Vous êtes sur la page 1sur 228

cabel catalogue

Welcome!

Dear Customer,
Our objective is to fulfil our customers demands to their utmost satisfaction at all times. This requires a perfect interplay of sales processes, a powerful IT system and the latest technology to provide maximum flexibility. It means that we can solve even the most complex of tasks and it is our employees who play the most important role in doing so. Flat hierarchies, a high level of training, and the freedom to act on their own initiative enable our employees to take responsibility, and at the same time to enjoy job satisfaction. You can get to know our employees and the jobs they perform by visiting us in the Internet, where information on all of our contact partners is available, complete with photos. This ensures that you always know who it is that you are dealing with. The independence that comes from being an owner-managed company, coupled with our solid financial base, enables us to draw up a long development strategy, with the goal of creating ongoing relationships with customers and suppliers. This leads to synergies which benefit all sides. The KLAUS FABER FOUNDATION is a guarantee that this will remain so, irrespective of any future developments. The institution is responsible for the short to medium term representation of the companys interests, as well as our involvement in the environment and society in general. We hope you enjoy reading our new catalogue! Yours, Klaus Faber

Content <<<
Power cables 1 up to 30 kV

Power cables 1 up to 30 kV
Low voltage cable Medium voltage cable Overhead line

Sheathed Building Wire

PVC-insulated wires and cords Rubber Insulated Cables Rubber insulated wires

Silicone insulated wires and cords PUR-insulated cords Special Versions

Telecommunication Cables and Cords


Indoor telecommunication cable Subscriber line cable Instrumentation cable Industrial electronic cable Insulated Cords

103

Control cable Electronic cable Bus cable

Fire resistant power cable Fire resistant communication cable

LAN cables
Network-cable Cables up to 100 MHz Cables up to 200 MHz Cables up to 1000 MHz Optical cables - indoor Optcal Cables - outdoor

Copper conductor

Other
Speaker cable Heat resistant cable Coaxial cable

199
Other

Technical Appendix
Type Designation Code Core identification acc. to VDE 0815/0816 Color code/Color coding of cores Identification of cores acc. to VDE 0293 Sizes of cable drums Legend of icons Index Delivery and payment terms

207

>>> www.faberkabel.de <<<

>3<

Technical Appendix

Conductor ropes

Conductor ropes

197

LAN cables

187

Cable with circuit integrity

Cable with circuit integrity E30 or E90

177

Control and Electronic Cable

Control and Electronic Cable

127

Telecommunication Cables and Cords

Flexible Cables

Flexible Cables

59

Building Wires

Building Wires

53

Rapid action for trade and export.

If you have any questions on trade or export matters, please contact Joachim Krimmel or Vojislav Jovanovic by telephone at +49 (0)681/9711-200 or -246.

FABER KABEL, Your partner at home and abroad.


FABER KABEL has always been a strong partner for trading companies. For us, the rapid processing of enquiries and efficient issuing of offers are simply a matter of course. We ship cables and conductors throughout Germany within a short time frame, while worldwide shipments take place every week on fixed days, to ensure that you always receive the goods you order within one week. In addition to our speed and flexibility, we are also characterised by our employees high level of advisory competence. Whether you wish to know more about product approvals or standards or you have some other technical problem, our employees are happy to help, to enable us to jointly locate the optimum solution for you. A special service that we provide to our trading partners at home and abroad comprises on-site presentations and seminars. These give both you and your customers a chance to satisfy yourselves of our products quality, and to familiarise yourselves with their special features, backed up by expert guidance.

> 4<

>>> www.faberkabel.de <<<

Solutions for all requirements.

Suppliers of solutions to meet all requirements: Gunther Gellert and Martin Leidner are there to advise you at +49 (0)681/9711-156 and -232.

Consultation for industrial and plant construction projects.


The more complex, the better is our motto regarding large-scale project solutions in industry or plant construction. Excellent familiarity with German and international standards, certifications and approvals means that our employees are able to provide assistance in supplying the cables you need to suit an extremely wide range of plants. Naturally, we place the focus not only on technical parameters, but our enquiry processing and analysis procedures also take into account financial and logistical aspects. This means that with FABER KABEL, you can always be sure of finding
>>> www.faberkabel.de <<<

the best solution. We coordinate the manufacture of standard warehouse products and special production runs, right down to the last detail. Error-free type determination is applied right from the start, to ensure that a precisely configured, project-specific product selection is always available by the agreed delivery date. Should you require special-purpose cables, we have a worldwide network to ensure that in such cases, we are still able to fulfil your needs in the shortest possible time. You can always be sure that you will obtain everything you need, from standard cables to special additional components and certifications, from a reliable partner, at first-class terms.

> 5<

Everything direct from stock.


One of Europes largest cable warehouses.
Two warehouses, around 400 different types of cable and almost 140,000m of warehouse space. These figures show clearly that FABER KABEL is the perfect supplier to satisfy your cable needs. Over 4,000 articles are stored in more than 30,000 high-rack storage locations. Virtually all orders can be called up directly from the warehouse. More than 100 employees are active on your behalf throughout our logistics centres every day, loading a total of 350 tonnes of products for our customers.

Active on your behalf at all times: Adolf Gtz and Wolfgang Ebert are responsible for warehouse and logistics.

Flexible order handling to satisfy your requirements.


Logistics that cannot be bettered.
Rapid order processing and flexible handling are two major strengths that characterise our business. Our IT solutions were developed inhouse, for maximum efficiency in conducting our transactions for you. If you need your products urgently, we can arrange for you to collect them yourselves. We place your pre-assembled products in separate interim stores, where they can be called up any time they may be required. A top service guaranteeing smooth procedures.

> 6<

>>> www.faberkabel.de <<<

Highest quality for simple handling.


FACAB sets the tone.
For more than 20 years, the FACAB trademark has been guaranteeing high and consistent product quality. Over and above the technical specifications required by DIN and VDE standards, our trademark stands for the excellent handling and use characteristics of each of our products. We supply internationally applicable test protocols for industry and trade and keep technical drawings, data and plans available.

Tailored for you.


Additional individual configuration to customer specification.
Cables with diameters of up to 85mm and a maximum cross-section of 120mm are machine produced and fitted with standard cable lugs, core-end sleeves or plug connectors for nominal currents of up to 125A. The length and type of pre-assembled cables can be individually specified. Cores and cables can also be given customer-specified labelling or markings. If you have any other pre-assembly requirements, please contact Willi Dorstewitz, who will be happy to help you.

>>> www.faberkabel.de <<<

> 7<

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity Flexible Cables Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Power cables 1 up to 30 kV

>8<

>>> Power cables 1 up to 30 kV

Notes:

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV <<<


Power cables 1 up to 30 kV

powerful

Content

Overhead line NFA2X >>> www.faberkabel.de <<<

52 52 >9<

Technical Appendix

Medium voltage cable N2XSY 6/10 kV N2XSY 12/20 kV N2XSY 18/30 kV NA2XSY 6/10 kV NA2XSY 12/20 kV NA2XSY 18/30 kV N2XS2Y 6/10 kV N2XS2Y 12/20 kV N2XS2Y 18/30 kV N2XS(F)2Y 6/10 kV N2XS(F)2Y 12/20 kV N2XS(F)2Y 18/30 kV N2XS(FL)2Y 6/10 kV N2XS(FL)2Y 12/20 kV NA2XS2Y 6/10 kV NA2XS2Y 12/20 kV NA2XS2Y 18/30 kV NA2XS(F)2Y 6/10 kV NA2XS(F)2Y 12/20 kV NA2XS(F)2Y 18/30 kV NA2XS(FL)2Y 6/10 kV NA2XS(FL)2Y 12/20 kV NA2XS(FL)2Y 18/30 kV N2XSEY 6/10 kV

31 31 32 33 34 35 36 37 38 39 40 41 42 43 43 44 45 46 47 48 49 50 50 51 51

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Low voltage cable NYY-J NYY-O NYY-JZ NYY-OZ NYCY NYCWY NAYY-J NAYY-O (N)YYk-J (N)2XY-J (N)2XY-O NYRY-J NYFGY 3,6/6 kV (N)Y(Zg)2Y N2XH-J N2XH-O N2XCH

10 10 11 13 14 15 16 17 18 19 20 22 24 24 25 26 27 29

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NYY-J
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage core identification protective conductor conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 011840 011742 010133 010116 010117 010118 010119 010120 010121 010147 010148 010506 010507 011225 012110 010003 010012 010020 010023 010004 010009 010015 010018 010021 010024 010026 010005 010007 010010 010013 010016 010019 010022 010025 010027 010006 010008 010011 010014 010017 010028 010034 010038 type 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 03X1,5 03X2,5 03X4 03X6 03X10 03X16 03X25 03X35 03X50 03X70 03X95 03X120 03X150 03X185 03X240 03X25/16 03X35/16 03X50/25 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95 03X240/120 03X300/150 04X1,5 04X2,5 04X4 VDE 0276-603 0,6 kV 1 kV 1,2 kV 4 kV

Power cables 1 up to 30 kV
Application: For fixed installation indoors, outdoors, in ground and in water.

Building Wires

colours acc. VDE 0293 (HD308) yes bare copper class 1, from 25 sqmm class 2 PVC DIV 4 70 C PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C -5 - +70 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 43 72 115 173 288 461 720 1008 1440 2016 2736 3456 4320 5328 6912 874 1162 1680 2352 3216 4128 4992 6240 8064 10080 58 96 154 DA mm 9,1 9,5 10,2 11,2 12,2 13,2 15,4 16,4 18,5 20,5 22,5 24,6 27,6 29,7 33,8 11,2 12,2 14,2 15,2 17,3 19,3 24,5 22,6 25,6 29,7 33,8 35,8 39,8 46 51 24,5 24,5 28,7 31,7 37,8 41 45 50 57 64 12,2 13,2 15,3 weight ca. kg/km 110 130 180 240 350 460 600 800 1100 1350 1650 2000 2600 3200 4100 190 240 330 420 580 810 1300 1400 1800 2400 3300 4000 4900 6500 8300 1500 1700 2300 2800 3800 4700 5600 7400 9600 11200 220 290 400 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 10 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 010040 010029 010032 011018 010036 010037 010039 010041 010042 010030 010031 010033 010035 010043 010046 010049 010050 010044 010045 010047 010048 011028 012086 012087 012088 type 04X6 04X10 04X16 04X16/RM 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 05X35 05X50 05X70 05X95 05X120 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 230 384 614 614 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 192 288 480 768 1200 1680 2400 3360 4560 5760 DA mm 16,3 18,3 21,4 21,4 25,5 27,7 29,8 33,8 38,9 42 47 52 58 13,2 14,2 16,3 18,3 20,4 22,4 27,5 33,6 40 42,4 50 51,3 weight ca. kg/km 510 720 1050 1050 1600 1750 2300 3100 4200 5200 6400 8050 11000 270 350 480 610 880 1250 1950 2400 3500 4450 6134 7483 packaging dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

NYY-J

NYY-O
Application: For fixed installation indoors, outdoors, in ground and in water. standard core identification nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage protective conductor conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 011512 012625 010085 010087 010076 010079 010082 012006 012007 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 01X25 01X25 colour bk bk bk bk bk bk bk rd gn CU kg/km 14,4 24 38 58 96 154 240 240 240 DA mm 7 7,9 9,1 9,5 10,2 11,2 12,2 12,2 12,2 VDE 0276-603 colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 1,2 kV 4 kV no bare copper class 1, from 25 sqmm class 2 PVC DIV 4

PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C -5 - +70 C weight ca. kg/km 63 105 110 130 180 240 350 350 350 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 11 <

Technical Appendix

Other

Conductor ropes

70 C

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NYY-O
p/n 010084 010086 010088 010089 010077 010078 010080 010081 010083 010115 010141 010283 010090 010093 010095 010096 010091 010092 010140 011554 011033 010480 010508 010483 010484 011032 010150 010149 010510 011552 011553 011849 010509 010109 010102 010105 010106 010107 010108 010110 010111 010103 010104 011010 011531 type 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 01X500 01X630 02X1,5 02X2,5 02X4 02X6 02X10 02X16 02X25 03X1,5 03X2,5 03X4 03X6 03X10 03X25 03X35 03X50 03X95 03X150 03X185 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240

Power cables 1 up to 30 kV
colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 336 480 672 912 1152 1440 1776 2304 2880 3840 4800 6048 29 48 77 115 192 307 480 43 72 115 173 288 720 1008 1440 2736 4320 5328 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 7104 9216 DA mm 13,2 15,4 16,4 18,5 20,5 22,5 24,6 27,6 29,7 33,8 38 42,5 11 12 14 15,2 16,6 19 23 11,2 12,2 14,2 15,2 17,3 24,5 22,6 25,6 33,8 39,8 46 12,2 13,2 15,3 16,3 18,3 21,4 25,5 27,7 29,8 33,8 38,9 42 47 52 58 weight ca. kg/km 460 600 800 1100 1350 1650 2000 2600 3200 4100 5200 6650 170 210 290 360 490 660 940 190 240 330 420 580 1300 1350 1800 3300 4900 6500 220 290 400 510 720 1050 1600 1750 2300 3100 4200 5200 6400 8050 11000 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 12 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For fixed installation indoors, outdoors, in ground and in water. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage core identification protective conductor conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation conductor construction p/n 010052 010053 010054 010918 010930 012060 012061 012062 012003 010055 010056 011216 010057 010058 010059 010060 011530 012197 010061 010062 010063 010064 011759 010065 010066 010067 010068 012256 010069 010070 012257 011511 010071 010072 010073 010074 010075 type 07X1,5 07X2,5 07X4 07X6 07X10 07X25 07X35 07X50 08X1,5 10X1,5 10X2,5 10X4 12X1,5 12X2,5 14X1,5 14X2,5 14X4 14X6 16X1,5 16X2,5 19X1,5 19X2,5 19X4 21X1,5 21X2,5 24X1,5 24X2,5 24X4 30X1,5 30X2,5 30X4 31X1,5 40X1,5 40X2,5 52X1,5 52X2,5 61X1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 101 168 269 403 672 1680 2352 3360 115 144 240 384 173 288 202 336 538 806 230 384 274 456 730 302 504 346 576 922 432 720 1152 446 576 960 749 1248 878 DA mm 16 17 19 21 23 30,9 34,7 40,2 14,2 19 20 23 19 21 20 21 25 25,9 21 22 22 23 28 23 25 25 27 30 26 28 32 29 31 32 35 34 VDE 0276-627 0,6 kV 1 kV 1,2 kV 4 kV gn-ye + numbers yes bare copper PVC DIV 4 PVC DMV 5

Low voltage cable <<<


Power cables 1 up to 30 kV

NYY-JZ

VDE 0482-332-1-2/IEC 60332-1 70 C 70 C -5 - +70 C solid, class 1 weight ca. kg/km 300 420 630 840 1150 2403 3191 4287 334 360 500 930 400 560 450 630 1000 1354 500 710 560 830 1354 620 910 700 1050 1636 810 1250 1962 834 1050 1650 1400 2150 1650 packaging dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 13 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NYY-OZ
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage core identification protective conductor conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation conductor construction p/n 011861 012095 010490 011687 011688 012089 012096 012090 011778 012103 011034 012097 011548 012091 011779 012104 011862 012098 012092 012099 012105 012093 012100 011863 011780 011035 012101 012094 012102 type 05X1,5 05X2,5 07X1,5 07X2,5 07X4 08X1,5 08X2,5 10X1,5 10X2,5 10X4 12X1,5 12X2,5 12X4 14X1,5 14X2,5 14X4 16X1,5 16X2,5 19X1,5 19X2,5 19X4 21X1,5 21X2,5 24X1,5 24X2,5 30X1,5 30X2,5 40X1,5 40X2,5 VDE 0276-627 0,6 kV 1 kV 1,2 kV 4 kV numbers no bare copper PVC DIV 4 PVC DMV 5

Power cables 1 up to 30 kV
Application: For fixed installation indoors, outdoors, in ground and in water.

Flexible Cables

Building Wires

VDE 0482-332-1-2/IEC 60332-1 70 C 70 C -5 - +70 C solid, class 1 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 72 120 101 168 269 115 192 144 240 384 173 288 461 202 336 538 230 384 274 456 730 302 504 346 576 432 720 576 960 DA mm 13,2 14,2 16 17 19 14,2 17,4 19 20 23,4 19 21 24,1 20 21 25 21 22 22 23 27,7 23 25 25 27 26 28 29 31 weight ca. kg/km 270 350 300 420 630 334 480 360 500 930 400 560 1100 450 630 1000 500 710 560 830 1354 620 910 700 1050 810 1250 1050 1650 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 14 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For fixed installation indoors, outdoors, in ground and in water. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems core identification test voltage protective conductor conductor material insulation sheathing material flame retardant max. operating temperature, fixed maximum temperature at conductor temperature, moved/ during installation conductor construction p/n 080030 080031 080032 080033 080035 080037 080038 080039 080040 080041 080042 080043 080044 080076 080083 080084 080045 080046 080047 080085 080098 080207 080091 080208 080048 080049 080086 080050 080051 080069 080052 080053 080073 080054 080055 080056 080057 080058 080130 080059 080068 080087 type 02X1,5/1,5 02X2,5/2,5 02X4/4 02X6/6 03X1,5/1,5 03X2,5/2,5 03X4/4 03X6/6 04X1,5/1,5 04X2,5/2,5 04X4/4 04X6/6 05X1,5/1,5 05X2,5/2,5 05X4/4 05X6/6 07X1,5/2,5 07X2,5/2,5 07X4/4 07X6/6 08X1,5/2,5 08X2,5/4 08X4/4 08X4/6 10X1,5/2,5 10X2,5/4 10X4/6 12X1,5/2,5 12X2,5/4 12X4/6 14X1,5/2,5 14X2,5/6 16X1,5/4 16X2,5/6 19X1,5/4 19X2,5/6 21X1,5/6 24X1,5/6 24X1,5/10 24X2,5/10 30X1,5/6 30X2,5/10 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 52 80 123 182 66 104 161 240 81 128 200 297 95 152 238 355 133 200 315 470 147 238 360 374 176 286 451 205 334 528 234 403 276 451 320 523 369 413 465 696 499 840 DA mm 13 13,6 15,4 16,9 13,2 14,2 16,3 17,3 14,2 15,3 17,3 18,4 15 16 19 21 15,3 17,4 20 22,5 17,5 19 20 21 18,4 20,4 23,5 19,4 20,5 24,5 20,4 21,5 20 22,5 22,5 23,5 23 25,5 25 27,6 26,5 29,5 VDE 0276-603 0,6 kV 1 kV 1,2 kV

Low voltage cable <<<


Power cables 1 up to 30 kV

NYCY

colored acc. to HD 308; more than 5 cores: numbers 4 kV no bare copper PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C 70 C -5 - +70 C class 1, from 25 sqmm class 2 weight ca. kg/km 200 260 350 430 220 280 390 500 250 340 460 580 330 400 550 700 350 450 600 790 450 530 770 751 410 600 900 470 660 1060 520 750 620 800 660 940 790 850 943 1150 1020 1600 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. PVC DIV 4

>>> www.faberkabel.de <<<

> 15 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NYCY
p/n 080074 080075 080072 080088 080089 080090 type 40X1,5/10 40X2,5/10 52X1,5/10 52X2,5/10 61X1,5/10 61X2,5/10

Power cables 1 up to 30 kV
colour bk bk bk bk bk bk CU kg/km 696 1080 869 1368 998 1584 DA mm 30 33 32 35 33 36 weight ca. kg/km 1280 1660 1600 2000 2000 2280 packaging dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

NYCWY
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage core identification protective conductor VDE 0276-603 0,6 kV 1 kV 1,2 kV 4 kV colours acc. VDE 0293 (HD308) no bare copper PVC DIV 4 70 C PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C -5 - +70 C class 1, from 25 sqmm class 2 colour bk bk bk bk bk bk bk bk bk bk bk CU kg/km 312 489 408 643 1003 1402 2000 2796 3791 4786 5970 DA mm 19,4 20,4 19,4 21,4 25,5 25,7 28,7 33,8 37,8 41,8 46 weight ca. kg/km 610 840 750 1050 1600 1850 2400 3300 4500 5500 6750 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

LAN cables

Cable with circuit integrity

conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation conductor construction p/n type

Other

Conductor ropes

Technical Appendix

080001 080002 080003 080008 080011 080013 080015 080017 080019 080004 080006

02X10/10 02X16/16 03X10/10 03X16/16 03X25/25 03X35/35 03X50/50 03X70/70 03X95/95 03X120/120 03X150/150

> 16 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 080010 080012 080014 080016 080018 080005 080007 080009 080061 080020 080023 080099 080025 080026 080027 080028 080029 080021 080022 080024 080062 type 03X25/16 03X35/16 03X50/25 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95 03X240/120 04X10/10 04X16/16 04X16RM/16 04X25/16 04X35/16 04X50/25 04X70/35 04X95/50 04X120/70 04X150/70 04X185/95 04X240/120 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 902 1190 1723 2410 3296 4236 5100 6383 8242 504 796 796 1142 1526 2203 3082 4208 5388 6540 8159 10546 DA mm 25,5 27,6 28,7 32,8 37,8 40,8 45 50 57 20,4 23,4 23,4 27,6 28,6 32,8 36,8 43,9 47 51 56 63 weight ca. kg/km 1600 1700 2300 2900 4000 5000 6000 7500 10000 870 1250 1250 1800 2050 2700 3750 5000 6300 7600 9300 11600 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

NYCWY

NAYY-J
Application: For fixed installation indoors, outdoors, in ground and in water. standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems core identification protective conductor conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 090010 090006 090007 090001 090002 090008 090003 090004 090005 090009 090022 090067 type 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 04X240SM 05X10 colour bk bk bk bk bk bk bk bk bk bk bk bk AL kg/km 186 290 406 580 812 1102 1392 1740 2146 2784 2784 145 DA mm 24 25 28,1 29,5 35 39 43 46 51 56 58 19,3 VDE 0276-603 0,6 kV 1 kV 4 kV 1,2 kV colours acc. VDE 0293 (HD308) yes aluminium PVC DIV 4 PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C 70 C -5 - +70 C weight ca. kg/km 750 950 1100 1200 1600 2100 2400 3000 3700 5000 5300 585 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 17 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NAYY-J
p/n 090068 090069 090070 type 05X16 05X25 05X35

Power cables 1 up to 30 kV
colour bk bk bk AL kg/km 232 362,5 507,5 DA mm 21,8 27,1 30,2 weight ca. kg/km 938 1188 1375 packaging dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

NAYY-O
standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems core identification protective conductor VDE 0276-603 0,6 kV 1 kV 4 kV 1,2 kV colours acc. VDE 0293 (HD308) no aluminium PVC DIV 4 PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 70 C 70 C -5 - +70 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk AL kg/km 145 203 275 348 435 536 696 870 1160 1450 1827 186 290 DA mm 15 17 19 20 22 25 28 30 34 37 43 24 25 weight ca. kg/km 298 383 490 575 695 845 1100 1379 1615 2015 2472 750 950 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

LAN cables

Cable with circuit integrity

conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 090036 090037 090038 090039 090040 090041 090035 090027 090042 090043 090034 090044 090045 type 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 01X500 01X630 04X16 04X25

Technical Appendix

Other

Conductor ropes

> 18 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 090046 090047 090048 090049 090050 090051 090052 090053 type 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 colour bk bk bk bk bk bk bk bk AL kg/km 406 580 812 1102 1392 1740 2146 2784 DA mm 28 30 35 39 43 46 51 56 weight ca. kg/km 1100 1200 1600 2100 2400 3000 3000 3000 packaging dr. dr. dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

NAYY-O

(N)YYk-J
Application: Energy distribution cable. For fixed installation inside of buildings, for direct burial in earth, in water as well as in concrete, designed for power supply and control of oil and fuel pumps. The resistance against oil and fuel is proofed by BAM-test report VI. 34/10389/96 and tests acc. to VDE 0472 p. 803, Test B. core identification protective conductor nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 011125 011126 011127 type 03X1,5 05X1,5 07X1,5 colour bk bk bk CU kg/km 43 72 101 DA mm 11,3 13,3 14,3 colours acc. VDE 0293 (HD308) yes 0,6 kV 1 kV 4 kV 1,2 kV bare copper PVC YI4 PVC YM3 VDE 0482-332-1-2/IEC 60332-1 70 C

-5 - +70 C weight ca. kg/km 190 270 300 packaging dr. dr. dr.

>>> www.faberkabel.de <<<

> 19 <

Technical Appendix

Other

Conductor ropes

70 C

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

(N)2XY-J
standard core identification nominal voltage UO IEC 60502

Power cables 1 up to 30 kV
colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers 0,6 kV 1 kV 1,2 kV 4 kV bare copper XLPE DIX3 90 C PVC ST2, UV-resistant VDE 0482-266-2-4/ IEC 60332-3-24 15 x DA -5 - +70 C -35 + 70 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 24 38,4 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 43,2 72 115,2 173 288 461 720 1008 1440 2016 2736 3456 4320 5328 6912 557 874 1162 1680 2352 3216 4128 4992 6240 DA mm 6,4 6,8 7,3 7,8 9,1 10,1 11,8 13,1 14,5 16,5 18,4 20,2 22,2 24,8 27,7 29,9 33,5 11,3 12,1 13,1 14,1 16,9 19,2 23,7 26,6 27,1 31,2 34,5 37,5 42,6 46,8 52,1 23,1 26,2 30,9 33,2 38,1 42,3 46,8 51,9 weight ca. kg/km 53 66 85 107 159 222 328 428 562 779 1040 1296 1579 1981 2560 3142 4021 177 223 291 370 562 790 1234 1620 1800 2400 3300 4000 4900 6500 8300 1030 1500 1700 2300 2800 3800 4700 5600 7400 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

Building Wires

nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material insulation maximum temperature at conductor sheathing material flame retardant bending radius, fixed installation temperature, moved/ during installation max. operating temperature, fixed p/n 012349 012350 012351 012352 012353 012354 012355 012356 012357 012358 012359 012360 012361 012362 012363 012364 012365 012366 012367 012368 012369 012370 012371 012373 012375 012377 012379 012381 012383 012385 012387 012389 012372 012374 012376 012378 012380 012382 012384 012386 012388 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 03X1,5 03X2,5 03X4 03X6 03X10 03X16 03X25 03X35 03X50 03X70 03X95 03X120 03X150 03X185 03X240 03X16/10 03X25/16 03X35/16 03X50/25 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 20 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 012390 012391 012392 012393 012394 012395 012396 012397 012398 012399 012400 012401 012402 012403 012404 012405 012406 012408 012409 012410 012411 012412 012413 012414 012415 012416 012417 012418 012419 012420 012421 012422 012423 012424 012425 012426 012427 012428 012429 012430 012431 012432 012433 012434 012435 012436 012437 012438 012439 012440 012441 012442 012443 012444 012445 012446 012447 012448 012449 012450 012451 012452 012453 012454 type 03X240/120 03X300/150 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 05X35 05X50 05X70 05X95 05X120 07X1,5 07X2,5 07X4 07X6 07X10 07X25 07X35 07X50 08X1,5 10X1,5 10X2,5 10X4 12X1,5 12X2,5 14X1,5 14X2,5 14X4 14X6 16X1,5 16X2,5 19X1,5 19X2,5 19X4 21X1,5 21X2,5 24X1,5 24X2,5 30X1,5 30X2,5 31X1,5 40X1,5 40X2,5 52X1,5 52X2,5 61X1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 8064 10080 58 96 154 230,4 384 614,4 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 192 288 480 768 1200 1680 2400 3360 4560 5760 101 168 269 403,2 672 1680 2352 3360 115,2 144 240 384 173 288 202 336 538 806,4 230,4 384 274 456 730 302,4 504 346 576 432 720 446,4 576 960 749 1248 878,4 DA mm 59,6 66,7 11,8 12,8 14,1 15,2 18,4 21,7 26,2 27,4 29,1 31,1 35,1 38,8 42,5 47,5 52,6 13,1 14,2 15,1 17,6 19,7 22,1 27,2 29,9 40,3 45,7 50,9 14,1 15,2 16,7 18,9 weight ca. kg/km 9600 11200 202 258 343 442 678 1013 1530 1990 2071 2908 3958 4959 6061 7632 9908 270 350 480 610 880 1250 1950 2400 3500 4450 6134 7483 300 420 630 840 1150 2403 3191 4287 334 360 500 930 400 560 450 630 1000 1354 500 710 560 830 1354 620 910 700 1050 810 1250 834 1050 1650 1400 2150 1650 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

(N)2XY-J

17,5 18,9 18,1 19,9

19,2 20,5 19,5 21,6 21,1 23,2 22,5 25,4 24,1 26,9 27,1 30,2 30,3 34,5 32,3

>>> www.faberkabel.de <<<

> 21 <

Technical Appendix

Other

Conductor ropes

LAN cables

17,1 18,5

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

(N)2XY-O
standard core identification nominal voltage UO IEC 60502

Power cables 1 up to 30 kV
colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers 0,6 kV 1 kV 1,2 kV 4 kV bare copper XLPE DIX3 90 C PVC ST2, UV-resistant VDE 0482-266-2-4/ IEC 60332-3-24 15 x DA -5 - +70 C -35 + 70 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 24 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 4800 6048 29 48 77 115,2 192 307,2 480 672 960 1344 43,2 72 115,2 173 288 461 720 1008 1440 2016 2736 3456 DA mm 6,4 6,8 7,3 7,8 9,1 10,1 11,8 13 14,5 16,5 18,4 20,2 22,2 24,8 27,7 29,9 33,5 38 42,5 10,7 11,5 12,5 13,5 16,1 18,2 22,4 25,1 25,1 25,1 11,3 12 13,1 14,1 16,9 19,2 23,7 26,6 27,1 31,2 34,5 37,5 weight ca. kg/km 63 66 110 130 180 240 350 460 600 779 1040 1350 1579 1981 2560 3142 4021 5200 6650 159 195 249 311 465 642 1000 1302 1824 2554 177 223 291 370 562 790 1234 1620 1800 2520 3300 3456 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

Building Wires

nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material insulation maximum temperature at conductor sheathing material flame retardant bending radius, fixed installation temperature, moved/ during installation max. operating temperature, fixed p/n 012261 012264 012262 012263 012265 012266 012267 012268 012269 012270 012271 012272 012273 012274 012275 012276 012277 012278 012279 012280 012281 012282 012283 012284 012285 012286 012287 012288 012289 012290 012291 012292 012293 012294 012295 012296 012297 012298 012299 012300 012301 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 01X500 01X630 02X1,5 02X2,5 02X4 02X6 02X10 02X16 02X25 02X35 02X50 02X70 03X1,5 03X2,5 03X4 03X6 03X10 03X16 03X25 03X35 03X50 03X70 03X95 03X120

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 22 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 012302 012303 012304 012305 012306 012307 012308 012309 012310 012311 012312 012313 012314 012315 012316 012317 012318 012319 012320 012321 012322 012333 012344 012323 012334 012324 012335 012345 012325 012336 012346 012326 012337 012347 012327 012338 012328 012339 012348 012329 012340 012330 012341 012331 012342 012332 012343 type 03X150 03X185 03X240 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 05X1,5 05X2,5 07X1,5 07X2,5 07X4 08X1,5 08X2,5 10X1,5 10X2,5 10X4 12X1,5 12X2,5 12X4 14X1,5 14X2,5 14X4 16X1,5 16X2,5 19X1,5 19X2,5 19X4 21X1,5 21X2,5 24X1,5 24X2,5 30X1,5 30X2,5 40X1,5 40X2,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 4320 5328 6912 58 96 154 230,4 384 614,4 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 101 168 269 115,2 192 144 240 384 173 288 461 202 336 538 230,4 384 274 456 730 302,4 504 346 576 432 720 576 960 DA mm 42,6 46,8 52,1 11,8 12,8 14 15,2 18,4 21,7 26,2 27,4 29 31,1 35,1 38,8 42,5 47,5 52,6 13,1 14,2 14,1 15,2 16,7 weight ca. kg/km 4900 6500 8432 202 258 343 442 678 1013 1530 1990 2071 2908 3958 4959 6061 7632 9908 270 350 300 420 630 334 480 360 500 930 400 560 1100 450 630 1000 500 710 560 830 1354 620 910 700 1050 810 1250 1050 1650 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

(N)2XY-O

17,1 18,5 17,5 18,9 18,1 19,9 19,2 23,5 19,5 21,6 21,1 23,2 22,5 25,4 24,1 26,9 27,1 30,2

>>> www.faberkabel.de <<<

> 23 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

NYRY-J
standard nominal voltage UO nominal voltage U conductor material maximum temperature at conductor insulation inner sheath armour sheathing material flame retardant max. operating temperature, fixed p/n 011763 011732 011731 011734 011764 011733 011765 011735 011766 011767 011768 011736 type 03X1,5 03X4 03X2,5 03X6 04X2,5 04X4 04X6 04X10 04X16 05X2,5 05X4 05X6 VDE 0271 0,6 kV 1 kV bare copper 70 C PVC DIV 4 PVC

Power cables 1 up to 30 kV
Application: Distribution cable for industry constructions and switching boxes. For fixed installation inside of buildings, direct burial in earth, in water as well as in concrete and for heavy-duty mechanical load.

Building Wires

round steel wire, galvanized PVC YM3 VDE 0482-332-1-2/IEC 60332-1 -5 - +70 C colour bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 43 115 72 173 96 154 230 384 614 120 192 288 weight ca. kg/km 357 538 419 908 480 626 850 1088 1440 543 823 986 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

NYFGY 3,6/6 kV
Cable with circuit integrity
core identification nominal voltage UO nominal voltage U test voltage conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed armour p/n 012108 012109 012115 012116 012117 012118 012119 012213 type 03X35 03X50 03X70 03X95 03X120 03X150 03X185 03X240 nature color 3,6 kV 6 kV 9 kV bare copper PVC DIV 4 70 C PVC YM3 VDE 0482-332-1-2/IEC 60332-1 -20 - +70 C galvanized flat steel wire colour rd rd rd rd rd rd rd rd CU kg/km 1008 1440 2016 2736 3456 4320 5328 6912 DA mm 37 39 43 44 47 59 64 61 weight ca. kg/km 2450 3100 3700 4600 5450 7300 7550 9641 packaging dr. dr. dr. dr. dr. dr. dr. dr. Application: Distribution cable for industry constructions and switching boxes. For fixed installation inside of buildings, direct burial in earth, in water as well as in concrete and for heavy-duty mechanical load.

Technical Appendix

Other

Conductor ropes

LAN cables

> 24 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: The cable is designed for self supporting aerial outdoor installation up to 50 m. For fixed installation inside of buildings and for direct burial in earth. The construction of the support system assists the pulling in of cable, so that the cable can be pulled into conduits (gas- and water pipelines) over longer distances. nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation maximum temperature at conductor reinforcing element sheathing material flame retardant bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 031735 031925 032859 031898 032071 032110 032111 032112 031952 031866 031956 031938 032113 type 03X1,5 04X1,5 05X1,5 03X2,5 04X4 04X6 04X10 04X16 04X2,5 05X2,5 05X4 05X6 05X10 colour bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 43 58 72 72 154 230 384 614 96 120 192 288 480 DA mm 12,1 13,8 14 13 16,8 17,9 20,2 22,8 14 15,8 17,9 19,7 22,8 0,6 kV 1 kV 4 kV

Low voltage cable <<<


Power cables 1 up to 30 kV

(N)Y(Zg)2Y

colours acc. VDE 0293 (HD308)

solid, class 1 PVC DIV 4 70 C in outer sheath embedded glass yarns polyethylene 2YM1 VDE 0482-332-1-2/IEC 60332-1 10 x DA -20 - +70 C +5 - +70 C weight ca. kg/km 160 180 230 195 350 440 630 880 240 240 410 520 780 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 25 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

bare copper

>>> Low voltage cable


Power cables 1 up to 30 kV

N2XH-J
standard core identification protective conductor nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation conductor construction p/n 012570 011544 012460 012259 012230 011070 011071 011073 011074 011075 011076 011077 011078 011079 011514 011515 011080 011081 011082 011083 011084 011085 011086 011087 011088 011089 011090 011091 011092 011093 011094 011095 011096 011097 011098 011099 011100 011101 011102 011103 type 01X16 01X95 01X120 01X185 01X240 03X1,5 03X2,5 03X4 03X6 03X10 03X16 03X25 03X35 03X50 03X25/16 03X35/16 03X50/25 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95 03X240/120 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 05X1,5 05X2,5 VDE 0276-604

Power cables 1 up to 30 kV
colours acc. VDE 0293 (HD308) yes 0,6 kV 1 kV 4 kV 1,2 kV bare copper XLPE 2XI1 90 C FRNC-compound HM4 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C 15 x DA class 1, from 25 sqmm class 2 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 154 912 1152 1776 2304 43 72 115 173 288 461 720 1008 1440 874 1162 1680 2352 3216 4128 4992 6240 8064 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 DA mm 12 20 22 26 29 12 13 14 15 16 20 22 25 26 24 26 32 37 41 45 49 55 62 13 14 15 16 18 20 26 29 32 37 41 48 50 53 58 14 15 weight ca. kg/km 270 1200 1500 2200 2750 179 225 291 371 523 773 1200 1600 1800 1200 1640 2200 2950 3900 4800 5750 7200 9150 208 265 352 454 647 964 1446 1906 2530 3418 4574 5300 6350 7800 10300 243 310 packaging dr. dr. dr. dr. dr. dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: Low-smoke, zero-halogen flame retardant power cable. For fixed indoor and outdoor installation as well as in concrete, but not for direct burial in ground or application in water.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 26 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
p/n 011104 011105 011106 011107 011169 011108 011115 011122 012199 012200 011109 011116 011110 011117 011123 011111 011118 012201 011112 011119 011113 011120 011114 011121 011170 type 05X4 05X6 05X10 05X16 05X25 07X1,5 07X2,5 07X4 07X6 07X10 10X1,5 10X2,5 12X1,5 12X2,5 12X4 14X1,5 14X2,5 14X4 19X1,5 19X2,5 24X1,5 24X2,5 30X1,5 30X2,5 40X1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 192 288 480 768 1200 101 168 269 403,2 672 144 240 173 288 461 202 336 538 274 456 346 576 432 720 576 DA mm 16 17 19 22 25 14 15 15 15,9 18,2 17 18 17 18 21 17 19 19,5 19 21 22 25 23 26 26 weight ca. kg/km 413 536 776 1165 1766 206 287 530 569 859 287 472 328 472 820 383 670 765 484 840 603 1050 730 1230 1200 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Low voltage cable <<<


Power cables 1 up to 30 kV

N2XH-J

N2XH-O
Application: Low-smoke, zero-halogen flame retardant power cable. For fixed indoor and outdoor installation as well as in concrete, but not for direct burial in ground or application in water. standard core identification protective conductor maximum permitted operating voltage in 3-phase systems nominal voltage UO nominal voltage U test voltage conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation conductor construction p/n 012541 012542 011049 011072 011051 011052 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 colour bk bk bk bk bk bk CU kg/km 14,4 24 38 58 96 154 DA mm VDE 0276-604 colours acc. VDE 0293 (HD308) no 1,2 kV 0,6 kV 1 kV 4 kV bare copper XLPE 2XI1 90 C

VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C 15 x DA class 1, from 25 sqmm class 2 weight ca. kg/km 53 90 140 160 210 270 packaging

9 10 11 12

>>> www.faberkabel.de <<<

> 27 <

Technical Appendix

dr. dr. dr. dr. dr. dr.

Other

Conductor ropes

FRNC-compound HM4

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

N2XH-O
p/n 011053 011054 011055 011056 011057 011058 011059 011060 011061 011062 011864 011543 012621 011063 011064 011065 011066 011067 011068 011069 011997 012622 012057 012456 011382 011547 012040 012211 012041 012212 012036 011381 012051 type 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 01X500 01X630 02X1,5 02X2,5 02X4 02X6 02X10 02X16 02X25 03X1,5 03X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 10X1,5

Power cables 1 up to 30 kV
colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 240 336 480 672 912 1152 1440 1776 2304 2880 3840 4800 6048 29 48 77 115 192 307 480 43 72 154 230 384 614 960 1344 1920 2688 3648 4608 144 DA mm 14 15 16 18 20 22 24 26 29 30 32 37 12 12,1 13 14 16 18 23 12 13 15 16 18 20 26 29 32 37 41 48 17 weight ca. kg/km 380 490 620 830 1200 1275 1700 2200 2750 3300 4420 4866 6650 180 210 270 340 450 600 980 179 225 352 454 647 964 1446 1906 2530 3418 4574 5300 287 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 28 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: Low-smoke, zero-halogen flame retardant power cable. For fixed indoor and outdoor installation as well as in concrete, but not for direct burial in ground or application in water. standard core identification nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation conductor construction p/n 011128 011129 011508 012528 012529 012530 011130 011131 011132 011133 011134 011135 011136 011137 011138 012063 012064 011139 011140 011141 011142 011029 011143 011144 011145 011146 011147 011148 011149 011150 011151 011152 012215 011153 011154 011155 011156 011979 011157 011158 012458 type 02X1,5/1,5 02X2,5/2,5 02X4/4 02X6/6 02X10/10 02X16/16 03X1,5/1,5 03X2,5/2,5 03X4/4 03X6/6 03X10/10 03X16/16 03X25/16 03X35/16 03X50/25 03X70/35 03X185/95 04X1,5/1,5 04X2,5/2,5 04X4/4 04X6/6 04X10/10 04X16/16 04X25/16 04X35/16 04X50/25 04X70/35 04X95/50 04X120/70 04X150/70 04X185/95 04X240/120 05X1,5/1,5 07X1,5/2,5 07X2,5/2,5 07X4/4 07X6/6 10X2,5/4 12X1,5/2,5 12X2,5/4 14X1,5/2,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 52 80 123 182 312 489 66 104 161 240 408 643 902 1190 1723 2410 6383 81 128 200 297 504 796 1142 1526 2203 3082 4208 5388 6540 8159 10546 95 133 200 315 470 286 205 334 234 DA mm 12 12 14 15 17 19 12 13 14 16 18 21 24 27 30 34 50 13 14 15 17 19 22 27 29 33 41 46 50 55 62 68 14 16 18 19 20 18 20 21 17,6 VDE 0276-604 0,6 kV 1 kV 4 kV 1,2 kV bare copper XLPE 2XI1 90 C FRNC-compound HM4 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C 15 x DA

Low voltage cable <<<


Power cables 1 up to 30 kV

N2XCH
colours acc. VDE 0293 (HD308)

class 1, from 25 sqmm class 2 weight ca. kg/km 250 280 320 410 550 780 250 320 400 500 750 1000 1600 1900 2400 2615 6680 235 302 411 527 762 1139 1634 2080 2790 3550 4800 6556 7904 9950 12912 283 380 480 650 850 550 550 750 486 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 29 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Low voltage cable


Power cables 1 up to 30 kV

N2XCH
p/n 011980 011159 011973 011160 011858 011161 type 21X2,5/10 24X1,5/6 24X2,5/10 30X1,5/6 30X2,5/6 30X2,5/10

Power cables 1 up to 30 kV
colour bk bk bk bk bk bk CU kg/km 624 413 696 499 840 840 DA mm 23 25 26 27 28 30 weight ca. kg/km 1050 950 1106 1100 1500 1500 packaging dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 30 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 011292 011288 011289 011326 011290 011327 011291 011328 011329 011330 011294 011331 011332 011333 011976 011974 type 1X35/16 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 1X630/50 colour rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 6442 6538 DA mm 24 25 27 28 30 31 31 33 33,5 35 35 37 41 44 49 49 VDE 0276-620 6 kV 10 kV 12 kV 21 kV bare copper stranded, class 2 XLPE DIX8 90 C PVC DMV6

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XSY 6/10 kV

VDE 0482-332-1-2/IEC 60332-1 +70 C -5 - +70 C 15 x DA weight ca. kg/km 920 1100 1300 1600 1850 2050 2200 2450 2550 3000 3150 3750 4650 5700 7090 6999 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 31 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

N2XSY 12/20 kV
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 011295 011296 011297 011298 011318 011334 011335 011336 011299 011337 011338 011339 011341 011340 012566 011529 type 1X35/16 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 1X800/35 VDE 0276-620 12 kV 20 kV 24 kV 42 kV bare copper

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation.

