Vous êtes sur la page 1sur 1

Bare Conductors

Type ACSR/AC
Aluminium conductors, aluminium-clad steel reinforced manufactured to AS 3607.
Physical and Mechanical Performance Data
Conductor
codename

Stranding and
wire diameter
no/mm
Aluminium
Steel

Angling
Aquatics
Archery
Baseball
Bowls
Cricket
Darts
Dice
Diving
Golf
Gymnastics
Hurdles
Lacrosse
Skating
Soccer
Swimming
Tennis

6/2.50
6/2.75
6/3.00
6/3.75
6/4.75
30/2.50
30/3.00
30/3.25
30/3.50
54/3.00
54/3.25
54/3.50
54/3.75
3/1.75
3/2.50
4/3.00
4/3.75

1/2.50
1/2.75
1/3.00
1/3.75
7/1.60
7/2.50
7/3.00
7/3.25
7/3.50
7/3.00
7/3.25
7/3.50
19/2.25
4/1.75
4/2.50
3/3.00
3/3.75

Nominal
overall
diameter
mm

Crosssectional
area
mm 2

Approximate
mass

Breaking
load

Modulus
of elasticity

Product
code

GPa

Coefficient
of linear
expansion
x10 6/C

kg/km

kN

7.5
8.3
9.0
11.3
14.3
17.5
21.0
22.8
24.5
27.0
29.3
31.5
33.8
5.3
7.5
9.0
11.3

34.4
41.6
49.5
77.3
120
182
262
307
356
431
506
587
672
16.8
34.4
49.5
77.3

113
137
163
254
385
636
913
1070
1240
1380
1620
1880
2150
83
171
218
340

10.6
12.7
15.1
22.3
32.7
64.4
91.6
106
122
120
139
159
180
12.3
24.9
28.9
42.6

79
79
79
79
76
82
82
82
82
75
75
75
74
119
119
106
106

20.1
20.1
20.1
20.1
20.6
19.4
19.4
19.4
19.4
20.6
20.6
20.6
20.7
15.3
15.3
16.5
16.5

Angling
Aquatics
Archery
Baseball
Bowls
Cricket
Darts
Dice
Diving
Golf
Gymnastics
Hurdles
Lacrosse
Skating
Soccer
Swimming
Tennis

Electrical Performance Data


Cond.
code
name

DC
resist.
at 20C
/km

Angling
0.923
Aquatics 0.763
Archery 0.641
Baseball 0.410
Bowls
0.259
Cricket
0.182
Darts
0.126
Dice
0.108
Diving
0.0928
Golf
0.0726
Gymnastics 0.0619
Hurdles
0.0533
Lacrosse 0.0465
Skating
2.75
Soccer
1.34
Swimming 0.807
Tennis
0.517

AC
resist.
at 50Hz
75C
/km

Inductive
reactance
to 0.3m
at 50Hz
/km

Continuous
Rural weathered
Winter night
Still
1m/s
2m/s
air
wind
wind

current carrying capacity, A


Summer noon
Still
1m/s
air
wind

1.24
1.03
0.861
0.551
0.352
0.245
0.155
0.133
0.114
0.0915
0.0782
0.0675
0.0590
3.70
1.80
1.08
0.695

0.296
0.290
0.285
0.271
0.256
0.240
0.228
0.223
0.219
0.212
0.207
0.202
0.198
0.346
0.324
0.302
0.288

111
126
141
192
265
342
458
511
569
662
740
821
904
57
92
127
170

87
98
109
145
195
246
319
354
391
452
503
555
607
46
72
96
127

191
215
240
318
425
532
706
779
857
980
1084
1190
1297
101
158
214
283

222
250
279
369
494
620
817
911
1013
1172
1309
1452
1596
118
184
249
329

172
193
215
282
372
465
609
668
732
834
917
1003
1088
92
143
191
251

2m/s
wind

Industrial weathered
Winter night
Still
1m/s
2m/s
air
wind
wind

Summer noon
Still
1m/s
air
wind

2m/s
wind

204
229
255
335
444
554
725
797
875
1012
1130
1252
1375
109
169
227
298

119
136
152
207
286
374
501
560
624
726
813
903
995
61
99
136
184

81
91
100
133
175
219
280
309
340
392
433
476
519
43
67
89
116

201
226
251
329
436
540
709
779
854
987
1101
1220
1339
108
167
224
293

195
221
246
327
440
555
735
812
895
1024
1134
1247
1361
103
162
219
291

226
255
285
378
506
637
842
939
1045
1208
1351
1499
1648
120
188
254
336

169
189
210
276
362
452
589
646
707
803
882
962
1042
91
140
187
245

Note Current ratings are based on the following conditions:


1 Conductor temperature rise above ambient of 40C
1 Ambient air temp. of 35C for summer noon or 10C for winter night
1 Direct solar radiation intensity of 1000W/m 2 for summer noon or zero for winter night
1 Diffuse solar radiation intensity of 100W/m 2 for summer noon or zero for winter night
1 Ground reflectance of 0.2
1 Emissivity of 0.5 for rural weathered conductor or 0.85 for industrial weathered conductor
1 Solar absorption coefficient of 0.5 for rural weathered conductor or 0.85 for industrial
weathered conductor