Académique Documents
Professionnel Documents
Culture Documents
SMPS
Notice: The information, specifications, and procedures in this manual are subject to change without notice. Lineage Power assumes no responsibility for any errors that may appear in this document.
Table of Contents
1. INTRODUCTION ...................................................................................................................................................5 OVERVIEW .........................................................................................................ERROR! BOOKMARK NOT DEFINED. GENERAL ASSEMBLY DRAWINGS ......................................................................ERROR! BOOKMARK NOT DEFINED. CUSTOMER SUPPORT .........................................................................................ERROR! BOOKMARK NOT DEFINED. Customer Training ............................................................................................... Error! Bookmark not defined. Customer Service ................................................................................................. Error! Bookmark not defined. Technical Support ................................................................................................ Error! Bookmark not defined. Product Repair and Return .................................................................................. Error! Bookmark not defined. Warranty Service.................................................................................................. Error! Bookmark not defined. Downloads and Software ..................................................................................... Error! Bookmark not defined. SAFETY MANUAL ..............................................................................................ERROR! BOOKMARK NOT DEFINED. Safety Statements.................................................................................................. Error! Bookmark not defined. Warning Statements and Safety Symbols ............................................................. Error! Bookmark not defined. Precautions .......................................................................................................... Error! Bookmark not defined. Handling Batteries ............................................................................................... Error! Bookmark not defined. 2. SYSTEM DESCRIPTION .....................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM BLOCK DIAGRAM.................................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM COMPONENTS ......................................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM CONFIGURATIONS ........................................................................................................................................6 SYSTEM ARCHITECTURE ............................................................................................................................................9 Single Line Diagram of EP48XXX Plant .............................................................................................................9 SYSTEM SPECIFICATION...........................................................................................................................................11 Key Features ......................................................................................................................................................15 Key Specifications ..............................................................................................................................................17 3. ICOMBO CONTROLLER...................................................................................................................................18 OVERVIEW ...............................................................................................................................................................18 GENERIC INTERFACE REQUIREMENTS .....................................................................................................................19 KEY FEATURES ........................................................................................................................................................19 SPECIFICATIONS.......................................................................................................................................................19 Analog Inputs .....................................................................................................................................................20 Digital Inputs .....................................................................................................................................................22 COMMUNICATIONS ..................................................................................................................................................23 GP Interface.......................................................................................................................................................23 Programming Interface......................................................................................................................................24 SYSTEM CONTROL INTERFACE ................................................................................................................................24 Alarm Outputs ....................................................................................................................................................24 Front Panel Alarm LEDs..................................................................................................................................25 Factory Default Assignments for Alarms & LEDs............................................................................................26 USER INTERFACE GUIDE ..........................................................................................................................................26 Front Panel Keypad ...........................................................................................................................................26 System Status Indicators ....................................................................................................................................27 Local and Remote Access Ports .........................................................................................................................28 User Interface Menu Structure...........................................................................................................................28 Personal Identification (PIN).............................................................................................................................29 User Interface Menu Flow Map .......................................................................................................................31 ...........................................................................................................................................................................35 CONFIGURATION-Continued in next page...................................................................................................35 ...........................................................................................................................................................................36 CONFIGURATION-Continued in next page...................................................................................................36 ...........................................................................................................................................................................37 STATUS ....................................................................................................................................................................38
IPMS Product Manual annexureJune- 2010 Rectifiers............................................................................................................................................................38 Batteries.............................................................................................................................................................38 Shunt Currents ..................................................................................................................................................39 Disconnect States ..............................................................................................................................................39 Alarm Thresholds..............................................................................................................................................39 Enabled/Disabled Info ......................................................................................................................................39 This section of the menu provides a location to determine the Enable/Disable status of most of the Icombo controller features..............................................................................................................................................39 System Info ........................................................................................................................................................40 CONTROL/OPERATIONS ...........................................................................................................................................41 History ...............................................................................................................................................................42 CONFIGURATION .....................................................................................................................................................42 Float Settings.....................................................................................................................................................42 Shunt Monitors..................................................................................................................................................43 Rectifiers............................................................................................................................................................44 Batteries.............................................................................................................................................................44 Contactors..........................................................................................................................................................46 Disconnects........................................................................................................................................................46 Boost ..................................................................................................................................................................47 ACO ...................................................................................................................................................................48 System Settings ..................................................................................................................................................49 Communication Ports .......................................................................................................................................49 OVERVIEW..............................................................................................................................................................54 4. EP2500AC48 Shelf........................................................................................................................................55 OVERVIEW ...............................................................................................................................................................55 A. Standalone Shelf for accommodating six rectifiers........................................................................................55 SPECIFICATIONS.......................................................................................................................................................56 CONFIGURATION REQUIREMENTS ............................................................................................................................57 B. Shelf-less Concept for accommodating 2, or 3 rectifiers...............................................................................58 5. EP2500AC48 RECTIFIERS .................................................................................................................................60 OVERVIEW ...............................................................................................................................................................60 SALIENT FEATURES .................................................................................................................................................61 INPUT BEHAVIOUR...................................................................................................................................................62 OUTPUT BEHAVIOUR ...............................................................................................................................................63 USER INTERFACE (LED INDICATIONS) ....................................................................................................................64 6. EP3000AC48 RECTIFIERS .................................................................................................................................66 OVERVIEW ...............................................................................................................................................................66 SALIENT FEATURES .................................................................................................................................................67 INPUT BEHAVIOUR...................................................................................................................................................68 OUTPUT BEHAVIOUR ...............................................................................................................................................69 USER INTERFACE (LED INDICATIONS) ....................................................................................................................70 APPENDIX B THE T1.317 COMMAND LANGUAGE .....................................................................................72 INITIALIZING THE IC091_ICOMBO CONTROLLER .....................................................................................................72 RS-232 TERMINAL ..................................................................................................................................................72 T1.317 COMMAND LANGUAGE ................................................................................................................................73 Objects and Attributes........................................................................................................................................73 APPENDIX C EXPLANATION OF BATTERY MANAGEMENT FUNCTIONS .........................................84 FLOAT MODE ...........................................................................................................................................................84 SLOPE THERMAL COMPENSATION ...........................................................................................................................84 High Temperature Alarm ...................................................................................................................................84 High Temperature Compensation ......................................................................................................................84 Low Temperature Compensation .......................................................................................................................85 PLANT BATTERY TEST.............................................................................................................................................87
IPMS Product Manual annexureJune- 2010 BOOST MODE ..........................................................................................................................................................89 Auto-Boost Charge.............................................................................................................................................89 Redundancy Loss Function ................................................................................................................................90 Battery Voltage Imbalance Detection ................................................................................................................90 Battery Recharge Current Limit.........................................................................................................................91 Battery Parameter Defaults ................................................................................. Error! Bookmark not defined. APPENDIX D - FACTORY DEFAULTS FOR ALARMS & LEDS ...................................................................92 ISSUE HISTORY ......................................................................................................................................................93 ISSUE 0.1 .................................................................................................................................................................93
1. Introduction Overview
Lineage Power developed the Galaxy Power System EP4803 / EP4806 / EP4812 to support -48 volt telecommunications powering solutions for the Indian market. The EP48XXX combines fan-cooled, switchmode rectifiers, microprocessor control technologies, battery and load disconnect/reconnect options in a modular front-access design. This modularity ensures easy access, simplified installation and maintenance, and allows the system to expand in capacity and features as power needs grow. The power system accepts alternating current from the commercial utility or a standby ac power source and rectifies it to produce dc power for connected equipment. The systems control and alarm functions interact with the rectifiers and the office. In addition, the system provides overcurrent protection and charge, discharge, and distribution facilities. Battery reserve automatically provides a source of dc power if the commercial or standby ac fails. With 1200-ampere maximum capacity, distribution flexibility, Energy Monitoring features for the AC input as well as DC Loads, the EP48XXX supports switching, transmission, and wireless applications in central office locations and environmentally controlled remote sites.
System Configurations
The EP 48XXX is available in two configurations: The half height cabinet, shown in Figure 1-1 (EP4803 & EP4806) mounts on top of a battery stand and can provide up to 600 amperes of dc power. The full height cabinet, shown in Figures 1-2 (EP4812) is a standalone unit suitable for floor anchoring, and can provide up to 1,200 amperes of dc power. Figure 2-2 shows the electrical schematic for the Half Height Cabinets. Figure 2-3 shows the electrical schematic for the Full Height Cabinets. Each system contains ac distribution, dc distribution panels, a battery connection panel, rectifiers, termination points for load circuits, and a system controller.
System Architecture
The architecture of the EP48XXX platform is based on the IC091_CB ICOMBO Controller, which works as a front end master controller in addition to providing the user interface for the plant. The ICOMBO Controller provides complete control functionality, Distribution Monitoring & Control. ICOMBO is a combination of features of Pulsar plus controllers family and add-on modules (IEPSO). This approach of design gives a more centralized control and operation of power system. The ICOMBO works along with power system components and provides all the necessary supervisory, measurement, monitoring and control functions as required by the India Market. The feature set of the ICOMBO has been optimally designed considering the India Market Requirements, with new and special features such as AC Energy Monitoring, DC Energy Monitoring and Energy Efficiency. This section describes the basic architecture of the EP48XXX Power Systems designed around the use of the IC091_CB ICOMBO Controller. The key features and specifications of the IC091_CB ICOMBO Controller are described in the next chapter.
System Components
The unit is internally wired for AC distribution from the MCBs / TB to each of the individual rectifier modules, through backplane interconnects of each shelf. Rectifiers convert an ac source voltage into the dc voltage level required to charge and float the batteries and to power the using equipment. The rectifiers are installed in the EP48XXX shelf, with each shelf accepting a maximum of six rectifiers. Up to four shelves may be present. Blocks are labeled and wired to a correspondingly marked rectifier as shown.
