The ControlLogix architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.
Rockwell Automation, Rockwell Software, Allen-Bradley, TechConnect, ControlLogix, GuardLogix, and RSLogix 5000 are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
AC digital
1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16 1756-IB16 1756-IB16D 1756-IB16I 1756-IB16ISOE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32
6 9 12 15 70 73 18 21 24 27 30 33 61 64 67 86 89
1756-OA8 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8 1756-OB8 1756-OB8EI 1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E 1756-OW16I 1756-OX8I
92 95 98 101 104 155 107 110 113 116 119 122 125 128 131 149 152 158 161 164 167 134 137 140 143
DC digital
Contact Analog 1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IT6I 1756-IT6I2 1756-IF8H 1756-IF16H 1756-CFM 1756-HSC 36 40 44 51 58 76 80 83 48 55 170 175
1756-OF8H 1756-PLS
146 179
The 1756 digital I/O modules support these features: Variety of voltage interface capabilities Isolated and nonisolated module types Point-level output fault states Direct-connect or rack-optimized communication Field-side diagnostics on select modules
Features Change of state: Software configurable Timestamp of inputs: 200 s Module keying: Electronic, software configurable RTB keying: User-defined mechanical
Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: 1756-OA8D, 1756-OA8E: Electronically fused per point 1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15 All other modules: Not protected. A fused IFM is recommended to protect outputs Module keying: Electronic, software configurable RTB keying: User-defined mechanical Reverse polarity protection: All modules except 1756-IG16 module Change of state: Software configurable Timestamp of inputs: 100 s for sequence of events modules 200 s for all other modules Module keying: Electronic, software configurable RTB Keying: User-defined mechanical Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: 1756-OB8EI, 1756-OB16D: Electronically fused per point 1756-OB16E, 1756-OV16E, 1756-OV32E: Electronically fused per group All other modules. Not protected. A fused IFM is recommended to protect outputs Module keying: Electronic, software configurable RTB keying: User-defined mechanical Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Configurable fault states per point: Hold last state, on or off (off is default) Configurable states in Program mode per point: Hold last state, on or off (off is default) Fusing: Not protected. A fused IFM is recommended to protect outputs Module keying: Electronic, software configurable RTB keying: User-defined mechanical
1756-IA8D
ControlLogix AC (79...132V) diagnostic input module
Simplified Schematic +5V
Not Used Daisy Chain to Other RTBs 1756-IA8D
2 4 1
L2-0
6 5
IN-0 IN-1
8 7
IN-2 IN-3
12 11
Group 0
L2-0 L2-1
14 13
47 k, 1/2 W 5% Resistor
IN-4 IN-5
16 15
GND
IN-6 IN-7
20 19
Group 1
47 k, 1/2 W, 5% Resistor
L2-1 L2-1 L2 L1
AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T
Attribute Inputs Voltage category Operating voltage range Input voltage, nom
1756-IA8D 8 diagnostic (4 points/group) 120V AC 79132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 3 mA 4.5 W @ 60 C (140 F) 15.35 BTU/hr 20V 2.5 mA
DIAG STIC NO
Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max
Attribute On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IA8D 5 mA @ 74V AC 16 mA @ 132V AC 250 mA 8.25 k @ 132V AC, 60 Hz 200 s...750 ms 125V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-IA8D 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 Hz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-IA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers)
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IA16
ControlLogix AC (79...132V) input module
1756-IA16
2 1
Simplified Schematic IN-O L2-0 GND ControlLogix Display Backplane Interface +5V
Group 0 Daisy Chain to Other RTBs
IN-1
4 3
IN-0 IN-2
6 5
IN-3 IN-5
8 7
IN-4 IN-6
10 9
Group 0
IN-7 L2-0
12 11
L2-0 IN-8
14 13
IN-9 IN-11
16 15
IN-10 IN-12
18 17
Group 1
IN-13 IN-15
20 19
Group 1
IN-14 L2-1
L2-1
L2
L1
AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T
Attribute Inputs Voltage category Operating voltage range Input voltage, nom
1756-IA16 16 (8 points/group) 120V AC 74132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 105 mA 2 mA 5.8 W @ 60 C (140 F) 18.41 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 13 mA @ 132V AC
DIAG STIC NO
Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max
Attribute Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IA16 250 mA peak (decaying to <37% in 22 ms, without activation) 10.15 k @ 132V AC, 60 Hz 200 s...750 ms 125V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports
10
Attribute Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IA16 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) UL CSA
1756-IA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
11
1756-IA16I
ControlLogix AC (79...132V) isolated input module
Simplified Schematic IN-O L2-0
L2-4 Isolated Wiring L2-0 L2-2 L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 1756-IA16I
2 4 6 8 10 1 3 5 7 9
+5V
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
L2-7 L2-8 L2-9 L2-10 L2-11 Nonisolated Wiring L2-12 L2-13 L2-14 L2-15 L2 L2-15 Not used
L1
Attribute
1756-IA16I 16 individually isolated 120V AC 79132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 125 mA 3 mA 4.9 W @ 60 C (140 F) 16.71 BTU/hr 20V 2.5 mA 5 mA @ 79V AC, 4763 Hz 15 mA @ 132V AC, 4763 Hz 250 mA
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max
12
1756-IA16I 8.8 k @ 132V AC, 60Hz 200 s...750 ms 125V (continuous), basic insulation type, inputs-tobackplane, and input-to-input Routine tested @ 1200V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
13
Certification(1) UL CSA
1756-IA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
14
1756-IA32
ControlLogix AC (74...132V) input module
Simplified Schematic IN-O L2-0 GND ControlLogix Display Backplane Interface +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1
1756-IA32
2 4 6 8 10
1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1
Group 0
Group 1
Group 1
L1
L2
Attribute
1756-IA32 32 diagnostic (4 points/group) 120V AC 74132V AC, 4763 Hz 120V AC Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 or 18 ms 165 mA 2 mA 6.1 W @ 60 C (140 F) 20.8 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 15 mA @ 132V AC 390 mA 14.0 k @ 132V AC, 60 Hz
AC INPUT
ST 0 1 2 3 4 5 6 7
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max
1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6
1 1 1 9 2 7
1 2 2 0 2 8
1 3 2 1 2 9
1 4 2 2 3 0
1 O 5 K 2 3 3 1
15
1756-IA32 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane 125V (continuous), basic insulation type, input group-togroup No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
16
Certification(1) UL CSA
1756-IA32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
17
1756-IB16
ControlLogix DC (10...31.2V) input module
Simplified Schematic
?
1756-IB16
IN-1
? ?
IN-0 IN-2
? ?
IN-3
IN-5
? ?
IN-4 IN-6
?
Group 0
IN-7 GND-0
?
GND-0 IN-8
? ?
IN-9 IN-11
IN-10
? ?
Group 1
IN-13
? ?
IN-12 IN14
? ?
Group 1
IN-15 GND-1
GND-1
DC COM
Attribute
1756-IB16 16 (8 points/group) 12/24V DC sink 10...31.2V DC 24V DC Hardware delay: 290 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 700 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 2 mA 5.1 W @ 60 C (140 F) 17.39 BTU/hr 5V 1.5 mA 2 mA @ 10V DC 10 mA @ 31.2V DC
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max
18
Attribute Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IB16 250 mA peak (decaying to < 37% in 22 ms, without activation) 3.12 k @ 31.2V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T3C T3 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports
19
Attribute Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IB16 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) UL CSA
1756-IB16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
20
1756-IB16D
ControlLogix DC (10...30V) diagnostic input module
Simplified Schematic Input +5V IN-0 ControlLogix Backplane Interface Display
Daisy Chain to Other RTBs GND-0 Group 0 GND-0 GND-0 GND-0 GND-1 GND-1 GND-1 GND-1 1756-IB16D
2 4 6 8 1 3 5 7
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used Group 14.3 k, 1/4 W 2% Resistor Group 14.3 k, 1/4 W 2% Resistor Group
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
GND-0 GND
Group 1
Group
GND-2 Group 2 GND-2 GND-2 GND-2 GND-3 GND-3 Group 3 GND-3 GND-3 GND-3 Not Used
Open Wire
DC COM
Attribute
1756-IB16D 16 diagnostic (4 points/group) 12/24V DC sink 10...30V DC 24V DC Hardware delay: 340 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 740 s nom/4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 150 mA 3 mA 5.8 W @ 60 C (140 F) 19.78 BTU/hr 5V
DC INPUT
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max
21
Attribute Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IB16D 1.5 mA 2 mA @ 10V DC 13 mA @ 30V DC 250 mA 2.31 k @ 30V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T3C T3 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
22
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-IB16D 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certifications(1) UL CSA
1756-IB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
23
1756-IB16I
ControlLogix DC (10...30V) isolated input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Display Backplane Interface
Isolated Wiring DC-0 (-) DC-1 (-) GND-0 GND-1 GND-2 Source Input Wiring DC-5 (-) DC-6 (-) GND-3 GND-4
10
1 3 5 7 9
2 4 6 8
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used
+ +
GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Nonisolated Wiring
DC (-)
DC (+)
Attribute
1756-IB16I 16 individually isolated 12/24V DC sink/source 10...30V DC 24V DC Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 3 mA 5 W @ 60 C (140 F) 17.05 BTU/hr 5V 1.5 mA 2 mA @ 10 V DC 10 mA @ 30V DC 250 mA peak (decaying to < 37% in 22 ms, without activation)
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max
24
1756-IB16I 3 k @ 30V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input-to-input Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports
25
Attribute Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IB16I 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) UL CSA
1756-IB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
26
1756-IB16ISOE
ControlLogix DC (10...55V) sequence of events input module
Simplified Schematic Electronic Current Limit Circuit IN-0
Isolated Wiring DC-0 (-)
2 4 6 8 1 3 5 7
1756-IB16ISOE
GND-0
GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) ControlLogix Display GND-10 Backplane GND-11 Nonisolated Interface GND-12 Wiring GND-13 GND-14 GND-15 Additional jumper bars are available as GND-15 DC (-) cat. no. 1756-JMPR. Not Used
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)
Attribute
1756-IB16ISOE(1) 16 individually isolated, sequence of events 24/48V DC sink/source 10...55V DC 24V DC Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 s + filter time: 0...50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 s nom/50 s max + firmware scan: up to 25 s + filter time: (0...50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) 320 mA 2 mA 5.5 W @ 60 C (140 F) 17.22 BTU/hr 5V 1.5 mA 2.0 mA @ 9V DC 4.5 mA @ 24...31V DC
SOE INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON
ON to OFF
Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, nom
27
Attribute On-state current, max Input impedance, max Cyclic update time Isolation voltage
1756-IB16ISOE(1) 5.1 mA @ 4855V DC 10.8 k @ 55V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4 None (open-style)
(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink module to coordinate system time. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
28
