Vous êtes sur la page 1sur 93

IPMS Product Manual annexureJune- 2010

IPMS Product Manual annexure for

SMPS
Notice: The information, specifications, and procedures in this manual are subject to change without notice. Lineage Power assumes no responsibility for any errors that may appear in this document.

All international rights reserved Printed in India

IPMS Product Manual annexureJune- 2010

Table of Contents
1. INTRODUCTION ...................................................................................................................................................5 OVERVIEW .........................................................................................................ERROR! BOOKMARK NOT DEFINED. GENERAL ASSEMBLY DRAWINGS ......................................................................ERROR! BOOKMARK NOT DEFINED. CUSTOMER SUPPORT .........................................................................................ERROR! BOOKMARK NOT DEFINED. Customer Training ............................................................................................... Error! Bookmark not defined. Customer Service ................................................................................................. Error! Bookmark not defined. Technical Support ................................................................................................ Error! Bookmark not defined. Product Repair and Return .................................................................................. Error! Bookmark not defined. Warranty Service.................................................................................................. Error! Bookmark not defined. Downloads and Software ..................................................................................... Error! Bookmark not defined. SAFETY MANUAL ..............................................................................................ERROR! BOOKMARK NOT DEFINED. Safety Statements.................................................................................................. Error! Bookmark not defined. Warning Statements and Safety Symbols ............................................................. Error! Bookmark not defined. Precautions .......................................................................................................... Error! Bookmark not defined. Handling Batteries ............................................................................................... Error! Bookmark not defined. 2. SYSTEM DESCRIPTION .....................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM BLOCK DIAGRAM.................................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM COMPONENTS ......................................................................................ERROR! BOOKMARK NOT DEFINED. SYSTEM CONFIGURATIONS ........................................................................................................................................6 SYSTEM ARCHITECTURE ............................................................................................................................................9 Single Line Diagram of EP48XXX Plant .............................................................................................................9 SYSTEM SPECIFICATION...........................................................................................................................................11 Key Features ......................................................................................................................................................15 Key Specifications ..............................................................................................................................................17 3. ICOMBO CONTROLLER...................................................................................................................................18 OVERVIEW ...............................................................................................................................................................18 GENERIC INTERFACE REQUIREMENTS .....................................................................................................................19 KEY FEATURES ........................................................................................................................................................19 SPECIFICATIONS.......................................................................................................................................................19 Analog Inputs .....................................................................................................................................................20 Digital Inputs .....................................................................................................................................................22 COMMUNICATIONS ..................................................................................................................................................23 GP Interface.......................................................................................................................................................23 Programming Interface......................................................................................................................................24 SYSTEM CONTROL INTERFACE ................................................................................................................................24 Alarm Outputs ....................................................................................................................................................24 Front Panel Alarm LEDs..................................................................................................................................25 Factory Default Assignments for Alarms & LEDs............................................................................................26 USER INTERFACE GUIDE ..........................................................................................................................................26 Front Panel Keypad ...........................................................................................................................................26 System Status Indicators ....................................................................................................................................27 Local and Remote Access Ports .........................................................................................................................28 User Interface Menu Structure...........................................................................................................................28 Personal Identification (PIN).............................................................................................................................29 User Interface Menu Flow Map .......................................................................................................................31 ...........................................................................................................................................................................35 CONFIGURATION-Continued in next page...................................................................................................35 ...........................................................................................................................................................................36 CONFIGURATION-Continued in next page...................................................................................................36 ...........................................................................................................................................................................37 STATUS ....................................................................................................................................................................38

IPMS Product Manual annexureJune- 2010 Rectifiers............................................................................................................................................................38 Batteries.............................................................................................................................................................38 Shunt Currents ..................................................................................................................................................39 Disconnect States ..............................................................................................................................................39 Alarm Thresholds..............................................................................................................................................39 Enabled/Disabled Info ......................................................................................................................................39 This section of the menu provides a location to determine the Enable/Disable status of most of the Icombo controller features..............................................................................................................................................39 System Info ........................................................................................................................................................40 CONTROL/OPERATIONS ...........................................................................................................................................41 History ...............................................................................................................................................................42 CONFIGURATION .....................................................................................................................................................42 Float Settings.....................................................................................................................................................42 Shunt Monitors..................................................................................................................................................43 Rectifiers............................................................................................................................................................44 Batteries.............................................................................................................................................................44 Contactors..........................................................................................................................................................46 Disconnects........................................................................................................................................................46 Boost ..................................................................................................................................................................47 ACO ...................................................................................................................................................................48 System Settings ..................................................................................................................................................49 Communication Ports .......................................................................................................................................49 OVERVIEW..............................................................................................................................................................54 4. EP2500AC48 Shelf........................................................................................................................................55 OVERVIEW ...............................................................................................................................................................55 A. Standalone Shelf for accommodating six rectifiers........................................................................................55 SPECIFICATIONS.......................................................................................................................................................56 CONFIGURATION REQUIREMENTS ............................................................................................................................57 B. Shelf-less Concept for accommodating 2, or 3 rectifiers...............................................................................58 5. EP2500AC48 RECTIFIERS .................................................................................................................................60 OVERVIEW ...............................................................................................................................................................60 SALIENT FEATURES .................................................................................................................................................61 INPUT BEHAVIOUR...................................................................................................................................................62 OUTPUT BEHAVIOUR ...............................................................................................................................................63 USER INTERFACE (LED INDICATIONS) ....................................................................................................................64 6. EP3000AC48 RECTIFIERS .................................................................................................................................66 OVERVIEW ...............................................................................................................................................................66 SALIENT FEATURES .................................................................................................................................................67 INPUT BEHAVIOUR...................................................................................................................................................68 OUTPUT BEHAVIOUR ...............................................................................................................................................69 USER INTERFACE (LED INDICATIONS) ....................................................................................................................70 APPENDIX B THE T1.317 COMMAND LANGUAGE .....................................................................................72 INITIALIZING THE IC091_ICOMBO CONTROLLER .....................................................................................................72 RS-232 TERMINAL ..................................................................................................................................................72 T1.317 COMMAND LANGUAGE ................................................................................................................................73 Objects and Attributes........................................................................................................................................73 APPENDIX C EXPLANATION OF BATTERY MANAGEMENT FUNCTIONS .........................................84 FLOAT MODE ...........................................................................................................................................................84 SLOPE THERMAL COMPENSATION ...........................................................................................................................84 High Temperature Alarm ...................................................................................................................................84 High Temperature Compensation ......................................................................................................................84 Low Temperature Compensation .......................................................................................................................85 PLANT BATTERY TEST.............................................................................................................................................87

IPMS Product Manual annexureJune- 2010 BOOST MODE ..........................................................................................................................................................89 Auto-Boost Charge.............................................................................................................................................89 Redundancy Loss Function ................................................................................................................................90 Battery Voltage Imbalance Detection ................................................................................................................90 Battery Recharge Current Limit.........................................................................................................................91 Battery Parameter Defaults ................................................................................. Error! Bookmark not defined. APPENDIX D - FACTORY DEFAULTS FOR ALARMS & LEDS ...................................................................92 ISSUE HISTORY ......................................................................................................................................................93 ISSUE 0.1 .................................................................................................................................................................93

IPMS Product Manual annexureJune- 2010

1. Introduction Overview
Lineage Power developed the Galaxy Power System EP4803 / EP4806 / EP4812 to support -48 volt telecommunications powering solutions for the Indian market. The EP48XXX combines fan-cooled, switchmode rectifiers, microprocessor control technologies, battery and load disconnect/reconnect options in a modular front-access design. This modularity ensures easy access, simplified installation and maintenance, and allows the system to expand in capacity and features as power needs grow. The power system accepts alternating current from the commercial utility or a standby ac power source and rectifies it to produce dc power for connected equipment. The systems control and alarm functions interact with the rectifiers and the office. In addition, the system provides overcurrent protection and charge, discharge, and distribution facilities. Battery reserve automatically provides a source of dc power if the commercial or standby ac fails. With 1200-ampere maximum capacity, distribution flexibility, Energy Monitoring features for the AC input as well as DC Loads, the EP48XXX supports switching, transmission, and wireless applications in central office locations and environmentally controlled remote sites.

Figure 1-1: Open Door Front View

IPMS Product Manual annexureJune- 2010

System Configurations
The EP 48XXX is available in two configurations: The half height cabinet, shown in Figure 1-1 (EP4803 & EP4806) mounts on top of a battery stand and can provide up to 600 amperes of dc power. The full height cabinet, shown in Figures 1-2 (EP4812) is a standalone unit suitable for floor anchoring, and can provide up to 1,200 amperes of dc power. Figure 2-2 shows the electrical schematic for the Half Height Cabinets. Figure 2-3 shows the electrical schematic for the Full Height Cabinets. Each system contains ac distribution, dc distribution panels, a battery connection panel, rectifiers, termination points for load circuits, and a system controller.

IPMS Product Manual annexureJune- 2010

Figure 2-2: Electrical schematic for the Half Height Cabinets.

IPMS Product Manual annexureJune- 2010

Figure 2-3: Electrical schematic for the Full Height Cabinets.

IPMS Product Manual annexureJune- 2010

System Architecture
The architecture of the EP48XXX platform is based on the IC091_CB ICOMBO Controller, which works as a front end master controller in addition to providing the user interface for the plant. The ICOMBO Controller provides complete control functionality, Distribution Monitoring & Control. ICOMBO is a combination of features of Pulsar plus controllers family and add-on modules (IEPSO). This approach of design gives a more centralized control and operation of power system. The ICOMBO works along with power system components and provides all the necessary supervisory, measurement, monitoring and control functions as required by the India Market. The feature set of the ICOMBO has been optimally designed considering the India Market Requirements, with new and special features such as AC Energy Monitoring, DC Energy Monitoring and Energy Efficiency. This section describes the basic architecture of the EP48XXX Power Systems designed around the use of the IC091_CB ICOMBO Controller. The key features and specifications of the IC091_CB ICOMBO Controller are described in the next chapter.

Single Line Diagram of EP48XXX Plant


Figure 2-4 shows the Single Line Diagram of a typical EP48XXX plant, highlighting the interconnections between the IC091_CB_ICOMBO Controller and the various other power system components.

IPMS Product Manual annexureJune- 2010

Figure 2-4: Single Line Diagram of EP48XXX Plant

IPMS Product Manual annexureJune- 2010

System Components
The unit is internally wired for AC distribution from the MCBs / TB to each of the individual rectifier modules, through backplane interconnects of each shelf. Rectifiers convert an ac source voltage into the dc voltage level required to charge and float the batteries and to power the using equipment. The rectifiers are installed in the EP48XXX shelf, with each shelf accepting a maximum of six rectifiers. Up to four shelves may be present. Blocks are labeled and wired to a correspondingly marked rectifier as shown.

(Front View)

IPMS Product Manual annexureJune- 2010

The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as shown below (viewed from front of the shelf), with background color indicating the respective phase from which the rectifier draws its input power. For Systems with less number of rectifiers, the uninstalled rectifiers occupy slots within the rightmost side of the shelf. R- Phase: L1 Y- Phase: L2 B- Phase: L3 G41 G31 G21 G11 G42 G32 G22 G12 G43 G33 G23 G13 G44 G34 G24 G14 G45 G35 G25 G15 G46 G36 G26 G16

IPMS Product Manual annexureJune- 2010

Controller provides the local and remote control, monitoring, and diagnostic functions required to control and monitor the power system. Batteries provide energy storage for an uninterrupted power feed to the using equipment during loss of ac input or rectifier failure. DC Distribution Panel provides over current protection, connection points for the using equipment, and bus bars used to interconnect the rectifiers, batteries, and dc distribution.

Distribution panels have DIN Circuit Breakers, or DIN Fuse modules DIN Style Breakers Ensure breakers are in the off position. Connect load cables to the load distribution return bus bar and the -48V outputs from the MCBs Verify wiring polarity at the input of the load equipment. Leave breaker switch in the OFF position until the load equipment is ready to be energized. DIN Style Fuses for Battery Connection Remove the fuses from the fuse base. Connect the negative cables of the battery to the fuse base and the positive cable from the battery to the +Ve return bus bar. Verify wiring polarity of the battery terminals. Do not install load fuse and alarm fuse until the load equipment is ready to be energized.

IPMS Product Manual annexureJune- 2010

Battery Connection Panel provides connection points for the battery strings through battery disconnect fuses or contactors and current monitoring shunts.
Connect -Ve terminal Return Battery String #2 here Connect -Ve terminal Return Battery String #3 here

Connect -Ve terminal Return Battery String #1 here

Secure Battery Cable connections with appropriate hardware. If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.

COG lead to be connected at the right most position of the DC return bus bar.

Secure COG connection with provided hardware: If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.

Connect +Ve terminal Return Common of Battery Strings and Loads here

IPMS Product Manual annexureJune- 2010

System Specification
Key Features Special Features
Redundant Power Supply for controller from AC Input, Plant Bus and Battery Strings. Energy Efficiency Algorithms

User Interface
Front accessible 64x128 LCD with control pad and intuitive menu navigation system Available front panel PIN (password) access feature Standard or customer specific factory defaults supported. Support of more than one factory default. Display of both plant voltages and plant currents on front panel. Alarm severity sensitive display backlight. Three separate configurable and assignable LED indicators, to differentiate between AC, DC and Battery events, along with Tri-color capability to indicate the severity of any alarm/event.

