Design of stringer bracing & connection The distance between verticals of stringer bracing is 1.5 2.0 m (so the diagonal is inclined at nearly 45 o)
Dl. of stringer Bracing Vl. of stringer Bracing X.G.
S=4.5-6.0m
M.G.
Important: So the shape of stringer bracing is as shown (according to spacing between X-G "S".
S=3-4m S=6.0-8.0m
X.G.
X.G.
The design of stringer bracing means design of both vertical and diagonal. The normal force on stringer and X.G. due to truss action is neglected.
a) Design of diagonal: The diagonal is designed as single angle subjected to tension & compression NOTE: For bracing members in bridges, the maximum allowable stresses shall not exceed 0.85 of the allowable stresses specified in this code if the bridge has not been considered as a space structure (E C P 8)
1/17 SB
X.G.
Stringer bracing
Force in the diagonal is calculated as following: The load of lateral shock is taken constant & equals to 6t.
S=3-4m
Force = Assume =
110*10
l = ------------- 140 rv
Check stresses as tension member (assume d = 24 mm) A1 = (a) t (No reduction for area due to presence of H.S.B.) R.F =
3 A1 3 A1 + A2
A2 = (a t) t Anet = A1 + A2 * (R.F.)
2/17 SB
Stringer bracing
b) Design of vertical member: Use channel [ 180
Det"B"
Det"A"
D iagonal
s tr
e ing
3/17 SB
Stringer bracing
str
e ng i
channel
Detail "B"
The statical system of the channel and the stringer is as shown:
Stringer
Stringer
Channel
C.L. of channel
The lateral shock "6t" affected at the top of the rail. The load of lateral shock is transmitted to upper flange of stringer. If we take the effect of sleeper, so there is 3t on each flange. If we didn't consider the effect of sleeper, so there is 6t on one flange.
4/17 SB
Stringer bracing
0.1*h = 6.0 8.0 1.0 0.5*[ = 9.0 S.I.B. 600 L 80x80x8 G.Pl. 10mm
[ 180
6t e 6t Critical
3t e
3t 6t
3t 3e
3t 6t 3e
OR
3t -3t
3t
0.1hstr 8 1 9
Angle 80*8
5/17 SB
Stringer bracing
e = 0.1h stringer + 8 cm (connecting angle) + 1 cm (gusset plate) +
1 * 18 cm (channel) 2
Design as beam-Column:
)
2
E C P 15 E C P 15 If
100
Or 2.1 13.5 * 10 -5 Or
7500 2
if
M Sx
Sx of channel 180 If
f ca 0.15 A1 =1.0 Fc
C mx 1.0 f ca 1 FEX
f ca 0.15 Fc
A1 =
Cmx = 0.6-0.4
ECP 26
6/17 SB
Stringer bracing
FEX =
7500 2 x
Where
180 rx
Design of Stringer connection: 1- Connection between diagonal and gusset plate: grade 10.9 N= assume M24
Force Ps
where PS = 5.55
(E C P 106)
2- Connection between stringer web and channel: The connection is subjected to Shear and Torsion Q=6t Mt = "M" used to design channel = 6 e Rshear =
6 = 1.5 t 4
Get r 2 = ( x 2 + y 2 ) Rx =
Mt
r2
Ry=
Mt
r2
RH =RShear + RX Rv = Ry RT= Rh 2 + Rv 2 Ps
For case if stringer is over X.G.: The stringer may be added over X.G. if it is required. (Important)
7/17 SB
Stringer bracing
C.L. of stringer
C.L. of channel
Stringer
Stringer
Channel
X.G. 6t
X.G.
3t
C.L. of stringer
3t
6t 6e 6(h-e) 3t
The moment is 6e + 3 (hstringer - e) In which e = 0.1hstringer + 8 + 1 + 9 The normal is 3t only
6t 6(h-e) 3t 3t -3t 3t
Solved Example: Design both the diagonal and vertical members of stringer bracing twice if the spacing between X. girders = 6 m and divided to 3 equal distance. The stringer is IPE 600 a- If the stringer is flushed with X.G. b- If the stringer is over X.G.
= tan
-1
1.8 2 = 42
8/17 SB
Stringer bracing
= 1.8 2 + 4 = 2.69 m Try single angle 110*10
=
f c
Fc =
Try single angle 120*12 and recheck Check Tension stresses: Assume M 24 A1 = (12)1.2 = 14.4 cm2 RF = A2 = (12 -1.2)*1.2 = 12.96 cm2
3 * 14.4 = 0.77 3 * 14.4 + 12.96 6 = 0.25< 1.4*0.85 = 1.19 t / cm 2 24.38 l 269 = =22.4 < 40 d 12
Check deflection:
6t 6e 6e C.L. of channel 6t
x =
Stringer bracing
f ca 0.21 = = 0.23 > 0.15 FC 0.92
Cmx = 0.6-0.4 FEX =
7500 26 2
= 11.1 t / cm2
Cb = 0.6
M smaller M bigger
A1 =
Fbx =
Taken 2 bolts
2 Design of connection between unequal angle and channel Use emin =1.5 d = 3.6 cm Pmin = 3 d = 7.2 cm P+2e = 2P = 6*2.4=14.4cm < h 2tf ie 100*150 in
The unequal angle must be sufficient to take the 2 bolts) this case
r
R=
6 = 1.5 t 4
Rx =
Ry =
h-2t f
Rx = 5 + 1.5 = 6.5
Ry = 5
10/17 SB
Stringer bracing
Use M27 and check height of channel 2*3*2.7 = 16.2cm > h 2tf Use channel 200 for connection and recheck connection. Or use 6 bolts but the angle width must be enough. 3*(3*2.4) = 21.6 cm > 20 cm The width of the angle 200 is not enough
6t -3t 3t 3t 3t
M2 = 3 * 36 = 108 cmt N = 3t
x =
A1 =1
fbx =
11/17 SB
Stringer bracing
Use channel 200 and recheck Fca =
x =
A1 =1
fbx =
12/17 SB
Stringer bracing
13/17 SB
Stringer bracing
14/17 SB
Stringer bracing
Df
15/17 SB
Stringer bracing
16/17 SB
Stringer bracing
yutuiy