Académique Documents
Professionnel Documents
Culture Documents
est compuesto
segn (3).
H A TO H
= + +
(3)
donde
A
: temperatura ambiente,
TO
: diferencia de
temperatura entre la temperatura del aceite en la parte superior
de la cuba y la temperatura ambiente y,
H
: diferencia de
temperatura entre el punto ms caliente del devanado y la
temperatura del aceite en la parte superior de la cuba.
A su vez,
TO
y
H
se definen en estado transitorio
(variacin de carga) de acuerdo con (4) y (5), respectivamente.
( )
t
TO
TO TO,U TO,i TO,i
1 e
( = +
(4)
( )
t
W
H H,U H,i H,i
1 e
( = +
(5)
donde, los subndices i y u indican los valores iniciales y
finales, respectivamente;
t o
y
w
son definidos en la
gua de carga IEEE, de acuerdo con (6) y (7), sustituyendo el
subndice x por el subndice i o u, segn sea el caso.
( )
n
2
TO,X TO,r X
K R 1 (R 1)
(
= + +
(6)
2m
H,X H,r X
K =
(7)
donde, el subndice r indica valores a carga nominal, K es
52 IEEE LATIN AMERICA TRANSACTIONS, VOL. 5, NO. 1, MARCH 2007
la relacin de la potencia del equipo con respecto a la potencia
nominal, R es la relacin de las prdidas a carga nominal con
respecto a las prdidas en vaco, n y m son constantes que
dependen del sistema de enfriamiento utilizado en el equipo.
Aunque es bien sabido que no es correcto considerar a n y m
constantes, ya que varan con las variaciones de carga. La gua
IEEE propone algunos valores para estos exponentes.
En la gua IEC las ecuaciones en estado estable son algo
distintas, dependiendo del sistema de enfriamiento utilizado en
el equipo.
La gua IEC es principalmente aplicable al aislamiento con
papel no enriquecido trmicamente y la temperatura de punto
caliente est limitada en la gua a 98 C, a una temperatura
ambiente de 20 C. Por otro lado, la gua del IEEE usa los
valores de 110 C a 30 C, para las mismas temperaturas,
respectivamente [8]. En la gua de IEC no hay caso en el cual
H
(sobre una
base continua).
15 000
27 3 18 H
Vida ( p.u.) 9.80 10 e
(
(
+
=
(8)
15000 15000
383 273
H
AA
F e
(
(
+ (
=
(9)
( 98) / 6
H
Tasa de Envejecimiento Re lativo V 2
= =
(10)
El F
AA
es ms grande que 1 cuando
H
es ms elevada que
110 C, lo que sugiere prdida de vida (para envejecimiento
normal) y es menor que 1 cuando
H
es inferior a 110 C, y
por tanto es indicador de la extensin de vida. Sin embargo, el
equivalente ganado en vida por operar a bajas temperaturas es
menor que la correspondiente prdida por trabajar a altas
temperaturas.
El uso de (10) puede ser considerado despreciable a un
H
por debajo de 80 C [19].
En la gua del IEEE la ecuacin (9) se usa para calcular el
envejecimiento equivalente del transformador. La vida
equivalente (F
EQA
) (en horas o das), a la temperatura de
referencia, que ser consumida en un perodo de tiempo dado t
para el ciclo de temperatura dada, se calcula por (11).
1
1
,
1 1
0
( )
= =
| |
= =
|
\ .
t
N N
EQA AA n AA n n
n n
F t F dt t F t
(11)
Con este valor el porcentaje de prdida de vida, si la vida
normal (NIL) es conocida, est definido por (12).
EQA
% Prdida de vida (F t 100) / NIL =
(12)
La NIL no se define de manera nica, por lo que se deja al
usuario la libertad de seleccionar un valor adecuado. La gua
de IEEE propone algunos valores de referencia para un
sistema de aislamiento bien seco.
Un procedimiento similar se observa en la gua de IEC, en
donde la prdida relativa de vida sobre un cierto intervalo de
tiempo se calcula mediante (13).
t 2
N
n 1
t1
1 1
L Vdt V
t N
=
= =
(13)
En la bsqueda de una posible comparacin entre ambas
guas de carga, en la fig. 1 se ha cambiado la referencia de V a
110 C y como se puede apreciar, a temperaturas superiores a
115 C, aproximadamente, ambos modelos arrojaran
resultados distintos. Esto se debe a que cada gua de carga est
elaborada tomando en consideracin distintos tipos de papel
aislante y por lo tanto distintos modelos. En la versin ms
reciente de la gua de carga IEC [23] se especifica que los
modelos son idnticos en el caso que el papel sea
trmicamente mejorado, como es el caso de la gua de carga
del IEEE [6]. En ambas guas se muestran ejemplos de clculo
de envejecimiento relativo y de
H
.
