To Read and Download all our Products catalogs: http://www.scribd.com/sunil_jha To Read and Download Online our MV-VFD Catalogs http://www.scribd.com/doc/63980384/MV-Drives To Watch Online Video Presentation on YouTube: http://www.youtube.com/watch?v=W2AVlS4-0SM To Read MV-VFD Presentation Online on our website: http://eaglewanlida.com/vfdpresentation.aspx To Read and Download online our relays catalog: http://www.scribd.com/doc/73143176/MMPR-620-HB-Micro-Computer-M otor-Protection-and-Monitoring-Device

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Manufactured by ZuHai Wanlida Electric co Ltd, China.

Sole Distributor in India: EAGLE TECHNOLOGY

Prepared by Proofed by Approved by

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Foreword
1. Model description
The structure type of MTPR-630Hb series protection is Hb, microcomputer transformer differential protection device.

2.

References
General specification for static protection, security and automatic equipment, DL 478-2001 Technical code for relaying protection and security automatic equipment, GB/T 14285-2006 Design code for relaying protection and automatic device of electric power installation, GB50062-92

3.

Caution
The appearance should be inspected before power is applied, to ensure that the panel is OK without scratch, the screws are tightened, the device is grounded firmly, all screws of plug-ins are tightened and in good contact. When power is applied, the Run indicator on the panel should flash, nixie tube and LCD display primary differential current in cycle. The operation circuit in the device fits DC power only, if it is to connect with AC power, the power should be rectified. It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device. It is prohibited to do binary output test when the device is running with primary equipments.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

1. Product description
1.1 Scope of application
MTPR-630Hb microcomputer transformer main protection device can protect various down step and up step three-winding transformers and other transformers in substation under 110KV.

1.2 Function and specification 1.2.1 Protective function


Differential instantaneous over-current protection Complex percential restraint differential protection Differential over-current alarm CT failure alarm and block function Body protection

1.2.2 Auxiliary Function


Harmonic spectrum analysis Phase display Fault recorder Alarm on device self-test fault Protective settings read and modified by remote Provide ethernet print function(manual print setting value, manual/auto print reports).

1.2.3 Communication capability


2 standard RS485 multipoint communication ports 2 industrial ethernet ports Supports single, dual network communication, it is fully qualified for network redundancy and backup IEC-60870-5-103 RS485 communication mode , IEC-60870-5-104 industrial ethernet communication mode standard communication protocol

1.2.4 GPS clock synchronization function


The device is able to receive GPS clock minute synchronization (or second synchronization) through RS485 differentiate voltage, and it can be done with monitoring system to accomplish GPS precise clock synchronization.

1.2.5 Device specifications


32-bit DSP microprocessor Real-time multi-task operating system and C++ program techniques, realizing online

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

programming Double-screen display (LCD display and nixie tube display), easy for inspection power quality analysis capabilities, complete harmonic analysis function Excellent hardware interchangeability, easy user maintenance and reduced quantity of spare parts Protection output relays can be configured flexibly for user convenience Using a 6U, 19/3 standard enclosure in a rear plug-in structure; the device can be installed in site on a switchboard or combined in a centralized manner

1.2.6 Main technical specifications Rated data


Power supplyDC/AC 86265V Operating voltageDC 220V or DC 110V AC current5A or 1A Frequency50Hz

Power consumption
DC circuit 10Wnormal operation15Wprotection operation. AC current circuit1VA/phaseIn=5A0.5VA/phaseIn=1A.

Overload capability
Protection current: 2 times rated current continuous operation 10 times rated currentallowed for 10 s 40 times rated currentallowed for 1 s

Range and error of setting value


Maximum range of setting value: Current component0.1In20In Time component0.00s100.00s Error of setting value3% setting Angle setting value2 Whole-group operation time (including relays intrinsic time): Intrinsic operation time of differential instantaneous overcurrent protection times 2 the setting value not greater than 30ms. Intrinsic operation time of percentage differential protection2 times the setting value not greater than 40ms.

Capacity of trip/closing output contact


Can be connected to DC 250V8A for prolonged periods.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

GPS time synchronization error


Synchronization error 2ms.