(Front View)
The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as shown below (viewed from front of the shelf), with background color indicating the respective phase from which the rectifier draws its input power. For Systems with less number of rectifiers, the uninstalled rectifiers occupy slots within the rightmost side of the shelf. R- Phase: L1 Y- Phase: L2 B- Phase: L3 G41 G31 G21 G11 G42 G32 G22 G12 G43 G33 G23 G13 G44 G34 G24 G14 G45 G35 G25 G15 G46 G36 G26 G16
Controller provides the local and remote control, monitoring, and diagnostic functions required to control and monitor the power system. Batteries provide energy storage for an uninterrupted power feed to the using equipment during loss of ac input or rectifier failure. DC Distribution Panel provides over current protection, connection points for the using equipment, and bus bars used to interconnect the rectifiers, batteries, and dc distribution.
Distribution panels have DIN Circuit Breakers, or DIN Fuse modules DIN Style Breakers Ensure breakers are in the off position. Connect load cables to the load distribution return bus bar and the -48V outputs from the MCBs Verify wiring polarity at the input of the load equipment. Leave breaker switch in the OFF position until the load equipment is ready to be energized. DIN Style Fuses for Battery Connection Remove the fuses from the fuse base. Connect the negative cables of the battery to the fuse base and the positive cable from the battery to the +Ve return bus bar. Verify wiring polarity of the battery terminals. Do not install load fuse and alarm fuse until the load equipment is ready to be energized.
Battery Connection Panel provides connection points for the battery strings through battery disconnect fuses or contactors and current monitoring shunts.
Connect -Ve terminal Return Battery String #2 here Connect -Ve terminal Return Battery String #3 here
Secure Battery Cable connections with appropriate hardware. If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.
COG lead to be connected at the right most position of the DC return bus bar.
Secure COG connection with provided hardware: If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.
Connect +Ve terminal Return Common of Battery Strings and Loads here
System Specification
Key Features Special Features
Redundant Power Supply for controller from AC Input, Plant Bus and Battery Strings. Energy Efficiency Algorithms
User Interface
Front accessible 64x128 LCD with control pad and intuitive menu navigation system Available front panel PIN (password) access feature Standard or customer specific factory defaults supported. Support of more than one factory default. Display of both plant voltages and plant currents on front panel. Alarm severity sensitive display backlight. Three separate configurable and assignable LED indicators, to differentiate between AC, DC and Battery events, along with Tri-color capability to indicate the severity of any alarm/event.
Battery Management
Upto a maximum of three Battery Strings. Battery Reverse Polarity Detection for all three strings. Plant Battery Test Slope Compensation, for both low & high temp., with independent adjustable slopes. Battery recharge current limit feature Step function for Manual and automatic Boost. Remote test, and periodic discharge test capability Manual time threshold for pass/fail criteria Reserve time calculations with configurable threshold Monitoring of upto 3 Battery Temperatures using Probes Configurable mid string imbalance alarm.
Disconnects
Drive Capability for both Latching and Non-Latching Contactor types. Up to two groups of Disconnect Contactors can be controlled, one for load and second for battery. By default, upto four parallel contactors comprise the group for load contactors and up to two contactors form the group for battery contactors. Load disconnects operated by low voltage. Battery disconnect operated by voltage threshold, All contactors can be closed or open using the Local port interface.
Communications
Supervision, measurement, monitoring and control functions through Easy View 2 PC interface software. Communication through command language based on the T1.317 standard.
Key Specifications
Item AC Input Voltage Range Specification 176~290Vrms per phase Full Power Voltage 90~176Vrms per phase De-rated Power Voltage 10 minutes withstand capability @ 500VAC per phase (for Battery Floated Application) 1Hr withstand capability @320VAC per phase (for non-battery floated applications) -48 volts: from -36.5 volts to -60 volts 20 Watts Maximum Single Phase or Three Phase 8-line by 40-character LCD; Three status LEDs; Front panel LCD display and menu keys; From ICOMBO Controller :RS232 port: T1.317 or Easy View Up to 3 thermal probes.
No Damage Input Volts Plant Voltage Range Quiescent Power Consumption Input Power Connections Front Panel LCD user interface System Configuration Methods
Temperature Monitoring
Alarm Contact Ratings 60 VDC, 0.5A Plant Voltage Measurement Accuracy 0 to 50C (0.05% of full scale + 1 count) 48V Systems: 40 mV; 24V Systems 25 mV -40 to 85C (0.1% of full scale + 1 count) 48V Systems: 70 mV; 24V Systems 40 mV Resolution 0.01V Plant Current Measurement Accuracy 0 to +50C 0.5% of full scale -40 to +85C 1.25% of full scale Resolution 1A Temperature Measurement Accuracy One-Wire Serial probes -5 to +55C 1C -40 to +85C 3C Resolution 0.1C Environmental Operating Temperature Range Humidity Audible Noise -5 to 50C
With 2.5% per Deg. C power derating above 50 Deg. C.
3. ICOMBO Controller
Overview
This section describes the architecture and operation of the ICOMBO Controller. It also provides detailed information about the features of the front panel keys, LEDs and Displays.
Fig shows the Front Panel user Interface and the display, identifying the control elements. For the EP48XXX plant, the available options at the front panel craft port presently include only the RS232 interface.
Key Features
For the key features and comprehensive capabilities of the ICOMBO Controller, please refer to the Advanced Features User Guide for the ICOMBO Controller Family, comcode CC109152360.
Specifications
For detailed product specifications of the ICOMBO Controller, please refer to the Advanced Features User Guide for the ICOMBO Controller, comcode CC109152360.
Battery Shunts
The controller by default assumes the positive terminal of any battery shunt, as the terminal that is more positive under battery discharge conditions. The shunts used in power plants need to be wired considering this assumption. Upto 3 Battery Shunts can be monitored. Connection as mentioned below:Connector HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 To Battery shunt-1+ve Battery shunt-2+ve Battery shunt-3+ve BATT +ve BB LOAD -ve BB GND BUFF-3107 (common RTM 1,2&3) RTM-2 Battery shunt-1-ve Battery shunt-2-ve Battery shunt-3-ve BATT -ve BB LOAD +ve BB GND RTM-1 RTM-3
Load Shunts Up to 4 Load Shunts can be monitored. Connection as mentioned below:Connector Pin To HDR-3 1 LOAD SHUNT-1+ve HDR-3 2 LOAD SHUNT-2+ve HDR-3 3 LOAD SHUNT-3+ve HDR-3 4 LOAD SHUNT-4+ve HDR-3 5 GND HDR-3 6 LOAD SHUNT-1-ve HDR-3 7 LOAD SHUNT-2-ve HDR-3 8 LOAD SHUNT-3-ve HDR-3 9 LOAD SHUNT-4-ve HDR-3 10 GND
Battery Mid-string
Up to three Battery Mid-string Voltages can be monitored. Connection as mentioned below:Connector HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 Pin 1 2 3 4 5 6 7 8 To VBT 1+ve VBT 2+ve VBT 3+ve Bus bar-ve VBT 1-ve VBT 2-ve VBT 3-ve Bus bar-ve
12 13 14 15 16 17 18 19 20
Digital Inputs
General Binary Inputs
There are three general binary inputs available at HDR7 connector. Activation of these inputs takes place by pulling the lines to -48V. Connector Pin To HDR-7 1 AC SPD HDR-7 2 DC SPD HDR-7 3 AMJ HDR-7 4 OS HDR-7 5 FAN FAIL HDR-7 6 TR HDR-7 7 AIR CONDITION HDR-7 8 DOOR OPEN HDR-7 9 HIGH TEMP HDR-7 10 HIGH PRESSURE
6 7 8 9 10 11 12
Contactor Drive
The ICOMBO can drive either latching or non-latching contactors. If Latching contactors are used, the jumper designated HDR2 should be placed across pins 1&2, else it should be placed across pins 2&3. Interface requirements as below:Connector HDR-9 HDR-9 HDR-9 HDR-9 HDR-9 HDR-9 Pin 1 2 3 4 5 6 To coil +ve (LVBD) coil -ve (LVLD) V bus +ve coil -ve (LVBD) coil -ve (LVLD) V bus -ve
Communications
GP Interface
Connector P2 (RJ11 connector) is for the GP interface to the ICOMBO controller. Connector P2 P2 P2 P2 P2 P2
Pin To
1 2 3 4 5 6
Programming Interface
SPI programming interface for the card available at six pin connector HDR1. System Control Interface Alarm Outputs There are a total of ten potential free relay outputs, which are wired up within the EP48XXX plant, from the output terminal block to the HDR10 connector of the ICOMBO Controller. All ten relays can be independently programmed to operate in normally open or normally closed condition, by appropriately configuring jumpers 1-10 located on the ICOMBO board. The configuration needs to be done as illustrated below:
Each jumper corresponds to one alarm relay and each relay output can be configured independently. The potential free contacts from the relay outputs are available at the HDR10 connector of the ICOMBO controller. Out of the ten alarm relays, seven provide the actual alarm condition, and three provide the severity associated with the alarm. The severity relays transmit Power Critical (PCR), Power Major (PMJ), or Power Minor (PMN). Each alarm is factory assigned a severity based on industry practices; however, they may be reassigned to PCR, MAJ, MIN, or RO (Record Only). An alarm condition with the RO severity results in the system controller transmitting the alarm without the severity but is stored in the history log. PCR, PMJ nor PMN are transmitted with the alarm. The seven selectable alarm relays are called User Alarm Relay 1 (R1) through User Alarm Relay 7 (R7). Each relay can operate under one or more events/conditions or even when a logical combination of certain events occur. Further, the active states for all the Relays are user definable (either normally open or closed). Table 3-1 indicates the interconnection between the I-combo Board and the user terminal blocks for the output relays. The factory default functionality for the relays is also indicated.