Alarms & Events Management


Alarm management of 48V DC distribution depending on the Load MCB card that are used of upto maximum of 64 MCBs Audible alarm and test feature 10 configurable alarm outputs with manual alarm test features 10 User definable alarm inputs. Emergency Power Off (EPO). Industry standard classification of all events, depending upon severity, into one of five categories namely Critical (PCR), Major (PMJ), Minor (PMN), Record Only (RO) Event History Log. Distribution and temperature Management Battery Fuse Fail Detection for upto 3 Fuses. DC distribution monitoring can monitor up to 8MCBs (in one card) * 8 nos. and more. Temperature monitoring upto 3 Thermal probes.

IPMS Product Manual annexureJune- 2010

Battery Management
Upto a maximum of three Battery Strings. Battery Reverse Polarity Detection for all three strings. Plant Battery Test Slope Compensation, for both low & high temp., with independent adjustable slopes. Battery recharge current limit feature Step function for Manual and automatic Boost. Remote test, and periodic discharge test capability Manual time threshold for pass/fail criteria Reserve time calculations with configurable threshold Monitoring of upto 3 Battery Temperatures using Probes Configurable mid string imbalance alarm.

Disconnects
Drive Capability for both Latching and Non-Latching Contactor types. Up to two groups of Disconnect Contactors can be controlled, one for load and second for battery. By default, upto four parallel contactors comprise the group for load contactors and up to two contactors form the group for battery contactors. Load disconnects operated by low voltage. Battery disconnect operated by voltage threshold, All contactors can be closed or open using the Local port interface.

Plant Analog Measurements


AC Energy Monitoring DC Energy Monitoring Upto 3 Battery Shunts and 4 Load Shunts Battery Mid string Voltage Measurements. Plant Bus Voltage

Communications
Supervision, measurement, monitoring and control functions through Easy View 2 PC interface software. Communication through command language based on the T1.317 standard.

Maintenance & Serviceability


Easily field replaceable controller card. Modular design & different packaging alternatives for the ICOMBO Controller.

IPMS Product Manual annexureJune- 2010

Key Specifications
Item AC Input Voltage Range Specification 176~290Vrms per phase Full Power Voltage 90~176Vrms per phase De-rated Power Voltage 10 minutes withstand capability @ 500VAC per phase (for Battery Floated Application) 1Hr withstand capability @320VAC per phase (for non-battery floated applications) -48 volts: from -36.5 volts to -60 volts 20 Watts Maximum Single Phase or Three Phase 8-line by 40-character LCD; Three status LEDs; Front panel LCD display and menu keys; From ICOMBO Controller :RS232 port: T1.317 or Easy View Up to 3 thermal probes.

No Damage Input Volts Plant Voltage Range Quiescent Power Consumption Input Power Connections Front Panel LCD user interface System Configuration Methods

Temperature Monitoring

Alarm Contact Ratings 60 VDC, 0.5A Plant Voltage Measurement Accuracy 0 to 50C (0.05% of full scale + 1 count) 48V Systems: 40 mV; 24V Systems 25 mV -40 to 85C (0.1% of full scale + 1 count) 48V Systems: 70 mV; 24V Systems 40 mV Resolution 0.01V Plant Current Measurement Accuracy 0 to +50C 0.5% of full scale -40 to +85C 1.25% of full scale Resolution 1A Temperature Measurement Accuracy One-Wire Serial probes -5 to +55C 1C -40 to +85C 3C Resolution 0.1C Environmental Operating Temperature Range Humidity Audible Noise -5 to 50C
With 2.5% per Deg. C power derating above 50 Deg. C.

10% to 95% non-condensing < 60 dBA

Table 2-1: Key System Specifications

IPMS Product Manual annexureJune- 2010

3. ICOMBO Controller
Overview
This section describes the architecture and operation of the ICOMBO Controller. It also provides detailed information about the features of the front panel keys, LEDs and Displays.

Fig 3-1: The ICOMBO Controller showing control elements

Fig shows the Front Panel user Interface and the display, identifying the control elements. For the EP48XXX plant, the available options at the front panel craft port presently include only the RS232 interface.

IPMS Product Manual annexureJune- 2010

Generic Interface Requirements


Fig 3.2 shows the typical interconnects and functionality of the various connectors available on the ICOMBO Board. For details on the specifications, functionality and interface requirements for each of the individual connectors, refer to the Advanced Features User Guide for the ICOMBO Controller.

Fig 3-2: Generic Interface Requirements for the ICOMBO Board

Key Features
For the key features and comprehensive capabilities of the ICOMBO Controller, please refer to the Advanced Features User Guide for the ICOMBO Controller Family, comcode CC109152360.

Specifications
For detailed product specifications of the ICOMBO Controller, please refer to the Advanced Features User Guide for the ICOMBO Controller, comcode CC109152360.

IPMS Product Manual annexureJune- 2010

Analog Inputs Power Supply Inputs


The ICOMBO can be wired up to derive its power from one of several sources. These sources are either one of a maximum of three battery strings, or the plant bus voltage. A bridge rectifier internal to the board is used to derive the power supply from these multiple sources. Wire up the board as below:Connector HDR-12 HDR-12 HDR-12 HDR-12 HDR-12 HDR-12 Pin 1 2 3 4 5 6 To BATT 1-ve BAT T2 -ve BATT 3 -ve LOAD -ve BATT +ve NC

Battery Shunts
The controller by default assumes the positive terminal of any battery shunt, as the terminal that is more positive under battery discharge conditions. The shunts used in power plants need to be wired considering this assumption. Upto 3 Battery Shunts can be monitored. Connection as mentioned below:Connector HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 HDR-13 Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 To Battery shunt-1+ve Battery shunt-2+ve Battery shunt-3+ve BATT +ve BB LOAD -ve BB GND BUFF-3107 (common RTM 1,2&3) RTM-2 Battery shunt-1-ve Battery shunt-2-ve Battery shunt-3-ve BATT -ve BB LOAD +ve BB GND RTM-1 RTM-3

IPMS Product Manual annexureJune- 2010

Load Shunts Up to 4 Load Shunts can be monitored. Connection as mentioned below:Connector Pin To HDR-3 1 LOAD SHUNT-1+ve HDR-3 2 LOAD SHUNT-2+ve HDR-3 3 LOAD SHUNT-3+ve HDR-3 4 LOAD SHUNT-4+ve HDR-3 5 GND HDR-3 6 LOAD SHUNT-1-ve HDR-3 7 LOAD SHUNT-2-ve HDR-3 8 LOAD SHUNT-3-ve HDR-3 9 LOAD SHUNT-4-ve HDR-3 10 GND

Battery Mid-string
Up to three Battery Mid-string Voltages can be monitored. Connection as mentioned below:Connector HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 HDR-11 Pin 1 2 3 4 5 6 7 8 To VBT 1+ve VBT 2+ve VBT 3+ve Bus bar-ve VBT 1-ve VBT 2-ve VBT 3-ve Bus bar-ve

Potential free outputs


10 potential free contacts are available. Out of which first 3 are for severity and 7 are factory programmed alarms. Connection as mentioned below:Connector HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 Pin 1 2 3 4 5 6 7 8 9 10 11 To PCR common PCR PMJ-C PMJ PMN-C PMN UR1-C UR1 UR2-C UR2 PCR

IPMS Product Manual annexureJune- 2010

HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10 HDR-10

12 13 14 15 16 17 18 19 20

UR3 UR4-C UR4 UR5-C UR5 UR6-C UR6 UR7-C UR7

Digital Inputs
General Binary Inputs
There are three general binary inputs available at HDR7 connector. Activation of these inputs takes place by pulling the lines to -48V. Connector Pin To HDR-7 1 AC SPD HDR-7 2 DC SPD HDR-7 3 AMJ HDR-7 4 OS HDR-7 5 FAN FAIL HDR-7 6 TR HDR-7 7 AIR CONDITION HDR-7 8 DOOR OPEN HDR-7 9 HIGH TEMP HDR-7 10 HIGH PRESSURE

Contactor Monitoring and Distribution Monitoring


The ICOMBO can control / monitor upto two groups of contactors namely Battery and Load. Battery group can have upto maximum of two battery contactors in parallel, and Load group can have upto maximum of four load contactors in parallel. Controller monitors the presence/absence as well as whether or not the contactors are closed or open. This is done by wiring up both the NC and NO contacts of the contactors to the board. Load distribution is monitored by load MCB fail card. It can cater upto 8 Distribution MCBs in one card. No of loads that can be monitored by the controller can be increased by connecting the cards in daisy chain distribution. Connector HDR-5 HDR-5 HDR-5 HDR-5 HDR-5 Pin 1 2 3 4 5 To GN-B1N1 GN-B1N3 LVD-NO-2 LVD-NC-2 NC

IPMS Product Manual annexureJune- 2010

HDR-5 HDR-5 HDR-5 HDR-5 HDR-5 HDR-5 HDR-5

6 7 8 9 10 11 12

MCB FAIL-IN GN-B1N-2 LVD-NO-1 LVD-NC-1 GND 3.3V out GND-out

Battery Polarity Detection


I-Combo controller prevents closure of LVBD when Battery is connected to the plant in reverse polarity. The EP48XXX plant has been typically wired up as given below, to provide this feature. Battery 1 VE Return Bus bar +Ve Battery 2 VE Return Bus bar +Ve Battery 3 VE Return Bus bar +Ve => => => => => => J1 Pin 21 J1 Pin 22 J1 Pin 23 J1 Pin 24 J1 Pin 25 J1 Pin 26

Contactor Drive
The ICOMBO can drive either latching or non-latching contactors. If Latching contactors are used, the jumper designated HDR2 should be placed across pins 1&2, else it should be placed across pins 2&3. Interface requirements as below:Connector HDR-9 HDR-9 HDR-9 HDR-9 HDR-9 HDR-9 Pin 1 2 3 4 5 6 To coil +ve (LVBD) coil -ve (LVLD) V bus +ve coil -ve (LVBD) coil -ve (LVLD) V bus -ve

Communications
GP Interface
Connector P2 (RJ11 connector) is for the GP interface to the ICOMBO controller. Connector P2 P2 P2 P2 P2 P2
Pin To

1 2 3 4 5 6

R485 + RS485 GND NC NC NC

IPMS Product Manual annexureJune- 2010

Programming Interface
SPI programming interface for the card available at six pin connector HDR1. System Control Interface Alarm Outputs There are a total of ten potential free relay outputs, which are wired up within the EP48XXX plant, from the output terminal block to the HDR10 connector of the ICOMBO Controller. All ten relays can be independently programmed to operate in normally open or normally closed condition, by appropriately configuring jumpers 1-10 located on the ICOMBO board. The configuration needs to be done as illustrated below:

Figure 3-3: Alarm Relay Configuration Jumpers for the ICOMBO

Figure 3-4: Configuring default active state for alarm Outputs

IPMS Product Manual annexureJune- 2010

Each jumper corresponds to one alarm relay and each relay output can be configured independently. The potential free contacts from the relay outputs are available at the HDR10 connector of the ICOMBO controller. Out of the ten alarm relays, seven provide the actual alarm condition, and three provide the severity associated with the alarm. The severity relays transmit Power Critical (PCR), Power Major (PMJ), or Power Minor (PMN). Each alarm is factory assigned a severity based on industry practices; however, they may be reassigned to PCR, MAJ, MIN, or RO (Record Only). An alarm condition with the RO severity results in the system controller transmitting the alarm without the severity but is stored in the history log. PCR, PMJ nor PMN are transmitted with the alarm. The seven selectable alarm relays are called User Alarm Relay 1 (R1) through User Alarm Relay 7 (R7). Each relay can operate under one or more events/conditions or even when a logical combination of certain events occur. Further, the active states for all the Relays are user definable (either normally open or closed). Table 3-1 indicates the interconnection between the I-combo Board and the user terminal blocks for the output relays. The factory default functionality for the relays is also indicated.
From TB- No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Name PCR PMJ PMN OP ALM1 OP ALM2 OP ALM3 OP ALM4 OP ALM5 OP ALM6 OP ALM7 To ICOMBO Connection HDR 10:1 HDR10:11 HDR10:2 HDR10:12 HDR10:3 HDR10:13 HDR10:4 HDR10:14 HDR10:5 HDR10:15 HDR10:6 HDR10:16 HDR10:7 HDR10:17 HDR10:8 HDR10:18 HDR10:9 HDR10:19 HDR10:10 HDR10:20 Default Functionality Power Critical Alarm Power Major Alarm Power Minor Alarm Battery on Discharge Multiple AC Fail / AC Fail Multiple Rectifier Fail / Rectifier Fail Very Low Voltage LVLD Fail / LVLD Open / Load MCB Trip High Voltage LVBD Fail / LVBD Open / Battery Fuse Fail Default Alarm State Close Close Close Close Close Close Close Close Close Close Alarm State Programmable? Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Table 3-1: User Terminal Block Default Assignments - Alarm Outputs

Front Panel Alarm LEDs


The ICOMBO Controller Front Panel has three tri-color LEDs namely AC, DC and BD, each of which can be independently assigned to glow under specific single events.

IPMS Product Manual annexureJune- 2010

Factory Default Assignments for Alarms & LEDs


Utilize the Easy View interface to reassign any of the alarm outputs to specific alarm events or to change the severity of the alarms. Refer To Appendix-E for a comprehensive list of the factory default assignments for the output alarm relays and the front panel LEDs against specific event(s) User Interface Guide Front Panel Keypad Refer to Fig 3-5, showing the User Interface of the controller. The ICOMBO controllers have six tactile buttons to use to navigate through a structured menu system. The buttons serve multiple purposes depending on the screen a user is at. These functions are summarized below.