Environmental conditions
Ambient temperature Operating-20+55. Storage-25+70rainproof and snow-proof rooms with relative humidity not greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas; no excitation quality is applied at the limits, the device shall not have any irreversible change; after temperature restoration, the device shall operate properly. Relative humidity: The average relative humidity of the most humid month shall not be greater than 90%, the average minimum temperature of this month not lower than 25 and there shall be no surface condensation; at the highest temperature of +40, the average maximum humidity shall not exceed 50% Atmospheric pressure80kPa110kPa(below relative altitude of 2km)

1.2.7 Hardware structure


The device uses a 6U, 19/3 standard enclosure, with aluminum alloy casing and installed by overall embedding. The display panel is mounted in the front, and the other plug-in modules are rear mounted. From the rear view, the power, I/O, CPU and AC plug-in modules are from the left to the right.

External dimensions and boring diagram

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010 Structural and dimensional diagram Boring diagram for installation

Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove the stents; installed the device on the screen from the front and push until close to the fixed plate; install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of stent1, and then screwed into stent 2 and tighten screw; the stents from up and down are installed in the same way; use grounding screws to connect grounding line.

2. Functional Description
2.1
Operating criterion Idif>Isd In which I dif

Differential instantaneous over-current protection


N

I
i 1

N is the number of transformer windingIi is rated frequency component of same name phase current

Isd Differential instantaneous over-current setting. Set according to the maximum unbalance current and magnetizing inrush current. When escaping external fault. This protection provides hard strap control function. Soft strap can control the ON or OFF of the protection. When serious short-circuit fault occurs in the transformer, differential current will increase sharply. When the current exceeds the setting value, protection operates instantaneously to protect transformer.
Differential instantaneous control word ON Hard plate function OFF Differential protection plate closed &

EAGLE TECHNOLOGY

Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 Protection output & IdaIsd E-mail: eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com
IdbIsd IdcIsd

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Fig.2-1 Differential instantaneous over-current protection operation diagram

2.2

Complex percential restraint differential protection

The same as with the differential instantaneous protection, this protection also provides hard strap control function. Soft strap can control the on or off of the protection. This protection uses Three Segments Polyline Percentage Differential principle. The operating formula is as follows 1. When Ires < Ir1 IdId0 2. When Ir1<Ires < Ir2Id Id0Kres1 * ( Ires - Ir1) 3. When Ires >Ir2Id Id0 Kres1 (Ir2 - Ir1)Kres2 *Ires Ir2 If any of the above conditions is met, and harmonic does not retainpercentage differential protection operates. Among the formulaId is differential currentId0 is setting value of differential threshold currentIres is restraint currentIr1 is the restraint current of turning-point1 Ir2 is the restraint current of turning-point 2, Kres1 is percentage coefficient 1Kres2 is percentage coefficient 2. Operating currentId =I1+I2+I3+I4 Restraint currentIres = | |Id|-|I1|-|I2|-|I3|-|I4| | In the formulaI1, I2, I3, I4 are secondary current of side 1,2,3,4 CT of the transformer (the equivalent current according to transformer wiring method after correction). The current transformers of the two sides are wired in Y mode and points to transformer. The device can adjust the current amplitude and phases of the two sides by setting unbalance coefficient and wiring mode. Percentage differential protection can make sure when external short-circuit occurs; protection will not operate; while protection is high sensitive to internal fault.
Id

Id0 Ires

Ir1

Ir2

Fig.2-2 Differential operation curve

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Through control word, protection can choose whether to block through CT failure. Harmonic restraint: three-phase cross restraint is applied, when the following formula is met, protection will operate

Ih<KxbId
Ih 2nd order harmonic quantity of differential current Kxb secondary harmonic restraint coefficient, set according to the magnetizing inrush current when escaping no-load closing of the transformer.

2.3

Differential over-current alarm

Max{Ida,Idb,Idc}Iset Which Iset is the differential over-current setting, and it is settable, when differential exceeds the setting, the device will send off differential over-current alarm after 10s delay.