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-IB16ISOE 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-IB16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
29
1756-IB32
ControlLogix DC (10...31.2V) input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
Group 0 Daisy Chain to Other RTBs IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 GND-1 1756-IB32
2 4 6 8 10 1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Group 1
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 GND-1
Group 0
Group 1
DC COM
DC INPUT
ST 0 1 2 3 4 5 6 7
Attribute Inputs
1756-IB32 32 (16 points/group) 12/24V DC sink 10...31.2V DC 24V DC Hardware delay: 380 s max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 420 s max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 120 mA 2 mA 6.2 W @ 60 C (140 F) 21.1 BTU/hr @ 60 C (140 F) 5V 1.5 mA 2 mA 5.5 mA 250 mA (decaying to < 37% in 22 ms, without activation) 5.67 k @ 31.2V DC
1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6
1 1 1 9 2 7
1 2 2 0 2 8
1 3 2 1 2 9
1 4 2 2 3 0
1 O 5 K 2 3 3 1
Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max
30
1756-IB32 200 s...750 ms 250V (continuous), reinforced insulation type, inputs-tobackplane 250V (continuous), basic insulation type, input group-togroup No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1 - on signal ports(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports
31
Attribute Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IB32 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) c-UL-us
1756-IB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
32
1756-IC16
ControlLogix DC (30...60V) input module
1756-IC16
Simplified Schematic
IN-1
IN-0
4 3
+5V
IN-3
IN-2
6 5
Group 0
IN-5
8 7
IN-4 IN-6
10 9
Group 0
IN-7 GND-0
12 11
GND-0 IN-8
14 13
IN-9 IN-11
16 15
IN-10 IN-11
18 17
Group 1
IN-13 IN-15
20 19
Group 1
IN-14 GND-1
GND-1
DC COM
Attribute
1756-IC16 16 (8 points/group) 48V DC sink 30...55V DC @ 60 C (140 F) 30...60V DC @ 55 C (131 F) 48V DC Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 3 mA 5.2 W @ 60 C (140 F) 17.73 BTU/hr 10V 1.5 mA 2 mA @ 30V DC
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min
33
Attribute On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IC16 7 mA @ 60V DC 250 mA 8.57 k @ 60V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane 125V (continuous), basic insulation type, input group-togroup No isolation between individual group inputs Routine tested @ 1350V AC for 2 s, inputs-to-backplane Routine tested @ 924V AC for 2 s, input group-to-group
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
34
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IC16 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) UL CSA
1756-IC16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
35
1756-IF6CIS
ControlLogix sourcing current loop analog input module
1756-IF6CIS 2-wire Transmitter Connected to the Module and the Module Providing 24V DC Loop Power
2 1
1756-IF6CIS 2-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1
VOUT-1
4 3
VOUT-0 IN-0/I
6 5
VOUT-1
4 3
VOUT-0 i
A
IN-1/I RTN-1
8 7
IN-1/I
6 5
IN-0/I RTN-0
8 7
RTN-0 VOUT-2
10 9
i
RTN-1 VOUT-3 Shield Ground
24V DC +
2-wire Transmitter
VOUT-3 IN-3/I
12 11
VOUT-2
10 9
IN-2/I RTN-2
14 13
IN-3/I
12 11
IN-2/I RTN-2
14 13
Shield Ground
VOUT-5 IN-5/I
20 19
VOUT-5 IN-5/I
20 19
IN-4/I RTN-4
IN-4/I RTN-4
RTN-5
RTN-5
Do not connect more than two wires to any single terminal. Place additional loop devices (such as strip chart recorders) at either A location in the current loop.
If separate power sources are used, do not exceed the specified isolation voltage. Do not connect more than two wires to any single terminal. Place additional loop devices (such as strip chart recorders) at either A location in the current loop.
36
1756-IF6CIS 4-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1
VOUT-1
4 3
VOUT-0 IN-0/I
6 5
i
A + +
IN-1/I RTN-1
8 7
RTN-0 VOUT-2
10 9
4-wire Transmitter
24V DC
VOUT-3 IN-3/I
12 11
IN-2/I RTN-2
14 13
Shield Ground
VOUT-5 IN-5/I
20 19
IN-4/I RTN-4
If separate power sources are used, do not exceed the specified isolation voltage. Do not connect more than two wires to any single terminal. Place additional loop devices (such as strip chart recorders) at either A location in the current loop. User-supplied power supply must not exceed 150VA.
RTN-5
Range 020 mA
Attribute
1756-IF6CIS 6 individually isolated current sourcing 021 mA 16 bits 0.34 A/bit 250 mA 275 mA 5.1 W @ 60 C (140 F) 17.4 BTU/hr 215 , approx 20V DC 30V DC Current limited to < 30 mA Zero reading within 5 s 30V AC/DC with PTC and sense resistor
Inputs Input range Resolution Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Sourcing voltage, min Sourcing voltage, max Sourcing current, max Open circuit detection time Overvoltage protection, max
37
Attribute Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F), nom Calibrated accuracy 25 C (77 F), max Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module input scan time, min Isolation voltage
1756-IF6CIS 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 3262 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 0.025% of range 12 months 200 nA/C 17 ppm/C 0.36 A/C 35 ppm/C max 0.74 A/C max 0.2% of range 25 ms min floating point 10 ms min integer 250V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating)
38
Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-IF6CIS 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IF6CIS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
39
1756-IF6I
ControlLogix isolated voltage/current analog input module
1756-IF6I Current 2-wire
2 1
IN-1/V
4 3
IN-0/V IN-0/I
6 5
+
2-wire Transmitter
IN-1/V
4 3
IN-0/V
IN-1/I RET-1
8 7
i A A
+
IN-0/I
IN-1/I
6 5
A A
4-wire Transmitter
RET-0 IN-2/V
10 9
RET-1
8 7
RET-0 IN-2/V
10 9
IN-3/V IN-3/I
12 11
IN-3/V IN-3/I
12 11
IN-2/I RET-2
14 13
IN-2/I RET-2
14 13
Shield Ground
IN-5/V IN-5/I
20 19
IN-4/I RET-4
RET-5 RET-4
RET-5
Place additional loop devices (such as strip chart recorders) at either A location.
Place additional loop devices (such as strip chart recorders) at either A location.
40
IN-1/V
4 3
IN-0/V IN-0/I
6 5
+
User Analog Input Device
IN-1/I RET-1
8 7
RET-0 IN-2/V
10 9
IN-3/V IN-3/I
12 11
IN-2/I RET-2
14 13
IN-5/V IN-5/I
20 19
IN-4/I RET-4
Shield Ground
RET-5
Low Signal and User Counts -10.54688V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts
High Signal and User Counts 10.54688V 32767 counts 10.54688V 32767 counts 5.27344V 32767 counts 21.09376V 32767 counts
Attribute
1756-IF6I 6 individually isolated 10.5V 010.5V 05.25V 021 mA 16 bits 10.5V: 343 V/bit 010.5V: 171 V/bit 05.25V: 86 V/bit 021 mA: 0.34 A/bit 250 mA
Resolution
41
Attribute Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Isolation voltage
1756-IF6I 100 mA Voltage: 3.7 W Current: 4.3 W Voltage: 12.62 BTU/hr Current: 14.32 BTU/hr Voltage: > 10 M Current: 249 Positive full scale reading within 5 s Voltage: 120V AC/DC Current: 8V AC/DC (with on-board current resistor) 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 2 V/C Voltage: 35 ppm/C, 80 ppm/C max Current: 45 ppm/C, 90 ppm/C max 0.54% of range 25 ms min floating point 10 ms min integer(1) 250V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
42
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IF6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
43
1756-IF8
ControlLogix voltage/current analog input module
1756-IF8 Differential Current Channel 0 Channel 0 1756-IF8 Differential Voltage
i
A
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground Channel 3 Jumper Wires Shield Ground
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
i
A
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-)
All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.
All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.
44
i
IN-0 IN-1 IN-2
2 4 6 8 10 1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Jumper Wires
Channel 0
+
IN-0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
IN-3 RTN
i
2-wire Transmitter
IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Shield Ground
Not Used Not Used Not Used Not Used Not Used Not Used Not Used
All terminals marked RTN are connected internally. For current applications, all terminals marked iRTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and i RTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal.
All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring. Do not connect more than two wires to any single terminal.
Attribute
1756-IF8 8 single-ended 4 differential 2 high-speed differential 10.25V 0...10.25V 0...5.125V 020.5 mA 10.25V: 320 V/cnt (15 bits plus sign bipolar) 010.25V: 160 V/cnt (16 bits) 05.125V: 80 /V cnt (16 bits) 020.5mA: 0.32 A/cnt (16 bits) 150 mA 40 mA
Inputs
Input range
Resolution
45
Attribute Power dissipation, max Thermal dissipation Input impedance Open circuit detection time
1756-IF8 Voltage: 1.73 W Current: 2.33 W Voltage: 5.88 BTU/hr Current: 7.92 BTU/hr Voltage: >1 M Current: 249 Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 45 V/C Voltage: 15 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 8 pt single-ended (floating point): 16488 ms 4 pt differential (floating point): 8244 ms 2 pt differential (floating point): 5122 m(1) 250V (continuous), reinforced insulation type, inputs-tobackplane. No isolation between individual inputs Routine tested at 1350V AC for 2 s
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min
Isolation voltage
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
46
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
47
1756-IF8H
ControlLogix voltage/current analog input module with HART protocol
1756-IF8H Current 1756-IF8H Voltage
Voltage Input +V IN0+
IN0+ IN0IN1+ 4 Wire Current Input IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN72 4 6 8 1 3 5 7 I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC
+ -
+-
2 4 6 8
1 3 5 7
I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC
-V
IN0IN1+ IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
+ + Wire + 4 XMTR - - -
Attribute
1756-IF8H 8 differential voltage or current 10V 0...5V 15V 0...10V 020 mA 420 mA 1621 bits 300 mA 70 mA Voltage: 3.21 W Current: 4.01 W Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr > 1 M voltage 250 current Positive full scale reading within 5 s Voltage: 30V DC Current: 8V DC > 80 dB @ 50/60 Hz > 100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 90 V/C Voltage: 10 ppm/C Current: 20 ppm/C
Resolution Current draw @ 5V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy Calibration interval Offset drift Gain drift with temperature
48
Attribute Module error Module input scan time, min Module HART scan time
1756-IF8H Voltage: 0.1% of range Current: 0.3% of range 18...488 ms (filter dependent) Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time 50V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Type tested at 1500V AC for 60 s
Isolation voltage
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2 - on signal ports(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
49
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-IF8H 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
1756-IF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR101622C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
50
1756-IF16
ControlLogix voltage/current analog input module
1756-IF16 Differential Current Channel 0 1756-IF16 Differential Voltage Channel 0 IN-0 IN-1 IN-2 Shield Ground Channel 3 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9
i
A i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
i
A
Channel 3
Shield Ground
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6 IN-8 (+), IN-9 (-), i RTN-8 IN-10 (+), IN-11 (-), i RTN-10 IN-12 (+), IN-13 (-), i RTN-12 IN-14 (+), IN-15 (-), i RTN-14
Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-) IN-8 (+), IN-9 (-) IN-10 (+), IN-11 (-) IN-12 (+), IN-13 (-) IN-14 (+), IN-15 (-)
All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.
