Vous êtes sur la page 1sur 7

TOTAL VOLUME FOR CITY GATE PRMS SECTION

PIPE SEGMENT / EQUIPMENT


LENGTH(MM) DIAMETER(IN) VOL (M3)
S304-18"-C1
11069
18
1.81723341
S305-6"-B1
5516
6
0.10061994
S304-16"-C1
9398
16
1.21908144
PRMS SKID
10" LINE
5969
10
0.30245369
14" LINE
2184
14
0.21690323
FILTER SEPARATOR
3330
27.55905512 1.28153418
TOTAL
1.81890002
18" LINE TO SCRAPPER
22714
18
3.72903059
LAUNCHER
3" LINE RECIEVER LINE FOR
6693
3
0.03052254
SCRAPPER LAUNCHER
PURGE LINE
46758
2
0.09477051
TOTAL

VOL (M3)
3.168304144

5.456700057

3.89286688

12.51787108

TOTAL VOLUME FOR CITY GATE VENT / BLOW DOWN HEADER SECTION
PIPE SEGMENT / EQUIPMENT
LENGTH(MM) DIAMETER(IN) VOL (M3)
VOL (M3)
6" VENT LINE S305-6"-A1
92879
6
1.69424942
2" BLOW DOWN LINE S407-2"-A1
8283
2
0.01678823
3.765658328
VENT SCRUBBER
2508
39.84251969 2.01733693
TOTAL
SPEED=6.6 FT/S
SECTION

PRESSURE
(PSIG)

INJECTION
RATE(CFM)

Fitting
Size(IN)

CITY GATE PRMS SECTION


CITY GATE VENT SECTION

20
20

720
720

2"
2"

PRESSURE
(PSIG)

INJECTION
RATE(CFM)

Fitting
Size(IN)

PURGE
PURGE
VOLUME(FT3) TIME (MIN)
442.0644863
132.9829812

0.61397845
0.18469859

SPEED= 3.5 FT/S


SECTION

PURGE
PURGE
VOLUME(FT3) TIME (MIN)

CITY GATE PRMS SECTION


7
370
2"
442.0644863 1.19476888
CITY GATE VENT SECTION
7
370
2"
132.9829812 2.78231091
NOTE PIPE OUTSIDE DIAMETER HAS BEEN USED TO ENSURE, SUFFICIENT NITROGEN VOLUMES ARE AVAILABLE

TOTAL VOLUME FOR UNICEM PRMS SECTION


PIPE SEGMENT / EQUIPMENT
LENGTH(MM)
DIAMETER(IN)
S904-18"-B1
15,985.00
18.00
S904-12"-B1
807.00
12.00
S304-16"-C1
16.00
PRMS SKID
8" LINE
3,467.00
8.00
14" LINE
1,790.00
14.00
FILTER SEPARATOR
3,330.00
27.56
TOTAL
18" LINE TO UNICEM PLANT

21,128.00

18.00

PURGE LINE

28,781.00

2.00

TOTAL VOLUME FOR CITY GATE VENT HEADER SECTION


PIPE SEGMENT / EQUIPMENT
LENGTH(MM)
DIAMETER(IN)
6" VENT LINE S906-6"-A1
26,781.00
6.00
2" BLOW DOWN LINE S407-2"-A1
61,011.00
2.00
VENT SCRUBBER
5,478.00
39.84
SPEED=6.6 FT/S
SECTION

PRESSURE
(PSIG)

UNICEM PRMS SECTION


UNICEM VENT/ BLOW DOWN
SECTION

INJECTION
RATE(CFM)

20.00

720.00

20.00

720.00

SPEED= 3.5 FT/S


SECTION
UNICEM PRMS SECTION
UNICEM VENT/ BLOW DOWN
SECTION

PRESSURE
(PSIG)

INJECTION
RATE(CFM)

370

370

NOTE PIPE OUTSIDE DIAMETER HAS BEEN USED TO ENSURE, SUFFICIENT NITROGEN VOLUM

MS SECTION
VOL (M3)
2.62
0.06
0.11
0.18
1.28
1.59
3.47
0.06
TOTAL

HEADER SECTION
VOL (M3)
0.49
0.12
4.41
TOTAL

VOL (M3)
2.71

4.76

3.56
11.03

VOL (M3)
5.07

2"

389.69

PURGE
TIME
(MIN)
0.54

2"

179.00

0.25

Fitting
Size(IN)

PURGE
VOLUME(FT3)

Fitting Size(IN)

PURGE
VOLUME(FT3)

2"

389.6850833

PURGE
TIME
(MIN)
1.0532

2"

178.9979487

2.06706

, SUFFICIENT NITROGEN VOLUMES ARE AVAILABLE

PIPE LENGTH
PIPE DIAMETER
3
PIPE VOL (M )

107000
18
17566.53489

PIPE VOL (Ft )

620356.3825
3

PIPE FITTINGS (Ft )

6203.563825

626559.9463

PURGE VOLUME (Ft )

939839.9195

SECTION

PRESSURE
(PSIG)

UKANAFUN-CITY GATE PIPE


LINE

20

TOTAL PIPE VOL (Ft )

INJECTION
Fitting
RATE(CFM) Size(IN)
720

2"

PURGE
3
VOLUME(FT )
939839.9195

TO ENSURE FLOW RATE AT VENT IS THE SAME, THE PIPE NEEDS TO BE CONNECTED TO A 2"
NOTE PIPE OUTSIDE DIAMETER HAS BEEN USED TO ENSURE, SUFFICIENT NITROGEN VOLUME

PURGE TIME
(HR)
21.75555369

CONNECTED TO A 2" VENT FITTING


NT NITROGEN VOLUMES ARE AVAILABLE

PIPE LENGTH
PIPE DIAMETER
3
PIPE VOL (M )

21000
18
3447.637688

PIPE VOL (Ft )

121752.1872
3

PIPE FITTINGS (Ft )

1217.521872

122969.7091

PURGE VOLUME (Ft )

184454.5636

SECTION

PRESSURE
(PSIG)

UKANAFUN-CITY GATE
PIPE LINE

20

TOTAL PIPE VOL (Ft )

INJECTION Fitting
RATE(CFM) Size(IN)
720

2"

PURGE
VOLUME(FT3)
184454.5636

TO ENSURE FLOW RATE AT VENT IS THE SAME, THE PIPE NEEDS TO BE CONNECTED TO A 2"
NOTE PIPE OUTSIDE DIAMETER HAS BEEN USED TO ENSURE, SUFFICIENT NITROGEN VOLUME

PURGE
TIME (HR)
4.26978157

BE CONNECTED TO A 2" VENT FITTING


IENT NITROGEN VOLUMES ARE AVAILABLE

Vous aimerez peut-être aussi