2.4

CT failure alarm and block function

When in normal operationthe sum of three phase current of each side is zero. When one phase CT failure occurs, the sum of three phase current is not zero. To distinguish from ground fault, the following should be judged: 1) Among three phase current, the minimum one is zero. 2) The maximum phase current is more than zero and less than CT failure block current. When detecting CT failure, block percentage differential protection according to on/off set by control words and delay sending alarm signal, and show the time of failure. CT failure detection function can be on/off according to control words. When differential instantaneous over-current protection operates, CT failure block protection will be off.

2.5

Body protection

Body protection of this device has body heavy gas, voltage regulation heavy gas and pressure releasethere is a standby non-electric quantityit corresponding operating terminals directly trip through the hardware of the device. High temperature protection, lost of cooling control power, body heavy gas, voltage regulation heavy gas, pressure release, body light gas, voltage regulation light gas and oil low signal are connected to the device through binary input. According to the device control word, the protection can be set, trip and send signal, in which, which, high temperaturehigh oil temperatureprotection and lost of cooling control power can set delay. Lost of cooling control power has long delay and short delay. Long delay corresponds to high temperature signal not presents, short delay corresponds to high temperature signal presents. The operation diagram of lost of cooling control power is as

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

follows:

No high temperature signal Cooling control power loss signal Cooling control power loss control word ON & Long time delay Protection output High temperature signal Cooling control power loss signal Cooling control power loss control word ON & Short time delay

Fig.2-3 Lost of cooling control power operation diagram

2.6

Fault Record

It records the current waveform sampled by the device, for more information please refer to communication code table.

3. List of parameters and setting values


3.1 System parameters
Range Basic parameters setting Secondary rated current of side1In Secondary rated current of side2 Secondary rated current of side3 Secondary rated current of side4 0-1 0-1 0-1 0-1 Set step:1factory default 0005A011A Set step:1factory default 0005A011A Set step:1factory default 0005A011A Set step:1factory default 0005A011A For harmonic calculation, select the corresponding Selection of harmonic calculation channel 0-12 reference quantity 0harmonic calculation function off 1:Ia1,2:Ib1,3:Ic1,4:Ia2,5:Ib2,6:Ic2,7:Ia3,8:Ib3,9:Ic3,10: Ia4,11:Ib4,12:Ic4 Parameters Description

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Parameters Wave Record

Range 0-1

Description Set step:1factory default 000off01on 0: External transform,1: Y/Y/Y/-11,2: Y/Y//-11, 3: Y///-11,4: Y/Y/Y/-1,5: Y/Y//-1, 6: Y///-1,7: Y/Y/Y/Y-12,8: //Y/Y-11 (factory default 0when choose Y/Y/Y/Y-12 wiring mode program will act as 11 oclock mode so as to the eliminate zero sequence influence)

Transformer Mode

0-8

Hardword on/off

0-1

Set step:1factory default 000Off01On balance coefficient setting

balance coefficient of side 1 balance coefficient of side 2 balance coefficient of side 3 balance coefficient of side 4

0.05-10.00 0.05-10.00 0.05-10.00 0.05-10.00

Set step:0.01factory default 1 Set step:0.01factory default 1 Set step:0.01factory default 1 Set step:0.01factory default 1 is used to remove the influence of unbalance current.

In whichbalance coefficient

The specific calculation is as follows 1 Calculate first rated current of each of the transformer

1n

I
which

1n

S 3U
n

is the maximum rated capacity of the transformer

is the rated voltage of

each side of the transformerThe actual operating voltage should be subject to. 2 Calculate secondary rated current of each side of the transformer

2n

2n

I K K
1n CT

con

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

which

CT

is CT ratio of each side

con

is CT secondary wring coefficientY wring

side of the transformer is

3 wring side is 1.