From TB- No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Name PCR PMJ PMN OP ALM1 OP ALM2 OP ALM3 OP ALM4 OP ALM5 OP ALM6 OP ALM7 To ICOMBO Connection HDR 10:1 HDR10:11 HDR10:2 HDR10:12 HDR10:3 HDR10:13 HDR10:4 HDR10:14 HDR10:5 HDR10:15 HDR10:6 HDR10:16 HDR10:7 HDR10:17 HDR10:8 HDR10:18 HDR10:9 HDR10:19 HDR10:10 HDR10:20 Default Functionality Power Critical Alarm Power Major Alarm Power Minor Alarm Battery on Discharge Multiple AC Fail / AC Fail Multiple Rectifier Fail / Rectifier Fail Very Low Voltage LVLD Fail / LVLD Open / Load MCB Trip High Voltage LVBD Fail / LVBD Open / Battery Fuse Fail Default Alarm State Close Close Close Close Close Close Close Close Close Close Alarm State Programmable? Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Direction Buttons
In the Menus, the direction buttons navigate to make a selection. A black box highlighting a menu item indicates that the item has sub-menus. Enters a sub-menu or confirms a parameter change. From the Home Page only, goes to the top level Main menu. Goes up one menu level or exits a parameter change without saving.
AC
The audible alarm may be disabled altogether through proper configuration at the front panel.
The front panel default screen displays the primary (Rectifier) system bus voltages along with total load. The larger font represents the rectifier output. Output voltages of rectifier outputs have two decimal points. The operating mode of the system is also displayed. Possible operating modes are: Float, Battery On Discharge, Boost, etc. Pressing the button accesses the main menu and the feature categories previously listed.
Main Menu
Access to alarms, warnings, equipment status detail, basic control and operations for maintenance purposes, and system configuration can be obtained. Note: the ICOMBO has the ability to have a front Panel Password that limits configuration as well as some operations. A person with administrator level access can enable this feature through the remote interfaces. Standard ICOMBO controllers are shipped from the factory with this feature enabled.
The up, down, left and right arrows are used to enter the appropriate password. Upon entering a correct PIN the following momentary screen shows up and then disappears leaving the user at the menu location prior to entering the PIN.
Once a user enters the PIN, total front panel access is allowed for as long as the user remains in menus other than the default menu and/or any one of the following :a) The front panel access will remain open once the PIN has been entered till the time out value. The Icombo controller has a factory configured default of 120 minutes. b) An internal counter shall be kept and reset if the user leaves the default menu and returns to others menus before the timeout period is reached.
Status Menu
Control/Operations
History Menus
Configuration Menu
Status
The Status section of the menu system provides an overview of system components, threshold settings, and feature configuration. Configuration is not possible from the status portion of the menu system. Status items are also available through the remote port connections such as the web interface or local craft port using Easy View.
Rectifiers
Installed Capacity On-line Capacity Provides the total installed rectifier capacity in the system. The total rectifier capacity of rectifiers On-line in the system and able to produce power. Rectifiers that are running or in Standby are considered to be On-line. Rectifiers that are in RFA, ACF, etc. are not counted in the On-line capacity. The total output current drain of all rectifiers. Each individual rectifiers DC output current, AC input current, and AC input voltage by rectifier number Gmn () is available. m represents the shelf number and n represents the rectifier position number in that shelf. The state of the rectifier is also identified in the () when current is not shown. These states could be OFF: Rectifier has been shutdown due to hardware failure (ex RFA, Temp, HV). STANDBY: User has inhibited the rectifier's output voltage. User may use remote interfaces or the ope command to place a rectifier into a standby condition or during execution of energy efficiency. MISSING: An acknowledged rectifier has been removed. VACANT: Rectifier has not been installed in that position.
Batteries
Installed Capacity Current (Chrg/Dchg) Battery Strings Highest Temp Temp Probes Mid-Cell Volts Battery Test Result Next Test Live reserve time Total installed battery capacity based upon the number of strings in the system and the Amp-Hour (AH) rating of the strings installed. Measured value of the current charging or Discharging of the batteries The total number of battery strings installed in the system. Highest battery temperature being measured by the RCB thermal probes attached in the system. Total number of installed thermal probes. Up to three probes can be monitored by the controller. Total number of installed Mid-String voltage measurement modules. Shows whether the most recent battery test was completed, and the last calculated reserve time. The date of the next automatic battery discharge test. The automatic discharge test feature must be enabled for this to work. Shows live calculated reserve time during battery discharge test.
Shunt Currents
ID1-8 Displays the individual shunt monitor currents. Distribution Up to eight values can be displayed. Factory default is ID1-3 Battery currents ID 4-7 load currents.
Disconnect States
LVBD Provides LVBD (Low Voltage Battery Disconnect) status. None-Displayed for each non-configured contactor. Closed-displayed when contactors are closed and battery is connected. Open-If contactors are opened and disconnected the battery. Provides status of the three LVLDs (Low Voltage Load Disconnects ) None-Displayed for each non-configured contactor. Closed-displayed when contactors are closed and battery is connected. Open-If contactors are opened or disconnected each respective load.
LVLD(1-3)
Alarm Thresholds
Float Voltage Alarms Shows the configured settings for the Float Settings: Very High Major High Minor Battery discharge Major (BD) Very Low Voltage (VLV) alarms. Values are shown in (xx.xxV) format. Shows the configured settings for the Boost Settings: Very High Major High Minor Values are shown in (xx.xxV) format. Shows measured value of the highest battery temperature of all attached battery thermal probes. Shows configured value for the Low battery reserve time alarm. Shows configured value for the Low battery real reserve time alarm
Enabled/Disabled Info
This section of the menu provides a location to determine the Enable/Disable status of most of the Icombo controller features.
Temp Comp Low Temp Comp Shows whether Battery Temperature Compensation is Enabled or Disabled. Shows if the Low Temperature compensation features is Enabled or Disabled.
Shows if the Recharge Current Limit feature is Enabled or Disabled. Displays whether or not the Emergency Power Off (Remote Emergency Battery Disconnect) feature is Enabled or Disabled. If Enabled, EPO is asserted when contact closure is applied to the EPO input. The controller will keep battery contactors open until this contact closure has been removed. The feature assumes that AC has been removed to the system. Shows if the automatic boost charge mode of operation is Enabled or Disabled. Shows if the automatic battery test feature is Enabled or Disabled. Shows if the Rectifier redundancy feature is Enabled or Disabled. Shows if the Mid-String Voltage imbalance detection feature is Enabled or Disabled. Shows if the Imminent system shutdown alarm (LVBD) feature is Enabled or Disabled. Shows if local buzzer is Enabled or Disabled. Shows if the energy efficiency management feature is Enabled or Disabled. Shows if the LVBD (Low Voltage Battery Disconnect) and LVLD1-3 (Low Voltage Load Disconnects) features are Enabled or Disabled. Whether or not the system can be configured through the local port.
Auto Boost Auto Batt Test Rect Redundancy Mid-Cell V Mon Imminent Shutdn Local buzzer Eff management En Disconnects Local Write
System Info
Controller Info Provides software versions running on the ICOMBO. These versions include the versions for the application code, the boot block, the display, the defaults file, and the web pages. Present Date of the ICOMBO on-board real-time clock using the configured Date format. Present time of the ICOMBO on-board real-time clock using the configured time format.
Date Time
Control/Operations
The following are the system control and operation functions that can be performed from the front panel. These operations are generally used in post installation and maintenance modes.
Alarm Cut-Off Start Lamp Test Restart Devices Temporarily cuts-off (Turns off) the on-bard audible alarm. Temporarily illuminates all status indicators of ICOMBO controller. Provides the ability to restart All system serial controlled rectifiers. Provides the ability to individually reset only rectifiers at a time. This operation does not affect rectifiers and other system devices that are already functioning. Used to clear momentary events or alarms. It clears the following system alarms: Check Battery, Reserve Time Low, Battery Voltage Imbalance Clears alarms related to the removal of a system component such as a rectifier, thermal probe etc. Running this command allows the system controller to retake inventory of using equipment. This area of the menus system can be used to clear the various items that the controller maintains history records. Once cleared the controller begins to keep history of new events. Alarm History: Clears only alarm event history. BD History: Clear only BD network access history. Boost History: Clears only Boost event history. This area of the menus system can be used to clear the various items that the controller maintains statistical records. Once cleared the controller begins to keep new statistical data. Clear Basic Clears individually or as a group the Basic statistical data kept on Plant Load, the highest battery temperature, and ambient. Clear Trend Clears the trend data kept on the plant load. Clears the Battery on Discharge (BD) statistics kept on the plant load and voltage during discharge. Provides ability to initiate an alarm relay test on all output relays. Alarm relays are asserted at the configured alarm interval. Provides ability to initiate a audio buzzer test. Resets reserve time Initiates the manual battery test feature. A stop battery test operation is displayed to interrupt the testing and return the unit to normal operation. The manual battery test utilizes the configured test duration and a system bus voltage threshold to represent the end of reserve. Initiates the manual battery Boost feature. A stop battery Boost operation is displayed to interrupt the Boost operation mode and return the unit to normal operation. Provides individual manual control (to open or close) of up to four Low Voltage Disconnects (LVBD, LVLD1-3) for maintenance purpose. This operation allows a user to bring back all factory defaults with a single operation. Factory defaults are also custom configuration defaults that are available. Custom configurations may support multiple factory defaults. Clear BD
Clear Statistics
Alarm Relay Test Alarm buzzer Test Reset reserve time Start Battery Test
Start Boost
Caution should be used when applying this command. Previous configuration changes will be overwritten. Resets user, super-user and administrator passwords back to standard defaults.