Building Wires

stranded, class 2 XLPE DIX8 90 C PVC DMV6 VDE 0482-332-1-2/IEC 60332-1 +70 C -5 - +70 C 15 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 6442 8094 DA mm 28 29 31 32 34 35 35 37 37 40 40 42 45 49 60 weight ca. kg/km 1100 1250 1500 1800 2050 2300 2400 2650 2800 3250 3400 4000 4950 6050 7090 9032 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 32 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 011342 011343 011344 011345 011346 011347 011348 011349 011350 011351 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 colour rd rd rd rd rd rd rd rd rd rd CU kg/km 662 854 1094 1334 1723 2059 2587 3163 4234 5194 DA mm 34 36 37 39 40 42 44 47 50 53 VDE 0276-620 18 kV 30 kV 36 kV 63 kV bare copper stranded, class 2 XLPE DIX8 90 C PVC DMV6

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XSY 18/30 kV

VDE 0482-332-1-2/IEC 60332-1 +70 C -5 - +70 C 15 x DA weight ca. kg/km 1550 1750 2050 2350 2700 3100 3700 4350 5350 6450 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 33 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XSY 6/10 kV
standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor temperature, moved/ during installation flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 011392 011393 012614 011394 011395 011396 011397 011398 011399 011400 011401 011402 011403 011404 012508 type 1X50/16 1X70/16 1X70/25 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 1X800/35 VDE 0276-620 6 kV 10 kV 21 kV 12 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation.

Building Wires

stranded, class 2 XLPE DIX8 PVC DMV6 90 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 +70 C 15 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 182 182 283 182 182 182 283 182 283 182 283 283 394 394 393 AL kg/km 145 203 203 276 348 435 435 537 537 696 696 870 1160 1450 2320 DA mm 25 27 28 30 31 31 33 33 35 35 37 41 44 weight ca. kg/km 780 870 1395 990 1100 1250 1300 1400 1450 1600 1650 1950 2350 2700 3973 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 34 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation. standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor temperature, moved/ during installation flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 011405 011406 011407 011408 011409 011410 011411 011412 011413 011414 011415 011416 011417 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 colour rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 182 182 182 182 182 283 182 283 182 283 283 394 394 AL kg/km 145 203 276 348 435 435 537 537 696 696 870 1160 1450 VDE 0276-620 12 kV 20 kV 42 kV 24 kV aluminium stranded, class 2 XLPE DIX8

Medium voltage cable <<<


Power cables 1 up to 30 kV

NA2XSY 12/20 kV

90 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 +70 C 15 x DA DA mm 29 31 32 34 35 35 37 37 40 40 42 45 48 weight ca. kg/km 970 1100 1200 1350 1450 1500 1650 1700 1850 1900 2200 2600 3000 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 35 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

PVC DMV6

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XSY 18/30 kV
standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor temperature, moved/ during installation flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 011418 011419 011420 011421 011422 011423 011424 011425 011426 011427 011428 011429 011430 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 VDE 0276-620 18 kV 30 kV 63 kV 36 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation.

Building Wires

stranded, class 2 XLPE DIX8 PVC DMV6 90 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 +70 C 15 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 182 182 182 182 182 283 182 283 182 283 283 394 394 AL kg/km 145 203 276 348 435 435 537 537 696 696 870 1160 1450 DA mm 34 36 37 39 40 40 42 42 44 44 47 50 53 weight ca. kg/km 1250 1350 1500 1600 1750 1850 1950 2000 2200 2250 2550 3000 3450 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 36 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011352 011353 011354 011355 011356 011357 011358 011359 011360 011361 011362 011363 011364 011365 012047 type 1X35/16 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 6384 DA mm 24 25 27 28 30 31 31 33 33 35 35 37 41 44 49 VDE 0276-620 6 kV 10 kV 12 kV 21 kV bare copper stranded, class 2 XLPE DIX8 no 90 C -20 - +70 C +70 C 15 x DA weight ca. kg/km 900 950 1200 1450 1700 1950 2050 2350 2400 2900 2950 3550 4500 5500 6840

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XS2Y 6/10 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 37 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

polyethylene DMP2

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

N2XS2Y 12/20 kV
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011366 011367 011368 011369 011370 011371 011372 011373 011374 011375 011376 011377 011378 011379 type 1X35/16 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 VDE 0276-620 12 kV 20 kV 24 kV 42 kV bare copper

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation.

Building Wires

stranded, class 2 XLPE DIX8 polyethylene DMP2 no 90 C -20 - +70 C +70 C 15 x DA colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 518 662 854 1094 1334 1622 1723 1958 2059 2486 2587 3163 4234 5194 DA mm 28 29 31 32 34 35 35 37 37 40 40 42 45 48 weight ca. kg/km 970 1150 1350 1650 1900 2150 2250 2550 2600 3100 3200 3800 4750 5800 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 38 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011380 011383 011384 011385 011386 011387 011388 011777 011389 011390 011391 011995 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X240/70 1X300/25 1X400/35 1X500/35 1X150/50 colour bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 662 854 1094 1334 1723 2059 2587 3084 3163 4234 5194 1969 DA mm 34 36 37 39 40 42 44 45 47 50 53 42 VDE 0276-620 18 kV 30 kV 36 kV 63 kV bare copper stranded, class 2 XLPE DIX8 no 90 C -20 - +70 C +70 C 15 x DA weight ca. kg/km 1350 1600 1900 2150 2550 2900 3500 4200 4150 5100 6200 2750

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XS2Y 18/30 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 39 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

polyethylene DMP2

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

N2XS(F)2Y 6/10 kV
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011479 011480 011481 011482 011483 011484 011485 011486 011487 011488 012224 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 VDE 0276-620 6 kV 10 kV 12 kV bare copper

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Building Wires

stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA colour bk bk bk bk bk bk bk bk bk bk bk CU kg/km 662 854 1094 1334 1723 2059 2587 3163 4234 5194 6442 DA mm 25 27 28 30 31 33 35 37 41 44 49 weight ca. kg/km 1150 1400 1650 1900 2300 2650 3250 3850 4800 5900 7014 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 40 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011546 011489 011490 011317 011491 011492 011309 011493 011494 011495 011496 012225 type 1X35/16 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 colour bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 518 662 854 1094 1334 1723 2059 2587 3163 4234 5194 6442 DA mm 28 29 31 32 34 35 37 40 42 45 48 52 VDE 0276-620 12 kV 20 kV 24 kV bare copper stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA weight ca. kg/km 1300 1350 1600 1900 2150 2500 2900 3500 4150 5100 6200 7365

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XS(F)2Y 12/20 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 41 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

N2XS(F)2Y 18/30 kV
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011516 011517 011526 011519 011520 011521 011972 011522 012216 011523 011524 011525 012226 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X185/35 1X240/25 1X240/70 1X300/25 1X400/35 1X500/35 1X630/35 VDE 0276-620 18 kV 30 kV 36 kV bare copper

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Building Wires

stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA colour bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 662 854 1094 1334 1723 2059 2175 2587 3084 3163 4234 5194 6442 DA mm 34 36 37 39 40 42 42 44 44 47 50 53 58 weight ca. kg/km 1650 1900 2150 2450 2750 3150 2955 3800 3786 4400 5450 6550 7803 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 42 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the laminated PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material bonded sheath bending radius, fixed installation maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 012467 012459 012639 012582 011825 012001 012613 012654 type 01X95/16 01X120/16 01X150/25 01X185/25 01X240/25 01X300/25 01X500/35 01X630/35 colour bk bk bk bk bk bk bk bk CU kg/km 1094 1334 1723 2059 2587 3163 5194 6442 DA mm 29 31 31 34,4 36 38 45 45,1 VDE 0276-620 6 kV 10 kV 12 kV 21 kV bare copper stranded, class 2 XLPE DIX8 yes 15 x DA 90 C +70 C -20 - +70 C weight ca. kg/km 1450 1900 1997 2463 3050 3720 5878 7014

Medium voltage cable <<<


Power cables 1 up to 30 kV

N2XS(FL)2Y 6/10 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr.

N2XS(FL)2Y 12/20 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the laminated PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material bonded sheath bending radius, fixed installation maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 011786 011750 012228 type 1X95/16 1X300/25 1X500/35 colour bk bk bk CU kg/km 1094 3163 5194 DA mm 33 43 50,5 VDE 0276-620 12 kV

24 kV 42 kV bare copper stranded, class 2 XLPE DIX8 polyethylene DMP2 yes 15 x DA

+70 C -20 - +70 C weight ca. kg/km 1900 3940 5948 packaging dr. dr. dr.

>>> www.faberkabel.de <<<

> 43 <

Technical Appendix

Other

90 C

Conductor ropes

LAN cables

20 kV

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

polyethylene DMP2

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XS2Y 6/10 kV
standard nominal voltage Uo nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011431 011432 011433 011498 011434 011435 011436 011437 011438 011439 011440 011441 011442 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 VDE 0276-620 6 kV 10 kV 21 kV 12 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation.

Building Wires

stranded, class 2 XLPE DIX8 polyethylene DMP2 no 90 C -20 - +70 C +70 C 15 x DA colour bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 182 182 182 182 182 283 182 283 182 283 283 394 394 AL kg/km 145 203 276 348 435 435 537 537 696 696 870 1160 1450 DA mm 25 27 28 30 31 31 33 33 35 35 37 41 44 weight packaging ca. kg/km 670 dr. 750 dr. 860 dr. 950 dr. 1100 dr. 1150 dr. 1250 dr. 1300 dr. 1400 dr. 1500 dr. 1750 dr. 2150 dr. 2500 dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 44 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011443 011444 011324 011323 011445 011325 011446 011321 011449 011448 011450 011451 011452 012227 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/16 1X150/25 1X185/16 1X185/25 1X240/16 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 182 182 182 182 182 283 182 283 182 283 283 394 394 394 AL kg/km 145 203 276 348 435 435 537 537 696 696 870 1160 1450 1827 VDE 0276-620 12 kV 20 kV 42 kV 24 kV aluminium stranded, class 2 XLPE DIX8 no 90 C -20 - +70 C +70 C 15 x DA DA mm 29 31 32 34 35 35 37 37 40 40 42 45 48 52,9 weight ca. kg/km 830 920 1050 1150 1300 1350 1450 1550 1650 1750 2000 2400 2800 3297

Medium voltage cable <<<


Power cables 1 up to 30 kV

NA2XS2Y 12/20 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 45 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

polyethylene DMP2

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XS2Y 18/30 kV
standard nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011453 011454 011455 011456 011457 011458 011459 011460 011461 011462 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 VDE 0276-620 20 kV 30 kV 63 kV 36 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation.

Building Wires

stranded, class 2 XLPE DIX8 polyethylene DMP2 no 90 C -20 - +70 C +70 C 15 x DA colour bk bk bk bk bk bk bk bk bk bk CU kg/km 182 182 182 182 283 283 283 283 394 394 AL kg/km 145 203 276 348 435 537 696 870 1160 1450 DA mm 34 36 37 39 40 42 44 47 50 53 weight ca. kg/km 1100 1200 1300 1450 1650 1800 2050 2300 2750 3150 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 46 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011463 011464 011465 011466 011467 011468 011469 011470 011471 011472 012053 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 colour bk bk bk bk bk bk bk bk bk bk bk CU kg/km 182 182 182 182 283 283 283 283 394 394 394 AL kg/km 145 203 276 348 435 537 696 870 1160 1450 1827 VDE 0276-620 6 kV 10 kV 12 kV aluminium stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA DA mm 25 27 28 30 31 33 35 37 41 44 49 weight ca. kg/km 850 950 1100 1200 1400 1550 1750 2050 2450 2850 2969

Medium voltage cable <<<


Power cables 1 up to 30 kV

NA2XS(F)2Y 6/10 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 47 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XS(F)2Y 12/20 kV
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011473 011474 011320 011319 012543 011306 011307 011308 012544 011475 011476 011477 011838 012258 type 1X50/16 1X70/16 1X95/16 1X120/16 1X120/50 1X150/25 1X185/25 1X240/25 1X240/50 1X300/25 1X400/35 1X500/35 1X630/35 1X800/35 VDE 0276-620 12 kV 20 kV 24 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Building Wires

stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA colour bk bk bk bk rd bk bk bk rd bk bk bk bk bk CU kg/km 182 182 182 182 560 283 283 283 560 283 394 394 394 394 AL kg/km 145 203 276 348 348 435 537 696 435 870 1160 1450 1827 2320 DA mm 29 31 32 34 35 35 37 40 40 42 45 48 52 59,5 weight ca. kg/km 1050 950 1300 1450 1718 1650 1800 2050 2237 2300 2800 3200 3268 3973 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 48 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011534 011478 011535 011536 011537 011538 011539 011540 011541 011542 012223 type 1X50/16 1X70/16 1X95/16 1X120/16 1X150/25 1X185/25 1X240/25 1X300/25 1X400/35 1X500/35 1X630/35 colour bk bk bk bk bk bk bk bk bk bk bk CU kg/km 182 182 182 182 283 283 283 283 394 394 394 AL kg/km 145 203 276 348 435 537 696 870 1160 1450 1827 VDE 0276-620 18 kV 30 kV 36 kV aluminium stranded, class 2 XLPE DIX8 90 C yes polyethylene DMP2 no -20 - +70 C +70 C 15 x DA DA mm 34 36 37 39 40 42 44 47 50 53 59,9 weight ca. kg/km 1350 1450 1600 1750 1950 2150 2400 2700 3200 3650 3738

Medium voltage cable <<<


Power cables 1 up to 30 kV

NA2XS(F)2Y 18/30 kV

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 49 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Medium voltage cable


Power cables 1 up to 30 kV

NA2XS(FL)2Y 6/10 kV
standard nominal voltage UO nominal voltage U conductor material conductor construction insulation bending radius, fixed installation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bonded sheath flame retardant p/n 012462 012461 012545 012463 type 01X150/25 01X240/25 01X240/50 01X400/35 VDE 0276-620 6 kV 10 kV aluminium

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Building Wires

stranded, class 2 XLPE DIX8

15 x DA polyethylene DMP2 90 C +70 C -20 - +70 C yes no colour bk bk bk bk CU kg/km 283 283 560 394 AL kg/km 435 696 696 1160 DA mm 31 35 36 41 weight ca. kg/km 1156 1850 1740 2466 packaging dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

NA2XS(FL)2Y 12/20 kV
standard conductor material conductor construction insulation VDE 0276-620 aluminium stranded, class 2 XLPE DIX8 Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Cable with circuit integrity

LAN cables

bending radius, fixed installation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bonded sheath flame retardant p/n 012533 012568 011551 011783 012569 011848 012512 011852 type 01X70/16 01X70/25 01X95/16 01X120/16 01X120/50 01X240/25 01X150/25 01X400/35

15 x DA polyethylene DMP2 90 C +70 C -20 - +70 C yes no colour bk bk bk bk bk bk bk bk CU kg/km 182 283 182 182 560 283 283 394 AL kg/km 203 203 276 348 348 696 435 1160 DA mm 36 32,2 32 34 34 40 35 45 weight ca. kg/km 1000 1395 1150 1250 1540 1850 1650 2466 packaging dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

> 50 <

>>> www.faberkabel.de <<<

Power cables 1 up to 30 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable. standard conductor material conductor construction insulation bending radius, fixed installation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bonded sheath flame retardant p/n 012509 012657 012510 012658 012511 type 01X95/16 01X120/16 01X240/25 01X300/25 01X400/35 colour bk bk bk bk bk CU kg/km 182 182 283 283 394 AL kg/km 276 348 696 870 1160 VDE 0276-620 aluminium stranded, class 2 XLPE DIX8

Medium voltage cable <<<


Power cables 1 up to 30 kV

NA2XS(FL)2Y 18/30 kV

15 x DA polyethylene DMP2 90 C +70 C -20 - +70 C yes no DA mm 37 39 44 47 50 weight ca. kg/km 1150 1750 1850 2700 2466 packaging dr. dr. dr. dr. dr.

N2XSEY 6/10 kV
Application: For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables must be protected against direct sun irradiation. standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction insulation sheathing material flame retardant maximum temperature at conductor temperature, moved/ during installation max. operating temperature, fixed bending radius, fixed installation p/n 011310 011311 011312 011313 011314 011315 011316 011497 type 3X35/16 3X50/16 3X70/16 3X95/16 3X120/16 3X150/25 3X185/25 3X240/25 colour rd rd rd rd rd rd rd rd CU kg/km 1209 1671 2247 2994 3714 4638 5646 7272 DA mm 49 52 55 60 64 67 71 77 VDE 0276-620 6 kV 10 kV 12 kV 21 kV bare copper

XLPE DIX8 PVC DMV6 VDE 0482-332-1-2/IEC 60332-1 90 C -5 - +70 C +70 C 15 x DA weight ca. kg/km 3300 3900 4700 5850 6800 7950 9300 11550 packaging dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 51 <

Technical Appendix

Other

Conductor ropes

LAN cables

stranded, class 2

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Overhead line


Power cables 1 up to 30 kV

NFA2X
standard nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation max. operating temperature, fixed p/n 090072 090026 090091 090092 090025 090095 090073 090028 090075 011699 090023 090029 090024 090030 090078 090105 090098 090080 090096 090097 type 01X16 01X25 01X35 01X50 01X70 01X95 02X16 02X25 04X16 04X25 04X35 04X50 04X70 04X95 04X70+25 04X70+35 04X70+2X25 04X70+2X35 04X35+35 04X95+25 VDE 0274 (Z) 0,6 kV 1 kV 1,2 kV aluminium

Power cables 1 up to 30 kV
Application: For overhead distribution, mainly for public distribution with a highest voltage not above 1,2 kV.

Building Wires

stranded, class 2 XLPE -20 - 80 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk AL kg/km 46,4 72 102 145 203 276 93 144 186 290 406 580 812 1102 885 914 956 1016 508 1175 DA mm 8 10 11 12,5 14 15,4 15,6 18,8 22 25 28 32 37 36 36,2 40,1 weight ca. kg/km 74 105 133 180 258 334 147 200 285 427 620 785 1032 1332 1105 1150 1232 1254 750 1405 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 52 <

>>> www.faberkabel.de <<<

customeroriented

>>> www.faberkabel.de <<< Sheathed Building Wire NYM-J NYM-O (N)YM(St)-J NHXMH-J NHXMH-O (N)HXMH(St)-J NYIF-J 54 54 55 56 56 57 58 58
LAN cables Cable with circuit integrity Control and Electronic Cable Telecommunication Cables and Cords Flexible Cables

Content
Building Wires <<<

> 53 <

Technical Appendix

Other

Conductor ropes

Building Wires

Power cables 1 up to 30 kV

>>> Sheathed Building Wire


Power cables 1 up to 30 kV

NYM-J
standard core identification nominal voltage U nominal voltage UO test voltage protective conductor conductor material insulation maximum temperature at conductor sheathing material max. operating temperature, fixed temperature, moved/ during installation flame retardant p/n 020003 020004 020005 020001 020002 020150 020006 020007 020302 020009 020166 020305 020010 020044 020050 020011 020012 020303 020015 020169 020018 020019 020013 020014 020016 020017 020020 020021 020304 020024 020170 020026 020027 020022 020023 020025 020295 020028 020029 020300 020030 020045 020294 020307 020301 type 01X2,5 01X4 01X6 01X10 01X16 01X25 03X1,5 03X1,5/TR 03X1,5/KTR 03X2,5 03X2,5/TR 03X2,5/KTR 03X4 03X6 03X10 04X1,5 04X1,5/TR 04X1,5/KTR 04X2,5 04X2,5/TR 04X4 04X6 04X10 04X16 04X25 04X35 05X1,5 05X1,5/TR 05X1,5/KTR 05X2,5 05X2,5/TR 05X4 05X6 05X10 05X16 05X25 05X35 07X1,5 07X2,5 08X1,5 10X1,5 12X1,5 12X2,5 16X1,5 61X1,5 VDE 0250-204 colours acc. VDE 0293 (HD308) 500 V 300 V 2 kV yes bare copper PVC TI1 70 C PVC TM1 70 C 5 - 70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 24 38 58 96 154 240 43 43 43 72 72 72 115 173 288 58 58 58 96 96 154 230 384 614 960 1344 72 72 72 120 120 192 288 480 768 1200 1680 101 168 115 144 173 288 230 878

Building Wires
Application: For installation in, on or under plaster, in dry, damp or wet rooms as well as in walls and concrete. Also suitable for installation outdoors if protected against direct sun irradiation.

Flexible Cables

Building Wires

Technical Appendix

DA mm 5,8 6,4 6,8 8 9,1 12,3 8,2 8,2 8,2 9,4 9,4 9,4 10,8 12,2 14,7 8,8 8,8 8,8 10,2 10,2 12,1 13,3 16,1 19 23,4 25,7 9,5 9,5 9,5 11 11 13,2 14,5 17,7 21,2 25,7 33,5 10,5 12,6 12,5 14,3 14,4 15,4 15,8 25,7

weight ca. kg/km 70 80 105 155 230 330 135 135 135 190 190 190 265 315 465 160 160 160 230 230 330 460 690 1090 1640 2090 190 190 190 270 270 410 540 850 1350 1990 2160 235 350 237 330 400 660 457 1436

Telecommunication Cables and Cords

packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 c. 100, c. 50 dr. dr. c. 100, c. 50, c. 250 dr. dr. dr., c. 100, c. 50 dr. dr. c. 100, c. 50 dr. dr. c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 50 c. 100, c. 50 dr. dr. c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr.

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 54 <

>>> www.faberkabel.de <<<

Building Wires
Application: For installation in, on or under plaster, in dry, damp or wet rooms as well as in walls and concrete. Also suitable for installation outdoors if protected against direct sun irradiation. standard core identification nominal voltage U nominal voltage UO test voltage protective conductor conductor material insulation maximum temperature at conductor sheathing material max. operating temperature, fixed temperature, moved/ during installation flame retardant p/n 020031 020043 020178 020177 020032 020033 020034 020167 020035 020168 020036 020174 020037 020175 020046 020038 020039 020040 020041 020042 020326 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 02X1,5 02X1,5/TR 02X2,5 02X2,5/TR 03X1,5 03X1,5/TR 04X1,5 04X1,5/TR 04X6 04X10 04X16 04X25 04X35 07X1,5 12X1,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 14,4 24 38 58 96 154 29 29 48 48 43 43 58 58 230 384 614 960 1344 101 173 DA mm 5,2 5,8 6,4 6,8 8 9,1 7,8 7,8 8,9 8,9 8,2 8,2 8,8 8,8 13,3 16,1 19 23,4 25,7 10,5 14,4 VDE 0250-204 500 V 300 V no bare copper PVC TI1 70 C PVC TM1 70 C 5 - 70 C 2 kV

Sheathed Building Wire <<<


Power cables 1 up to 30 kV

NYM-O
colours acc. VDE 0293 (HD308)

VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 45 70 80 105 155 230 115 115 157 157 135 135 160 160 460 690 1090 1640 2090 235 400 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50 dr. c. 100, c. 50 dr. c. 100, c. 50 dr. c. 100, c. 50 dr. dr., c. 50 dr., c. 50 dr., c. 100, c. 50 dr., c. 50 dr. dr., c. 100, c. 50 c. 100, c. 50, dr.

>>> www.faberkabel.de <<<

> 55 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Sheathed Building Wire


Power cables 1 up to 30 kV

(N)YM(St)-J
core identification nominal voltage U nominal voltage UO test voltage protective conductor conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n type 03X1,5 03X2,5 03X4 03X6 04X1,5 04X2,5 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 07X1,5 colours acc. VDE 0293 (HD308) 500 V 300 V 2 kV yes bare copper PVC TI1 70 C PVC TM1 VDE 0482-332-1-2/IEC 60332-1 70 C 5 - 70 C colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 51 80 123 180 65 104 80 128 200 296 488 776 1208 108

Building Wires
Application: This cable has a static foil screen for limiting its irradiated electromagnetic field in areas with high requirements to EMC as computer rooms, hospitals as well as in living rooms with high sensitivity to electrical and/or magnetical fields. For installation on and under plaster in dry and wet rooms, as well as inside of walls or in concrete. Also for outdoor use, if the cable is protected against direct sun irradiation.

Flexible Cables

Building Wires

020308 020312 020315 020317 020309 020313 020310 020314 020316 020318 020319 020320 020321 020311

Control and Electronic Cable

DA mm 9 11 11,5 15 11 11,5 11,5 12 13,5 15,5 18 26 11,9

weight ca. kg/km 154 203 290 379 184 256 208 284 444 567 863 1347 2023 248

packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr. dr. dr. dr., c. 50

Cable with circuit integrity

Telecommunication Cables and Cords

NHXMH-J
standard core identification VDE 0250 T. 214 colours acc. VDE 0293 (HD308) 300 V 500 V 2 kV yes bare copper XLPE 2XI1 70 C FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 70 C colour gy gy gy gy gy gy gy gy gy gy CU kg/km 15 24 39 58 96 154 240 43 72 115 DA mm 5,2 5,6 7 7,4 7,8 9,6 12 8,6 9,5 10,7 weight ca. kg/km 75 85 135 150 200 295 350 130 165 235 packaging dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100 dr. Application: Low-smoke zero-halogen flame retardant building wire for installation on and under plaster, in cable ducts and conduits. For indoor use only.

LAN cables

nominal voltage UO nominal voltage U test voltage protective conductor conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed

Conductor ropes

Other

p/n 020278 020279 020232 020280 020281 020233 020282 020185 020188 020206

type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 03X1,5 03X2,5 03X4

Technical Appendix

> 56 <

>>> www.faberkabel.de <<<

Building Wires
p/n 020207 020208 020192 020209 020187 020189 020210 020190 020191 020211 020214 020195 020179 020196 020212 020194 020277 020197 020213 020229 020230 020231 020296 type 03X6 03X10 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 07X1,5 07X2,5 10X1,5 12X1,5 24X1,5 24X2,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 173 288 58 96 154 230 384 614 960 1344 72 120 192 288 480 768 1200 101 168 144 173 346 576 DA mm 12,3 14,8 9,2 10,2 12,2 13,2 15,8 20 24,5 27,5 9,8 10,7 13,2 14,8 17,4 22 28 10,2 12,2 14,5 16,5 20 23 weight ca. kg/km 320 480 150 200 300 395 595 935 1420 1910 175 235 350 480 710 1140 1900 210 300 280 320 570 787

Sheathed Building Wire <<<


Power cables 1 up to 30 kV

NHXMH-J
packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

NHXMH-O
Application: Low-smoke zero-halogen flame retardant building wire for installation on and under plaster, in cable ducts and conduits. For indoor use only. standard core identification nominal voltage UO nominal voltage U test voltage protective conductor conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n 020198 020199 020200 020201 020202 020203 020204 020205 020234 020235 020236 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 02X1,5 02X2,5 04X10 04X16 04X25 colour gy gy gy gy gy gy gy gy gy gy gy CU kg/km 15 24 39 58 96 154 29 48 384 614 960 DA mm 5,2 5,6 7,1 7,4 7,8 8,8 8,2 9 15,7 19,5 23,8 VDE 0250 T. 214 colours acc. VDE 0293 (HD308) 300 V 500 V 2 kV no bare copper XLPE 2XI1

FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 70 C weight ca. kg/km 92 110 135 160 215 295 110 130 615 935 1420 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 57 <

Technical Appendix

Other

Conductor ropes

LAN cables

70 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Sheathed Building Wire


Power cables 1 up to 30 kV

(N)HXMH(St)-J
core identification nominal voltage UO nominal voltage U test voltage conductor material maximum temperature at conductor insulation sheathing material flame retardant colours acc. VDE 0293 (HD308) 300 V 500 V 2 kV bare copper 70 C XLPE 2XI1 FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 colour gy gy gy gy gy gy gy CU kg/km 48 77 63 77 125 206 107

Building Wires
Application: Flame retardant building wire, for installation on and under plaster in dry and wet rooms, as well as in concrete. The cable is screened to limit the the propagation of electromagnetic field of the conductors. It is designed for application in EMC-sensible environments as hospitals, data processing facilities, laboratories but also in living rooms.

Flexible Cables

Building Wires

p/n 020283 020284 020285 020286 020287 020297 020306

type 03X1,5/1,5 03X2,5/1,5 04X1,5/1,5 05X1,5/1,5 05X2,5/1,5 05X4/1,5 07X1,5/1,5

Control and Electronic Cable

Telecommunication Cables and Cords

DA mm 9,5 9,8 9,6 10,3 11,3 15,1 12,1

weight ca. kg/km 168 209 192 220 282 393 310

packaging dr. dr. dr. dr. dr. dr. dr.

NYIF-J
standard nominal voltage UO nominal voltage U test voltage core identification protective conductor conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed VDE 0250-201 230 V 400 V 2 kV colours acc. VDE 0293 (HD308) yes bare copper PVC TI1 70 C cross-linked rubber blend VDE 0482-332-1-2/IEC 60332-1 70 C 5 - 60 C colour NT NT NT NT NT CU kg/km 43 58 72 72 120 wxh ca. mm 19 x 4,4 26 x 4,4 33 x 4,4 21,5 x 5,2 37 x 5,2 weight ca. kg/km 115 160 205 160 260 packaging c. 50 c. 50 c. 50 c. 100, c. 50 c. 50 Application: For fixed installation in dry zones, on and under plaster. Whitout plaster sheet in cavities of ceilings and walls of not combustible building materials.

LAN cables

Cable with circuit integrity

Conductor ropes

temperature, moved/ during installation p/n 020289 020292 020288 020291 020290 type 03X1,5 04X1,5 05X1,5 03X2,5 05X2,5

Technical Appendix

Other

> 58 <

>>> www.faberkabel.de <<<

Flexible Cables <<<


Power cables 1 up to 30 kV

reliable

Content
PVC-insulated wires and cords H05V-K H05V-U H07V-K H07V-U H07V-R H03VV-F H05VV-F X03VH-H H03VVH2-F Rubber Insulated Cables H05RR-F Roller blind cable H07RN-F H07BN4-F H07ZZ-F H01N2-D NSSHu-J NSSHu-O NSHTu YSLTOE-J (Korbflex) Immersion pump cable (-J) Subersible pump cable (-O) H05RNH2-F NGFLGOEU NGFLCGOU L-STN FACAB SOLAR 125 FACAB SOLAR PV1-F FACAB SOLAR VE Trailing cables/British Standard Rubber insulated wires H05Z-K H07Z-K NSGAFu NSHXAF GGSG Silicone insulated wires and cords SiD SiF SiHF-J SiHF-O SiF/GL H05SJ-K SiHFCSi-J SiHFCSi-O SiHF/GLS-P H05SS-F FZLSi 2GTL 13,8/15,0 kV PUR-insulated cords H05BQ-F H07BQ-F X07BQ-F Special Versions Livz6YYw H05V2V2D3-F (NYPLYw) Li2GYw (SiHYw PV/P) NYL 60 60 61 61 63 64 65 66 67 67 68 68 68 69 71 71 72 73 74 75 76 77 77 78 78 79 80 81 82 83 84 85 85 86 87 88 89 90 90 90 92 93 93 94 94 95 96 97 98 98 99 99 99 100 101 101 101 102 102

>>> www.faberkabel.de <<<

> 59 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> PVC-insulated wires and cords


Power cables 1 up to 30 kV

H05V-K
standard conductor construction nominal voltage UO nominal voltage U conductor material insulation maximum temperature at conductor flame retardant max. operating temperature, fixed p/n 040221 040257 040219 040220 040253 040240 040217 040216 040218 040241 040254 040006 040001 040222 040223 040003 040007 040004 040005 040002 040191 040190 040702 040013 040010 040008 040224 040225 040014 040011 040012 040009 040188 040193 040411 040697 040701 040703 040727 040728 type 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X0,75 01X0,75 VDE 0281-3 fine stranded, class 5 300 V 500 V bare copper PVC TI2 70 C VDE 0482-332-1-2/IEC 60332-1 70 C colour bk bu lbu dbu wh vt ge/ye rd bn gy og bk bu lbu dbu ge/ye wh gy rd bn vt og dbu/wh bk ge/ye bu lbu dbu wh gy rd bn vt og gn bu/wh dbu/wh ye bu/wh rd/wh CU kg/km 4,8 4,8 4,8 4,8 4,8 4,8 4,8 4,8 4,8 4,8 4,8 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 7,2 7,2

Flexible Cables
Application: For internal wiring of switching boxes and other electrical appliances. For installation in closed conduits and tubes. Not for direct installation under plaster.

Flexible Cables

Building Wires

DA mm 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,7 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,8 2,8 2,7 2,7

weight ca. kg/km 10 10 10 10 10 10 10 10 10 10 10 12 12 12 12 12 12 12 12 12 12 12 12 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 12 12

packaging c. 100, barrel c. 100 c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel dr., c. 100, barrel c. 100 c. 100, barrel dr., c. 100, barrel c. 100, c. 50, barrel c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel c. 100, barrel c. 100, barrel c. 100 c. 100, barrel dr., c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, c. 50, barrel c. 100, barrel c. 100, barrel c. 100, barrel dr., c. 100 c. 100 c. 100 c. 100 c. 100 c. 100

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 60 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For internal wiring of switching boxes and other electrical appliances. For installation in closed conduits and tubes. Not for direct installation under plaster. standard conductor construction nominal voltage UO nominal voltage U conductor material insulation maximum temperature at conductor flame retardant max. operating temperature, fixed p/n 040020 040015 040748 040749 040021 040017 040016 040018 040019 040027 040024 040022 040750 040751 040025 040026 040028 040023 040258 type 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1 colour bk bu lbu dbu wh ge/ye bn gy rd bk ge/ye bu lbu dbu gy rd wh bn vt CU kg/km 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 7,2 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 9,6 DA mm 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3

PVC-insulated wires and cords <<<


Power cables 1 up to 30 kV

H05V-U
VDE 0281-3 solid, class 1 300 V bare copper PVC TI2 70 C VDE 0482-332-1-2/IEC 60332-1 70 C weight ca. kg/km 10 10 10 10 10 10 10 10 10 14 14 14 14 14 14 14 14 14 14 packaging c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100

H07V-K
Application: For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster. standard conductor construction nominal voltage UO nominal voltage U test voltage conductor material insulation maximum temperature at conductor flame retardant temperature, moved/ during installation p/n 040035 040031 040226 040030 040033 040036 040034 040037 040195 040194 040212 type 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 colour bk ge/ye lbu bn gy vt rd wh og TR dbu CU kg/km 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 DA mm 2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8 2,8 VDE 0281-3 fine stranded, class 5 450 V 750 V 2500 V PVC TI2 70 C VDE 0482-332-1-2/IEC 60332-1 5 - 70 C weight ca. kg/km 20 20 20 20 20 20 20 20 20 20 20 packaging c. 100, c. 50, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel bare copper

>>> www.faberkabel.de <<<

> 61 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

500 V

>>> PVC-insulated wires and cords


Power cables 1 up to 30 kV

H07V-K
p/n 040374 040029 040058 040054 040227 040052 040056 040196 040057 040059 040213 040051 040450 040451 040067 040066 040228 040065 040197 040251 040229 040256 040704 040074 040073 040230 040071 040198 040252 040231 040380 040663 040705 040042 040040 040232 040039 040041 040233 040049 040047 040234 040235 040046 040048 040349 040061 040060 040383 040199 040752 040753 040063 040062 040200 040754 040755 040387 040696 040069 040068 040075 040176 040076 040185 040043 type 01X1,5 01X1,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 VZ 01X2,5 VZ 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X6 01X6 01X6 01X6 01X6 01X6 01X6 01X6 01X6 01X6 01X10 01X10 01X10 01X10 01X10 01X10 01X16 01X16 01X16 01X16 01X16 01X16 01X16 01X25 01X25 01X25 01X25 01X25 01X25 01X35 01X35 01X35 01X35 01X35 01X35 01X35 01X50 01X50 01X70 01X70 01X95 01X95 01X120 colour ye bu bk ge/ye lbu bn gy vt rd wh dbu bu bn lbu bk ge/ye lbu bn rd gy dbu bu vt bk ge/ye lbu bn rd gy dbu wh og vt bk ge/ye lbu bn rd dbu bk ge/ye lbu dbu bn rd gy bk ge/ye bn bu lbu dbu bk ge/ye bu lbu dbu bn wh bk ge/ye bk ge/ye bk ge/ye bk CU kg/km 14,4 14,4 24 24 24 24 24 24 24 24 24 24 24 24 38 38 38 38 38 38 38 38 38,4 58 58 58 58 58 58 58 58 58 58 96 96 96 96 96 96 154 154 154 154 154 154 154 240 240 240 240 240 240 336 336 336 336 336 336 336 480 480 672 672 912 912 1152

Flexible Cables
DA mm 2,8 2,8 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,9 3,9 3,9 3,9 3,9 3,9 3,9 3,9 4,8 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,5 5,3 5,8 5,8 5,8 5,8 5,8 5,8 7 7 7 7 7 7 7 8,5 8,5 8,5 8,5 8,5 8,5 9,8 9,8 9,8 9,8 9,8 9,8 9,8 11,6 11,6 13,3 13,3 15,3 15,3 16,9 weight ca. kg/km 21 20 32 32 32 32 32 32 32 32 32 32 32 32 46 46 46 46 46 46 46 46 46 65 65 65 65 65 65 65 65 65 65 115 115 115 115 115 115 170 170 170 170 170 170 170 260 260 260 260 260 260 360 360 360 360 360 360 360 515 515 710 710 940 940 1180 packaging c. 100 c. 100 dr., c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100 c. 100, barrel dr., c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100 c. 100, dr. c. 100, barrel c. 100, c. 50, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100, barrel c. 100 c. 100 c. 100, dr. c. 100 c. 100, dr. c. 100 c. 100 c. 100 c. 100 dr., c. 100, c. 50 dr., c. 100 c. 100 c. 100 c. 100, dr. c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 50 dr., c. 100 dr. dr. dr. dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr. dr. dr., c. 100 dr., c. 100 dr., c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 62 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 040186 040044 040700 040050 040351 040238 040342 type 01X120 01X150 01X150 01X185 01X185 01X240 01X240 colour ge/ye bk ge/ye bk ge/ye bk ge/ye CU kg/km 1152 1440 1440 1776 1776 2304 2304 DA mm 16,9 18,8 18,8 21 21 24 24

PVC-insulated wires and cords <<<


Power cables 1 up to 30 kV

H07V-K
weight ca. kg/km 1180 1600 1600 2100 2100 3015 3015 packaging dr. dr. dr. dr. dr. dr. dr.

H07V-U
Application: For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster. standard conductor construction nominal voltage UO nominal voltage U test voltage conductor material insulation maximum temperature at conductor flame retardant temperature, moved/ during installation p/n 040100 040096 040236 040095 040098 040101 040099 040102 040214 040118 040114 040237 040112 040116 040119 040117 040120 040215 040111 type 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 colour bk ge/ye lbu bn gy vt rd wh dbu bk ge/ye lbu bn gy vt rd wh dbu bu CU kg/km 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 24 24 24 24 24 24 24 24 24 24 DA mm 2,7 2,7 2,7 2,7 2,7 2,7 2,7 2,7 2,7 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 VDE 0281-3 solid, class 1 450 V 750 V 2500 V bare copper PVC TI2

VDE 0482-332-1-2/IEC 60332-1 5 - 70 C weight ca. kg/km 20 20 20 20 20 20 20 20 20 31 31 31 31 31 31 31 31 31 31 packaging c. 100, barrel c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 dr., c. 100 dr., c. 100 c. 100 dr., c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 dr., c. 100

>>> www.faberkabel.de <<<

> 63 <

Technical Appendix

Other

Conductor ropes

LAN cables

70 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> PVC-insulated wires and cords


Power cables 1 up to 30 kV

H07V-U
p/n 040124 040122 040761 040762 040121 040181 040123 040249 040128 040126 040177 040763 040764 040125 040107 040105 040103 040104 040765 040766 040429 type 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X6 01X6 01X6 01X6 01X6 01X6 01X10 01X10 01X10 01X10 01X10 01X10 01X16 colour bk ge/ye lbu dbu bu bn gy rd bk ge/ye bu lbu dbu bn bk ge/ye bu bn lbu dbu ge/ye CU kg/km 38 38 38 38 38 38 38 38 58 58 58 58 58 58 96 96 96 96 96 96 154

Flexible Cables
DA mm 3,8 3,8 3,8 3,8 3,8 3,8 3,8 3,8 4,3 4,3 4,3 4,3 4,3 4,3 5,5 5,5 5,5 5,5 5,5 5,5 6,4 weight ca. kg/km 46 46 46 46 46 46 46 46 65 65 65 65 65 65 110 110 110 110 110 110 170 packaging c. 100 c. 100, c. 50 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100, dr. c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 c. 100 dr., c. 100

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

H07V-R
standard conductor construction nominal voltage UO nominal voltage U test voltage conductor material insulation maximum temperature at conductor flame retardant temperature, moved/ during installation p/n 040082 040081 040205 040085 040084 040756 040757 040211 040087 040086 040239 040758 040759 040207 040089 040088 040208 040091 040090 type 01X16 01X16 01X16 01X25 01X25 01X25 01X25 01X25 01X35 01X35 01X35 01X35 01X35 01X35 01X50 01X50 01X50 01X70 01X70 VDE 0281-3 stranded, class 2 450 V 750 V 2500 V bare copper PVC TI2 70 C VDE 0482-332-1-2/IEC 60332-1 5 - 70 C colour bk ge/ye rd bk ge/ye lbu dbu rd bk ge/ye bu lbu dbu rd bk ge/ye rd bk ge/ye CU kg/km 154 154 154 240 240 240 240 240 336 336 336 336 336 336 480 480 480 672 672 DA mm 6,8 6,8 6,8 8,5 8,5 8,5 8,5 8,5 9,5 9,5 9,5 9,5 9,5 9,5 11,2 11,2 11,2 12,7 12,7 weight ca. kg/km 175 175 175 275 275 275 275 275 370 370 370 370 370 370 500 500 500 710 710 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr., c. 50 dr. dr. dr. Application: For laying in pipes on top of or under plaster and in closed installation ducts and for internal wiring of machinery, switchgear and distributor systems. The cable is not suitable for direct laying under plaster.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 64 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 040209 040093 040092 040210 040078 040077 040080 040079 040300 040594 type 01X70 01X95 01X95 01X95 01X120 01X120 01X150 01X150 01X185 01X300 colour rd bk ge/ye rd bk ge/ye bk ge/ye ge/ye ge/ye CU kg/km 672 912 912 912 1152 1152 1440 1440 1776 2880 DA mm 12,7 14,8 14,8 14,8 16,3 16,3 18,2 18,2 25,5

PVC-insulated wires and cords <<<


Power cables 1 up to 30 kV

H07V-R
weight ca. kg/km 710 970 970 970 1200 1200 1470 1470 1806 2929 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

H03VV-F
Application: For the connection of light electrical appliances (table and standing lamps, kitchen appliances, domestic vacuum cleaners, office appliances, radios etc.) at low mechanical stresses in households, kitchens and offices. Not for the connection of cooking and heating appliances or commercial electric tools, not for outdoor use, in agricultural or commercial businesses. standard core identification nominal voltage U nominal voltage UO protective conductor test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation VDE 0281-5 colours acc. VDE 0293 (HD308) 300 V 300 V yes 2 kV bare copper fine stranded, class 5 PVC TI2 60 C PVC TM2 VDE 0482-332-1-2/IEC 60332-1 +50 C 3 x DA

bending radius, moved 5 x DA application p/n 030004 030005 031047 030006 030007 031581 030009 type 02X0,75 02X0,75 02X0,75 03G0,75 03G0,75 04G0,75 04G0,75 colour bk wh bn bk wh bk wh CU kg/km 14,4 14,4 14,4 21,6 21,6 29 29 DA mm 5,3 5,3 5,3 5,5 5,5 6,1 6,1 weight ca. kg/km 46 46 46 55 55 69 69 packaging c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50

>>> www.faberkabel.de <<<

> 65 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> PVC-insulated wires and cords


Power cables 1 up to 30 kV

H05VV-F
standard core identification nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation VDE 0281-5 colours acc. VDE 0293 (HD308) 300 V 500 V 2 kV bare copper fine stranded, class 5 PVC TI2 60 C PVC TM2 VDE 0482-332-1-2/IEC 60332-1 +50 C 3 x DA

Flexible Cables
Application: For the connection of light electrical appliances (table and standing lamps, kitchen appliances, domestic vacuum cleaners, office appliances, radios etc.) at low mechanical stresses in households, kitchens and offices. Not for the connection of cooking and heating appliances or commercial electric tools, not for outdoor use, in agricultural or commercial businesses.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

bending radius, moved 5 x DA application p/n 031050 031610 030724 030012 030013 030014 030039 030015 030016 030017 031052 030019 030018 030743 030021 030020 030041 030605 031051 034506 030023 030022 031053 031054 031055 034677 030024 030025 030027 030026 031058 031057 031061 031060 030029 030028 031059 030031 030030 type 02X0,75 02X0,75 02X1 02X1 02X1,5 02X1,5 02X2,5 02X2,5 03G0,75 03G0,75 03G0,75 03G1 03G1 03G1 03G1,5 03G1,5 03G1,5 03G1,5 03G1,5 03G1,5 03G2,5 03G2,5 04G0,75 04G0,75 04G1 04G1 04G1,5 04G1,5 04G2,5 04G2,5 05G0,75 05G0,75 05G1 05G1 05G1,5 05G1,5 05G1,5 05G2,5 05G2,5 colour wh lbu bk wh bk wh bk wh bk wh gy wh bk bn wh bk bn og gy ye wh bk bk wh bk wh bk wh wh bk bk wh bk wh wh bk bn wh bk CU kg/km 14,4 14,4 19 19 29 29 48 48 21,6 21,6 21,6 29 29 29 43 43 43 43 43 43,2 72 72 29 29 38 38,4 58 58 96 96 36 36 48 48 72 72 72 120 120 DA mm 5,8 6,5 6,5 7,5 7,5 9 9 6,5 6,5 6,5 7 7 7 8,2 8,2 8,2 8,2 8,2 8,2 9,8 9,8 6,7 6,7 7,2 7,2 9,2 9,2 10,7 10,7 7,5 7,5 8 8 10,2 10,2 10,2 13 13 weight ca. kg/km 52 52 65 65 90 90 115 115 70 70 70 80 80 80 115 115 115 115 115 115 175 175 75 75 92 92 145 145 210 210 96 96 113 113 175 175 175 260 260 packaging c. 100, c. 50 dr., c. 100 c. 100, c. 50, dr. c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50 c. 100, c. 50, c. 200 c. 100, c. 50, c. 200 c. 100, c. 50 dr., c. 100, c. 50, c. 300 dr., c. 100, c. 50, c. 300 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100 dr., c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50 dr., c. 100, c. 50 c. 100, c. 50

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 66 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: Connecting cable for lightning electrical appliances, radio appliances, table lamps, watches etc. for light duty mechanical appliances in households, kitchen and office rooms, as far as this is permitted in the relevant appliances regulations. core identification nominal voltage UO nominal voltage U conductor material conductor construction insulation bending radius, fixed installation flame retardant sheathing material p/n 033520 033521 033522 type 02X0,75 02X0,75 02X0,75 colour bn bk wh CU kg/km 14,4 14,4 14,4 wxh ca. mm 3,1 x 6,3 3,1 x 6,3 3,1 x 6,3 300 V 300 V

PVC-insulated wires and cords <<<


Power cables 1 up to 30 kV

X03VH-H
colours acc. VDE 0293 (HD308)

bare copper

PVC 6 x DA VDE 0482-332-1-2/IEC 60332-1 PVC weight ca. kg/km 26 26 26 packaging dr., c. 100 c. 100 c. 100

H03VVH2-F
Application: For the connection of light electrical appliances (table and standing lamps, kitchen appliances, domestic vacuum cleaners, office appliances, radios etc.) at low mechanical stresses in households, kitchens and offices. Not for the connection of cooking and heating appliances or commercial electric tools, not for outdoor use, in agricultural or commercial businesses. standard core identification nominal voltage UO nominal voltage U conductor material conductor construction maximum temperature at conductor insulation sheathing material max. operating temperature, fixed p/n 031049 030011 type 02X0,75 02X0,75 colour bk wh CU kg/km 14,4 14,4 VDE 0281-5 colours acc. VDE 0293 (HD308) 300 V 300 V bare copper fine stranded, class 5 60 C

PVC +5 - +40 C

>>> www.faberkabel.de <<<

> 67 <

Technical Appendix

Other

Conductor ropes

LAN cables

weight packaging ca. kg/km 39 dr., c. 100, c. 50 39 c. 100, c. 50

Cable with circuit integrity

PVC

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

fine stranded class 6

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

H05RR-F
standard core identification nominal voltage UO nominal voltage U version conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n type 02X0,75 02X1 02X1,5 02X2,5 03G0,75 03G1 03G1,5 03G2,5 04G0,75 04G1 04G1,5 04G2,5 05G1,5 05G2,5 05G0,75 VDE 0282-4 colours acc. VDE 0293 (HD308) 300 V 500 V round bare copper fine stranded, class 5 rubber (EPR) EI4 60 C rubber (CR) EM2 VDE 0482-332-1-2/IEC 60332-1 -25 - 60 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 19 29 48 21,6 29 43 72 29 38 58 96 72 120 36

Flexible Cables
Application: For connection of electrical appliances (vacuum cleaners, kitchen appliances, soldering iron etc.) with low mechanical stress in households, kitchens, offices. Not for permanent outdoor use.