3 It should be referenced to I sidecalculate each side balance coefficient transformerside m

b, m

of the

K
which

b, m

I I

2 n ,1 2 n ,m

U K K U K K
n ,m n ,1 CT , m CT ,1

con,1

con, m

n ,1

CT ,1

K
n, m

con,1

are rated voltage, CT ration and CT secondary wring ,

coefficient of side

CT , m

con, m

are respectively rated voltage, CT ration

and CT secondary wring coefficient of side M

3.2

Setting value
Rang Description Differential instantaneous over-current protection Instant Diff. Percentage differential 1/0 1/0on/off(factory default: off)

Setting value

Protection control word

protection Percent Diff. Differential current over-current alarm Diff.C OverLimit CT Failure Alarm CT Failure Lock High temperature protection High Temperature Lost of cooling control power Cooling Lost

1/0

1/0on / off (factory default: off)

1/0 1/0 1/0 1/0

1/0on / off (factory default: off) 1/0on / off (factory default: off) 1/0on / off (factory default: off) 1/0on / off (factory default: off)

1/0

1/0on / off (factory default: off)

Mutation startup Abrupt Current Starting current Startup Current 0.100.00A Set step:0.01A(factory default 1A)

Differential instantaneous over-current protection Instant Diff.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Setting value Differential instantaneous over-current setting Inst.Current

Rang 0.1-20In

Description Set step:0.01A(factory default 20In)

Percentage differential protection Percent Diff. Percentage differential threshold current Percent Diff.Sill) Percentage differential restraint turning-point point1 Per. Res. Inflex. 1 Percentage differential restraint turning-point2 Per. Res. Inflex. 2 Percentage restraint coefficient1 Restraint Coef. 1 Percentage restraint coefficient2 Restraint Coef. 2 Secondary harmonic restraint coefficient Sec.Res.Coef. 0.00-1.00 Set step:0.01(factory default 1.00) 0.1-20In Set step:0.01A(factory default 20In) 0.1-2In Set step:0.01A(factory default 2In) 0.1-2In Set step:0.01A(factory default 2In)

0.00-1.00

Set step:0.01(factory default 1.00)

0.00-1.00

Set step:0.01(factory default 1.00)

Differential over-current alarm Diff.C Overlimit Differential over-current setting Diff.C OL Value (0.12)In Set step:0.01A(factory default 2In)

CT failure alarm/block CT Failure Block current Overload Current Delay setting Time Set 0-10A 0.50-15.00s Set step:0.01A(factory default 10A) Set step:0.01s(factory default 15s)

High temperature protection High Temperature Delay setting Time Set 0-9999s Set step:1s(factory default 20s)

Lost of cooling control power Cooling Lost Long Delay setting Long Time Set Short Delay setting Short Time Set 0-9999s 0-9999s Set step:1s(factory default 100s) Set step 1s(factory default 20s)

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

3.3

Monitoring analog quantities


UnderCurrent1~ 4menu inState Displaymonitor analog quantity.press the

, keys to flip over. The precision of the device has been calibrated. The protection current is calibrated at double the rated current, and the measuring current is calibrated at a time the rated current. The list and description are as follows: Analog quantity Analog quantity name Test method terminal Terminals D01, D02 Terminals D03, D04 Terminals D05, D06 Terminals D07, D08 Terminals D09, D10 Terminals D11, D12 Terminals D13, D14 Terminals D15, D16 Terminals D17, D18 Terminals D19, D20 Terminals D21, D22 Terminals D23, D24 1 side protection phase A current (Ia1) 1 side protection phase B current (Ib1) 1 side protection phase C current (Ic1) 2 side protection phase A current (Ia2) 2 side protection phase B current (Ib2) 2 side protection phase C current (Ic2) 3 side protection phase A current (Ia3) 3 side protection phase B current (Ib3) 3 side protection phase C current (Ic3) 4 side protection phase A current (Ia4) 4 side protection phase B current (Ib4) 4 side protection phase C current (Ic4) Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1% Add double the rating, displayed deviation not exceed 1%

