Fiber optic cable is a bounded media that generates signals by transmitting photons (light) through very thin optical fibers
A cable may house one or more fibers
For network applications typically at least 2
fibers one for sending data and the other for receiving data
Fiber optic cable is used in a wide variety of telecommunications and industrial environments
Although this set of slides deals with many of the general properties of fiber, the focus is on its use for network applications in commercial buildings
Fiber Advantages
Fiber optic cable offers several advantages compared to wired-based media (e.g. UTP, STP, ScTP, coax)
Potential for much greater bandwidth than TP Lower attenuation rate than TP allowing for longer cable runs Attenuation rate does not increase when signal frequency increases
With TP, increasing frequency causes increased
attenuation
Smaller cable diameter than comparable UTP cable (about 15% smaller) so it can be installed in smaller areas Improved personal and equipment safety
E.g. Does not transmit electricity if struck by lightening
Fiber Disadvantages
signals where the fiber cable connects to network devices (e.g. switches, routers, PCs)
Optical cable is often made up of more than one optical fiber but regardless of the number of fibers in the bundle there are two additional components
1. 2.
Strengthening materials Provides crush resistance and minimizes pressure on the fibers when cable is pulled during installation Typically made of strands of Kevlar - aramid is the generic name for this material
Cable jacket Outside layer protecting against abrasion, oil, solvents, etc. Usually defines the cable's duty and flammability rating
Heavy-duty cables have thicker, tougher jackets Jacket material must meet building code flammability
standards
As photons travel along the optical fiber they reflect off the interface between the core and the cladding
This principle is called total internal reflection Internal reflection since the photons are retained inside the core through reflection Total because if everything works properly, virtually all of the photons will reach the end of the cable
10
Importance Of Angles
If the photons strike the core/cladding interface at too sharp of an angle, the photons are absorbed into the cladding (blue path) rather than being retained in the core as they reflected back and forth off of the interface (green path)
11
Modes
The angle at which a light ray is injected into the optical cable determines the exact path the light will take to the end of the cable
This path is referred to as the light rays mode An optical fiber can have from one mode to tens of thousands of modes depending upon the cores diameter
The smaller the core, the few potential modes
12
Mode Types
These are some of the most commonly used multimode and single mode fiber core diameters
m is the symbol for micron 1 millionth of a meter 1 thousandth of a millimeter A human hair has a diameter of about 100 microns
14
15
arrive at the end of the cable at the same time if originally sent at the same time? Explain why!
16
Photons in a single mode fiber all follow the same path from signal to signal so there is no chance of photons overtaking each other due to mode differences regardless of cable length
17
18
Dispersion
Modal dispersion
2.
Chromatic dispersion
Light is made up of different colours Each colour has a unique wavelength Different wavelengths travel at different speeds Refining the transmitters wavelength range reduces chromatic dispersion and increases bandwidth potential
19
Chromatic Dispersion
Over distance, shorter wavelengths travel faster and begin to overtake the longer and slower wavelengths of the previously sent signal
Overlapping signals become unreadable
20
On multimode fiber, both modal and chromatic dispersion are factors that have to be taken into account
On single mode, only chromatic dispersion must be factored in
Why! . Only one mode
21
Cable length Wavelength range of the light transmitter Fiber core diameter Numerical aperture and Acceptance angle
Various industry standards specify the parameters for fiber networks to ensure appropriate performance is achieved
These standards will be covered later in this
course
22
For both modal and chromatic dispersion, the issue is the leading part of a signal catching up to the trailing part of the previously sent signal
The longer the cable run, the greater the chances that trailing signals will overlap signals sent earlier (more time to catch up) For longer cable runs, the time between each transmission signal must be increased
Results in reduced bandwidth
23
Type of light transmitter being used is a key factor for chromatic dispersion
Effects of chromatic dispersion decrease as the wavelength range of the light transmitter is reduced
Laser sources can provide smaller wavelength ranges than LED light sources which is one reason why laser technology is used in higher bandwidth fiber applications
24
25
Numerical aperture (NA) measures the light gathering ability of the fiber The angle at which light enters the fiber core determines whether or not the light will propagate (i.e. travel) along the fiber or be absorbed into the cladding
Acceptance angle is the term used to identify
the maximum angle at which light entering the core will be propagated
26
Photons entering outside the acceptance angle are absorbed into the cladding (e.g. red lines) Photons entering within the acceptance angle are propagated along the fibers core (e.g. blue lines)
27
The Numerical Aperture (NA) for a fiber will be a value between 0 and 1
0 means the fiber has no light gathering ability 1 means the fiber accepts and propagates all
light directed toward it Actual NA values will be a decimal number between 0 and 1
28
High NA (close to 1)
Easier to inject light into the fiber Lower bandwidth potential since modal
dispersion is increased
Low NA (close to 0)
More difficult to inject light Makes splicing fiber cables more difficult Higher bandwidth potential since modal
dispersion is reduced
29
In addition to multimode and single mode, fiber cable has two multimode subclassifications based on a property referred to as index
1. 2.