Flexible Cables

Building Wires

Cable with circuit integrity

050019 050020 050021 050022 050023 050024 050025 050026 050027 050100 050028 050029 050030 050031 050897

DA mm 6,2 6,8 8,2 9,7 6,6 7,2 8,8 10,2 7,2 7,8 9,8 11,2 10,7 12,5 9,9

weight ca. kg/km 60 70 100 150 80 90 130 180 90 110 170 230 190 280 113

packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Roller blind cable


core identification green-yellow, blue, brown, black bare copper fine stranded, class 5 60 C -25 - +60 C -25 - +60 C yes conductor material conductor construction maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation for outdoor use Application: For the fixed and flexible connection of electrical appliances at low mechanical stresses in dry, damp and wet areas and outdoors. Thanks to the wire designation and the UV-resistant outer sheath, the cables are particularly suitable for the connection of roller blind and Venetian blind drives.

Conductor ropes

LAN cables

bending radius, moved 15 x DA application bending radius, fixed installation 7,5 x DA VDE 0482-332-1-2/IEC 60332-1 colour bk bk bk og CU kg/km 29 29 29 29 DA mm 7,6 7,8 7,6 7,6 weight ca. kg/km 76 76 76 76 packaging dr., c. 100 dr. c. 100, dr. dr., c. 100, c. 50

Other

flame retardant p/n 050820 050938 050920 050322 type

Technical Appendix

S05RR-F 4G0,75 S05ZZ-F 4G0,75 A05RN-F 4G0,75 H05BQ-F 4G0,75

> 68 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For use at medium mechanical stress in dry, wet and damp locations, as well as in free air. Also for fixed installation on plaster or machines. The cable is resistant to oil, uv-radiation and ozon. standard nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 050214 050358 050233 050205 050033 050036 050037 050038 050039 050041 050042 050034 050035 050111 050113 050195 050408 050045 050046 050048 050114 050115 050101 050102 050240 050309 050185 050375 050050 050054 050057 050059 050051 050053 050055 050056 050058 050060 050061 050052 050187 050196 050837 050062 050065 050067 050068 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 03G1 03G1,5 03G2,5 03G4 03G6 03G10 03G16 03G25 03G35 03G50 04G1 04G1,5 04G2,5 04G4 04G6 04G10 04G16 04G25 04G35 04G50 04G70 04G95 04G120 04G150 04G185 04G240 05G1,5 05G2,5 05G4 05G6 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 24 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 29 43 72 115 173 288 461 720 1008 1440 38 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 7104 9216 72 120 192 288 DA mm 5,9 6,6 7,4 8,1 9,7 11 12,9 14,6 16,8 18,9 21,1 23,1 25,6 27,9 31 34,1 38,5 8,4 9,4 11,1 12,9 14,3 19,3 22,1 27 29,6 36 9,5 10,4 12,3 14,2 15,9 21,3 24,2 29,3 33 38,2 43,2 49 53,6 58,7 65 74 11,5 13,5 15,9 17,9 VDE 0282-4 450 V 750 V 2,5 kV bare copper

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

H07RN-F

fine stranded, class 5 rubber (EPR) EI4 80 C rubber (CR) EM5 VDE 0482-332-1-2/IEC 60332-1 -25 - +80 C -25 - +80 C weight ca. kg/km 50 80 100 130 220 280 400 520 720 940 1220 1510 1900 2300 2900 3600 4800 125 155 235 310 400 810 1000 1250 1850 3790 129 190 280 380 510 940 1250 1850 2310 3160 4250 5590 6790 8230 9700 13120 230 340 470 630 packaging dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50

>>> www.faberkabel.de <<<

> 69 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

colours acc. VDE 0293 (HD308)

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

H07RN-F
p/n 050063 050064 050066 050160 050217 050319 050352 050858 050216 050219 050215 050204 050218 050220 050242 050243 050202 050750 050861 050862 050651 050652 050170 050043 050044 050228 050229 050880 050881 050882 050883 050884 050885 050886 050887 050888 050889 050890 type 05G10 05G16 05G25 05G35 05G50 05G70 05G95 05G120 07G1,5 07G2,5 12G1,5 12G2,5 18G2,5 19G1,5 19G2,5 24G1,5 24G2,5 25G1,5 27G1,5 27G2,5 37G1,5 37G2,5 02X1 02X1,5 02X2,5 02X4 02X6 03X1 03X1,5 03X2,5 03X6 03X10 03X16 03X25 03X35 04X10 04X16 04X25 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 480 768 1200 1680 2400 3360 4560 5760 101 168 175 288 432 274 456 346 576 360 390 648 533 888 19 29 48 77 115 29 43 72 173 288 461 720 1008 384 614,4 960

Flexible Cables
DA mm 22,3 26,9 32,5 38 44,5 47 58 61 14,5 17 18,3 19 26 23,5 26,6 25,5 31,5 26 weight ca. kg/km 1150 1540 2200 2700 3950 4893 6600 8051 370 520 450 750 1032 800 1068 1000 1380 889 973 1365 1780 1940 100 130 195 280 400 90 155 235 495 730 1020 1250 1733 940 1250 1850 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

28 34 7,8 8,7 10,4 12 13,3 8,4 9,4 11,1 14,3 19,3 22,1 27 29,6 21,3 24,2 29,3

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 70 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For installation in dry and wet rooms as well as in open air at medium mechanical stress. For fixed and flexible connection of electrical tools and aplliances. Also suitable for application in wind power generators at medium stress. standard core identification protective conductor nominal voltage UO nominal voltage U nominal voltage (DC) conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed p/n 050898 050835 050906 050817 050818 050763 050907 050902 050819 050911 type 01X95 01X120 01X150 01X185 01X240 01X300 01X400 04G35 05G25 05G35 colour bk bk bk bk bk bk bk bk bk bk CU kg/km 912 1152 1440 1776 2304 2880 3840 1344 1200 1680 DA mm 24,5 26,5 29,1 35 35,1 38,5 43,1 33 37,1 41,1 VDE 0282-12 yes 450 V 1238 V bare copper 750 V

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

H07BN4-F
colours acc. VDE 0293 (HD308)

fine stranded, class 5 rubber EI7 90 C rubber EM7 VDE 0482-332-1-2/IEC 60332-1 yes -50 - +75 C weight ca. kg/km 1160 1430 1740 2160 2730 3480 4510 2310 2070 2715 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

H07ZZ-F
Application: These cable are used for installation inside of buildings and the temporary application in free air. Particularly designed for applications, where in the case of fire only small quantities of smoke and corrosive gases are allowed. standard core identification nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant temperature, moved/ during installation p/n 050673 050674 050675 050680 050681 050682 050683 050698 050699 type 02X1 02X1,5 02X2,5 02X25 03G1 03G1,5 03G2,5 04G1 04G1,5 colour bk bk bk bk bk bk bk bk bk CU kg/km 19 29 48 480 29 43 72 38 58 DA mm 9,2 10,2 12,2 29,2 10,1 11,9 14 11,1 12,9 VDE 0282-13 colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers 450 V 750 V bare copper fine stranded, class 5 rubber EI8 90 C rubber (EPR) EM8 VDE 0482-266-2-4/IEC 603323-24 50 C weight ca. kg/km 95 119 172 1154 115 144 211 141 176 packaging dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr.

>>> www.faberkabel.de <<<

> 71 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

H07ZZ-F
p/n 050700 050701 050702 050703 050704 050705 050706 050707 050708 050709 050710 050711 050712 050713 050715 050716 050717 050718 050719 050720 050721 050722 051002 050726 050727 050728 050729 050865 050731 050732 050734 050735 050863 050864 type 04G2,5 04G4 04G6 04G10 04G16 04G25 04G35 04G50 04G70 04G95 04G120 04G150 04G185 04G240 05G1 05G1,5 05G2,5 05G4 05G6 05G10 05G16 05G25 05G35 07G1,5 07G2,5 12G1,5 12G2,5 14G2,5 18G1,5 18G2,5 24G1,5 24G2,5 37G1,5 52G1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 7104 9216 48 72 120 192 288 480 768 1200 1680 101 168 173 288 336 259 432 346 576 533 749

Flexible Cables
DA mm 15,3 17,7 19,8 26,5 30,1 36,6 41,1 47,5 53,8 60,9 65,8 72,7 80,1 86,4 12,2 14,2 16,9 19,8 22,1 29,1 33,3 38,4 19,1 21,5 22,4 26,2 25 26,3 29,3 30,7 34,6 36,2 43,1 weight ca. kg/km 235 365 501 872 1194 1822 2307 3253 4130 5720 6965 8644 10598 12100 170 214 316 448 607 1075 1480 2255 2700 303 448 496 724 860 702 1045 935 1325 1317 1766 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

H01N2-D cables with normal flexibility


LAN cables
standard nominal voltage UO nominal voltage U protective conductor test voltage conductor material sheathing material flame retardant max. operating temperature, fixed maximum temperature at conductor oil resistant acc. to EN 60811-2-1 p/n 060008 060009 060010 060011 060012 060013 060014 type 01X16 01X25 01X35 01X50 01X70 01X95 01X120 VDE 0282-6 100 V 100 V no 1 kV bare copper rubber (CR) EM5 VDE 0482-332-1-2/IEC 60332-1 -20 - 85 C 85 C yes colour bk bk bk bk bk bk bk CU kg/km 154 240 336 480 672 912 1152 DA mm 9,2 10,5 12,1 13,5 16,2 18,5 20,1 weight ca. kg/km 220 300 410 560 770 1050 1290 packaging dr., c. 50 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr. dr. Application: In dry, damp and wet rooms as welding cable for machine or hand operation.

Technical Appendix

Other

Conductor ropes

> 72 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 060016 060018 060029 type 01X150 01X185 01X240 colour bk bk bk CU kg/km 1440 1776 2304

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

H01N2-D cables with normal flexibility


DA mm 22,5 24,4 29,5 weight ca. kg/km 1590 1916 2540 packaging dr. dr. dr.

NSSHu-J
Application: At high mechanical stresses for the connection of heavy-duty underground mining, industrial and construction equipment, in dry and damp areas, and outdoors. The cable is largely flame-resistant and oil-proof. standard protective conductor core identification nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material oil resistant acc. to EN 60811-2-1 flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 050128 050129 050130 050140 050141 050212 050891 050131 050132 050133 050134 050135 type 03X1,5 03X2,5 03X4 03X70/35 03X95/50 03X120/70 03X150/70 04X1,5 04X2,5 04X4 04X6 04X10 colour ye ye ye ye ye ye ye ye ye ye ye ye CU kg/km 43 72 115 2352 3216 4128 4992 58 96 154 230 384 DA mm 12,5 13,2 16,2 44,6 53,1 54 73,1 12,6 15,9 17,5 18,8 23 VDE 0250 T. 812 yes colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 3 kV tinned copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free 90 C rubber (CR) 5GM5 yes VDE 0482-332-1-2/IEC 60332-1 -40 - +80 C -20 - +80 C weight ca. kg/km 200 260 380 4460 5910 7300 7119 230 350 450 560 860 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 73 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

NSSHu-J
p/n 050136 050137 050138 050139 050239 050234 050235 050236 050468 050142 050143 050144 050145 050146 050147 050148 050237 050149 050150 050151 050764 050152 050153 type 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 05X35 07X1,5 07X2,5 10X1,5 11X1,5 12X2,5 18X2,5 colour ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye ye CU kg/km 614 960 1344 1920 2688 3648 4608 5760 7104 72 120 192 288 480 768 1200 1680 101 168 144 158 288 432

Flexible Cables
DA mm 27,3 34,5 36,4 41,5 46,5 56,8 65,5 73,2 76,2 15,1 17,2 19,4 21,4 23,5 30,1 35,5 44,1 16,9 19,5 20,5 22,1 21,6 27,8 weight ca. kg/km 1350 2010 2590 3660 4605 6400 7705 8200 10604 255 385 560 670 1000 1570 2340 3400 410 500 545 600 770 1160 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

NSSHu-O
standard protective conductor core identification test voltage nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor sheathing material oil resistant acc. to EN 60811-2-1 flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 050121 050359 050190 050122 050123 050124 050125 050410 050434 050422 type 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 VDE 0250 T. 812 no colours acc. VDE 0293 (HD308) 3 kV 0,6 kV 1 kV tinned copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free 90 C rubber (CR) 5GM5 yes VDE 0482-332-1-2/IEC 60332-1 -40 - +80 C -20 - +80 C colour ye ye ye ye ye ye ye ye ye ye CU kg/km 154 240 336 480 672 912 1152 1440 1776 2304 DA mm 11,4 13,1 14,5 19 20 22,2 24 27,1 30,2 34,2 weight ca. kg/km 260 400 500 680 900 1150 1440 1750 2180 2790 packaging dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. Application: At high mechanical stresses for the connection of heavy-duty underground mining, industrial and construction equipment, in dry and damp areas, and outdoors. The cable is largely flame-resistant and oil-proof.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 74 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 050557 050227 050738 type 01X300 02X1,5 02X2,5 colour ye ye ye CU kg/km 2880 29 48 DA mm 42,1 11,8 12,8 weight ca. kg/km 3460 190 210 dr. dr. dr.

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

NSSHu-O
packaging

NSHTu
Application: As connection and control cable in lifting devices, hoisting plants and transporting machines for heavy mechanical load, and as drum and drag cable or hawser in dry, damp or wet rooms and in wet industrial conditions. The cable can be reeled and is resistant to acids, lyes, and oils. The permissible reeling speed may be up to V = 2 m/s. standard core identification nominal voltage UO nominal voltage U test voltage protective conductor conductor material conductor construction insulation maximum temperature at conductor inner sheath sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 050523 050529 050536 050537 050538 050539 050540 050541 050542 050543 050544 050545 type 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 colour bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 58 96 154 230,4 384 615 960 1344 1920 2688 3648 4608 DA mm 14,4 17,2 18,8 20,2 24,4 27,9 34,9 37,5 44,2 48,6 55,4 62 VDE 0250 T. 602 colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 3 kV yes tinned copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free 90 C rubber GM1b rubber (CR) 5GM3 VDE 0482-332-1-2/IEC 60332-1 -40 - +80 C -20 - +80 C weight ca. kg/km 275 415 530 684 1017 1370 1985 2605 3593 4950 6490 8600 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 75 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

NSHTu
p/n 050766 050767 050524 050530 050548 050546 050547 050749 050313 050556 050525 050531 050526 050532 050312 050534 050527 050535 050740 type 04X150 04X185 05X1,5 05X2,5 05X4 05X6 05X10 05X16 07X1,5 07X2,5 12X1,5 12X2,5 18X1,5 18X2,5 24X1,5 24X2,5 30X1,5 30X2,5 50X2,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 5760 7104 72 120 192 288 480 768 101 168 173 288 260 432 346 576 432 720 1200

Flexible Cables
DA mm 67,6 73,2 15,4 18,2 20,1 22,7 26,3 30,1 18,8 20,8 25,1 28,2 25,2 29,2 29,4 34,3 32,9 38,5 47,7 weight ca. kg/km 9090 9730 317 464 630 790 1200 1700 414 575 607 904 743 1230 1024 1583 1327 1841 3050 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

YSLTOE-J (Korbflex)
core identification nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed p/n type 42X2,5 gn-ye + numbers 300 V 500 V 2 kV bare copper fine stranded, class 5 PVC TI2 polyurethan 11YM1 VDE 0482-332-1-2/IEC 60332-1 -20 - +70 C colour bk CU kg/km 1008 weight packaging ca. kg/km 3530 dr. Application: As feeder for load suspension devices for heavy mechanical load in vertically operated hoisting cages, indoors and outdooors. The cable is resistant to ozone, UV-rays and dampness.

LAN cables

Cable with circuit integrity

Technical Appendix

Other

Conductor ropes

050392

> 76 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: As connection cable for submersible electric motors (pumps) for the permanent use in potable water up to temperature of 70 C. The cable is chlor resistant (31C, 1,0 mg/l) and moreover for use in dry, damp and wet rooms with medium mechanical load. Test certificates of different national and international institutes are available on request. nominal voltage UO nominal voltage U test voltage core identification protective conductor version conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant p/n 050562 050501 050499 050502 050503 050549 050550 050504 050551 050753 050653 050754 050993 type 03X1,5 03X2,5 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 colour bu bu bu bu bu bu bu bu bu bu bu bu bu CU kg/km 43 72 58 96 154 230 384 614 960 1344 1920 2688 3648 DA mm 11,1 12,1 11,5 13,5 15,5 18,1 23,9 27,5 33,1 35,2 42,2 47,9 450 V 750 V 2,5 kV

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

Immersion pump cable (-J)

colours acc. VDE 0293 (HD308) round bare copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free 90 C rubber (EPR) GM1a VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 150 220 190 250 380 520 950 1400 1950 2700 3600 4900 5590 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Subersible pump cable (-O)


Application: As connection cable for submersible electric motors (pumps) for the permanent use in potable water up to temperature of 70 C. The cable is chlor resistant (31C, 1,0 mg/l) and moreover for use in dry, damp and wet rooms with medium mechanical load. Test certificates of different national and international institutes are available on request. nominal voltage UO nominal voltage U test voltage version conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant p/n 050498 050961 050903 050910 050624 050928 050929 type 01X1,5 01X25 01X50 01X70 01X95 01X185 01X240 colour bu bu bu bu bu bu bu CU kg/km 14,4 240 480 672 912 1776 2304 DA mm 6,4 14,2 18,5 21,1 23,4 31,1 34,5 450 V 750 V 2,5 kV round bare copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free 90 C rubber (EPR) GM1a VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 54 400 730 1000 1300 2300 2900 packaging dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 77 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

yes

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

H05RNH2-F
standard version core identification nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n type 02X1,5 VDE 0282-8 flat colours acc. VDE 0293 (HD308) 300 V 500 V bare copper fine stranded, class 5 rubber (EPR) EI4 60 C rubber (CR) EM2 VDE 0482-332-1-2/IEC 60332-1 -25 - 60 C colour gn CU kg/km 28,8

Flexible Cables
Application: Cable for dry and wet rooms as well as outdoor for temporary installation of fairy lights.

Flexible Cables

Building Wires

Telecommunication Cables and Cords

050411

wxh ca. mm 14 x 6

weight packaging ca. kg/km 145 dr., c. 100, c. 50

Control and Electronic Cable

NGFLGOEU
standard nominal voltage UO nominal voltage U test voltage core identification conductor material VDE 0250 T. 809 300 V 500 V 2000 V colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers bare copper fine stranded class 6, up from 35 sqmm class 5 rubber (EPR) 3GI3, halogen-free rubber (CR) 5GM3 90 C -40 - +80 C -35- +80 C 5 x DA VDE 0482-332-1-2/IEC 60332-1 Application: For the connection of mobile parts of machine tools, conveyor plants and major items of equipment, if the cable is exposed to bends in only one level; in dry, damp and wet areas as well as outdoors.

Cable with circuit integrity

LAN cables

conductor construction insulation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation flame retardant

Conductor ropes

bending radius, moved 10 x DA application

Other

p/n 050505 050506 050507 050508 050509 050374 050510 050555 050568

type 04X1,5 05X1,5 07X1,5 08X1,5 10X1,5 12X1,5 24X1,5 04X2,5 05X2,5

colour bk bk bk bk bk bk bk bk bk

Technical Appendix

CU kg/km 58 72 101 115 144 173 346 96 120

wxh ca. mm 17,5 x 6,2 21,5 x 6,2 29,1 x 6,2 31,5 x 6,2 39,9 x 6,5 47,1 x 6,5 54,9 x 6,5 21,1 x 12,5 27,1 x 7,5

weight ca. kg/km 200 240 360 370 460 620 1300 280 332

packaging dr. dr. dr. dr. dr. dr. dr. dr., c. 50 dr.

> 78 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 050372 050511 050569 050512 050570 050513 050571 050373 050514 050521 050522 050515 050768 050516 050572 050517 050573 050518 050574 050519 050575 050520 050576 type 07X2,5 08X2,5 10X2,5 12X2,5 24X2,5 04X4 05X4 07X4 04X6 05X6 07X6 04X10 05X10 04X16 05X16 04X25 05X25 04X35 07X35 04X50 04X70 04X95 04X120 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 168 192 240 288 576 154 192 269 230 288 403 384 480 614 768 960 1200 1344 2352 1920 2688 3648 4608 wxh ca. mm 34,9 x 7,5 39,1 x 7,5 47,9 x 8,1 56,1 x 8,1 70,9 x 16,2 26,1 x 9,1 32,1 x 9,1 41,9 x 9,1 29,1 x 9,5 35,1 x 9,5 42,1 x 9,5 33,1 x 11,1 44,1 x 11,1 37,8 x 12,9 49,8 x 12,9 49,5 x 15,1 59,8 x 16,1 54,9 x 17,1 88,2 x 17,1 62,8 x 18,9 71,2 x 22,1 79,8 x 24,8 85,8 x 27,2 weight ca. kg/km 520 550 680 800 1480 410 560 700 600 650 850 800 1135 1150 1450 1700 2200 2200 3820 3000 3910 5300 6400 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

NGFLGOEU
packaging

NGFLCGOU
Application: For the connection of mobile parts of machine tools, conveyor plants and major items of equipment, if the cable are exposed to bends in only one level. For installation in dry, damp and wet areas as well as outdoor. Due to the screening of each single core the cable has improved EMC performance. standard nominal voltage UO nominal voltage U test voltage core identification conductor construction conductor material insulation screen coverage sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation VDE 0250 T. 809 300 V 500 V 2000 V colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers fine stranded class 6, up from 35 sqmm class 5 rubber (EPR) 3GI3, halogen-free 80 % rubber (CR) 5GM3 90 C -40 - +80 C -35- +80 C 5 x DA

bending radius, moved 10 x DA application

p/n 050578 050426 050402 050387 050905 050489 050469 050839

type 04X1,5 08X1,5 12X1,5 04X2,5 12X2,5 04X4 04X6 04X10

colour bk bk bk bk bk bk bk bk

>>> www.faberkabel.de <<<

> 79 <

Technical Appendix

CU kg/km 99 228 342 163 500 241 353 495

wxh ca. mm 18,5 x 6,5 36,1 x 7,5 54,5 x 8,5 22,5 x 7,5 69,5 x 9,5 29,1 x 10,5 31,1 x 10,5 36,1 x 10,5

weight ca. kg/km 230 640 770 340 1061 505 600 855

packaging dr. dr. dr. dr. dr. dr. dr. dr.

Other

flame retardant

VDE 0482-332-1-2/IEC 60332-1

Conductor ropes

LAN cables

bare copper

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

NGFLCGOU
p/n 050840 050841 050842 050843 type 04X16 04X25 04X35 04X50 colour bk bk bk bk CU kg/km 687 1114 1482 2012

Flexible Cables
wxh ca. mm 41,5 x 13,5 47,1 x 15,1 55,1 x 17,1 66,1 x 20,5 weight ca. kg/km 1160 1640 2540 3030 packaging dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

L-STN
nominal voltage UO nominal voltage U test voltage protective conductor core identification conductor material 450 V 750 V 3 kV yes colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers bare copper fine stranded class 6 rubber (EPR) EI4 VDE 0482-332-1-2/IEC 60332-1 rubber 5GM2 -40 - +70 C -30 - +70 C Application: Highly flexible elevator cable with integrated textile strength members for heights up to 80 m. For application in conveyor plants and energy chain with more frequent, movement also obligation-led. For the application inside of buildings and outdoors.

Cable with circuit integrity

LAN cables

conductor construction insulation flame retardant sheathing material max. operating temperature, fixed

Conductor ropes

temperature, moved/ during installation

bending radius, moved 10 x DA application p/n 050625 050626 050627 050628 050629 050631 050632 050633 050634 050635 050636 050637 050638 type 03X1 07X1 12X1 18X1 24X1 54X1 03X1,5 04X1,5 05X1,5 07X1,5 09X1,5 12X1,5 18X1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 32 73 125 195 262 656 48 64 80 112 143 187 291 DA mm 8,9 13,5 19,5 20,1 22,5 32,2 9,5 11,5 11,9 13,5 16,5 20,9 22,1 weight ca. kg/km 110 204 389 471 650 1399 113 150 180 270 359 510 619 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

> 80 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 050639 050641 050642 050643 type 24X1,5 04X2,5 05X2,5 07X2,5 colour bk bk bk bk CU kg/km 376 106 138 193 DA mm 24,8 12,5 14,5 17,5 weight ca. kg/km 817 210 255 380 dr. dr. dr. dr.

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

L-STN
packaging

FACAB SOLAR 125


Application: Designed specially for application in solar generators. Thanks to cross-linked insulating and sheathing materials very good resistance against mechanical and environmental factors is achieved, as well as a very high electrical performance. At the same time the current rating is higher than in comparable rubber- or EPR-insulated cables. The cable is short-circuit-proof and resistant against UV-irradiation and ozon. Insulation and sheath may be separated easily. The GLX-version has an additional rodent protection (glass yarns). nominal voltage UO nominal voltage U nominal voltage (DC) test voltage conductor construction conductor material insulation sheathing material flame retardant maximum temperature at conductor max. operating temperature, fixed bending radius, fixed installation 600 V 1000 V 0,9/1,5 kV 5 kV fine stranded, class 5 copper, bare or tinned cross-linked polyolefin-copolymer cross-linked polyolefin-copolymer VDE 0482-332-1-2/IEC 60332-1 125 C -40 - +125 C 5 x DA

bending radius, moved 15 x DA application p/n 040723 040724 040745 040746 040747 040803 040804 040805 type 01X10 VZ 01X16 VZ 01X25 VZ 01X35 VZ 01X50 VZ 01X70 VZ 01X95 VZ 01X120 VZ colour bk bk bk bk bk bk bk bk CU kg/km 96 154 240 336 480 672 912 1152 DA mm 8,5 9,5 11,5 13,3 15,1 18,1 19,9 22,2 weight ca. kg/km 159 232 295 395 630 987 1276 1702 packaging c. 100, dr. c. 100, dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 81 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

FACAB SOLAR PV1-F


standard nominal voltage UO nominal voltage U nominal voltage (DC) test voltage conductor material conductor construction maximum temperature at conductor insulation sheathing material flame retardant 2 Pfg 1169 0,6 kV 1 kV 0,9/1,8 kV 6,5 kV tinned copper fine stranded, class 5 120 C cross-linked polyolefin-copolymer cross-linked polyolefin-copolymer VDE 0482-266-2-4/IEC 603323-24

Flexible Cables
Application: For free movable or fixed installation in photovoltaic installations according to EN 60364-7-712. Cable may be used indoor, outdoor, in explosion hazard areas in industry and agriculture. It is treated as short-circuit and earth-fault safe.

Flexible Cables

Building Wires

Telecommunication Cables and Cords

bending radius, moved 6 x DA application bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 040784 040725 040807 040808 040770 040726 040809 040810 040771 040785 040786 type 01X2,5 VZ 01X4 VZ 01X4 VZ 01X4 VZ 01X4 VZ V2 01X6 VZ 01X6 VZ 01X6 VZ 01X6 VZ V2 01X10 VZ 01X16 VZ 4 x DA -40 - +90 C -40 - +90 C colour bk bk bu rd bk bk bu rd bk bk bk CU kg/km 24 38,4 38,4 38,4 38,4 58 58 58 58 96 154 DA mm 4,6 4,9 4,9 4,9 5,6 5,5 5,5 5,5 6,1 6,7 7,7 weight ca. kg/km 52 71 71 71 71 102 102 102 102 159 232 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 82 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For free movable or fixed installation in photovoltaic installations according to EN 60364-7-712. Cable may be used indoor, outdoor, in explosion hazard areas in industry and agriculture. It is treated as short-circuit and earth-fault safe. nominal voltage UO nominal voltage U nominal voltage (DC) test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant 0,6 kV 1 kV 0,9/1,8 kV 6,5 kV tinned copper

Rubber Insulated Cables <<<


Power cables 1 up to 30 kV

FACAB SOLAR VE

fine stranded, class 5 cross-linked polyolefin-copolymer 120 C

VDE 0482-332-1-2/IEC 60332-1

bending radius, moved 6 x DA application bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 040788 040789 040790 040791 040792 040793 type 01X4 VZ 01X4 VZ 01X4 VZ 01X6 VZ 01X6 VZ 01X6 VZ colour bk bu rd bk bu rd CU kg/km 38,4 38,4 38,4 58 58 58 DA mm 4,7 4,7 4,7 5,3 5,3 5,3 4 x DA -40 - +90 C -40 - +90 C weight ca. kg/km 71 71 71 102 102 102 packaging dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 83 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

cross-linked polyolefin-copolymer

Building Wires

>>> Rubber Insulated Cables


Power cables 1 up to 30 kV

Trailing cables/British Standard


Trailing cables

Flexible Cables

Trailing cables according to VDE 0250 p. 605 are available in many different designs and under different brandings. Usually they are offered under the VDE type code as NTSCGEWU or N3GHSSYCY. Apllication fields are open and closed cast mining, tunelling, harbours or, in general, power supply of medium voltage operated moving equipement. The application defines, which of the numerous constructional options are used in a certain design: - conductor construction - design of protective conductor - different control conductors/cores - design of torsion protection - integration of ptical elements - color and material of outer sheath This listing is not complete and may be amended according to customers requirements. Beginning with 2010 Faber Kabel offers a basic selection of trailing cables NTSCGEWU. The cable is VDE-approved and covers range of basic applications for trailing cables.

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Cables according to British Standard

LAN cables

Cables and cords play a major role on the global market. The most characteristic feature, compared with cables to German standards, is the steel wire armour, allthough there are BS-cables without it. Special care has to be taken to the core identification. Since the colour code according to HD 308 has been introduced in Europe, there are BS-cables with "old" core identification (i.e. red, white or yellow, blue, black, green-yellow) as well as cable with harmonized core identification. Faber offers PVC and LSF sheathed low voltage cables according to BS 5467 and BS 6724, plus medium voltage cables according to BS 6622.

Technical Appendix

Other

Conductor ropes

> 84 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For installation in tubes and ducts on and under plaster, for the internal wiring of electrical appliances, switching and distribution tools, as well as in busses and railborn vehicles. standard nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation flame retardant max. operating temperature, fixed p/n 040287 040288 040290 040289 040321 040433 040320 040291 040292 040294 040293 040323 040322 040698 040295 040296 040298 040297 040434 040325 040324 type 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X1 01X1 01X1 01X1 01X1 01X1 01X1 colour bk ge/ye lbu bn dbu gy rd bk ge/ye lbu bn dbu rd og bk ge/ye lbu bn gy dbu rd CU kg/km 4,8 4,8 4,8 4,8 4,8 4,8 4,8 7,2 7,2 7,2 7,2 7,2 7,2 7,2 9,6 9,6 9,6 9,6 9,6 9,6 9,6 DA mm 1,9 1,9 1,9 1,9 1,9 1,9 1,9 2,2 2,2 2,2 2,2 2,2 2,2 2,2 2,5 2,5 2,5 2,5 2,5 2,5 2,5 VDE 0282-9 300 V 500 V 2,5 kV bare copper

Rubber insulated wires <<<


Power cables 1 up to 30 kV

H05Z-K

fine stranded, class 5 90 C polyolefin EI5, halogen-free, cross-linked VDE 0482-332-1-2/IEC 60332-1 70 C weight ca. kg/km 9 9 9 9 9 9 9 13 13 13 13 13 13 12 15 15 15 15 15 15 15 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 c. 100 dr., c. 100 dr., c. 100

>>> www.faberkabel.de <<<

> 85 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber insulated wires


Power cables 1 up to 30 kV

H07Z-K
standard nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation VDE 0282-9 450 V 750 V 2,5 kV bare copper fine stranded, class 5 90 C polyolefin EI5, halogen-free, cross-linked VDE 0482-332-1-2/IEC 60332-1 70 C colour bk ge/ye lbu bn dbu rd bk ge/ye lbu bn dbu rd bk ge/ye lbu bn dbu rd bk ge/ye lbu bn dbu rd bk ge/ye lbu dbu rd bk ge/ye lbu dbu rd bk ge/ye lbu dbu rd bk ge/ye bk ge/ye bk ge/ye bk ge/ye bk ge/ye bk CU kg/km 14,4 14,4 14,4 14,4 14,4 14,4 24 24 24 24 24 24 38 38 38 38 38 38 58 58 58 58 58 58 96 96 96 96 96 154 154 154 154 154 240 240 240 240 240 336 336 480 480 672 672 912 912 1152 1152 1440

Flexible Cables
Application: For installation in tubes and ducts on and under plaster, for the internal wiring of electrical appliances, switching and distribution tools, as well as in busses and railborn vehicles.

Building Wires

Flexible Cables

flame retardant max. operating temperature, fixed p/n 040264 040265 040267 040266 040327 040326 040268 040269 040271 040270 040329 040328 040272 040274 040276 040275 040331 040330 040277 040278 040280 040279 040333 040332 040281 040282 040767 040335 040334 040283 040284 040768 040337 040336 040285 040286 040769 040339 040338 040301 040311 040302 040312 040303 040313 040304 040314 040305 040315 040306 type 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X4 01X4 01X4 01X4 01X4 01X4 01X6 01X6 01X6 01X6 01X6 01X6 01X10 01X10 01X10 01X10 01X10 01X16 01X16 01X16 01X16 01X16 01X25 01X25 01X25 01X25 01X25 01X35 01X35 01X50 01X50 01X70 01X70 01X95 01X95 01X120 01X120 01X150

Technical Appendix

DA mm 3,1 3,1 3,1 3,1 3,1 3,1 3,8 3,8 3,8 3,8 3,8 3,8 4,4 4,4 4,4 4,4 4,4 4,4 5,4 5,4 5,4 5,4 5,4 5,4 6,5 6,5 6,5 6,5 6,5 7,3 7,3 7,3 7,3 7,3 9,5 9,5 9,5 9,5 9,5 10,9 10,9 11,7 11,7 13,5 13,5 15,5 15,5 17 17 19

weight ca. kg/km 21 21 21 21 21 21 34 34 34 34 34 34 47 47 47 47 47 47 72 72 72 72 72 72 120 120 120 120 120 170 170 170 170 170 260 260 260 260 260 360 360 515 515 710 710 940 940 1180 1180 1600

packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr., c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr. dr. dr. dr. dr.

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 86 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 040316 040308 040317 040309 040318 040310 040319 type 01X150 01X185 01X185 01X240 01X240 01X300 01X300 colour ge/ye bk ge/ye bk ge/ye bk ge/ye CU kg/km 1440 1776 1776 2304 2304 2880 2880 DA mm 19 21 21 24 24 weight ca. kg/km 1600 2100 2100 3015 3015 3398 3398 dr. dr. dr. dr. dr. dr. dr.

Rubber insulated wires <<<


Power cables 1 up to 30 kV

H07Z-K
packaging

NSGAFu
Application: This wire is designed for application in busses and railborn vehicles. If used in distribution or switching appliances the wire is considered to be short circuit proof. It is resistant against most oils and grease. standard nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation sheathing material maximum temperature at conductor flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 050194 050178 050159 050165 050172 050183 050184 050163 050164 050182 050208 050244 050241 050245 050246 type 01X1,5 01X2,5 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 24 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 DA mm 5,5 5,9 6,4 7 8,4 9,2 11,5 12,8 14,3 16 18,2 19,9 21,8 23,8 26,7 VDE 0250 T. 602 1,8 kV 3,6 kV 6 kV tinned copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free

90 C VDE 0482-332-1-2/IEC 60332-1 -40 - +90 C

>>> www.faberkabel.de <<<

> 87 <

Technical Appendix

weight ca. kg/km 60 70 90 120 180 250 390 470 625 880 1190 1430 1750 2160 2640

packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr. dr. dr.

Other

Conductor ropes

-25 - +90 C

LAN cables

rubber (CR) 5GM5

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Rubber insulated wires


Power cables 1 up to 30 kV

NSGAFu
p/n 050247 050471 050472 type 01X300 01X400 01X500 colour bk bk bk CU kg/km 2880 3840 4800

Flexible Cables
DA mm 38 40,5 42 weight ca. kg/km 3178 4200 5500 packaging dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

NSHXAF
standard nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant oil resistant acc. to EN 60811-2-1 maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 050476 050477 050379 050380 050381 050382 050383 050376 050377 050353 050356 050355 050384 050385 type 01X1,5 3KV 01X2,5 3KV 01X4 3KV 01X6 3KV 01X10 3KV 01X16 3KV 01X25 3KV 01X35 3KV 01X50 3KV 01X70 3KV 01X95 3KV 01X120 3KV 01X150 3KV 01X185 3KV VDE 0250 T. 606 1,8 kV 3 kV 6 kV bare copper fine stranded, class 5 rubber (EPR) 3GI3, halogen-free FRNC compound HM3 VDE 0482-332-1-2/IEC 60332-1 yes 90 C -40 - 70 C -25 - 70 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 14,4 24 38,4 57,6 96 153,6 240 336 480 672 912 1152 1440 1776 DA mm 7 7,5 9 9,5 11 13 15 16,5 18 20,5 24 25,1 28 31 weight ca. kg/km 60 70 85 110 160 240 365 494 656 880 1090 1340 1640 2160 packaging dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. Application: This insulated wire is designed for application in busses and railborn vehicles. If used in distribution or switching appliances up to 1000 V, it is considered to be short circuit proof. The cable is halogen-free, flame-retardant and resistant against most oils and grease.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 88 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 050386 050654 050893 050892 type 01X240 3KV 01X300 3KV 01X400 3KV 01X500 3KV colour bk bk bk bk CU kg/km 2304 2890 3840 4800 DA mm 34,5 38 40,1 42,1 weight ca. kg/km 2570 3470 4180 5860 dr. dr. dr. dr.

Rubber insulated wires <<<


Power cables 1 up to 30 kV

NSHXAF
packaging

GGSG
Application: The cable is designed for use on railways, where narrow bending radii and vibrations may occur. nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems nominal voltage (DC) test voltage conductor material conductor construction maximum temperature at conductor insulation flame retardant sheathing material max. operating temperature, fixed temperature, moved/ during installation p/n 011865 type 01X300/95 colour rd CU kg/km 3904 DA mm 46 1,8 kV 3 kV 2160 kV 2700 V 6 kV bare copper

90 C rubber (EPR) EI6 VDE 0482-332-1-2/IEC 60332-1 rubber (CR) EM2 -35 - +80 C -25 - +80 C weight packaging ca. kg/km 4850 dr.

>>> www.faberkabel.de <<<

> 89 <

Technical Appendix

Other

Conductor ropes

LAN cables

fine stranded class 6

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Silicone insulated wires and cords


Power cables 1 up to 30 kV

SiD
nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor max. operating temperature, fixed flame retardant 300 V 500 V 2 kV tinned copper solid, class 1 silicone rubber 180 C -60- +180 C VDE 0482-332-1-2/IEC 60332-1

Flexible Cables
Application: For operation at environment temperatures above 55 C, for internal wiring of lamps, heating equipment and electrical appliances as well as for switching boxes and distributions.