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

3.4

Check of binary input quantity


Under Binary Inputmenu inState Displaymenucheck binary input, press the

, keys to flip over. Binary input terminal B01 Binary input common terminal used to be connected with the negative pole of DC220 and DC110V external power B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 C12 C13 C14 C15 C16 Body heavy gas signal Voltage regulation heavy gas signal Pressure release signal Standby non-electric quantity signal Body light gas signal Voltage regulation light gas signal Oil temperature high Oil low signal Lost of cooling control power Binary input 10 Binary input 11 Binary input12 Positive pole of self-generated DC 24V Binary input 13 Binary input 14 Binary input 15 Differential protection strap Binary input common terminal (+24V) Connect C16 to C12, C13, C14, C15, underBinary Inputmenu inState Display, the input state can be seen. Binary input can be connected to external 220V or110V DC power. Connect negative pole to terminal B01 connect positive pole to terminals B02B13 under Binary Input menu inState Display, the input status can be seen. This device also provides 24V DC power. If a self-generated power is used, terminal B14 can be connected to terminals B02 B13 under Binary Input menu inState Display,the input status can be seen. For the choice of input power, please specify in the order. Factory default is external DC220V. Binary input name Check method

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

3.5

Check of binary output quantity


UnderOutput Test menu monitor binary output. Press the , keys to flip over.

Binary output terminal B15-B16 B17-B18 B19-B20 B21-B22 B23-B24 B25-B26 B27-B28 B29-B30 B31-B32normal open B32-B33normal close B34-B35normal open B35-B36normal close

Binary output name Device fault signal Protection operation signal Alarm signal Differential trip side 1 Differential trip side 2 Differential trip side 3 Differential trip side 4 Differential trip side standby Output terminal 9

Check method

Enter On/Off menu, use +, -keys to operate. The corresponding terminals should be connected. B31-B32 and B34-B35 are normal open terminals that should be closed. B32-B33 and B35-B36 are normal closed terminals that should be connected.

Output terminal 10

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

4. Operation instructions
4.1
Control panel of device

128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation; the LCD will be illuminated automatically when any key is pressed or in case of protection trip or alarm.) Signal indicator: run, communication, operation, alarm, non-electric, fault (device fault) Open, Close position indication: not used in this device Key pad: Cancel, -, +, Enter, Revert The 6-bit nixie tube displays the primary protection value in real timeIa1, Ib1, Ib1, Ia2, Ib2, Ic2, Ia3, Ib3, Ic3, Ia4, Ib4, Ic4. Noteprotection Ia11AAprotection Ib11bA, protection Ic1 1CA protection Ia22AAprotection Ib22bA, protection Ic22CA protection Ia33AAprotection Ib33bA, protection Ic33CA

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

4.2

Instructions for use of key pad and LCD display During the devices normal operation, it will display the measuring current, power,

time in cycle. Press the Enter key to enter the main menu, which is a multi-level tree menu. Press the , keys to move the cursor to the desired entry, press the Enter key to enter this entry, and press the Cancel key to return to the next higher level of screen. If this screen is still a menu, continue to press the , key to select the desired entry, press the Enter key to enter the next level of screen, and press the Cancel key to return to the next higher level of menu. If there is no menu screen, be sure to press the Cancel key to return to the next higher level of menu. The main menu is shown at the center of the following figure, with the corresponding submenus on both sides. The main interface displays each side protection current in turn.
1State Display Current Data Diff. Date Binary input Phase Angle Harmonic data 4Output Test Device Fallure Protection Signal Alarm Signal Differential 1 Differential 2

Main menu

Differential 3 Differential 4 Diff. Standby Output terminal 9 Output terminal 10 Operate All 5. ParametersNote 1 Setting zone No. Comm. Setting B. Parameters Balance Coef. Channel Coef. Output Matrix ...... Input Password

2Signal Revert Enter 3Report Display Trip Report Binary Report Event Report Clear Report 6SettingsNote 2 Protection ON/OFF ...... Note: See protection setting table. 7Clock setting Date-- Time::

1. State Display 2. Signal Revert 3. Report Display 4. Output Test 5. SYS Parameters 6. Setting Value 7. Clock Setting 8. Password 9. Version Info.
TypeMTPR-630Hbnote 3 Ver V.. Date20-- CRC H

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Note 1Basic parameters in system parameters and D/A setting are different according
to devices, see device description for details.

Note 2See protection setting table for detailed setting menus. Note 3Corresponding to version 103, 104, this program respectively displays
103CRC, 104CRC.