The main difference is related to how they are designed to refract (bend) light signals
30
31
Index of refraction is lower toward the outside of the core and progressively increases toward the center of the core
As light moves away from the center of the core, it is bent back toward the center which shortens distance traveled thereby reducing modal dispersion and reducing signal absorption into the cladding
32
Uniform refractive index throughout the core Signal bounces off the cladding as it moves down the core Modal dispersion is higher so bandwidths are lower plus signal absorption into the cladding is higher making attenuation higher however this type of cable is cheaper to manufacture than graded-index
33
Fiber Attenuation
Like all energy forms, light pulses lose energy over distance (i.e. energy attenuates)
Attenuation for fiber is measured in dB/km
High quality glass single mode fiber
attenuation is typically less than 1 dB/km Plastic multimode fiber attenuation can range up to 1,000 dB/km
Note: Signal strength is reduced by
34
When purchasing fiber you may see product specifications similar to the following:
Attenuation @850 nm: 3.75 dB/km Attenuation @1310 nm: 1.0 dB/km Attenuation @1550 nm: 0.75 dB/km
These specifications provide the fibers attenuation rating based upon a given wavelength from the light emitter
35
Optical windows refer to specific wavelength ranges at which fiber operates better with regards to the attenuation rate
36
Optical Windows
37
The 3 main optical windows used by light emitters for standard network applications are: 1. 850 nm 2. 1310 nm 3. 1550 nm
nm is the abbreviation for nanometer 1 billionth of a meter These wavelengths were chosen because they best match the transmission properties of available light sources with the transmission qualities of optical fiber
38
39
Safety Concern
Never look into the end of a fiber which may have a laser emitter coupled to it
Laser light is invisible but can still damage eyes
Direct viewing does not cause pain however
the eyes retina can be seriously damaged Unlike with visible light, the iris of the eye will not close involuntarily when exposed to laser light
40
For example if a 200 meter cable run offered a 800 MHz maximum bandwidth potential then:
Bandwidth potential for a 100 meter cable run would
be 1600 MHz all other things being equal Bandwidth potential for a 400 meter cable run would be 400 MHz all other things being equal
41
It is possible for a transmitted light signal to be reflected back toward the light source If enough reflected light gets back to the transmitter then it can interfere with the operation of a laser source
LED light sources are not effected by reflection
impedance changes
42
Return loss readings (recorded as dB) measure the strength of the light signal being reflected back to the source compared to the original outgoing light signal
The higher the return loss dB reading, the weaker the reflected light signal therefore the better the performance
For example, a 20 dB return loss means that the
reflected light returned back to the source is 99% weaker than the original transmissions strength (e.g. reflected light getting back to the source is only 1% of the original light)
A 30 dB return loss means reflected light getting back to
44
larger the minimum bend radius Plastic fibers tend to have smaller minimum bend radius than glass
45
Potential problems:
Broken and cracked fibers Increased attenuation Increased return loss Increased cladding absorption
46
displace the geometry of the twists resulting in various interference problems (e.g. crosstalk)
Generally, wire-based cable supports a smaller minimum bend radius than fiber
47
Variations from manufacturer-to-manufacturer and product-to-product however the widely accepted minimum bend radius specifications are:
Rule of Thumb
4 x diameter 6 x diameter 10 x diameter
1 1.2
48
Core Material
Sometimes called GOF (Glass Optical Fiber) Dominates the commercial cabling market
2.
Plastic
Sometimes called POF (Plastic Optical Fiber) Minimal use in the commercial cabling market Much larger core (120 to 1000 microns)
49
alignment easier More tolerant of dust between connections due to the large core Smaller % of core is blocked
50
51
Core/Cladding Size
Core/cladding size refers to the diameter of an individual fibers core and cladding components
For example, 8/125 indicates the core diameter is 8 microns and the surrounding cladding diameter is 125 microns
52
50/125
Multimode Better bandwidth and distance potential than
62.5/125
62.5/125
Multimode Been in use longer than 50/125 therefore has a larger
install base
53
54
Buffer Design
Buffer design refers to how optical fibers within a cable are protected from physical stress and weather conditions
The two main designs are:
1.
Tight buffered
Thermoplastic covering directly over each fiber Most often used for indoor applications Cable fiber(s) are inside a tough plastic pipe which is typically filled with a protective water-blocking gel Most often used for long haul, outdoor applications
55
2.
Buffer Designs
56
Designed to withstand the elements (e.g. moisture, sub-zero temperatures) and physical pressure of being buried underground Higher splicing and termination costs
Systems must be used to block the gel from
oozing out the cable ends but still make the fibers accessible for splicing and termination
Termination or splicing to indoor fiber usually
needed near the buildings entrance since the gel filling is often incompatible with indoor fire codes
57
Splicing
Splicing refers to a permanent joining of fiber ends without the use of a connector Terminating means a connector is used
Two common splicing techniques are:
1.
Mechanical splicing
2.