All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.
51
i
IN-0 IN-1 IN-2 Shield Ground 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground
IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10
1 3 5 7 9
i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15
i
A
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Shield Ground
All terminals marked RTN are connected internally. For current applications, all terminals marked i RTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and iRTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal.
All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring. Do not connect more than two wires to any single terminal.
1756-IF16 16 single ended, 8 differential or 4 differential (high speed) 10.25V 010.25V 05.125V 020.5 mA 10.25V (15 bits + sign bipolar) 010.25V (16 bits) 05.125V (16 bits) 020.5 mA (16 bits) 150 mA 65 mA Voltage: 2.3 W Current: 3.9 W
Resolution
52
1756-IF16 Voltage: 7.84 BTU/hr Current: 13.3 BTU/hr Voltage: >10 M Current: 249 Differential voltage - Positive full scale reading within 5 s Single-ended/differential current - Negative full scale reading within 5 s Single-ended voltage - Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F) Offset drift Gain drift with temperature Module error Module input scan time, min
Voltage: 30V DC Current: 8V DC >80 dB @ 60 Hz(1) 100 dB @ 50/60 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Voltage: Better than 0.05% of range Current: Better than 0.15% of range 45 V/C Voltage: 15 ppm Current: 20 ppm Voltage: 0.1% of range Current: 0.3% of range 16 pt single-ended: 16...488 ms 8 pt differential: 8...244 ms 4 pt differential: 5...122 ms(1) 250V (continuous), reinforced insulation type, inputs-tobackplane No isolation between individual inputs Routine tested at 1350V AC for 2 s
Isolation voltage
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
53
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IF16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
54
1756-IF16H
ControlLogix current analog input module with HART protocol
2 Wire HART Device
2 Wire XMTR 24V DC Power Supply
+ -
+-
2 4 6 8 10
1 3 5 7 9
When a common supply is used you should tie the IN- to RTN.
RTN IN4+ IN5+ IN6+ IN7+ IN8+ IN9+ IN10+ IN11+ RTN IN12+ IN13+ IN14+ IN15+
+ + -
+ -
4 Wire XMTR
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Attribute Inputs
1756-IF16H 16 differential, current 020 mA 420 mA 16...21 bits 200 mA 125 mA 6W 12 BTU/hr 249 Positive full scale reading within 5 s 8V DC 74 dB @ 50/60 Hz (15 Hz filter) 90 dB @ 60 Hz (20 Hz filter) > 90 dB @ 50/60 Hz (15 and 20 Hz filters only) Better than 0.01% of range (15 and 20 Hz filters only) Better than 0.13% of range (all filters)
Input range Resolution Current draw @ 5V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Repeatability Calibrated accuracy
55
Attribute Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time
1756-IF16H 12 months 27 V/C 11ppm/C 0.3% of range 11...328 ms (filter dependent) Typically 1 s Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time
Isolation voltage
50V (continuous), basic insulation type, inputs-tobackplane No isolation between individual inputs Type tested at 1500V DC for 60 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2 - on signal ports(2) T5 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
56
1756-IF16H 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 3 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) c-UL-us
1756-IF16H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
57
1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
1756-IF4FXOF2F Current
(-) i
1756-IF4FXOF2F Voltage (+) (+) User Analog Input Device (-) Shield Ground +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
(+)
2-wire A Transmitter
A
+IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
2 4 6
1 3 5
+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 i I OUT-0 RTN-0 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
A
2 4 6 8
1 3 5 7
+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 I OUT-0 RTN-0 Not Used (-) Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground (+)
8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 24 26 28 21 23 25 27
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
30 29 32 31 34 33 36 35
Attribute
1756-IF4FXOF2 4 high-speed, sub-millisecond, differential 2 high-speed voltage or current 375 mA 100 mA Voltage: 4.3 W Current: 4.7 W Voltage: 14.66 BTU/hr Current: 16.02 BTU/hr 250V (continuous), basic insulation type, inputs and outputs to backplane No isolation between individual inputs or outputs Routine tested at 1350V AC for 2 s
Inputs Outputs Current draw at 5.1V Current draw at 24V Power dissipation, max Thermal dissipation Isolation voltage
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2)
Wire category
58
Attribute North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Inputs 4 high-speed, sub-millisecond, differential 10.5V 010.5V 05.25V 021 mA Approx. 14 bits across 10V DC (21V total) 10V: 1.3 mV/bit, 14-bit effective 010.5V: 1.3 mV/bit, 13-bit effective 05.25V: 1.3 mV/bit, 12-bit effective Approx. 12 bits across 21 mA 021 mA: 5.25 A/bit Voltage: >1 M Current: 249 Positive full-scale reading within 1 s Voltage: 30V DC Current: 8V AC/DC 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months Voltage: 25 ppm/C max Current: 35 ppm/C max 0.2% of range 300 s min(1)
Resolution
Impedance Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module scan time
Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: >2000 Current: 0750 < 2 ms to 95% of final value with resistive loads
50 V/ C 1 A/ C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.2% of range Current: 0.3% of range
(1) 300 s min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F, Series A, firmware revision 1.x.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
59
Attribute Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-IF4FXOF2 595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IF4FXOF2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
60
1756-IG16
ControlLogix TTL input module
Standard Wiring
1756-IG16
DC
2 1
CE Compliant Wiring
1756-IG16
I/O Wire
IN-1
IN-0
4 3
IN-1
4 3
IN-0 IN-2
6 5
IN-3
6 5
IN-2 IN-4
8 7
5V DC
IN-3 IN-5
8 7
IN-5
IN-4 IN-6
10 9
I/O Wire
+
TTL Input Device
IN-7
+ DC
DC Power Wire
IN-7
10 9
IN-6
DC COM 0
12 11
DC-0(+) IN-9
14 13
DC-0(+)
12 11
DC COM 0
IN-8 IN-10
16 15
IN-9
14 13
IN-8 IN-10
16 15
IN-11
5V DC Power
IN-11 IN-13
18 17
IN-13
18 17
IN-12 IN-14
20 19
IN-12
IN-15
IN-15
20 19
IN-14
DC COM 1
DC-1(+)
DC COM 1
DC-1(+)
Simplified Schematic
+5 DC 1.5 K IN 1K 74HCT14 560
DC COM
61
Attribute
1756-IG16 16 (8 points/group) 5V DC TTL source (Low=True)(1) 4.5...5.5V DC 50 mV P-P ripple max Hardware delay: 270 s nom/450 s max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 390 s nom/ 700 s max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 110 mA 2 mA 1.4 W @ 60 C (140 F) 4.8 BTU/hr @ 60 C (140 F) 2V 4.1 mA 1.4 k min 1.5 k typical 3.7 mA @ 5V DC 4.1 mA @ 5V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs Voltage category Operating voltage range Input delay time OFF to ON (5-to-0V DC transition) ON to OFF (0-to-5V DC transition) Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max Input impedance, max Input current, nom Input current, max Cyclic update time Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T5 T5 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
62
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-IG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
63
1756-IH16I
ControlLogix DC (90...146V) isolated input module
1756-IH16I
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Display Backplane Interface
DC-7 (-) Jumper Bar (Cut to Length) DC-0 (-) Isolated Wiring DC-3 (-) GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 GND-15 Not Used
2 4 6 8 1 3 5 7
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Ysed
DC-0 (+)
DC-3 (+)
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
D C-7 (+ )
Nonisolated Wiring
DC (-)
DC (+)
Attribute
1756-IH16I 16 individually isolated 125V DC sink/source 90...146V DC(1) 125V DC Hardware delay: 2 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 6 max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 125 mA 3 mA 5 W @ 60 C (140 F) 17.05 BTU/hr 20V DC 0.8 mA 1 mA @ 90V DC 3 mA @ 146V DC 90...146V DC 90...146V DC @ 50 C (122 F), 12 Channels ON 90...132V DC @ 55 C (131 F), 14 Channels ON 90...125V DC @ 60 C (140 F), 16 Channels ON 90...146V DC @ 30 C (86 F), 16 Channels ON
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max On-state voltage Derated as follows
64
Attribute Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-IH16I 250 mA 48.67 k @ 146V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input-to-input Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4 None (open-style)
Wire category North American temperature code Enclosure type (1) 90...146V DC @ 50 C 90...132V DC @ 55 C 90...125V DC @ 60 C 90...146V DC @ 30 C (122 F),12 channels on (131 F), 14 channels on (140 F), 16 channels on (86 F), 16 channels on.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports
65
Attribute Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
1756-IH16I 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
Certification(1) UL CSA
1756-IH16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
66
1756-IH16ISOE
ControlLogix DC (90...140V) sequence of events input module
Simplified Schematic +5V IN-0
1756-IH16ISOE
GND-0
GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 ControlLogix Display Jumper Bar GND-9 (Cut to Length) Backplane GND-10 Interface GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 Additional jumper bars are available as GND-15 cat. no. 1756-JMPR. GND-15 DC (-) Not Used
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)
Attribute
SOE INPUT
Inputs
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
1756-IH16ISOE(1) 16 individually isolated, sequence of events 125V DC sink/source 90...140V DC 125V DC Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 s + filter time: 0...50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 s nom/50 s max + firmware scan: up to 25 s + filter time: (0...50 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) 275 mA 2 mA 5.5 W @ 60 C (140 F) 17.22 BTU/hr 20V 0.3 mA 1.15 mA @ 90V DC 1.85 mA @ 140V DC 74.8 k
Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON
ON to OFF
Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max
67
1756-IH16ISOE(1) 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input-to-input Routine tested @ 1350V AC for 2 s, inputs-to-backplane
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T3C None (open-style)
(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink module to coordinate system time. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
68
Certification(1) UL CSA
1756-IH16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
69
1756-IM16I
ControlLogix AC (159...265V) input module
Simplified Schematic
Isolated Wiring 1756-IM16I
IN-O L2-0
+5V
L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 L2-7 L2-8 L2-9 L2-10 L2-11
2 4 6 8 10
1 3 5 7 9
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used L1
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Nonisolated Wiring
L2
Attribute
1756-IM16I 16 individually isolated 240V AC 159265V AC, 4763 Hz(1) 240V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 3 mA 5.8 W @ 60 C (140 F) 19.78 BTU/hr 40V 2.5 mA 5 mA @ 159V AC, 60 Hz 13 mA @ 265V AC, 60 Hz
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max
70
1756-IM16I 159...265V AC, 47...63Hz @ 30 C (86 F) all channels ON 159...265V AC, 47...63Hz @ 40 C (104 F) 8 points ON 159...253V AC, 47...63Hz @ 45 C (113 F) all channels ON 159...242V AC, 47...63Hz @ 60 C (140 F) all channels ON 250 mA 20.38 k @ 265V AC, 60 Hz 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input-to-input Routine tested @ 1350V AC for 2 s
Inrush current, max Input impedance, max Cyclic update time Isolation voltage
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4 None (open-style) (86 F) all channels on (104 F) 8 points on (113 F) all channels on (140 F) all channels on.