History
This area of the menu system contains event history information. The controller works on a first record in first record out once the record size of a specific field is reached. The following system history logs are available:
Alarm History BD History Boost History Chronological view of the last 500 alarms and events that have occurred since the last time the history log was cleared. Chronological view of the last 16 battery on discharge (BD) events since the last time the history log was cleared. Chronological view of the last 16 times the system entered boost mode since the last time the history log was cleared.
Configuration
The Configuration section of the menu system is where system operational parameters, system device information, and alarm thresholds are set-up and modified. Factory defaults are provided for the standard ICOMBO controller. Some defaults are dependent on the battery type. Consult Appendix E for default settings of different battery. Valve-Regulated Lead Acid (VRLA) batteries and default settings defined for the Standard configuration are assumed in this section. Customer specific configurations may be different. When there is doubt, contact Lineage Power technical support. All items are field configurable. Modified settings are stored in non-volatile memory. The ICOMBO controllers require time to update sectors in flash memory for changes. Allow approximately a minute for the controller to accept and store modifications in non-volatile memory before removing power to the unit.
Float Settings
Set Point Parameter sets the value that primary (rectifier) DC bus will be set and regulated. Range: 42.00V to -56.50V factory default is -54.00V This is an Independent High Voltage Shutdown threshold during the Float mode of operation that is sent to and stored in the rectifiers that is used by each rectifier for independent high voltage monitoring. Range: 42.00V to -56.50V factory default is -54.00V Very High Major This alarm indicates an abnormally high output voltage on the secondary DC bus during Float mode. This is second and critical level of high voltage alarm. The alarm does not attempt to shut the offending unit down.
ISHVSD
Voltage alarms
High Minor This alarm indicates an abnormally high output voltage on the secondary DC bus during Float mode. This is first level of high voltage alarm. The alarm does not attempt to shut the offending unit down. The threshold can be set from Range: -50.00V to -60.00V Factory default: -56.00 BD (Battery on Discharge) Major Primary DC bus threshold setting that determines when the system is determined to be operating on battery reserve. Range: -46.00V to - 55.00V. Factory default: -51.00V. Very Low Voltage Major Primary DC bus alarm threshold used to indicate a very low output voltage (VLV). Range: -40.00V to- 51.00V. Factory default: -46.00V.
Shunt Monitors
The ICOMBO controller can manage 3 battery shunts and 4 battery shunts. Shunt sizes for each assigned battery or load type must also be configured. All shunts are assumed to have a voltage rating of 50mV. The current rating of each shunt is programmable between 0 to 9999A. Systems shipped with the I-combo controllers are appropriately pre-configured in the factory for the right shunt values and assignments.
ID1-7 The operation Type of each shunt monitoring must be assigned based upon actual system implementation. The operational Type may be: None (For no shunt), Battery (Monitoring battery currents), and Load (for load currents). The current rating of each shunt being monitored by ICOMBO controller must be configured based upon actual system implementation. All shunts are assumed to be 50mV. The current rating may be from 0-9999 Amps. The factory default is 300A for battery and 200A for the load shunts.
ID1-7 Rating
Defaults The ICOMBO controller is factory configured with: ID1 ID2 ID3 ID4 Type: Battery Type: Battery Type: Battery Type: Load Shunt: 300A Shunt: 300A Shunt: 300A Shunt: 200A
Front panel displays summation of load current for default ID type settings.
Rectifiers
Redundancy An alarm is automatically generated when the load on system is more than N-X for a On-line rectifier capacity of N+X based system. X is the desired number of rectifiers to check for redundancy. The factory default for this feature is Enabled and X=1. Provides the ability to disable or enable energy efficiency feature The rectifier which takes current below this %age value will be eligible to enter into Energy efficiency standby mode. The current of that rectifier is then shared by other rectifiers. This process continues until a steady state is reached. Range: 20-95 % The rectifier which takes current above this %age value will turn ON. This process continues until a steady state is reached. Range: 25-100 % Time delay setting for the first rectifier to enter into energy efficiency mode. Range: 1-30 min Time delay setting for the next rectifier to enter into energy efficiency mode. Range: 1-30 min
Eff Turn ON
Batteries
Battery Type The type of batteries used in the system can be selected from the following battery types loaded in the Standard controller:
Generic VRLA (Valve Regulated Lead Acid) Generic FLOODED (flooded lead acid) Generic NiCd (Nickel Cadmium)
Once selected the user has the opportunity to automatically accept the standard defaults for all battery Type related features. Parameters such as float voltage, float alarms, thermal compensation parameters, etc. are automatically adjusted if defaults are accepted. The system factory default is Valve-Reg. Installed Capacity Capacity of an individual battery string in the system which is used to derive the total installed system battery capacity. This value has to be entered for Generic battery types but is automatically configured for specific battery models. The value configured should be the rating to 1.75V at an 8-hr discharge rate.
The available range is 0-30000 AH. The system factory default is 0 AH corresponding to the Generic Valve-Reg. Battery Strings The total number of battery string installed in the system entered by the user for inventory purposes and initial reserve time calculations. Range is 0-16 The user defined system bus voltage at which the batteries are considered to be at the end of their reserve capability for manual battery testing (End of Discharge). This end-of-discharge voltage is used for automatic and opportunistic reserve time calculations. Battery Temp Management* Range: -36.00V to -48.00V Factory default of -44.44V for 48V
End of Dchrg
This section includes all the parameters required for thermal management of the batteries. Parameters include the ability to enable/disable thermal compensation for high and low temperatures and set the slope decrease and increase rates, respectively. There is also a High Temperature alarm threshold feature. Factory default Enabled
Batt Test*
This section includes all the parameters required for battery testing through manual or automatic means. Configuration for manual test duration and the system test end-voltage for manual battery test are here along with the interval, start date, start time, time from last battery on discharge BD, and enable/disable for periodic battery test. The rectifier voltage during battery discharge testing and system reserve time low alarm threshold are also available. Automatic battery testing is factory disabled.
Enable or disable battery recharge limiting and set recharge current limit. When enabled, the controller will regulate the current into the batteries to be below the setting. Recharge current limit is factory Disabled. The current limit range is 5 to 1000A and has a factory default of 50A for Valve-Reg batteries. User defined voltage threshold for a mid-string voltage imbalance alarm. Range 1.4 - 3.0 Volts. The factory default is 1.7V for Valve-Reg batteries. This alarm is only generated after batteries have been sitting on float for a minimum of 12 hours and the total battery current is less than 3A.
Voltage Imbal
*See Appendix C for detailed descriptions of the Thermal Compensation and Battery Test features and parameters.
Contactors
The ICOMBO controller monitors and controls contactors. Contactor controlled by appropriately configuring a unique board ID and associating it to a specific contactor function at the controller.
ID1-6 Associates the ID numbers set on the controller to one of four independent set of contactor controls. These contactor controls are: LVBD (Low Voltage Battery Disconnect), LVLD1 (Low Voltage Load Disconnect 1), LVLD2 (Low Voltage Load Disconnect 2), and LVLD3 (Low Voltage Load Disconnect 3).
The ICOMBO has assigned each unique board ID number as follows: ID1 to LVBD ID2 to LVLD1 ID3 to LVLD2 ID4 to LVLD3
Disconnects
This section of the configuration menu contains the parameters associated with the individual function assignments made in the previous section. Each LVD type (LVBD and LVLD1-3) can individually be enabled or disabled. Only the LVBD and LVLD1 are enabled from the factory. The LVDs disconnect and reconnect method of operation used by the controller can be configured for each assignment. The method of disconnect or reconnect can be based on the traditional means of reaching a system bus voltage threshold (Voltage) or based on both reaching the system bus voltage threshold and an elapsed time from once the system has been placed on discharge (BD) and at least two or more rectifiers are reporting AC failures (Voltage/Time). The same Voltage and Voltage/Time mode of operation can also be selected for reconnecting LVDs. In this case the elapsed time configured is the time from once the reconnect voltage threshold has been reached. Note: selecting None for a reconnect mode will require manual intervention to shut the contactor. Selecting None for the disconnect mode will not allow a LVD to open. The ICOMBO has factory defaults of the following:
LVBD (Enabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-48.0V); Range:-39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec
LVLD1 (Enabled)
LVLD2 (Disabled)
LVLD3 (Disabled)
Shutdown Alarm
Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V/+19.5 to +25.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage/Time); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (30 sec); Range: 0-300sec Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec When enabled, the Imminent Shutdown Alarm is generated prior to opening the LVBD. Once the LVBD threshold has been reached, the alarm is generated. The alarm is issued 15 seconds prior to opening the contactor to provide an indication that system shutdown is imminent due to a system battery disconnect. The alarm is based on the configured LVBD battery disconnect threshold. The factory default for this feature is Disabled. If enabled, the remote Emergency Power Off (EPO) feature allows the controller to detect the occurrence of a contact closure between J3.5 and J.10 and force open all battery contactors in the system. The battery contactor will open five seconds after the contact has been asserted. Once the contact is removed, the battery contactor will be re-asserted to its previous operational state. The factory default for this feature is Enabled.
Boost
The Boost function allows battery charging to be expedited by raising the system voltage to boost level for a set time. The following boost mode parameters are set in this area of the menu system:
Set Point Primary DC bus voltage set-point during the Boost mode of operation. Boost (set point) is adjustable from -48.00V to -58.00V in 0.1V increments. Factory default setting is -55.20V. This is an Independent High Voltage Shutdown threshold during the Boost mode of operation that is sent to and stored in the rectifiers that is used by each rectifier for independent high voltage monitoring.