State Display
State Displaymenu contains 5 submenus, side one to four current, restraint

harmonic current, binary input, phase angle display and harmonic data. It is described as follows Current Ia1 = Ib1 = Ic1 = Ia2 = Ib2 = Ic2 = Ia3 = Ib3 = Ic3 = 1 A A A A A A A A A

Diff.C Ida = Idb = Idc = Ira = Irb = Irc = Iha = Ihb = Ihc =

A A A A A A A A A

Differential current

Restraint current

Secondary harmonic current

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Binary input
Heavy Gas VRHeavy Gas Press-relief Spare Non-e. Light Gas VR Light Gas Oil High T Oil Level Low Cooling Lost Input 10

Description depends on protection device, see device terminal diagram

NoteIn the standard configurations, the input circuit of binary input has the connection

to an external 220VDC control power supply. When no DC control power supply or control system is available on site, but a 110VDC control power supply is available, a 110VDC control power supply may be used for direct connection through local hardware adjustment, or the 24V power supply of the device may be used as the input power supply (when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept float). However, this must be specified upon ordering. Phase Angle Ia1=. Ib1=. Ic1=. Ia2=. Ib2=. Ic2=. Ia3=. Ib3=. Ic3=.
The 1 side angles with respect to Ia1, the angle of Ia1 is set to be 0.

The 2 side angles with respect to Ia1

The 3 side angles with respect to Ia1

Harmonic 2nd % 3rd % 4th % 5th % 11th %

The order of harmonic from 211 is selected in system parameters

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Signal Revert In the [Signal Revert] menu, press the Enter key, the signal relay and the Operation

indicator on the panel will be reset.

Report Display The [Report Display] menu includes 4 submenus, including trip report, remote signal

report, event report and clear report. Event recording includes: device self-check fault, device setting value modification, system parameter modification and setting zone number modification, etc. The maximum events can be stored are: 50, 100, 30. Beyond this, the latest report will overwrite the earliest one. Press the Enter key to enter the corresponding [To view xx report, please enter report number: 00] menu, and enter 0~49, press the Enter key to display the contents of that report. The screen is as follows

Report No. --

Year, month, day Hour, minute, second and millisecond when it took place Report content description

Press key to see the specific operation value. Press the keys and to flip over.

Operation values
Ia1 = A Ib1 = A Ic1 = A Ia2 = A Ib2 = A Ic2 = A Ia3 = A Ib3 = A Ic3 = A Ia4 = A Ib4 = A Ic4 = A Ida = A Idb = A Idc = A Ira = A Irb = A Irc = A Iha = A EAGLE TECHNOLOGY Ihb = No. 201, L-2, B-11, Surya City, Bangalore-560081 A Address: E-mail: eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Ihc = A

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Output Test
After entering the [Output Test] menu, the correct password is required to enter the

[Output Test] menu. It displays the following

4 Output Test Device Fallure Protection Signal Alarm Signal Differential 1 Differential 2 Differential 3 Differential 4 Diff. Standby Output terminal 9 Output terminal 10 Operate All

Press Enter key


Press Cancel key Device fault signal

On

Off

(NoteAfter the signal relay closes, make sure to press Revert key or select Signal revert menu and press Enter key to revert the signal relay. When doing output test to protection outputs, the startup relay will be closed automatically. The +, - keys are used for switching between the On/Off control.

System Parameters
After entering the [SYS Parameters] menu, the correct password is required to enter

the [SYS Parameters] menu. It displays the following

5Parameters Setting zone No. Comm. Setting B. Parameters Balance Coef. Channel Coef. Output Matrix Language

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Setting zone number setting: range 00~07

Communication setting
Com. Setting RS485 device address RS485 baud rate IP address Subnet mask 002.4KB014.8KB029.6KB0319.2KB 0438.4KB05115.2KB Communication address of device 0199

Setting of basic parameters see the description of the protection device for
K W default value basic parameters B. Parameters Rating Current 1

Rating Current 2

Rating Current 3

Rating Current 4

Setting Value
After entering the password, you can enter the [Setting Value] menu. See the setting

description of the protection device for the detailed description.