Fusion splicing
Fiber ends are butted together then the joint area is heated to soften the glass ends so they are bonded together once they cool
58
Distribution Cable
Breakout Cable
Tight buffered design includes two subcategories: 1. Tight buffered distribution cable
Usually just called distribution cable on vendor websites
Distribution Cable
Two or more optical fibers bundled together all sharing the same jacket, strengthening materials & padding materials
Could be one cable like this
Could be multiple jacketed
sub-cables each containing multiple fibers inside one common jacket like this
Typically appropriate for more light duty use since fibers dont have individual strengthening & padded materials
60
Breakout Cable
Multiple sub-cables in a common outer jacket but with each sub-cable containing a single optical fiber and having its own strengthening materials and padding materials
Appropriate for more Due to multiple sub-cable jackets heavy duty use breakout cables are more Designed to handle pressure, strain, expensive and have larger impact, and repetitive diameters than distribution motion better than cables with same # of fibers distribution cable
61
and padding materials so termination using regular connectors (e.g. LC, SC) is possible
Distribution optical fibers lack individual strengthening
and padding materials so termination procedures require more care since you are working with individual tight buffered fibers therefore direct termination with regular connectors is not possible (i.e. often terminated at a fiber patch panel)
62
Number Of Fibers/Cable
In fiber cable descriptions 3 terms are used to classify cables based on the number of fibers:
1.
2. 3.
Simplex cables
A single optical fiber inside one jacket
Duplex cables
Two optical fibers inside one jacket
Multifiber cables
From three to hundreds of optical fibers
Number Of Fibers/Cable
It is possible to send light signals from both ends of a fiber optic cable at the same time
The light signals do NOT collide but rather pass through
Given this fact one would assume that a single fiber is all that would be needed for full duplex (i.e. sending and receiving simultaneously) network communications In reality, most standard fiber-based network applications will use a cable containing two fibers one to send signals and one to receive Why? Because it is cheaper and simpler to implement
64
One would assume that a cable with one fiber is cheaper than a cable with two fibers
That is correct however it is the complexity of the transmitting/receiving device attached to the cable that has the biggest impact on total cost
It is much simpler and cheaper to build an interface that only sends or only receives a specific light wavelength than it is to build an interface that must coordinate between sending and receiving as well as possibly working with a variety of wavelengths
65
Multifiber Cables
Most network fiber applications require duplex cables (send fiber receive fiber) however there will be applications where two fibers are not enough
Bandwidth demands exceed duplex cable
Typically the number of fibers in a multifiber cable is a multiple of two to accommodate the duplex requirements of applications
66
Dark Fiber
Dark Fiber is the term used to identify fibers in a multifiber cable that are not being used immediately after the cable has been installed
These extra fibers serve as backups
In the event that a fiber becomes damaged it is
faster, cheaper and more convenient to activate this fiber than it would be to run another fiber cable
These spare fibers are considered to be dark because they are currently not in use so no light signals are passing through them
67
Terminating Fiber
Termination is the process of attaching a connector to the cable end Connectors should provide a junction with minimal power loss and minimal signal distortion Core alignment is the biggest challenge, especially when splicing two fibers given that the core diameter can be as small as 8 microns
68
Ferrule
69
There are two main techniques use to ensure a fiber retains its appropriate position within the ferrule
1.
2.
Epoxy
Basically gluing the fiber into position
Crimping
Using a sophisticated type of pliers (called
a crimper) to squeeze the appropriate part of the connector so that it clamps the fiber into its correct location
70
Fiber Connectors
Here are several popular fiber connector choices: 1. SC (Subscriber Connector) 2. ST (Straight Tip) 3. MT-RJ 4. LC Connector
There are several other types from which to choose There is no problem having different connectors at each end of the cable Connector on the device (e.g. switch) to which the cable is being connect determines which connector the cable should use
71
SC Subscriber Connector
Ferrule is partially protected by enclosing it in the connectors body Uses a push-pull mechanism for mating for easy connection/disconnection Male (top) and female (bottom) connectors shown here
72
ST Straight Tip
73
MT-RJ
Small form factor connector Smaller than SC and ST connectors Small size and housing 2 fibers allows more connectors in a given area (higher port density) Rectangular ferrule rather than round
Male (top) and female (bottom) connectors shown here
74
LC Connector
Another small form factor connector that allows higher port densities
Male (top) and female (bottom) connectors shown here
75
In the late 1990s it appeared that twisted-pair was approaching its upper limit and that fiber would begin to dominate however advancements in twisted-pair have kept pace or exceed the needs of most standard network applications
Now wireless networks have begun to make significant inroads in the networking area and you may see articles from time to time suggesting wireless will eventually obsolete both twisted-pair and fiber Regardless of the advancements of both wireless and twisted-pair media, fiber has significant advantages that the other two media will never be able to match
76
At the beginning of this module we noted some of fibers major advantages in the areas of attenuation, security and interference But the main advantage that fiber will always have over both wire-based and wireless media is its enormous bandwidth potential As the relative cost and manageability differences between wire-based and fiber-based technologies continue to shrink, fiber will become more of a force in the enterprise network environment
77