ISHVSD
Voltage Alarms
Has the ability to set similar DC bus level alarms during Boost as found with the Float mode of operation. This includes Very High Major, High Minor, and BD. Very High Major This alarm indicates an abnormally high output voltage on the secondary DC bus during Boost. This is second and critical level of high voltage alarm. The alarm does not attempt to shut the offending unit down. Range: -50.00V to -60.00V Factory default: -57.00 High Minor This alarm indicates an abnormally high output voltage on the secondary DC bus during Boost. This is first level of high voltage alarm. The alarm does not attempt to shut the offending unit down. The threshold can be set from Range: -50.00V to -60.00V Factory default: -56.00
Max Duration
Defines the maximum time duration the system can remain in the Boost mode of operation. Range: 1 to 80 hours. Factory default: 5 hours. Enables or Disables the automatic boost feature. Boost will end once the monitored battery current reaches less than 5A or Max duration is elapsed. Factory default: Enabled
Automatic
ACO
Local buzzer Duration Enables or Disables the Local buzzer. Factory default: Enabled To set the alarm cutoff duration. Range:30-480 min Factory default: 60min
Alarm Test
Relay duration To set the relay test duration. Range:5-300 sec Factory default: 05 sec To set Local buzzer test duration setting
Buzzer Duration
System Settings
Date Time Daylight Savings Display T Units Allows setting system Date. Factory default format: Date - yyyy-mm-dd Allows setting system Time. Factory default format: Time - hh:mm:ss (24HR format). Enable or disable daylight savings. Factory default: Enabled. Allows setting of temperature in C or F. Factory default is C.
Communication Ports
Menus for configuring the following communication parameters:
Port Type Sets the RS232 asynchronous serial communication port for either Local terminal or Modem application. Factory default: Local. Provides the ability to Enable or Disable Write access to the controller, the ability to change system settings through the SNMP management or local port. Write Access, baud rate and flow control parameters for the port is configurable. Factory default: Write Access-Enabled Baud rate-Auto flow control-None
Using a standard browser, a login page similar to that depicted below should be served up by the ICOMBO controller. There are three levels of access through the port; Read-Only, Read/Write, and Read/Write with password management privileges. Passwords defaults for the Craft port as well as other remote access means default as follows: Access User (Read-Only) Super-User (Read/Write) Administrator (Read/Write/Password Administration) Default Password lineage super-user administrator
Security Levels/Passwords
The ICOMBO controller supports three levels of access: (User, Super-User, and Administrator). Password defaults can be changed only by a user of administrator privileges. User security level: Can view almost every parameter in the system Can change only a few parameters considered to be of standard maintenance practices Default password: lineage Super-User security level: Can do everything the user can do Can change any configuration parameter in the system (except passwords) Default password: super-user Administrator security level: Can do everything the super-user can do
Can change passwords Can upgrade controller software Default password: administrator After the controller has granted access, the controller serves up a Home page similar to that shown below. Front panel access and capabilities are a super-set of the functions and features available through the Craft port. Configuration of individual parameters and features can be performed by using the items located in the Settings tab or a general quick configuration of the system can be performed through the Installation tab. The Home Page has tabs that are partitioned as the following:
After login in, main menu screen will show graphic of the power components which are: the number of shelves, rectifiers in place with their appropriate outputs, empty slots, and indicate which rectifiers are in alarm condition. High-level summary for the Batteries, Distribution, Alarms present, and controller summary are also shown. There are also quick link tabs that take you to specific features. These tabs are the Home, Reports, Maintenance, Settings, and Installation.
Home
The reports tab displays reports or history records of the system that is recorded in the controller. These reports include Inventory, Battery Discharge and Statistics. Individual history groups like Alarm History, Boost History and Trends also available.
Reports
Maintenance
Allows remote access to Control/Operation commands that are available through the front panel. These include restarting rectifiers, starting alarm or battery tests, asserting boost, clearing history and statistics, clearing latched events and missing equipment, placing rectifiers/converters in and out of Standby, cutting of the audible alarm. The T1.317 Terminal button provides a quick link to a Telnet session to the controller that allows the T1.317 command interface to be utilized.
Note: The Load Defaults button under system loads the factory default settings assigned to a specific battery type as defined in the defaults configuration file. In the Standard controller this function will Standard configuration file. Custom configured controllers will utilize the specific custom configuration file defined for that particular configuration.
Items in this menu are used to configure all the individual system parameters, features, and thresholds. These fields are arranged by System, Reserve, Power, Communication and Programming.
Settings
This tab provides access to quickly configure the primary items typically needed for a site. These configurations are the minimum for basic system operation. These items include selecting the battery type, date, time, and the site ID mentioned during the front panel configuration start-up section.
Installation
Overview
Broadly, The ICOMBO is capable of the below: GP Bus interface to system controller Control/monitoring of two contactors (latching/non-latching). System configuration can include either all contactors of latching type or all contactors of non-latching type. Hardwired Selectable contactor type (latching/non-latching). If Latching contactors are used, the jumper designated HDR2 should be placed across pins 1&2, else it should be placed across pins 2&3. 1 Bus Voltage Measurement 3 Mid-String Voltage Measurement 4 Load Shunt Currents Measurement 3 Battery charge/discharge shunt Currents Measurement Configurable Shunt Size for each shunt. 3 Battery Reverse Polarity Connection sensing 3 configurable alarm inputs (3 General Binary Inputs) Monitors up to 64 load breakers/fuses Monitors 3 battery fuses Automatic input presence detection Configurable Alarm Input configuration o Polarity o Type 3 Phase AC Parameter Measurement (RMS voltage, RMS current and frequency) (Achieved using a dedicated True RMS AC measurement chip, accuracy < 1%) Configurable CTR (current transformer ratio) for each AC current phase. 1 Tri-Color Status LED
4. EP2500AC48 Shelf
Overview
Figure 4-1: EP48XXX Plant Shelf & Rectifier Arrangement The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as shown below (viewed from front of the shelf), with background color indicating the respective phase from which the rectifier draws its input power. The EP48XXX plant is internally wired for AC distribution from the MCBs / TB to each of the individual rectifier modules, through backplane interconnects of each shelf. R- Phase: L1 Y- Phase: L2 B- Phase: L3
For Systems with less number of rectifiers, the uninstalled rectifiers shall occupy slots within the rightmost side of the shelf.
Specifications
Parameter
1 2 3 1 2 3 4 Total Output Power Output Voltage: Voltage Isolation Range Input / Chassis Output/Chassis Storage Temperature Operating Storage Operating Input Voltage Full Power Derated Power No damage
Min
176 90 0 -42 343 1500 500 -20 -5 +55 10 5 -
Nom
230 -52 25
Max
290 176 500 15000 -57 75 +55 +70
Unit
V rms V rms V rms Watts Vdc A VAC VAC C C C % % inches inches mm -
Additional Information
Continuous Rated
For 1 minute. For 1 minute. Full Power Rated. Assumes 2.5%/ Deg. C power derating above 55 Deg. C Non condensing - no corrosion. For 96 consecutive hours & no more than 15 days / year. 3U Hieght with Rectifiers inserted inside shelf Depends on whether 19 / 23 Shelf No tool is required to change a rectifer 2 Bit Addressing using piano switches All rectifiers installed have load share hardwired to backplane. Between shelves, two connectors available for cascading load share cables from one to another.
Humidity
Size
Configuration Requirements
Shelf ID Switch
GP Interface Conn.
Table 4-2: EP2500AC48 Rear View Components Identification a. b. c. d. Shelf ID switch of bottommost shelf needs to be configured as 00 Shelf ID switch of second shelf (from bottom) needs to be configured as 01 Shelf ID switch of third shelf (from bottom) needs to be configured as 10 Shelf ID switch of fourth shelf (from bottom) needs to be configured as 11
Note:- Configuring the shelf ID switch (piano switch) as 0 means the switch should not be pressed.
Below is indicated a backplane PWB that accommodates three rectifiers. SW1 (rightmost) lone switch is for shelf selection, and (SW2, SW3, SW4) left most group of three switches, with SW2 in the leftmost position. SW2 SW3 SW4 SW1
Based upon above combinations, where the three rectifiers Backplane PCB is used, below are the switch settings to identify the rectifier position.
Close means pressed 2nd Sw3_1 Sw3_2 Slot # Close Close 2 Close Open 2 Open Close 4 Open Open 5 3rd Slot # 3 invalid 5 6
1st Slot # 1 1 3 4
Based upon above combinations, where the two rectifiers Backplane PCB is used, below are the switch settings to identify the rectifier position. Close means pressed.
Sw2_1 Close Open Sw2_2 Close Open 1st Slot # 1 3 2nd Slot # 2 4
5. EP2500AC48 Rectifiers
Overview
The EP2500AC48 Rectifiers are rugged and robust rectifiers that have been exclusively designed to take care of wide line fluctuations and extreme climatic conditions prevailing typically in rural/ semi-urban areas (B & C telecom Circles) of India . The Rectifiers are designed to operate as an integral part of the EP48XXX Plant, with or without battery back-up. These Rectifiers are compatible with the Galaxy family of controllers available from Lineage Power. These Rectifiers are compatible for installation into the EP48XXX shelf.