Wire category North American temperature code Enclosure type (1) 159265V AC, 4763Hz @ 30 C 159265V AC, 4763Hz @ 40 C 159253V AC, 4763Hz @ 45 C 159242V AC, 4763Hz @ 60 C
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
71
1756-IM16I 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) FM CSA
1756-IM16I FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
72
1756-IN16
ControlLogix AC (10...30V) input module
Simplified Schematic IN-O L2-0 GND
L2 Group 0 IN-7
10 9
1756-IN16
+5V
IN-1 L1 IN-3
IN-0
4 3
IN-2
6 5
IN-5
8 7
L2-0 IN-9
14 13
IN-8 IN-10
16 15
IN-12 IN-14
20 19
Group 1
IN-15 L2-1
L2-1
Attribute
1756-IN16 16 (8 points/group) 24V AC 1030V AC, 4763 Hz 24V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 10 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 2 mA 5.1 W @ 60 C (140 F) 17.39 BTU/hr 5V 2.75 mA 5 mA @ 10V AC, 60 Hz 1.2 mA @ 30V AC, 60 Hz 250 mA 2.5 k @ 30V AC, 60 Hz
AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max
73
1756-IN16 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T3C T3 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
74
Certification(1) UL CSA
1756-IN16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
75
1756-IR6I
ControlLogix temperature sensing analog input module
1756-IR6I 3-wire RTD
2 1
IN-1/A
4 3
IN-0/A IN-0/B
6 5
IN-1/B RTN-1/C
8 7
IN-3/A IN-3/B
12 11
IN-2/B RTN-2/C
14 13
Shield Ground
IN-5/A IN-5/B
20 19
IN-4/B RTN-4/C
RTN-5/C
Do not connect more than two wires to any single terminal. IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and RTN-x/C are shorted together as shown.
76
IN-1/A
4 3
IN-0/A IN-0/B
6 5
IN-1/B RTN-1/C
8 7
IN-3/A IN-3/B
12 11
IN-2/B RTN-2/C
14 13
Shield Ground
IN-5/A IN-5/B
20 19
IN-4/B RTN-4/C
RTN-5/C
Do not connect more than two wires to any single terminal. Wiring is exactly the same as the 3-wire RTD with one wire left open.
Low Signal and User Counts 0.859068653 -32768 counts 2 -32768 counts 4 -32768 counts 8 -32768 counts
High Signal and User Counts 507.862 32767 counts 1016.502 32767 counts 2033.780 32767 counts 4068.392 32767 counts
Attribute
1756-IR6I 6 individually isolated RTD 1487 21000 42000 84020 16 bits 1487 : 7.7 m/bit 21000 :15 m/bit 42000 :30 m/bit 84020 :60 m/bit
Resolution
77
1756-IR6I 100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper 250 mA 125 mA 4.3 W 14.66 BTU/hr Negative full scale reading within 5 s with any combination of lost wires, except input terminal A alone. If input terminal A is lost by itself, the module reads a positive full scale reading within 5 s 24V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 10 M/C 50 ppm/C 90 ppm/C 0.54% of range 25 ms min floating point (ohms) 50 ms min floating point (temperature) 10 ms min integer (ohms)(1) 250V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection time
Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time
Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
78
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IR6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
79
1756-IT6I
ControlLogix temperature sensing analog input module
1756-IT6I
2 1
+
IN-0
IN-0
4 3
RTN-1
IN-2 Thermocouple
IN-3
10 9
CJC+
12 11
Not Used
RTN-3
14 13
CJC-
Wire
IN-5
18 17
RTN-4
Do not connect more than two wires to any single terminal. One CJC, part number 94238301, is shipped with the module. A replacement can be ordered as RP-94238301.
Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts
High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts
1756-IT6I 6 individually isolated thermocouple 1 CJC -1278 mV -1230 mV 16 bits -12...78 mV: 1.4 V/bit -12...30 mV: 0.7 V/bit
OK
Resolution
80
Attribute Thermocouples Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time
1756-IT6I B, E, J, K, R, S, T, N, C 250 mA 125 mA 4.3 W 14.66 BTU/hr >10 M Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 0.33.2 C, depending on channel 0.3 C 0.5 V/C 65 ppm/C 80 ppm/C 0.5% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) 250V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
81
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IT6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
82
1756-IT6I2
ControlLogix enhanced thermocouple analog input module
1756-IT6I Cold Junction Sensor
Wire
Spade Lug
Not Used CJC RTN-0 RTN-1 RTNRTN-3 RTNRTN-5 CJC Not used
Thermocouple
?
IN-3 IN-4 IN-5 CJC+ Not used
Wire
Spade Lug
Do not connect more than two wires to any single terminal. Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.
Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts
High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts
Analog Input
CAL OK
1756-IT6I2 6 individually isolated thermocouple 2 CJC -1278 mV (1.4 V per bit) -1230 mV (0.7 V per bit high resolution range) 16 bits -12...78 mV: 1.4 V/bit -12...30 mV: 0.7 V/bit B, E, J, K, R, S, T, N, C, D, L (TXK/XK)
Thermocouples
83
Attribute Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature, nom
1756-IT6I2 200 mA 150 mA 4.6 W 15.7 BTU/hr Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 160 dB min, tested @ 600V AC/60 Hz applied with 100 differential resistance 15 Hz(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 12 months 0.3 C 0.3 C 0.5 V/C 15 ppm/C 1.4 V/C for -1278 mV 0.6 V/C for -1230 mV 25 ppm/C 2.3 V/C for -1278 mV 1.1 V/C for -1230 mV 0.15% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) 250V (continuous), basic insulation type, input channelsto-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s
Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type (1) Notch filter dependent.
(2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
84
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-IT6I2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
85
1756-IV16
ControlLogix DC (10...30V) sourcing input module
1756-IV16
Simplified Schematic +5V DC-0+ IN-0 GND ControlLogix Display Backplane Interface
Group 0 IN-5 IN-1
IN-0
4 3
IN-3
6 5
IN-7
10 9
IN-6 DC-0 +
12 11
DC-0 + IN-9
14 13
IN-8 IN-10
16 15
IN-12 IN-14
20 19
Group 1
IN-15 DC-1 +
DC-1 +
+
Daisy Chain to Other RTBs
DC COM
Attribute
1756-IV16 16 (8 points/group) 12/24V DC source 10...30V DC 24V DC Hardware delay: 280 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 110 mA 2 mA 5.41 W @ 60 C (140 F) 18.47 BTU/hr 5V DC 1.5 mA 2 mA @ 10V DC 10 mA @ 30V DC 250 mA
DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 1 1 21 1 5 K 0 11 3 41
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max
86
1756-IV16 3.2 k @ 30V DC 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
87
Certification(1) UL CSA
1756-IV16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
88
1756-IV32
ControlLogix DC (10...30V) sourcing input module
Simplified Schematic +5V DC-0+
Group 0 IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 1756-IV32
2 4 6 8 10 1 3 5 7 9
IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 DC-0 (+) IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 DC-1 (+) Group 1 Group 0
IN-0
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Jumper Wire
Group 1
DC COM
Attribute
1756-IV32 32 (16 points/group) 12/24V DC source 10...30V DC 24V DC Hardware delay: 350 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 120 mA 2 mA 4.1 W @ 60 C (140 F) 14 BTU/hr @ 60 C (140 F) 5V 1.5 mA 2 mA 3.5 mA 250 mA (decaying to <37% in 22 ms, without activation) 8.6 k @ 30V DC
DC INPUT
ST 0 1 2 1 ST 8 9 0 11 1 ST 6 7 8 22 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 1 3 2 1 2 9 6 1 4 2 2 3 0 7 1 O 5 K 2 3 3 1
Inputs Voltage category Operating voltage range Input voltage, nom Input delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max
89
1756-IV32 200 s...750 ms 250V (continuous), basic insulation type, inputs-tobackplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1 - on signal ports(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1k Hz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
90
Certification(1) UL CSA
1756-IV32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
91
1756-OA8
ControlLogix AC (74...265V) output module
Simplified Schematic +5V L1-0
2 1
1756-OA8
L1-0
4 3
OUT-0 OUT-1
6 5
L1-0
OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 20 A Current Surge
Group 0
L1-0
8 7
OUT-2 OUT-3
10 9
Group 0
L1-0 L1-0
12 11
L1-1 L1-1
16 15
OUT-5 OUT-6
18 17
Group 1
L1-1 L1-1
20 19
Group 1
2A 0 43 ms
L1-1
Time
Attribute
1756-OA8 8 (4 points/group) 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 2 mA 5.1 W @ 60 C (140 F) 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ <50 mA 2 A @ 60 C (140 F) linear derating
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON
ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max
92
Attribute Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage
1756-OA8 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Inhibit voltage, max Removable terminal block Slot width Wire size
Zero crossing 60V peak 1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4A None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
93
Attribute Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OA8 CISPR 11: Group 1, Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OA8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
94
1756-OA8D
ControlLogix AC (74...132V) diagnostic output module
Simplified Schematic ControlLogix Backplane Interface Diagnostic Control Block with Opto and Transformer Isolation
VAC Short Verify/ No Load GATE
Group 0
2
1756-OA8D
1
L1
Not Used
4 3
L2-0 OUT-0
6 5
L1-0 L1-0
8 7
OUT-1 OUT-2
10 9
Group 0
OUT L2
L1-0 L1-0
Display
OUT-3
12 11
Surge Current Chart 8A Current 5A 1A 500 mA 0 Time Surge @ 30 C (86 F) Surge @ 60 C (140 F) Continuous @ 30 C (86 F) Continuous @ 60 C (140 F) 43 ms
L1-1
14 13
OUT-4 OUT-5
16 15
L1-1 L1-1
OUT-6
18 17
Group 1 L1-1
Group 1 OUT-7
20
19
L1-1
Attribute Short trip, min No load Output verification Pulse test Field power loss (zero cross) Time stamp of diagnostics
1756-OA8D 12 A for 500 s Off-state detection only On-state detection only Configurable maximum width and max time delay from zero cross Detects at 25V peak min (firmware phase locked loop) 1 ms
Attribute
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K FLT 0 1 2 3 4 5 6 7
DIAGNOSTIC
95
1756-OA8D 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 175 mA 250 mA 5.3 W @ 60 C (140 F) 18.0 BTU/hr 3 mA per point 2.5V peak @ 0.5 A 3V peak @ 1 A 1 A @ 30 C (86 F) linear derating 0.5 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 8 A for 43 ms per point, repeatable every 2 s @ 30 C (86 F) 5 A for 43 ms per point, repeatable every 1 s @ 60 C (140 F) 10 mA per point 125V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s
ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point
Inhibit voltage, max Removable terminal block Slot width Wire size
Zero crossing 25V peak 1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
96
Attribute Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OA8D 595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
97
1756-OA8E
ControlLogix AC (74...132V) electronically-fused output module
Simplified Schematic ControlLogix Backplane Interface Opto and Transformer Isolation
VAC Short GATE
L1-0
6 5 2
1756-OA8E
1
L1
Not Used
4 3
Group 0
L1-0 L1-0
10 9
Group 0
OUT-2 OUT-3
12 11
OUT-4 OUT-5
16 15
L1-1 L1-1
18 17
OUT-6 OUT-7
20 19
Group 1
L1-1 L1-1
Group 1
L2-1 L2
2A 0 43 ms
Daisy Chain to Other RTBs
Time
L1
Attribute Short trip, min Field power loss (zero cross) Time stamp of diagnostics
1756-OA8E >20 A for 100 ms Detects at 25V peak min (firmware phase locked loop) 1 ms
Attribute
1756-OA8E 8 electronic fusing (4 points/group) 120V AC 74132V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 250 mA 5.5 W @ 60 C (140 F)
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K
Outputs Voltage category Operating voltage range Output delay time OFF to ON
ELECTRONICALLY FUSED
ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max
98
Attribute Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Load current, min Isolation voltage
1756-OA8E 18.76 BTU/hr 3 mA per point 4V peak @ 2 A 2 A @ 60 C (140 F) 4 A @ 30 C (86 F) linear derating 2 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 125V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s
Inhibit voltage, max Removable terminal block Slot width Wire size
Zero crossing 25V peak 1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
99