Fig. 1. Faa (IEEE) y V (IEC) en funcin de la temperatura de punto caliente
El procedimiento para calcular la vida de un transformador,
basado en las guas de carga, se considera de fcil
aplicabilidad pero impreciso debido a que solamente se tiene
en cuenta la temperatura como el nico agente de degradacin,
ignorando los efectos de otros tipos de degradacin presentes
en condiciones de servicio [20]. Adems, si se desconocen los
factores ambientales que influyen en la degradacin del papel
p.e. oxgeno y humedad, las tasas de reaccin son
impredecibles con un factor de 3-4 [15]. Por otro lado, si la
temperatura no es medida, sino estimada por mtodos
imprecisos sugeridos por estndares o por mediciones del
punto caliente realizadas por imagen trmica, esto aade un
error de alrededor de 2 en la tasa de reaccin.
IV. CONCLUSIONES
Las guas de carga siguen siendo la referencia, aunque
hasta cierto punto conservadora, en la obtencin de un valor
con mayor consenso de la vida del aislamiento del
transformador de potencia.
FLORES et al.: LIFE OF POWER TRANSFORMERS IMMERSERD 53
Por otro lado, es recomendable realizar pruebas a diferentes
condiciones de carga, distintas de la nominal, con la finalidad
de obtener el perfil de variacin de los valores n y m, para as
reducir posibles errores en la obtencin del valor de la
temperatura de punto caliente, y por consiguiente, en la
obtencin de la vida del aislamiento.
V. AGRADECIMIENTOS
W. Flores agradece a los profesores M. Duval y L. Simoni
por la amabilidad de compartir su informacin.
VI. REFERENCIAS
[1] The Hartford Steam Boiler. Inspection and Insurance Co. Disponible
en: http://www.hsb.com/.
[2] A.M. Emsley, et al., Review of chemical indicators of degradation of
cellulosic electrical paper insulation in oil-filled transformers, IEE
Proc.-ci.Meas.Technol.,Vol.141,no.5,September 1994
[3] M. Wang, et al, Review of condition assessment of power transformers
in service, Electrical Insulation Magazine, IEEE Volume 18, Issue 6,
Nov.-Dec. 2002 Page(s): 12 25
[4] William H. Bartley, An analysis of transformer failures, Part 1 1988
through 1997-. Disponible en: http://www.hsb.com/thelocomotive/
[5] L. Pettersson, Estimation of the remaining service life of power
transformers and their insulation, Electra, no.133, pp.65-71, 1990.
[6] IEEE Guide for loading mineral oil-immersed transformers. IEEE Std.
C57.91-1995
[7] IEC Loading guide for oil-immersed power transformers. IEC
publication 354, 1991
[8] Sen, et al. Overloading and Loss of Life Assessment Guidelines of Oil-
Cooled Transformers, IEEE Rural Electric Power Conference, 2001,29
April-1 May 2001 pp: B4/1 - B4/8
[9] W.J. McNutt, Insulation Thermal Life Considerations for Transformer
Loading Guides, IEEE Transactions on Power Delivery, Vol. 7, No. 1,
January 1992
[10] D.H. Shroff, A. W. Atannett, A review of paper aging in power
transformers, IEE Proceedings, Vol.132, Pt.C, No.6, November 1985.
[11] IEEE Standard general principles for temperature limits in the rating of
electrical equipment and for the evaluation of electrical insulation,
1986. IEEE standard 1-1986
[12] IEEE recommended practice for the preparation of test procedures for
the thermal evaluation of insulation systems for electrical equipment,
1980. IEEE standard 99-1980
[13] IEEE recommended practice for thermal evaluation of insulation
systems for ac electric machinery employing form-wound pre-insulated
coils for machines rated 6900 V. and below, 1981. IEEE standard 275-
1981
[14] IEC guide for the determination of thermal endurance properties of
electrical insulating materials, (parts 1 to 4), 1990. IEC standard 216
[15] Working group 09 of study committee 12. (WG 12.09), Lifetime
evaluation of transformers, Electra No. 150, October 1993, pp. 39-51.