Salient Features
176Vac to 290Vac input operation at Full Power. 90Vac to 176Vac de-rated linearly from below 176Vac. The linear de-ration of output power ensures optimum power performance at sites with poor grid voltage 2500W power from 44 to 56Vdc (56.8A@ 44V, 52A @ 48V, 44.6A@ 56V) Operating temp. range: -5 to +70C Full power range: -5 to +55 C De-rated power range : +55 C to +70C (de-rated power @ 2.5% per C ) Efficiency >92% for input voltages>230Vac and load between 50% to 100% No Damage Input voltage range: 0 to 500Vac (Line to Neutral) for battery floated application This ensures adequate protection even against Line to Line voltages appearing across the rectifiers in case of Neutral disconnect or Neutral shift conditions which are not uncommon in rural/ semi-urban areas) Can withstand 96 hrs of salt spray test (as per ASTM B117), Special protective coating on the PCBs and superior plating on the metal parts. This makes the rectifier suitable for working in coastal areas having salty atmosphere Less than 10% Current THD Typical Power Factor Correction Low electrical output noise Hot Swappable, Hot Pluggable and Parallel operation with load sharing Radiated and Conducted EMI emissions at system level to conform with CISPR-22 Class A ON/Standby control Through Controller only Rectifier control and alarms operational during input ac failure. Auto recoverable from over temperature shutdown. Latched and auto-restart shutdowns with software restart or AC input recycling. Front LED indicators and Controller signaling are powered via the DC output (back biased) Fuse fail detection of Input Fuse
Input Behavior
Linear de-ration of power for poor grid voltage Input operating voltage range (90 to 290Vac) Full power range (2500W) -176 to 290Vac De-rated power range - 90 to 175Vac (Linearly de-rated power @0.6% / Vac, 1200W at 90Vac) The linear de-ration of output power ensures optimum power performance at sites with poor grid voltage
70
90
110 130 150 170 190 210 230 250 270 290 310
Input Voltage (Vac)
Output Behavior
Constant Power rectifier 2500W power from 44 to 56Vdc (56.8A@ 44V, 52A @ 48V, 44.6A@ 56V) Constant Power range down to 44V ensures that rectifier delivers full power when needed most i.e. charging a fully discharged battery
VI Characteristics
75
Figure 5-4: EP2500AC48 Rectifiers Front View with LEDs The LEDs are ACF (yellow), NORM (green), FAIL (red) from left to right. A Logical Summary of LED Indications on Panel is as given below:AC Fail (Amber) 2 Status ON - AC input out of range (i.e. <90Vac or >290Vac) OFF - AC is normal Normal (Green) 4 Status ON - DC Output OK OFF- DC Output Not OK Blink (0.5 Sec ON and 0.5 Sec OFF) - Rectifier in Current limit Wink (0.5 Sec ON and 2 Sec OFF) - Rectifier in Standby/ Sleep mode Fault (Red) 3 status ON - Rectifier Internal fault OFF - No faults Blink (0.5 Sec ON and 0.5 Sec OFF) - Communication fail
Detailed summary of LED indications against specific events are given in the table below :-
S. System State No 1 2 3 4 5 6 7 8 9 10 11 12 13 Rectifier delivers power in a normal mode & Communication is OK Rectifier can deliver power in a normal mode & Communication has Failed. AC Input out of range (irrespective of whether Rectifier is in standby or not) Output Current Limit OR Rectifier Walk-in OR Hiccup due to deep overload` Output voltage <38Vdc and not current limit Output short shutdown (latch) Fan fail Over temperature protection Output over voltage Present not OK, Rectifier is not plugged OK Controller keeps Rectifier in standby. No AC, have DC power for rectifier control circuit No AC, No DC
ACF AMB 0 0 1 0 0 0 0 0 0 0 0 1 0
6. EP3000AC48 Rectifiers
Overview
The EP3000AC48 Rectifiers are rugged and robust rectifiers that have been exclusively designed to take care of wide line fluctuations and extreme climatic conditions prevailing typically in rural/ semi-urban areas (B & C telecom Circles) of India . The Rectifiers are designed to operate as an integral part of the EP48XXX Plant, with or without battery back-up. These Rectifiers are compatible with the Galaxy family of controllers available from Lineage Power. These Rectifiers are compatible for installation into the EP48XXX shelf.
Salient Features
Backward compatible with EP2500AC48. 176Vac to 290Vac input operation at Full Power. 90Vac to 176Vac de-rated linearly below 176Vac @ 0.65% per volt, leading to 1323W at 90VAC Output power of 3000W from -48V to -58V Operating temp. range: -10 to +75C Full power range: -10 to +50 C De-rated power range : +50 C to +75C (de-rated power @ 2.4% per C ) Efficiency >92% for input voltages>230Vac, Output = 54VDC & load between >= 40% , at an ambient temperature of 25 Deg. C. No Damage Input voltage range: 0 to 500Vac (Line to Neutral) for battery floated application This ensures adequate protection even against Line to Line voltages appearing across the rectifiers in case of Neutral disconnect conditions which are not uncommon in rural/ semiurban areas) Can withstand 96 hrs of salt spray test (as per ASTM B117), Special protective coating on the PCBs and superior plating on the metal parts. This makes the rectifier suitable for working in coastal areas having salty atmosphere Less than 10% Current THD Typical Power Factor Correction Low electrical output noise Hot Swappable, Hot Pluggable and Parallel operation with load sharing Radiated and Conducted EMI emissions at system level to conform with CISPR-22 Class A ON/Standby control Through Controller only Rectifier control and alarms operational during input ac failure. Auto recoverable from over temperature shutdown. Latched and auto-restart shutdowns with software restart or AC input recycling. Front LED indicators and Controller signaling are powered via the DC output (back biased) Fuse fail detection of Input Fuse
Input Behavior
Linear de-ration of power for poor grid voltage Input operating voltage range (90 to 290Vac) Full power range (3000W) -176 to 290Vac 90Vac to 176Vac de-rated linearly below 176Vac @ 0.65% per volt, leading to 1323W at 90VAC Power De-rating with input voltage
3000
Power (W)
1000 500 0 70 90 110 130 150 170 190 210 230 250 270 290 310
Output Behavior
3000W power capability, with a constant power range of 48 to 58Vdc Capability of delivering upto 62.5Amps @ 48Vdc & 58Amp@52VDC.
VI Characteristics
75
48
Constant Current 25
Figure 6-4: EP3000AC48 Rectifiers Front View with LEDs The LEDs are ACF (yellow), NORM (green), FAIL (red) from left to right. A Logical Summary of LED Indications on Panel is as given below:AC Fail (Amber) 2 status ON - AC input out of range (i.e. <90Vac or >290Vac) OFF - AC is normal Normal (Green) 4 status ON - DC Output OK OFF- DC Output Not OK Blink (0.5 Sec ON and 0.5 Sec OFF) - Rectifier in Current limit Wink (0.5 Sec ON and 2 Sec OFF) - Rectifier in Standby/ Sleep mode Fault (Red) 3 status ON - Rectifier Internal fault OFF - No faults Blink (0.5 Sec ON and 0.5 Sec OFF) - Communication fail
Detailed summary of LED indications against specific events are given in the table below :-
S. System State No 1 2 3 4 5 6 7 8 9 10 11 12 13 Rectifier delivers power in a normal mode & Communication is OK Rectifier can deliver power in a normal mode & Communication has Failed. AC Input out of range (irrespective of whether Rectifier is in standby or not) Output Current Limit OR Rectifier Walk-in OR Hiccup due to deep overload` Output voltage <38Vdc and not current limit Output short shutdown (latch) Fan fail Over temperature protection Output over voltage Present not OK, Rectifier is not plugged OK Controller keeps Rectifier in standby. No AC, have DC power for rectifier control circuit No AC, No DC
ACF AMB 0 0 1 0 0 0 0 0 0 0 0 1 0
Three levels of security protect incoming access: user, super-user, and administrator. A user has read ability and can only get status information from the controller. A super-user can change configurations and perform control operations. An administrator has all the abilities of a super-user but can also change passwords. All access to ICOMBO is via the T1.317 command set, to be discussed later. This section describes how to log into the system via an RS-232 local port. The first step to logging in is to get to an ENTER PASSWORD: prompt. From a terminal connected to the RS-232 port, simply press ENTER until you see the log-in prompt. The number of ENTER keys required will depend on the baud rate you are trying to connect at. The controller will adjust its baud rate automatically until it recognizes the carriage return character (ASCII 13) sent by pressing ENTER. At the ENTER PASSWORD: prompt, type the user or super-user password. The default password for each level of security is listed below. Default User password Default Super-user password Default Administrator password lineage super-user administrator
After receiving the correct password, the controller will respond with one of the following command line prompts: User command-line prompt: *
Super-user command-line prompt: ** When these prompts appear the controller is ready to accept commands. Note that the session will be terminated if the port is idle for 15 minutes.
To enable low-temperature slope thermal compensation, type in the following command: cha sc1,rve=1 To change the voltage at which the LVD contactor disconnects the batteries from the load to 40V, type the following: cha cn1,dth=40 To initiate a manual boost charging, i.e., place the plant into boost charging mode, type in the following command: ope dc1,stt=boost The tables below summarize the object-attribute pairs in the system along with the commands that can be used with the pair and the valid range that the attribute may have. The values in bold text are the default settings for the attributes.
