
mm
mm
mm
mm
kg/km
35 35 35 35 35 50
76 79 82 87 92 98
76 79 82 87 92 98
Insulation thickness
Diam of conductor
mm2
mm2
mm
mm
mm
mm
kg/km
76/132kV (145kV) Max discharge at 114kV: 5pC Impulse Voltage Level 650kV
35 35 35 35 35 35 35 50
18 18 18 18 18 18 17.5 17.5
71 73 76 80 85 89 93 100
42
64/110kV (123kV) Single core, Copper conductor XLPE insulated, Lead sheath screen PE outer sheathed
Type 2X(F)K2Y
CHARACTERISTICS: Max. continuous operating conductor temperature: 90C Max. conductor temperature during short circuit: 250C Max. one second short-circuit conductor current density 143.2 A/mm2 (acc to IEC 949) Initial temperature at short circuit' in metallic screen: 80C Final temperature at short circuit in metallic screen: 210C Max. one second short circuitj metallic screen current density: 24.3A/mm2 (acc to IEC949) Max. discharge at 1.5Uo = (96kV) 5pC Impulse voltage level 550kV CONSTRUCTION: Conductor: Stranded copper wires circular compacted or MILLIKEN, construction (segmental stranded for 800sq.mm and above conductor cross section area). Insulation: A triple extrusion of a thermosetting semiconducting material as a conductor screen, a XLPE insulating layer and a thermosetting semiconducting layer
with an overlapped semiconducting swelling tape as an insulation screen. Metallic screen: An extruded lead alloy vibration resistant to provide an electrical screening, a radial water proofing, an active conductor for the capacitive and homopolar short-circuit current and a contribution for a mechanical protection.
Note: A special design for metallic screen to be suitable to carry higher fault currents can be perform and shall consist of copper wires and a lead alloy sheath. Outer sheath: An extruded layer of PE with a semiconducting graphite coating to allow dielectric tests on sheath after installation. Tests of cables: According to IEC 840.
Insulation thickness
Diam of cond.
mm2
mm
mm
mm
mm
mm2
mm
mm
kg/km
65 70 71 76 77 86 91 95
76/132kV (145kV) Single core, Copper conductor XLPE insulated, Lead sheath screen PE outer sheathed
Type 2X(F)K2Y
CHARACTERISTICS: Max. continuous operating conductor temperature: 90C Max. conductor temperature during) short circuit: 250C Max. one second short-circuit conductor current density 143.2 A/mm2 (acc to IEC 949) Initial temperature at short circuit' in metallic screen: 80C Final temperature at short circuit in metallic screen: 210C Max. one second short circuitj metallic screen current density: 24.3A/mm2 (acc to IEC949) Max. discharge at 1.5Uo = (114kV) 5pC Impulse voltage level 650kV CONSTRUCTION: Conductor: Stranded copper wires circular compacted or MILLIKEN, construction (segmental stranded for 800sq.mm and above conductor cross section area). Insulation: A triple extrusion of a thermosetting semiconducting material as a conductor screen, a XLPE insulating layer and a thermosetting semiconducting layer
44
with an overlapped semiconducting swelling tape as an insulation screen. Metallic screen: An extruded lead alloy vibration resistant to provide an electrical screening, a radial water proofing, an active conductor for the capacitive and homopolar short-circuit current and a contribution for a mechanical protection.
Note: A special design for metallic screen to be suitable to carry higher fault currents can be perform and shall consist of copper wires and a lead alloy sheath. Outer sheath: An extruded layer of PE with a semiconducting graphite coating to allow dielectric tests on sheath after installation. Tests of cables: According to IEC 840.
Insulation thickness
Diam of cond.
mm2
mm
mm
mm
mm
mm2
mm
kg/km
18 18 18 18 18 18 17.5 17.5
71 76 77 81 86 91 96 100
87/150kV (170kV) Single core, Copper conductor XLPE insulated, Lead sheath screen PE outer sheathed
Type 2X(F)K2Y
CHARACTERISTICS: Max. continuous operating conductor temperature: 90C Max. conductor temperature during) short circuit: 250C Max. one second short-circuit conductor current density 143.2 A/mm2 (acc to IEC 949) Initial temperature at short circuit' in metallic screen: 80C Final temperature at short circuit in metallic screen: 210C Max. one second short circuitj metallic screen current density: 24.3A/mm2 (acc to IEC949) Max. discharge at 1.5Uo = (130kV) 5pC Impulse voltage level 750kV CONSTRUCTION: Conductor: Stranded copper wires circular compacted or MILLIKEN, construction (segmental stranded for 800sq.mm and above conductor cross section area). Insulation: A triple extrusion of a thermosetting semiconducting material as a conductor screen, a XLPE insulating layer and a thermosetting semiconducting layer
with an overlapped semiconducting swelling tape as an insulation screen. Metallic screen: An extruded lead alloy vibration resistant to provide an electrical screening, a radial water proofing, an active conductor for the capacitive and homopolar short-circuit current and a contribution for a mechanical protection.
Note: A special design for metallic screen to be suitable to carry higher fault currents can be perform and shall consist of copper wires and a lead alloy sheath. Outer sheath: An extruded layer of PE with a semiconducting graphite coating to allow dielectric tests on sheath after installation. Tests of cables: According to IEC 840.
Insulation thickness
Diam of cond.
mm2
mm
mm
mm
mm
mm2
mm
kg/km
83 85 91 95 103 108
45