Clock Setting
A battery-back real-time clock is provided in the device, which can perform time

adjust remotely via the communication network or in-site time adjust in the [Clock Setting] menu.
Enter this menu and press the Enter key, the clock will stop refreshing and a cursor will appear. Move the cursor to the desired position for modification by pressing the , keys, modify to the desired value with the +, - keys. Press the Enter key to complete setting. If the Cancel key is pressed, the setting will be cancelled and the screen continues to refresh the clock.

7. Clock setting Date20 Time

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Password
The [Password] menu is used to modify the password for entry into the Settings,

System parameters and Output Test submenus. The initial password is provided by the factory. The universal password is 1000.
Move the cursor to the desired position for modification by pressing the keys , , modify to the desired password with the +, - keys. Press the Enter key to enter the new password setting menu as above; press the Cancel key to cancel the setting.

Input Password 0 0 0 0

GPS clock synchronization


The GPS clock synchronization signal is input as rs485 differential voltage, the device

is able to receive GPS clock minute synchronization (or second synchronization). If there is GPS signal, there will be wont. The principle of GPS clock synchronization: The second pulse or minute pulse act with the monitoring system, the time base with second precision is sent by monitoring system, when the GPS second differential signal arrives, the time base is unified and the milliseconds are cleared. Version Information In the main menu, after entering the [9. Version Info.] menu, the model, software version and date of the device will be displayed. : For a corresponding nonstandard model, the devices displayed model does not have to be changed and flashing on the bottom of cycle menu; otherwise

5. Check of protection function

5.1 Check of differential instantaneous over-current protection


Set differential instantaneous over-current protection to on. Hard strap function is off

(when its on, C15 differential protection strap should be connected). Add each side current and make the differential current more than the setting the differential instantaneous over-current protection will operate. According to output matrix the corresponding terminals should be connected. For example

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Wire as the following diagram. Set differential instantaneous over-current protection to on. Hard strap function is off.

MTPR-630Hb Ia1 Ia1 Ib1 Ib1 Ic1 Ic1 D01 D02 D03 D04 D05 D06 A02 A01
Power supply

Set according to the following table. Measure the operating current and take them down in the following table. When instantaneous over-current protection operates, according to output matrixthe corresponding terminals should be connected. Instantaneous over-current protection setting(A) Operating value Instantaneous over-current protection setting (A) Operating value Instantaneous over-current protection setting (A) Operating value 1ln 2ln 5ln 10ln 1ln 2ln 5ln 10ln 1ln 2ln 5ln 10ln

Add only phase A currentcheck the operating value Add only phase B currentcheck the operating value Add only phase C currentcheck the operating value

5.2 Check of Complex percential percentage differential protection


Set percentage differential protection to on, only add phase A current to each side same angle do not add harmonic. Let differential current exceed percential differential minimum threshold, restraint current should be zero. When percentage differential operatesaccording to output matrixthe corresponding terminals should be connected.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

Only add phase A current to each side, check operating zone

The minimum threshold of percentage differential (A) Operating value Operating zone

1ln

2ln

5ln

10ln

For protection check under other conditions, please refer to the detailed description about percentage differential in device function of this manual. Concerning in this manual, add all sides current and satisfy percential differential curve and harmonics dont restrain.

5.3 Check of differential over-current alarm


Set differential over-current alarm to On, add current to every side and make the differential current exceed differential over-current setting, the device will report differential over-current alarm. Test corresponding terminals according to output matrix should be short. Differential instantaneous protection checking method should be referenced.

5.4 Lost of cooling control power


There are long and short delay for lost of cooling control power, when lost of cooling control power signal exists, together with oil high temperature signal, the device will output after short delay; when lost of cooling control power signal exists, no oil high temperature signal exists, the device will output after long delay. Wire according to the following Fig, set lost of cooling control power to On.

MTPR-630Hb
Input common port Oil temperature is high Cooling control power

B01 B08 A01


Power supply

B10

A02

Connect B01-B08 and B01-B10note that I/O board has external DC 220V and self-generated 24V, the device will output after short delay; If only B01-B10 is short, the device will output after long delay. Test the 2 delays and compare them with setting.

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

After it operates, test the terminals should be shorted according to output matrix.