Flexible Cables

Building Wires

bending radius, moved 6 x DA application p/n 031939 031940 031941 031942 031943 032653 031944 type 01X1 01X1 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 colour bk wh bu bn ge/ye gy bk CU kg/km 9,6 9,6 14,4 14,4 14,4 14,4 14,4 DA mm 2,3 2,3 2,6 2,6 2,6 2,6 2,6 weight ca. kg/km 13 13 19 19 19 19 19 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100

Control and Electronic Cable

Telecommunication Cables and Cords

SiF
nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor 300 V 500 V 2 kV tinned copper fine stranded, class 5 silicone rubber 180 C VDE 0482-332-1-2/IEC 60332-1 -60- +180 C 6 x DA Application: For operation at environment temperatures above 55 C, for internal wiring of lamps, heating equipment and electrical appliances as well as for switching boxes and distributions.

LAN cables

Cable with circuit integrity

flame retardant max. operating temperature, fixed bending radius, fixed installation

Conductor ropes

bending radius, moved 15 x DA application p/n 031069 031070 031071 031072 031073 031074 031075 031076 031077 031078 031079 031080 031081 031082 031083 031084 type 01X0,25 01X0,25 01X0,25 01X0,25 01X0,25 01X0,25 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,5 01X0,75 01X0,75 01X0,75 colour bu bk bn gy wh rd ge/ye bu bk bn gy wh rd gy wh rd CU kg/km 2,4 2,4 2,4 2,4 2,4 2,4 4,8 4,8 4,8 4,8 4,8 4,8 4,8 7,2 7,2 7,2 DA mm 1,8 1,8 1,8 1,8 1,8 1,8 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,4 2,4 2,4 weight ca. kg/km 5,5 5,5 5,5 5,5 5,5 5,5 8,6 8,6 8,6 8,6 8,6 8,6 8,6 11 11 11 packaging dr., c. 200 dr., c. 200 dr., c. 200 dr., c. 200 dr., c. 100, c. 200 dr., c. 200 c. 100 c. 100 c. 100 c. 100 c. 100 dr., c. 100 c. 100 c. 100 c. 100 c. 100

Technical Appendix

Other

> 90 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 030993 030992 030991 030990 030994 030997 030996 030995 031085 031086 031087 030999 030998 030972 030971 030970 031088 031089 031090 031091 030967 030968 030969 031092 031093 031094 031095 031096 031097 031098 031099 031100 031101 031102 031103 031104 031105 031106 031107 031108 032021 032022 031109 032025 031115 031111 031112 031113 031114 031116 031117 030963 031118 031119 031281 031288 032108 032109 type 01X0,75 01X0,75 01X0,75 01X0,75 01X1 01X1 01X1 01X1 01X1 01X1 01X1 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X4 01X4 01X4 01X4 01X4 01X4 01X4 01X6 01X6 01X6 01X6 01X6 01X6 01X6 01X10 01X10 01X10 01X10 01X10 01X16 01X16 01X25 01X25 01X35 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 colour bk bn bu ge/ye ge/ye bk bn bu gy wh rd bu ge/ye rd bn bk gy wh ge/ye bu bk rd bn gy wh ge/ye bu bk bn gy wh rd ge/ye bu bk bn gy wh rd bk bu bn ge/ye wh bk ge/ye bk ge/ye bk ge/ye bk bk bk bk bk bk bk bk CU kg/km 7,2 7,2 7,2 7,2 9,6 9,6 9,6 9,6 9,6 9,6 9,6 14,4 14,4 14,4 14,4 14,4 14,4 14,4 24 24 24 24 24 24 24 38,4 38,4 38,4 38,4 38,4 38,4 38,4 57,6 57,6 57,6 57,6 57,6 57,6 57,6 96 96 96 96 96 153,6 153,6 240 240 336 336 480 672 912 1152 1440 1776 2304 2880 DA mm 2,4 2,4 2,4 2,4 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,8 2,8 2,8 2,8 2,8 2,8 2,8 3,4 3,4 3,4 3,4 3,4 3,4 3,4 4,2 4,2 4,2 4,2 4,2 4,2 4,2 5,2 5,2 5,2 5,2 5,2 5,2 5,2 7 7 7 7 7 8 8 9,9 9,9 11,2 11,2 13,8 14,8 18,2 19,2 21,9 23 26,5 30

Silicone insulated wires and cords <<<


Power cables 1 up to 30 kV

SiF
weight ca. kg/km 11 11 11 11 13,6 13,6 13,6 13,6 13,6 13,6 13,6 20,3 20,3 20,3 20,3 20,3 20,3 20,3 32 32 32 32 32 32 32 48,5 48,5 48,5 48,5 48,5 48,5 48,5 71 71 71 71 71 71 71 124 124 124 124 124 188 188 296 296 400 400 570 766 1030 1300 1563 1915 2440 3100 packaging c. 100 c. 100 c. 100 dr., c. 100 c. 100 c. 100 c. 100, c. 50 c. 100, c. 50 c. 100 c. 100 c. 100 dr., c. 100, barrel dr., c. 100, c. 50, barrel dr., c. 100, barrel c. 100, dr., barrel dr., c. 100, barrel c. 100, dr., barrel dr., c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel dr., c. 100, barrel c. 100 c. 100 c. 100 c. 100 dr., c. 100 c. 100 c. 100 c. 100 dr., c. 100 c. 100 c. 100 c. 100, c. 50, dr. c. 100 c. 100 c. 100 c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 50, c. 100 dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr., c. 50 dr. dr., c. 100 dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 91 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Silicone insulated wires and cords


Power cables 1 up to 30 kV

SiHF-J
protective conductor nominal voltage UO nominal voltage U test voltage yes 300 V 500 V 2 kV colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers tinned copper fine stranded, class 5 silicone rubber 180 C silicone rubber -60- +180 C VDE 0482-332-1-2/IEC 60332-1 15 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 21,6 28,8 36 43,2 50,4 28,8 38,4 48 67,2 192 43,2 57,6 72 101 115,2 172,8 259,2 288 345,6 72 96 120 168 288 384 456 600 115 154 192 269 173 230 288 403 384 480 615 768 960 1344 1920

Flexible Cables
Application: For connection of mobile electrical appliances without mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants. For fixed installation in mechanical protected conduits. For indoor and outdoor use.

Building Wires

core identification conductor material conductor construction insulation maximum temperature at conductor sheathing material max. operating temperature, fixed flame retardant bending radius, fixed installation p/n 030709 030710 030942 031120 030943 030676 030682 030944 030678 032872 030680 030665 030711 030800 032635 030791 032625 030945 030946 030664 030674 030691 030766 033890 033511 032636 032314 031126 030668 030696 031127 031129 031130 030690 030951 030708 033749 030707 031611 031332 032880 032847 type 03X0,75 04X0,75 05X0,75 06X0,75 07X0,75 03X1 04X1 05X1 07X1 20X1 03X1,5 04X1,5 05X1,5 07X1,5 08X1,5 12X1,5 18X1,5 20X1,5 24X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 16X2,5 19X2,5 25X2,5 03X4 04X4 05X4 07X4 03X6 04X6 05X6 07X6 04X10 05X10 04X16 05X16 04X25 04X35 04X50

Telecommunication Cables and Cords

Flexible Cables

Technical Appendix

DA mm 6,8 7,8 8,5 9,4 9,6 7,4 8 8,8 10 15,8 8 8,8 9,6 10,9 11,6 14,8 17,6 18,5 20,2 9,7 10,6 11,6 13,2 18 19,1 20,6 25,7 11,5 13 15 16,2 14,2 16,2 17,7 19,3 21,4 22,5 24 26,9 29,3 33 34

weight ca. kg/km 66 84 101 126 158 78 95 116 177 400 98 122 148 232 213 332 510 549 635 152 189 229 348 530 659 912 1200 249 330 359 487 352 429 564 685 710 900 1014 1206 1460 2044 2990

packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50, c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 50 dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 92 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For connection of mobile electrical appliances without mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants. For fixed installation in mechanical protected conduits. For indoor and outdoor use. protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material max. operating temperature, fixed flame retardant bending radius, fixed installation p/n 034943 031179 031180 031181 031182 031183 031184 type 02X0,5 02X0,75 02X1 02X1,5 02X2,5 02X4 02X6 colour rd rd rd rd rd rd rd CU kg/km 9,6 14,4 19,2 28,8 48 76,8 116 DA mm 5,4 6,4 6,6 7,6 9,2 10,8 13,4 no

Silicone insulated wires and cords <<<


Power cables 1 up to 30 kV

SiHF-O
300 V 500 V 2 kV tinned copper fine stranded, class 5 silicone rubber 180 C silicone rubber -60- +180 C VDE 0482-332-1-2/IEC 60332-1 15 x DA weight ca. kg/km 42 57 64 87 137 192 289 packaging dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100

SiF/GL
Application: For operation at environment temperatures above 55 C, for internal wiring of lamps, heating equipment and electrical appliances as well as for switching boxes and distributions. nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation max. operating temperature, fixed bending radius, fixed installation p/n 034720 032651 034721 034722 034723 034522 034724 033844 033845 033846 033847 033848 034725 type 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 colour wh wh wh wh wh wh wh wh wh wh wh wh wh CU kg/km 38,4 58 96 154 240 336 480 672 912 1152 1440 1776 2304 DA mm 4,7 5,4 7,6 8,9 10,9 12,1 14,4 14,9 18,4 19,4 23,4 24 300 V 500 V 2 kV tinned copper fine stranded, class 5 180 C silicone rubber -60 - +180 C 15 x DA weight ca. kg/km 53 77 129 198 303 413 578 831 1117 1410 1695 2077 2498 packaging dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 93 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Silicone insulated wires and cords


Power cables 1 up to 30 kV

H05SJ-K
standard nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor max. operating temperature, fixed flame retardant p/n 031711 031795 type 01X1,5 01X2,5 VDE 0282-3 300 V 500 V 2 kV tinned copper fine stranded, class 5 silicone rubber 90 C -60 - +180 C VDE 0482-332-1-2/IEC 60332-1 colour wh wh CU kg/km 14,4 24

Flexible Cables
Application: For operation at environment temperatures above 55 C, for internal wiring of lamps, heating equipment and electrical appliances as well as for switching boxes and distributions.

Flexible Cables

Building Wires

DA mm 3,5 4,2

weight packaging ca. kg/km 24 dr., c. 100 35,6 dr.

Control and Electronic Cable

Telecommunication Cables and Cords

SiHFCSi-J
protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor inner sheath screen coverage sheathing material max. operating temperature, fixed flame retardant yes 300 V 500 V 2 kV tinned copper fine stranded, class 5 silicone rubber 180 C silicone rubber 85 % silicone rubber -60- +180 C VDE 0482-332-1-2/IEC 60332-1 Application: For connection of electrical appliances without mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants. For indoor and outdoor use. The cable is designed for connections in EMI-sensitive applications.

Conductor ropes

LAN cables

Cable with circuit integrity

bending radius, moved 10 x DA application bending radius, fixed installation p/n 031574 031894 032639 033737 032889 033729 032890 031895 031951 032322 033730 032637 type 03X0,75 04X0,75 07X0,75 03X1 04X1 05X1 07X1 24X1 03X1,5 04X1,5 05X1,5 07X1,5 5 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 69,1 86 113,3 86,2 97 110 142 325 103,5 132 149 193,4 DA mm 10,1 11,6 9,7 10,7 11,6 12,1 weight ca. kg/km 130 159 214 146 174 203 247 526 198 230 276 342 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

12,1 13,3 14,3

> 94 <

>>> www.faberkabel.de <<<

Flexible Cables
p/n 031806 034764 032789 032043 034795 032319 033482 033731 033732 033744 033745 033746 034551 034552 034553 034554 type 12X1,5 03X2,5 04X2,5 05X2,5 07X2,5 04X4 04X6 05X4 05X6 04X10 04X16 04X25 02X0,75 02X1 02X1,5 02X2,5 colour rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 298 148 189 214,9 266 294 449 374 563 759 1180 1236 62 67 88 123 DA mm 12,9 14,2 16,9 17,1 18,8 19,4 21,2 25,7 28,4 35 9,2 9,5 10,7 12,1

Silicone insulated wires and cords <<<


Power cables 1 up to 30 kV

SiHFCSi-J
weight ca. kg/km 454 275 334 394 488 520 781 592 844 1294 1988 2995 124 132 172 230 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

SiHFCSi-O
Application: For connection of electrical appliances without mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants. For indoor and outdoor use. The cable is designed for connections in EMI-sensitive applications. protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor inner sheath screen coverage sheathing material max. operating temperature, fixed flame retardant no 300 V 500 V 2 kV tinned copper fine stranded, class 5 silicone rubber

silicone rubber 85 % silicone rubber -60- +180 C VDE 0482-332-1-2/IEC 60332-1

bending radius, moved 10 x DA application bending radius, fixed installation p/n 034551 034552 034553 034554 type 02X0,75 02X1 02X1,5 02X2,5 colour rd rd rd rd CU kg/km 62 67 88 123 DA mm 9,2 9,5 10,7 12,1 5 x DA weight ca. kg/km 124 132 172 230 packaging dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 95 <

Technical Appendix

Other

Conductor ropes

LAN cables

180 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Silicone insulated wires and cords


Power cables 1 up to 30 kV

SiHF/GLS-P
nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation sheathing material armour maximum temperature at conductor max. operating temperature, fixed bending radius, fixed installation flame retardant p/n 032325 032326 032327 032328 032033 032329 032330 031748 032331 031936 032332 032333 032079 032334 032292 032023 032309 032336 032337 031970 032338 032339 032340 032343 032324 032344 032347 032348 032921 032349 032350 034669 type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 02X1 03X1 04X1 05X1 07X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 24X1,5 02X2,5 03X2,5 04X2,5 05X2,5 06X2,5 07X2,5 04X4 05X4 07X4 04X6 05X6 07X6 04X10 04X16 04X25 300 V 500 V 2 kV colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers tinned copper fine stranded, class 5 silicone rubber silicone rubber steel wire braiding, galvanized 180 C -60 - +180 C 10 x DA VDE 0482-332-1-2/IEC 60332-1 colour SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA SWA CU kg/km 14,4 21,6 29 36 50 19,2 29 38,4 48 67,2 29 43,2 58 72 101 173 346 48 72 96 120 144 168 154 192 269 230,4 288 403 384 614,4 960

Flexible Cables
Application: For connection of electrical appliances with high mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

DA mm 7,9 8,3 9,3 10,1 10,7 7,9 8,9 9,4 10,4 11,1 9,1 9,5 10,3 11,1 12,1 15,5 21,5 10,7 11,2 12,1 13,3 14,3 14,4 14,9 16,1 17,5 18,1 19,4 20,7 22,1 26,1 30,4

weight ca. kg/km 84 95 116 140 177 91 110 142 155 197,7 119 137 170 193 198 328 600 175 194 278 304 340 368 359 435 559 508 615 768 925 1235 1700

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 96 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: For connection of mobile electrical appliances without mechanical stress at increased environmental temperatures, for example in steel-works, but also at low temperatures. Insulation and sheath are resistant against most oils, acids, lyes and oxydants. For fixed installation in mechanical protected conduits. For indoor and outdoor use. standard core identification nominal voltage UO nominal voltage U protective conductor conductor material conductor construction insulation maximum temperature at conductor sheathing material max. operating temperature, fixed flame retardant

Silicone insulated wires and cords <<<


Power cables 1 up to 30 kV

H05SS-F
VDE 0282-15 colours acc. VDE 0293 (HD308) 300 V 500 V tinned copper fine stranded, class 5 silicone rubber 180 C silicone rubber -60- +180 C VDE 0482-332-1-2/IEC 60332-1 yes

bending radius, moved 7,5 x DA application bending radius, fixed installation p/n 033448 033449 033450 033451 033452 033453 033454 033455 033456 032873 033457 032919 033458 033459 032878 032879 033460 032901 033461 032942 033463 033465 type 02X0,75 03G0,75 04G0,75 05G0,75 02X1 03G1 04G1 05G1 02X1,5 03G1,5 04G1,5 04G1,5 05G1,5 02X2,5 03G2,5 03G2,5 04G2,5 04G2,5 05G2,5 05G2,5 04G4 04G6 colour bk bk bk bk bk bk bk bk bk bk bk rd bk bk bk rd bk rd bk rd bk bk CU kg/km 14,4 22 29 36 19,2 29 38,4 48 29 43,2 58 58 72 48 72 72 96 96 120 120 154 230,4 DA mm 7,4 8,1 8,8 9,9 8 8,5 9,3 10,3 10,8 11,4 12,6 12,6 13,7 12,6 13,4 13,4 14,8 11,6 16,3 16,3 17,2 19,1 4 x DA weight ca. kg/km 57 71 90 109 67 84 101 125 90 114 137 137 163 149 169 169 209 195 255 255 331 488 packaging dr. dr., c. 100 dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 97 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Silicone insulated wires and cords


Power cables 1 up to 30 kV

FZLSi
nominal voltage U test voltage conductor material conductor construction insulation max. operating temperature, fixed p/n 031753 032294 type 01X1 01X1,5 10 kV 20 kV tinned copper fine stranded, class 5 silicone rubber -50 - +180 C colour rd bu CU kg/km 9,6 14,4

Flexible Cables
Application: Ignition wire for use under heavy transient environment temperatures. For fixed or flexible installation in the thermo and process technology, refrigeration and air conditioning technology.

Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

DA mm 7,2 7,4

weight packaging ca. kg/km 60 dr., c. 100 95 dr., c. 100

2GTL 13,8/15,0 kV
nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage conductor material conductor construction 13,8 kV 15 kV 27,6 kV 31 kV tinned copper fine stranded, class 5 180 C silicone rubber 6 x DA -50 - +180 C VDE 0482-332-1-2/IEC 60332-1 colour bk bk bk bk bk bk bk bk bk bk bk CU kg/km 96 154 240 336 480 672 912 1152 1440 1776 2304 DA mm 12,1 14,1 15,6 16,7 18,6 20,7 22,5 24,3 26,7 28,7 30,9 weight ca. kg/km 211 287 389 496 685 866 1096 1340 1646 1975 2485 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: Flexible connecting cable for increased ambient temperatures, for example transformers, generators and motors. For installation indoors and cable ducts for power stations, industry and distribution networks etc.. The halogen sheath is resistant against transformer oil and fuel oil.

Cable with circuit integrity

LAN cables

maximum temperature at conductor insulation bending radius, fixed installation max. operating temperature, fixed flame retardant p/n 033428 031930 033429 033430 031933 033431 032143 033432 033433 033434 033435 type 01X10 13 01X16 13 01X25 13 01X35 13 01X50 13 01X70 13 01X95 13 01X120 13 01X150 13 01X185 13 01X240 13

Technical Appendix

Other

Conductor ropes

> 98 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: In dry and wet environment as well as in free air for medium mechanical stress. For connection of electrical tools on building sites or in cold environments. H07BQ-F has a filler. standard core identification protective conductor nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n 050320 050324 050321 050325 050322 050326 050323 050327 type 02X0,75 02X1 03G0,75 03G1 04G0,75 04G1 05G0,75 05G1 colour og og og og og og og og CU kg/km 14,4 19,2 21,6 28,8 29 38,4 36 48 DA mm 6,4 7 7,1 7,4 7,6 8,1 8,5 9 VDE 0282-10 yes 300 V bare copper fine stranded, class 5 rubber (EPR) EI4 90 C polyurethan no -40 - +80 C 500 V

PUR-insulated cords <<<


Power cables 1 up to 30 kV

H05BQ-F
colours acc. VDE 0293 (HD308)

H07BQ-F
Application: In dry and wet environment as well as in free air for medium mechanical stress. For connection of electrical tools on building sites or in cold environments. H07BQ-F has a filler. standard core identification protective conductor nominal voltage U nominal voltage UO conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n 050328 050332 050329 050333 050491 050330 050334 050492 050493 050494 050495 050331 050335 050416 type 02X1,5 02X2,5 03G1,5 03G2,5 03G4 04G1,5 04G2,5 04G4 04G6 04G10 04G16 05G1,5 05G2,5 05G4 colour og og og og og og og og og og og og og og CU kg/km 28,8 48 43,2 72 115,2 57,6 96 154 230 384 614,4 72 120 192 DA mm 8,4 10 8,9 10,6 12,9 9,9 11,8 14,5 16,2 21,6 24,2 10,8 13,1 16 VDE 0282-10 colours acc. VDE 0293 (HD308) yes 750 V 450 V bare copper

rubber (EPR) EI4 90 C polyurethan

-40 - +80 C weight ca. kg/km 87,5 128 106,5 158,5 228 136 206 294 436 722 1103 169,5 258 345 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50

>>> www.faberkabel.de <<<

> 99 <

Technical Appendix

Other

Conductor ropes

no

LAN cables

fine stranded, class 5

Cable with circuit integrity

Control and Electronic Cable

weight packaging ca. kg/km 48,5 dr., c. 100, c. 50, c. 250 57 dr., c. 100, c. 50 60 dr., c. 100, c. 50 71 dr., c. 100, c. 50 76 dr., c. 100, c. 50 92 dr., c. 100, c. 50 98 dr., c. 100, c. 50 115,5 dr., c. 100, c. 50

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> PUR-insulated cords


Power cables 1 up to 30 kV

H07BQ-F
p/n 050417 050418 050419 type 05G6 05G10 05G16 colour og og og CU kg/km 288 480 768

Flexible Cables
DA mm 17,9 23,2 26,9 weight ca. kg/km 518 864 1382 packaging dr., c. 100, c. 50 dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

X07BQ-F
standard nominal voltage UO nominal voltage U core identification protective conductor conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant VDE 0282-10 450 V 750 V colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers yes bare copper fine stranded, class 5 rubber (EPR) EI4 90 C polyurethan no -40 - +80 C colour og og og og og og og og og CU kg/km 1200 1680 2400 3360 4560 101 168 172 288 DA mm 35 39 46,5 53 60 13,2 15,2 16 20,8 weight ca. kg/km 2400 2500 3290 5556 7274 267 352 340 520 packaging dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 Application: In dry and wet environment as well as in free air for medium mechanical stress. For connection of electrical tools on building sites or in cold environments. H07BQ-F has a filler.

Conductor ropes

LAN cables

Cable with circuit integrity

max. operating temperature, fixed p/n 050420 050409 050437 050421 050413 050345 050347 050401 050350 type 05G25 05G35 05G50 05G70 05G95 07X1,5 07X2,5 12G1,5 12X2,5

Technical Appendix

Other

> 100 <

>>> www.faberkabel.de <<<

Flexible Cables
Application: Cable with wide application area in electronics, nuclear engineering, aviation, marine and military, heating devices and lighting. The insulation is flame retardant, mechanical robust and heat resistant. nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 032904 032609 032905 032906 032907 032984 type 02X0,75 FL 03G0,75 04G0,75 05G0,75 07G0,75 04G1,5 T colour TR TR TR TR TR TR CU kg/km 14,4 22 29 36 50,4 58 DA mm 5 5,6 6,2 7 300 V 500 V 2 kV tinned copper

Special Versions <<<


Power cables 1 up to 30 kV

Livz6YYw

200 C FEP special PVC-compound VDE 0482-332-1-2/IEC 60332-1 -20 - +90 C 7,5 x DA weight ca. kg/km 56 66 80 91 124 144 packaging dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100, c. 50

H05V2V2D3-F (NYPLYw)
Application: As drawbars as well as for fixed installation in lights (not permitted for the connection of localvariable loads). Breaking load of the strength member 250 N. nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed p/n 032870 032871 type 04G0,75 04G0,75 colour bk wh CU kg/km 29 29 DA mm 9 9 300 V 500 V 2 kV green-yellow, blue, brown, black bare copper fine stranded, class 5 PVC TI3

PVC YM3 VDE 0482-332-1-2/IEC 60332-1 +5 - +90 C

>>> www.faberkabel.de <<<

> 101 <

Technical Appendix

Other

Conductor ropes

weight packaging ca. kg/km 72 c. 100 72 c. 100

LAN cables

90 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

fine stranded, class 5

>>> Special Versions


Power cables 1 up to 30 kV

Li2GYw (SiHYw PV/P)


core identification nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 031847 031848 031849 type 02X1,5 02X2,5 02X4 red, blue 24 V 500 V bare copper fine stranded, class 5 silicone rubber 180 C PVC VDE 0482-332-1-2/IEC 60332-1 -40 - +90 C +5 - +90 C 7,5 x DA colour bk bk bk CU kg/km 28,8 48 76,8

Flexible Cables
Application: As connecting cable between transformer and halogen-lamps in low voltage lightning systems.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

wxh ca. mm 5,8 x 3,5 6,8 x 4 7,8 x 4,4

weight ca. kg/km 44 66 96

packaging c. 100, dr. dr., c. 100 dr., c. 100

Control and Electronic Cable

NYL
standard nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation flame retardant bending radius, fixed installation p/n 032902 type 01X1,5 5KV VDE 0283-1 5 kV 10 kV tinned copper fine stranded, class 5 PVC 70 C -40 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 4 x DA colour ye CU kg/km 14,4 DA mm 7,5 weight packaging ca. kg/km 59 dr., c. 100 Application: PVC tube light cables are suitable for laying on plaster, in lighting housings and relief fittings and in cable ducts of metal to VDE 128.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 102 <

>>> www.faberkabel.de <<<

Telecommunication Cables and Cords <<<


Power cables 1 up to 30 kV
105

I-Y(St)Y .. Lg

Instrumentation cable RD-Y(St)Y RE-2X(St)Y FR RE-2X(St)Yv FR RE-2X(St)Yv FR PiMF RE-2Y(St)Yv 0,5 qmm RE-2Y(St)Yv 0,75 qmm RE-2Y(St)Yv 1,3 qmm Industrial electronic cable JE-Y(St)Y JE-Y(St)Y ... FR JE-LiYCY JE-LiHCH Insulated wires YR

117 117 118 118 119 120 121 122 123 123 124 124 125 126 126

>>> www.faberkabel.de <<<

> 103 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Subscriber line cable A-2Y(L)2Y nx2x0,6 A-2Y(L)2Y nx2x0,8 A-2YF(L)2Y nx2x0,6 A-2YF(L)2Y nx2x0,8 A-02YSOF(L)2Y 0,6 mm A-02YSOF(L)2Y 0,8 mm AJ-Y(St)YDY Bd A-2YF(L)2YB2Y St III Bd A-Y(St)Y

110 110 111 112 113 114 114 115 115 116

Control and Electronic Cable

Fire signalisation cable J-2Y(St)Y St III Bd J-H(ST)H J-H(St)H BMK J-2Y(St)H St III Bd

106 106 107 108 109

Telecommunication Cables and Cords

Indoor telecommunication cable I-YY

104 104

Flexible Cables

Building Wires

qualityconscious

Content

>>> Indoor telecommunication cable


Power cables 1 up to 30 kV

I-YY

Telecommunication Cables and Cords


VDE 0815 colours + rings 100 nF/km 300 V 800 V 130 Ohm/km 1,7 dB/km bare copper solid, class 1 PVC TI1 PVC TM1 VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C -5 - +50 C 7,5 x DA colour gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 11 23 34 57 90 113 136 170 226 283 339 452 565 DA mm 5 6,5 7 8,5 9,5 11 12 13,5 15 16,5 18,5 20 22,5 weight ca. kg/km 30 50 70 100 160 180 220 280 360 440 520 700 840 packaging dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the cable is protected against direct sun irradiation. Not for use in power circuits!

standard core identification operating capacity nominal voltage U test voltage loop resistance attenuation at 800 Hz conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 100039 100040 100041 100042 100149 100150 100151 100152 100153 100080 100154 100155 100066 type 02X2X0,6 04X2X0,6 06X2X0,6 10X2X0,6 16X2X0,6 20X2X0,6 24X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 60X2X0,6 80X2X0,6 100X2X0,6

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 104 <

>>> www.faberkabel.de <<<

Telecommunication Cables andIndoor telecommunication cable <<< Cords


Application: For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the cable is protected against direct sun irradiation. Not for use in power circuits! standard core identification operating capacity nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant bending radius, fixed installation temperature, moved/ during installation max. operating temperature, fixed p/n 100001 100003 100005 100007 100009 100011 100013 100017 100019 100021 100023 100025 100027 100029 100031 100033 100035 100037 100015 100436 100002 100004 100006 100008 100010 100012 100014 100018 100020 100022 100024 100026 100028 100030 100032 100034 100036 100038 100016 type 01X2X0,6 02X2X0,6 03X2X0,6 04X2X0,6 05X2X0,6 06X2X0,6 08X2X0,6 10X2X0,6 12X2X0,6 14X2X0,6 16X2X0,6 20X2X0,6 24X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 60X2X0,6 80X2X0,6 100X2X0,6 150X2X0,6 01X2X0,8 02X2X0,8 03X2X0,8 04X2X0,8 05X2X0,8 06X2X0,8 08X2X0,8 10X2X0,8 12X2X0,8 14X2X0,8 16X2X0,8 20X2X0,8 24X2X0,8 30X2X0,8 40X2X0,8 50X2X0,8 60X2X0,8 80X2X0,8 100X2X0,8 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 7 13 18 24 30 35 46 58 71 82 93 116 139 172 229 286 342 455 568 850 11 21 31 41 52 62 82 102 123 144 164 204 244 304 405 506 606 807 1008 DA mm 5 5,5 6,3 6,8 7,2 7,5 8 9 9,5 10 10,5 11 11,5 13 15 17 18 20,5 23 6 7 8,5 9 9,5 10,5 11,5 13 14 14,5 15,5 16,5 19 20 22,5 25,5 28 31 32 VDE 0815 colours acc. VDE 0815 100 nF/km 300 V bare copper solid, class 1 PVC TI1 PVC TM1 VDE 0482-332-1-2/IEC 60332-1 7,5 x DA -5 - +50 C -30 - +70 C weight ca. kg/km 30 35 50 55 65 75 90 110 130 150 155 200 235 275 350 445 520 675 870 1180 40 55 80 95 115 130 160 205 240 280 300 380 445 540 710 875 1085 1440 1790 packaging dr., c. 100, c. 50, c. 250 dr., c. 100, c. 50, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 50, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 50, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr. dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100 dr. dr., c. 50 dr. dr. dr. dr. dr. dr., c. 100, c. 250 dr., c. 100, c. 50, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 50, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr., c. 100, c. 250 dr. dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. 800 V

>>> www.faberkabel.de <<<

> 105 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

I-Y(St)Y .. Lg

>>> Indoor telecommunication cable


Power cables 1 up to 30 kV

Fire signalisation cable

Telecommunication Cables and Cords


colours acc. VDE 0815 100 nF/km 300 V 800 V bare copper solid, class 1 PVC TI1 PVC TM1 VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C -5 - +50 C 7,5 x DA colour rd rd rd rd rd rd rd rd rd rd rd rd CU kg/km 11 21 41 52 62 102 204 304 405 506 807 1008 DA mm 5,5 7 9 9,4 10,5 13 16,5 20 22 25,5 31 32 weight ca. kg/km 38 55 95 114 130 205 380 570 710 875 1440 1780 packaging dr., c. 100 dr., c. 100, c. 50, c. 250 dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. Application: For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the cable is protected against direct sun irradiation. The special imprint identifies the cable as fire signalisation cable.

core identification operating capacity nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 100947 100056 100057 100948 100058 100059 100060 100145 100146 100147 100148 100144 type 01X2X0,8 02X2X0,8 04X2X0,8 05X2X0,8 06X2X0,8 10X2X0,8 20X2X0,8 30X2X0,8 40X2X0,8 50X2X0,8 80X2X0,8 100X2X0,8

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

J-2Y(St)Y St III Bd
operating capacity nominal voltage U test voltage conductor material conductor construction insulation sheathing material 52 nF/km 300 V 800 V bare copper solid, class 1 polyethylene PVC VDE 0482-332-1-2/IEC 60332-1 7,5 x DA -30 - +70 C -5 - +50 C 100 Ohm type 02X2X0,6 04X2X0,6 06X2X0,6 10X2X0,6 20X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 colour gy gy gy gy gy gy gy gy CU kg/km 13 24 35 58 116 172 229 286 DA mm 5,5 7,5 8,5 9 12 14,5 16 18,5 weight ca. kg/km 42 66 80 115 217 283 370 434 packaging dr., c. 100, c. 250 dr., c. 250 dr. dr. dr. dr. dr. dr. Application: For connection of computer units, ISDN-sub-units and -devices and for data transmission. Suitable for transmission of analog- and digital signals up to 16 Mbit/s. For installation in dry and wet rooms.

Conductor ropes

LAN cables

flame retardant bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation impedance

Other

p/n 100210 100211 100212 100213 100214 100215 100216 100217

Technical Appendix

> 106 <

>>> www.faberkabel.de <<<

Telecommunication Cables andIndoor telecommunication cable <<< Cords


p/n 100218 100219 100220 type 60X2X0,6 80X2X0,6 100X2X0,6 colour gy gy gy CU kg/km 342 455 568 DA mm 20 22,5 25 weight ca. kg/km 526 678 861 packaging dr. dr. dr.

J-H(ST)H
Application: Low Smoke Zero Halogen communication cable. For connection of communication units indoors in wet and dry rooms on and under plaster. For outdoor installation the cable must be protected against direct sun irradiation. standard nominal voltage U test voltage operating capacity conductor material insulation sheathing material flame retardant max. operating temperature, fixed p/n 100294 100295 100296 100297 100298 100299 100300 100301 100302 100303 100304 100305 100306 100307 100308 100309 100310 100311 100312 type 002X2X0,6 004X2X0,6 006X2X0,6 010X2X0,6 020X2X0,6 030X2X0,6 040X2X0,6 050X2X0,6 060X2X0,6 080X2X0,6 100X2X0,6 002X2X0,8 004X2X0,8 006X2X0,8 010X2X0,8 020X2X0,8 030X2X0,8 040X2X0,8 050X2X0,8 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 14 25 37 59 116 172 229 286 342 455 568 25 45 65 106 206 307 407 508 DA mm 5,5 6,8 7,5 9 11 13 15 17 18 20,5 23 7 9 10,5 13 16,5 20 22,5 25,5 VDE 0815 300 V 800 V 120 nF/km bare copper FRNC compound HI1 FRNC-compound HM1 VDE 0482-266-2-4/ IEC 60332-3-24 -5 - +50 C weight ca. kg/km 49 92 101 146 310 352 464 573 661 876 1056 69 136 152 230 508 599 787 973 packaging dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 107 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

J-2Y(St)Y St III Bd

>>> Indoor telecommunication cable


Power cables 1 up to 30 kV

J-H(ST)H
p/n 100314 100313 100315

Telecommunication Cables and Cords


type 060X2X0,8 080X2X0,8 100X2X0,8 colour gy gy gy CU kg/km 608 809 1010 DA mm 28 31 32 weight ca. kg/km 1121 1476 1805 packaging dr. dr. dr.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

J-H(St)H BMK
standard core identification operating capacity nominal voltage U test voltage conductor material insulation sheathing material flame retardant max. operating temperature, fixed p/n 100354 100355 100356 100357 100358 100359 100360 100361 100362 100363 100364 type 002X2X0,8 004X2X0,8 006X2X0,8 010X2X0,8 020X2X0,8 030X2X0,8 040X2X0,8 050X2X0,8 060X2X0,8 080X2X0,8 100X2X0,8 VDE 0815 (with ref. to) colours + rings 120 nF/km 300 V 800 V bare copper FRNC compound HI1 FRNC-compound HM1 VDE 0482-266-2-4/ IEC 60332-3-24 -5 - +50 C colour rd rd rd rd rd rd rd rd rd rd rd CU kg/km 25 45 65 106 206 307 407 508 608 809 1010 DA mm 7 9 10,5 13 16,5 20 22,5 25,5 28 31 32 weight ca. kg/km 69 136 152 230 508 599 787 973 1121 1476 1805 packaging dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: Low Smoke Zero Halogen communication cable with improved flame retardance. For connection of communication units indoors in wet and dry rooms on and under plaster. The special imprint identifies the cable as fire signalisation cable.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 108 <

>>> www.faberkabel.de <<<

Telecommunication Cables andIndoor telecommunication cable <<< Cords


Application: Halogen free and flame retardant ISDN-System cable, for connection of telecommunication an IT-components up to 16 Mbit/s (cat. 3).For installation indoor, in and under plaster, in dry as well as wet rooms. core identification operating capacity nominal voltage U test voltage conductor material insulation transfer impedance sheathing material flame retardant impedance max. operating temperature, fixed p/n 100454 100390 100471 100470 100521 100536 100537 100522 100523 100538 100520 type 02X2X0,6 04X2X0,6 06X2X0,6 10X2X0,6 20X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 60X2X0,6 80X2X0,6 100X2X0,6 colour gy gy gy gy gy gy gy gy gy gy gy CU kg/km 13 25 35 58 116 172 229 286 342 455 568 DA mm 4,9 6,9 7 9,2 12 14,5 16,2 18,2 19,6 22,1 24,7 colours + rings 45 nF/km 225 V 800 V polyethylene 200 Ohm/km FRNC-compound HM2 VDE 0482-332-1-2/IEC 60332-1 100 Ohm bare copper

>>> www.faberkabel.de <<<

> 109 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

weight ca. kg/km 42 60 85 115 217 300 370 434 526 680 861

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Telecommunication Cables and Cords

Flexible Cables

-5 - +50 C

Building Wires

Power cables 1 up to 30 kV

J-2Y(St)H St III Bd

>>> Subscriber line cable


Power cables 1 up to 30 kV

A-2Y(L)2Y nx2x0,6

Telecommunication Cables and Cords


VDE 0816 colours + rings 225 V 2000 V 130 Ohm/km 52 nF/km 1,04 dB/km bare copper solid, class 1 polyethylene 2YI1 70 C yes polyethylene 2YM1 yes no 70 C 7,5 x DA colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 11 23 34 57 113 170 226 283 396 565 848 1131 1414 1696 1979 2262 2827 DA mm 9 11 12 13,5 16 18 20 21 25 28 33 38 41,5 44,5 47,5 51 56 weight ca. kg/km 80 120 130 155 240 310 385 460 605 870 1345 1755 2140 2525 2930 3300 4050 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

standard core identification nominal voltage U test voltage loop resistance operating capacity attenuation at 800 Hz conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material for outdoor use flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 110080 110075 110025 110029 110035 110037 110039 110041 110043 110027 110031 110033 110101 110083 110103 110082 110068 type 02X2X0,6 04X2X0,6 06X2X0,6 10X2X0,6 20X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 70X2X0,6 100X2X0,6 150X2X0,6 200X2X0,6 250X2X0,6 300X2X0,6 350X2X0,6 400X2X0,6 500X2X0,6

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 110 <

>>> www.faberkabel.de <<<

Telecommunication Cables and CordsSubscriber line cable <<<


Application: For fixed installation indoors, outdoors, in ground and in water. standard core identification nominal voltage U loop resistance test voltage operating capacity attenuation at 800 Hz conductor material conductor construction insulation maximum temperature at conductor bonded sheath sheathing material for outdoor use flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 110076 110024 110026 110093 110030 110092 110036 110038 110040 110042 110044 110028 110032 110034 110090 110102 110104 110105 110106 110107 type 02X2X0,8 04X2X0,8 06X2X0,8 08X2X0,8 10X2X0,8 12X2X0,8 20X2X0,8 30X2X0,8 40X2X0,8 50X2X0,8 70X2X0,8 100X2X0,8 150X2X0,8 200X2X0,8 250X2X0,8 300X2X0,8 350X2X0,8 400X2X0,8 500X2X0,8 600X2X0,8 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 20 40 60 81 101 123 201 302 402 503 704 1005 1508 2011 2514 3016 3519 4022 5027 6032 DA mm 9 12 13 14 15 15,2 18,5 21 23 26 29 34 40 44 51 53 56 60 68 74 VDE 0816 colours + rings 225 V 73,2 Ohm/km 55 nF/km 0,78 dB/km bare copper solid, class 1 polyethylene 2YI1 70 C yes polyethylene 2YM1 yes no 70 C 7,5 x DA weight ca. kg/km 90 140 160 180 205 250 355 475 600 745 1100 1425 2200 2900 3550 4200 4900 5500 6800 8100 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. 2000 V

>>> www.faberkabel.de <<<

> 111 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

A-2Y(L)2Y nx2x0,8

>>> Subscriber line cable


Power cables 1 up to 30 kV

A-2YF(L)2Y nx2x0,6

Telecommunication Cables and Cords


VDE 0816 225 V 2000 V colours + rings 52 nF/km 1,04 dB/km 130 Ohm/km bare copper solid, class 1 70 C polyethylene 2YI1 yes polyethylene 2YM1 yes no 70 C 7,5 x DA colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 11 23 34 57 113 170 226 283 396 565 848 1131 1414 1696 1979 2262 2827 3392 DA mm 9 11 12 13,5 16,5 19,5 21,5 23,5 27 31,5 37,5 42,5 47,5 51,5 53,5 60,5 66 73,5 weight ca. kg/km 80 130 140 190 310 430 545 660 875 1225 1780 2315 2895 3480 4000 4550 5690 6880 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For fixed installation indoors, outdoors, in ground and in water.

standard nominal voltage U test voltage core identification operating capacity attenuation at 800 Hz loop resistance conductor material conductor construction maximum temperature at conductor insulation bonded sheath sheathing material for outdoor use flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 110077 110079 110001 110005 110011 110016 110018 110020 110022 110003 110007 110009 110013 110014 110067 110072 110081 110100 type 02X2X0,6 04X2X0,6 06X2X0,6 10X2X0,6 20X2X0,6 30X2X0,6 40X2X0,6 50X2X0,6 70X2X0,6 100X2X0,6 150X2X0,6 200X2X0,6 250X2X0,6 300X2X0,6 350X2X0,6 400X2X0,6 500X2X0,6 600X2X0,6

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 112 <

>>> www.faberkabel.de <<<

Telecommunication Cables and CordsSubscriber line cable <<<


Application: For fixed installation indoors, outdoors, in ground and in water. standard nominal voltage U test voltage core identification operating capacity attenuation at 800 Hz loop resistance conductor material conductor construction maximum temperature at conductor insulation bonded sheath sheathing material for outdoor use flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 110078 110074 110002 110006 110012 110017 110019 110021 110023 110112 110004 110008 110010 110091 110015 110069 110073 110099 type 02X2X0,8 04X2X0,8 06X2X0,8 10X2X0,8 20X2X0,8 30X2X0,8 40X2X0,8 50X2X0,8 70X2X0,8 80X2X0,8 100X2X0,8 150X2X0,8 200X2X0,8 250X2X0,8 300X2X0,8 350X2X0,8 400X2X0,8 500X2X0,8 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 20 40 60 101 201 302 402 503 704 804 1005 1508 2011 2514 3016 3519 4022 5027 DA mm 10 13 13,5 15,5 20 23 26,5 28,5 33 35 38,5 47 52 58 62 66 72 79 VDE 0816 225 V 2000 V colours + rings 0,78 dB/km 73,2 Ohm/km bare copper solid, class 1 70 C polyethylene 2YI1 yes polyethylene 2YM1 yes no 70 C 7,5 x DA weight ca. kg/km 100 175 200 280 485 675 885 1070 1420 1700 2000 2935 3800 4590 5480 6350 7350 8920 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. 55 nF/km

>>> www.faberkabel.de <<<

> 113 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

A-2YF(L)2Y nx2x0,8

>>> Subscriber line cable


Power cables 1 up to 30 kV

A-02YSOF(L)2Y 0,6 mm
standard

Telecommunication Cables and Cords


VDE 0816 52 nF/km 130 Ohm/km 225 V bare copper solid, class 1 foam-PE yes polyethylene 7,5 x DA -30 - +70 C colour bk bk bk bk CU kg/km 57 113 283 565 DA mm 15,8 21,4 28,2 weight ca. kg/km 190 255 510 940 packaging dr. dr. dr. dr. Application: Subscriber line cable for connecting telecom network components. For installation in tubes ducts or direct burial in ground.

operating capacity loop resistance nominal voltage U conductor material conductor construction insulation bonded sheath sheathing material bending radius, fixed installation max. operating temperature, fixed p/n 110227 110228 110229 110230 type 10X2X0,6 20X2X0,6 50X2X0,6 100X2X0,6

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Control and Electronic Cable

A-02YSOF(L)2Y 0,8 mm
standard operating capacity nominal voltage U loop resistance conductor material conductor construction insulation bonded sheath sheathing material bending radius, fixed installation VDE 0816 55 nF/km 225 V 73,2 Ohm/km bare copper solid, class 1 foam-PE yes polyethylene 7,5 x DA -30 - +70 C colour bk bk bk bk bk bk bk CU kg/km 60 101 201 302 503 1005 2011 DA mm 13,2 17,2 20 23,7 32,4 44 weight ca. kg/km 200 230 360 675 750 1440 2650 packaging dr. dr. dr. dr. dr. dr. dr. Application: Subscriber line cable for connecting telecom network components. For installation in tubes ducts or direct burial in ground.