1756-OA8E 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1k V line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OA8E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
100
1756-OA16
ControlLogix AC (74...265V) output module
Simplified Schematic ControlLogix Backplane +5V Interface L1-0
OUT-1 Group 0 Daisy Chain to Other RTBs
4 3
1756-OA16
2 1
OUT-0 OUT-2
6 5
OUT-3 OUT-5
8 7
OUT-4 OUT-6
10 9
Group 0
OUT-7 L1-0
12 11
L2-0 OUT-8
14 13
OUT-9 OUT-11
16 15
OUT-10 OUT-12
18 17
OUT-13 OUT-15
Group 1
L1 OUT-14
L2-1
20
19
20 A Current 5A 2A 500 mA 0
L2
43 ms Time
Attribute
1756-OA16 16 mechanically fused/group (8 points/group) 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 400 mA 2 mA
AC OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15 FUSE O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON
101
Attribute Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Surge current per group Load current, min Commutating voltage Isolation voltage
1756-OA16 6.5 W @ 60 C (140 F) 22.17 BTU/hr 3 mA per point 1.5V @ 0.5 A 5.7V @ load current < 50 mA 0.5 A @ 60 C (140 F) 2 A @ 60 C (140 F) 4 A @ 60 C (140 F) 5 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 15 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
Zero crossing 60V peak Mechanically fused/group 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4 None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
102
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
Certification(1) UL CSA
1756-OA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
103
1756-OA16I
ControlLogix AC (74...265V) isolated output module
Simplified Schematic +5V L1-0
1756-OA16I Isolated Wiring L1-0 L1-2 L1-4 L1-0 L1-1 L1-2 L1-3 L1-4 L1-5 L1-6 L1-7 Jumper Bar (Cut to Length) L1-8 L1-9 L1-10 Nonisolated Wiring L1-11 L1-12 L1-13 L1-14 L1-15 L1 L1-15 Not Used
10 1 3 5 7 9 2 4 6 8
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used L2
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
2A 1A 0 Time
Attribute
1756-OA16I 16 individually isolated 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 300 mA 2.5 mA 5.5 W @ 60 C (140 F) 18.76 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ load current < 50 mA
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K
Outputs Voltage category Operating voltage range Output delay time OFF to ON
ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max
104
Attribute Current per point, max Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage
1756-OA16I 2 A @ 30 (86 F) linear derating 1 A @ 60 C (140 F) linear derating 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
Inhibit voltage, max Removable terminal block Slot width Wire size
Zero crossing 60V peak 1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4A None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
105
Attribute Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OA16I 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
Certification(1) UL CSA
1756-OA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
106
1756-OB8
ControlLogix DC (10...30V) output module
Simplified Schematic +5V OUT-0
Group 0
DC-0(+)
1756-OB8
1
DC-0 (+)
4 3
OUT-0 OUT-1
6 5
Group 0
OUT-2
8 7
RTN OUT-0
DC-0 (+)
10 9
RTN OUT-0
4A Current
Surge
DC-1 (+) Group 1
OUT-4
14 13
OUT-5
16 15
Group 1 OUT-6
Continuous @ 60 C (140 F) 2A
DC-1 (+)
18 17
DC-1 (+)
20 19
RTN OUT-1
0 Time
10 ms
Daisy Chain to Other RTBs
DC COM
Attribute
1756-OB8 8 electronically fused, individually isolated 12/24V DC source 10...30V DC 1 ms max 2 ms max 250 mA 2 mA 4.7 W @ 60 C (140 F) 16.03 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 2 s 3 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
107
1756-OB8 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
108
Certification(1) UL CSA
1756-OB8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
109
1756-OB8EI
ControlLogix DC (10...30V) electronically-fused, isolated output module
1756-OB8EI
+5V
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0
Nonisolated Wiring
DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
2A
Continuous @ 60 C (140 F)
0 Time
10 ms
DC COM
1756-OB8EI > 4.5 A for 500 s max (output on, then short) > 4.5 A for 1.5 ms max (output on into short) 1 ms
Attribute
1756-OB8EI 8 individually isolated 12/24V DC source 10...30V DC 1 ms max 5 ms max 165 mA 2 mA 4.7 W @ 60 C (140 F) 16.03 BTU/hr
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation
ELECTRONICALLY FUSED
110
Attribute Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage
1756-OB8EI 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C (140 F) 10 A @ 60 C (140 F) 16 A @ 55 C (131F) linear derating 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
111
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-OB8EI 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-OB8EI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
112
1756-OB8I
ControlLogix DC (10...30V) isolated output module
+5V Simplified Schematic DC-0(+)
Isolated Wiring 1756-OBI
OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0
Continuous @ 60 C (140 F) 2A
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used
2 4 6 8
1 3 5 7
10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
0 Time
10 ms
Attribute
1756-OB8I 8 individually isolated 12/24V DC source 10...30V DC 1 ms max 2 ms max 165 mA 2 mA 4.6W @ 60 C (140 F) 15.70 BTU/hr 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C (140 F) 16 A @ 60 C (140 F) 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA
DC OUTPUT
ST 01234567 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
113
1756-OB8I 250V (continuous), reinforced insulation type, outputs-tobackplane 250V (continuous), basic insulation type, output-tooutput Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
114
Certification(1) UL CSA
1756-OB8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
115
1756-OB16D
ControlLogix DC (19.2...30V) diagnostic output module
Simplified schematic +5V +5V Short Circuit Detect Optoisolation +5V + DC
Daisy Chain to Other RTBs +DC-0 +DC-0 +DC-0 +DC-0 Group 0 +DC-0 +DC-0 +DC-0 GND-0 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 Group 1 +DC-1 +DC-1 GND-1 GND-1 Not Used Daisy Chain to Other RTBs 1756-OB16D
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used Group 1 Group 0
OUT ControlLogix Backplane Interface Display Output Verify/No Load Surge Current Chart 4A Current Surge RTN
2A
32
34 36
0 Time
10 ms
DC COM
Attribute Short trip No load Output verification Pulse test Time stamp of diagnostics
1756-OB16D 8 A for 180 ms 10 A for 120 ms Off-state detection only On-state detection only Configurable maximum pulse width 1 ms
Attribute
1756-OB16D 16 diagnostic (8 points/group) 24V DC source 19.2...30V DC 60 s nom/1 ms max 630 s nom/5 ms max 250 mA 140 mA
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V
116
Attribute Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage
1756-OB16D 3.3 W @ 60 C (140 F) 11.25 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 30 C (86 F) linear derating 1 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 4 A for 10 ms per point, repeatable every 1 s 3 mA per point 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
117
1756-OB16D 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
118
1756-OB16E
ControlLogix DC (10...31.2V) electronically-fused output module
Simplified Schematic Optoisolation
1756-OB16E
Display
DC-0(+)
OUT-1 OUT-3
OUT-0
4 3
Group 0
OUT-2
6 5
Group 0
OUT-0 ControlLogix Backplane Interface Electronic Fuse Circuitry Surge Current Chart Surge RTN OUT-0
OUT-5
8 7
OUT-4 OUT-6
10 9
OUT-7 DC-0(+)
12 11
OUT-9 OUT-11
16 15
OUT-10 OUT-12
18 17
2A Current 1A
OUT-13 Group 1
Group 1 OUT-14
Continuous @ 60 C (140 F)
OUT-15
20 19
DC-1(+)
RTN OUT-1
0 Time
10 ms
+
DC COM
Attribute
1756-OB16E 16 electronically fused (8 points/group) 12/24V DC source 10...31.2V DC 70 s nom/1 ms max 360 s nom/1 ms max 250 mA 2 mA 4.1 W @ 60 C (140 F) 13.98 BTU/hr 1 mA per point 400 mV DC @ 1 A 1 A @ 60 C (140 F) 8 A @ 60 C (140 F) 2 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 3 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE K ST 8 9 10 11 12 13 14 15 FUSE ELECTRONICALLY FUSED
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
119
1756-OB16E 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
120
Certification(1) UL CSA
1756-OB16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
121
1756-OB16I
ControlLogix DC (10...30V) isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16I Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)
DC-0(+) +5V
DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)
Nonisolated Wiring
DC(+)
2A
0 Time
Attribute
1756-OB16I 16 individually isolated 12/24V DC sink/source 10...30V DC 1 ms max 2 ms max 350 mA 2.5 mA 3.6 W @ 60 C (140 F) 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C (86 F) 1 A @ 60 C (140 F) 8 A @ 30 C (86 F) 4 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 2 s 1 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
122
1756-OB16I 250V (continuous), basic insulation type, outputs-tobackplane 125V (continuous), basic insulation type, output-tooutput Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
123
Certification(1) UL CSA
1756-OB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
124
1756-OB16IS
ControlLogix DC (10...30V) scheduled, isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16IS Isolated Sourcing Output Wiring DC-0 (-) DC-2 (-)
DC-0(+) +5V
2A
DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used
DC-6 (-)
DC(-)
0 Time
10 ms
Attribute
1756-OB16IS 16 individually isolated, 8 scheduled 12/24V DC sink/source 10...30V DC 1 ms max 2 ms max 350 mA 2.5 mA 3.6 W @ 60 C (140 F) 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C (86 F) 1 A @ 60 C (140 F) 8 A @ 30 C (86 F) 4 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 2 s 1 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
125
1756-OB16IS 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) Copper T4A T4 None (open-style)
Wire category Wire type North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
126
Certification(1) UL CSA
1756-OB16IS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
127
1756-OB32
ControlLogix DC (10...31.2V) output module
1756-OB32
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1
Group 0
Group 1
1A Current
_
DC COM
Attribute
1756-OB32 32 (16 points/group) 12/24V DC source 10...31.2V DC 60 s nom/1 ms max 200 s nom/1 ms max 300 mA 2 mA 4.8 W @ 60 C (140 F) 16.37 BTU/hr 0.5 mA per point 200 mV DC @ 0.5 A 0.5 A @ 50 C (122 F) linear derating 0.35 A @ 60 C (140 F) 16 A @ 50 C (122 F) linear derating 10 A @ 60 C (140 F) 1 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 3 mA per point
DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 4 11 12 12 90 22 78 5 6 11 3 4 22 1 2 23 9 0 7 1 O 5 K 2 3 3 1
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point, max Load current, min
128
1756-OB32 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T3C T3 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
129
Certification(1) UL CSA
1756-OB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
130
1756-OC8
ControlLogix DC (30...60V) output module
Simplified Schematic +5V OUT-0
DC-0 (+) Group 0 DC-0 (+)
8 7
1756-OC8
2 1
DCDC-0 (+)
4 3
OUT-0 OUT-1
6 5
DC-0 (+)
10 9
RTN OUT-0
12 11
DC-1(+)
DC-1(+)
16 15
DC-1(+) DC-1(+)
OUT-7
20 19
2A
Continuous @ 60 C (140 F)
RTN OUT-1
RTN OUT-1
0 Time
10 ms
DC COM
Attribute
1756-OC8 8 (4 points/group) 48V DC source 30...60V DC 1 ms max 2 ms max 165 mA 2 mA 4.9 W @ 60 C (140 F) 16.71 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 1 s @ 60 C (140 F) 2 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
131
1756-OC8 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
132
Certification(1) UL CSA
1756-OC8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
133
1756-OF4
ControlLogix voltage/current output analog module
1756-OF4 Current
2 1
1756-OF4 Voltage
Not Used
4 3
VOUT-0 IOUT-0
6 5
i
A Current Output Load
+
VOUT-0 IOUT-0
Not Used
4 3
Not Used
6 5
RTN VOUT-1
10 9
RTN
8 7
RTN VOUT-1
10 9
IOUT-1 VOUT-2
14 13
IOUT-1
12 11
Shield Ground
Shield Ground
Not Used
14 13
VOUT-2 IOUT-2
16 15
IOUT-2 RTN
18 17
RTN VOUT-3
20 19
VOUT-3 IOUT-3
Not Used
IOUT-3
Place additional loop devices (such as strip chart recorders) at the A location noted above. Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.
Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.
Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts
High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts
Attribute
1756-OF4 8 voltage or current 10.4V 021 mA Voltage: 15 bits across 10.5V, 320 V/bit Current: 15 bits across 21mA, 650 nA/bit 150 mA 120 mA
Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V
134
Attribute Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Isolation voltage
1756-OF4 3.25 W, 4 channel current 10.91 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21mA or less Voltage: >2000 Current: 0750 <2 ms to 95% of final value with resistive loads Better than 0.05% of range from 421 mA, 10.410.4V 12 months typical 50 V/ C 100 nA/C Voltage: 25 ppm/C, 520 V/C Current: 50 ppm/C, 1050 A/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point 8 ms integer 250V (continuous), reinforced insulation type, output channels-to-backplane No isolation between individual output channels Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
595% noncondensing
135
Attribute Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OF4 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OF4 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
136
1756-OF6CI
ControlLogix current loop output analog module
1756-OF6CI 0...550
2 1
1756-OF6CI 551...1000
2 1
OUT-1
4 3
OUT-0
OUT-1
OUT-0
4 3
i
User Analog Output Device
i
User Analog Output Device
ALT-1
6 5
ALT-0 RTN-0
8 7
ALT-1
6 5
ALT-0 RTN-0
8 7
RTN-1 OUT-3
10 9
RTN-1 OUT-3
10 9
OUT-2
OUT-2
ALT-3
12 11
ALT-2 RTN-2
14 13
ALT-3
12 11
ALT-2 RTN-2
14 13
RTN-3
Shield Ground
Not Used
Not Used
16 15
OUT-5
18 17
OUT-4 ALT-4
20 19
OUT-5
18 17
OUT-4 ALT-4
20 19
ALT-5 RTN-5
ALT-5 RTN-5
RTN-4
RTN-4
Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.
Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.
Range 0...20 mA
Attribute
1756-OF6CI 6 individually isolated 021 mA 13 bits across 21 mA (2.7 A) 250 mA for 0...550 W loads terminated on OUTs and RTNs (Total backplane power in this range 6.7 W) 250 mA for 551...1000 W loads terminated on OUTs and ALTs (Total backplane power in this range 8.5 W)
137
1756-OF6CI 225 mA for 0...550 W loads terminated on OUTs and RTNs (Total backplane power in this range 6.7 W) 300 mA for 551...1000 W loads terminated on OUTs and ALTs (Total backplane power in this range 8.5 W) 5.5 W (0550 loads) 6.1 W (5511000 loads) 18.76 BTU/hr (0550 loads) 20.80 BTU/hr (5511000 loads) None 24V DC Electronically current limited to 21mA or less 01000 Separate field terminations for 0550 and 5511000 < 2 ms to 95% of final value with resistive loads Better than 0.1% of range from 421 mA 6 months typical 1 A/C typical 60 ppm/C 100 ppm/C 0.6% of range 25 ms floating point 10 ms integer 250V (continuous), basic insulation type, output channels-tobackplane, and output channel-to-channel Routine tested at 1350V AC for 2 s
Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time, max Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
138
Attribute Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OF6CI 595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OF6CI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
139
1756-OF6VI
ControlLogix voltage loop output analog module
1756-OF6VI
2 1
+
OUT-0 Not Used User Analog Output Device
OUT-1
4 3 5
Not Used
6
RTN-1
8 7
RTN-0 OUT-2
10 9
OUT-5
18 17
Not Used
20 19
RTN-5
Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.
Range 10V
Attribute
1756-OF6VI 6 individually isolated 10.5V 14 bits across 21V (1.3 mV) (13 bits across 10.5V +sign bit) 250 mA 175 mA 4.85 W 16.54 BTU/hr <1 None 24V DC Electronically current limited > 1000 loads, 10 mA
Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Output impedance Open circuit detection Overvoltage protection Short circuit protection Drive capability
140
Attribute Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time, max Isolation voltage
1756-OF6VI < 2 ms to 95% of final value with resistive loads Better than 0.1% of range 6 months typical 60 V/ C typical 50 ppm/C 80 ppm/C 0.5% of range 25 ms floating point 10 ms integer 250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
141
1756-OF6VI 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF Immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OF6VI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
142
1756-OF8
ControlLogix voltage/current output analog module
1756-OF8 Current
2 1
1756-OF8 Voltage
2 1
VOUT-4
4 3
VOUT-0 IOUT-0
6 5
i
A
VOUT-4
4 3
VOUT-0 IOUT-0
6 5
IOUT-4 RTN
8 7
RTN VOUT-1
10 9
RTN
8 7
VOUT-5 IOUT-5
12 11
VOUT-5
10 9
IOUT-5 VOUT-6
14 13
VOUT-6 IOUT-6
16 15
VOUT-2 IOUT-2
16 15
IOUT-2 RTN
18 17
IOUT-6 RTN
18 17
RTN VOUT-7
20 19
RTN VOUT-3
20 19
VOUT-3
VOUT-7
IOUT-3
IOUT-7
IOUT-7
IOUT-3
Place additional loop devices (such as strip chart recorders) at the A location noted above. Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.
Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.
Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts
High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts
Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V
1756-OF8 8 voltage or current 10.4V 021 mA 15 bits across 21 mA - 650 nA/bit 15 bits across 10.4V - 320 V/bit 150 mA 210 mA
143
Attribute Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, max Module error Module scan time, min Isolation voltage
1756-OF8 4.92 W, 4 channel current 16.78 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: > 2000 Current: 0750 < 2 ms to 95% of final value with resistive loads Better than 0.05% of range from 421 mA, 10.410.4V 12 months typical 50 V/C typical 100 nA/C1 A/C typical Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point 8 ms integer 250V (continuous), reinforced insulation type, output channels-to-backplane No isolation between individual output channels Routine tested at 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
595% noncondensing
144
Attribute Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OF8 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
145
1756-OF8H
ControlLogix voltage/current output analog module with HART protocol
1756-OF8H
Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts
High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts
1756-OF8H 8 voltage or current 10.4V 020 mA 420 mA 1516 bits 200 mA 230 mA 4.92 W, 8 channel current 16.78 BTU/hr Voltage: >2 k @ 10.4V Current: 50750 drive Current output only (output must be set to < 0.1mA) 24V DC Voltage: > 2000 @ 10.4V Current: 50750 with short circuit survival current Voltage: 1 F Current: 10 H Current (no HART): < 23 ms to 95% with resistive loads Current (with HART): < 37 ms to 95% with resistive loads Voltage: < 8.5 ms to 95% with resistive loads
Resolution
HART
Current draw @ 5V Current draw @ 24V Power dissipation, max Thermal dissipation Output impedance Open circuit detection time Overvoltage protection, max Drive capability Load reactance, max Settling time
146
Attribute Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module output scan time, min Module HART scan time
1756-OF8H Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months typical 100 V/C typical 200 nA/C typical Voltage: 20 ppm/C Current: 35 ppm/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point Typically 1 s per HART channel enabled Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time 50V (continuous), basic insulation type, output channelsto-backplane No isolation between individual output channels Type tested at 1500V AC for 60 s
Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2(2) T4A T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
147
Attribute Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-OF8H CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-OF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR101622C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
FM TV
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
148
1756-OG16
ControlLogix TTL output module
Standard Wiring
1756-OG16
DC
+
2 1
CE Compliant Wiring
1756-OG16
DC Power Wire
2 1 3
OUT-1
4 3
OUT-0 OUT-2
6 5
5V DC Power
OUT-1
4
OUT-0 OUT-2
+5 V DC
OUT-3 OUT-5
8 7
OUT-3
6 5
OUT-4 OUT-6
10 9
OUT-5
8 7 9
OUT-4
10
OUT-7 + DC DC-0(+)
12 11
DC COM 0 OUT-8
14 13
I/O Wire
OUT-7 DC-0(+)
12 11
OUT-9 OUT-11
16 15 17 19
OUT-10
18 20
OUT-9
14 13
OUT-11
Capacitor 0.01 F Typical (See notes below.)