Power System obj,attr description ps1,des Power system description ps1,sid Site ID ps1,swv Software version ps1,verb Boot Version ps1,dflt Defaults file version ps1,usl Uninstall missing equipment ps1,ltt Lamp test ps1,dat Date ps1,tim Time ps1,dls Daylight savings enable ps1,ptt Communication port type ps1,dss Daylight saving start ps1,dse ps1,amt ps1,cst ps1,fst ps1,fstl ps1,rss ps1,uet ps1,fpp ps1,slv Daylight saving end System ambient temperature Display contrast Load factory default Load factory defaults list Restart all devices in system Uninstall popup timeout Front Panel Pin Port security level
type text text text text text number number date time number text d:d:d:d d:d:d:d number number text text number number Number text
range:default IC091 Up to 15 characters: mm.nn mm.nn desc-mm.nn 1 1:do it yyyy-mm-dd Hh:mm:ss (24 hour format) 0:disabled 1:enabled:0 LOCAL,MODEM:LOCAL mon:wk:dow:min mon:-1:dom:min mon:wk:dow:min mon:-1:dom:min dd C 0 to 100%:50 Up to 15 characters comma delimitated list 1:do it 0 to 60: 15 4 digit Pin (only viewable as admin)
AC Distribution obj,attr description Acd1,prv Phase R voltage Acd1,psv Phase S voltage Acd1,ptv Phase T voltage Acd1,pra Phase R current Acd1,psa Phase S current Acd1,pta Phase T current
DC Plant obj,attr dc1,stt dc1,vdc dc1,adc dc1,sha1 dc1,trd dc1,cap dc1,olcap dc1,scap dc1,isd dc1,rss dc1,bod dc1,nst dc1,rtm
description Plant state Plant voltage Plant load current External shunt size Plant total rectifier drain Total installed rectifier capacity Total on-line rectifier capacity Battery String capacity Imminent shutdown enable Rectifier restart Battery on discharge Number of battery strings Actual reserve time
type text number number number number number number number number number number number text
Efficiency management enable Efficiency target Efficiency turn on rectifier threshold Efficiency initial delay Efficiency delay related command sta cha ope
range:default FLOAT, BOOST dd.dd V ddd.d A synonym for dcm01,sha ddd.d A ddd.d A ddd.d A dddd A 0:disable 1:enable:0 0:no action 1:restart 0:on discharge 1:not on discharge 0-16:0 Low Current-Batt current too low High Current-Batt current too high dd.d (in hours) 0=disable, 1=enable 20 to 95 % 25 to 100 % 1 to 30 minutes 1 to 30 minutes
Alarms With Two Thresholds obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,led LED objid,fth Alarm boost threshold objid,bth Alarm float threshold objid,sev Alarm severity
range R1- R7, or 0:not active 1:active BD,AC,DC, see below see below CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted
acc
default attribute values (range:default) sev fth bth MIN 50-60V:56 50-60V:56 MAJ 50-60V:57 50-60V:57
Alarms With One Threshold obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,led LED objid,thr Alarm threshold objid,sev Alarm severity
range R1- R7, or 0:not active 1:active BD,AC,DC, see below CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted
Object IDs obj amth1 amtl1 bda1 bta1 rrtl1 rtl1 vla1 description High ambient temp Low ambient temp Battery on discharge High battery temperature Real-time reserve low Reserve time low Very low voltage
default attribute values (range:default) acc sev thr MIN 35-75C:75 MIN -40-10C:-40 R1 MAJ 46-55V:51 MIN 30-85C:55 MAJ 0-99.9hrs:0 MIN 0-99.9hrs:0 R1 MAJ 40-51V:46
Alarms With No Threshold obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,sev Alarm severity
objid,led
LED
text
range R1- R7, or 0:not active 1:active CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted BD,AC,DC,
Object IDs obj acf1 amj1 bbl1 bfa1 description AC fail Major auxiliary alarm Clock battery low Check battery alarm
btf1 btj1 btn1 bts1 cnf1 cnf2 cnf3 cnf4 cma1 cno1 cno2 cno3 cno4 cpa1 epo1 faj1 fan1 isd1 macf1 mcm1 mrfa1 osa1 rf1 rfa1 rfn1 rls1 rpff1 rprl1 rpfj1 rpxj1 rpxn1 scd1 tpa1 vmf1 vsf1
(lithium) Battery fuse Multiple (lithium) battery fail (lithium) Battery fail Battery test active Battery contactor fail Load 1 contactor fail Load 2 contactor fail Load 3 contactor fail Minor communication Battery contactor open Load 1 contactor open Load 2 contactor open Load 3 contactor open Modem failure Emergency power (battery) off Major fuse alarm Minor fuse alarm Imminent shutdown Multiple AC fail Major communication Multiple rectifier fail Open string alarm Ringer 1 fail Rectifier fail Rectifier fan fail Rectifier redundancy loss Ringer 1 fan fail Ringer 1 redundancy loss Ringer 1 fail major Ringer 1 major external fault Ringer 1 minor external fault Battery voltage imbalance Thermal probe fail Voltage module fail Sense voltage fail
R4
R2 R3
R3
MAJ MAJ MIN RO MAJ MAJ MAJ MAJ MIN MAJ MAJ MAJ MAJ MIN MAJ MAJ MIN MAJ MAJ MAJ MAJ MAJ MIN MIN MIN MIN MIN MIN MAJ MAJ MIN MAJ MIN MIN MAJ
Alarm Test obj,attr description at1,stt Auxiliary event 1-6 description at1,stg Auxiliary event 1-6 alarm state at1,dur Auxiliary event 1-6 severity at1,pcrj Include PCR relay in test at1,pmj Include PMJ relay in test at1,pmn Include PMN relay in test at1,r1 Include R1 relay in test at1,r2 Include R2 relay in test at1,r3 Include R3 relay in test
type text text text number number number number number number
Range:default 0=not in progress 1=in progress 5 to 300:60 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable
Include R4 relay in test Include R5 relay in test Include R6 relay in test Include R7 relay in test Audio Test State Audio Test Duration
0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 1=start test 5-300 seconds
type text
range:default ON,OFF,STANDBY,MISSIN G,VACANT Only ON and STANDBY maybe used with the OPE command. ddd number number number
range:default dd C d A (+ for discharge, - for charge) ddddd AH ddddd AH 0:stop 1:start 0=disable,1=enable
detection enable br1,scv br1,ntm br1,nvm br1,cle br1,clt Battery imbalance threshold Number of temperatures present Number of mid-cell V present Recharge current limit enable Recharge current limit threshold Discharge test results number
number number
(Automatically enabled when mid cell V monitor present) 1.5-3.0V:1.7 d d 0=disable,1=enable:0 5-1000A/string:10
br1,btr
text
br1,btc
Battery type
text
br1,btl br1,bty br1,sev br1,bte br1,atd br1,ath br1,atw br1,tin br1,tmd br1,tev br1,btv
Battery type list Battery model String end of discharge voltage Auto test enable Auto test date Auto test start hour Auto test min hours after BD Auto test interval Manual test duration Manual test alarm voltage Battery test rectifier voltage
Text number number date number number number number number number
result, reserve, load result is one of the following: COMPLETED CHECK BATTERY INTERRUPTED ACTIVE NOT RUN reserve is hours calculate by last complete test load is load at beginning of test "VALVE-REG","FLOODED", "LIRK", "NICD", "LI-LMP":"VALVEREG" Comma delimited list Up to 14 chars 36-48 V:44.4 0=disable,1=enable:0 dd-mmm-yy 0-23:0 0-240 hours:0 1-18 months:12 0.1-99.9 hours: 4 36-48 V:44.4 42-52 V:44
Ringer Plant obj,attr description RP1,frq Ringer output frequency RP1,vsp Ringer voltage set-point RP1,ofe Ringer offset enable RP1,rme Redundancy monitor enable RP1,rss Ringer restart
type number
RC1-2,va RC1-2,pri
number text
RC1-2,sec
Secondary ringer
text
Minor ringer failed Fan in chassis failed Major ringer failed Redundancy lost in chassis Major external fault Minor external fault
range:default ON FAN, -REDUN OFF FAIL, -EXT, -TA, -RET, FAN STANDBY MISSING The ope command supports the ON and STANDBY states dd.d VA sr where s is the shelf number r is the ringer position 1=first primary ringer 3=second primary ringer First ringers are in the odd shelf slot. Second ringers are in the even shelf slot sr where s is the shelf number r is the ringer position 2=first secondary ringer 4=second secondary ringer First ringers are in the odd shelf slot. Second ringers are in the even shelf slot 1=failed 1=failed 1=failed 1=failed 1=failed 1=failed
Boost Management obj,attr description bs1,abe Auto boost enable bs1,tmd Maximum boost duration in hrs
type text
Disconnect remaining time Reconnect threshold Reconnect delay Reconnect auto mode
cn1-4,rtm
number
range:default NONE MISSING CLOSED OPEN -MAN, - REM, -EPO, -V, TIME, -FAIL 0=disable,1=enable:1 39-50V:42 0-300 minutes:0 0=NONE 1=VOLTAGE 2= VOLTAGE+TIME :1 >0 means going to disconnect 39-55:44V 0-300 seconds:0 0=NONE 1=VOLTAGE 2=VOLTAGE+TIME :1 >0 means going to reconnect
The contactors are identified as follows: CN1 = Battery Disconnect (LVBD1) CN2 = Load 1 Disconnect (LVLD1) CN3 = Load 2 Disconnect (LVLD2) CN4 = Load 3 Disconnect (LVLD3)
Distribution Current Monitor obj,attr description dcm01-07,stt State related commands sta cha ope type text range:default NONE MISSING PRESENT NONE LOAD BATTERY ddd.d Amps 0-9999 Amps
Shunt Type
text
number number
The shunt type defaults are as follows: DCM01 = Battery DCM02 = Battery DCM03 = Battery DCM04 = Load
type text
dcn01-04,typ
text
The contactor interface type defaults are as follows: DCN01 = LVBD1 DCN02 = NONE DCN03 = NONE DCN04 = LVLD1
Slope Thermal Compensation obj,attr Description sc1,stt Slope compensation enable sc1,rve Raise voltage enable sc1,ltt Low temperature limit sc1,ntt Nominal temperature sc1,utt Upper temperature limit sc1,spt Step temperature sc1,lsp Low temperature slope sc1,usp Upper temperature slope related commands sta cha ope type number number number number number number number number range:default 0=disable 1=enable:1 0=disable 1=enable:0 -5-20:0C 15-30:25C 30-55:45C 45-85:75C 1-5:3mV/C per cell 1-5:3mV/C per cell
Input Management obj,attr description inmn,stt Input state inmn,typ Input alarm type
inmn,pol Input alarming polarity text where: m is the distribution interface module ID from 1 to 4 n is the input number from 01 to the number of inputs supported by the distribution interface module
range:default 0:not alarming 1:alarming alarm object ID (i.e. faj1,fan1,aux1 to aux6, and remlvd) remlvd identifies the remote disconnect function; the contactor will open when input is in the alarming state. CLOSED, OPEN
Serial Ports obj,attr Description mp1,bdr Modem baud rate mp1,ins Modem initialization string mp1,nrg mp1,hsh mp1,wre lp1,bdr lp1,hsh Modem number of rings before answering Modem handshaking Write Enable Local RS-232 baud rate Local RS-232 handshaking
range:default 2400,4800,9600:2400 Up to 20 characters: AT&FEV&C1S0=0H 1-9:1 rings NO: none SW: xon and xoff 0=disable 1=enable AUTO,2400,4800,9600:AUTO NO: none SW: xon and xoff HW: cts and rts 0=disable 1=enable
lp1,wre
Write Enable
Number
type number
Range 5-1000A
CutAlarm Cut-off obj,attr Description aco1,dur Cut-off duration aco1,stt Alarm Cut-off State aco1,lbe Local Buzzer Enable
Figure C-1: Slope Thermal Compensation The following describes the configuration parameters which may be activated or altered by the user. Refer to Appendix D for the ranges of values the parameters may take and their factory default settings. Lower Thermal Limit (ltt): The lower temperature where, if Low Temperature Compensation is enabled, the controller will increase plant voltage to a level corresponding to (lsp * (ntt - ltt)* 24)V above the fsp. Plant voltage will be increased proportionally at any temperature between this point and the Battery Thermal Slope Nominal Temperature (ntt). Low Temperature Compensation Enable (rve): A 0 disables and 1 enables the Low Temperature Thermal Compensation feature. Since rve increases plant voltage rather than decreasing it based on temperature, the option is provided to disable it separately from the entire feature so that equipment loads sensitive to high voltages can be protected.