Cable with circuit integrity

LAN cables

max. operating temperature, fixed p/n 110413 110213 110231 110301 110232 110233 110393 type 06X2X0,8 10X2X0,8 20X2X0,8 30X2X0,8 50X2X0,8 100X2X0,8 200X2X0,8

Technical Appendix

Other

Conductor ropes

> 114 <

>>> www.faberkabel.de <<<

Telecommunication Cables and CordsSubscriber line cable <<<


Application: Subscriber line cable in local distributation networks for short and medium distances, interconnection of distribution points etc., if special requirements to EMC are applicable. Suitable for direct burial in earth (the jellyfilling is protected against intruding water), as well as in cable ducts and tubes. The FR-version is flame retardant acc. to VDE 0482-266-2-4/IEC 60332-3-24. standard attenuation at 800 Hz operating capacity test voltage conductor material conductor construction insulation inner sheath sheathing material flame retardant bending radius, fixed installation temperature, moved/ during installation max. operating temperature, fixed p/n 110198 110163 110200 110165 110201 110214 110285 110202 type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 20X2X0,8 40X2X0,8 48X2X0,8 100X2X0,8 colour bk bk bk bk bk bk bk bk CU kg/km 193 213 253 294 374 575 661 1265 DA mm 12,5 15,1 17,5 19,5 22,5 28,5 30,2 40,3 VDE 0816 1,1 dB/km 100 nF/km 500 V bare copper solid, class 1 PVC TI1 PVC PVC TM1 VDE 0482-332-1-2/IEC 60332-1 10 x DA - 5 - +50 C -30 - +70 C weight ca. kg/km 325 375 480 327 730 1100 1215 1890 packaging dr. dr. dr. dr. dr. dr. dr. dr.

A-2YF(L)2YB2Y St III Bd
Application: For fixed installation indoors, outdoors, in ground and in water. standard nominal voltage U test voltage loop resistance operating capacity conductor material conductor construction insulation bonded sheath inner sheath armour sheathing material max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 110267 110268 110235 110236 110273 110237 110238 110239 type 02X2X0,8 04X2X0,8 06X2X0,8 10X2X0,8 20X2X0,6 20X2X0,8 30X2X0,8 40X2X0,8 colour bk bk bk bk bk bk bk bk CU kg/km 20 40 60 101 113 201 302 402 DA mm 12,7 15,5 15,8 17,8 23,1 26,3 28,8 VDE 0816 (with ref. to) 225 V 500 V 73,2 Ohm/km 42 nF/km bare copper solid, class 1 polyethylene 2YI1 yes polyethylene 2YM2 polyethylene 2YM2 -30 - +70 C - 5 - +50 C 7,5 x DA weight ca. kg/km 198 288 320 410 454 710 890 1070 packaging dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 115 <

Technical Appendix

Other

Conductor ropes

Steel tape

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

AJ-Y(St)YDY Bd

>>> Subscriber line cable


Power cables 1 up to 30 kV

A-2YF(L)2YB2Y St III Bd
p/n 110240 110241 110300

Telecommunication Cables and Cords


type 50X2X0,8 70X2X0,8 100X2X0,8 colour bk bk bk CU kg/km 503 704 1005 DA mm 31,1 35,5 42 weight ca. kg/km 1280 1620 1985 packaging dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

A-Y(St)Y
standard core identification nominal voltage U test voltage conductor material conductor construction insulation inner sheath sheathing material bending radius, fixed installation oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed p/n 110184 110179 type 04X0,75 08X0,75 VDE 0816 numbers 200 V 2000 V tinned copper stranded, class 2 PVC PVC special PVC-compound 12 x DA yes -30 - +70 C colour bk bk CU kg/km 36 65 DA mm 9,1 10,8 weight packaging ca. kg/km 144 dr. 222 dr. Application: These data transmission cables are used for connections between petrol pumps and the cash register. The cable is oil and fuel-resistance. For fixed installation inside of buildings, outdoor as well as in earth without mechanical stress.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 116 <

>>> www.faberkabel.de <<<

Instrumentation cable <<< Telecommunication Cables and Cords


Application: In measuring and controlcircuits of industrial installations for transfer of analog and digital data up to 10 kHz. For fixed installation inside of buildings The version with blue outer sheath is suitable for application in intrinsical-safe circuits. operating capacity nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant impedance bending radius, fixed installation max. operating temperature, fixed p/n 100928 100929 100443 100602 100445 100580 100446 100501 100447 100958 100448 100723 100394 100581 100449 100502 100450 100724 100395 100444 100970 100972 type 01X2X0,5 01X2X0,5 02X2X0,5 02X2X0,5 04X2X0,5 04X2X0,5 08X2X0,5 08X2X0,5 12X2X0,5 12X2X0,5 16X2X0,5 16X2X0,5 24X2X0,5 24X2X0,5 32X2X0,5 32X2X0,5 48X2X0,5 48X2X0,5 96X2X0,5 16X2X1 02X2X1 04X2X1 colour gy bu gy bu gy bu gy bu gy bu gy bu gy bu gy bu gy bu gy gy gy gy CU kg/km 15 15 25 25 45 45 85 85 125 125 165 165 245 245 325 325 485 485 965 332 51 91 DA mm 5,5 6,5 6,5 9,1 9,1 11,5 11,5 13,5 13,5 15,5 15,5 17,8 17,8 21,1 21,1 25,5 25,5 33,5 18,2 7,6 10,4 120 nF/km 600 V 2000 V bare copper

PVC PVC VDE 0482-332-1-2/IEC 60332-1 130 Ohm 7,5 x DA -5 - + 50 C weight ca. kg/km 35 35 65 55 110 110 190 190 290 290 370 370 480 480 700 700 1000 1000 1617 700 130 220 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 117 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

stranded, class 2

Power cables 1 up to 30 kV

RD-Y(St)Y

>>> Instrumentation cable


Power cables 1 up to 30 kV

RE-2X(St)Y FR

Telecommunication Cables and Cords


bare copper cl.2, 7-wired construction XLPE PVC VDE 0482-266-2-4/ IEC 60332-3-24 -5 - +50 C 7,5 x DA colour bk bk bu bk bu bu bk bu bu bu bk bu CU kg/km 15 30 30 46 46 85 130 130 163 202 250 250 DA mm 8,2 10,2 10,2 11,1 11,1 13,8 15,7 15,7 17,5 18,7 20,2 20,2 weight ca. kg/km 70 98 98 130 130 85 266 266 340 400 455 455 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth.

conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 100988 100989 100999 100990 101000 101001 100992 101002 101003 101004 100995 101005 type 01X2X0,5 02X2X0,5 02X2X0,5 04X2X0,5 04X2X0,5 08X2X0,5 12X2X0,5 12X2X0,5 16X2X0,5 20X2X0,5 24X2X0,5 24X2X0,5

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

RE-2X(St)Yv FR
operating capacity nominal voltage U test voltage conductor material conductor construction insulation sheathing material 120 nF/km 300 V 2000 V bare copper cl.2, 7-wired construction XLPE PVC, enforced VDE 0482-266-2-4/ IEC 60332-3-24 -5 - +50 C 7,5 x DA colour bu bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu CU kg/km 25 47 47 64 64 184 184 370 370 34 34 50 50 60 60 114 114 218 DA mm 7,7 10,4 10,4 11,7 11,7 16,8 16,8 22,1 22,1 8,4 8,4 10 10 11,6 11,6 13,2 13,2 16,4 weight ca. kg/km 80 101 101 160 160 344 344 610 610 102 102 110 110 125 125 220 220 360 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth.

LAN cables

Cable with circuit integrity

flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 100637 100564 100518 100639 100626 100643 100644 100647 100624 100650 100615 100651 100652 100562 100589 100653 100654 100657 type 01X2X0,75 02X2X0,75 02X2X0,75 04X2X0,75 04X2X0,75 12X2X0,75 12X2X0,75 24X2X0,75 24X2X0,75 01X2X1,3 01X2X1,3 01X3X1,3 01X3X1,3 02X2X1,3 02X2X1,3 04X2X1,3 04X2X1,3 08X2X1,3

Technical Appendix

Other

Conductor ropes

> 118 <

>>> www.faberkabel.de <<<

Instrumentation cable <<< Telecommunication Cables and Cords


Power cables 1 up to 30 kV

RE-2X(St)Yv FR

p/n 100658 100563 100603 100660 100479

type 08X2X1,3 12X2X1,3 12X2X1,3 24X2X1,3 24X2X1,3

colour bk bu bk bu bk

RE-2X(St)Yv FR PiMF
Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth. operating capacity nominal voltage U test voltage core identification conductor material conductor construction insulation sheathing material bending radius, fixed installation 115 nF/km 300 V 1500 V core A: black, core B: white with number bare copper cl.2, 7-wired construction XLPE PVC, enforced 7,5 x DA

bending radius, moved 15 x DA application flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 100679 100680 100681 100685 100686 100687 100690 100691 100620 100560 100565 100583 100696 type 02X2X0,75 04X2X0,75 04X2X0,75 08X2X0,75 12X2X0,75 12X2X0,75 24X2X0,75 24X2X0,75 02X2X1,3 02X2X1,3 04X2X1,3 06X2X1,3 12X2X1,3 colour bk bu bk bk bu bk bu bk bu bk bu bu bu CU kg/km 47 82 82 160 237 237 470 470 68 68 124 181 353 DA mm 11,4 13 13 16,1 18,8 18,8 25,5 25,5 12,6 12,6 14,4 17 21,3 VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C -5 - +50 C weight ca. kg/km 140 190 190 310 410 410 760 760 135 135 220 301 580 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 119 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

CU kg/km 218 322 322 684 684

DA mm 16,4 19,2 19,2 26,1 26,1

weight ca. kg/km 360 488 488 912 912

packaging dr. dr. dr. dr. dr.

>>> Instrumentation cable


Power cables 1 up to 30 kV

RE-2X(St)Yv FR PiMF
p/n 100697 100699 100700

Telecommunication Cables and Cords


type 12X2X1,3 24X2X1,3 24X2X1,3 colour bk bu bk CU kg/km 353 697 697 DA mm 21,3 29 29 weight ca. kg/km 580 1090 1090 packaging dr. dr. dr.

Flexible Cables

Building Wires

RE-2Y(St)Yv 0,5 qmm


nominal voltage U test voltage conductor resistance operating capacity core identification conductor material conductor construction insulation sheathing material flame retardant bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n type 01X2X0,5 01X2X0,5 02X2X0,5 02X2X0,5 04X2X0,5 04X2X0,5 06X2X0,5 06X2X0,5 08X2X0,5 08X2X0,5 10X2X0,5 10X2X0,5 12X2X0,5 12X2X0,5 16X2X0,5 16X2X0,5 20X2X0,5 20X2X0,5 24X2X0,5 24X2X0,5 300 V 2000 V 39,2 Ohm/km 75 nF/km core A: black, core B: white with number bare copper fine stranded, class 5 polyethylene PVC TM1 VDE 0482-332-1-2/IEC 60332-1 7,5 x DA -30 - +50 C -5 - +50 C colour bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu CU kg/km 15 15 30 30 50 50 70 70 90 90 110 110 130 130 170 170 210 210 250 250 DA mm 8,2 8,2 10,2 10,2 11 11,5 12,6 12,6 13,8 13,8 14,9 14,9 15,7 15,7 17,5 17,5 18,8 18,8 20,2 20,2 weight ca. kg/km 74 74 117 117 138 138 190 190 210 210 220 220 273 273 348 348 383 383 467 467 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth.

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

100777 100804 100778 100805 100727 100806 100779 100807 100780 100808 100781 100809 100728 100810 100782 100811 100783 100812 100729 100813

Technical Appendix

Other

Conductor ropes

> 120 <

>>> www.faberkabel.de <<<

Instrumentation cable <<< Telecommunication Cables and Cords


Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth. nominal voltage U test voltage conductor resistance operating capacity core identification conductor material conductor construction insulation sheathing material flame retardant bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 100786 100816 100754 100817 100787 100818 100788 100819 100789 100820 100790 100821 100755 100822 100791 100823 100792 100824 100793 100825 type 01X2X0,75 01X2X0,75 02X2X0,75 02X2X0,75 04X2X0,75 04X2X0,75 06X2X0,75 06X2X0,75 08X2X0,75 08X2X0,75 10X2X0,75 10X2X0,75 12X2X0,75 12X2X0,75 16X2X0,75 16X2X0,75 20X2X0,75 20X2X0,75 24X2X0,75 24X2X0,75 colour bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu CU kg/km 20 20 35 35 65 65 95 95 125 125 155 155 185 185 245 245 305 305 365 365 DA mm 7,9 7,9 10,6 10,6 11,8 11,8 13,6 13,6 14,6 14,6 16,1 16,1 17 17,1 19,1 18,9 21,5 21,5 23,2 23,2 300 V 2000 V 24,6 Ohm/km 75 nF/km core A: black, core B: white with number bare copper fine stranded, class 5 polyethylene PVC TM1 VDE 0482-332-1-2/IEC 60332-1 7,5 x DA -30 - +50 C -5 - +50 C weight ca. kg/km 72 72 127 127 167 167 215 215 262 262 308 308 353 353 443 443 523 523 615 615 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 121 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

RE-2Y(St)Yv 0,75 qmm

>>> Instrumentation cable


Power cables 1 up to 30 kV

RE-2Y(St)Yv 1,3 qmm

Telecommunication Cables and Cords


300 V 2000 V 14,3 Ohm/km 100 nF/km core A: black, core B: white with number bare copper fine stranded, class 5 polyethylene PVC TM1 VDE 0482-332-1-2/IEC 60332-1 7,5 x DA -30 - +50 C -5 - +50 C colour bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bu bk bk CU kg/km 31 31 62 62 114 114 168 168 218 218 322 322 426 426 684 684 44 44 30 95 DA mm 9,4 9,4 11,7 11,7 13,5 13,5 16,1 16,1 17,1 17,1 19,3 19,3 22,1 22,1 26,5 26,5 9,7 9,7 10,2 13,6 weight ca. kg/km 102 102 161 161 230 230 310 310 376 376 515 515 654 654 951 951 111 111 117 215 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, in outdoor and direct burial in earth.

nominal voltage U test voltage conductor resistance operating capacity

Building Wires

core identification conductor material conductor construction insulation sheathing material flame retardant bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 100796 100828 100703 100829 100797 100830 100798 100831 100799 100832 100800 100833 100801 100834 100802 100835 100803 100836 100778 100788 type 01X2X1,3 01X2X1,3 02X2X1,3 02X2X1,3 04X2X1,3 04X2X1,3 06X2X1,3 06X2X1,3 08X2X1,3 08X2X1,3 12X2X1,3 12X2X1,3 16X2X1,3 16X2X1,3 24X2X1,3 24X2X1,3 01X3X1,3 01X3X1,3 02X2X0,5 06X2X0,75

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

> 122 <

>>> www.faberkabel.de <<<

Industrial Telecommunication Cables and Cords electronic cable <<<


Application: For signal transmission between electronic devices, in computer systems or process control units. For installation in dry and wet rooms. standard loop resistance operating capacity nominal voltage U test voltage core identification conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 100106 100484 100497 100107 100496 100108 100481 100109 101055 100110 100482 100111 100483 100112 100113 100850 100114 100115 100116 100117 100595 100599 type 02X2X0,8 02X2X0,8 03X2X0,8 04X2X0,8 04X2X0,8 08X2X0,8 08X2X0,8 12X2X0,8 12X2X0,8 16X2X0,8 16X2X0,8 20X2X0,8 20X2X0,8 24X2X0,8 32X2X0,8 32X2X0,8 40X2X0,8 48X2X0,8 80X2X0,8 100X2X0,8 08X3X0,8 08X3X0,8 colour gy bu gy gy bu gy bu gy bu gy bu gy bu gy gy bu gy gy gy gy bu gy CU kg/km 25 25 35 45 45 85 85 126 126 166 166 206 206 246 327 327 407 488 809 1015 126 126 DA mm 6,9 6,9 8,2 9,1 9,1 11,5 11,5 14 14 15,5 15,5 16,5 16,5 19 21 20 22,5 26,6 31 32 VDE 0815 73,2 Ohm/km 100 nF/km 225 V colours + rings bare copper solid, class 1 PVC TI1 PVC TM1 VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C 7,5 x DA weight ca. kg/km 60 60 90 96 96 158 158 235 235 295 295 355 355 430 555 538 670 740 1290 1495 235 235 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. 500 V

>>> www.faberkabel.de <<<

> 123 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

JE-Y(St)Y

>>> Industrial electronic cable


Power cables 1 up to 30 kV

JE-Y(St)Y ... FR

Telecommunication Cables and Cords


73,2 Ohm/km 100 nF/km 1,1 dB/km 225 V 2000 V bare copper solid, class 1 PVC TI1 special PVC-compound VDE 0482-266-2-4/ IEC 60332-3-24 Application: For signal transmission between electronic devices, in computer systems or process control units. For installation in dry and wet rooms.

loop resistance operating capacity attenuation at 800 Hz nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant

Flexible Cables

Building Wires

bending radius, moved 15 x DA application bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 100851 100852 100853 100854 100855 100856 type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 16X2X0,8 20X2X0,8 7,5 x DA -30 - +70 C -5 - +50 C colour gy gy gy gy gy gy CU kg/km 25 45 85 126 166 206 DA mm 6,5 8 10,5 11,5 12,5 16,5 weight ca. kg/km 60 90 150 200 260 315 packaging dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Cable with circuit integrity

JE-LiYCY
standard nominal voltage U test voltage core identification operating capacity attenuation at 800 Hz conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation p/n 100125 100230 100126 100234 100127 100231 100128 100248 100202 100194 100130 type 02X2X0,5 02X2X0,5 04X2X0,5 04X2X0,5 08X2X0,5 08X2X0,5 12X2X0,5 12X2X0,5 16X2X0,5 16X2X0,5 20X2X0,5 VDE 0815 225 V 500 V colours + rings 100 nF/km 1,1 dB/km bare copper fine stranded, class 5 PVC PVC VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C 7,5 x DA colour gy bu gy bu gy bu gy bu gy bu gy CU kg/km 48 48 84 84 140 140 193 193 243 243 292 DA mm 8,1 8,1 10,1 10,1 13,5 13,5 15,5 15,5 17,5 17,5 20,1 weight ca. kg/km 81 81 137 137 194 194 307 307 375 375 461 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For signal transmission between electronic devices, in computer systems or process control units with increased requirements to electromagnetic compatibility. For installation in dry and wet rooms.

Technical Appendix

Other

Conductor ropes

LAN cables

> 124 <

>>> www.faberkabel.de <<<

Industrial Telecommunication Cables and Cords electronic cable <<<


Power cables 1 up to 30 kV

JE-LiYCY

p/n 100249 100131 100250 100132 100251 100133

type 20X2X0,5 24X2X0,5 24X2X0,5 32X2X0,5 32X2X0,5 40X2X0,5

colour bu gy bu gy bu gy

JE-LiHCH
Application: For signal transmission between electronic devices, in computer systems or process control units with increased requirements to electromagnetic compatibility. core identification operating capacity nominal voltage UO test voltage conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation p/n 100556 100557 100558 100742 100743 100744 101009 100745 100746 101093 type 02X2X0,5 04X2X0,5 08X2X0,5 12X2X0,5 16X2X0,5 20X2X0,5 24X2X0,5 32X2X0,5 40X2X0,5 48X2X0,5 colour gy gy gy gy gy gy gy gy gy gy CU kg/km 48 84 152 193 243 292 342 435 531 665 DA mm 9,1 10,3 13,3 15,6 17,1 18,5 20,8 23,5 25,9 colours + rings 120 nF/km 250 V 1,2 kV bare copper fine stranded, class 5 FRNC compound HI1

70 % FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 no -30 - +70 C -5 - +70 C 7,5 x DA weight ca. kg/km 92 155 250 315 389 457 556 680 823 988

>>> www.faberkabel.de <<<

> 125 <

Technical Appendix

dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Other

packaging

Conductor ropes

LAN cables

70 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

CU kg/km 292 342 342 435 435 531

DA mm 20,1 21,1 21,1 23,1 23,1 25,5

weight ca. kg/km 461 570 570 690 690 831

packaging dr. dr. dr. dr. dr. dr.

>>> Insulated wires


Power cables 1 up to 30 kV

YR

Telecommunication Cables and Cords


100 V 300 nF/km bare copper solid, class 1 PVC PVC -5 - +70 C 7,5 x DA colour wh wh wh wh wh gy wh wh wh wh wh wh wh CU kg/km 9,6 14,4 19,2 24 28,8 38 38 48 58 67 77 96 115 DA mm 4,2 4,8 5,2 5,8 6,1 6,3 6,3 7,4 7,7 8,2 8,4 9,4 10,4 weight ca. kg/km 24 32 47 46 52 70 70 92 106 107 124 160 220 packaging c. 100, dr. c. 100 dr., c. 100, c. 50 c. 100 c. 100 c. 50 c. 100, c. 50 c. 100 dr., c. 100 dr., c. 100 dr., c. 100 c. 100 dr., c. 100 Application: For fixed installation on or under plaster. Core identification: bk, bu, br, ye, gn, vio, wh, tr, gr

nominal voltage U operating capacity conductor material conductor construction insulation sheathing material max. operating temperature, fixed bending radius, fixed installation p/n 031841 031656 031424 032934 032080 031193 032124 031842 031438 032935 032138 032936 031435 type 02X0,8 03X0,8 04X0,8 05X0,8 06X0,8 08X0,8 08X0,8 10X0,8 12X0,8 14X0,8 16X0,8 20X0,8 24X0,8

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 126 <

>>> www.faberkabel.de <<<

Control and Electronic Cable <<<


Power cables 1 up to 30 kV

cooperative

Content

Bus cables

174

>>> www.faberkabel.de <<<

> 127 <

Technical Appendix

Electronic cable LiYY LIYY/EB LiYCY LiYCY/EB Li2YCYv Li2YCY PiMF Li12YC11Y LiHCH

163 163 165 165 169 170 170 171 172

Other

Conductor ropes

Control cable Y-JZ Y-JB Y-OZ Y-OB CY-JZ CY-OZ CY-JB H-JZ H-OZ CH-JZ CH-OZ H05VV5-F H05VVC4V5-K F-CY-JZ F-CY-OZ Y-JZ 600 Y-OZ 600 CY-JZ 600 CY-OZ 600 SY-JZ 2YSL(St)CYv H07VVH6-F AD 100 P AD 100 F-CP SL AD 300 Y SL AD 300 CY SL AD 300 P SL AD 300 CP SL AD 400 CP 05VV2SV

128 128 130 132 133 134 135 136 137 139 139 141 141 143 145 146 147 148 149 150 150 152 153 154 155 156 157 158 159 160 161

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

Y-JZ
core identification protective conductor nominal voltage U nominal voltage UO test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material bending radius, fixed installation yes 500 V 300 V 2 kV

Control and Electronic Cable


gn-ye + numbers Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneeringt. The cable is resistant against most usual chemicals, oil and grease.

Building Wires

bare copper fine stranded, class 5 PVC TI1 70 C PVC TM2 4 x DA

Flexible Cables

bending radius, moved 15 x DA application max. operating temperature, fixed temperature, moved/ during installation flame retardant p/n 030643 030644 030645 030647 030648 030649 030650 030651 030604 031992 030653 030654 030860 030655 030656 030657 030658 030659 031196 030102 030104 030105 030106 030107 031197 030861 030109 030110 030111 030112 031198 030859 030114 031300 030115 030116 031199 030117 030118 030119 030973 031200 030121 type 03X0,5 04X0,5 05X0,5 07X0,5 08X0,5 10X0,5 12X0,5 14X0,5 18X0,5 19X0,5 21X0,5 25X0,5 30X0,5 34X0,5 40X0,5 42X0,5 50X0,5 61X0,5 65X0,5 03X0,75 04X0,75 05X0,75 06X0,75 07X0,75 08X0,75 09X0,75 10X0,75 12X0,75 15X0,75 18X0,75 20X0,75 21X0,75 25X0,75 30X0,75 32X0,75 34X0,75 41X0,75 42X0,75 50X0,75 61X0,75 65X0,75 80X0,75 03X1 -20 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 14,4 19,2 24 33,6 38 48 58 67 86 91,2 101 120 144 163 192 202 240 293 312 22 29 36 43,2 50,4 58 64,8 72 86,4 108 130 144 151,2 180 216 230 245 295 302 360 439 468 576 29 DA mm 5,7 6,1 6,6 7 7,4 9,1 9,6 9,8 11,1 11,1 11,3 13,4 14 14,4 15,5 15,6 17,5 19,1 21,4 6,1 6,6 7,2 7,3 7,7 8 9,3 10,1 10,4 11,5 12,1 12,8 13,8 14,9 15,3 15,8 16,9 17,2 18 20,3 21,7 24,7 26,5 6,5 weight ca. kg/km 47 58 75 93 115 142 150 172 216 187 249 257 303 398 452 471 510 670 714 66 78 91 108 124 143 162 185 191 229 283 288 293 388 445 467 546 668 673 730 890 948 1165 68 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr. dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 128 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 030122 030123 031318 030125 030862 030863 030128 030129 030130 031201 030131 030960 030132 031202 030134 030135 030864 030137 030139 031203 030455 030981 031204 034660 030141 030142 030143 031957 030144 030716 030704 030531 030776 030148 030149 031205 030150 031206 031207 030152 030153 030154 030155 030156 030456 031208 031209 031401 030158 030159 030160 030161 034781 030169 030163 031210 030164 031211 031212 030165 030166 031213 030576 030167 030570 031214 type 04X1 05X1 06X1 07X1 08X1 09X1 10X1 12X1 14X1 16X1 18X1 19X1 20X1 21X1 25X1 34X1 41X1 42X1 50X1 56X1 61X1 65X1 80X1 100X1 03X1,5 04X1,5 05X1,5 06X1,5 07X1,5 08X1,5 09X1,5 10X1,5 11X1,5 12X1,5 14X1,5 16X1,5 18X1,5 20X1,5 21X1,5 25X1,5 32X1,5 34X1,5 42X1,5 50X1,5 61X1,5 65X1,5 80X1,5 100X1,5 03X2,5 04X2,5 05X2,5 07X2,5 08X2,5 12X2,5 14X2,5 16X2,5 18X2,5 20X2,5 21X2,5 25X2,5 34X2,5 40X2,5 42X2,5 50X2,5 61X2,5 03X4 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 38,4 48 57,6 67 76,8 86,4 96 115,2 134,4 154 173 183 192 201,6 240 326,4 395 403 480 538 586 624 768 960 43,2 58 72 86,4 101 115,2 129,6 144 158,4 173 202 230 259,2 288 302 360 461 490 605 720 878,4 936 1152 1440 72 96 120 168 192 288 336 384 432 480 504 600 816 960 1008 1200 1464 115,2 DA mm 7,1 7,8 8,3 8,3 9 10 11,1 11,3 11,8 12,8 13,7 13,9 14,1 14,1 16,5 18,5 20,8 20,9 22,4 23,2 24,3 25,7 27,5 28,3 7,4 8,1 9,1 9,5 10 10,9 12,3 13,1 13,3 13,5 14,2 15,2 16,2 16,5 17,5 19,6 21,8 22,3 23,6 25,9 27,4 28,5 30,6 35,2 9,2 10,2 11,2 12,9 13,4 16,8 18,4 19,1 19,8 20,8 21,5 24,2 26,8 26,9 27,1 32,4 34,4 10,6 weight ca. kg/km 85 110 135 146 148 178 210 232 271 300 328 346 357 444 531 618 715 731 843 962 1080 1150 1416 1602 95 117 152 183 192 205 220 252 295 312 349 403 456 507 573 638 820 860 1052 1296 1502 1600 1970 2460 148 236 263 298 339 522 588 665 749 832 928 1024 1513 1660 1800 2200 2553 235 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr. dr., c. 100, c. 50 dr. dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr. dr. dr., c. 100, c. 50 dr., c. 50 dr., c. 50 dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

Y-JZ

>>> www.faberkabel.de <<<

> 129 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

Y-JZ
p/n 030546 030593 030597 031958 031215 030602 030594 030598 032316 034556 031216 030590 030595 030607 030591 030596 030732 030600 030608 031217 030601 030606 031913 031337 031704 030592 type 04X4 05X4 07X4 12X4 03X6 04X6 05X6 07X6 19X6 03X16 03X10 04X10 05X10 07X10 04X16 05X16 07X16 04X25 05X25 07X25 04X35 05X35 05X50 07X35 03X50 04X50

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 154 192 269 460,8 172,8 230 288 403 1094 461 288 384 480 672 614 768 1075 960 1200 1680 1344 1680 2400 2352 1440 1920 DA mm 10,8 11,9 14,4 19,5 12,2 13 14,9 16,2 26,7 18 15,8 16,2 18,8 20,4 19,8 22,5 24,1 23,4 27 31,2 28,1 30,6 37 38,3 27,9 34,9 weight ca. kg/km 299 363 488 790 415 480 583 782 1600 827 682 737 914 1191 1087 1370 1779 1582 1998 2597 2106 2485 3936 2998 2550 2943 packaging dr., c. 100, c. 50 dr., c. 50, c. 100 dr., c. 50 dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Y-JB
core identification protective conductor nominal voltage U nominal voltage UO test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material bending radius, fixed installation colours acc. VDE 0293 (HD308) yes 500 V 300 V 2 kV bare copper fine stranded, class 5 PVC TI1 70 C PVC TM2 4 x DA Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneeringt. The cable is resistant against most usual chemicals, oil and grease.

Conductor ropes

LAN cables

Cable with circuit integrity

bending radius, moved 15 x DA application max. operating temperature, fixed temperature, moved/ during installation flame retardant -20 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy CU kg/km 14,4 19,2 24 22 29 36 29 38,4 DA mm 5,7 6,1 6,6 6,1 6,6 7,2 6,5 7,1 weight ca. kg/km 47 58 75 66 78 91 68 85 packaging dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50

Other

p/n 030865 030866 030867 030612 030616 030620 030613 030617

type 03X0,5 04X0,5 05X0,5 03X0,75 04X0,75 05X0,75 03X1 04X1

Technical Appendix

> 130 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 030621 034843 030614 030618 030622 030615 030619 030623 034217 031218 030695 030694 034218 031219 030783 030693 034219 031338 030784 031223 034220 034221 030785 031222 034222 030692 031221 034223 030786 031220 034224 030787 034225 034226 030788 034228 031339 034227 034229 034230 031340 034231 034232 type 05X1 10X1 03X1,5 04X1,5 05X1,5 03X2,5 04X2,5 05X2,5 07X2,5 03X4 04X4 05X4 07X4 03X6 04X6 05X6 07X6 03X10 04X10 05X10 07X10 03X16 04X16 05X16 03X25 04X25 05X25 03X35 04X35 05X35 03X50 04X50 05X50 03X70 04X70 03X95 04X95 05X70 05X95 03X120 04X120 04X150 04X185 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 48 96 43,2 58 72 72 96 120 168 115,2 154 192 269 172,8 230 288 403,2 288 384 480 672 461 614 768 720 960 1200 1080 1344 1680 1440 1920 2400 2016 2688 2736 3648 3360 4560 3456 4608 5760 7104 DA mm 7,8 10,6 7,4 8,1 9,1 9,2 10,2 11,2 11,9 10,6 10,8 11,9 16,8 12,2 13 14,9 19,1 15,8 16,2 18,8 23 23,1 19,8 22,5 23,3 23,4 27 26,6 28,1 30,6 31 34,9 38,6 37,1 36 41,3 41,4 46,3 50,2 46,6 51 58,9 65,8 weight ca. kg/km 110 195 95 117 152 148 236 263 321 235 299 363 484 415 480 583 638 682 737 914 1082 912 1087 1370 1388 1582 1998 1766 2106 2485 2556 2943 3936 3182 4050 4676 5626 5122 6266 5628 6994 7570 9102 packaging dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

Y-JB

>>> www.faberkabel.de <<<

> 131 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

Y-OZ
core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material bending radius, fixed installation numbers no 300 V 500 V 2 kV

Control and Electronic Cable


Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneeringt. The cable is resistant against most usual chemicals, oil and grease.

Building Wires

bare copper fine stranded, class 5 PVC TI1 70 C PVC TM2 4 x DA

Flexible Cables

bending radius, moved 15 x DA application max. operating temperature, fixed temperature, moved/ during installation flame retardant p/n 030642 030868 030869 030870 030871 030103 030547 030548 030549 030633 031595 030168 030624 030627 030630 030634 032011 031834 030140 030625 030628 030631 030635 031150 030626 030629 030632 type 02X0,5 03X0,5 04X0,5 05X0,5 07X0,5 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 15X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 02X2,5 03X2,5 04X2,5 05X2,5 -20 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 9,6 14,4 19,2 24 33,6 15 22 29 36 50,4 108 19,2 29 38,4 48 67 115,2 173 29 43,2 58 72 101 48 72 96 120 DA mm 5,4 5,7 6,1 6,6 7 5,8 6,1 6,6 7,2 7,7 6,2 6,5 7,1 7,8 8,3 11,1 13,4 7 7,4 8,1 9,1 10 8,7 9,2 10,2 11,2 weight ca. kg/km 40 47 58 75 93 56 66 78 91 124 229 57 68 85 110 148 232 300 78 95 117 152 192 115 148 236 263 packaging dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100 dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 132 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneeringt. The cable is resistant against most usual chemicals, oil and grease. core identification protective conductor nominal voltage U nominal voltage UO test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material bending radius, fixed installation colours acc. VDE 0293 (HD308) no 500 V 300 V bare copper fine stranded, class 5 PVC TI1 70 C PVC TM2 4 x DA 2 kV

Control cable <<<


Power cables 1 up to 30 kV

Y-OB

bending radius, moved 15 x DA application max. operating temperature, fixed temperature, moved/ during installation flame retardant p/n 031017 031013 030637 031314 033440 030638 031426 030639 031427 031224 031810 031313 type 02X0,5 03X0,5 02X0,75 03X0,75 04X0,75 02X1 03X1 02X1,5 03X1,5 02X2,5 02X4 03X4 colour gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 9,6 14,4 15 22 29 19,2 29 29 43,2 48 76,8 115,2 DA mm 5,4 5,7 5,8 6,1 6,6 6,2 6,5 7 7,4 8,7 10,1 11,8 -20 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 40 47 56 66 67,28 57 68 78 95 115 187 235 packaging dr. dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr. dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 133 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

CY-JZ
core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation inner sheath screen coverage sheathing material bending radius, fixed installation yes 300 V 500 V 2 kV

Control and Electronic Cable


gn-ye + numbers Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease.

Building Wires

bare copper fine stranded, class 5 70 C PVC TI2 PVC 70 % PVC TM2 6 x DA

Flexible Cables

Telecommunication Cables and Cords

bending radius, moved 20 x DA application temperature, moved/ during installation max. operating temperature, fixed flame retardant p/n 030421 030422 030436 030423 030437 030438 030439 030440 030532 030562 033742 030577 030424 030425 030443 030444 030445 030446 030447 030448 030533 030449 030563 030426 030427 030420 034516 030428 030451 030429 030430 030452 030453 030454 030578 030431 030733 030534 030535 030579 type 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 34X0,75 42X0,75 50X0,75 51X0,75 61X0,75 03X1 04X1 05X1 07X1 12X1 18X1 25X1 34X1 42X1 50X1 61X1 03X1,5 04X1,5 05X1,5 06X1,5 07X1,5 12X1,5 18X1,5 25X1,5 34X1,5 42X1,5 50X1,5 61X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 -5 - +70 C -20 - +70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 69,2 87 95,1 111 180,2 243 312 413 445 535 535 619,8 77 97 108 128,3 210 286 388,5 505 578 688 770 102 117 146 134 196 280 389 535 702 845 1006 1075 148 171,5 213 288 477,3 DA mm 8,2 8,8 9,4 9,9 12,5 14,1 16,6 18,5 20 21,6 21,6 23,8 8,8 9,3 9,9 10,5 13,3 15,3 18,1 20,2 21,5 23,5 25 9,6 10,3 11 11,2 11,7 15,2 17,6 20,9 23,3 24,6 27,1 28,5 11,3 12,5 13,4 14,6 18,8 weight ca. kg/km 145 163 183 233 384 492 671 822 1002 1154 1180 1435 156 178 209 255 426 552 766 973 1110 1322 1596 200 247 304 337 393 615 793 1116 1376 1596 1881 2246 211 298 326 498 796 packaging dr. dr., c. 100 dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr. dr. dr. dr., c. 100 dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 50 dr. dr. dr., c. 100

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 134 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 030581 031319 031312 034517 031336 031344 031335 031345 031320 031346 031347 031348 type 18X2,5 04X4 05X4 03X6 04X6 05X6 04X10 05X10 04X16 05X16 04X25 05X25 colour gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 572 290 328 240 360 441 535 714 910 1050 1310 1486 DA mm 21,9 12,7 13,9 13,7 15,7 16,1 19,2 22,9 22,5 25,6 26,4 36,2 weight ca. kg/km 1080 351 480 415 553 600 901 1048 1122 1402 1699 2124 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

CY-JZ

CY-OZ
Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease. core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation inner sheath screen coverage sheathing material bending radius, fixed installation numbers no 300 V 500 V 2 kV bare copper fine stranded, class 5

PVC TI2 PVC 70 % PVC TM2 6 x DA

bending radius, moved 20 x DA application temperature, moved/ during installation max. operating temperature, fixed flame retardant p/n 031341 031599 031342 031746 031343 031916 type 02X0,75 03X0,75 02X1 03X1 02X1,5 03X1,5 colour gy gy gy gy gy gy CU kg/km 61,3 69,2 66,5 77 86,4 102 DA mm 8 8,2 8,6 8,8 9,2 8,7 -5 - +70 C -20 - +70 C VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 108 145 143 156 189 200 packaging dr., c. 100 dr. dr., c. 100 dr. dr., c. 100 dr.

>>> www.faberkabel.de <<<

> 135 <

Technical Appendix

Other

Conductor ropes

LAN cables

70 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

CY-JB
core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation inner sheath screen coverage sheathing material bending radius, fixed installation yes 300 V 500 V 2 kV

Control and Electronic Cable


colours acc. VDE 0293 (HD308) Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease.

Building Wires

bare copper fine stranded, class 5 70 C PVC TI2 PVC 70 % PVC TM2 6 x DA

Flexible Cables

Telecommunication Cables and Cords

bending radius, moved 20 x DA application temperature, moved/ during installation max. operating temperature, fixed flame retardant p/n 031669 031670 031671 031672 031673 031674 031675 031586 031587 031676 031734 031733 type 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 -5 - +70 C -20 - +70 C VDE 0482-332-1-2/IEC 60332-1 colour gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 290 360 535 910 1310 1693 2342 3090 4060 5299 7033 9023 DA mm 12,7 15,7 19,2 22,5 34,1 35,6 41,1 42,9 44,7 49,2 70,1 62,1 weight ca. kg/km 320 470 740 1450 1520 2010 2840 3880 5070 6430 7650 9300 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 136 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Halogen free and LSOH control cable for multiple purposes in control and measurement circuits with increased requirements to electromagnetic compatibility. core identification protective conductor nominal voltage UO nominal voltage U conductor construction conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 031620 031621 031622 031623 031624 031625 031626 032945 032946 032947 032948 032949 032950 031627 031628 031629 031630 032951 032953 031631 032954 031632 032955 031633 032956 032957 032958 032959 032960 032961 032962 031634 031635 031636 031637 032964 032965 031638 032966 031639 032967 031640 032968 032969 032970 032971 032972 type 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 34X0,75 37X0,75 41X0,75 42X0,75 50X0,75 61X0,75 03X1 04X1 05X1 07X1 08X1 10X1 12X1 16X1 18X1 20X1 25X1 34X1 37X1 41X1 42X1 50X1 61X1 65X1 03X1,5 04X1,5 05X1,5 07X1,5 08X1,5 10X1,5 12X1,5 16X1,5 18X1,5 20X1,5 25X1,5 34X1,5 37X1,5 50X1,5 61X1,5 65X1,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 22 29 36 50,4 86,4 130 180 245 260 296 302 360 439 29 38,4 48 67 77 96 115,2 154 173 192 240 326 355 394 403 480 586 628 43,2 58 72 101 115 144 173 230 259,2 288 360 490 533 720 878 936 DA mm 6 6,5 7 7,5 10,2 11,9 14,6 16,4 17,2 17,6 17,8 19,8 20,9 6,4 7 7,8 8,1 9,4 10,4 11,1 12 13,4 13,5 16,2 17,4 18,4 18,9 18,9 21 22,2 22,8 7,3 7,8 8,9 9,8 10,6 11,7 13,2 13,8 15,9 15,2 19,2 19,8 20,2 23,7 25,3 26 gn-ye + numbers yes 300 V 500 V

Control cable <<<


Power cables 1 up to 30 kV

H-JZ

bare copper FRNC-compound HI2 70 C FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C weight ca. kg/km 66 78 91 124 191 283 388 641 795 800 715 815 1028 68 85 110 148 200 245 232 363 328 438 531 688 833 925 835 978 1140 1304 95 117 152 192 278 309 312 415 456 585 638 890 1140 1410 1630 1810 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 137 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

fine stranded, class 5

>>> Control cable


Power cables 1 up to 30 kV

H-JZ
p/n 031648 031649 031650 031651 032973 032974 031645 032975 031646 032976 031647 032977 031660 032654 031661 032979 032980 032981 032982 032983 032986 032655 031662 032987 032989 032990 032991 032992 032994 032995 032996 032997 032998 031663 032999 033000 033001 033002 033003 033004 033005 033006 033007 033008 033009 033010 033011 033012 033013 type 03X2,5 04X2,5 05X2,5 07X2,5 08X2,5 10X2,5 12X2,5 16X2,5 18X2,5 20X2,5 25X2,5 30X2,5 03X4 04X4 05X4 07X4 08X4 10X4 12X4 16X4 03X6 04X6 05X6 07X6 03X10 04X10 05X10 07X10 03X16 04X16 05X16 07X16 03X25 04X25 05X25 03X35 04X35 05X35 03X50 04X50 05X50 03X70 04X70 05X70 03X95 04X95 05X95 03X120 04X120

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 72 96 120 168 192 240 288 384 432 480 600 720 115,2 154 192 269 307 384 461 614 173 230,4 288 403,2 288 384 480 672 461 614 768 1075 720 960 1200 1008 1344 1680 1440 1920 2400 2016 2688 3360 2736 3648 4560 3456 4608 DA mm 9 10 11 12,7 13,2 14,7 16,5 17,5 18,4 18,7 23,8 23,7 11,8 11,7 13,2 16 17,8 19,6 20,2 22,8 12,7 14,1 16,5 17,6 16,2 18 19,8 22,5 18,7 20,6 23,5 26,2 24,5 26 30,8 29,8 33,7 37,7 33,8 38 42,1 40,2 44,2 48,5 46,6 51,2 56,3 49,8 54,8 weight ca. kg/km 148 236 263 298 378 444 522 730 749 1070 1024 1280 235 305 363 468 603 798 984 1350 390 465 583 782 750 746 917 1283 998 1089 1285 1835 1238 1582 1920 1664 1980 2765 2678 2824 4133 3339 4295 5715 4914 5817 7278 5515 7350 packaging dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr. dr. dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 138 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Halogen free and LSOH control cable for multiple purposes in control and measurement circuits with increased requirements to electromagnetic compatibility. core identification protective conductor nominal voltage UO nominal voltage U conductor construction conductor material insulation maximum temperature at conductor sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 032885 032952 032963 032939 032978 032985 032988 032993 034935 type 02X0,75 02X1 02X1,5 02X2,5 02X4 02X6 02X10 02X16 02X0,5 colour gy gy gy gy gy gy gy gy gy CU kg/km 14,4 19,2 29 48 77 115,2 192 307 9,6 DA mm 5,5 5,7 6,3 7,7 9,8 12 15 17,3 5,1 numbers no 300 V 500 V

Control cable <<<


Power cables 1 up to 30 kV

H-OZ

bare copper FRNC-compound HI2 70 C FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C weight ca. kg/km 33 58 87 124 195 258 490 665 38 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr.