16 15
OUT-10 OUT-12
18 17
OUT-13 OUT-15
20 19
OUT-14 DC COM 1
DC-1(+)
Simplified Schematic
+5 DC 74AC14 OUT
74AC14 OUT
DC COM
149
Attribute
1756-OG16 16 (8 points/group) 5V DC TTL (Low=True(1) 4.5...5.5V DC source 50 mV P-P ripple max 45 s nom/450 s max 145 s nom/700s max 210 mA 2 mA 1.5 W @ 60 C (140 F) 5.2 BTU/hr @ 60 C (140 F) 0.1 mA per point 0.4V DC 24 mA 24 mA 384 mA 0.15 mA 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Outputs Voltage category Operating voltage range Output delay time (resistive load) OFF to ON (5V-to-0V DC transition) ON to OFF (0V-to-5V DC transition) Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Continuous current, max Load current per point, max Load current per module, max Load current Isolation voltage
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 2(3) T5 T5 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
150
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-OG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
151
1756-OH8I
ControlLogix DC (90...146V) isolated output module
Simplified Schematic +5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 4A Current Surge
Daisy chain to other RTBs Non-Isolated Wiring
DC-0
Isolated Wiring +
1756-OH8I
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not used Not used
2 4 6 8 10
1 3 5 7 9
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not used Not used
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Continuous @ 60 C (140 F) 2A
Time
10 ms
DC COM
Attribute
1756-OH8I 8 individually isolated 120V DC sink/source 90...146V DC 2 ms max 2 ms max 210 mA 2 mA 3.3 W @ 60 C (140 F) 11.25 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 1 s @ 60 C (140 F) 2 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min
152
1756-OH8I 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
153
Certification(1) UL CSA
1756-OH8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
154
1756-ON8
ControlLogix AC (10...30V) output module
Simplified Schematic +5V L1-0
L1-0
4 3
1756-ON8
1
OUT-0 OUT-1
6 5
L1-0
Group 0
L1-0
8 7
OUT-2 OUT-3
10 9
Group 0
L1-0 L1-0
Not Used
12 11
OUT-4
14 13
20 A Current
Surge
L1-1 Group 1 L1-1
OUT-5
16 15
Group 1 OUT-6
18
17
L1-1
OUT-7
20 19
2A
L1-1
Not Used
L2
Time
43 ms
L1
Attribute
1756-ON8 8 (4 points/group) 24V AC 1030V AC, current >50 mA, 4763Hz 1630V AC, current <50 mA, 4763Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 2 mA 5.1 W @ 60 C (140 F) 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ < 50 mA 2 A @ 60 C (140 F)
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Outputs Voltage category Operating voltage range Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max
155
Attribute Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage
1756-ON8 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(2) 1(3) T4A T4 None (open style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Maximum wire size requires extended housing, catalog number 1756-TBE. (3) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
156
Attribute Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-ON8 CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-ON8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
157
1756-OV16E
ControlLogix DC (10...30V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation
2
1756-OV16E
1
DC-0(+) OUT-0
Group 0
OUT-1
4 3
OUT-0 OUT-2
6 5
OUT-3 OUT-5
8 7
OUT-4 OUT-6
10 9
Group 0
RTN OUT-0
OUT-7 DC-0(+)
12 11
OUT-9 OUT-11
OUT-10
16 15
OUT-13
18 17
OUT-12 OUT-14
20 19
Group 1
2A Current 1A 0
OUT-15 DC-1(+)
RTN OUT-1
10 ms Time
Daisy Chain to Other RTBs
1756-OV16E 5 A for 20 ms @ 24V DC (output on, then short) 5 A for 20 ms @ 24V DC (output on into short) 1 ms
Attribute
1756-OV16E 16 electronically fused (8 points/group) 12/24V DC sink 75 s nom/1 ms max 360 s nom/1 ms max 10...30V DC 210 mA 2 mA 6.72 W @ 60 C (140 F) 22.94 BTU/hr
DC O UTPUT
ST 0 1 2 3 4 5 6 7 FU SE FU SE E C O ALLYFU D LE TR NIC SE O K ST 8 9 1 11 3 1 5 01 21 41
Outputs Voltage category Output delay time OFF to ON ON to OFF Operating voltage range Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation
158
Attribute Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage
1756-OV16E 1 mA per point 700 mV DC @ 1 A 1 A @ 60 C (140 F) 8 A @ 60 C (140 F) 2 A for 10 ms per Point, repeatable every 2 s @ 60 C (140 F) 2 mA per point 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBNH 1756-TBSH 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
159
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-OV16E 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certification(1) UL CSA
1756-OV16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
FM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
160
1756-OV32E
ControlLogix DC (10...30V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation DC-0(+) OUT-0
Group 0 Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 1756-OV32E
2 4 6 8 10 1 3 5 7 9
Daisy Chain to Other RTBs OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1 Group 1
RTN OUT-0
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Group 0
2A Current 1A 0
10 ms Time
_
DC COM
1756-OV32E 5 A for 20 ms @ 24V DC (output on then short) 5 A for 20 ms @ 24V DC (output into short) 1 ms
Attribute
1756-OV32E 32 electronically fused (16 points/group) 12/24V DC sink 10...30V DC 75 s nom/300 s max 230 s nom/1 ms max 390 mA 2 mA 5.88 W @ 60 C (140 F) 20.1 BTU/hr 1 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 1 1 1 9 2 7 1 2 2 0 2 8 1 3 2 1 2 9 1 4 2 2 3 0 1 5 2 3 3 1 F 0 O K F 1
Outputs Voltage category Operating voltage range Output delay time (24V to 0V DC transition) OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max
ELECTRONIC FUSING
161
Attribute On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Load current, min Isolation voltage
1756-OV32E 350 mV DC @ 0.5 A 0.5 A @ 50 C (122 F) linear derating 0.35 A @ 60 C (140 F) 8 A @ 50 C (122 F) linear derating 5 A @ 60 C (140 F) 16 A @ 50 C (122 F) linear derating 10 A @ 60 C (140 F) 2 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 2 mA per output 250V (continuous), basic insulation type, outputs-tobackplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4 T4 None (open-style)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges
162
1756-OV32E 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-OV32E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
163
1756-OW16I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
Simplified Schematic +24V Display ControlLogix Backplane Interface L1 OUT
1756-OW16I Isolated Wiring L1-0 L1-1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 L1-5 L1-6 L1-7 Jumper Bar L1-8 (Cut to Length) L1-9 L1-10 L1-11 Nonisolated L1-12 Wiring L1-13 L1-14 L1-15 L1-15 L1 Not Used Daisy Chain to Other RTBs L1-0
2 4 6 8 10 1 3 5 7 9
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used L2
L2-0 L2-2
DC-4 (-)
Attribute Outputs
1756-OW16I 16 N.O. individually isolated UL C300 R150 5...150V DC 10...265V AC 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 10 ms max 10 ms max 150 mA 150 mA 4.5 W @ 60 C (140 F) 15.35 BTU/hr 1.5 mA per point 100 m 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive
RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K
Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life
164
1756-OW16I 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
165
Certification(1) UL CSA
1756-OW16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
166
1756-OX8I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
1756-OX8I
OUT-0 N.C.
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
OUT-0 N.O.
OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used L2
L2-0
DC-2 (-)
Attribute
1756-OX8I 8 N.O. 8 N.C. individually isolated (2 points/group) UL C300 R150 5...150V DC 10...265V AC @ 4763 Hz 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 13 ms max 13 ms max 100 mA 100 mA 3.1 W @ 60 C (140 F) 10.57 BTU/hr 0 mA 100 m @ 6V 1 A 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive 250V (continuous), basic insulation type, outputs-tobackplane, and output-to-output Routine tested @ 1350V AC for 2 s
RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O K
Output delay time OFF to ON ON to OFF Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state leakage current per point, max Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Isolation voltage
167
1756-OX8I 1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 1(2) T4A None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz 3 kV
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
168
Certification(1) UL CSA
1756-OX8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers
C-Tick FM TV
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: Capable of SIL 2
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
169
1756-CFM
ControlLogix configurable flow meter module
1756-CFM Standard Magnetic Pickup
2 1
Z0 12-24V DC
4 3
Z1 12-24V DC Z1 5V DC
6 5
Z0 12-24V DC
4 3
Z1 12-24V DC Z1 5V DC
6 5
Z0 5V DC Z0 Return
8 7
Z0 5V DC Z0 Return
8 7
Z1 RET F1
10 9
Z1 RET F1
10 9
Input Device
+
Shield Ground
F0 F0 Return
12 11
F0 F0 Return
12 11
Customer VCC
+
Load
20
Customer VCC
This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds. You must use RSLogix 5000 software to choose the appropriate threshold level for your specific application. If separate power sources are used, do not exceed the specified isolation voltage.
If separate power sources are used, do not exceed the specified isolation voltage.
170
12-24V DC
1 3 5
Z0 12-24V DC
4
Z1 1224V DC Z1 5V DC
Z0 5V DC
6
Shield Ground
Z0 Return
8 7
Z1 RET F1
10 9
Input Device
+
Shield rGound
F0 F0 Return
12 11
Customer VCC
Detectors 1 and 2 must be wired in parallel. Customer VCC may be used to power detectors. In this case, though, the maximum current on the wiring arm must be less than 4 A. The wiring example above shows a 12-24V DC standard prover connected to the module. If you use a 5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such as Z0 5V DC). If separate power sources are used, do not exceed the specified isolation voltage.
