Vous êtes sur la page 1sur 4

APC Smart-UPS RT 3000V 230V A

http://www.apc.com/products/resource/include/techspec_index.cfm?ba...

APC Smart-UPS RT 3000VA 230V


Part Number: SURTD3000XLI

Output

Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Note Efficiency at Full Load Output Voltage Distortion Output Frequency (sync to mains) Crest Factor Waveform Type Output Connections

2100 Watts / 3000 V A 2100 Watts / 3000 V A 230V Configurable for 220 : 230 or 240 nominal output voltage 92% Less than 3% 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 3:1 Sine wave (8) IEC 320 C13 (2) IEC 320 C19 (2) IEC Jumpers

Bypass
Input

Internal Bypass (Automatic and Manual)

Nominal Input V oltage Input Frequency Input Connections

230V 50/60 Hz +/- 5 Hz (auto sensing) British BS1363A IEC-320 C20 Schuko CEE 7/EU1-16P 2.44 meters

Cord Length

1 of 4

11/04/2011 04:59 PM

APC Smart-UPS RT 3000V 230V A

http://www.apc.com/products/resource/include/techspec_index.cfm?ba...

Batteries & Runtime

Battery Type Included Battery Modules Typical recharge time Replacement Battery RBC Quantity Extended Run Options Runtime Graph Curve A B C D E Part Number(s) SURTD3000XLI SURTD3000XLI + (1)SURT192XLBP SURTD3000XLI + (2)SURT192XLBP SURTD3000XLI + (3)SURT192XLBP SURTD3000XLI + (4)SURT192XLBP

Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof 2 2.50 hour(s) RBC44 1 APC Smart-UPS RT 3000VA 230V

Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Graph View Runtime Chart

Energy Use/Efficiency

2 of 4

11/04/2011 04:59 PM

APC Smart-UPS RT 3000V 230V A

http://www.apc.com/products/resource/include/techspec_index.cfm?ba...

Hover over the line on the graph above to view the efficiency at any desired load Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Chart

Communications & Management

Interface Port(s)

RJ-45 Serial,Smart-Slot

Available SmartSlot Interface 1 Quantity Control panel Audible Alarm Emergency Power Off (EPO)
Surge Protection and Filtering

LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm Yes

Surge energy rating Filtering

480 Joules Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height Maximum Width Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height Shipping Width Shipping Depth l
3 of 4

432.00 mm 130.00 mm 660.00 mm 3U 54.55 KG 63.64 KG 347.00 mm 603.00 mm 980.00 mm

11/04/2011 04:59 PM

APC Smart-UPS RT 3000V 230V A

http://www.apc.com/products/resource/include/techspec_index.cfm?ba...

Environmental

Operating Environment Operating Relative Humidity Operating Elevation Storage Temperature Storage Relative Humidity Storage Elevation

0 - 40 C 0 - 95% 0-3000 meters -15 - 45 C 0 - 95% 0-15000 meters

Audible noise at 1 meter from 55.00 dBA surface of unit Online Thermal Dissipation
Conformance

609.00 BTU/hr

Regulatory Approvals Standard Warranty Environmental Compliance

BSMI,C-tick,CE,CSA,EN 50091-1,EN 50091-2,EN 55022 Class A,EN 60950,EN 61000-3-2,GOST,JEON,UL 1778,VCCI,VDE 2 years repair or replace RoHS 7b Exemption,REACH: Contains No SVHCs

**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. Copyright American Power Conversion Corp., all rights reserved

4 of 4

11/04/2011 04:59 PM

Vous aimerez peut-être aussi