Installation Manual

ControlLogix Flash Update


Introduction
Use this document to install a ControlLogix flash software and/or firmware update. You may need to install an update to: a. take advantage of a new feature b. upgrade your RSLogix 5000 software c. update the firmware of a replacement module when the firmware on the replacement differs from that of the installed module In addition, when you work with our Technical Support -- PLC/Logix Hardware Group, they may sometimes recommend an update. Attention: Stop the operation of your application and shut down production
before you begin to install an update.

Refer to the Compatibility Matrix

As you install updates, refer to the compatibility matrix available at the following URL: http://www.ab.com/support/products/controllogix.html This matrix lists recommended revision levels for combinations of ControlLogix products. Important: Be aware that this matrix is extremely dynamic and is updated very frequently. To ensure that you have the latest revision level information, be certain to check the listed URL for updates to the matrix each time you install a flash update. For your convenience, we include an example of this matrix (partial, not updated) below. Important: You must maintain identical software and firmware revision levels on the controllers. When you upgrade your RSLogix 5000 software, you must always flash the firmware of your system processor, and, for full system functionality, we recommend that you also update your ControlLogix communication modules.

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

Install an Update

The following diagram illustrates the steps you should follow to install an update. The remainder of this document describes each step and provides references to other publications for more detail. To install an update, you need, at minimum: a 90MHz Pentium processor 32MB RAM Microsoft Windows NT, Service Pack 4 RSLogix 5000 RSLinx or RSLinx Lite ControlFlash (for firmware updates) RSNetWorx (for systems that use ControlNet networking)
Refer to the documentation for each software package for specific requirements. You may also want to gather the following manuals for reference:

Determine what to update see page 3

Back up your program files see page 4

3 4

Update the software see page 5


Update the firmware see page 6

ControlFlash Firmware Upgrade Kit User Manual, publication 1756-6.5.6 RSNetworx for ControlNet Getting Results Guide, publication 9399-CNETGR RSLogix 5000 Getting Results Guide, publication 9399-RLD300GR RSLinx Getting Results Guide, publication 9399-LINXGR

Reload program files see page 8

Plan for future updates see page 8

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

Determine what to update

Currently, you need to install particular revisions of firmware to operate with particular revisions of software, i.e., the firmware and software revision levels in your ControlLogix system must be compatible, as listed in the compatibility matrix on page 1. To maintain compatible revision levels more easily, we strongly encourage you to develop and maintain a list of the software and firmware revision levels in your system. To create this list initially, you can use the Module Info function in RSLogix 5000 software. See the following section, Determine the Current Revision Levels of Your Devices for information about how to do this. To determine which products you need to update, follow these steps: 1. Determine the current software and firmware revision levels of the devices in your system. 2. Compare the revision levels of the devices in your system with those listed in the compatibility matrix on page 1.

Determine what to update

Determine the Current Revision Levels of Your Devices


You can use the Module Info function under Module Properties in RSLogix 5000 software to determine the current firmware revision level of a module in the I/O configuration folder. To do this: Important: You need to be on a computer with RSLinx, RSLogix 5000, and a
communication card installed to attach to a device.

1. Go on line with the controller. 2. From the I/O Configuration folder, select the module whose revision level you want to determine. 3. Right-click on the module to select Properties. 4. Select the Module Info tab to display the catalog number, serial number, and current firmware revision level of the module. 5. Repeat steps 2 through 4 for each module whose revision level you want to determine. To determine the current firmware revision level of a module that is used in the system but is not in the I/O configuration folder, do the following: 1. In RSLinx release 2.20.107 or later, browse to the module whose revision level you want to determine. If you are using an earlier release of RSLinx software, skip to step 3.

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

2. Right-click to select Device Properties. The software displays the modules revision information. Skip steps 3 and 4 in this procedure. 3. In ControlLogix Gateway software (1756-GTWY), browse to the module whose revision level you want to determine. 4. Double-click on the module. The software displays the modules revison information in the Product Information dialog box..

Compare Revision Levels


Compare the revision level reported by the software in step 1, Determine what to update, with that listed in the compatibility matrix on page 1. If the revision level is not identical, then you should install an update for that module. Important: You must maintain identical software and firmware revision levels on the controllers. When you upgrade your RSLogix 5000 software, you must always flash the firmware of your system processor, and, for full system functionality, we recommend that you also update your ControlLogix communication modules. Important: You must back up your RSLogix 5000 application program and your RSNetWorx configuration file as described in step 2, Back up the program files, before you install a firmware update.

Back up the program files

You should back up the program files because, once you install the firmware update, you will no longer be able to access these program files. To back up your RSNetWorx configuration file: 1. Open RSNetWorx software. 2. Save the configuration file for the system. To back up your RSLogix 5000 application program: 1. Open RSLogix 5000 software. 2. Go on line to the 1756-family controller.

Back up the program files

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

3. Save the application program. If the software displays a message that reports a difference between the controller file and the file that is stored on your computers hard disk, then you need to upload or download the program file that you want to save, as appropriate.

Update the software

The following sections describe how to update your software.

