Capacitor Bank Sizing Calculation & Cost Comparission

Inputs Required Supply System Supply Voltage Supply Frequency Input Power or Load Efficiency Old Power Factor (Cos1) Old Power Factor (Cos2) Load Current (I) Capacitor Connected in Daily Working Hours Tarrif Charge/kVA Tarrif Charge/KW Capacitor cost/kVA Annual Interest & Depriation / Capacitor Calculation for KVAR required Tan1 Tan2 Kvar of the Load Kvar per Phase Calculation for Capacitance of Capacitor Kvar per Phase = V*IC*1000 Capacitive Current (IC) Capacitive Current (IC) = 2**f*C Tharefore Capacitance C = IC/(2**f) Capacitance required in F Results Required capacitor is Cost Comparission Before PF Correction Maximum Demand Charge for kVA demand Unit Consumed per year Energy Charge per Year Total Annual Cost 3 415 50 110 96 0.8 0.95 191.296363 STAR 24 100 10 60 12 V Hz KW %

Amps Hr Rs Rs Rs %

Need to get from capacitor vendor

0.75 0.32868411 46.3447484 Kvar 15.4482495 Kvar

= (Load KW*(Tan1-Tan2)) = (Kvar/No. Of Phase)

15.4482495 64.4731761

=Kvar per Phase = V*IC*1000

=(Kvar per Phase*1000)/(VL/1.732) for STAR connect

=(Kvar per Phase*1000)/(VL) for DELTA connected Ca

0.20522449 Farad 205224.494 F

3 Nos of

15.45 kVAR

137.50 13750 963600 9636000 9649750

kVA Rs KWh Rs Rs

After PF Correction Maximum Demand Charge for kVA demand Unit Consumed per year Energy Charge per Year Annual Electricity Bill Capital cost of Capacitor Annual Interest & Depriation Total Annual Cost

Annual Savings

ssion

VL/1.732) for STAR connected Capacitor

VL) for DELTA connected Capacitor as VL=VPh

mand demand d per year per Year ity Bill Capacitor t & Depriation ost

115.7895 11578.95 963600 9636000 9647579 2780.685 333.6822 9647913

avings

1837.37