Figure 3-5: User Interface of controller


Buttons Parameter Change Description When changing a system parameter, the buttons increase or decrease the value of the parameter.

Direction Buttons

In the Menus, the direction buttons navigate to make a selection. A black box highlighting a menu item indicates that the item has sub-menus. Enters a sub-menu or confirms a parameter change. From the Home Page only, goes to the top level Main menu. Goes up one menu level or exits a parameter change without saving.

Enter Button ESC Button

IPMS Product Manual annexureJune- 2010

System Status Indicators


The ICOMBO controller provides three separate LED indicators to help assist in providing more specific indications of the system status. These LEDs are used to provide specific indication concerning the AC and DC system status as well as a separate indicator for a Battery on Discharge state. These LEDs have factory assigned defaults as indicated in the table below. However assignments can be customized in the field using the remote interfaces.
LED Status Condition AC input to all rectifiers is in range. AC input to one rectifier is missing or out of range. AC input to two or more rectifiers is missing or out of range. DC output to all loads is normal. DC One or more of the following alarms are present: Fuse Minor 48. One or more of the following alarms are present: Open String, LVBD Open, Fuse Major 48 System under battery test (blinks) BD State not presently assigned. System equal to or below configured Battery on Discharge (BD) threshold. The ICOMBO has an audible alarm located in its display assembly. This alarm will sound when any Critical, Major, or Minor alarm is detected by the controller. The alarm can be cut-off temporary from control/operations menu. Once the audible cut-off is selected the alarms at present in the system can be observed in alarms shortcut in the main screen. An indicator on the default front panel screen is provided to inform that the audible alarm cutoff is active. The audible alarm can also be turned-back on following similar procedures.

AC

The audible alarm may be disabled altogether through proper configuration at the front panel.

IPMS Product Manual annexureJune- 2010

Local and Remote Access Ports


The ICOMBO provides communication ports for local remote access. Access to these ports depends on the specific controller configuration. The ICOMBO used in the EP48XXX plant has a front panel local DB9 RS232 asynchronous serial port.
Port Front Panel Description A laptop PC can be connected to standard DB9 connector to provide a groundreferenced RS-232 serial connection using Easy View for local access.

User Interface Menu Structure


Feature content is functionally divided at the Main Menu into following categories:

Status, Control/Operations, History & Configuration


Access to the main menu starts at the default front panel screen shown below.
Front Panel Default Menu

The front panel default screen displays the primary (Rectifier) system bus voltages along with total load. The larger font represents the rectifier output. Output voltages of rectifier outputs have two decimal points. The operating mode of the system is also displayed. Possible operating modes are: Float, Battery On Discharge, Boost, etc. Pressing the button accesses the main menu and the feature categories previously listed.

IPMS Product Manual annexureJune- 2010

Main Menu

Access to alarms, warnings, equipment status detail, basic control and operations for maintenance purposes, and system configuration can be obtained. Note: the ICOMBO has the ability to have a front Panel Password that limits configuration as well as some operations. A person with administrator level access can enable this feature through the remote interfaces. Standard ICOMBO controllers are shipped from the factory with this feature enabled.

Personal Identification (PIN)


The ICOMBO controller has the ability to restrict access from the front panel of the unit. It has the ability to enforce a four digit Personal Identification Number (PIN) requirement for users of the front panel for control/operations and configurable items. These control/operations and configurations are generally considered the items that should only be done during initial install or by specific personnel. This feature is shipped enabled from the factory in the standard ICOMBO controller. The factory default for the PIN is 1234. Each position of the password is configurable between 0~9. A sample screen like that following is required for PIN access.

The up, down, left and right arrows are used to enter the appropriate password. Upon entering a correct PIN the following momentary screen shows up and then disappears leaving the user at the menu location prior to entering the PIN.

IPMS Product Manual annexureJune- 2010

Once a user enters the PIN, total front panel access is allowed for as long as the user remains in menus other than the default menu and/or any one of the following :a) The front panel access will remain open once the PIN has been entered till the time out value. The Icombo controller has a factory configured default of 120 minutes. b) An internal counter shall be kept and reset if the user leaves the default menu and returns to others menus before the timeout period is reached.

IPMS Product Manual annexureJune- 2010

User Interface Menu Flow Map


Detailed menu flow map for each primary category of the main menu is documented and listed in the following pages. This information is followed up with brief descriptions of each of the menu items. Alarms are not hierarchal mapped and are presented in chronological order of occurrence when they are present. No Active Alarms will be displayed when there are no alarms detected by the controller.

Status Menu

STATUS-Continued in next page

IPMS Product Manual annexureJune- 2010

IPMS Product Manual annexureJune- 2010

Control/Operations

History Menus

IPMS Product Manual annexureJune- 2010

Configuration Menu

CONFIGURATION-Continued in next page

IPMS Product Manual annexureJune- 2010

CONFIGURATION-Continued in next page

IPMS Product Manual annexureJune- 2010

CONFIGURATION-Continued in next page

IPMS Product Manual annexureJune- 2010

IPMS Product Manual annexureJune- 2010

Status
The Status section of the menu system provides an overview of system components, threshold settings, and feature configuration. Configuration is not possible from the status portion of the menu system. Status items are also available through the remote port connections such as the web interface or local craft port using Easy View.

Rectifiers
Installed Capacity On-line Capacity Provides the total installed rectifier capacity in the system. The total rectifier capacity of rectifiers On-line in the system and able to produce power. Rectifiers that are running or in Standby are considered to be On-line. Rectifiers that are in RFA, ACF, etc. are not counted in the On-line capacity. The total output current drain of all rectifiers. Each individual rectifiers DC output current, AC input current, and AC input voltage by rectifier number Gmn () is available. m represents the shelf number and n represents the rectifier position number in that shelf. The state of the rectifier is also identified in the () when current is not shown. These states could be OFF: Rectifier has been shutdown due to hardware failure (ex RFA, Temp, HV). STANDBY: User has inhibited the rectifier's output voltage. User may use remote interfaces or the ope command to place a rectifier into a standby condition or during execution of energy efficiency. MISSING: An acknowledged rectifier has been removed. VACANT: Rectifier has not been installed in that position.

Total Output Current Gmn ()

Batteries
Installed Capacity Current (Chrg/Dchg) Battery Strings Highest Temp Temp Probes Mid-Cell Volts Battery Test Result Next Test Live reserve time Total installed battery capacity based upon the number of strings in the system and the Amp-Hour (AH) rating of the strings installed. Measured value of the current charging or Discharging of the batteries The total number of battery strings installed in the system. Highest battery temperature being measured by the RCB thermal probes attached in the system. Total number of installed thermal probes. Up to three probes can be monitored by the controller. Total number of installed Mid-String voltage measurement modules. Shows whether the most recent battery test was completed, and the last calculated reserve time. The date of the next automatic battery discharge test. The automatic discharge test feature must be enabled for this to work. Shows live calculated reserve time during battery discharge test.

IPMS Product Manual annexureJune- 2010

Shunt Currents
ID1-8 Displays the individual shunt monitor currents. Distribution Up to eight values can be displayed. Factory default is ID1-3 Battery currents ID 4-7 load currents.

Disconnect States
LVBD Provides LVBD (Low Voltage Battery Disconnect) status. None-Displayed for each non-configured contactor. Closed-displayed when contactors are closed and battery is connected. Open-If contactors are opened and disconnected the battery. Provides status of the three LVLDs (Low Voltage Load Disconnects ) None-Displayed for each non-configured contactor. Closed-displayed when contactors are closed and battery is connected. Open-If contactors are opened or disconnected each respective load.

LVLD(1-3)

Alarm Thresholds
Float Voltage Alarms Shows the configured settings for the Float Settings: Very High Major High Minor Battery discharge Major (BD) Very Low Voltage (VLV) alarms. Values are shown in (xx.xxV) format. Shows the configured settings for the Boost Settings: Very High Major High Minor Values are shown in (xx.xxV) format. Shows measured value of the highest battery temperature of all attached battery thermal probes. Shows configured value for the Low battery reserve time alarm. Shows configured value for the Low battery real reserve time alarm

Boost Voltage Alarms

High Batt Temp Reserve Low Real Time Reserve

Enabled/Disabled Info
This section of the menu provides a location to determine the Enable/Disable status of most of the Icombo controller features.
Temp Comp Low Temp Comp Shows whether Battery Temperature Compensation is Enabled or Disabled. Shows if the Low Temperature compensation features is Enabled or Disabled.

IPMS Product Manual annexureJune- 2010

Recharge I lim Emrgncy Pwr Off

Shows if the Recharge Current Limit feature is Enabled or Disabled. Displays whether or not the Emergency Power Off (Remote Emergency Battery Disconnect) feature is Enabled or Disabled. If Enabled, EPO is asserted when contact closure is applied to the EPO input. The controller will keep battery contactors open until this contact closure has been removed. The feature assumes that AC has been removed to the system. Shows if the automatic boost charge mode of operation is Enabled or Disabled. Shows if the automatic battery test feature is Enabled or Disabled. Shows if the Rectifier redundancy feature is Enabled or Disabled. Shows if the Mid-String Voltage imbalance detection feature is Enabled or Disabled. Shows if the Imminent system shutdown alarm (LVBD) feature is Enabled or Disabled. Shows if local buzzer is Enabled or Disabled. Shows if the energy efficiency management feature is Enabled or Disabled. Shows if the LVBD (Low Voltage Battery Disconnect) and LVLD1-3 (Low Voltage Load Disconnects) features are Enabled or Disabled. Whether or not the system can be configured through the local port.

Auto Boost Auto Batt Test Rect Redundancy Mid-Cell V Mon Imminent Shutdn Local buzzer Eff management En Disconnects Local Write

System Info
Controller Info Provides software versions running on the ICOMBO. These versions include the versions for the application code, the boot block, the display, the defaults file, and the web pages. Present Date of the ICOMBO on-board real-time clock using the configured Date format. Present time of the ICOMBO on-board real-time clock using the configured time format.

Date Time

IPMS Product Manual annexureJune- 2010

Control/Operations
The following are the system control and operation functions that can be performed from the front panel. These operations are generally used in post installation and maintenance modes.
Alarm Cut-Off Start Lamp Test Restart Devices Temporarily cuts-off (Turns off) the on-bard audible alarm. Temporarily illuminates all status indicators of ICOMBO controller. Provides the ability to restart All system serial controlled rectifiers. Provides the ability to individually reset only rectifiers at a time. This operation does not affect rectifiers and other system devices that are already functioning. Used to clear momentary events or alarms. It clears the following system alarms: Check Battery, Reserve Time Low, Battery Voltage Imbalance Clears alarms related to the removal of a system component such as a rectifier, thermal probe etc. Running this command allows the system controller to retake inventory of using equipment. This area of the menus system can be used to clear the various items that the controller maintains history records. Once cleared the controller begins to keep history of new events. Alarm History: Clears only alarm event history. BD History: Clear only BD network access history. Boost History: Clears only Boost event history. This area of the menus system can be used to clear the various items that the controller maintains statistical records. Once cleared the controller begins to keep new statistical data. Clear Basic Clears individually or as a group the Basic statistical data kept on Plant Load, the highest battery temperature, and ambient. Clear Trend Clears the trend data kept on the plant load. Clears the Battery on Discharge (BD) statistics kept on the plant load and voltage during discharge. Provides ability to initiate an alarm relay test on all output relays. Alarm relays are asserted at the configured alarm interval. Provides ability to initiate a audio buzzer test. Resets reserve time Initiates the manual battery test feature. A stop battery test operation is displayed to interrupt the testing and return the unit to normal operation. The manual battery test utilizes the configured test duration and a system bus voltage threshold to represent the end of reserve. Initiates the manual battery Boost feature. A stop battery Boost operation is displayed to interrupt the Boost operation mode and return the unit to normal operation. Provides individual manual control (to open or close) of up to four Low Voltage Disconnects (LVBD, LVLD1-3) for maintenance purpose. This operation allows a user to bring back all factory defaults with a single operation. Factory defaults are also custom configuration defaults that are available. Custom configurations may support multiple factory defaults. Clear BD

Clear Events Uninstall Equipment Clear History

Clear Statistics

Alarm Relay Test Alarm buzzer Test Reset reserve time Start Battery Test

Start Boost

Disconnects Load Config Defaults

IPMS Product Manual annexureJune- 2010

Reset Admin Password

Caution should be used when applying this command. Previous configuration changes will be overwritten. Resets user, super-user and administrator passwords back to standard defaults.

History
This area of the menu system contains event history information. The controller works on a first record in first record out once the record size of a specific field is reached. The following system history logs are available:
Alarm History BD History Boost History Chronological view of the last 500 alarms and events that have occurred since the last time the history log was cleared. Chronological view of the last 16 battery on discharge (BD) events since the last time the history log was cleared. Chronological view of the last 16 times the system entered boost mode since the last time the history log was cleared.

Configuration
The Configuration section of the menu system is where system operational parameters, system device information, and alarm thresholds are set-up and modified. Factory defaults are provided for the standard ICOMBO controller. Some defaults are dependent on the battery type. Consult Appendix E for default settings of different battery. Valve-Regulated Lead Acid (VRLA) batteries and default settings defined for the Standard configuration are assumed in this section. Customer specific configurations may be different. When there is doubt, contact Lineage Power technical support. All items are field configurable. Modified settings are stored in non-volatile memory. The ICOMBO controllers require time to update sectors in flash memory for changes. Allow approximately a minute for the controller to accept and store modifications in non-volatile memory before removing power to the unit.