[16] Duval et al, Recent developments in DGA interpretation CIGRE JTF
D1-01/A2-11. October 2004
[17] S. Glasstone, K. Laidler, H. Eyring, The theory of rate processes,
Mcgraw-Hill, 1941. pp-1-9.
[18] L. Simoni, About models for aging and life of electrical insulation,
Materials Engineering 1992, Vol. 3, No1, pp.15-46
[19] IEC Loading Guide for Oil-Immersed Transformers. IEC publication
354, 1972
[20] M. K. Pradhan, T.S. Ramu, On the estimation of elapsed life of oil-
immersed power transformers, IEEE, Transaction On Power Delivery,
Vol.20, No.3, July 2005.
[21] W. Flores, E. Mombello, G. Ratt, J. Jardini, Vida de transformadores
de potencia sumergidos en aceite: Situacin actual. Parte II. Correlacin
entre resultados de ensayos fsico-qumicos. Revista IEEE
Latinoamericana. Sometido a revisin.
[22] A.M. Emsley, et al., Degradation of Cellulosic insulation in power
transformers. Part 2: Formation of Furan products in Insulating Oil,
IEE Proc.-Sci. Meas. Technol. Vol. 147, No.3, May 2000.
[23] IEC 60076-7 Loading Guide for Oil-Immersed Power Transformers.
First Edition 2005-12
[24] Du, Y. et al, Moisture Equilibrium in Transformers Paper Oil
Systems, IEEE Electrical Insulation, Vol. 15, No.1, Jan-Feb 1999,
pp.11-20.
[25] M. Horning, J. Kelly, S.D. Myers and R. Stebbins. Transformer
Maintenance Guide. Third Edition, 2004.
[26] Detlev W. Gross and Markus Soller, Partial Discharge Diagnosis on
Large Power Transformers, Conference Record of the 2004 IEEE
International Symposium of Electrical Insulation 19-22 September 2004.
[27] IEC 60450 Measurement of the Average Viscometric Degree of
Polymerization of New and Aged Cellulosic Electrically Insulating
Materials. Second Edition 2004-04.
VII. BIOGRAFAS
Wilfredo Flores nacido en Tegucigalpa, Honduras,
en 1972. Recibi el grado de ingeniero electricista de
la Universidad Nacional Autnoma de Honduras
(UNAH), en 1996 y el grado de Maestra en
Administracin de Empresas, del Instituto
Tecnolgico de Estudios Superiores de Monterrey
(ITESM), en 2001.
En la actualidad, el ingeniero Flores realiza estudios
de postgrado para obtener el grado de Doctor en
Ingeniera Elctrica en el Instituto de Energa Elctrica, Universidad Nacional
de San Juan (IEE-UNSJ), Argentina.
Enrique E. Mombello (M95-SM00) nacido en
Buenos Aires, Argentina, en 1957. Recibi el grado
de ingeniero elctrico en 1982 y el grado de Doctor
en Ingeniera Elctrica en 1998, ambos en la
Universidad Nacional de San Juan (UNSJ),
Argentina.
Su campo de inters abarca temas tales como
transformadores, alta tensin, comportamiento
transitorio de componentes de sistemas de potencia y
coordinacin del aislamiento.
Giuseppe Ratt (SM02) Desde marzo de 1997 es
director del Instituto de Energa Elctrica-
Universidad Nacional de San Juan (IEE-UNSJ),
Argentina. Profesor titular exclusivo de las ctedras
de Medidas Elctricas y Tcnicas en Alta Tensin.
Sus campos de inters son transformadores, alta
tensin y comportamiento transitorio de
componentes de sistemas de potencia.
Jos Antonio Jardini (M66-SM78-F90) nacido en
So Paulo, Brasil, en 1941. Recibi el grado de
ingeniero elctrico en 1963 y los grados de M.Sc. y
Ph.D. en 1970 y 1973, respectivamente, todos en la
Universidad de So Paulo (USP), Brasil.
En la actualidad, el Dr. Jardini es titular en el
Departamento de Ingeniera de Energa y
Automatizacin Elctrica en la USP. Es miembro de
CIGRE y fue el representante brasileo en el SC38
de CIGRE. El Dr. Jardini es distinguido conferencista
de IAS/IEEE.
Sus campos de inters son Automatizacin en Generacin, Transmisin y
Distribucin de Potencia.
54 IEEE LATIN AMERICA TRANSACTIONS, VOL. 5, NO. 1, MARCH 2007