Application: LSOH control cable for multiple purposes in control and measurement circuits with increased requirements to electromagnetic compatibility. For indoor use only.

core identification protective conductor nominal voltage U nominal voltage UO conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation

gn-ye + numbers yes 500 V 300 V bare copper strand fine stranded, class 5 FRNC-compound HI2 70 C

FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C weight ca. kg/km 55 66 80 108 162 227 317 70 80 100 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 139 <

Technical Appendix

032741 032742 032743 032744 032745 032746 032747 032749 032750 032751

03X0,5 04X0,5 05X0,5 07X0,5 12X0,5 18X0,5 25X0,5 03X0,75 04X0,75 05X0,75

gy gy gy gy gy gy gy gy gy gy

Other

p/n

type

colour

CU kg/km 50 55 66 80,5 139 156,2 250 58 64 77,4

DA mm 6,2 6,6 7,2 8,6 9,9 11,9 13,7 6,7 8 8,3

Conductor ropes

70 %

LAN cables

Cable with circuit integrity

CH-JZ

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

fine stranded, class 5

>>> Control cable


Power cables 1 up to 30 kV

CH-JZ
p/n 032752 032753 032159 032160 032755 032756 032757 032758 032759 032760 032761 031889 031867 031860 031890 031891 031892 031893 032763 031819 031852 031854 031973 032765 031843 032161 032766 032768 031856 031853 032769 032771 031820 032772 032773 031857 032774 032775 032776 031858 032777 032778 032040 032779 032780 032129 032781 032782 032656 032783 032784 032657 032785 032786 032787 type 07X0,75 12X0,75 18X0,75 25X0,75 03X1 04X1 05X1 07X1 12X1 18X1 25X1 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 03X4 04X4 05X4 07X4 03X6 04X6 05X6 07X6 03X10 04X10 05X10 07X10 04X16 05X16 07X16 03X25 04X25 05X25 03X35 04X35 05X35 03X50 04X50 05X50 03X70 04X70 05X70 03X95 04X95 05X95 03X120 04X120

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 102 177 245 276 65,3 78,1 91 117 188 286 389 77 96,2 125 159 254,5 367,7 492,4 149 174,2 200,8 288 441 178,1 248 328 388 280 362 453 542 385 558 640 850 910 1051 1470 900 1289 1486 1130 1690 2015 1766 2325 2781 2218 3089 3696 3010 4013 5016 3802 5067 DA mm 9,5 11,3 14,8 15,8 6,9 7,5 8,5 9,9 11,7 13,9 16,4 7,5 8,2 8,9 11,3 13 15,6 19,1 9,5 10 11,5 13,8 18,2 10,7 11,9 13,1 15,1 12,5 14,2 16,2 19,2 15,9 17,8 19,6 21,6 20,8 22,9 25,2 24,8 26,2 29,4 27,9 33,5 33,8 35,7 39,2 43,3 41,4 45,3 49,6 47,7 52,4 57,5 51 56,1 weight ca. kg/km 133 203 284 380 80 98 121 160 245 376 502 119 125 182 232 360 507 694 160 194 386 498 796 249 288 337 488 347 399 770 670 501 698 828 1254 987 1207 1816 1214 1592 2002 1622 2380 2664 2471 3003 3882 3840 4939 6572 5651 6690 8370 6342 8453 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 140 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: LSOH control cable for multiple purposes in control and measurement circuits with increased requirements to electromagnetic compatibility. For indoor use only. core identification protective conductor nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 032740 032748 032754 031888 032762 type 02X0,5 02X0,75 02X1 02X1,5 02X2,5 colour gy gy gy gy gy CU kg/km 35 45 50 63,3 98 DA mm 5,8 6,4 6,6 8,2 8,5 numbers no 300 V 500 V bare copper strand fine stranded, class 5 FRNC-compound HI2 70 C 70 % FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +70 C -5 - +70 C weight ca. kg/km 47 58 64 97 132 packaging dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

CH-OZ

H05VV5-F
Application: Flexible power, process control and instrumentation cable for industry and machinery environment. The cable is resistant against most usual chemicals, oil and grease. standard core identification nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material bending radius, fixed installation VDE 0281-13 gn-ye + numbers 300 V 500 V 2 kV bare copper fine stranded, class 5 PVC TI2 70 C PVC TM2

bending radius, moved 12,5 x DA application temperature, moved/ during installation max. operating temperature, fixed oil resistant acc. to EN 60811-2-1 flame retardant p/n 031478 031479 031480 031481 031482 031483 031484 type 03X0,5 04X0,5 05X0,5 07X0,5 08X0,5 12X0,5 18X0,5 colour gy gy gy gy gy gy gy CU kg/km 14,4 19,2 24 33,6 38,4 57,6 86,4 DA mm 6,5 7,1 7,7 9,5 10,1 11,7 13,6 -5 - +70 C -40 - +70 C yes VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 51 62 75 117 134 174 248 packaging

>>> www.faberkabel.de <<<

> 141 <

Technical Appendix

dr. dr. dr. dr. dr. dr. dr.

Other

Conductor ropes

4 x DA

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

H05VV5-F
p/n 031485 031486 031487 031488 031489 031490 031491 031492 031493 031494 031495 031496 031497 031498 031499 031500 031501 031502 031503 031504 031505 031506 031507 031508 031509 031510 031511 031512 031513 031514 031515 031516 031517 031518 031519 031520 031521 031522 031523 031524 031525 031526 031527 031528 031529 031530 031531 031532 031533 031534 031535 031536 031537 031538 031539 031972 031540 031541 031542 031543 031544 031545 031546 031547 031548 031549 type 21X0,5 25X0,5 30X0,5 32X0,5 34X0,5 50X0,5 52X0,5 60X0,5 03X0,75 04X0,75 05X0,75 07X0,75 09X0,75 12X0,75 15X0,75 18X0,75 25X0,75 32X0,75 34X0,75 41X0,75 42X0,75 50X0,75 52X0,75 60X0,75 03X1 04X1 05X1 07X1 09X1 12X1 14X1 18X1 25X1 32X1 34X1 41X1 50X1 52X1 56X1 60X1 03X1,5 04X1,5 05X1,5 07X1,5 09X1,5 12X1,5 14X1,5 18X1,5 25X1,5 32X1,5 34X1,5 42X1,5 50X1,5 52X1,5 60X1,5 61X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 25X2,5 32X2,5 34X2,5 42X2,5

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 100,8 120 144 153,6 163,2 240 249,6 288 21,6 28,8 36 50,4 64,8 86,4 108 129,6 180 230,4 244,8 295,2 302,4 360 374,4 432 28,8 38,4 48 67,2 86,4 115,2 134,4 172,8 240 307,2 326,4 393,6 480 499,2 537,6 576 43,2 57,6 72 100,8 129,6 172,8 201,6 259,2 360 460,8 489,6 604,8 720 748,8 864 878 72 96 120 168 288 432 600 768 816 1008 DA mm 14,9 16,7 17,3 17,9 19,2 22,3 22,3 23,6 7,2 7,8 9 10,5 12,4 13 14,4 15,1 18,6 20,6 21,3 22,8 23 24,8 25 26,9 7,4 8 9,2 10,8 12,7 13,4 14 16,2 19,8 21,2 22 23,6 26,2 26,4 27 27,8 8 9,2 10 12,2 13,9 14,6 15,4 17,7 21,6 23,2 24,1 26,4 28,8 29 30,5 30,9 9,7 11 12,1 14,2 17,7 21,3 25,9 27,9 28,9 31,6 weight ca. kg/km 297 348 420 448 476 650 676 753 61 75 100 141 160 214 255 306 427 555 590 699 716 807 839 985 71 89 116 166 209 251 297 385 534 658 700 847 993 1010 1087 1165 92 125 155 227 248 330 394 506 700 865 920 1120 1320 1352 1560 1639 146 196 235 343 535 800 1100 1350 1436 1753 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 142 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 031550 031551 031552 034910 type 50X2,5 52X2,5 60X2,5 04G10 colour gy gy gy gy CU kg/km 1200 1248 1440 384 DA mm 34,4 34,6 37,1 18,1 weight ca. kg/km 2070 2180 2515 701 packaging dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

H05VV5-F

H05VVC4V5-K
Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease. standard core identification nominal voltage UO nominal voltage U conductor material conductor construction insulation maximum temperature at conductor inner sheath screen coverage transfer impedance sheathing material bending radius, fixed installation VDE 0281-13 gn-ye + numbers 300 V 500 V bare copper fine stranded, class 5 PVC TI2

PVC 70 % 250 Ohm/km PVC TM2 6 x DA

bending radius, moved 20 x DA application max. operating temperature, fixed temperature, moved/ during installation flame retardant oil resistant acc. to EN 60811-2-1 p/n 033868 033850 033869 033851 033870 033871 type 02X0,5 03X0,5 04X0,5 05X0,5 06X0,5 07X0,5 colour gy gy gy gy gy gy CU kg/km 32 36 58 48 58 86 DA mm 8,1 8,4 9,1 10,1 10,7 11,4 -40 - +70 C -5 - +70 C VDE 0482-332-1-2/IEC 60332-1 yes weight ca. kg/km 90 109 126 156 176 199 packaging

>>> www.faberkabel.de <<<

> 143 <

Technical Appendix

dr. dr. dr. dr. dr. dr.

Other

Conductor ropes

LAN cables

70 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

H05VVC4V5-K
p/n 033874 033875 033852 033876 033971 033972 033973 033974 033975 033976 033977 033978 033979 033980 031453 031454 031455 031456 031457 031458 031459 031460 031461 031462 031463 031464 031465 031466 034937 034968 034969 034955 034956 031467 031468 031469 031470 031471 031472 031473 031741 031474 031475 031476 031477 034737 034738 034739 034668 034885 034886 034887 034888 type 08X0,5 09X0,5 12X0,5 14X0,5 18X0,5 25X0,5 27X0,5 34X0,5 36X0,5 41X0,5 42X0,5 50X0,5 61X0,5 65X0,5 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 03X1 04X1 05X1 07X1 12X1 18X1 25X1 34X1 36X1 48X1 50X1 65X1 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 34X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 25X2,5 07X6 05X10 05X16 05X25 05X35

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 72 80 105 114 170 268 236 298 317 349 349 470 530 563 55 67 79 109 184,5 257,3 318,6 75 86 102 127 198 303,6 411,9 500 511 656 736 914 95 116 130 218 309,7 411,4 546,5 754 148 163 200 288,9 517 598 897 505 604 1030 1420 2020 DA mm 12,5 12,5 13,5 14,2 15,8 18,6 18,6 20,8 20,8 23,1 23,1 25,1 26,8 28,4 9,1 10,3 11 12,4 15,2 18,2 21,5 9,6 10,7 11,4 12,9 16,9 19,4 22,8 24,1 23,8 23,8 28,9 32,4 10,7 11,5 12,1 14,1 18 20,8 25 26,3 12 13,1 14,2 16,3 24,3 25,6 29,3 28,4 24,6 28,4 35,1 39,4 weight ca. kg/km 211 230 280 302 400 554 599 649 620 770 720 966 1122 1198 125 150 180 230 310 470 640 140 170 200 230 410 550 735 920 1001 1270 1290 1510 180 200 235 330 470 680 930 1353 240 290 340 465 748 1051 1380 1031 927 1626 1972 2780 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 144 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease. core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material flame retardant oil resistant acc. to EN 60811-2-1 bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 033293 033294 033295 033297 033298 033300 033303 033308 033312 033314 032857 033322 032133 033324 033326 033332 033333 033336 033339 033340 033341 033345 033346 032876 033347 033350 033266 033357 033361 033365 033366 033367 033371 033372 032136 033373 033375 033376 033379 032137 033383 type 03X0,75 04X0,75 05X0,75 07X0,75 08X0,75 12X0,75 18X0,75 25X0,75 34X0,75 37X0,75 03X1 04X1 05X1 07X1 12X1 25X1 27X1 34X1 41X1 50X1 61X1 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 34X1,5 41X1,5 50X1,5 61X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 04X4 05X4 04X6 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 50 61 72 98 110 151 211 280 370 386 76 80 92 120 186 360 360 454 521 662 710 90 110 125 152 268 373 530 683 734 977 1120 148 174 203 253 441 570 248 331 343 DA mm 6,5 7,1 7,8 8,6 9,4 11,1 12,9 15,6 17,8 18,1 7,4 7,6 7,8 9,1 12,4 18 16,2 20,6 21,4 24,2 27,3 7,7 8,3 9,4 10,7 13,5 15,8 20,3 21,3 22,5 26,7 29,1 9,1 10,2 10,9 13,7 18,2 18,9 12,9 13,2 14,7 gn-ye + numbers yes 300 V 500 V bare copper fine stranded, class 5 PVC 70 C 70 % PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 no 10 x DA -20 - +70 C -5 - +70 C weight ca. kg/km 69 88 120 153 145 220 306 431 521 592 100 117 127 178 275 607 562 746 843 1015 1205 115 149 180 230 354 523 722 950 1071 1303 1705 180 220 270 342 580 879 306 370 422 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. 2 kV

Control cable <<<


Power cables 1 up to 30 kV

F-CY-JZ

>>> www.faberkabel.de <<<

> 145 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

F-CY-JZ
p/n 033384 033388 033389 type 05X6 04X10 05X10

Control and Electronic Cable


colour gy gy gy CU kg/km 441 535 714 DA mm 16,4 18,9 20,7 weight ca. kg/km 506 731 853 packaging dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

F-CY-OZ
core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material flame retardant oil resistant acc. to EN 60811-2-1 bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation numbers no 300 V 500 V 2 kV bare copper fine stranded, class 5 PVC 70 C 70 % PVC DMV 5 VDE 0482-332-1-2/IEC 60332-1 no 10 x DA -20 - +70 C -5 - +70 C colour gy gy gy gy gy gy gy gy CU kg/km 43 53 62 73 98 55 65 98 DA mm 6,2 6,5 7,1 7,8 8,6 6,7 7,3 8,3 weight ca. kg/km 57 66 89 126 156 76 93 141 packaging dr. dr. dr. dr. dr. dr. dr. dr. Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease.

Other

Conductor ropes

LAN cables

Cable with circuit integrity

p/n 032097 032098 032099 032100 032101 033321 033344 033370

type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 02X1 02X1,5 02X2,5

Technical Appendix

> 146 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Flexible power, process control and instrumentation cable for industry, machinery and outdoor environment. The cable is resistant against most usual chemicals, oil and grease. nominal voltage UO nominal voltage U test voltage core identification protective conductor conductor material conductor construction insulation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation 600 V 1000 V 4 kV gn-ye + numbers bare copper fine stranded, class 5 PVC special PVC-compound 70 C -40 - +70 C -5 - +70 C 4 x DA yes

Control cable <<<


Power cables 1 up to 30 kV

Y-JZ 600

bending radius, moved 7,5 x DA application for outdoor use flame retardant p/n 033581 033582 033583 033584 033585 033586 033587 033588 033589 033590 033591 033592 033593 033594 033595 033596 033597 033598 033599 033600 033601 033602 033603 033604 033605 033606 033608 033609 033610 033612 033615 033616 033619 033623 033626 033640 033641 033477 032045 033647 031832 type 03X0,75 04X0,75 05X0,75 06X0,75 07X0,75 08X0,75 09X0,75 10X0,75 12X0,75 14X0,75 15X0,75 18X0,75 20X0,75 21X0,75 25X0,75 32X0,75 34X0,75 37X0,75 40X0,75 41X0,75 42X0,75 50X0,75 61X0,75 65X0,75 80X0,75 100X0,75 03X1 04X1 05X1 07X1 10X1 12X1 18X1 25X1 34X1 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 22 29 36 43,2 50,4 58 65 72 86,4 101 108 130 144 151,2 180 230,4 245 266,4 288 296 302,4 360 439,2 468 576 720 29 38,4 48 67,2 96 115,2 173 240 326,4 43,2 58 72 101 173 259,2 DA mm 8,7 9,2 9,9 10,3 11,1 11,7 12,6 12,8 13,4 14 14,8 15,6 17 17,3 18,9 20,6 21,5 21,6 23,2 23,2 23,3 25,6 28,2 29 31,4 36,2 9 9,6 10,4 12,1 14,1 14,5 17,3 21,1 24 10,1 10,8 11,7 13,5 16,6 19,7 yes VDE 0482-332-1-2/IEC 60332-1 weight ca. kg/km 91 120 134 165 177 211 226 236 248 283 317 350 392 421 478 592 626 690 718 733 760 871 1060 1105 1490 1874 98 110 136 179 268 287 408 567 751 122 150 176 192 363 520 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 147 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

Y-JZ 600
p/n 033653 033655 033657 033658 033660 033661 033663 033665 033666 033478 033667 033669 033671 033673 033681 033682 033687 033688 033691 033692 033695 type 25X1,5 34X1,5 42X1,5 50X1,5 61X1,5 65X1,5 100X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 25X2,5 04X4 05X4 04X6 05X6 04X10 05X10 04X16

Control and Electronic Cable


colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 360 490 605 720 878,4 936 1440 72 96 120 168 288 432 600 154 192 230,4 288 384 480 614,4 DA mm 23,9 27,2 29,5 32,5 36,8 38,2 45,6 11,3 12,2 13,3 15,2 18,7 22 26,9 14 15,3 15,7 17,9 19,5 23 21,9 weight ca. kg/km 740 959 1110 1399 1680 1875 2675 176 209 252 335 544 788 1101 311 398 429 602 759 927 1093 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Y-OZ 600
core identification protective conductor conductor material conductor construction insulation sheathing material maximum temperature at conductor numbers no bare copper fine stranded, class 5 PVC special PVC-compound 70 C -40 - +70 C -5 - +70 C 4 x DA Application: Flexible power, process control and instrumentation cable for industry, machinery and outdoor environment. The cable is resistant against most usual chemicals, oil and grease.

LAN cables

Cable with circuit integrity

max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation

Conductor ropes

bending radius, moved 7,5 x DA application for outdoor use flame retardant p/n 033580 034936 033607 033734 033639 033733 033664 034979 034980 type 02X0,75 03X0,75 02X1 03X1 02X1,5 03X1,5 02X2,5 03X2,5 04X2,5 yes VDE 0482-332-1-2/IEC 60332-1 colour bk bk bk bk bk bk bk bk bk CU kg/km 14,4 22 19,2 29 29 43,2 48 72 96 DA mm 8,3 8,7 8,6 9 9,6 10,1 10,8 10,1 12,2 weight ca. kg/km 81 91 84 98 103 122 152 175 182 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

> 148 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease. For indoor and outdoor application. nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation maximum temperature at conductor inner sheath screen coverage sheathing material for outdoor use flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation 600 V 1000 V 4 kV gn-ye + numbers bare copper fine stranded, class 5 PVC 70 C PVC 70 % special PVC-compound yes VDE 0482-332-1-2/IEC 60332-1 no -20 - +70 C -5 - +70 C 5 x DA

Control cable <<<


Power cables 1 up to 30 kV

CY-JZ 600

p/n 032061 033195 033196 033197 033198 033199 033741 032627 033166 033167 033168 032846 033169 033170 033171 032626 033173 032875 033174 034515 033175 033176 033177 033179 033180 033181 033182 033183 033184 033185 033202 033203 033212 033204 033205 033209 033210

type 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 41X0,75 03X1 04X1 05X1 07X1 12X1 18X1 25X1 03X1,5 04X1,5 05X1,5 07X1,5 09X1,5 12X1,5 18X1,5 25X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 25X2,5 04X4 05X4 12X4 04X6 05X6 04X10 05X10

colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk

>>> www.faberkabel.de <<<

> 149 <

Technical Appendix

CU kg/km 57 68 79 97 169 229 296 415 67 97 94 122 204 280 369 87 104 125 180 224 284 391 521 124 170 204 268 423 572 740 238 303 581 319 421 576 620

19,6 23,4 28,2 13,5 14,6 15,7 17,9 21,9 26,1 31,9 16,7 18,6 26,9 18,7 20,7 21,9 24,1

Other

Conductor ropes

DA mm 9 11,4 12,1 13 15,8 18 22,8 24,7 11,2 11,8 12,6 14,5 17,4 20,7 24,8 10,9 12,2 13,3 16

weight ca. kg/km 155 214 250 319 437 588 746 908 196 231 270 289 493 658 870 187 265 289 416 482 641 872 1211 326 379 471 590 897 1355 1995 557 695 1510 723 984 1267 1635

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

LAN cables

Cable with circuit integrity

Control and Electronic Cable

bending radius, moved 10 x DA application

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

CY-OZ 600
conductor material conductor construction insulation maximum temperature at conductor inner sheath screen coverage sheathing material for outdoor use flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation

Control and Electronic Cable


bare copper fine stranded, class 5 PVC 70 C PVC 70 % special PVC-compound yes VDE 0482-332-1-2/IEC 60332-1 no -20 - +70 C -5 - +70 C 5 x DA Application: Flexible power, process control and instrumentation cable for industry and machinery environment with increased requirements to electromagnetic compatibility. The cable is resistant against most usual chemicals, oil and grease. For indoor and outdoor application.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

bending radius, moved 10 x DA application p/n 033186 033194 033165 033172 033178 033200 type 02X0,5 02X0,75 02X1 02X1,5 02X2,5 02X4 colour bk bk bk bk bk bk CU kg/km 38 46 52 69 99 156 DA mm 10,1 8,7 10,8 10,2 11,5 14,3 weight ca. kg/km 147 143 174 162 272 306 packaging dr. dr. dr. dr., c. 100 dr. dr.

Cable with circuit integrity

Control and Electronic Cable

SY-JZ
nominal voltage Uo nominal voltage U test voltage core identification 300 V 500 V 3000 V gn-ye + numbers bare copper fine stranded, class 5 70 C PVC TI2 PVC TM2 steel wire braiding, galvanized PVC TM2 VDE 0482-332-1-2/IEC 60332-1 -20 - +70 C -5 - +70 C 6 x DA Application: Flexible power, process control and instrumentation cable for industry and mechanical engeneeringt. The cable is resistant against most usual chemicals, oil and grease.

LAN cables

conductor material conductor construction maximum temperature at conductor insulation inner sheath armour sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation

Other

Conductor ropes

bending radius, fixed installation

bending radius, moved 20 x DA application

Technical Appendix

p/n 033035 031897 033036 033037

type 03X0,75 04X0,75 05X0,75 07X0,75

colour TR TR TR TR

CU kg/km 22 28,8 36 50,4

DA mm 8,2 8,6 9,5 10,5

weight ca. kg/km 110 126 164 195

packaging dr. dr. dr. dr.

> 150 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 032026 033042 033044 033046 033047 033048 033049 033051 033052 031606 033054 033057 033059 033061 033062 031984 031604 031605 031710 031607 033077 032634 033086 031445 033087 033088 033089 033091 031444 033098 033101 033104 033107 033110 033112 033114 type 12X0,75 18X0,75 25X0,75 34X0,75 41X0,75 50X0,75 61X0,75 03X1 04X1 05X1 07X1 12X1 18X1 25X1 34X1 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 04X4 05X4 04X6 04X10 04X16 04X25 04X35 04X50 colour TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR TR CU kg/km 86 130 180 245 296 360 439 29 38,4 48 67 115,2 173 240 326,4 43 58 72 101 173 259,2 360 72 96 120 168 288 432 153,6 192 230,4 384 614 960 1344 1920 DA mm 12,8 14,8 17,4 19,4 21,1 23,2 24,9 8,6 9,4 9,9 11,2 13,7 15,7 18,4 20,5 9,5 10,1 10,9 12,3 15,2 17,4 20,5 11,3 12,9 13,2 14,3 18,2 21,4 13,9 15,1 16,1 19,9 22,8 28,9 32,1 38,2 weight ca. kg/km 292 378 523 655 723 866 1014 131 161 164 220 347 426 616 804 102 173 202 248 396 605 752 226 249 324 399 643 846 348 470 531 837 1396 1983 2550 3502 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

SY-JZ

>>> www.faberkabel.de <<<

> 151 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

2YSL(St)CYv
nominal voltage Uo nominal voltage U maximum permitted operating voltage in 3-phase systems test voltage core identification conductor material conductor construction insulation screen coverage sheathing material transfer impedance flame retardant maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation bending radius, fixed installation 600 V 1000 V 1,7 kV 3 kV

Control and Electronic Cable


Application: The cable has been developed for connecting motors to inverse rectifiers under consideration of EMCrequirements. It may be used under medium mechanical stress for fixed installations and temporary movement. Also for outdoor installation, but not for direct burial. The cable is resistant against most usual oil and grease.

Building Wires

colours acc. VDE 0293 (HD308) bare copper fine stranded, class 5 polyethylene 75 % PVC, enforced 250 Ohm/km VDE 0482-332-1-2/IEC 60332-1 70 C -30 - +70 C -5 - +70 C 10 x DA

Telecommunication Cables and Cords

Flexible Cables

Control and Electronic Cable

bending radius, moved 25 x DA application oil resistant acc. to EN 60811-2-1 p/n 031719 031720 031721 031712 031722 031723 031724 031713 031725 031727 031714 031728 031715 031729 031730 032929 031994 031995 031996 031871 031997 031870 031998 031999 031869 032000 031868 032001 032002 032130 032928 type 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X185 04X240 04X300 3X2,5+3X0,5 3X4+3X0,75 3X6+3X1 3X10+3X1,5 3X16+3X2,5 3X25+3X4 3X35+3X6 3X50+3X10 3X70+3X10 3X95+3X16 3X120+3X16 3X150+3X25 3X185+3X35 3X240+3X50 3X300+3X70 yes colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 95 150 235 320 533 789 1236 1663 2345 3196 4316 5435 6394 8203 11008 13485 144 224 298 511 723 1204 1535 2208 2980 3953 5007 5412 6969 9123 11965 DA mm 10,4 12,3 14,5 16,8 19,7 22 27 30,3 35 39,4 46 51,4 58,8 61,1 70 11,4 13,1 14,9 18,4 21,6 25,3 27,8 32,6 38,9 44,3 46,8 53,5 59,5 70 weight ca. kg/km 154 229 339 451 667 892 1440 1861 2547 3404 4888 5703 7040 9150 12500 15508 220 323 420 615 819 1402 1718 2399 3173 4162 5253 6128 7450 10800 13760 packaging dr., c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 152 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: PVC insulated flat cables are used as trailing cable for crane installations, floor conveyer systems and shelf control units. Max. suspension length 35 m. standard core identification nominal voltage Uo nominal voltage U test voltage protective conductor conductor material conductor construction insulation sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n 031974 032153 032351 032004 032352 031975 031976 031977 031978 032154 032353 032354 032355 032356 032357 032358 032359 032041 032301 032360 031979 032302 032024 032361 033469 032152 034819 034557 type 04G1,5 05G1,5 07G1,5 08G1,5 10G1,5 12G1,5 14G1,5 18G1,5 04G2,5 05G2,5 07G2,5 08G2,5 12G2,5 24G2,5 04G4 05G4 07G4 04G6 05G6 07G6 04G10 05G10 04G16 05G16 04G25 04G35 04G50 04G70 colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 58 72 101 115 144 173 202 259 96 120 168 192 288 604 154 192 269 230 288 403 384 480 614 768 960 1344 1920 2688 wxh ca. mm 15 x 5 18 x 5 27 x 5 29 x 5 36 x 5 41 x 5 51 x 5 65 x 5 18,5 x 5,7 22,1 x 5,7 33,5 x 5,7 37,1 x 5,7 50,9 x 5,7 59,2 x 5,7 21,5 x 6,9 61,5 x 19,1 37,9 x 6,9 24,5 x 7,6 29,5 x 7,6 41,1 x 7,1 31,1 x 9,6 37,5 x 10,2 35,5 x 10,9 43,4 x 11,1 41,5 x 12,7 49,1 x 15,7 61,5 x 19,1 64,1 x 21,1 VDE 0281-404 colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers 450 V 750 V 2,5 kV yes bare copper fine stranded, class 5

Control cable <<<


Power cables 1 up to 30 kV

H07VVH6-F

PVC TM2 VDE 0482-332-1-2/IEC 60332-1 yes -40 - +70 C -25 - +70 C weight ca. kg/km 135 140 260 265 358 442 435 559 206 240 365 410 610 950 327 402 567 430 525 755 709 935 1015 1317 1367 1920 2822 3817 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 153 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

PVC TI2

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

AD 100 P
core identification nominal voltage Uo nominal voltage U test voltage conductor material insulation sheathing material maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation 300 V 500 V 3000 V

Control and Electronic Cable


gn-ye + numbers Application: In dry and wet environment as well as in free air for medium mechanical stress. For connection of electrical tools with improved oil- and abrasion resistance.

Building Wires

bare copper special PVC-compound polyurethan 80 C -40 - +80 C -5 - +80 C

Flexible Cables

bending radius, moved 7,5 x DA application bending radius, fixed installation oil resistant acc. to EN 60811-2-1 p/n 032800 032801 032802 032803 032804 034355 032805 032806 034356 032807 034357 032808 034358 032809 032810 034359 034360 032811 032812 031717 031716 032813 032815 032816 032817 032818 034365 034366 032820 032821 032822 032823 032010 032824 032825 032826 032827 034372 034373 034374 032829 032830 032831 032832 032833 type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 08X0,75 10X0,75 12X0,75 14X0,75 18X0,75 21X0,75 25X0,75 30X0,75 34X0,75 41X0,75 42X0,75 50X0,75 02X1 04X1 03X1 05X1 07X1 12X1 18X1 25X1 34X1 42X1 50X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 34X1,5 42X1,5 50X1,5 02X2,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 4 x DA yes colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 14,4 22 29 36 50 58 72 86,4 101 130 151,2 180 216 245 295,2 302,4 360 19,2 38,4 29 48 67 115,2 173 240 326,4 404 480 29 43,2 58 72 101 173 260 360 490 605 720 48 72 96 120 168 288 DA mm 5,4 5,7 6,2 6,8 8,1 8,7 9,6 9,9 10,4 11,9 13,3 14,5 15,1 16,3 17,4 17,7 19,4 5,7 6,6 6 7,1 8,6 10,7 12,9 14,9 17,4 18,8 20,9 6,2 6,6 7,2 8 9,6 12 14,1 16,8 19,5 21,1 25,4 7,8 8,3 9,2 10,1 12,3 15,3 weight ca. kg/km 43 55 67 83 106 111 151 181 202 255 269 325 400 473 529 600 720 53 85 61 89 126 219 309 414 592 730 890 77 92 110 132 159 290 422 594 799 1100 1250 110 149 175 204 280 489 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. c. 100 c. 100, dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 154 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 034375 034376 032834 032835 032837 032838 type 18X2,5 25X2,5 04X4 05X4 04X6 05X6 colour gy gy gy gy gy gy CU kg/km 432 600 154 192 230,4 288 DA mm 18,2 22,3 11,4 12,7 13,4 14,9 weight ca. kg/km 740 1095 266 315 383 477 packaging dr. dr. dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

AD 100 P

AD 100 F-CP
Application: Ruggedized PUR-sheathed control cable, highly resistant against wear and tear. The oil and coolant resistance allows application in industrial environments, machine building, engineering or even steel works. For medium mechanical stress without tension load and forced guiding. For indoor and outdoor use. core identification nominal voltage U nominal voltage Uo test voltage conductor material conductor construction maximum temperature at conductor insulation screen coverage transfer impedance sheathing material gn-ye + numbers 300 V 500 V 3000 V bare copper fine stranded, class 5 70 C special PVC-compound 85 % 250 Ohm/km polyurethan

bending radius, moved 10 x DA application bending radius, fixed installation flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n 034538 033532 033533 033534 033535 033536 033538 033540 033542 033543 033545 033546 032012 031990 031787 032013 034559 032050 034564 034566 034567 034568 type 04X0,5 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 34X0,75 41X0,75 50X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 25X1 34X1 41X1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 49 47 54 77 86 96 151 207 280 420 467 480 50 77 87 90 112 194 268 354 452 510 DA mm 6,5 5,8 6,1 6,5 7,1 8,3 10,3 12,1 14,9 19,8 17,9 19,7 6,1 6,3 6,9 7,5 8,9 10,9 13,9 15,9 17,9 19,3 5 x DA VDE 0482-332-1-2/IEC 60332-1 yes -40 - +80 C

>>> www.faberkabel.de <<<

> 155 <

Technical Appendix

weight ca. kg/km 72 77 89 102 117 152 231 333 447 599 689 775 66 82 129 128 174 262 388 596 740 855

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Other

Conductor ropes

LAN cables

-5 - 80 C

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

AD 100 F-CP
p/n 034569 034475 031772 033824 032049 032044 033825 034574 033826 034616 034617 034618 034619 033827 034620 034621 034622 033828 034624 033829 034627 034628 034631 034632 034634 034635 034636 034637 type 50X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 34X1,5 42X1,5 50X1,5 02X2,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 25X2,5 04X4 05X4 04X6 05X6 04X10 04X16 04X25 04X35

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 630 65 83 100 120 152 268 373 530 683 770 976 96 147 175 203 253 445 569 827 248 300 343 418 535 800 1075 1576 DA mm 21,2 7,1 6,9 7,5 8,4 10 12,1 15,6 17,9 20,8 21,8 23,6 8,2 8,6 9,9 11 12,6 15,5 19 22,2 11,7 13,3 14,2 15,2 17,2 20,2 25,1 28 weight ca. kg/km 1027 92 135 146 159 207 352 516 719 907 1040 1292 131 178 215 246 342 580 978 1358 308 386 427 510 710 1050 1570 2070 packaging dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Cable with circuit integrity

SL AD 300 Y
protective conductor nominal voltage UO nominal voltage U test voltage core identification yes 300 V 500 V 4 kV numbers bare copper fine stranded class 6 special PVC-compound PVC VDE 0482-332-1-2/IEC 60332-1 yes -40 - +80 C 0 - +80 C colour gy gy gy gy gy gy gy gy gy gy gy CU kg/km 15 22 29 37 51 89 130 19,2 29 38,4 48 DA mm 5,4 5,7 6,4 7,1 8,3 10,2 12,1 5,7 6,1 6,8 7,4 weight ca. kg/km 48 60 73 86 134 181 292 57 75 94 117 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: Extremely flexible control cable for application in permantently moved production units (indoor). For use in free movement without tensile stress application in drag-chains is permitted. The cable is flame retardant and resistant against most in industry environment occurring chemicals. Please pay attention to our notes for the use of drag chain cable.

LAN cables

conductor material conductor construction insulation sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 02X1 03X1 04X1 05X1

Other

Conductor ropes

Technical Appendix

032380 032068 032381 032069 032382 032141 032386 032396 032315 032397 032398

> 156 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 032399 030934 031579 032413 031760 031321 031063 030936 031439 031066 032425 032054 031591 type 07X1 12X1 18X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 02X2,5 03X2,5 04X2,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 67,2 115,2 172,8 29 43,2 57,6 72 101 172,8 259,2 48 72 96 DA mm 8,8 10,8 13,1 6,4 6,8 7,4 8,3 9,9 12,1 14,5 7,7 8,4 9,1 weight ca. kg/km 164 261 361 73 93 134 168 232 351 507 113 145 203 packaging dr., c. 100 dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

SL AD 300 Y

SL AD 300 CY
Application: Highly-flexible data cable for continuous mobile use under extreme conditions with particular requirements on EMC. It is applicable in standard drag chains without tensile load. The cable is flame retardant, and largely resistant against most chemicals used in industrial environment. Please note our instructions for the use of drag-chain cables. protective conductor nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation inner sheath sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n 032463 032464 032465 032466 032467 032029 032471 032481 032482 032483 032484 032485 032486 032488 type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 56 64 80 92 110 189 259 61 71 90 114 136 235 309 DA mm 7,3 7,8 8,3 9,1 10,2 12,6 14,5 7,8 8,1 9,5 9,5 10,9 13,1 15,4 yes 300 V 500 V 4 kV numbers bare copper fine stranded class 6

PVC PVC VDE 0482-332-1-2/IEC 60332-1 yes -40 - +80 C 0 - +80 C weight ca. kg/km 101 118 148 168 225 253 462 111 131 163 203 257 257 534 packaging dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 157 <

Technical Appendix

Other

Conductor ropes

LAN cables

special PVC-compound

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

SL AD 300 CY
p/n 032495 032496 031582 032497 032498 031583 032298 032507 031590 032508 031769 032509 type 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 79 94 119 132 218 310 481 140 169,3 194 296 405 DA mm 8,3 8,7 9,5 10,2 12,2 14,5 16,9 10,5 11,2 12,7 14,8 18 weight ca. kg/km 141 167 210 242 328 546 684 222 321 342 418 683 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 50 dr. dr., c. 100 dr.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

SL AD 300 P
core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed temperature, moved/ during installation oil resistant acc. to EN 60811-2-1 numbers yes 300 V 500 V 3 kV bare copper fine stranded class 6 TPE polyurethan VDE 0482-332-1-2/IEC 60332-1 -50 - +80 C -30 - +80 C yes Application: Highly flexible control cable for the constantly moved equipment under extreme conditions indoor and outdoor. The cable is halogen-free, flame retardant and resistant against most in industry environment occurring chemicals. Please pay attention to our notes for the use of drag chain cable.

Cable with circuit integrity

Control and Electronic Cable

LAN cables

bending radius, moved 7,5 x DA application bending radius, fixed installation p/n type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 25X1 02X1,5 03X1,5 04X1,5 05X1,5 4 x DA colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 15 22 29 36 50,4 86,4 130 180 19,2 29 38,4 48 67,2 115,2 173 240 29 47 60 72 DA mm 6,2 6,5 7 7,8 9 11 12,9 15,4 6,9 7,4 8 8,7 10,2 12,6 14,8 17,8 7,6 8,1 8,7 9,7 weight ca. kg/km 57 73 95 76 106 248 252 351 65 84 111 138 182 261 390 445 65 110 134 168 packaging dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Conductor ropes

Technical Appendix

031001 031002 031003 032526 032527 031029 032528 032530 031004 031009 031005 031006 031026 031028 031030 031152 032537 031007 031067 030955

Other

> 158 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 031023 031584 031158 031416 032543 031585 031580 031022 032094 031428 032544 type 07X1,5 12X1,5 18X1,5 25X1,5 02X2,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5 colour gy gy gy gy gy gy gy gy gy gy gy CU kg/km 101 173 259,2 360 48 72 96 120 168 288 432 DA mm 11,3 13,8 16,3 19,7 9,2 9,7 10,5 11,6 13,8 16,9 20 weight ca. kg/km 232 305 507 647 115 143 174 198 266 421 714 packaging dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

SL AD 300 P

SL AD 300 CP
Application: Highly flexible control cable for the constantly moved equipment under extreme conditions indoor and outdoor. The cable is halogen-free, flame retardant and resistant against most in industry environment occurring chemicals. Please pay attention to our notes for the use of drag chain cable. nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction insulation inner sheath screen coverage sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation 300 V 500 V 3 kV gn-ye + numbers bare copper fine stranded class 6 TPE 80 % polyurethan VDE 0482-332-1-2/IEC 60332-1 yes -50 - +80 C -30 - +80 C

bending radius, moved 7,5 x DA application bending radius, fixed installation p/n 031442 030958 032558 032559 032560 032561 032562 032564 032565 type 02X0,5 05X0,5 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 colour gy gy gy gy gy gy gy gy gy CU kg/km 48 66 53 63 77 87 107 156 235 DA mm 8,3 9,7 8,8 9,3 9,7 10,5 11,9 14,2 16,3 4 x DA weight ca. kg/km 91 131 98 120 83 94 125 308 420 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 159 <

Technical Appendix

Other

Conductor ropes

LAN cables

TPE

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

SL AD 300 CP
p/n 032567 032570 032571 032572 031923 031986 030953 031919 032574 032581 032582 031910 032583 032584 032064 032065 032586 032591 032592 031556 032067 031918 031766 031767 type 25X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 25X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 12X1,5 18X1,5 25X1,5 02X2,5 03X2,5 04X2,5 05X2,5 07X2,5 12X2,5 18X2,5

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 313 60 71 88 99 128 186 280 378 79 94 119 129 170 279 394 533 104 137 165 191 275 453 607 DA mm 19,2 8,8 9,3 9,7 10,5 11,9 14,2 16,3 19,2 9,7 10 10,8 11,7 13,4 16 18,5 23,7 11,9 12,6 13,6 14,7 17,4 20,9 24,2 weight ca. kg/km 579 65 81 96 168 240 358,2 418 641 134 109 217 148 325 416 564 888 198 284 321 293 418 589 885 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

SL AD 400 CP
standard core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant UL/CSA gn-ye + numbers yes 600 V 1000 V 4 kV bare copper fine stranded class 6 polyolefin 60 C polyurethan VDE 0482-332-1-2/IEC 60332-1 Application: Flexible control cable for permantent moved applications under heavy duty conditiones combined with requirements to EMC. The cable is halogen-free, flame retardant and resistant against most often used chemical substances in industrial environment. Please pay attention to our installation instructions for drag-chain cables.

LAN cables

Cable with circuit integrity

Conductor ropes

bending radius, moved 7,5 x DA application bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation 5 x DA -50 - +80 C -30 - +80 C colour og og og og og og og CU kg/km 119 168 231,4 332,1 527 794 1180 DA mm 10 11,9 13 15 18 22 27,5 weight ca. kg/km 175 234 338 466 674 1148 1650 packaging dr. dr. dr. dr. dr. dr. dr.

Other

p/n 033164 033719 033720 033721 033722 033723 033724

type 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25

Technical Appendix

> 160 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 033725 033726 033727 type 04X35 04X50 04X70 colour og og og CU kg/km 1603 2165 3196 DA mm 32 36,7 42,5 weight ca. kg/km 2400 3150 4600 packaging dr. dr. dr.