Float Settings
Set Point Parameter sets the value that primary (rectifier) DC bus will be set and regulated. Range: 42.00V to -56.50V factory default is -54.00V This is an Independent High Voltage Shutdown threshold during the Float mode of operation that is sent to and stored in the rectifiers that is used by each rectifier for independent high voltage monitoring. Range: 42.00V to -56.50V factory default is -54.00V Very High Major This alarm indicates an abnormally high output voltage on the secondary DC bus during Float mode. This is second and critical level of high voltage alarm. The alarm does not attempt to shut the offending unit down.

ISHVSD

Voltage alarms

IPMS Product Manual annexureJune- 2010

Range: -50.00V to -60.00V Factory default: -57.00

High Minor This alarm indicates an abnormally high output voltage on the secondary DC bus during Float mode. This is first level of high voltage alarm. The alarm does not attempt to shut the offending unit down. The threshold can be set from Range: -50.00V to -60.00V Factory default: -56.00 BD (Battery on Discharge) Major Primary DC bus threshold setting that determines when the system is determined to be operating on battery reserve. Range: -46.00V to - 55.00V. Factory default: -51.00V. Very Low Voltage Major Primary DC bus alarm threshold used to indicate a very low output voltage (VLV). Range: -40.00V to- 51.00V. Factory default: -46.00V.

Shunt Monitors
The ICOMBO controller can manage 3 battery shunts and 4 battery shunts. Shunt sizes for each assigned battery or load type must also be configured. All shunts are assumed to have a voltage rating of 50mV. The current rating of each shunt is programmable between 0 to 9999A. Systems shipped with the I-combo controllers are appropriately pre-configured in the factory for the right shunt values and assignments.
ID1-7 The operation Type of each shunt monitoring must be assigned based upon actual system implementation. The operational Type may be: None (For no shunt), Battery (Monitoring battery currents), and Load (for load currents). The current rating of each shunt being monitored by ICOMBO controller must be configured based upon actual system implementation. All shunts are assumed to be 50mV. The current rating may be from 0-9999 Amps. The factory default is 300A for battery and 200A for the load shunts.

ID1-7 Rating

Defaults The ICOMBO controller is factory configured with: ID1 ID2 ID3 ID4 Type: Battery Type: Battery Type: Battery Type: Load Shunt: 300A Shunt: 300A Shunt: 300A Shunt: 200A

IPMS Product Manual annexureJune- 2010

ID5 ID6 ID7

Type: Load Type: Load Type: Load

Shunt: 200A Shunt: 200A Shunt: 200A

Front panel displays summation of load current for default ID type settings.

Rectifiers
Redundancy An alarm is automatically generated when the load on system is more than N-X for a On-line rectifier capacity of N+X based system. X is the desired number of rectifiers to check for redundancy. The factory default for this feature is Enabled and X=1. Provides the ability to disable or enable energy efficiency feature The rectifier which takes current below this %age value will be eligible to enter into Energy efficiency standby mode. The current of that rectifier is then shared by other rectifiers. This process continues until a steady state is reached. Range: 20-95 % The rectifier which takes current above this %age value will turn ON. This process continues until a steady state is reached. Range: 25-100 % Time delay setting for the first rectifier to enter into energy efficiency mode. Range: 1-30 min Time delay setting for the next rectifier to enter into energy efficiency mode. Range: 1-30 min

Efficiency management Eff Target

Eff Turn ON

Eff Initial delay Eff Delay

Batteries
Battery Type The type of batteries used in the system can be selected from the following battery types loaded in the Standard controller:
Generic VRLA (Valve Regulated Lead Acid) Generic FLOODED (flooded lead acid) Generic NiCd (Nickel Cadmium)

Once selected the user has the opportunity to automatically accept the standard defaults for all battery Type related features. Parameters such as float voltage, float alarms, thermal compensation parameters, etc. are automatically adjusted if defaults are accepted. The system factory default is Valve-Reg. Installed Capacity Capacity of an individual battery string in the system which is used to derive the total installed system battery capacity. This value has to be entered for Generic battery types but is automatically configured for specific battery models. The value configured should be the rating to 1.75V at an 8-hr discharge rate.

IPMS Product Manual annexureJune- 2010

The available range is 0-30000 AH. The system factory default is 0 AH corresponding to the Generic Valve-Reg. Battery Strings The total number of battery string installed in the system entered by the user for inventory purposes and initial reserve time calculations. Range is 0-16 The user defined system bus voltage at which the batteries are considered to be at the end of their reserve capability for manual battery testing (End of Discharge). This end-of-discharge voltage is used for automatic and opportunistic reserve time calculations. Battery Temp Management* Range: -36.00V to -48.00V Factory default of -44.44V for 48V

End of Dchrg

This section includes all the parameters required for thermal management of the batteries. Parameters include the ability to enable/disable thermal compensation for high and low temperatures and set the slope decrease and increase rates, respectively. There is also a High Temperature alarm threshold feature. Factory default Enabled

Batt Test*

This section includes all the parameters required for battery testing through manual or automatic means. Configuration for manual test duration and the system test end-voltage for manual battery test are here along with the interval, start date, start time, time from last battery on discharge BD, and enable/disable for periodic battery test. The rectifier voltage during battery discharge testing and system reserve time low alarm threshold are also available. Automatic battery testing is factory disabled.

Recharge Amp Limit

Enable or disable battery recharge limiting and set recharge current limit. When enabled, the controller will regulate the current into the batteries to be below the setting. Recharge current limit is factory Disabled. The current limit range is 5 to 1000A and has a factory default of 50A for Valve-Reg batteries. User defined voltage threshold for a mid-string voltage imbalance alarm. Range 1.4 - 3.0 Volts. The factory default is 1.7V for Valve-Reg batteries. This alarm is only generated after batteries have been sitting on float for a minimum of 12 hours and the total battery current is less than 3A.

Voltage Imbal

*See Appendix C for detailed descriptions of the Thermal Compensation and Battery Test features and parameters.

IPMS Product Manual annexureJune- 2010

Contactors
The ICOMBO controller monitors and controls contactors. Contactor controlled by appropriately configuring a unique board ID and associating it to a specific contactor function at the controller.
ID1-6 Associates the ID numbers set on the controller to one of four independent set of contactor controls. These contactor controls are: LVBD (Low Voltage Battery Disconnect), LVLD1 (Low Voltage Load Disconnect 1), LVLD2 (Low Voltage Load Disconnect 2), and LVLD3 (Low Voltage Load Disconnect 3).

The ICOMBO has assigned each unique board ID number as follows: ID1 to LVBD ID2 to LVLD1 ID3 to LVLD2 ID4 to LVLD3

Disconnects
This section of the configuration menu contains the parameters associated with the individual function assignments made in the previous section. Each LVD type (LVBD and LVLD1-3) can individually be enabled or disabled. Only the LVBD and LVLD1 are enabled from the factory. The LVDs disconnect and reconnect method of operation used by the controller can be configured for each assignment. The method of disconnect or reconnect can be based on the traditional means of reaching a system bus voltage threshold (Voltage) or based on both reaching the system bus voltage threshold and an elapsed time from once the system has been placed on discharge (BD) and at least two or more rectifiers are reporting AC failures (Voltage/Time). The same Voltage and Voltage/Time mode of operation can also be selected for reconnecting LVDs. In this case the elapsed time configured is the time from once the reconnect voltage threshold has been reached. Note: selecting None for a reconnect mode will require manual intervention to shut the contactor. Selecting None for the disconnect mode will not allow a LVD to open. The ICOMBO has factory defaults of the following:
LVBD (Enabled) Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-48.0V); Range:-39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec

IPMS Product Manual annexureJune- 2010

LVLD1 (Enabled)

LVLD2 (Disabled)

LVLD3 (Disabled)

Shutdown Alarm

Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V/+19.5 to +25.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage/Time); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (30 sec); Range: 0-300sec Disconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Disconnect Voltage (-42.0V); Range:-39.0 to -50.0V Time Delay (0 min); Range: 0-300min Reconnect Mode (Voltage); Range: Voltage, Voltage/Time, None Reconnect Voltage (-44.0V); Range: 39.0 to -55.0V Time Delay (0 sec); Range: 0-300sec When enabled, the Imminent Shutdown Alarm is generated prior to opening the LVBD. Once the LVBD threshold has been reached, the alarm is generated. The alarm is issued 15 seconds prior to opening the contactor to provide an indication that system shutdown is imminent due to a system battery disconnect. The alarm is based on the configured LVBD battery disconnect threshold. The factory default for this feature is Disabled. If enabled, the remote Emergency Power Off (EPO) feature allows the controller to detect the occurrence of a contact closure between J3.5 and J.10 and force open all battery contactors in the system. The battery contactor will open five seconds after the contact has been asserted. Once the contact is removed, the battery contactor will be re-asserted to its previous operational state. The factory default for this feature is Enabled.

Remote Emergency Power Off (EPO)

Boost
The Boost function allows battery charging to be expedited by raising the system voltage to boost level for a set time. The following boost mode parameters are set in this area of the menu system:
Set Point Primary DC bus voltage set-point during the Boost mode of operation. Boost (set point) is adjustable from -48.00V to -58.00V in 0.1V increments. Factory default setting is -55.20V. This is an Independent High Voltage Shutdown threshold during the Boost mode of operation that is sent to and stored in the rectifiers that is used by each rectifier for independent high voltage monitoring.

ISHVSD

IPMS Product Manual annexureJune- 2010

Voltage Alarms

Range: -52.00V to -60.00V Factory default: -58.5.00

Has the ability to set similar DC bus level alarms during Boost as found with the Float mode of operation. This includes Very High Major, High Minor, and BD. Very High Major This alarm indicates an abnormally high output voltage on the secondary DC bus during Boost. This is second and critical level of high voltage alarm. The alarm does not attempt to shut the offending unit down. Range: -50.00V to -60.00V Factory default: -57.00 High Minor This alarm indicates an abnormally high output voltage on the secondary DC bus during Boost. This is first level of high voltage alarm. The alarm does not attempt to shut the offending unit down. The threshold can be set from Range: -50.00V to -60.00V Factory default: -56.00

Max Duration

Defines the maximum time duration the system can remain in the Boost mode of operation. Range: 1 to 80 hours. Factory default: 5 hours. Enables or Disables the automatic boost feature. Boost will end once the monitored battery current reaches less than 5A or Max duration is elapsed. Factory default: Enabled

Automatic

ACO
Local buzzer Duration Enables or Disables the Local buzzer. Factory default: Enabled To set the alarm cutoff duration. Range:30-480 min Factory default: 60min

Alarm Test
Relay duration To set the relay test duration. Range:5-300 sec Factory default: 05 sec To set Local buzzer test duration setting

Buzzer Duration

IPMS Product Manual annexureJune- 2010

Range:5-300 sec Factory default: 05 sec

System Settings
Date Time Daylight Savings Display T Units Allows setting system Date. Factory default format: Date - yyyy-mm-dd Allows setting system Time. Factory default format: Time - hh:mm:ss (24HR format). Enable or disable daylight savings. Factory default: Enabled. Allows setting of temperature in C or F. Factory default is C.

Communication Ports
Menus for configuring the following communication parameters:
Port Type Sets the RS232 asynchronous serial communication port for either Local terminal or Modem application. Factory default: Local. Provides the ability to Enable or Disable Write access to the controller, the ability to change system settings through the SNMP management or local port. Write Access, baud rate and flow control parameters for the port is configurable. Factory default: Write Access-Enabled Baud rate-Auto flow control-None

Local Port Settings

Easy View PC User Interface


The ICOMBO can be integrated to communicate to PC through RS232 communication port. It requires for the user to install EASY VIEW software in the system. EASY VIEW 2 is the latest updated version of ICOMBO software that is factory shipped. The pages support the majority of the functionality that is performed through the controller front panel. Following are few sample screens. Note: web pages are continuously updated for functionality and aesthetics. Thus, some of the screens shown may be slightly different than those served up by your ICOMBO.

IPMS Product Manual annexureJune- 2010

Using a standard browser, a login page similar to that depicted below should be served up by the ICOMBO controller. There are three levels of access through the port; Read-Only, Read/Write, and Read/Write with password management privileges. Passwords defaults for the Craft port as well as other remote access means default as follows: Access User (Read-Only) Super-User (Read/Write) Administrator (Read/Write/Password Administration) Default Password lineage super-user administrator

Security Levels/Passwords
The ICOMBO controller supports three levels of access: (User, Super-User, and Administrator). Password defaults can be changed only by a user of administrator privileges. User security level: Can view almost every parameter in the system Can change only a few parameters considered to be of standard maintenance practices Default password: lineage Super-User security level: Can do everything the user can do Can change any configuration parameter in the system (except passwords) Default password: super-user Administrator security level: Can do everything the super-user can do

IPMS Product Manual annexureJune- 2010

Can change passwords Can upgrade controller software Default password: administrator After the controller has granted access, the controller serves up a Home page similar to that shown below. Front panel access and capabilities are a super-set of the functions and features available through the Craft port. Configuration of individual parameters and features can be performed by using the items located in the Settings tab or a general quick configuration of the system can be performed through the Installation tab. The Home Page has tabs that are partitioned as the following:
After login in, main menu screen will show graphic of the power components which are: the number of shelves, rectifiers in place with their appropriate outputs, empty slots, and indicate which rectifiers are in alarm condition. High-level summary for the Batteries, Distribution, Alarms present, and controller summary are also shown. There are also quick link tabs that take you to specific features. These tabs are the Home, Reports, Maintenance, Settings, and Installation.