Attribute
1756-CFM 4 (2 per channel) 2 Flowmeter (F) inputs used for all modes 2 Gate inputs used in Totalizer mode for prover/store count 2 current sourcing 300 mA 6 mA 1.7 W 6 W @ 60 C (140 F) 20.4 BTU/hr 250V (continuous), reinforced insulation type, I/O-tobackplane 250V (continuous), basic insulation type, I/O group-togroup Routine tested at 1900V DC for 2 s
METERING
F 0 Z 0 O O 0 1 F 1 Z 1 O K
Outputs Current draw at 5.1V Current draw at 24V Backplane power, total Power dissipation, max Thermal dissipation Isolation voltage
DC I/O
1756-TBNH 1756-TBSH
171
1756-CFM 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2 on signal ports 1 on power ports(2) T4 None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Attributes Inputs Inputs per channel Input type Count range, max Input frequency, max Flowmeter input voltage
Value 4 (2 per channel) 2 Flowmeter (F) inputs used for all modes 2 Gate inputs used in Totalizer mode for prover/store count IEC Type 2 (630 mA) @ 24V DC 2,147,483,647 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz) 30V, selectable input thresholds of 50 mV, 1.3V and 4V: 30V peak unterminated open circuit voltage, magnetic pickup TTL compatible, input voltage >1.3V DC is Logic 1 and -0.71.3V DC is Logic 0 1224V DC powered preamp output, 4V DC threshold 5 k 30% resistive Firmware selectable: High-speed 100 kHz or low-pass filter for frequencies < 70 Hz 5V operation: 4.55.5V DC 12/24V operation: 1031.2V DC 4 mA 15 mA Software selectable User selectable
Flowmeter input impedance Filtering (inputs F0 & F1) Gate input voltage range Gate input on-state current, min Gate input on-state current, nom Mechanical filter debouncing (Z0 & Z1 Inputs) Input sampling period
172
Attribute Outputs Output voltage source Output voltage range, nom Output type Output Current per point Surge current Off-state leakage current, max On-state voltage drop, max Output control Output switching time Overload current Output short circuit protection Output reverse polarity protection
Value 2 current sourcing Customer supplied 5V operation: 4.55.5V DC for 320 mA load per point 12/24V operation: 1031.2V DC for 40 mA1 A load per point IEC 1A 24V DC 1 A @ 1031.2V DC 20 mA @ 4.55.5V DC(1) 2 A for 50 ms, repeatable every 2 s < 300 A @ 31.2V DC 0.6 x current Any number of outputs is assignable to any of 2 flowmeter channels Each output can have 2 turn-on and turn-off preset values < 50 s turn on, <300 s turn off Outputs triggered by Total; all other turn-on and turn-off times <1ms Electronic (< 4A) Electronic (No indication of fault. Remove overload and toggle output on/ off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1k Hz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
173
Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
1756-CFM 4 kV at 5 kHz on unshielded output and power ports 4 kV at 5 kHz on shielded input ports 1 kV line-line (DM) and 2 kV line-earth (CM) on unshielded output and power ports 2 kV line-earth (CM) on shielded input ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Certification(1) UL CSA
1756-CFM UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
174
1756-HSC
ControlLogix high-speed counter module
1756-HSC to Allen-Bradley 845 Incremental Encoder
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12..24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V)
Whit
Z1 (5V) Blue Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) Black A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+) 12...24V
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
Jumper
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) Black A0 (12...24V) A0 (5V) Blue A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10
1 3 5 7 9
Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35
12...24V DC
12...24V DC Return
175
Attribute
1756-HSC 2 3 (A, B, Z for gate/reset) 4 (2 points/group) 5V operation: 4.55.5V DC 12/24V operation: 1031.2V DC 300 mA 3 mA 1.9 W 5.6 W @ 60 C (140 F) 19.1 BTU/hr 125V (continuous), basic insulation type, input group-to-backplane 30V (continuous), basic insulation type, input group-to-input group Routine tested at 1900V DC for 2 s
COUNTER
A B Z 0 0 0 O O 0 1 A B Z 1 1 1 O K O O 2 3
Number of counters Inputs per counter Outputs Operating voltage range Current draw at 5.1V Current draw at 24V Backplane power, total Power dissipation, max Thermal dissipation Isolation voltage
DC I/O
Removable terminal block Slot width Wire size Wire category North American temperature code IEC temperature code Enclosure type
1756-TBCH 1756-TBS6H 1 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1) 2 on signal ports 1 on power ports(2) T4 T4 None (open-style)
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Value 2 3 (A, B, Z for gate/reset) 1 MHz in counter modes (A input) 500 kHz in rate measurement mode (A input) 250 kHz in encoder mode (A/B inputs, X1 or X4) 70 Hz with filter enabled 016, 777, 214 1000 kHz 4 mA 15 mA
Count range Counting frequency, max Input current, min Input current, nom
176
Attribute Outputs Output delay time OFF to ON ON to OFF Off-state leakage current per point, max On-state voltage drop, max Output current rating, per point Current limit Surge current per point Load current per point, min Output control Short circuit protection Reverse polarity protection
Value 4 (2 per common) 20 s nom/50 s max 60 s nom/300 s max 300 A 0.55V 20 mA @ 4.55.5V DC 1.0 A @ 1031.2V DC <9A 2 A for 10 ms every 1s @ 60 C (140 F) 5V operation: 3 mA 12/24V operation: 40 mA Any number of output channels is assignable to each counter channel Each output can have 2 turn-on and turn-off preset values Electronic (Remove overload and toggle On/Off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on power ports 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on power ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 2 kV line-earth (CM) on shielded ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
177
Certification(1) UL CSA
1756-HSC UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
178
1756-PLS
ControlLogix programmable limit switch module
1756-PLS Inputs - Left Side
2 1
OUTPUT 0
4 3
INPUT 0 INPUT 1
6 5
OUTPUT 8
4 3
INPUT 8 INPUT 9
6 5
OUTPUT 1 OUTPUT 2
8 7
OUTPUT 9
INPUT 2 INPUT 3
10 9
+ _
10...30V DC
OUTPUT 10
8 7
INPUT 10 INPUT 11
10 9
OUTPUT 4 OUTPUT 5
16 15
OUTPUT 12 OUTPUT 13
INPUT 5 INPUT 6
18 17
INPUT 13
16 15
OUTPUT 6 OUTPUT 7
20 19
+ _
OUTPUT 14
18 17
INPUT 14 INPUT 15
20 19
DC PWR 4...7
DC COM 12...15
+ _
1756-PLS Resolver
Do Not Use
4 3
Do Not Use
F (S3)
Sine +
Do Not Use
16 15
Sine
18 17
Cosine + Cosine
A (R1) B (R2)
Reference
179
OUT 0 1 2 3 4 5 6 7
O IN 0 1 2 3 4 5 6 7 K
O K
OUT 8 9 10 11 12 13 14 15
O IN 8 9 10 11 12 13 14 15 K
DC I/O
RESOLVER
DC I/O
1756-PLS Left section: 2 groups of 4 outputs and 4 inputs each Center section: resolver interface and I/O control Right section: 2 groups of 4 outputs and 4 inputs each 1000 mA 125 mA 22.62 W @ 30 C (86 F) 18.22 W @ 60 C (140 F) 25.7 W @ 30 C (86 F) 21.3 W @ 60 C (140 F) 77.23 BTU/hr @ 30 C (86 F) 62.2 BTU/hr @ 60 C (140 F) 87.74 BTU/hr @ 30 C (86 F) 72.72 BTU/hr @ 60 C (140 F) 250V (continuous), basic insulation type, I/O-tobackplane, I/O group-to-group, resolver-to-backplane, and resolver-to-I/O Routine tested at 1900V DC for 2 s
Current draw at 5.1V Current draw at 24V Power dissipation, nom Power dissipation, max Thermal dissipation, nom Thermal dissipation, max Isolation voltage
Requires 3 RTBs: 1756-TBNH or 1756-TBSH 3 Center: Alpha Cable #6054C (use 3 of 4 twisted pairs) Left and right: 0.33... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max(1)
Wire category North American temperature code IEC temperature code Enclosure type
(1) Maximum wire size requires extended housing, catalog number 1756-TBE. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
180
Attribute Resolver location Compatible resolver Resolver interface Reference voltage Reference frequency Digital resolution Angular resolution Digital count range Maximum tracking rate Repeatability Accuracy
Value Center section Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options) 2V rms, reference output (differential pair) 2V rms, sine and cosine inputs (2 differential pairs) 2V rms 20% 5 kHz 20% 12 bits (4096 counts from hardware) 0.088 /bit 04095 (decimal) 1800 RPM 0.0488% of full scale 0.0976% of full scale
Attribute Inputs Voltage category Operating voltage range Input delay time OFF to ON
Value 16 (2 groups of 4 per I/O section) 12/24V DC 10.831.2V DC < 15 s @ 30 C (86 F) < 150 s @ 60 C (140 F) < 30 s @ 30 C (86 F) < 200 s @ 60 C (140 F) 1.86 W @ 60C (140 F) 2.8 W @ 60C (140 F) 6.35 BTU/hr 9.56 BTU/hr 10V DC 10.8...26.4V DC 31.2V DC 5V DC 1.5 mA 3 mA 10 mA 3.3 k @ 24V DC Yes
ON to OFF Power dissipation, inputs, nom Power dissipation, inputs, max Thermal dissipation, inputs, nom Thermal dissipation, inputs, max On-state voltage, min On-state voltage, nom On-state voltage, max Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Reverse polarity protection
181
Attribute Output delay time OFF to ON ON to OFF Power dissipation, outputs, nom Power dissipation, outputs, max Thermal dissipation, outputs, nom Thermal dissipation, outputs, max Off-state leakage current per point, nom Off-state leakage current per point, max On-state voltage, min On-state voltage, nom On-state voltage, max Output voltage drop, max Current per point, max Current per group, max Current per module, max Current limit Surge current per point Load current per point, min Output switching time Short circuit protection Reverse polarity protection
Value < 15 s @ 60 C (140 F) < 25 s @ 60 C (140 F) 5.4 W @ 30 C (86 F) 3.2 W @ 60 C (140 F) 6 W @ 30 C (86 F) 3.8 W @ 60 C (140 F) 18.43 BTU/hr @ 30 C (86 F) 10.93 BTU/hr @ 60 C (140 F) 21.48 BTU/hr @ 30 C (86 F) 11.93 BTU/hr @ 60 C (140 F) <10 A @ 60 C (140 F) 300 mA @ 60 C (140 F) 10V DC 10.826.4V DC 31.2V DC 0.55V DC 1 A @ 30 C(1) (86 F) 4 A @ 30 C(2) (86 F) 8 A @ 30 C(3) (86 F) < 4A 2 A for 10 ms every 1s @ 60 C (140 F) 40 mA Switching 1 A @ 24V DC Electronic (No indication of fault. Remove load and toggle on/off to restore.) Yes, current limited. (If wired incorrectly, outputs may be permanently disabled.)
(1) Derate 16.7 mA/ C above 30 C (86 F): 0.5 A @ 60 C (140 F). (2) Derate 66.8 mA/ C above 30 C (86 F): 2 A @ 60 C (140 F). (3) Derate 133.6 mA/ C above 30 C (86 F): 4 A @ 60 C (140 F).
Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating)
182
Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3
1756-PLS 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz 4 kV at 5 kHz on unshielded I/O and power ports 2 kV at 5 kHz on shielded resolver ports 1 kV line-line (DM) and 2 kV line-earth (CM) on unshielded I/O and power ports 2 kV line-earth (CM) on shielded resolver ports 10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6
Certification(1) UL CSA
1756-PLS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
183
Place 1756 I/O modules in any slot in a 1756 chassis. Each chassis requires a power supply.
Product Chassis Power supply, standard Power supply, redundant Cat. No. 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 1756-CPR2 cable
For more information on chassis, see ControlLogix Chassis Specifications Technical Data, publication 1756-TD006. For more information on power supplies, see ControlLogix Power Supply Specifications Technical Data, publication 1756-TD005.
184
Wiring Systems
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of: interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.
RTB Pre-wired Cable Connector I/O Module Factory-wired Field Wiring Interface Module (IFM)