Vous êtes sur la page 1sur 2

SMA Solar Technology AG | Sonnenallee 1 | 34266 Niestetal | Germany Phone: +49 561 9522-0 | Fax: +49 561 9522-100

| Internet: www.SMA.de | E-mail: info@SMA.de Register court: Amtsgericht Kassel HRB 3972

Declaration of Conformity according to AS4777.2 and EN 60950


The Sunny Mini Central SMC 6000TL, SMC 7000TL, SMC 8000TL grid connected inverter complies with the following required standards Grid Connection of Inverter Systems in Australia:

Standards AS4777.2 clause 4.1

Test type General

Comments

AS4777.2 clause 4.2 AS4777.2 clause 4.3 AS4777.2 clause 4.4 AS4777.2 clause 4.5

Compatibility with electrical installations Power flow direction Power factor


In either direction.

Electrical safety in accordance to IEC 60950-1:2001, EN 60950-1:2001, AS/NZS 60950.1:2003 + complies Amdt 1:2006 + Amdt 2:2008 + Amdt 3:2008. The inverter has voltage and frequency in accordance with AS 60038 (230VAC, 50Hz). complies noted complies complies

Harmonic currents

Both, SMC 6000TL and SMC 8000TL fulfil the requirements. Thus, SMC 7000TL can be seen to fulfil the requirements as well. Both, SMC 6000TL and SMC 8000TL fulfil the requirements. Thus, SMC 7000TL can be seen to fulfil the requirements as well.

Voltage fluctuations and flicker AS4777.2 clause 4.6

AS4777.2 clause 4.7

Impulse protection

Maximum permissible voltage fluctuation (expressed as a percentage complies of nominal voltage at 100% power) and flicker. Less than 16A per phase according to AS/NZS 61000-3-3, more than 16 A per phase according to AS/NZS 61000-3-5. After applying the impulse, the test inverter was tested for normal operation. The inverter operated normal. There is no significant change in the performance of the test inverter. The test was performed with the SMC 8000TL since it has the highest output power. The results are applicable for the hardware-identical SMC 7000TL and SMC 6000TL. This test result can be seen as the worst case dc-injection since the SMC 8000TL has the widest current range. The result is applicable for the SMC 7000TL and SMC 6000TL. The unit itself was reviewed to IEC 60950-1 inclusive the datalogging. complies

AS4777.2 clause 4.8

Transient voltage limits

complies

AS4777.2 clause 4.10

Data logging and communication devices

complies

AS4777_EN60950_SMC60-70-80TL-ZEN093010

AS4777.2 clause 4.9

complies

1/2

DC current injection

Declaration of Conformity according to AS4777.3


Standards AS4777.3 clause 5.1 General and Safety Requirements and Grid Protection Requirements General Comments

AS4777.3 clause 5.2

Disconnect device

The device includes an automatic disconnecting facility for photovoltaic installations (under/ over voltage/ under/ over frequency and anti islanding). There is no galvanic isolation provided between input and output of the inverter. Therefore, the unit is switched off by two mechanical relays in series.

complies

complies

Voltage and frequency limits (passive anti islanding protection) AS4777.3 clause 5.3

Active anti islanding protection AS4777.3 clause 5.5 AS4777.3 clause 5.7

After the SMC 8000TL was tripped on under/over voltage and under/over frequency, it reconnected after 60 seconds when voltage complies and frequency were returned to the nominal value. Both, SMC 6000TL and SMC 8000TL are well within the specification. Thus, the SMC 7000TL can be seen to fulfil the requirements as well. Test circuit according to AS 4777.3. Grid voltage equal to nominal load, load +/-5% and load match plus 10%. Both, SMC 6000TL and complies SMC 8000TL are well within the specification. Thus, the SMC 7000TL can be seen to fulfil the requirements as well. Settings only available with password for the service personal. A range of local load conditions as required i.e. light electronic load, load match and load match plus 10% was tested. The inverters tripped within the required time (less than 2 seconds) under all local load conditions. Both, SMC 6000TL and SMC 8000TL are well within the specification. Thus, the SMC 7000TL can be seen to fulfil the requirements as well. complies

Security of protection settings

Compliance with grid protection requirements AS4777.3 clause 5.8

complies

Conclusions: The SMC 6000TL, SMC 7000TL, SMC 8000TL grid connected inverter was tested for compliance with requirements of theAustralian guidelines for Grid Connection of energy systems via inverters. Based on the testresults for the tested inverter it complies with the requirements of AS4777 parts 2 & 3 for Grid Connection of Energy Systems via Inverters. Test House Details: Bureau Veritas E&E Product Services GmbH Businesspark A96, 86842 Trkheim Germany

Product Family SMC 6000TL / 7000TL / 8000TL We hereby declare that the Solar Inverters SMC 6000TL, SMC 7000TL and SMC 8000TL technically are members of one single product family and have identical technical features. The compliance of the SMC 8000TL according to Australian Standards AS 4777 was tested at Bureau Veritas E&E Product Services GmbH and can be reviewed in the test report 08TH0002-AS4777_0. Niestetal, 22.07.2009 SMA Solar Technology AG

i. V. Tobias Henne (Director, Product Management Solar Inverters)

AS4777_EN60950_SMC60-70-80TL-ZEN093010