Home

IPMS Product Manual annexureJune- 2010

The reports tab displays reports or history records of the system that is recorded in the controller. These reports include Inventory, Battery Discharge and Statistics. Individual history groups like Alarm History, Boost History and Trends also available.

Reports

Maintenance

Allows remote access to Control/Operation commands that are available through the front panel. These include restarting rectifiers, starting alarm or battery tests, asserting boost, clearing history and statistics, clearing latched events and missing equipment, placing rectifiers/converters in and out of Standby, cutting of the audible alarm. The T1.317 Terminal button provides a quick link to a Telnet session to the controller that allows the T1.317 command interface to be utilized.

IPMS Product Manual annexureJune- 2010

Note: The Load Defaults button under system loads the factory default settings assigned to a specific battery type as defined in the defaults configuration file. In the Standard controller this function will Standard configuration file. Custom configured controllers will utilize the specific custom configuration file defined for that particular configuration.

Items in this menu are used to configure all the individual system parameters, features, and thresholds. These fields are arranged by System, Reserve, Power, Communication and Programming.

Settings

IPMS Product Manual annexureJune- 2010

This tab provides access to quickly configure the primary items typically needed for a site. These configurations are the minimum for basic system operation. These items include selecting the battery type, date, time, and the site ID mentioned during the front panel configuration start-up section.

Installation

Overview
Broadly, The ICOMBO is capable of the below: GP Bus interface to system controller Control/monitoring of two contactors (latching/non-latching). System configuration can include either all contactors of latching type or all contactors of non-latching type. Hardwired Selectable contactor type (latching/non-latching). If Latching contactors are used, the jumper designated HDR2 should be placed across pins 1&2, else it should be placed across pins 2&3. 1 Bus Voltage Measurement 3 Mid-String Voltage Measurement 4 Load Shunt Currents Measurement 3 Battery charge/discharge shunt Currents Measurement Configurable Shunt Size for each shunt. 3 Battery Reverse Polarity Connection sensing 3 configurable alarm inputs (3 General Binary Inputs) Monitors up to 64 load breakers/fuses Monitors 3 battery fuses Automatic input presence detection Configurable Alarm Input configuration o Polarity o Type 3 Phase AC Parameter Measurement (RMS voltage, RMS current and frequency) (Achieved using a dedicated True RMS AC measurement chip, accuracy < 1%) Configurable CTR (current transformer ratio) for each AC current phase. 1 Tri-Color Status LED

IPMS Product Manual annexureJune- 2010

4. EP2500AC48 Shelf
Overview

A. Standalone Shelf for accommodating six rectifiers


The shelf conforms to 23 standard and accommodates upto 6 rectifiers. The EP48XXX Plant can accommodate upto a maximum of 4 shelves.

Figure 4-1: EP48XXX Plant Shelf & Rectifier Arrangement The AC distribution for the ultimate capacity of 24 Rectifiers installed in the plant is as shown below (viewed from front of the shelf), with background color indicating the respective phase from which the rectifier draws its input power. The EP48XXX plant is internally wired for AC distribution from the MCBs / TB to each of the individual rectifier modules, through backplane interconnects of each shelf. R- Phase: L1 Y- Phase: L2 B- Phase: L3

G41 G31 G21 G11

G42 G32 G22 G12

G43 G33 G23 G13

G44 G34 G24 G14

G45 G35 G25 G15

G46 G36 G26 G16

Figure 4-2: EP48XXX Plant Rectifiers AC Input Wire Mapping

IPMS Product Manual annexureJune- 2010

For Systems with less number of rectifiers, the uninstalled rectifiers shall occupy slots within the rightmost side of the shelf.

Specifications
Parameter
1 2 3 1 2 3 4 Total Output Power Output Voltage: Voltage Isolation Range Input / Chassis Output/Chassis Storage Temperature Operating Storage Operating Input Voltage Full Power Derated Power No damage

Min
176 90 0 -42 343 1500 500 -20 -5 +55 10 5 -

Nom
230 -52 25

Max
290 176 500 15000 -57 75 +55 +70

Unit
V rms V rms V rms Watts Vdc A VAC VAC C C C % % inches inches mm -

Additional Information

Continuous Rated

For 1 minute. For 1 minute. Full Power Rated. Assumes 2.5%/ Deg. C power derating above 55 Deg. C Non condensing - no corrosion. For 96 consecutive hours & no more than 15 days / year. 3U Hieght with Rectifiers inserted inside shelf Depends on whether 19 / 23 Shelf No tool is required to change a rectifer 2 Bit Addressing using piano switches All rectifiers installed have load share hardwired to backplane. Between shelves, two connectors available for cascading load share cables from one to another.

Humidity

95 95 5.25 19/23 400 -

Size

Height Width Depth Ease of Use

Addressing Load Share

Table 4-1: EP2500AC48 Shelf Specifications

IPMS Product Manual annexureJune- 2010

Configuration Requirements

Load Share Conn.

Shelf ID Switch

GP Interface Conn.

Earth Line Neutral

Table 4-2: EP2500AC48 Rear View Components Identification a. b. c. d. Shelf ID switch of bottommost shelf needs to be configured as 00 Shelf ID switch of second shelf (from bottom) needs to be configured as 01 Shelf ID switch of third shelf (from bottom) needs to be configured as 10 Shelf ID switch of fourth shelf (from bottom) needs to be configured as 11

Note:- Configuring the shelf ID switch (piano switch) as 0 means the switch should not be pressed.

IPMS Product Manual annexureJune- 2010

B. Shelf-less Concept for accommodating 2, or 3 rectifiers


The shelf also comes in a variant called shelf-less, a concept introduced to reduce the overall system cost. Such shelves come with combinations of backplane PWBs that accommodate either 2 rectifiers or 3 rectifiers. Below is indicated a backplane PWB that accommodates two rectifiers. Here SW1 is for shelf position identification. SW2 SW1

Below is indicated a backplane PWB that accommodates three rectifiers. SW1 (rightmost) lone switch is for shelf selection, and (SW2, SW3, SW4) left most group of three switches, with SW2 in the leftmost position. SW2 SW3 SW4 SW1

IPMS Product Manual annexureJune- 2010

The combination of the backplane PWBs used is as below:-

Based upon above combinations, where the three rectifiers Backplane PCB is used, below are the switch settings to identify the rectifier position.
Close means pressed 2nd Sw3_1 Sw3_2 Slot # Close Close 2 Close Open 2 Open Close 4 Open Open 5 3rd Slot # 3 invalid 5 6

Sw2_1 Close Open Close Open

Sw2_2 Close Close Close Open

1st Slot # 1 1 3 4

Sw4_1 Close Close Open Open

Sw4_2 Close Open Close Open

Based upon above combinations, where the two rectifiers Backplane PCB is used, below are the switch settings to identify the rectifier position. Close means pressed.
Sw2_1 Close Open Sw2_2 Close Open 1st Slot # 1 3 2nd Slot # 2 4

IPMS Product Manual annexureJune- 2010

5. EP2500AC48 Rectifiers
Overview
The EP2500AC48 Rectifiers are rugged and robust rectifiers that have been exclusively designed to take care of wide line fluctuations and extreme climatic conditions prevailing typically in rural/ semi-urban areas (B & C telecom Circles) of India . The Rectifiers are designed to operate as an integral part of the EP48XXX Plant, with or without battery back-up. These Rectifiers are compatible with the Galaxy family of controllers available from Lineage Power. These Rectifiers are compatible for installation into the EP48XXX shelf.

Figure 5-1: EP2500AC48 Rectifiers

IPMS Product Manual annexureJune- 2010

Salient Features
176Vac to 290Vac input operation at Full Power. 90Vac to 176Vac de-rated linearly from below 176Vac. The linear de-ration of output power ensures optimum power performance at sites with poor grid voltage 2500W power from 44 to 56Vdc (56.8A@ 44V, 52A @ 48V, 44.6A@ 56V) Operating temp. range: -5 to +70C Full power range: -5 to +55 C De-rated power range : +55 C to +70C (de-rated power @ 2.5% per C ) Efficiency >92% for input voltages>230Vac and load between 50% to 100% No Damage Input voltage range: 0 to 500Vac (Line to Neutral) for battery floated application This ensures adequate protection even against Line to Line voltages appearing across the rectifiers in case of Neutral disconnect or Neutral shift conditions which are not uncommon in rural/ semi-urban areas) Can withstand 96 hrs of salt spray test (as per ASTM B117), Special protective coating on the PCBs and superior plating on the metal parts. This makes the rectifier suitable for working in coastal areas having salty atmosphere Less than 10% Current THD Typical Power Factor Correction Low electrical output noise Hot Swappable, Hot Pluggable and Parallel operation with load sharing Radiated and Conducted EMI emissions at system level to conform with CISPR-22 Class A ON/Standby control Through Controller only Rectifier control and alarms operational during input ac failure. Auto recoverable from over temperature shutdown. Latched and auto-restart shutdowns with software restart or AC input recycling. Front LED indicators and Controller signaling are powered via the DC output (back biased) Fuse fail detection of Input Fuse

IPMS Product Manual annexureJune- 2010

Input Behavior
Linear de-ration of power for poor grid voltage Input operating voltage range (90 to 290Vac) Full power range (2500W) -176 to 290Vac De-rated power range - 90 to 175Vac (Linearly de-rated power @0.6% / Vac, 1200W at 90Vac) The linear de-ration of output power ensures optimum power performance at sites with poor grid voltage

Output Power Characteristics w.r.t input


3000
2500W,175Vac 2500W, 290Vac

2500 Power (W) 2000 1500 1000 500 0


1200W, 90Vac

70

90

110 130 150 170 190 210 230 250 270 290 310
Input Voltage (Vac)

Figure 5-2: EP2500AC48 Rectifiers Input Behavior

IPMS Product Manual annexureJune- 2010

Output Behavior
Constant Power rectifier 2500W power from 44 to 56Vdc (56.8A@ 44V, 52A @ 48V, 44.6A@ 56V) Constant Power range down to 44V ensures that rectifier delivers full power when needed most i.e. charging a fully discharged battery

VI Characteristics
75

Constant Voltage DC Output V oltage (V ) 56 50 48 44 Constant Power (2500W)

Constant Current 25 57.5

0 0 30 44.6 DC Output current (A) 52 56.8 60

Figure 5-3: EP2500AC48 Rectifiers Output Behavior

IPMS Product Manual annexureJune- 2010

User Interface (LED Indications)


Front Panel Layout of the Rectifier is as shown below.

Figure 5-4: EP2500AC48 Rectifiers Front View with LEDs The LEDs are ACF (yellow), NORM (green), FAIL (red) from left to right. A Logical Summary of LED Indications on Panel is as given below:AC Fail (Amber) 2 Status ON - AC input out of range (i.e. <90Vac or >290Vac) OFF - AC is normal Normal (Green) 4 Status ON - DC Output OK OFF- DC Output Not OK Blink (0.5 Sec ON and 0.5 Sec OFF) - Rectifier in Current limit Wink (0.5 Sec ON and 2 Sec OFF) - Rectifier in Standby/ Sleep mode Fault (Red) 3 status ON - Rectifier Internal fault OFF - No faults Blink (0.5 Sec ON and 0.5 Sec OFF) - Communication fail

IPMS Product Manual annexureJune- 2010

Detailed summary of LED indications against specific events are given in the table below :-

S. System State No 1 2 3 4 5 6 7 8 9 10 11 12 13 Rectifier delivers power in a normal mode & Communication is OK Rectifier can deliver power in a normal mode & Communication has Failed. AC Input out of range (irrespective of whether Rectifier is in standby or not) Output Current Limit OR Rectifier Walk-in OR Hiccup due to deep overload` Output voltage <38Vdc and not current limit Output short shutdown (latch) Fan fail Over temperature protection Output over voltage Present not OK, Rectifier is not plugged OK Controller keeps Rectifier in standby. No AC, have DC power for rectifier control circuit No AC, No DC

ACF AMB 0 0 1 0 0 0 0 0 0 0 0 1 0

NORM GRN 1 1 0 Blink 0 0 0 0 0 Blink Blink 0 0

FLT RED 0 Blink 0 0 1 1 1 1 1 1 0 0 0

Table 5-1: EP2500AC48 Rectifiers Table of LED Indications

IPMS Product Manual annexureJune- 2010

6. EP3000AC48 Rectifiers
Overview
The EP3000AC48 Rectifiers are rugged and robust rectifiers that have been exclusively designed to take care of wide line fluctuations and extreme climatic conditions prevailing typically in rural/ semi-urban areas (B & C telecom Circles) of India . The Rectifiers are designed to operate as an integral part of the EP48XXX Plant, with or without battery back-up. These Rectifiers are compatible with the Galaxy family of controllers available from Lineage Power. These Rectifiers are compatible for installation into the EP48XXX shelf.