Control cable <<<


Power cables 1 up to 30 kV

SL AD 400 CP

05VV2SV
Application: For the connection of control buttons or as unsupported switch cable for<mt:br/>heights up to 50 m. For indoor or outdoor use. core identification protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers yes 300 V 500 V 2000 V bare copper

PVC 70 C PVC VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C -30 - +70 C

bending radius, moved 10 x DA application bending radius, fixed installation p/n 034638 031814 031862 034639 034640 032788 034641 type 12G1 18X1 25G1 30G1 08G1,5 12G1,5 15G1,5 colour bk bk bk bk bk bk bk CU kg/km 115,2 172,8 240 288 115,2 173 230 10 x DA packaging dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 161 <

Technical Appendix

weight ca. kg/km 427 528 665 760 396 486 575

Other

Conductor ropes

LAN cables

fine stranded, class 5

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Control cable


Power cables 1 up to 30 kV

05VV2SV
p/n 034642 034643 031815 type 18G1,5 20G1,5 24X1,5

Control and Electronic Cable


colour bk bk bk CU kg/km 259,2 288 346 weight ca. kg/km 640 729 820 packaging dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 162 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: For signal transmission between electronic devices, in computer systems or process control units. core identification operating capacity nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation sheathing material impedance flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n 030174 030175 030395 030177 030178 030179 030180 030181 030182 030183 030184 030575 031374 030186 030187 030603 030188 030189 030190 030191 030192 030193 031375 030494 031376 031377 030197 030198 030199 030200 030201 030202 030203 030204 030205 030206 030207 030208 030495 031378 030209 030210 031379 030568 type 02X0,14 03X0,14 04X0,14 05X0,14 06X0,14 07X0,14 08X0,14 10X0,14 12X0,14 14X0,14 16X0,14 18X0,14 20X0,14 21X0,14 24X0,14 25X0,14 27X0,14 30X0,14 32X0,14 36X0,14 40X0,14 44X0,14 48X0,14 50X0,14 52X0,14 56X0,14 61X0,14 02X0,25 03X0,25 04X0,25 05X0,25 06X0,25 07X0,25 08X0,25 10X0,25 12X0,25 14X0,25 16X0,25 18X0,25 20X0,25 21X0,25 24X0,25 25X0,25 27X0,25 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 2,7 4,1 5,4 6,8 8,1 9,5 10,8 13,5 16,2 18,9 21,6 24,1 26,9 28,4 32,3 34,3 36,3 40,5 43 48,6 54 59 64,5 67,5 69,9 75,3 82 4,8 7,2 9,6 12 14,4 16,8 19,2 24 28,8 33,6 38,4 43,2 48 50,4 57,6 60 64,8 DA mm 3,2 3,4 3,7 4 4,4 4,7 5,3 5,6 5,8 6,1 6,4 6,7 7,4 7,5 7,8 7,9 8,7 8,8 9 9,3 9,7 10,4 10,8 11 11,1 11,3 11,5 3,6 3,8 4,1 4,5 5 5,4 6,1 6,4 6,6 6,9 7,3 7,7 8,2 9,1 9,4 9,6 9,9 colours acc. DIN 47100 120 nF/km 250 V 250 V bare copper fine stranded, class 5 70 C PVC PVC 85 Ohm 1,2 kV

Electronic cable <<<


Power cables 1 up to 30 kV

LiYY

VDE 0482-332-1-2/IEC 60332-1 no -30 - +80 C -5 - +70 C weight ca. kg/km 12 17 19 22 25 27 30 41 48 54 60 72 73 77 94 100 107 112 123 137 152 167 186 202 210 218 237 17 21 27 32 40 42 51 61 71 81 98 110 128 134 140 148 153 packaging dr., c. 100 dr., c. 100 dr., c. 100, c. 250 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr. dr., c. 100

>>> www.faberkabel.de <<<

> 163 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Electronic cable


Power cables 1 up to 30 kV

LiYY
p/n 030212 030213 030214 030497 030569 031380 030498 031381 030218 030219 030220 030221 030222 030223 030224 030574 030225 030573 030226 030227 030228 030229 030230 030231 030232 030233 030234 030235 030236 030502 030240 030241 030242 030243 030244 030246 030587 030248 030567 030250 030545 030252 030527 030528 030529 031308 031433 030337 030338 030339 030340 030341 030342 type 30X0,25 32X0,25 36X0,25 40X0,25 44X0,25 48X0,25 50X0,25 56X0,25 61X0,25 02X0,34 03X0,34 04X0,34 05X0,34 06X0,34 07X0,34 08X0,34 10X0,34 12X0,34 14X0,34 16X0,34 18X0,34 21X0,34 24X0,34 27X0,34 30X0,34 32X0,34 36X0,34 40X0,34 44X0,34 50X0,34 61X0,34 02X0,5 03X0,5 04X0,5 05X0,5 07X0,5 08X0,5 10X0,5 12X0,5 16X0,5 21X0,5 24X0,5 02X0,75 03X0,75 04X0,75 02X1 04X1 02X2X0,14 03X2X0,14 04X2X0,14 05X2X0,14 06X2X0,14 08X2X0,14

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 72 77 86,4 96,1 105,6 115,2 120 134,4 146,4 6,5 9,8 13,1 16,3 19,6 22,8 26 32,6 39,2 45,7 52,2 58,8 68,6 78,4 88,2 98 104,4 117,5 130,6 143,6 163 199,1 9,6 14,4 19,2 24 33,6 38,4 48 57,6 76,8 96 120 14,4 21,6 28,8 19,2 38,4 5,4 8 10,7 13,4 16,1 21,5 DA mm 10 10,3 10,7 11,2 12,4 12,7 12,9 13,3 13,7 4,2 4,5 4,9 5,6 6,1 6,6 7,2 7,6 7,9 8,7 9,2 9,6 10,8 11,2 12,1 12,3 12,8 13,2 13,8 14,8 15,5 16,4 5,6 5,9 6,4 7 7,6 7,9 9,4 9,7 10,8 12,6 13,6 5,9 6 6,5 6 6,5 5,1 5,8 6,4 6,7 7,2 7,7 weight ca. kg/km 168 188 208 227 249 271 312 349 398 19 25 32 38 44 50 61 73 85 104 116 131 149 167 184 212 225 249 273 300 404 508 23 31 39 47 65 75 92 121 146 184 221 48 57 69 61 85 19 26 34 42 48 62 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 164 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: For signal transmission between electronic devices, in computer systems or process control units. The blue outer sheath allows installation in intrinsically safe circuits. conductor material conductor construction insulation sheathing material flame retardant temperature, moved/ during installation max. operating temperature, fixed p/n 031654 030661 033122 033123 032663 033130 033131 032864 033132 032944 033135 031421 030778 033136 033137 type 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 02X1 03X1 04X1 05X1 07X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 colour bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu CU kg/km 14,4 21,6 29,4 37 52 20 30 38 48 69,1 29 43,2 57,6 72 101 DA mm 5,9 6,1 6,2 6,9 5,8 6,3 6,6 7,3 8,6 6,6 bare copper fine stranded, class 5 PVC

Electronic cable <<<


Power cables 1 up to 30 kV

LIYY/EB

VDE 0482-332-1-2/IEC 60332-1 -5 - +70 C -30 - +80 C weight ca. kg/km 43 61 74 89 117 58 75 86 111 143 86 99 125 152 190 packaging dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr.

LiYCY
Application: For signal transmission between electronic devices, in computer systems or process control units with increased requirements to electromagnetic compatibility. core identification operating capacity protective conductor nominal voltage UO nominal voltage U test voltage conductor material conductor construction maximum temperature at conductor insulation screen coverage sheathing material flame retardant oil resistant acc. to EN 60811-2-1 max. operating temperature, fixed temperature, moved/ during installation p/n 030253 030254 030255 030256 030257 030258 030259 030260 type 02X0,14 03X0,14 04X0,14 05X0,14 06X0,14 07X0,14 08X0,14 10X0,14 colour gy gy gy gy gy gy gy gy CU kg/km 12,4 14,1 15,8 19,6 22,2 23,5 25,2 28,3 DA mm 3,9 4 4,2 4,6 4,9 5 6 6,5 colours acc. DIN 47100 120 nF/km no 250 V 250 V 1,2 kV bare copper fine stranded, class 5 70 C PVC PVC VDE 0482-332-1-2/IEC 60332-1 no -30 - +80 C -5 - +70 C weight ca. kg/km 21 40 43 47 52 54 58 76 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100

>>> www.faberkabel.de <<<

> 165 <

Technical Appendix

Other

Conductor ropes

70 %

LAN cables

Cable with circuit integrity

Control and Electronic Cable

8,3 9,8

Telecommunication Cables and Cords

Flexible Cables

Building Wires

PVC

>>> Electronic cable


Power cables 1 up to 30 kV

LiYCY
p/n 030261 030262 030263 030264 030926 030266 030267 031382 030268 030269 030270 030271 030272 030274 031383 030538 031384 031385 030278 031334 030280 030281 030282 030283 030284 030285 030286 030287 030288 030289 031386 030290 030291 030927 030292 030293 031387 030294 030295 030296 030297 030298 030300 031388 030459 031389 031390 030304 030305 030306 030307 030308 030571 030309 030310 030311 030312 030460 030313 030314 030928 030315 030316 030317 030462 030318 type 12X0,14 14X0,14 16X0,14 18X0,14 20X0,14 21X0,14 24X0,14 25X0,14 27X0,14 30X0,14 32X0,14 36X0,14 40X0,14 44X0,14 48X0,14 50X0,14 52X0,14 56X0,14 61X0,14 01X0,25 02X0,25 03X0,25 04X0,25 05X0,25 06X0,25 07X0,25 08X0,25 10X0,25 12X0,25 14X0,25 15X0,25 16X0,25 18X0,25 20X0,25 21X0,25 24X0,25 25X0,25 27X0,25 30X0,25 32X0,25 36X0,25 40X0,25 44X0,25 48X0,25 50X0,25 52X0,25 56X0,25 61X0,25 02X0,34 03X0,34 04X0,34 05X0,34 06X0,34 07X0,34 08X0,34 10X0,34 12X0,34 14X0,34 16X0,34 18X0,34 20X0,34 21X0,34 24X0,34 27X0,34 30X0,34 32X0,34

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 31,4 34,9 48 51,5 58,3 60,2 74,3 76,2 84,3 97,6 105,2 116,4 126 138,2 145,8 155 157,4 166,5 176,5 8 16 21 24 29 32,4 37 42,1 49,9 59 64,2 67,5 70,8 83 88 93 114,2 116,7 122 132,3 137,8 152 163,5 179 192 203 233,1 237 287,2 21 27 33 36 45 51 54 74 80 86 94 107,5 115,3 119 139 149 161,5 170,8 DA mm 6,7 6,9 7,3 7,5 7,8 7,9 9,1 9,2 9,4 9,5 10 10,2 10,5 11,2 11,7 12 12,3 12,7 12,8 4,6 4,8 5,2 5,7 6,3 6,3 6,4 6,7 7,8 8 9,4 9,6 10 10,2 10,5 12,1 12,1 12,2 12,6 13 13,6 14,1 14,7 14,8 16 16,2 16,6 20 4,8 5 5,4 5,9 6,6 6,7 7 8,9 9 9,5 10 10,7 10,9 11,2 13 13,1 13,3 13,8 weight ca. kg/km 81 89 97 100 116 131 158 165 179 194 198 231 252 276 301 327 340 366 377 13 28 34 40 47 54 61 66 80 91 120 127 135 150 157 163 212 220 226 243 256 280 302 329 444 461 479 516 593 31 38 46 54 62 70 76 114 128 141 155 186 195 201 244 261 282 298 packaging dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 166 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 030319 030320 030322 031391 030463 031392 031393 030323 032607 030325 030326 030327 030328 030564 030330 030883 030332 030333 030565 030464 030933 030410 030566 031394 031395 030465 031396 031397 030550 031398 030511 030512 030513 030514 030572 030515 031678 030471 030472 030473 030583 034913 030474 030475 030736 033873 030705 030672 030673 030670 031154 031256 030671 031257 031258 031259 031260 031261 030584 030586 030558 031155 031156 031262 031263 031264 type 36X0,34 40X0,34 44X0,34 48X0,34 50X0,34 52X0,34 56X0,34 61X0,34 01X0,5 02X0,5 03X0,5 04X0,5 05X0,5 06X0,5 07X0,5 08X0,5 10X0,5 12X0,5 16X0,5 18X0,5 20X0,5 21X0,5 24X0,5 25X0,5 27X0,5 30X0,5 32X0,5 42X0,5 50X0,5 61X0,5 02X0,75 03X0,75 04X0,75 05X0,75 06X0,75 07X0,75 08X0,75 10X0,75 12X0,75 18X0,75 20X0,75 24X0,75 25X0,75 30X0,75 32X0,75 40X0,75 02X1 03X1 04X1 05X1 07X1 08X1 10X1 12X1 16X1 18X1 20X1 25X1 02X1,5 03X1,5 04X1,5 05X1,5 07X1,5 08X1,5 10X1,5 12X1,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 188,3 203,5 223,5 264,8 268 269,6 292 418 15 29 39 46 57 68,6 80 91,4 100 117 129 152 165 171 236 250 265 297 301 304,6 407 580 38 50 58 70 87 100 110 140 154 207 238 270 280,8 318,7 330 480 46 56 69 89 118 130 145 168 220 252 269 335 63 76 108 129 164 172 195 254 DA mm 14,3 14,8 16,3 16,8 17,1 17,4 17,6 18 3,4 5 5,3 5,7 6,4 6,9 7 7,3 8,8 9,5 10,7 11 11,6 11,7 13,3 13,4 13,6 14 14,5 16,6 18 61,5 6,7 7 7,6 8,2 9,1 9,7 9,8 11,7 12 13,9 14,9 15 16,6 18 18,2 20,9 7 7,3 8 8,6 9,2 10,5 11,5 12 13,1 14,4 14,5 16 7,7 8 9 10 10,8 12,5 13 14 weight ca. kg/km 325 352 399 544 566 589 634 736 40 36 45 54 67 76 84 107 134 155 186 217 239 251 300 313 338 348 363 525 625 764 62 73 92 110 128 145 151 182 216 311 332 390 404 497 520 676 74 89 107 132 158 179 215 254 330 366 399 478 86 107 129 150 192 219 274 315 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr. dr. dr.

Electronic cable <<<


Power cables 1 up to 30 kV

LiYCY

>>> www.faberkabel.de <<<

> 167 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Electronic cable


Power cables 1 up to 30 kV

LiYCY
p/n 031265 031266 031267 031959 030360 030361 030362 030363 030364 030366 030367 030368 030369 030370 030371 030372 030374 030376 030476 030377 030378 030536 030537 030379 030516 030380 030381 030517 030518 030382 030383 030480 030481 030878 030879 030880 030881 030687 031271 030887 031269 031270 030392 030519 030393 030520 030521 030394 030485 034976 030522 030414 030523 030524 034855 031745 031322 031327 031189 034862 032127 032132 type 18X1,5 20X1,5 25X1,5 03X2,5 02X2X0,14 03X2X0,14 04X2X0,14 05X2X0,14 06X2X0,14 08X2X0,14 10X2X0,14 12X2X0,14 14X2X0,14 16X2X0,14 18X2X0,14 20X2X0,14 25X2X0,14 30X2X0,14 32X2X0,14 36X2X0,14 44X2X0,14 50X2X0,14 55X2X0,14 02X2X0,25 03X2X0,25 04X2X0,25 05X2X0,25 06X2X0,25 08X2X0,25 10X2X0,25 12X2X0,25 16X2X0,25 25X2X0,25 02X2X0,34 03X2X0,34 04X2X0,34 06X2X0,34 08X2X0,34 12X2X0,34 16X2X0,34 18X2X0,34 24X2X0,34 02X2X0,5 03X2X0,5 04X2X0,5 06X2X0,5 08X2X0,5 12X2X0,5 16X2X0,5 32X2X0,5 02X2X0,75 03X2X0,75 04X2X0,75 06X2X0,75 08X2X0,75 12X2X0,75 02X2X1 03X2X1 04X2X1,0 24X1 02X2X1,5 02X2X1,5

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy bk gy CU kg/km 350 375 550 124 22,6 25,7 39,3 44,5 51,4 56,9 65,3 78,4 84,3 93,4 99,4 104,8 127,7 142,8 148,8 185,5 210,5 244,9 260,7 28 39,6 44,9 55 69,5 76,9 110 121,5 146,5 233 40,5 49,8 62,9 84,1 97,5 138,3 166,2 205,6 266,1 54 73,7 91 120 144 199 254 477 58 85 108 146 180 261 84 103 132 344 116 116 DA mm 15,5 17 18,5 5 5,6 6,1 6,5 7,2 8,3 9 9,4 11 11 11,9 12,2 13,4 14,6 14,6 15,4 17,1 17,8 18,8 6,8 7,3 7,9 9,4 10,2 10,5 13,3 13,7 15,1 19,4 7,4 8 9,5 10,6 10,9 14,3 15,4 16,6 18,6 7,3 8,4 9,4 11,2 11,5 15,1 17,3 23,3 9,5 9,6 10,3 12,4 14,7 10,3 10,5 11 16,2 weight ca. kg/km 450 500 618 188 44 53 60 80 85 115 130 160 180 220 240 260 315 375 390 435 530 590 620 54 66 81 98 115 130 158 190 238 344 74 98 114 157 195 272 349 399 464 93 129 146 198 259 354 459 786 106 140 179 246 306 390 136 174 226 440 168 168 packaging dr. dr. dr. dr. dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr., c. 100, c. 50 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr., c. 100 dr. dr. dr., c. 100 dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 168 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


Application: For signal transmission between electronic devices, in computer systems or process control units with increased requirements to electromagnetic compatibility. Due to the blue outer sheath the cable is suitable for application in intrinsical safe circuits. operating capacity core identification nominal voltage U test voltage conductor material conductor construction insulation maximum temperature at conductor screen coverage sheathing material bending radius, fixed installation flame retardant max. operating temperature, fixed temperature, moved/ during installation impedance p/n 032848 031554 034844 034845 030697 030662 030734 032020 030929 032644 032642 033763 033765 033766 031036 032284 031037 031718 031038 032005 032006 031418 032060 033767 031914 031613 034761 032144 031904 034762 033769 032643 031948 033770 033470 031949 031929 033773 034921 034922 034925 type 02X0,5 03X0,5 04X0,5 12X0,5 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 34X0,75 41X0,75 02X1 03X1 04X1 05X1 07X1 12X1 18X1 24X1 25X1 34X1 02X1,5 03X1,5 03G1,5 04X1,5 05X1,5 07G1,5 12X1,5 18X1,5 24X1,5 25X1,5 34X1,5 02X2X0,75 04X2X0,75 06X2X0,75 12X2X0,75 16X2X0,75 24X2X0,75 colour bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu bu CU kg/km 29 35 46 114 35 58 66 92 103 151 211 281 350 397 58 78 98 95 160 245 286 345 396 440 78 94 94 128 144 159 268 373 448 530 645 60 115 146 270 342 490 DA mm 4,9 5,3 6,3 9,6 6,7 7,1 7,6 8,2 9,7 12 13,9 15,1 16,9 18,3 6,9 7,3 8,1 8,6 9,2 12,1 14,4 14,5 16,1 17,9 7,7 8 8 9 10 10,5 13,7 15,5 19,5 19,5 20,8 9,5 10,3 13,3 16,8 20 24,3 120 nF/km numbers 250 V 1,2 kV bare copper fine stranded, class 5 PVC 70 C 85 % PVC 15 x DA VDE 0482-266-2-4/ IEC 60332-3-24 -30 - +80 C -5 - +70 C 85 Ohm weight ca. kg/km 36 45 54 156 56 70 95 130 168 202 304 425 523 680 84 106 130 140 192 260 340 450 534 741 97 125 125 170 180 233 356 528 705 720 900 106 179 236 430 562 794 packaging dr. dr. dr. dr. dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr., c. 100 dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Electronic cable <<<


Power cables 1 up to 30 kV

LiYCY/EB

>>> www.faberkabel.de <<<

> 169 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Electronic cable


Power cables 1 up to 30 kV

Li2YCYv
core identification nominal voltage U test voltage operating capacity conductor material conductor construction insulation screen coverage sheathing material impedance for outdoor use bending radius, fixed installation max. operating temperature, fixed p/n 031688 031689 031690 031693 031694 031695 031696 031682 031683 031684 031685 031686 031687 032858 type 02X2X0,22 03X2X0,22 04X2X0,22 01X2X0,34 02X2X0,34 03X2X0,34 04X2X0,34 01X2X0,5 02X2X0,5 03X2X0,5 04X2X0,5 08X2X0,5 10X2X0,5 24X2X0,5 250 V 2 kV 60 nF/km

Control and Electronic Cable


colours acc. DIN 47100 Application: For signal transmission in the mA-range under heavy environmental influences, in free air and for direct burial. The cable is suitable for Maxi-Thermi-Point contacting.

Building Wires

bare copper cl.2, 7-wired construction polyethylene 75 % PVC, enforced 100 Ohm yes 15 x DA -30 - +80 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 20 26 31 20 29 38 47 28 37 53 60 106 148 363 DA mm 7,9 8,2 8,8 7,4 9,1 9,5 10,1 7,9 9,9 10,3 11,1 13,9 15,8 22,8 weight ca. kg/km 46 67 83 44 68 79 95 61 73 109 122 234 284 595 packaging dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr.

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Li2YCY PiMF
nominal voltage U 250 V 2000 V colours acc. DIN 47100 75 nF/km 80 Ohm/km bare copper fine stranded, class 5 polyethylene 80 % PVC -15 - +70 C 12 x DA colour gy gy gy gy gy gy gy gy CU kg/km 33 35 49 74 91 125 38 50 DA mm 7,7 7,8 8,3 10,8 11,5 9 9,1 weight ca. kg/km 38 57 83 133 164 190 70 85 packaging dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. test voltage core identification operating capacity loop resistance conductor material conductor construction insulation screen coverage sheathing material max. operating temperature, fixed bending radius, fixed installation Application: Data cable with low operating capacity, pairs individually screened and common copper screen. Suitable for connection of control devices in environments with high level of electrical interferences. For fixed installation inside of buildings.

Other

Conductor ropes

LAN cables

p/n 031749 034575 031750 034576 034577 031850 034578 034579

type 02X2X0,22 03X2X0,22 04X2X0,22 08X2X0,22 10X2X0,22 12X2X0,25 02X2X0,34 03X2X0,34

Technical Appendix

> 170 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 034580 032142 034581 034587 034588 034589 032365 034596 031778 034604 034606 034605 034607 type 04X2X0,34 08X2X0,34 10X2X0,34 02X2X0,75 03X2X0,75 04X2X0,75 02X2X1 03X2X1 04X2X1 02X2X1,5 03X2X1,5 04X2X1,5 05X2X1,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 61 115 150 61 97 141 72 104 187 81 141 261 284 DA mm 9,4 13,4 14,3 10,4 11,3 14 11,7 12,2 12,7 12,8 14,1 17,4 18,4 weight ca. kg/km 103 191 230 117 142 222 130 158 360 164 197 480 516 packaging dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr.

Electronic cable <<<


Power cables 1 up to 30 kV

Li2YCY PiMF

Application: Highly-flexible data cable for continuous mobile use under extreme conditions with particular requirements on EMC. The cable is halogen-free, flame resistant, hydrolysis- and microbe-resistant and largely oil-resistant. Please note our instructions for the use of drag-chain cables.

nominal voltage U test voltage core identification operating capacity conductor material conductor construction insulation screen coverage transfer impedance sheathing material max. operating temperature, fixed temperature, moved/ during installation

300 V 1500 V colours acc. DIN 47100 70 nF/km bare copper fine stranded class 6 TPE 85 % 250 Ohm/km polyurethan -40 - +80 C -20 - +80 C

bending radius, moved 7,5 x DA application p/n 032139 032118 032106 032849 032893 032317 032860 033254 033255 033256 033257 033258 033259 033260 032063 033155 033156 031062 032854 032034 033157 031317 033158 032912 032913 033159 type 02X2X0,25 03X2X0,25 04X2X0,25 02X2X0,5 03X2X0,5 04X2X0,5 02X2X0,75 03X2X0,75 04X2X0,75 05X2X0,75 06X2X0,75 08X2X0,75 10X2X0,75 14X2X0,75 02X0,25 03X0,25 04X0,25 05X0,25 07X0,25 10X0,25 12X0,25 14X0,25 18X0,25 24X0,25 25X0,25 02X0,34 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 36 46 50 52 73 75 62 86 101 113 135 192,2 258 317 18,1 21 26 28,1 46 54 67 74 85 114 101 20 DA mm 6,1 8,1 8,9 7,2 10,4 11,4 9,6 11,4 12,5 13,5 14,7 18,1 20,7 20,7 4,5 5,1 5,5 6,1 6,7 8,5 8,8 9,2 11 12,3 12,3 4,9 weight ca. kg/km 60 72 89 100 118 148 112 152 170 203 229 343 467 546 38 42 49 53 80 109 124 119,4 112 195 210 31 packaging dr. dr. dr. dr. dr. dr., c. 100, c. 50 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 171 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Li12YC11Y

Flexible Cables

Building Wires

>>> Electronic cable


Power cables 1 up to 30 kV

Li12YC11Y
p/n 031296 031297 033160 033161 033162 033241 033242 033243 033244 032892 type 03X0,34 04X0,34 05X0,34 07X0,34 10X0,34 12X0,34 14X0,34 18X0,34 24X0,34 25X0,34

Control and Electronic Cable


colour gy gy gy gy gy gy gy gy gy gy CU kg/km 24 36 39,1 55 70 80 89 110 147,1 155 DA mm 5,4 6,2 6,8 7,6 9,3 9,4 9,6 10,5 12,9 12,8 weight ca. kg/km 44 52 52 72 99 166 116 140 300 292 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

LiHCH
operating capacity nominal voltage UO test voltage core identification conductor material conductor construction insulation sheathing material flame retardant max. operating temperature, fixed bending radius, fixed installation 120 nF/km 250 V 1200 V colours acc. DIN 47100 bare copper fine stranded, class 5 FRNC compound HI1 FRNC-compound HM1 VDE 0482-332-1-2/IEC 60332-1 -30- +70 C 7,5 x DA Application: For signal transmission between electronic devices, in computer systems or process control units with increased requirements to electromagnetic compatibility.

Cable with circuit integrity

Control and Electronic Cable

bending radius, moved 15 x DA application p/n 032696 032697 032698 032104 032700 032107 032105 032703 031966 031963 031833 031964 031967 032085 032705 032706 032662 032707 032664 032708 032709 032710 032711 032712 032713 type 02X0,5 03X0,5 04X0,5 05X0,5 07X0,5 12X0,5 18X0,5 25X0,5 02X0,75 03X0,75 04X0,75 05X0,75 07X0,75 12X0,75 18X0,75 25X0,75 02X1 03X1 04X1 05X1 07X1 02X1,5 03X1,5 04X1,5 05X1,5 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 29 35 45 54 72 101 143 211 35 46 58 70 90 154 195 280 43 56 68 79 118 58 74 108 129 DA mm 5,8 6,1 6,5 7,2 7,9 9,8 11,7 13,9 6,2 6,5 7,2 7,8 8,5 11,1 12,7 15,5 6,5 7 7,5 8,2 8,8 7,7 8,1 8,7 9,5 weight ca. kg/km 38 47 62 76 86 148 210 319 45 60 92 97 120 196 327 454 72 90 109 126 171 90 115 153 176 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

> 172 <

>>> www.faberkabel.de <<<

Control and Electronic Cable


p/n 031809 031872 031816 032658 031846 032724 032725 031817 031818 031896 032728 032729 032730 032731 032732 032733 032659 032734 032735 032736 type 07X1,5 02X2X0,25 03X2X0,25 04X2X0,25 06X2X0,25 08X2X0,25 10X2X0,25 12X2X0,25 02X2X0,5 03X2X0,5 04X2X0,5 06X2X0,5 08X2X0,5 12X2X0,5 02X2X0,75 03X2X0,75 04X2X0,75 06X2X0,75 08X2X0,75 12X2X0,75 colour gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy gy CU kg/km 164 28 39,6 54,5 69,5 78 110 120 48,1 73,7 82 110 139 199 65 92 115 146 180 270 DA mm 10,7 7,2 7,3 8,1 9,1 10,5 11,2 12,1 8,8 9 10,3 11,4 13,3 16 9,5 10,1 11,5 13,4 14,9 18,3 weight ca. kg/km 220 54 66 81 115 130 155 190 93 129 140 187 259 342 106 138 170 241 305 441 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Electronic cable <<<


Power cables 1 up to 30 kV

LiHCH

>>> www.faberkabel.de <<<

> 173 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Bus cables


Power cables 1 up to 30 kV

Bus cables, industrial


Type 100456 100396 101011 101010 100569 100568 100571 100570 100926 100573 100574 100961 100613 100621 100578 100935 100488 100579 100576 100544 100575 100533 100503 100543 100542 033831 033833

Control and Electronic Cable


FACAB EIB-Busleitung halogenfrei 02X2X0,8 GN FACAB EIB-Busleitung 02X2X0,8 GN FACAB EIB-Busleitung 04X2X0,8 GN FACAB EIB-Busleitung 02X2X0,8 GN FACAB AS-Interface BUS Gummi 02X1,5 SW FACAB AS-Interface BUS Gummi 02X1,5 GE FACAB AS-Interface BUS TPE 02X1,5 SW FACAB AS-Interface BUS TPE 02X1,5 GE CAN-Bus-Sk PUR 04X1X0,25 VL CAN-Bus UL/CSA Li02YSC11Y 02X2X0,5 VL CAN-Bus Li02YSCY 02X2X0,5 VL CAN-Bus UL/CSA Li02YSCY 02X2X0,34 VL CAN-Bus UL/CSA Li02YSCY 01X2X0,34 VL CAN-Bus UL/CSA Li02YSCY 02X2X0,22 VL Profibus Schleppkette L2/FIP/DP/FMS AD(St)C11Y 01X2X0,64 VL Profibus Festoon PVC L2/FIP/DP/FMS 01X2X0,65 PT Profibus Erdverlegung L2/FIP/DP/FMS 2Y(St)CY2Y 01X2X0,64 SW Profibus UL/CSA L2 FIP/DP/FMS 2Y(St)CY 01X2X0,64 VL Profibus Fast Connect L2/FIP/DP/FMS 2YY(St)CY 01X2X0,64 VL Profibus FRNC L2/FIP/DP/FMS 2Y(St)CH 01X2X0,64 GN Profibus PVC L2/FIP/DP/FMS 2Y(St)CY 01X2X0,64 VL Sprechanlagen-Bus FRNC LiH 02X1,5 + Li2Y 02X2X0,6 GR Sprechanlagen-Bus LiY 02X1,5 + Li2Y 02X2X0,6 GN Profibus PA 01X2X1 SW Wellenwiderstand 100 +- 20 Ohm Profibus PA 01X2X1 BL Wellenwiderstand 100 +- 20 Ohm AES/EBU & DMX 110 Ohm (02X0,34)StDY BL AES/EBU & DMX 110 Ohm (04X0,34)StCY SW CU kg/km 21 21 41 21 29 29 28 28 41,3 59,4 59,4 46,4 23 36 28 30,1 26 26 26 22,4 26 57 53 45 45 50 33 G kg/km 55 55 92 55 57 57 57 57 58 106 106 88 55 70 64 63 87 57 60 55 57 90 90 73 73 10,2 65 DA [mm] 6,3 6,3 6,3 4 x 10 4 x 10 4 x 10 4 x 10 9,6 9,6 9,6 8,0 6,5 6,9 8,1 8,3 10,0 7,8 7,8 7,8 7,8 8,5 8,5 7,9 7,9 6,6 7,2

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 174 <

>>> www.faberkabel.de <<<

Control and Electronic Cable

Bus cables <<<


Power cables 1 up to 30 kV

Frequently used bus-systems

Frequently used bus-systems Typ Interbus PROFIBUS CAN (Controller-Area Network) AS-I (Actor-Sensor Interface) LON (Local Operating Network) EIB/KNX DeviceNetTM DESINA Standard IEC 61158 ISO 11898-2 EN 50295, IEC 62026-2 EN 14908 EN 50090, ISO/IEC 14543 ODVA VDW Structure of network Ring linear linear/Stern jede linear Data rate 500 kBit/s 500 kBit/s 100 kBit/s 167 kBit/s

>>> www.faberkabel.de <<<

> 175 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

In the meantime, components for many bus systems are certified by the body which determines the bus specifications. This reveals that the differences between the individual cables of different bus systems or within one single system are less to be found in the electrical or transmission technology properties of the cables but rather in their suitability for often extremely limited applications, e.g. their use in drag chains, laying directly in the ground or resistance against various environmental factors. In some systems, the power for the individual components is also supplied via the bus alongside the data, sometimes even via the same pair of wires. Furthermore, most cable types are available in a "conventional" (usually PVC-covered) or halogen-free version.

Building Wires

Application: The use of sensors, actors and processing electronics has been a standard instrument in industrial measurement, control and regulation technology for decades now. In this area, systems using distributing intelligence compete with centrally organised systems. In all cases, however, data must be transported to and from the sources, consumers or processors of information. In most cases this still takes place through copper data cables, although wireless radio or IR solutions or optic fibre cables are gaining more and more ground. Together with the corresponding transmitting and receiving components, these data cables form a so-called bus system. Even if the interior of the data lines in most systems is quite similar (one or two pairs of twisted wires mfor serial data transmission), each different system supplier has still developed a series of more or less proprietary cables which have been specially designed for the application of his individual bus system.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity Flexible Cables Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Power cables 1 up to 30 kV

> 176 <

>>> Cabel with circuit integrity E30 or E90

Notes:

>>> www.faberkabel.de <<<

Cabel with circuit integrity E30 or E90 <<<


Power cables 1 up to 30 kV

creative

Content

184 185 185 186

>>> www.faberkabel.de <<<

> 177 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Fire resistant communication cable JE-H(St)H FE180/E30 JE-H(St)H FE180/E30 Brandmeldekabel JE-H(St)H E30-E90 JE-H(St)H E30-E90 BMK JE-H(St)HRH FE180/E90

184 184

Telecommunication Cables and Cords

Fire resistant power cable NHXH-J/-O E30 NHXCH E30 NHXH-J/-O E90 NHXCH E90

178 178 180 181 182

Flexible Cables

Building Wires

>>> Fire resistant power cable


Power cables 1 up to 30 kV

NHXH-J/-O E30

Cabel with circuit integrity E30 or E90


VDE 0266 colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 4 kV 1,2 kV bare copper class 1, from 25 sqmm class 2 FRNC compound HI1 FRNC-compound HM1 90 C -5 - +70 C 12 x DA E 30 FE 180 VDE 0482-266-2-4/ IEC 60332-3-24 colour og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og CU kg/km 38 58 96 154 240 336 480 672 912 1152 1440 1776 2304 2880 29 48 77 115 192 307 480 1776 2304 43 72 115 173 288 461 720 1008 1440 2016 874 1162 1680 2352 3216 4128 4992 6240 DA mm 6,9 7,9 8,1 8,9 10,9 11,9 12,9 15,9 17,9 18,9 20,9 23,9 26,9 32,9 10,2 10,9 11,9 12,8 14,4 17,3 21,1 23,9 26,9 10,9 11,9 12,9 13,9 15,9 17,9 23,9 25,9 28,9 31,9 23,4 26,9 29,9 34,9 38,9 42,9 46,9 52,9 weight ca. kg/km 100 120 160 200 310 410 540 740 1020 1380 1560 1930 2540 3180 190 220 270 320 430 620 900 1930 2540 210 260 320 400 550 790 1150 1490 1980 2830 1500 1800 2600 3400 4600 5700 6800 8500 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814 (180 min., = IEC 60331). Furthermore the cable passed the test of 30 min. circuit integrity according to DIN 4102 part 12 (E 30) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by the Amtlichen Materialprfanstalt fr das Bauwesen. For calculation of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 800 C is approximately four times higher than at 20 C and the current carrying capacity is reduced respectively.

standard core identification nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor max. operating temperature, fixed bending radius, fixed installation circuit integrity Circuit integrity flame retardant p/n 011238 011240 011229 011232 011235 011237 011239 011241 011242 011230 011231 011233 011234 011236 011243 011246 011248 011249 011244 011245 011247 012034 012198 011044 011171 011172 011194 011182 011185 011251 011253 011255 011257 011252 011254 011256 011258 011186 011269 011270 011271 type 01X4 01X6 01X10 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 02X1,5 02X2,5 02X4 02X6 02X10 02X16 02X25 01X185 01X240 03X1,5 03X2,5 03X4 03X6 03X10 03X16 03X25 03X35 03X50 03X70 03X25/16 03X35/16 03X50/25 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

> 178 <

>>> www.faberkabel.de <<<

Fire resistant power cable <<< Cabel with circuit integrity E30 or E90
Power cables 1 up to 30 kV

NHXH-J/-O E30

p/n 011272 011188 011045 011217 011218 011219 011220 011221 011189 011222 011196 011261 011259 011260 011190 011046 011192 011193 011173 011195 011262 012469 011047 011223 011214 011180 011263 011264 011265 011266 011267 011268

type 3X240/120 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 05X35 07X1,5 07X2,5 12X1,5 12X2,5 19X1,5 19X2,5 24X1,5 24X2,5 30X1,5 30X2,5

colour og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og

CU kg/km 8064 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 72 120 192 288 480 768 1200 1680 101 168 173 288 274 456 346 576 432 720

DA mm 58,8 11,9 12,9 13,9 14,9 16,9 19,9 24,9 27,9 31,9 36,9 40,9 44,9 49,9 12,9 13,9 14,9 16,9 18,9 22,9 26,6 30,5 13,9 14,9 18,9 21,9 21,9 23,9 24,9 26,9 25,9 28,9

weight ca. kg/km 11000 240 300 390 490 670 950 1430 1890 2510 3650 4750 5910 7240 280 354 450 570 820 1140 1710 2384 330 430 500 650 720 950 890 1210 1090 1470

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 179 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Fire resistant power cable


Power cables 1 up to 30 kV

NHXCH E30

Cabel with circuit integrity E30 or E90


VDE 0266 colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 4 kV 1,2 kV bare copper class 1, from 25 sqmm class 2 FRNC compound HI1 FRNC-compound HM1 90 C -5 - +70 C 12 x DA VDE 0482-266-2-4/ IEC 60332-3-24 E 30 FE 180 colour og og og og og og og og og og og og og og og og og og og og og og og og og og CU kg/km 52 80 123 66 104 5100 6383 81 128 200 297 504 796 1142 1526 2203 3082 4208 5388 6540 8159 10546 133 200 205 334 DA mm 10,8 11,9 12,9 11,9 12,9 46,9 52,9 13,9 14,1 14,9 16,9 18,9 21,9 26,9 29,9 33,9 38,9 42,9 46,9 52,9 58,9 64,9 16,9 17,9 19,9 21,9 weight ca. kg/km 300 350 420 320 380 7713 8810 249 313 412 522 746 1119 1583 2002 2700 3838 5181 6500 7950 10130 13190 500 600 700 900 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For installation in dry and wet rooms, also for direct bedding in concrete, but not for direct burial in ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814 (180 min., = IEC 60331). Furthermore the cable passed the test of 30 min. circuit integrity according to DIN 4102 part 12 (E 30) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by the Amtlichen Materialprfanstalt fr das Bauwesen. For calculation of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 800 C is approximately four times higher than at 20 C and the current carrying capacity is reduced respectively.

standard core identification nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor max. operating temperature, fixed bending radius, fixed installation flame retardant circuit integrity Circuit integrity p/n 011505 011506 011507 011278 011215 011831 011832 011280 011281 011282 011226 011224 011181 011167 011183 011227 011168 011184 011274 011275 011276 011277 011279 011283 011284 011285 type

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Technical Appendix

Other

Conductor ropes

02X1,5/1,5 02X2,5/2,5 02X4/4 03X1,5/1,5 03X2,5/2,5 03X150/70 03X185/95 04X1,5/1,5 04X2,5/2,5 04X4/4 04X6/6 04X10/10 04X16/16 04X25/16 04X35/16 04X50/25 04X70/35 04X95/50 04X120/70 04X150/70 04X185/95 04X240/120 07X1,5/2,5 07X2,5/2,5 12X1,5/2,5 12X2,5/4

LAN cables

Cable with circuit integrity

> 180 <

>>> www.faberkabel.de <<<

Fire resistant power cable <<< Cabel with circuit integrity E30 or E90
Application: For installation in dry and wet rooms, also for direct bedding in concrete, butnot for direct burial in ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814 (180 min., = IEC 331) Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by the Amtlichen Materialprfanstalt fr das Bauwesen. For calculation of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 1000 C is approximately 4,5 times higher than at 20 C and the current carrying capacity has to be reduced respectively. standard core identification test voltage nominal voltage UO nominal voltage U maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor max. operating temperature, fixed bending radius, fixed installation flame retardant circuit integrity Circuit integrity p/n 012020 012021 012022 011757 011843 011756 011744 011177 011755 011754 011178 012221 012011 010951 010952 010953 010954 010955 010956 010957 010958 010959 010960 010961 010962 010963 010964 011950 011955 011949 011956 011869 011963 010965 010966 010967 010968 010969 010970 010971 012042 type 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 01X300 01X400 02X1,5 03X1,5 03X2,5 03X4 03X6 03X10 03X16 04X1,5 04X2,5 04X4 04X6 04X10 04X16 04X25 04X35 04X50 04X70 04X95 04X120 04X150 04X240 05X1,5 05X2,5 05X4 05X6 05X10 05X16 05X25 05X50 colour og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og CU kg/km 154 240 336 480 672 912 1152 1440 1776 2304 2880 3840 29 43 72 115 173 288 461 58 96 154 230 384 614 960 1344 1920 2688 3648 4608 5760 9216 72 120 192 288 480 768 1200 2400 DA mm 10,5 12,5 13,5 13,9 16,5 18,9 20,5 22,5 24,9 27,9 30,9 34,9 13,9 14,9 15,9 16,7 17,8 19,4 22,3 16,1 16,9 17,9 19,2 21,1 24,3 28,1 30,9 35,1 39,9 45,2 48,9 50,9 64,9 17,4 18,4 19,5 20,9 22,9 26,6 30,9 VDE 0266 colours acc. VDE 0293 (HD308) 4 kV 0,6 kV 1 kV 1,2 kV bare copper class 1, from 25 sqmm class 2

FRNC-compound HM1 90 C -5 - +70 C 12 x DA VDE 0482-266-2-4/ IEC 60332-3-24 E 90 FE 180 weight ca. kg/km 230 340 440 600 800 1100 1350 1650 2000 2600 3200 4200 210 210 243 302 399 546 765 245 299 376 474 657 973 1422 1858 2900 3900 5200 6300 6800 10700 290 359 457 577 807 1145 1765 3700 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 181 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

FRNC compound HI1

Building Wires

Power cables 1 up to 30 kV

NHXH-J/-O E90

>>> Fire resistant power cable


Power cables 1 up to 30 kV

NHXH-J/-O E90
p/n

Cabel with circuit integrity E30 or E90


type 07X1,5 07X2,5 12X1,5 12X2,5 24X1,5 colour og og og og og CU kg/km 101 168 173 288 346 DA mm 18,6 19,8 23,5 25,2 26,9 weight ca. kg/km 350 443 545 780 735 packaging dr. dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

010989 011124 011020 011982 011162

NHXCH E90
standard core identification nominal voltage UO nominal voltage U test voltage maximum permitted operating voltage in 3-phase systems conductor material conductor construction insulation sheathing material maximum temperature at conductor VDE 0266 colours acc. VDE 0293 (HD308) 0,6 kV 1 kV 4 kV 1,2 kV bare copper class 1, from 25 sqmm class 2 FRNC compound HI1 FRNC-compound HM1 90 C -5 - +70 C 12 x DA VDE 0482-266-2-4/ IEC 60332-3-24 E 90 FE 180 colour og og og og og og og og og CU kg/km 66 104 161 240 408 643 902 1190 1723 DA mm 16,8 17,9 18,9 20,9 24,1 27,3 30,7 33,3 37,4 weight ca. kg/km 348 410 500 614 830 1073 1450 1798 2394 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For installation in dry and wet rooms, also for direct bedding in concrete, butnot for direct burial in ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814 (180 min., = IEC 331) Furthermore the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E 90) for all so called standard-installation systems (ladder, tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108. A special test certificate about the circuit integrity is issued by the Amtlichen Materialprfanstalt fr das Bauwesen. For calculation of electrical systems with circuit integrity has to bee considered that electrical resistance of copper conductors at 1000 C is approximately 4,5 times higher than at 20 C and the current carrying capacity has to be reduced respectively.