3.1

Terminal diagram of device

POWER

I/O
B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 Input 10 B12 Input 11 B13 Input 12 B14 (+24V) B15 B16 B17 B18 B19 Alarm signal B20 Alarm signal B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 B31 B32 B33 B34 B35 B36

CPU
Net1

AC
D01 Ia1 Ia1' D02

D03 Ib1

Ib1' D04

ON OFF

Net2

D05 Ic1

Ic1'

D06

COM1 COM2 Run

D07 Ia2

Ia2' D08

D09 Ib2

Ib2' D10

D11 Ic2

Ic2'

D12

A01 A02 A03 A04 A05 Power off A06 Power off A07 A08 A09 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 A23 A24

Debug

D13 Ia3

Ia3' D14

D15 Ib3

Ib3' D16

D17 Ib3

Ib3' D18

C01 GPSA C02 GPSB C03 COM1A C04 COM1A C05 COM1B C06 COM1B C07 C08 COM2A C09 COM2A C10 COM2B C11 COM2B C12 Input 13 C13 Input 14 C14 Input 15 C15 C16 C17 C18 C19 C20

D19 Ia4

Ia4' D20

D21 Ib4

Ib4' D22

D23 Ic4

Ic4'

D24

Note: 1.Ia1,Ib1,Ic1 are protection currents of side I. 2.Ia2,Ib2,Ic2 are protection currents of side II. 3.Ia3,Ib3,Ic3 are protection currents of side II I. 4.Ia4,Ib4,Ic4 are protection currents of side I V. 5.COM1 and COM2 are 485 interfaces, Net1 and Net2 are ethernet interfaces. 6. Whether +24V on IO board is standard configuration or not can be fixed when using internal +24V as feeder.

Terminals diagram of MTPR-630Hb microcomputer transformer differential protection device

EAGLE TECHNOLOGY
E-mail: Address: No. 201, L-2, B-11, Surya City, Bangalore-560081 eagleteam.in@hotmail.com, Phone No: +91-9535-122013 , Web: http://eaglewanlida.com

Users manual for MTPR-630Hb main transformer differential protection measuring and control device

Document No. ETWLD[K]-JY-226-2010

3.2 Typical wiring diagram of device


A B C

D01 D02 D03 D04 D05 D06 D07 D08 D09 D10 D11 D12 D13 D14 D15 D16 D17 D18 D19 D20 D21 D22 D23 D24 Ia1 Ia1 Ib1 Ib1 Ic1 Ic1 Ia2 Ia2 Ib2 Ib2 Ic2 Ic2 Ia3 Ia3 Ib3 Ib3 Ic3 Ic3 Ia4 Ia4 Ib4 Ib4 Ic4 Ic4

Current of side I

Current of side I I

Current of side I II
AC plug-ins

Current of side I V

Fiber communication port Debugging port

MTPR-630Hb microcomputer transformer differential protection device

Power supply+ A01 Power supplyA02 A03 A04 Power off A05 A06

AC/DC AC/DC

C01 C02 C03 C04 C05 C06 C07

GPSA GPSB

CPU plug-ins

COM1A COM1A COM1B COM1B

A07

Power plug-ins

trip side I

A08 A09

I/O plug-ins

trip side II

A10 A11

B20 Alarm signal B21 Differential trip side I Differential trip B22 side I Differential trip B23 side II Differential trip B24 side II Differential trip B25 side III Differential trip B26 side III Differential trip B27 side IV B28 Differential trip side IV Differential trip B29 standby B30 Differential trip standby Output contact 9 B31 normally open B32 Output contact 9 common B33 Output contact 9 nomally closed Output contact B34 Output contact B35 10 common B36 nomally closed

C08 C09 C10 C11 C12 C14 C13 C15 C16

COM A

trip side III

A12 A13

B19 Alarm signal

COM A COM B COM2B


Input 13

trip side IV

A14 A15 A16 A17 A18 A19

Input 14
Input 15
Differential protection plate Input common port24V

B14 +24V Device fault B15 signal Device fault B16 signal Protection B17 operation signal Protection B18 operation signal

A20 A21 A22 A23 A24

B11 Input 10

B01

B02

B03

B04

B05

Typical wiring diagram of MTPR-630Hb microcomputer transformer differential protection device