Figure 6-1: EP3000AC48 Rectifiers

IPMS Product Manual annexureJune- 2010

Salient Features
Backward compatible with EP2500AC48. 176Vac to 290Vac input operation at Full Power. 90Vac to 176Vac de-rated linearly below 176Vac @ 0.65% per volt, leading to 1323W at 90VAC Output power of 3000W from -48V to -58V Operating temp. range: -10 to +75C Full power range: -10 to +50 C De-rated power range : +50 C to +75C (de-rated power @ 2.4% per C ) Efficiency >92% for input voltages>230Vac, Output = 54VDC & load between >= 40% , at an ambient temperature of 25 Deg. C. No Damage Input voltage range: 0 to 500Vac (Line to Neutral) for battery floated application This ensures adequate protection even against Line to Line voltages appearing across the rectifiers in case of Neutral disconnect conditions which are not uncommon in rural/ semiurban areas) Can withstand 96 hrs of salt spray test (as per ASTM B117), Special protective coating on the PCBs and superior plating on the metal parts. This makes the rectifier suitable for working in coastal areas having salty atmosphere Less than 10% Current THD Typical Power Factor Correction Low electrical output noise Hot Swappable, Hot Pluggable and Parallel operation with load sharing Radiated and Conducted EMI emissions at system level to conform with CISPR-22 Class A ON/Standby control Through Controller only Rectifier control and alarms operational during input ac failure. Auto recoverable from over temperature shutdown. Latched and auto-restart shutdowns with software restart or AC input recycling. Front LED indicators and Controller signaling are powered via the DC output (back biased) Fuse fail detection of Input Fuse

IPMS Product Manual annexureJune- 2010

Input Behavior
Linear de-ration of power for poor grid voltage Input operating voltage range (90 to 290Vac) Full power range (3000W) -176 to 290Vac 90Vac to 176Vac de-rated linearly below 176Vac @ 0.65% per volt, leading to 1323W at 90VAC Power De-rating with input voltage

Output Power Characteristics w.r.t input


3500
3000W,176Vac 3000W, 290Vac

3000

Power (W)

2500 2000 1500


1320W, 90Vac

1000 500 0 70 90 110 130 150 170 190 210 230 250 270 290 310

Input Voltage (Vac)


Figure 6-2: EP3000AC48 Rectifiers Input Behavior

IPMS Product Manual annexureJune- 2010

Output Behavior
3000W power capability, with a constant power range of 48 to 58Vdc Capability of delivering upto 62.5Amps @ 48Vdc & 58Amp@52VDC.

VI Characteristics
75

DC Output Voltage (V) 58

Constant Voltage Constant Power (3000W)

48

Constant Current 25

0 0 30 51.7 DC Output current (A) 62.5

Figure 6-3: EP3000AC48 Rectifiers Output Behavior

IPMS Product Manual annexureJune- 2010

User Interface (LED Indications)


Front Panel Layout of the Rectifier is as shown below.

Figure 6-4: EP3000AC48 Rectifiers Front View with LEDs The LEDs are ACF (yellow), NORM (green), FAIL (red) from left to right. A Logical Summary of LED Indications on Panel is as given below:AC Fail (Amber) 2 status ON - AC input out of range (i.e. <90Vac or >290Vac) OFF - AC is normal Normal (Green) 4 status ON - DC Output OK OFF- DC Output Not OK Blink (0.5 Sec ON and 0.5 Sec OFF) - Rectifier in Current limit Wink (0.5 Sec ON and 2 Sec OFF) - Rectifier in Standby/ Sleep mode Fault (Red) 3 status ON - Rectifier Internal fault OFF - No faults Blink (0.5 Sec ON and 0.5 Sec OFF) - Communication fail

IPMS Product Manual annexureJune- 2010

Detailed summary of LED indications against specific events are given in the table below :-

S. System State No 1 2 3 4 5 6 7 8 9 10 11 12 13 Rectifier delivers power in a normal mode & Communication is OK Rectifier can deliver power in a normal mode & Communication has Failed. AC Input out of range (irrespective of whether Rectifier is in standby or not) Output Current Limit OR Rectifier Walk-in OR Hiccup due to deep overload` Output voltage <38Vdc and not current limit Output short shutdown (latch) Fan fail Over temperature protection Output over voltage Present not OK, Rectifier is not plugged OK Controller keeps Rectifier in standby. No AC, have DC power for rectifier control circuit No AC, No DC

ACF AMB 0 0 1 0 0 0 0 0 0 0 0 1 0

NORM GRN 1 1 0 Blink 0 0 0 0 0 Blink Blink 0 0

FLT RED 0 Blink 0 0 1 1 1 1 1 1 0 0 0

Table 6-1: EP3000AC48 Rectifiers Table of LED Indications

IPMS Product Manual annexureJune- 2010

Appendix B The T1.317 Command Language


Initializing the IC091_Icombo Controller
This section outlines programming the controller using the Hyper Terminal program that is shipped with most IBM compatible PC's. Connect the cable between the computer RS-232 port, and the ICOMBO Controller. After Hyper Terminal has started and the programming cable is connected to the controller and the PC, you should see the login screen that allows access to the controller programming features. RS-232 Terminal This interface provides a T1.317 interface for local access. This interface provides access to all status, configuration, and operations. It also provides call-out on alarm capability. The controller communicates to local port using the following settings: Write Access ( ENA) Baud rate ( Auto) Flow control (None)

Three levels of security protect incoming access: user, super-user, and administrator. A user has read ability and can only get status information from the controller. A super-user can change configurations and perform control operations. An administrator has all the abilities of a super-user but can also change passwords. All access to ICOMBO is via the T1.317 command set, to be discussed later. This section describes how to log into the system via an RS-232 local port. The first step to logging in is to get to an ENTER PASSWORD: prompt. From a terminal connected to the RS-232 port, simply press ENTER until you see the log-in prompt. The number of ENTER keys required will depend on the baud rate you are trying to connect at. The controller will adjust its baud rate automatically until it recognizes the carriage return character (ASCII 13) sent by pressing ENTER. At the ENTER PASSWORD: prompt, type the user or super-user password. The default password for each level of security is listed below. Default User password Default Super-user password Default Administrator password lineage super-user administrator

IPMS Product Manual annexureJune- 2010

After receiving the correct password, the controller will respond with one of the following command line prompts: User command-line prompt: *

Super-user command-line prompt: ** When these prompts appear the controller is ready to accept commands. Note that the session will be terminated if the port is idle for 15 minutes.

T1.317 Command Language


The ICOMBO controller command language is based on the T1.317 standard. This section describes the commands, objects and attributes used to access measurements, configuration, and control parameters in the ICOMBO controller. Objects and Attributes The T1.317 standard organizes system parameters called attributes into groups called objects. All commands, objects, attributes and ranges for their respective parameters for the ICOMBO controller are given in the following tables. An object-attribute pair uniquely identifies a measurement, configuration, or control parameter. For example, the object-attribute pair dc1,vdc identifies the plant voltage while the object-attribute pair dc1,adc identifies the plant load current. In each of these examples dc1 identifies the plant object and vdc and adc identify DC voltage and DC current, respectively. There are three main commands involved with plant operations in the system controller command set. The command sta is used to get the status of the plant, the command cha is used to change a plant parameter, and the command ope is used to initiate a plant function. A person at the user level can only perform the sta operations. A person at the super-user and administrator level can also perform the "cha" and "ope" operations. Instructions in the T1.317 command set take the following form: command object,attribute[=parameter]. Certain commands do not require a value for parameter, while others do. Note that text parameters are to be enclosed in quotation marks while numeric parameters are not to be enclosed in quotation marks. For example, to obtain the plant voltage, type in the following command: sta dc1,vdc

IPMS Product Manual annexureJune- 2010

To enable low-temperature slope thermal compensation, type in the following command: cha sc1,rve=1 To change the voltage at which the LVD contactor disconnects the batteries from the load to 40V, type the following: cha cn1,dth=40 To initiate a manual boost charging, i.e., place the plant into boost charging mode, type in the following command: ope dc1,stt=boost The tables below summarize the object-attribute pairs in the system along with the commands that can be used with the pair and the valid range that the attribute may have. The values in bold text are the default settings for the attributes.

Power System obj,attr description ps1,des Power system description ps1,sid Site ID ps1,swv Software version ps1,verb Boot Version ps1,dflt Defaults file version ps1,usl Uninstall missing equipment ps1,ltt Lamp test ps1,dat Date ps1,tim Time ps1,dls Daylight savings enable ps1,ptt Communication port type ps1,dss Daylight saving start ps1,dse ps1,amt ps1,cst ps1,fst ps1,fstl ps1,rss ps1,uet ps1,fpp ps1,slv Daylight saving end System ambient temperature Display contrast Load factory default Load factory defaults list Restart all devices in system Uninstall popup timeout Front Panel Pin Port security level

related commands sta cha ope

type text text text text text number number date time number text d:d:d:d d:d:d:d number number text text number number Number text

range:default IC091 Up to 15 characters: mm.nn mm.nn desc-mm.nn 1 1:do it yyyy-mm-dd Hh:mm:ss (24 hour format) 0:disabled 1:enabled:0 LOCAL,MODEM:LOCAL mon:wk:dow:min mon:-1:dom:min mon:wk:dow:min mon:-1:dom:min dd C 0 to 100%:50 Up to 15 characters comma delimitated list 1:do it 0 to 60: 15 4 digit Pin (only viewable as admin)

IPMS Product Manual annexureJune- 2010

AC Distribution obj,attr description Acd1,prv Phase R voltage Acd1,psv Phase S voltage Acd1,ptv Phase T voltage Acd1,pra Phase R current Acd1,psa Phase S current Acd1,pta Phase T current

related commands sta cha ope

type number number number number number number

range ddd V ddd V ddd V dd.d A dd.d A dd.d A

DC Plant obj,attr dc1,stt dc1,vdc dc1,adc dc1,sha1 dc1,trd dc1,cap dc1,olcap dc1,scap dc1,isd dc1,rss dc1,bod dc1,nst dc1,rtm

description Plant state Plant voltage Plant load current External shunt size Plant total rectifier drain Total installed rectifier capacity Total on-line rectifier capacity Battery String capacity Imminent shutdown enable Rectifier restart Battery on discharge Number of battery strings Actual reserve time

related commands sta cha ope

type text number number number number number number number number number number number text

dc1,eme dc1,emt dc1,emo dc1,emi dc1,emw

Efficiency management enable Efficiency target Efficiency turn on rectifier threshold Efficiency initial delay Efficiency delay related command sta cha ope

Number Number Number Number Number

range:default FLOAT, BOOST dd.dd V ddd.d A synonym for dcm01,sha ddd.d A ddd.d A ddd.d A dddd A 0:disable 1:enable:0 0:no action 1:restart 0:on discharge 1:not on discharge 0-16:0 Low Current-Batt current too low High Current-Batt current too high dd.d (in hours) 0=disable, 1=enable 20 to 95 % 25 to 100 % 1 to 30 minutes 1 to 30 minutes

Alarms With Two Thresholds obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,led LED objid,fth Alarm boost threshold objid,bth Alarm float threshold objid,sev Alarm severity

type text number text number number text

range R1- R7, or 0:not active 1:active BD,AC,DC, see below see below CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted

IPMS Product Manual annexureJune- 2010

Object Ids obj hfv1 hva1

description High voltage Very high voltage

acc

default attribute values (range:default) sev fth bth MIN 50-60V:56 50-60V:56 MAJ 50-60V:57 50-60V:57

Alarms With One Threshold obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,led LED objid,thr Alarm threshold objid,sev Alarm severity

related command sta cha ope

type text number text number text

range R1- R7, or 0:not active 1:active BD,AC,DC, see below CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted

Object IDs obj amth1 amtl1 bda1 bta1 rrtl1 rtl1 vla1 description High ambient temp Low ambient temp Battery on discharge High battery temperature Real-time reserve low Reserve time low Very low voltage

default attribute values (range:default) acc sev thr MIN 35-75C:75 MIN -40-10C:-40 R1 MAJ 46-55V:51 MIN 30-85C:55 MAJ 0-99.9hrs:0 MIN 0-99.9hrs:0 R1 MAJ 40-51V:46

Alarms With No Threshold obj,attr description objid,acc Alarm relay objid,ast Alarm state objid,sev Alarm severity

related command sta cha ope

type text number text

objid,led

LED

text

range R1- R7, or 0:not active 1:active CRIT -PCR asserted MAJ -PMJ asserted MIN -PMN asserted RO -PCR, PMJ, PMN not asserted BD,AC,DC,

Object IDs obj acf1 amj1 bbl1 bfa1 description AC fail Major auxiliary alarm Clock battery low Check battery alarm

default attribute values acc sev R2 MIN MAJ RO MIN

IPMS Product Manual annexureJune- 2010

btf1 btj1 btn1 bts1 cnf1 cnf2 cnf3 cnf4 cma1 cno1 cno2 cno3 cno4 cpa1 epo1 faj1 fan1 isd1 macf1 mcm1 mrfa1 osa1 rf1 rfa1 rfn1 rls1 rpff1 rprl1 rpfj1 rpxj1 rpxn1 scd1 tpa1 vmf1 vsf1

(lithium) Battery fuse Multiple (lithium) battery fail (lithium) Battery fail Battery test active Battery contactor fail Load 1 contactor fail Load 2 contactor fail Load 3 contactor fail Minor communication Battery contactor open Load 1 contactor open Load 2 contactor open Load 3 contactor open Modem failure Emergency power (battery) off Major fuse alarm Minor fuse alarm Imminent shutdown Multiple AC fail Major communication Multiple rectifier fail Open string alarm Ringer 1 fail Rectifier fail Rectifier fan fail Rectifier redundancy loss Ringer 1 fan fail Ringer 1 redundancy loss Ringer 1 fail major Ringer 1 major external fault Ringer 1 minor external fault Battery voltage imbalance Thermal probe fail Voltage module fail Sense voltage fail