Update the software

Update RSLogix 5000 Software


1. Close all applications on your computer. 2. Run the setup program from the RSLogix 5000 CD. 3. The installation program informs you that a previous version of RSLogix 5000 software is installed on your computer. Click Yes to uninstall the previous version of RSLogix 5000. 4. Click Yes when prompted to preserve the current RSLogix 5000 configuration. 5. Click Yes to remove shared files. 6. Read and accept the software license agreement as prompted and enter appropriate registration information as prompted. 7. Complete the installation and setup process. For specific installation instructions, refer to the Getting Results with RSLogix 5000 Guide, publication number 9399-RLD300GR

Update ControlFlash Software


Insert the ControlFlash disk and run setup. The install prompts you for additional disks as needed. Refer to the ControlFlash Firmware Upgrade Kit Users Manual, publication 1756-6.5.6, for detailed instructions about how to use the software program. Important: If a previous version of ControlFlash is already installed, we recommend that you still install the new revision of ControlFlash to load the latest firmware update files and ControlFlash drivers. You do not need to uninstall the previous revision of ControlFlash.

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

Update RSLinx Software


Insert the RSLinx CD that came with your RSLogix 5000 software and run setup. Refer to the RSLinx Getting Results Guide, publication number 9399-LINXGR, for detailed instructions about how to use the software program.

Update RSNetWorx for ControlNet Software


Insert the RSNetWorx for ControlNet CD and run setup. Refer to the RSNetWorx for ControlNet Getting Results Guide, publication number 9399-CNETGR, for detailed instructions about how to use the software program.

Update the firmware

Update the firmware

Use ControlFlash software to install any necessary controller, communication module, and/or I/O firmware updates. For important additional guidelines, refer to the Update the ControlLogix ControlNet Communication Module section on page 7 as you install firmware updates to 1756-CNB and -CNBR communication modules. Important: If you need to update firmware, we recommend that you update the controller firmware first. We suggest that you next install updates to communication modules, then motion, and finally I/O modules, as necessary per the decisions you made in step 1, Determine what to update. Important: You need to be on a computer with RSLinx, ControlFlash, and a communication card installed to attach to a device. 1. Start the ControlFlash software program. 2. Select the catalog number of the device to update. RSLinx opens. 3. Use the RSWho Browse utility to select the device to update. 4. Click OK. 5. The Firmware Revision screen displays the catalog number, serial number, and current revision of the device.

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

6. Select the firmware revision to install (refer to step 1, Determine what to update, for help in selecting the appropriate revision level). 7. If you are installing a later revision level and that firmware revision is not displayed, verify that you have installed the appropriate revision of ControlFlash on the computer. You should have installed the revision of ControlFlash that you received along with your RSLogix 5000 software or the one that you received from the Technical Support -- PLC/Logix Hardware Group. If you have installed the appropriate revision of ControlFlash and the appropriate firmware revision is not displayed, contact the Technical Support -- PLC/Logix Hardware Group at 440.646.6800. 8. If you are installing an earlier revision level, click Show All to determine if this revision level is installed on the computer. 9. Click Finish to complete installation of the update. Important: Do not break communication with the module that you are updating until the update is completed and you see a message reporting that the installation is complete. If you receive an error message, install the update again. If the module no longer communicates properly, send the device to Technical Repair. For assistance with the flash process, contact the Technical Support -- PLC/Logix Hardware Group at 440.646.6800.

Update the ControlLogix ControlNet Communication Module


Keep the following guidelines in mind when you install an update to a 1756-CNB or -CNBR Communication Module.

When you upgrade an earlier series 1756-CNB or -CNBR module to a later series, you must modify the module profile under the I/O Configuration tree in RSLogix 5000 software. To do this, you need to delete the child modules in the 1756-CNBR profile and reconfigure them after you modify the 1756-CNBR profile. If you plan to upgrade to series D hardware, you must replace the 1756-CNB/R module (e.g., you cannot install a firmware update to upgrade from series B to series D). To ensure system integrity, all systems should include either series B, revision 2.24 or later, series D, revision 5.21, or later 1756-CNB/ R modules. These modules alone are compliant with the ControlNet International Specification. Therefore, you should install updates to all series A, revision 1.19 and series B, revision 2.10 modules to upgrade to series B, revision 2.24.

Publication 1756-IN111A-EN-P - August 2000

ControlLogix Flash Update

If your ControlLogix system includes any series D 1756-CNB/R modules on a ControlNet network, you must use RSNetworx for ControlNet revision 2.22.18 or later to set up the network.

Reload program files

To reload your program files: 1. Download the RSLogix 5000 .ACD file to the controller.

Reload program files

Important: When you open an RSLogix 5000 program that was created with a previous revision of software, RSLogix 5000 displays a message that requires you to convert the project to the latest revision. If the revision of RSLogix 5000 installed on your computer is not compatible with the revision of firmware in the 1756-L1 module, RSLogix 5000 displays a message to notify you of the discrepancy when you attempt to download the program to the controller. If this occurs, you need to install an update to the controller. See page 6 for information about installing a controller firmware update. Important: Once you update RSLogix 5000 software (and the .ACD file), you cannot view this file with an older revision of RSLogix 5000 software. 2. Run RSNetWorx and open the configuration file that you backed up in step 2. RSNetWorx prompts you to convert the RSNetWorx .xc file to the new revision. 3. Convert the file. 4. Select Enable Edits and then go on line. 5. Save the file. You have successfully re-established scheduled connections to the system.

Plan for future updates

Plan for future updates

As discussed on page 3, to maintain compatible revision levels more easily, we strongly encourage you to develop and maintain a list of the software and firmware revision levels in your system. Do not forget to update this list as you install updates using this document.