Lower Temperature Slope (lsp): The slope rate for the voltage increase per cell when
the battery temperature is below the ntt (Battery Thermal Slope Nominal Temperature). Battery Thermal Slope Nominal Temperature (ntt): The zero compensation temperature point. Temperatures monitored between this point and the Upper Temperature Limit (utt) will result in a proportional decrease of plant voltage to a level corresponding to (usp*(uttntt)*24)V below the fsp at the utt. If Low Temperature Compensation is enabled, temperatures monitored between this point and the Lower Thermal Limit (ltt) will result in a proportional increase of plant voltage to a level corresponding to (lsp*(ntt-ltt)*24)V above the fsp at the ltt. Upper Temperature Slope (usp): The slope rate for the voltage decrease per cell when the battery temperature is above the ntt (Battery Thermal Slope Nominal Temperature). Upper Temperature Limit (utt): The upper temperature where Battery Thermal Compensation will have reduced plant voltage to a level corresponding to (usp*(utt-ntt)*24)V below the fsp. Plant voltage will be reduced proportionally at any temperature between this point and the Battery Thermal Slope Nominal Temperature (ntt). Battery Thermal Alarm Threshold (thr): A monitored battery temperature above this threshold results in a Battery Thermal alarm with a PMN severity. Battery Thermal Step Temperature (spt): A monitored battery temperature above this threshold results in an additional 4.08V step decrease in plant voltage.
Automatic Test: Enable or disable automatic periodic running of the battery test. The factory default setting is disabled. Interval: The test interval (time between tests) can be set from 1 to 18 months in 1 month increments. The factory default setting is 12 months. Next Test: Enter a particular day in dd-mm-yy format to automatically run the battery test on that day. Start Time: Enter a particular time in hh-mm format to automatically run the battery test at that time. The setting can be configured from 0 to 23 hours. 00:00 is midnight. Hours from BD: Time interval needed to elapse since the last Battery on Discharge alarm before a battery test can be performed. This can be set from 0 to 240 hours in 1 hour increments. The factory default setting is 72 hours. Recharge Amp Limit: This section contains the settings for battery recharge current limit. Limit: Enable or disable battery discharge current limiting. Limit To: Current limit setting, from 5A to 1000A. The factory default setting is 50A. During this test, the controller lowers the rectifier voltage to 44V. (This value was chosen to be higher than 1.2V plus the highest possible LVD contactor disconnect threshold so as not to accidentally open the LVD contactor.) Lowering the rectifier output voltage to 44V creates a battery on discharge condition. If the batteries are present and healthy, the plant voltage will remain above 48V and the batteries will support the load. If the batteries are not present or are not able to support the load, the plant voltage will immediately drop to approximately 44V without any consequence to the load. The Battery on Discharge alarm is masked during this test. The test is terminated by the occurrence of any of the following conditions:
Initiating another Plant Battery Test. That is, once the test has been initiated, the test may be stopped by initiating another test either through the controller or by shorting pins 19 and 20 of the host interface connector. An alarm condition occurring. Any alarm condition that occurs during this test will result in the test being aborted regardless of whether the contact-closure exists between pins 19 and 20 of the host interface connector. The test has continued for over 100 minutes.
The plant voltage has dropped below 44V. In this case, the system will abort the test and resume rectifier operation.
After the test has stopped, the plant will revert to the float mode. It may go to boost mode if the auto-boost feature has been enabled.
Boost Mode
Boost charging is a feature of I-combo controller, which allows the user to temporarily raise the plant voltage to a higher, predetermined level, thus, reducing the time needed to charge batteries. The system may manually be placed in the boost-mode through the front panel. Note that the measured boost voltage may not exactly match the value chosen by the user if the thermal compensation feature is enabled. This is because the Galaxy Pulsar Plus performs thermal compensated boost charging and will adjust the boost value based on the battery temperature per the slope chosen by the user. The plant will exit the boost mode and enter the float mode if any of the following occurs:
The current flowing into the battery string(s) is less than 5A The duration of boost mode charging has reached the configured duration time (1-80) hours The controller receives either a High-Voltage, Rectifier Fail alarm, or High-Battery Temperature alarms User sets the plant state to Float via the TI.
Once initiated, the boost mode may be exited by placing the Plant State to Float.
Auto-Boost Charge
This feature may be enabled from the TI. See Appendix B for details. When enabled, the plant enters the boost-charging mode of operation following a battery discharge once the BD alarm has been retired, provided the duration of the discharge was greater than 4 minutes. The controller will not enter the auto-boost-charging mode if the discharge duration was less than 4 minutes. When in auto-boost mode, the controller raises the plant voltage to the value selected by the user. The controller keeps the plant in this mode of operation for a minimum of 5 minutes. The exit conditions for the Auto-Boost Charge are the same as those for Boost Charge.
enough time to charge up to the nominal fsp and to prevent any spurious BD alarm conditions. This feature may be used by customers as part of their overall battery maintenance program in determining the health of battery strings. A voltage imbalance of 1.7V between half-string voltages may mean a shorted-cell, loose connection, or some other abnormality somewhere in the string. A service person should be sent out to the site and determine if the string should be replaced.
Description High Voltage Minor (HFV) High Voltage Major (HFVS) Battery on Discharge (BD) Very Low Float Voltage (VLV) Fuse Major Fuse Minor Auxiliary Major Alarm AC SPD Fail DC SPD Fail Auxiliary 3 Fan Fail Air Cond Fail Door Open Hi Ext Amb Hydrogn Prsnt Auxiliary 9 Auxiliary 10 Voltage Imbalance Detect High Battery Temperature Batter Test Active Open String Emergency Power Off (EPO) Check Battery (Plant Battery Test Fail) Defective Temp Probe Reserve Time Low Real-Time Reserve Time Low
CRIT
PMJ
PMN MIN
RO
R1
R2
R3
R4
R5
R6 R6 R6
R7
BD
AC
DC
MAJ MAJ CRIT CRIT MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MIN MAJ RO MAJ MAJ MIN MIN RO RO R1 R4 R5 R5
BD
DC DC
BD R7 DC
ISD1 CNF1 CNO1 CNF2 Contactor Alarms CNO2 CNF3 CNO3 CNF4 CNO4 RLS1 RFA1 Rectifiers MRFA1 RFN1 ACF1 AC Power MACF1 CMA1 MCM1 Controller VSF1
Imminent LVBD Shutdown LV Disconnect Contactor 1 Fail LV Disconnect Contactor 1 Open LV Disconnect Contactor 2 Fail LV Disconnect Contactor 2 Open LV Disconnect Contactor 3 Fail LV Disconnect Contactor 3 Open LV Disconnect Contactor 4 Fail LV Disconnect Contactor 4 Open Rectifier Redundancy Loss Single Rectifier Fail (RFA) Multiple Rectifier Fail (MRFA) Rectifier Fan Fail Single AC Fail (ACF) Multiple AC Fail (MACF) Communication Loss Minor Communication Loss Major Sense Fuse Controller Fail (Not user mappable) Un-powered Controller CRIT
MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MIN MIN R3 R3 MIN MIN MAJ MIN MAJ MIN x x x x x x x x x x R2 R2 AC AC R5 R5 R7 R7 DC DC DC DC
Issue History
Issue 0.1: Released for review and comments