R4

R2 R3

R3

MAJ MAJ MIN RO MAJ MAJ MAJ MAJ MIN MAJ MAJ MAJ MAJ MIN MAJ MAJ MIN MAJ MAJ MAJ MAJ MAJ MIN MIN MIN MIN MIN MIN MAJ MAJ MIN MAJ MIN MIN MAJ

Alarm Test obj,attr description at1,stt Auxiliary event 1-6 description at1,stg Auxiliary event 1-6 alarm state at1,dur Auxiliary event 1-6 severity at1,pcrj Include PCR relay in test at1,pmj Include PMJ relay in test at1,pmn Include PMN relay in test at1,r1 Include R1 relay in test at1,r2 Include R2 relay in test at1,r3 Include R3 relay in test

related command sta cha ope

type text text text number number number number number number

Range:default 0=not in progress 1=in progress 5 to 300:60 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable

IPMS Product Manual annexureJune- 2010

at1,r4 at1,r5 at1,r6 at1,r7 at1,bzt at1,bzi

Include R4 relay in test Include R5 relay in test Include R6 relay in test Include R7 relay in test Audio Test State Audio Test Duration

number number number number Number Number

0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 0=disable 1=enable 1=start test 5-300 seconds

Configurable Auxiliary Input Alarms


Configurable Auxiliary Input Alarms obj,attr description aux1Auxiliary event 1-6 description 6,des aux1-6,ast Auxiliary event 1-6 alarm state aux1Auxiliary event 1-6 severity 6,sev aux1Auxiliary event 1-6 relay 6,acc Rectifier Management obj,attr description gm1,fsd Float High Voltage Shutdown gm1,bsd Boost High Voltage Shutdown gm1,fsp Rectifier float set-point gm1,bsp Rectifier boost set-point gm1,rme Redundancy monitor enable Rectifiers obj,attr gsr,stt related command sta cha ope type text text text text Range:default up to 32 characters 0:not active 1:active CRIT, MAJ, MIN , or RO:MAJ R1-R7, or :

related commands sta cha ope

type number number number number number

range:default 50-60 V : 56.5V 52-60 V : 58.5V 42-56.5V:54.5 48-60 V:55.2 0=disable,1=enable:0

description Individual rectifier state

related commands sta cha ope

type text

gsr,adc gsr,cap gsr,vac gsr,aac

Individual rectifier current Capacity AC Voltage AC Current

number number number number

range:default ON,OFF,STANDBY,MISSIN G,VACANT Only ON and STANDBY maybe used with the OPE command. ddd number number number

s stands for shelf number (1, 2, or 3)


r stands for rectifier number (1 to 5) Battery Reserve Management obj,attr description br1,hbt Highest battery temperature br1,adc Total battery current br1,cap Installed battery capacity br1,olcap On-line battery capacity br1,bts Plant battery test (lower rect V) br1,scd Battery voltage imbalance related commands sta cha ope

type number number number number number number

range:default dd C d A (+ for discharge, - for charge) ddddd AH ddddd AH 0:stop 1:start 0=disable,1=enable

IPMS Product Manual annexureJune- 2010

detection enable br1,scv br1,ntm br1,nvm br1,cle br1,clt Battery imbalance threshold Number of temperatures present Number of mid-cell V present Recharge current limit enable Recharge current limit threshold Discharge test results number

number number

(Automatically enabled when mid cell V monitor present) 1.5-3.0V:1.7 d d 0=disable,1=enable:0 5-1000A/string:10

br1,btr

text

br1,btc

Battery type

text

br1,btl br1,bty br1,sev br1,bte br1,atd br1,ath br1,atw br1,tin br1,tmd br1,tev br1,btv

Battery type list Battery model String end of discharge voltage Auto test enable Auto test date Auto test start hour Auto test min hours after BD Auto test interval Manual test duration Manual test alarm voltage Battery test rectifier voltage

Text number number date number number number number number number

result, reserve, load result is one of the following: COMPLETED CHECK BATTERY INTERRUPTED ACTIVE NOT RUN reserve is hours calculate by last complete test load is load at beginning of test "VALVE-REG","FLOODED", "LIRK", "NICD", "LI-LMP":"VALVEREG" Comma delimited list Up to 14 chars 36-48 V:44.4 0=disable,1=enable:0 dd-mmm-yy 0-23:0 0-240 hours:0 1-18 months:12 0.1-99.9 hours: 4 36-48 V:44.4 42-52 V:44

Ringer Plant obj,attr description RP1,frq Ringer output frequency RP1,vsp Ringer voltage set-point RP1,ofe Ringer offset enable RP1,rme Redundancy monitor enable RP1,rss Ringer restart

related commands sta cha ope

type number number number number number

range:default 15-50Hz:20 65-100V:100 0=disable,1=enable:1 0=disable,1=enable:1 1=restart

IPMS Product Manual annexureJune- 2010

Ringer Chassis obj,attr description RC1-2,stt Ringer group state

related commands sta cha ope

type number

RC1-2,va RC1-2,pri

Ringer output va Primary ringer

number text

RC1-2,sec

Secondary ringer

text

RC1-2,rf RC1-2,rpff RC1-2,rpfj RC1-2,rprl RC1-2,rpxj RC12,rpxn

Minor ringer failed Fan in chassis failed Major ringer failed Redundancy lost in chassis Major external fault Minor external fault

Number Number Number Number Number Number

range:default ON FAN, -REDUN OFF FAIL, -EXT, -TA, -RET, FAN STANDBY MISSING The ope command supports the ON and STANDBY states dd.d VA sr where s is the shelf number r is the ringer position 1=first primary ringer 3=second primary ringer First ringers are in the odd shelf slot. Second ringers are in the even shelf slot sr where s is the shelf number r is the ringer position 2=first secondary ringer 4=second secondary ringer First ringers are in the odd shelf slot. Second ringers are in the even shelf slot 1=failed 1=failed 1=failed 1=failed 1=failed 1=failed

Boost Management obj,attr description bs1,abe Auto boost enable bs1,tmd Maximum boost duration in hrs

related commands sta cha ope

type number Number

range:default 0=disable,1=enable:0 1-80:5

IPMS Product Manual annexureJune- 2010

Disconnect Disconnect Contactor Control obj,attr description cn1-4,stt Disconnect state

related commands sta cha ope

type text

cn1-4,ena cn1-4,dth cn1-4,ddy cn1-4,dam

Control enable Disconnect threshold Disconnect delay Disconnect automode

number number text

cn1-4,dtm cn1-4,rth cn1-4,rdy cn1-4,ram

Disconnect remaining time Reconnect threshold Reconnect delay Reconnect auto mode

number number number text

cn1-4,rtm

Reconnect remaining time

number

range:default NONE MISSING CLOSED OPEN -MAN, - REM, -EPO, -V, TIME, -FAIL 0=disable,1=enable:1 39-50V:42 0-300 minutes:0 0=NONE 1=VOLTAGE 2= VOLTAGE+TIME :1 >0 means going to disconnect 39-55:44V 0-300 seconds:0 0=NONE 1=VOLTAGE 2=VOLTAGE+TIME :1 >0 means going to reconnect

The contactors are identified as follows: CN1 = Battery Disconnect (LVBD1) CN2 = Load 1 Disconnect (LVLD1) CN3 = Load 2 Disconnect (LVLD2) CN4 = Load 3 Disconnect (LVLD3)
Distribution Current Monitor obj,attr description dcm01-07,stt State related commands sta cha ope type text range:default NONE MISSING PRESENT NONE LOAD BATTERY ddd.d Amps 0-9999 Amps

dcm0107,typ dcm01-07,val dcm0107,sha

Shunt Type

text

Reading Shunt amp rating

number number

The shunt type defaults are as follows: DCM01 = Battery DCM02 = Battery DCM03 = Battery DCM04 = Load

IPMS Product Manual annexureJune- 2010

DCM05 = Load DCM06 = Load DCM07 = Load


Distribution Contactor Interface obj,attr description dcn01-04,stt State related commands sta cha ope

type text

dcn01-04,typ

Contactor interface type

text

range:default NONE MISSING PRESENT NONE LVBD1 LVLD1 LVLD2 LVLD3

The contactor interface type defaults are as follows: DCN01 = LVBD1 DCN02 = NONE DCN03 = NONE DCN04 = LVLD1
Slope Thermal Compensation obj,attr Description sc1,stt Slope compensation enable sc1,rve Raise voltage enable sc1,ltt Low temperature limit sc1,ntt Nominal temperature sc1,utt Upper temperature limit sc1,spt Step temperature sc1,lsp Low temperature slope sc1,usp Upper temperature slope related commands sta cha ope type number number number number number number number number range:default 0=disable 1=enable:1 0=disable 1=enable:0 -5-20:0C 15-30:25C 30-55:45C 45-85:75C 1-5:3mV/C per cell 1-5:3mV/C per cell

Input Management obj,attr description inmn,stt Input state inmn,typ Input alarm type

related commands sta cha ope

type text text

inmn,pol Input alarming polarity text where: m is the distribution interface module ID from 1 to 4 n is the input number from 01 to the number of inputs supported by the distribution interface module

range:default 0:not alarming 1:alarming alarm object ID (i.e. faj1,fan1,aux1 to aux6, and remlvd) remlvd identifies the remote disconnect function; the contactor will open when input is in the alarming state. CLOSED, OPEN

IPMS Product Manual annexureJune- 2010

CallCall-Out obj,attr p1,phn a1,phn

Description Primary phone number Alternate phone number

related commands sta cha ope

type text text

range:default Up to 20 characters: Up to 20 characters:

Serial Ports obj,attr Description mp1,bdr Modem baud rate mp1,ins Modem initialization string mp1,nrg mp1,hsh mp1,wre lp1,bdr lp1,hsh Modem number of rings before answering Modem handshaking Write Enable Local RS-232 baud rate Local RS-232 handshaking

related commands sta cha ope

type text text number text Number text text

range:default 2400,4800,9600:2400 Up to 20 characters: AT&FEV&C1S0=0H 1-9:1 rings NO: none SW: xon and xoff 0=disable 1=enable AUTO,2400,4800,9600:AUTO NO: none SW: xon and xoff HW: cts and rts 0=disable 1=enable

lp1,wre

Write Enable

Number

Generator obj,attr gn1,clt

description On-Generator Battery Recharge Current Limit Threshold

related commands sta cha ope

type number

Range 5-1000A

CutAlarm Cut-off obj,attr Description aco1,dur Cut-off duration aco1,stt Alarm Cut-off State aco1,lbe Local Buzzer Enable

related commands sta cha ope

type Text Number Number

range 30 480 mins (8 hours) 0=deactive 1=activate 0=Disable 1=Enable

IPMS Product Manual annexureJune- 2010

Appendix C Explanation of Battery Management Functions


Float Mode
Float mode is the default operation mode of the power system. The system voltage, while in float mode, is determined by the configuration parameter Rectifier Float Set point (fsp) and may be adjusted by the Battery Thermal Compensation circuit, if active. No individual adjustment of plant rectifiers is necessary and load sharing among plant rectifiers is automatic in all plant modes and will take effect within several seconds of a new rectifier being added to the system. The Rectifier Float Set point should be set per the battery manufacturer's recommendations. Note that the actual Rectifier Float Set point measured on the plant may differ from the value set by the user if battery thermal compensation (STC) is enabled.

Slope Thermal Compensation


The following is a list of slope thermal compensation parameters that can be configured in the controller.

High Temperature Alarm


Alarm threshold can be set from 30C to 85C. The alarm retires when the temperature drops to 10C below the set threshold. The factory default setting is 55C.

High Temperature Compensation


The system controller automatically enables high temperature compensation if a VT thermal probe is detected. The feature can be disabled by disconnecting all thermal probes and updating the serial links using the Lamp Test function. Settings for this feature are as follows. V Step Down: Battery step temperature can be set from 45C to 85C. The factory default setting is 75C. High Comp Limit: The upper temperature thermal limit can be set from 30C to 55C. The factory default setting is 45C. Decrease: The upper temperature slope setting (rate of decrease) can be set from -1mV to 10mV in -.1mV steps. The factory default is -3mV. Nominal Temperature: Temperature above or below which Slope Thermal Compensation is enabled. The stable range is 15 to 30C. The factory default setting is 25C.

IPMS Product Manual annexureJune- 2010

Low Temperature Compensation


This feature is disabled by default, and can be enabled only if Temperature Slope Thermal Compensation is enabled. The following are the associated parameters. Low Comp Limit: Low temperature thermal compensation can be set from -5C to 20C. The factory default setting is 0C. Increase: The low temperature slope (rate of increase) can be set from 1mV to 10mV in .1mV increments. The factory default setting is 3mV. I-Combo controller has a flexible Thermal Compensation feature which provides voltage compensation from that level established by the Plant Float Set-Point (fsp) or Boost Set-Point (bsp), dependent on the highest temperature monitored by the QS873A VT-Probes attached to the system batteries. Thermal Compensation should be used in a plant containing sealed or valve regulated maintenance free batteries. Note that Thermal Compensation is automatically enabled from the factory when Valve-Regulated Lead Acid batteries are the system battery type. The feature is not automatically enabled upon detection of a VT-Probe. Refer to the Installation Instructions for more details on wiring and configuring this feature. Thermal Compensation lowers plant voltage from the fsp for monitored battery temperatures which are above the ideal temperature established during configuration as the Battery Thermal Slope Nominal Temperature (ntt). (The items in parenthesis are the user configurable points referred to in the graph shown below.) Lowering the plant voltage helps to keep the batteries at their optimum state of charge while protecting them from thermal runaway. Thermal runaway is a complex sealed battery phenomenon where, for one or more of a number of reasons, one or more cells in a string are unable to dissipate the internal heat generated by their charging current and experience an increase in internal temperature. By lowering the float voltage as cell temperature increases, the float current is lowered to a point where this destructive behavior can be avoided. If a cell failure is imminent and the cell temperature continues to rise above the threshold configured for Battery Thermal Step Temperature (stp), plant voltage drops in a single step to a level which keeps the remaining cells in the string from overcharging and being damaged. Refer to Figure C-1 for a graphical view of Battery Thermal Compensation and the relationship of its various set points. I-combo controller can also increase plant voltage above that set by the fsp or bsp for colder environments, again seeking to keep batteries at their optimum charge state. Batteries will lose capacity as the battery temperature drops below their optimal operating temperature. Increasing the plant voltage with decreases in battery temperature will cause more current to flow into the batteries. This results in electrolysis of the water in the batteries. Since this reaction is exothermic, it also serves to keep batteries warm. This feature results in an increase in plant voltage, and is required to be enabled during controller configuration.

IPMS Product Manual annexureJune- 2010

Figure C-1: Slope Thermal Compensation The following describes the configuration parameters which may be activated or altered by the user. Refer to Appendix D for the ranges of values the parameters may take and their factory default settings. Lower Thermal Limit (ltt): The lower temperature where, if Low Temperature Compensation is enabled, the controller will increase plant voltage to a level corresponding to (lsp * (ntt - ltt)* 24)V above the fsp. Plant voltage will be increased proportionally at any temperature between this point and the Battery Thermal Slope Nominal Temperature (ntt). Low Temperature Compensation Enable (rve): A 0 disables and 1 enables the Low Temperature Thermal Compensation feature. Since rve increases plant voltage rather than decreasing it based on temperature, the option is provided to disable it separately from the entire feature so that equipment loads sensitive to high voltages can be protected.

IPMS Product Manual annexureJune- 2010

Lower Temperature Slope (lsp): The slope rate for the voltage increase per cell when
the battery temperature is below the ntt (Battery Thermal Slope Nominal Temperature). Battery Thermal Slope Nominal Temperature (ntt): The zero compensation temperature point. Temperatures monitored between this point and the Upper Temperature Limit (utt) will result in a proportional decrease of plant voltage to a level corresponding to (usp*(uttntt)*24)V below the fsp at the utt. If Low Temperature Compensation is enabled, temperatures monitored between this point and the Lower Thermal Limit (ltt) will result in a proportional increase of plant voltage to a level corresponding to (lsp*(ntt-ltt)*24)V above the fsp at the ltt. Upper Temperature Slope (usp): The slope rate for the voltage decrease per cell when the battery temperature is above the ntt (Battery Thermal Slope Nominal Temperature). Upper Temperature Limit (utt): The upper temperature where Battery Thermal Compensation will have reduced plant voltage to a level corresponding to (usp*(utt-ntt)*24)V below the fsp. Plant voltage will be reduced proportionally at any temperature between this point and the Battery Thermal Slope Nominal Temperature (ntt). Battery Thermal Alarm Threshold (thr): A monitored battery temperature above this threshold results in a Battery Thermal alarm with a PMN severity. Battery Thermal Step Temperature (spt): A monitored battery temperature above this threshold results in an additional 4.08V step decrease in plant voltage.

Plant Battery Test


The following is a list of plant battery test parameters that can be configured in the controller. The result of the Plant Battery Test is available in the Batteries sub-menu of the Status menu. Manual Test: Permits manually starting a battery discharge test. The test can be set to end on either of the following two parameters. Duration: The duration of the test can be set from 0.1 hours to 99.9 hours. Cutoff Cell V: The test can be set to end when battery cell voltage reaches this cutoff voltage. Cutoff voltage can be set from 1.5V to 2.0V. Automatic Test: This utility offers the flexibility of running pre-programmed battery tests at specific times and days, and for specific durations.

IPMS Product Manual annexureJune- 2010

Automatic Test: Enable or disable automatic periodic running of the battery test. The factory default setting is disabled. Interval: The test interval (time between tests) can be set from 1 to 18 months in 1 month increments. The factory default setting is 12 months. Next Test: Enter a particular day in dd-mm-yy format to automatically run the battery test on that day. Start Time: Enter a particular time in hh-mm format to automatically run the battery test at that time. The setting can be configured from 0 to 23 hours. 00:00 is midnight. Hours from BD: Time interval needed to elapse since the last Battery on Discharge alarm before a battery test can be performed. This can be set from 0 to 240 hours in 1 hour increments. The factory default setting is 72 hours. Recharge Amp Limit: This section contains the settings for battery recharge current limit. Limit: Enable or disable battery discharge current limiting. Limit To: Current limit setting, from 5A to 1000A. The factory default setting is 50A. During this test, the controller lowers the rectifier voltage to 44V. (This value was chosen to be higher than 1.2V plus the highest possible LVD contactor disconnect threshold so as not to accidentally open the LVD contactor.) Lowering the rectifier output voltage to 44V creates a battery on discharge condition. If the batteries are present and healthy, the plant voltage will remain above 48V and the batteries will support the load. If the batteries are not present or are not able to support the load, the plant voltage will immediately drop to approximately 44V without any consequence to the load. The Battery on Discharge alarm is masked during this test. The test is terminated by the occurrence of any of the following conditions:

Initiating another Plant Battery Test. That is, once the test has been initiated, the test may be stopped by initiating another test either through the controller or by shorting pins 19 and 20 of the host interface connector. An alarm condition occurring. Any alarm condition that occurs during this test will result in the test being aborted regardless of whether the contact-closure exists between pins 19 and 20 of the host interface connector. The test has continued for over 100 minutes.

IPMS Product Manual annexureJune- 2010

The plant voltage has dropped below 44V. In this case, the system will abort the test and resume rectifier operation.

After the test has stopped, the plant will revert to the float mode. It may go to boost mode if the auto-boost feature has been enabled.

Boost Mode
Boost charging is a feature of I-combo controller, which allows the user to temporarily raise the plant voltage to a higher, predetermined level, thus, reducing the time needed to charge batteries. The system may manually be placed in the boost-mode through the front panel. Note that the measured boost voltage may not exactly match the value chosen by the user if the thermal compensation feature is enabled. This is because the Galaxy Pulsar Plus performs thermal compensated boost charging and will adjust the boost value based on the battery temperature per the slope chosen by the user. The plant will exit the boost mode and enter the float mode if any of the following occurs:

The current flowing into the battery string(s) is less than 5A The duration of boost mode charging has reached the configured duration time (1-80) hours The controller receives either a High-Voltage, Rectifier Fail alarm, or High-Battery Temperature alarms User sets the plant state to Float via the TI.

Once initiated, the boost mode may be exited by placing the Plant State to Float.

Auto-Boost Charge
This feature may be enabled from the TI. See Appendix B for details. When enabled, the plant enters the boost-charging mode of operation following a battery discharge once the BD alarm has been retired, provided the duration of the discharge was greater than 4 minutes. The controller will not enter the auto-boost-charging mode if the discharge duration was less than 4 minutes. When in auto-boost mode, the controller raises the plant voltage to the value selected by the user. The controller keeps the plant in this mode of operation for a minimum of 5 minutes. The exit conditions for the Auto-Boost Charge are the same as those for Boost Charge.

IPMS Product Manual annexureJune- 2010

Redundancy Loss Function


This feature must be enabled from the front panel. The controller determines the number of rectifiers present and compares the actual currents being drawn by the load to that produced by the total number of rectifiers less one. If the measured load current exceeds the N rectifiers capacity for over 1 min, the alarm condition is activated. The alarm condition is latched on until the Clear Events command is activated from the front panel. This feature may be used by customers to determine if the load being served is greater than N rectifiers worth, in an N+1 system. That is, the load requirements have changed such that the power system is no longer operating as a redundant power system. An additional rectifier may be required to ensure continuous redundant operation. If enabled, this feature will be disabled during battery discharge and recharge conditions. It will be enabled when the battery charging current falls below 5A.

Battery Voltage Imbalance Detection


This feature requires the use of the ES771A Remote Voltage Monitoring Module. Note that this feature is automatically enabled if the controller detects the presence of the ES771A module. This module is to be placed in the electronics cabinet and utilizes the QS873A VTProbes to measure the voltage of the battery string being monitored. The VT-Probe is to be placed on the negative battery terminal located in the middle of the battery string. I-combo controller has data on the plant voltage; the half-string voltage measured from each monitored battery string is compared to the plant voltage minus the measured half-string voltage. If the comparison results in a difference of greater than 1.7V (or the configured value) for longer than 12 hours, the alarm is asserted. The alarm may be retired by initiating the Clear Events command from the front panel. After this feature has been enabled, the system waits for 12 hours to ensure the battery strings are stable. A battery string is considered to be stable if the charging current is less than 3A. If a stable battery string yields a difference measurement greater than 1.7V (or the configured value) for over 12 continuous hours, a Battery Voltage Imbalance alarm is generated. When the alarm is issued, the Float Set-Point (fsp) and the Battery On Discharge (BD) threshold values are reduced by fsp/Number of Cells per string. Once the alarm has been cleared by the Clear Events (CLE) command, the plant reverts to its normal Float Set-Point (fsp); however, the BD threshold is maintained at the new threshold for up to four minutes before reverting back to the old threshold. This is done to ensure the batteries have had

IPMS Product Manual annexureJune- 2010

enough time to charge up to the nominal fsp and to prevent any spurious BD alarm conditions. This feature may be used by customers as part of their overall battery maintenance program in determining the health of battery strings. A voltage imbalance of 1.7V between half-string voltages may mean a shorted-cell, loose connection, or some other abnormality somewhere in the string. A service person should be sent out to the site and determine if the string should be replaced.

Battery Recharge Current Limit


The battery recharge current limit feature enables the I-combo controller to limit the recharge current flowing into a battery section during the charge cycle. The recharge current flowing into the battery section can be limited to any value between 5A and 1000A. Note that this feature will not have any impact on the current being delivered to the load. Further, there will be no effect on the discharge current flowing from the battery strings to the load during an ac fail condition. The controller will maintain the recharge current within 10% of the set level.

IPMS Product Manual annexureJune- 2010

Appendix D - Factory Defaults for Alarms & LEDs


SEVERITY RELAY Object ID HFV1 HVA1 BDA1 Low Voltage VLA1 FAJ1 FAN1 AMJ1 AUX1 AUX2 AUX3 Fuse/CB Alarms AUX4 AUX5 AUX6 AUX7 AUX8 AUX9 AUX10 SCD1 BTA1 BTS1 OSA1 Battery Alarms EPO1 BFA1 TPA1 RTL1 RRTL1 ADDITIONAL RELAY LED

Category High Voltage

Description High Voltage Minor (HFV) High Voltage Major (HFVS) Battery on Discharge (BD) Very Low Float Voltage (VLV) Fuse Major Fuse Minor Auxiliary Major Alarm AC SPD Fail DC SPD Fail Auxiliary 3 Fan Fail Air Cond Fail Door Open Hi Ext Amb Hydrogn Prsnt Auxiliary 9 Auxiliary 10 Voltage Imbalance Detect High Battery Temperature Batter Test Active Open String Emergency Power Off (EPO) Check Battery (Plant Battery Test Fail) Defective Temp Probe Reserve Time Low Real-Time Reserve Time Low

CRIT

PMJ

PMN MIN

RO

R1

R2

R3

R4

R5

R6 R6 R6

R7

BD

AC

DC

MAJ MAJ CRIT CRIT MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MIN MAJ RO MAJ MAJ MIN MIN RO RO R1 R4 R5 R5

BD

DC DC

BD R7 DC

IPMS Product Manual annexureJune- 2010

ISD1 CNF1 CNO1 CNF2 Contactor Alarms CNO2 CNF3 CNO3 CNF4 CNO4 RLS1 RFA1 Rectifiers MRFA1 RFN1 ACF1 AC Power MACF1 CMA1 MCM1 Controller VSF1

Imminent LVBD Shutdown LV Disconnect Contactor 1 Fail LV Disconnect Contactor 1 Open LV Disconnect Contactor 2 Fail LV Disconnect Contactor 2 Open LV Disconnect Contactor 3 Fail LV Disconnect Contactor 3 Open LV Disconnect Contactor 4 Fail LV Disconnect Contactor 4 Open Rectifier Redundancy Loss Single Rectifier Fail (RFA) Multiple Rectifier Fail (MRFA) Rectifier Fan Fail Single AC Fail (ACF) Multiple AC Fail (MACF) Communication Loss Minor Communication Loss Major Sense Fuse Controller Fail (Not user mappable) Un-powered Controller CRIT

MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MAJ MIN MIN R3 R3 MIN MIN MAJ MIN MAJ MIN x x x x x x x x x x R2 R2 AC AC R5 R5 R7 R7 DC DC DC DC

Issue History
Issue 0.1: Released for review and comments

Vous aimerez peut-être aussi