Conductor ropes

LAN cables

Cable with circuit integrity

max. operating temperature, fixed bending radius, fixed installation flame retardant circuit integrity Circuit integrity

Other

p/n 011042 011043 011209 011208 011207 011206 011205 011204 011197

type 03X1,5/1,5 03X2,5/2,5 03X4/4 03X6/6 03X10/10 03X16/16 03X25/16 03X35/16 03X50/25

Technical Appendix

> 182 <

>>> www.faberkabel.de <<<

Fire resistant power cable <<< Cabel with circuit integrity E30 or E90
Power cables 1 up to 30 kV

NHXCH E90

p/n 011203 011213 011202 011201 011200 011198 010995 010996 010997 010987 010994 010998 010999 010993 011000 011001 011002 011003 011004 011005 011006 011747 011749 010988 011007 011008 011009 011748 011210 011211 011212 011199

type 03X70/35 03X95/50 03X120/70 03X150/70 03X185/95 03X240/120 04X1,5/1,5 04X2,5/2,5 04X4/4 04X6/6 04X10/10 04X16/16 04X25/16 04X35/16 04X50/25 04X70/35 04X95/50 04X120/70 04X150/70 04X185/95 04X240/120 05X2,5/2,5 05X4/4 07X1,5/2,5 07X2,5/2,5 12X1,5/2,5 12X2,5/4 12X4/6 24X1,5/6 24X2,5/10 30X1,5/6 30X2,5/10

colour og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og og

CU kg/km 2410 3296 4236 5100 6383 8242 81 128 200 297 504 796 1142 1526 2203 3082 4208 5388 6540 8159 10546 152 238 133 200 205 334 528 413 696 499 840

37,6 40,9 39,8 42,9

>>> www.faberkabel.de <<<

> 183 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

20,5 20,9 22,1 26,2 28,4

Telecommunication Cables and Cords

DA mm 42,5 47,8 51,4 55,7 61,7 67,9 17,9 19,2 20,3 22,5 26,4 29,3 33,1 35,9 41,1 46,2 51,9 55,9 60,9 67,5 74,4

weight ca. kg/km 2796 4434 5534 6546 8303 10605 398 470 578 726 983 1370 1904 2427 3177 4378 5803 7230 8707 10894 13933 480 600 498 680 718 1050 1100 1305 1400 1519 1550

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Flexible Cables

Building Wires

>>> Fire resistant communication cable


Power cables 1 up to 30 kV

JE-H(St)H FE180/E30
standard

Cabel with circuit integrity E30 or E90


VDE 0815 colours + rings tinned copper solid, class 1 FRNC compound HI1 FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 E 30 FE 180 -5 - +50 C colour og og og og og og og og og CU kg/km 25 45 85 126 166 206 326 407 529 DA mm 7,5 9,3 11,4 13,5 15 16,5 19,5 22,5 25,2 weight ca. kg/km 76 130 232 318 430 514 730 962 1200 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For signal transmission within systems for measuring-, data-, control- engineering and as installation cable in fire hazardous rooms with a high concentration of persons or material value, for installation of fire survival cable systems acc. to DIN 4102 part 12. For fixed installation in dry and wet rooms.

core identification conductor material conductor construction insulation sheathing material flame retardant circuit integrity Circuit integrity max. operating temperature, fixed p/n 100418 100419 100420 100421 100422 100423 100424 100425 100426 type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 16X2X0,8 20X2X0,8 32X2X0,8 40X2X0,8 52X2X0,8

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

JE-H(St)H FE180/E30 Brandmeldekabel


core identification operating capacity nominal voltage U conductor material insulation sheathing material flame retardant colours + rings 120 nF/km 225 V bare copper FRNC compound HI1 FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 E 30 FE 180 15 x DA -30 - +70 C colour rd rd rd rd rd rd rd rd rd CU kg/km 25 45 85 126 166 206 326 407 529 DA mm 7,5 9,3 11,4 13,5 15 16,5 19,5 22,5 25,2 weight ca. kg/km 76 130 232 318 430 514 730 962 1200 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: For signal transmission between electronic devices, in computer systems of process control units in fireendangered areas with high person or real value concentration, for installation of circuits with circuit integrity E30/E90 according to DIN 4102 part 12, with tested cable systems. For fixed installation in dry and damp areas on certified carrier systems. By the special seath printing this cable is particularly designed for the use in fire signalisation systems.

Cable with circuit integrity

LAN cables

circuit integrity Circuit integrity bending radius, fixed installation max. operating temperature, fixed p/n 100427 100428 100429 100430 100431 100432 100433 100434 100435 type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 16X2X0,8 20X2X0,8 32X2X0,8 40X2X0,8 52X2X0,8

Technical Appendix

Other

Conductor ropes

> 184 <

>>> www.faberkabel.de <<<

Fire resistant communication cable <<< Cabel with circuit integrity E30 or E90
Application: For signal transmission within systems for measuring-, data-, control- engineering and as installation cable in fire hazardous rooms with a high concentration of persons or material value, for installation of fire survival cable systems acc. to DIN 4102 part 12. For fixed installation in dry and wet rooms. standard core identification operating capacity test voltage conductor material insulation sheathing material flame retardant Circuit integrity circuit integrity max. operating temperature, fixed p/n 100275 100276 100277 100292 100278 100279 100280 100281 100282 type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 16X2X0,8 20X2X0,8 32X2X0,8 40X2X0,8 52X2X0,8 colour og og og og og og og og og CU kg/km 25 45 85 126 166 206 326 407 529 DA mm 7,4 11,1 15,6 18,1 19,8 22,5 27,7 30,8 34,7 VDE 0815 colours + rings 120 nF/km 300 V FRNC compound HI1 FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 FE 180 E30-E90 -5 - +50 C weight ca. kg/km 76 130 232 318 430 514 730 962 1200 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. tinned copper

JE-H(St)H E30-E90 BMK


Application: For signal transmission between electronic devices, in computer systems of process control units in fireendangered areas with high person or real value concentration, for installation of circuits with circuit integrity E30/E90 according to DIN 4102 part 12, with tested cable systems. For fixed installation in dry and damp areas on certified carrier systems. By the special seath printing this cable is particularly designed for the use in fire signalisation systems. standard core identification operating capacity test voltage conductor material insulation sheathing material flame retardant circuit integrity Circuit integrity max. operating temperature, fixed VDE 0815 colours + rings 120 nF/km 300 V tinned copper FRNC compound HI1 FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 E30-E90 FE 180 -5 - +50 C

p/n 100283 100284 100285 100286 100287 100288 100289 100290 100291

type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 16X2X0,8 20X2X0,8 32X2X0,8 40X2X0,8 52X2X0,8

colour rd rd rd rd rd rd rd rd rd

CU kg/km 25 45 85 126 166 206 326 407 529

DA mm 7,4 11,1 15,6 18,1 19,8 22,5 27,7 30,8 34,7

weight ca. kg/km 76 130 232 318 430 514 730 962 1200

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 185 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Power cables 1 up to 30 kV

JE-H(St)H E30-E90

>>> Fire resistant communication cable


Power cables 1 up to 30 kV

JE-H(St)HRH FE180/E90
standard

Cabel with circuit integrity E30 or E90


VDE 0815 colours + rings tinned copper solid, class 1 FRNC compound HI1 halogenfrei steel wire braiding, galvanized FRNC-compound HM2 VDE 0482-266-2-4/ IEC 60332-3-24 E 90 FE 180 -5 - +50 C colour rd rd rd rd rd CU kg/km 25 45 85 126 206 DA mm 11,3 15,3 22,1 22,9 28 weight ca. kg/km 174 286 465 600 777 packaging dr. dr. dr. dr. dr. Application: For signal transmission within systems for measuring-, data-, control- engineering and as installation cable in fire hazardous rooms with a high concentration of persons or material value, for installation of fire survival cable systems acc. to DIN 4102 part 12. For fixed installation in dry and wet rooms.

core identification conductor material conductor construction insulation inner sheath armour sheathing material flame retardant

Flexible Cables

Building Wires

circuit integrity Circuit integrity max. operating temperature, fixed p/n type 02X2X0,8 04X2X0,8 08X2X0,8 12X2X0,8 20X2X0,8

Telecommunication Cables and Cords

100465 100466 100467 100464 100468

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 186 <

>>> www.faberkabel.de <<<

LAN cable <<<


Power cables 1 up to 30 kV

independent

Content

Cables up to 100 MHz FACAB dataline 100 Cables up to 200 MHz FACAB dataline 200 Cables up to 1000 MHz FACAB dataline 1000 FACAB dataline 1000 outdoor Optical cables - indoor I-V(ZN)H - Standard I-V(ZN)H - High Grade I-D(ZN)H - Standard I-D(ZN)H - High Grade Optical Cables - outdoor A-DQ(ZN)B2Y A-DQ(ZN)2Y U-DQ(ZN)BH A-DQ(ZN)B2Y ... 1,2 kN

189 189 190 190 191 191 191 192 192 192 193 193 194 194 194 195 195

>>> www.faberkabel.de <<<

> 187 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Network-cable Industrial Ethernet

188 188

Flexible Cables

Building Wires

>>> Network-cable
Power cables 1 up to 30 kV

Industrial Ethernet
core identification operating capacity test voltage conductor material conductor construction insulation screen coverage sheathing material category velocity factor impedance bending radius, fixed installation flame retardant max. operating temperature, fixed p/n 100717 100716 100837 101040 type 2X2XAWG 26 2X2XAWG 24 4X2XAWG 26 2X2XAWG 22 colours acc. IEC 60708 48 nF/km 1000 V bare copper see part description foam-skin 85 % polyurethan 5e 0,75 v/c 100 Ohm 8 x DA VDE 0482-332-1-2/IEC 60332-1 -5 - +70 C colour gn gn gn gn CU kg/km 35 42 27 42 DA mm 5,9 5,9 6,5

LAN cables
Application: For connection of IT system units in the desktop and distribution area in industrial environments (INDUSTRIAL ETHERNET). For use in dry and wet rooms as well as temporary outdoors under medium mechanical stress. The AWG 26 version may be connected with RJ 45 plugs.

Telecommunication Cables and Cords

Flexible Cables

Building Wires

weight ca. kg/km 45 53 55 64

packaging dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

> 188 <

>>> www.faberkabel.de <<<

LAN cables
Application: For connection of IT system units in the desktop area, between workstations and as riser cable up to 100 Mbit/s (Categorie 5). It fully complies with the equirements to electromagnitc compatibilty (EMC) of the European Standard EN 55 022. standard test voltage operating capacity conductor material conductor construction insulation sheathing material category impedance bending radius, fixed installation 500 V 50 nF/km bare copper solid, class 1 polyolefin polyolefin 5 100 Ohm 4 x DA

Cables up to 100 MHz <<<


Power cables 1 up to 30 kV

FACAB dataline 100


ISO/IEC 11801, EN 50173, EN 55022, E DIN 44312-5

bending radius, moved 8 x DA application velocity factor p/n 100366 100386 type colour CU kg/km 19,2 10 DA mm 6,6 5 0,66 v/c weight packaging ca. kg/km 44 dr. 27 dr.

4X2XAWG 24 og 4X2XAWG 26 flex gy

>>> www.faberkabel.de <<<

> 189 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Cables up to 200 MHz


Power cables 1 up to 30 kV

FACAB dataline 200


core identification operating capacity loop resistance conductor material conductor construction insulation sheathing material max. operating temperature, fixed bending radius, fixed installation colours acc. IEC 60708 50 nF/km 170 Ohm/km bare copper solid, class 1 cross-linked polyolefincopolymer polyolefin-compound HM4, FRNC -5 - +50 C 8 x DA

LAN cables
Application: To the connection of EDP system units within the desktop area (Tertiary period range), as between floor distributors and desktop acc. to category 5e (enhanced). It corresponds to the requirements of the EN 55022 and the guidelines of the European postal administration regarding interferences (EMV). Additionally the tinned screen braid offers a smooth connection to screened data plugs.

Flexible Cables

Building Wires

bending radius, moved 4 x DA application flame retardant category impedance velocity factor transfer impedance p/n 100592 100593 type 4X2XAWG 24 2X4XAWG 24 VDE 0482-332-1-2/IEC 60332-1 5e 100 Ohm 0,66 v/c 100 Ohm/km colour og og CU kg/km 29 58 DA mm 6,6 wxh ca. mm 13,4 x 6,6 weight packaging ca. kg/km 54 dr., c. 100 108 dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 190 <

>>> www.faberkabel.de <<<

LAN cables
Application: For connection of IT system units in the desktop area, between workstations and as riser cable up to 1000 Mbit/s (category 7+). It fully complies with the requirements to electromagnetic compatibilty (EMC) of the European Standard EN 55022. Additional the copper braiding ensures perfect matching with screened connectors. core identification test voltage conductor material insulation transfer impedance sheathing material flame retardant category velocity factor impedance max. operating temperature, fixed 500 V bare copper foam-PE 5 Ohm/km

Cables up to 1000 MHz <<<


Power cables 1 up to 30 kV

FACAB dataline 1000


colours acc. IEC 60708

FRNC-compound HM2 VDE 0482-332-1-2/IEC 60332-1 7+ 0,74 v/c 100 Ohm

bending radius, moved 8 x DA application bending radius, fixed installation p/n 100952 100951 101043 type colour CU kg/km 32 64 32 DA mm 7,5 15 7,5 4 x DA weight ca. kg/km 65 130 65 packaging dr., c. 50, c. 100 dr., c. 50, c. 100 box

4X2XAWG 23 og 2X4X2XAWG 23 og 4X2XAWG 23 og

FACAB dataline 1000 outdoor


Application: For connection of IT system units in the desktop area, between workstations and as riser cable up to 1000 Mbit/s (category 7+). It fully complies with the requirements to electromagnetic compatibilty (EMC) of the European Standard EN 55022. Additional the copper braiding ensures perfect matching with screened connectors. category conductor material insulation 7+ bare copper foam-PE

bending radius, moved 8 x DA application bending radius, fixed installation sheathing material for outdoor use velocity factor impedance max. operating temperature, fixed temperature, moved/ during installation 4 x DA polyethylene yes 0,78 v/c 100 Ohm -20 - +70 C -20 - +50 C weight packaging ca. kg/km 95 dr.

p/n 101008

type 4X2XAWG 23

colour bk

CU kg/km 44

DA mm 9,4

>>> www.faberkabel.de <<<

> 191 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

wxh ca. mm

Flexible Cables

- 20 bis 70 C

Building Wires

>>> Optical cables - indoor


Power cables 1 up to 30 kV

I-V(ZN)H - Standard
fiber quality standard fiber quality flame retardant sheathing material max. operating temperature, fixed temperature, moved/ during installation for outdoor use p/n type 02X1G50 01X4G50 02X1G62,5 01X4G62,5 01X6G50 01X8G50 01X10G50 01X12G50 01X16G50 01X6G62,5 01X8G62,5 01X10G62,5 01X12G62,5 01X4G50 02X1G50 standard on request VDE 0482-332-1-2/IEC 60332-1 FRNC-compound HM1 -20 - 60 C -20 - 60 C no colour og og og og og og og og og og og og og OH OH DA mm 6 5,1 5,1 5,5 5,7 6,5 6,5 5,5 5,7 6,5 6,5 5,1

LAN cables
Application: Indoor distribution cable with tight buffers and LSOH jacket. For installation on cable trays and ducts. The cable offers up to 24 fibers, which may be directly assembled to connectors and are suitable for field-assembly.

Building Wires

Control and Electronic Cable

070114 070112 070113 070111 070147 070122 070150 070152 070221 070148 070149 070151 070153 070241 070240

weight ca. kg/km 19,3 32 19,3 32 36 36 41 41 43 36 36 41 41 32 19

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Telecommunication Cables and Cords

Flexible Cables

I-V(ZN)H - High Grade


fiber quality standard fiber quality flame retardant sheathing material max. operating temperature, fixed temperature, moved/ during installation for outdoor use p/n 070240 070241 type 02X1G50 01X4G50 high-grade on request VDE 0482-332-1-2/IEC 60332-1 FRNC-compound HM1 -20 - 60 C -20 - 60 C no colour OH OH DA mm 5,1 weight packaging ca. kg/km 19 dr. 32 dr. Application: Indoor distribution cable with tight buffers and LSOH jacket. For installation on cable trays and ducts. The cable offers up to 24 fibers, which may be directly assembled to connectors and are suitable for field-assembly.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 192 <

>>> www.faberkabel.de <<<

LAN cables
Application: Optical indoor cable with central multi fiber loose buffer and halogen-free outer sheath. For installation inside of buildings on cabel trays and in cable ducts. The cable must be terminated with a cable termination or in a cable splitter, direct mounting of fiber-connectors is not possible. fiber quality standard fiber quality for outdoor use flame retardant sheathing material max. operating temperature, fixed temperature, moved/ during installation p/n 070110 070108 070106 070220 070109 070107 070105 070243 070244 070245 070242 type 01X4G50 01X8G50 01X12G50 01X24G50 01X4G62,5 01X8G62,5 01X12G62,5 01X8G50 01X12G50 01X24G50 01X4G50 colour og og og og og og og OH OH OH OH DA mm 6 6 6 10 6 6 6 6 6 10 6 standard on request no

Optical cables - indoor <<<


Power cables 1 up to 30 kV

I-D(ZN)H - Standard

VDE 0482-332-1-2/IEC 60332-1

-20 - 60 C -20 - 60 C weight ca. kg/km 33 33 33 35 33 33 33 33 33 35 33 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

I-D(ZN)H - High Grade


Application: Optical indoor cable with central multi fiber loose buffer and halogen-free outer sheath. For installation inside of buildings on cabel trays and in cable ducts. The cable must be terminated with a cable termination or in a cable splitter, direct mounting of fiber-connectors is not possible. fiber quality standard fiber quality for outdoor use flame retardant sheathing material max. operating temperature, fixed temperature, moved/ during installation p/n 070244 070245 070242 070243 type 01X12G50 01X24G50 01X4G50 01X8G50 colour OH OH OH OH high-grade on request no VDE 0482-332-1-2/IEC 60332-1 FRNC-compound HM1 -20 - 60 C -20 - 60 C weight ca. kg/km 33 35 33 33 packaging dr. dr. dr. dr.

>>> www.faberkabel.de <<<

> 193 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

FRNC-compound HM1

>>> Optical Cables - outdoor


Power cables 1 up to 30 kV

A-DQ(ZN)B2Y
standard standard fiber quality for outdoor use flame retardant sheathing material bendig radius with tension load bending radius without tension load max. operating temperature, fixed temperature, moved/ during installation p/n 070044 070137 070049 070006 070089 070095 070091 070086 070067 070023 070104 070066 070138 070103 070202 070090 type 01X4G50 01X6G50 01X8G50 01X12G50 01X16G50 01X24G50 03X12G50 04X12G50 01X4G62,5 01X6G62,5 01X8G62,5 01X12G62,5 01X16G62,5 01X24G62,5 03X12G62,5 04X12G62,5 ISO/IEC 794, DIN VDE 0888 on request yes no polyethylene 220 mm 170 mm -20 - +70 C 0 - +50 C colour bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk bk DA mm 8,4 8,4 8,4 8,4 8,4 8,4 11,5 11,5 8,4 8,4 8,4 8,4 8,4 9,2 11,5 11,5

LAN cables
Application: Optical cable with central loose tube, glass yarn strength members/rodentprotection and water blocking elements. Due to the abrasion resistant PE-jacket and good mechanical properties the cable is suitable for installation in trunking in industrial environments or for direct burial.

Flexible Cables

Building Wires

weight ca. kg/km 64 64 64 64 64 74 107 107 64 64 64 64 64 74 107 107

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

A-DQ(ZN)2Y
standard standard fiber quality for outdoor use ISO/IEC 794, DIN VDE 0888 on request yes no polyethylene 220 mm 170 mm -20 - +70 C 0 - +50 C colour dbu dbu dbu dbu dbu dbu dbu dbu dbu dbu DA mm 8,4 8,4 8,4 8,4 9,2 8,4 8,4 8,4 8,4 9,2 weight ca. kg/km 60 60 60 60 65 60 60 60 60 65 packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. Application: Optical cable with central or stranded loose tubes, glass yarn strength members/rodent protection and water blocking elements. Due to the wear resistant PE-jacket and good mechanical properties the cable is suitable for installation in trunking in industrial environments or for direct burial. The small bending radius and diameter allow as well an indoor application of the cable, for example as riser.

LAN cables

flame retardant sheathing material bendig radius with tension load bending radius without tension load max. operating temperature, fixed temperature, moved/ during installation p/n 070178 070180 070182 070184 070190 070179 070181 070183 070185 070191 type

Conductor ropes

Technical Appendix

01X4G50 01X6G50 01X8G50 01X12G50 01X24G50 01X4G62,5 01X6G62,5 01X8G62,5 01X12G62,5 01X24G62,5

Other

> 194 <

>>> www.faberkabel.de <<<

LAN cables
Application: LSOH optical cable with central loose tube and glass yarn strength members. For fixed installation indoors and outdoors, as well as for direct burial. The cable is therefore optimally suitable for connection between buildings. standard standard fiber quality for outdoor use flame retardant sheathing material bendig radius with tension load bending radius without tension load max. operating temperature, fixed temperature, moved/ during installation p/n 070698 070699 070700 070701 type 01X12G50 01X24G50 01X12G62,5 01X24G62,5 colour bk bk bk bk DA mm 6,4 7,5 6,4 7,5 on request yes

Optical Cables - outdoor <<<


Power cables 1 up to 30 kV

U-DQ(ZN)BH
ISO/IEC 794, DIN VDE 0888

VDE 0482-332-1-2/IEC 60332-1

150 mm 140 mm -20 - +70 C -5 - +50 C weight ca. kg/km 48 62 48 62 packaging dr. dr. dr. dr.

A-DQ(ZN)B2Y ... 1,2 kN (Zentralader)


Application: Optical cable with central loose tube, glass yarn strength members/rodentprotection and water blocking elements. Due to the abrasion resistant PE-jacket and good mechanical properties the cable is suitable for installation in trunking in industrial environments or for direct burial. standard standard fiber quality for outdoor use flame retardant sheathing material bendig radius with tension load bending radius without tension load max. operating temperature, fixed temperature, moved/ during installation p/n 070682 070683 type 01X12G50 01X24G50 colour bk bk DA mm 6 7 ISO/IEC 794, DIN VDE 0888 on request yes no polyethylene 160 mm 140 mm -20 - +70 C -5 - +50 C weight packaging ca. kg/km 43 dr. 59 dr.

>>> www.faberkabel.de <<<

> 195 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

polyolefin

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity Flexible Cables Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Power cables 1 up to 30 kV

> 196 <

>>> Conductor ropes

Notes:

>>> www.faberkabel.de <<<

optimistic

>>> www.faberkabel.de <<< Copper conductor ESUY Copper conductor 198 198 198
LAN cables Cable with circuit integrity Control and Electronic Cable Telecommunication Cables and Cords Flexible Cables Building Wires

Content
Conductor ropes <<<

> 197 <

Technical Appendix

Other

Conductor ropes

Power cables 1 up to 30 kV

>>> Copper conductor


Power cables 1 up to 30 kV

ESUY
test voltage insulation conductor material conductor construction temperature, moved/ during installation p/n 033441 033442 031947 032102 032323 031915 033163 034775 034776 034777 type 01X16 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 5 kV PVC bare copper fine stranded class 6 -5 - +70 C colour TR TR TR TR TR TR TR TR TR TR CU kg/km 194 280 415 585 820 1090 1360 1650 2150 2750

Conductor ropes
Application: Earthing cable with braided fine-wire conductor core for use in portable earthing and short-circuit devices, particularly for repair work on high-voltage systems for the safety of technical personnel.

Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

DA mm 9,6 10,7 12,5 14,2 16,8 19,8 23,2 26,3 30 33

weight ca. kg/km 213 305 575 670 910 1220 1505 1945 2395 3095

packaging dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Flexible Cables

Copper conductor
standard p/n 012238 012240 012242 012235 012247 type 01x50 01x70 01x95 01x120 01x150 {VDE 0295 / IEC 60228} colour VZ VZ VZ VZ VZ Application: For earthing purposes in electrical installations. CU kg/km 480 672 912 1152 1470 DA mm 9 10,5 12,5 13,9 15,8 weight ca. kg/km 480 672 912 1152 1470 packaging dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

> 198 <

>>> www.faberkabel.de <<<

Other <<<
Power cables 1 up to 30 kV

dynamic

Content

Heat resistant cable FACAB THERM 145 FACAB THERM 400 Coaxial cable RG-cables SAT, CATV

202 202 203 204 204 205

>>> www.faberkabel.de <<<

> 199 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Speaker cable YFAZ YFAZ Ultraflat LAS-JZ

200 200 200 201

Flexible Cables

Building Wires

>>> speaker cable


Power cables 1 up to 30 kV

YFAZ
nominal voltage U test voltage conductor material conductor construction insulation flame retardant max. operating temperature, fixed temperature, moved/ during installation p/n 032903 031807 031763 031931 031757 031764 031758 031759 031765 033743 type 2X0,75/0,2 2X1,5/0,15 2X2,5/0,15 02X4/0,10 02X4/0,15 02X6/0,15 02X6/0,2 02X10/0,1 02X10/0,15 2X0,75/0,2 250 V 2000 V bare copper fine stranded class 6 PVC VDE 0482-332-1-2/IEC 60332-1 -30 - +70 C -10 - +70 C colour TR TR TR TR TR TR TR TR TR wh CU kg/km 14,4 30 50 80 80 120 120 220 200 14,4 wxh ca. mm 4,9 x 2,35 5,8 x 2,5 7,4 x 3,6 9,7 x 4,5 9,7 x 4,5 12,5 x 6,1 12,5 x 6,1 15 x 7 15 x 7 weight ca. kg/km 23 42 60 105 120 141 141 252 252 23

other
Application: This is a high-quality speaker cable for home application as well as for use in cinemas, theaters and other public buildings. The special construction of copper conductor guarantees long-life flexibility of the cable.

Flexible Cables

Building Wires

packaging dr., c. 100 dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr., c. 100, c. 50 dr., c. 100, c. 50 dr. dr. dr. dr.

Control and Electronic Cable

Telecommunication Cables and Cords

YFAZ Ultraflat
operating capacity test voltage conductor material insulation flame retardant max. operating temperature, fixed temperature, moved/ during installation 70 nF/km 2000 V Oxygen Free Copper (OFC) special PVC-compound no -30 - +70 C -10 - +70 C colour wh wh wh CU kg/km 30 50 80 wxh ca. mm 12,8 x 2,4 14,6 x 2,6 17,5 x 3 weight ca. kg/km 42 60 105 packaging dr., c. 100 dr., c. 100 dr., c. 100 Application: Universally applicable highly flexible loudspeaker cable for the use in the homes, in cinemas, in theatres and other public buildings. The special conductor construction allows installation below carpets or baseboards. The grove gives the polarity identification.

LAN cables

Cable with circuit integrity

p/n 032289 032290 032291

type 2X1,5/0,1F 2X2,5/0,1F 2X4/0,1F

Technical Appendix

Other

Conductor ropes

> 200 <

>>> www.faberkabel.de <<<

other
Application: Flexible cord for application in light and sound systems for connection of lamps or speakers. For installation in dry and wet rooms as well as outdoors. nominal voltage UO nominal voltage U test voltage core identification conductor material conductor construction maximum temperature at conductor insulation sheathing material 0,6 kV 1 kV 4 kV gn-ye + numbers bare copper fine stranded, class 5 70 C PVC PVC

speaker cable <<<


Power cables 1 up to 30 kV

LAS-JZ

bending radius, moved 7,5 x DA application bending radius, fixed installation max. operating temperature, fixed temperature, moved/ during installation p/n 032915 032916 032917 type 18X1,5 14X2,5 18X2,5 colour bk bk bk CU kg/km 259,2 336 432 DA mm 15,3 16,8 18,9 4 x DA -30 - +70 C -5 - +70 C weight ca. kg/km 456 588 749 packaging dr. dr. dr.

>>> www.faberkabel.de <<<

> 201 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Heat resistant cable


Power cables 1 up to 30 kV

FACAB THERM 145


conductor material conductor construction insulation tinned copper fine stranded, class 5 cross-linked polyolefin-copolymer cross-linked polyolefin-copolymer VDE 0482-266-2-4/ IEC 60332-3-24 4 x DA

other
Application: This electron-beam-networked halogen-free control cable is used for the connection of lights, heating units and machines, but also for sensors in environments with increased temperatures. In addition to a long working life, the high permissible conductor temperature also guarantees increased current carrying capacity in comparison to conventional cables. The outer sheath is UV- and ozone-resistant, so that the cable can also be used outdoors.

Building Wires

sheathing material flame retardant bending radius, fixed installation

Flexible Cables

bending radius, moved 8 x DA application maximum temperature at conductor max. operating temperature, fixed temperature, moved/ during installation p/n 040416 040417 040418 040419 040437 040404 040423 040405 040406 040407 040408 040409 040410 040412 040413 040692 040664 040424 040425 040426 040414 040689 040436 040449 040435 040430 040442 040443 040389 040444 040348 040422 040446 040340 040445 type 01X0,75 01X0,75 01X0,75 01X0,75 01X0,75 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X1,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X2,5 01X4 01X6 01X10 01X25 01X35 01X50 01X70 01X95 01X120 01X150 01X185 01X240 145 C -55 - +145 C -35 - +125 C colour og bk vt dbu bn bn dbu ye gn gy lbu rd vt wh bk ge/ye ge/ye bn dbu rd bk gn wh bk bk bk bk bk bk bk bk bk bk bk bk CU kg/km 7,2 7,2 7,2 7,2 7,2 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 14,4 24 24 24 24 24 24 24 38,4 58 96 240 336 480 672 912 1152 1440 1776 2304 DA mm 2,2 2,2 2,2 2,2 2,2 3 3 3 3 3 3 3 3 3 3 3 3,7 3,7 3,7 3,7 3,7 3,7 3,7 4,3 6,2 6,7 10,2 11,7 13,7 15,8 17,3 20,2 22,1 23,6 27,7 weight ca. kg/km 11 11 11 11 11 21 21 21 21 21 21 21 21 21 21 20 32 31 31 31 32 32 32 48 76 120 265 386 580 765 1040 1273 1582 2100 2526 packaging dr., c. 100 dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr., c. 100 dr. dr. dr. dr. dr. dr. dr. dr. dr. dr.

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

> 202 <

>>> www.faberkabel.de <<<

other
Application: Thanks to its extremely large usage temperature range, this cable is particularly suitable for use in aerospace applications, in power stations and in chemicals and metallurgy businesses. The conductor resistances varying from copper conductors must be observed! nominal voltage UO nominal voltage U test voltage conductor material conductor construction insulation max. operating temperature, fixed bending radius, fixed installation p/n 040398 040669 040760 040670 040671 040382 type 01X1,5 01X2,5 01X2,5 01X4 01X6 01X6 colour BE BE bk BE BE bk CU kg/km 14,4 24 24 38,4 58 57,6 DA mm 2,8 3,4 3,4 4,5 4,9 4,9 300 V 500 V 2000 V nickel

Heat resistant cable <<<


Power cables 1 up to 30 kV

FACAB THERM 400

{Glasseidengeflecht, getrnkt} -60 - +400 C 18 x DA weight ca. kg/km 20 32 32 46 65 65 packaging dr., c. 100 dr., c. 100 c. 100, dr. dr., c. 100 dr., c. 100 dr., c. 100

>>> www.faberkabel.de <<<

> 203 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

fine stranded, class 5

>>> Coaxial cable


Power cables 1 up to 30 kV

RG-cable
Application: For transmission of data and RF signal ina wide range of frequencies and distances, for connection of receiving and transmitting antennas etc.

Other

Building Wires

p/n 100476 100258 100104 100605 100095 100967 100101 100182 100848 101019 100353 100201 100529

type RG 8/U RG 11 A/U RG 58 C/U RG 58 C/U FRNC RG 59 B/U RG 59 B/U FRNC RG 62 A/U RG 71 B/U RG 142 B/U RG 174 A/U RG 179 B/U RG 213 RG 214 /U

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Z Ohm 50 75 50 50 75 75 93 93 50 50 75 50 50

CU kg/km 54,8 56 20 20 24 24 25 45 45 6 7 76 118

DA mm 9,5 10,2 5,0 5,0 6,1 6,1 6,2 6,2 4,6 2,8 2,5 10,3 10,8

weight kg/km 125 144 38 38 57 57 52 65 65 11 16,5 155 205

packaging dr. dr. dr. dr. dr., c. 100 dr. dr., c. 100 dr. dr. dr., c. 100 dr. dr. r.

Flexible Cables

> 204 <

>>> www.faberkabel.de <<<

Other
Application: For connection of satelite antennas/dishes, video and BC-TV components, but also for terrestrical antennas.

Coaxial cable <<<


Power cables 1 up to 30 kV

SAT, CATV

p/n 110251 110161 110162 110250 100477 100616 100867 100478 100492 100594 100498 100463 100735 100469 100499 100943 101012 100719 100731

type A-2YK2Y1 iKx 1,1/7,3 75 Ohm SW A-2YOK2Y1 nKx 2,2/8,8 75 Ohm SW A-2YOK2Y1 qKx 3,3/13,5 75 Ohm SW A-2YOK2Y1 sKx 4,9/19,4 75 Ohm SW FACAB SAT 0,7/2,9 Twin 75 Ohm WS FACAB SAT 1,0/4,6 DIGITAL 4-S >105 dB 75 Ohm WS FACAB SAT 1,1/5,0 DIGITAL 1GHz 75 Ohm WS FACAB SAT 1,1/5,0 DIGITAL 3 GHz 75 Ohm WS FACAB SAT 1,1/5,0 halogenfrei DIGITAL 3 GHz 75 Ohm WS FACAB SAT Multimedia 0,75/3,4 + 2X2X0,6 75 Ohm WS SAT+BK PE Erdkabel 1,6/7,3 DIGITAL 75 Ohm GN FACAB VIDEO 0,6/3,7 75 Ohm GN FACAB VIDEO flexibel 0,6L/3,7 75 Ohm GN FACAB VIDEO halogenfrei 0,6/3,7 75 Ohm GN FACAB VIDEO Innenkabel 1,0/6,6 75 Ohm DIGITAL GN FACAB VIDEO Slimline 0,6/2,8 75 Ohm GN Video Systemkabel 0,6/3,7 75 Ohm + 2X0,5 qmm SW Video Systemkabel 0,6/3,7 75 Ohm + 2X0,75 qmm SW Video Systemkabel halogenfrei 0,6/3,7 75 Ohm + 2X0,75 qmm GR

>>> www.faberkabel.de <<<

> 205 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

CU kg/km 69 115 208 375 26 25 21 25 25 23,5 50,5 24 24 24 73 17 36 38 38

G kg/km 142 183 347 500 58 48 51 55 55 70 105 45 45 45 140 32 96 98.5 98.5

DA mm 11,0 12,5 17,0 24,4 4,5x9,0 6,0 6,8 6,8 6,8 11,5 x 5,5 10,3 6,2 6,2 6,2 9,8 4,5 10,1 x 6,1 11,8 x 6,1 11,8 x 6,1

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity Flexible Cables Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Power cables 1 up to 30 kV

> 206 <

>>> Technical Appendix


Notes:

>>> www.faberkabel.de <<<

Technical Appendix <<<


Power cables 1 up to 30 kV

Clever

Index

Type Designation Code for cables Core identification according to VDE 0815 Core identification according to VDE 0816 Colour code Colour coding of cores Identification of cores acc. to VDE 0293 Sizes of cable drums Legend of icons Abbreviations for colours Index Delivery and payment terms

208 209 211 212 213 214 215 216 217 218 220
Cable with circuit integrity Technical Appendix Other Conductor ropes LAN cables Telecommunication Cables and Cords Control and Electronic Cable

>>> www.faberkabel.de <<<

> 207 <

Flexible Cables

Building Wires

>>> Type Designation Code for cables


Power cables 1 up to 30 kV

Technical Appendix
Telecommunication cables acc. to VDE 0815/16 - XX
12 345 6 7 8 9 10 1. Relationship to Standards A outdoor cable G mining cable J installation cable L equipment wire S switch cable Li equipment wire with fine stranded conductor RD rhenomatic-cable RE instrumentation cable 2. Additional specifications B lightning protection J Indukction protection E Industry-electronics 3. Insulating materials Y PVC 2Y PE 02Y cell-PE 02YS foam-Skin 5Y PTFE (teflon) 6Y FEP (teflon) 7Y ETFE (teflon) P paper 4. Special construction F petrol jelly filler L aluminium sheath LD corrugated Al.-sheath (L) laminated aluminium sheath C copper braided screen (St) screen of plastic coated Al-foil (K) copper tape screen (B) amouring (Z) steel wire amouring (Zg) strain-bearing element with glass yarn bundles (ZN) strain-bearing element non metalic W corrugated steel sheath M lead sheath Mz special lead sheath b amouring c jute jacket+ bituminous compund compund with embedded tape E 5. Sheathing materials see 3.insulation materials 6. Number of elements number of stranding elements 7. Stranding elements 1 single core 2 pair 4 quat 8. Conductor diameter 9. Typ of stranding F star quad (railway) St star quad with phantom circiut (long distance) St I star quad (long distance) St III star quad (subscriber line) TF star quad for carrier frequenycy PiMF pair in metal foil DIMF triple in metal foil ViMF quad in metal foil 10. Stranding layout Lg stranding in layer Bd stranding in unit

Power cables acc. to VDE 0250 X


123456 7 8 1. Relationship to Standards N according to VDE (N)/X with reference to VDE 2. Insulating materials Y PVC 4Y polyamide 5Y PTFE (teflon) 6Y FEP (teflon) 9Y polypropylen 11Y polyurethan (PUR) 2X XLPE G elastomer 2G silicon 3G EPR-rubber 4G EVA 5G polychloroprene HX LSOH 3. Cable description A single-core D solid wire AF single-core, fine stranded F flexible wire for fittings L fluorescent tube cable LH connecting cable for light mechanical load MH connecting cable for middle mechanical load SH connecting cable for, heavy mechanical load SSH connecting cable for special mechanical load SL control/welding cable S control cable LS light control cable FL flat cable Si silicon cable Z twin cable GL glass fibre Li stranded wires acc to. VDE 812 LiF fine stranded wires acc. to VDE 812 4. Special constructions T strength member oil-resistant u flame resistant w heat-/weather resistant FE fire resistant C screen S steel wire armouring 5. Sheathing materials l see 2.insulation materials P Polyurethan 6. Protective conductor -J with green/yellow core -O without green/yellow core 7. Number of cores

Harmonized cables acc. to VDE 0281/0282


1234 - 56789 1. Relationship to Standards H Harmonized type (HAR) A authorised national standards 2. Nominal voltage 01 100 V 03 300/300 V 05 300/500 V 07 450/750 V 11 600/1000 V 3. Insulating materials V PVC V2 PVC (90 oC) V3 PVC cold-resistant B EPR-rubber (90 C) G EVA E PE R natural or synthetic rubber S silicon rubber X XLPE Z LSOH -compound 4. Sheathing materials V PVC V2 PVC (90 oC) V3 PVC cold-resistant V4 PVC cross-linked V5 PVC oil-resistant R natural or synthetic rubber N chloroprene rubber N2 chloroprene rubber for welding cables N4 chloroprene rubber heatresistant N8 chloroprene rubber (water-resistant) J glass fibre braid T textil braid T6 textil over each core Q polyurethan (PUR) Q4 polyamide Z LSOH -compound 5. Special constructions C concentric copper conductor C4 copper braided screen H flat , divisible cords H2 flat , non divisible cords H6 flat , non divisible cords for elevators H7 two-layer insulating jacket H8 helical cord 6. Conductor form U round, solid R round, stranded K fine stranded, (fixed installation) F fine stranded (flexibel cords) H fine stranded (highly fexible) Y tensil conductor D fine stranded for welding cables E fine stranded for welding cables (highly fexible) 7. Number of cores 8. Protective conductor X without green/yellow core G with green/yellow core 9. Cross-section of conductor

Power cables acc. to VDE 0276 X


1 2 3 4 5 6 7 8 9 10 11 12 1. Relationship to Standards N according to VDE (N) with reference to VDE 2. Conductor copper A aluminium 3. Insulating materials Y PVC 2Y PE 2X XLPE H LSOH compound 4. Concentric conductor C Concentric copper conductor CW Concentric copper conductor reversing lay up 5. Screen S common copper shield SE individually screened cores 6. Metal sheath K lead 7. Inner protection or plastic sheath see 3.insulation materials 8. Armouring F flat steel wire R round steel wire G steel tape 9. Outer sheath see 3.insulation materials 10. Protective conductor -J with green/yellow core -O without green/yellow core 11. Number of cores 12. Conductor form RE round, solid RM round, stranded SE sector shaped, solid SM sector shaped, stranded

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

Technical Appendix

8. Cross-section of conductor

> 208 <

>>> www.faberkabel.de <<<

Technical Appendix
1. Colour coding for installation cabels J-Y(St)Y ... Lg
For two-pair cable pair 1: a-red, b-black pair 2: a-white, b-yellow For cables with more than 2 pairs

Core identification <<<


Power cables 1 up to 30 kV

according to VDE 0815

> The colour of the a-core in the first pair of each layer is red ("counting" pair), in all other pairs it is white. > The colour of the b-core is blue, yellow, green, brown, black in repeating order as follows: colour of b-core blue yellow green brown black blue yellow green brown black Nr. of pair 1 2 3 4 5 51 52 53 54 55 6 7 8 9 10 56 57 58 59 60 11 12 13 14 15 61 62 63 64 65 16 17 18 19 20 66 67 68 69 70 21 22 23 24 25 71 72 73 74 75 26 27 28 29 30 76 77 78 79 80 31 32 33 34 35 81 82 83 84 85 36 37 38 39 40 86 87 88 89 90 41 42 43 44 45 91 92 93 94 95 46 47 48 49 50 96 97 98 99 100

2. Colour coding for installation cabels JE-Y(St)Y ... Bd JE-LiYCY ... Bd JE-H(St)H ... Bd JE-LIHCH ... Bd RD-Y(St)Y AJ-Y(St)YDY Bd Si
For two-pair cable pair 1: a-blue, b-red pair 2: a-grey, b-yellow For cables with more than 2 pairs Colour of basic insulation of pairs in one bunch: Paar core colour a blue 1 b red a grey 2 b yellow a green 3 b brown a white 4 b black

For identification of bunches, cores are marked with black rings and bunches are wrapped by a colored tape. > ring group I > ring group II > ring group III > ring group IV
>>> www.faberkabel.de <<< > 209 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Core identification


Power cables 1 up to 30 kV

according to VDE 0815


Identification of bunches
Bunch-N Colour of rings rings for bunches of 4 cores 8 cores resp. 4 pairs I I I II II III II IV I II III IV I II III IV I II III IV I II III IV

Technical Appendix

tape

Building Wires

Control and Electronic Cable

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

pink

orange

Telecommunication Cables and Cords

violet

pink

blue

Flexible Cables

orange

red

Cable with circuit integrity

3. Colour coding for installation cables J-YY ... Bd J-H(St)H ... Bd J-2Y(St)Y St III Bd
The five star-quads of each bunch have the following identification:

LAN cables

Conductor ropes

1. basic insulation of all cores rot 2. basic insulation of all cores green 3. basic insulation of all cores grey 4. basic insulation of all cores yellow 5. basic insulation of all cores white The cores within one star-quad are marked by rings: > a-core > b-core

} }

side circuit 1

Other

> a-core > b-core

side circuit 2

Technical Appendix

The counting bunch is marked by a red tape in each layer. All other bunches have a white or nature tape.

> 210 <

>>> www.faberkabel.de <<<

Technical Appendix
4. Core identification for outdoor telephone cables
The five star-quads of each basic unit have the following identification: Quad 1. basic insulation of all cores red Quad 2. basic insulation of all cores green Quad 3. basic insulation of all cores grey Quad 4. basic insulation of all cores yellow Quad 5. basic insulation of all cores white The basic insulation of spare quads is red. The cores within one star-quad are marked by rings: > a-core > b-core > a-core > b-core

Core identification <<<


Power cables 1 up to 30 kV

according to VDE 0816

side circuit 1

side circuit 2

The first basic- or main-unit in each layer is to be marked by an open helix of plastic tape of red (marker). All other basic- or main-units must be wrapped with an open helix of white or uncoloured plastic tape. The quads of a basic-unit are to be counted according to the sequence of basic colours. In cables with more than 5 star quads, the basic- and main-units must be counted continuously beginning with maker-unit at inner layer towards outside.

Examples for unit stranding:

1 basic-unit 1 star quad

> 5 star quads stranded into basic unit

>>> www.faberkabel.de <<<

> 211 <

Technical Appendix

> 5 basic units each stranded into one main unit = 50 DA

Other

1 star quad

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Colour code


Power cables 1 up to 30 kV

FACAB dataline LWL colour code

Technical Appendix

The following colors are used for identification of fibers in loose tubes of standard optical cables (with reference to VDE 0888-3, IEC 60304): Fiber-N. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 colour red green yellow blue white violet orange black grey brown pink turquoise red/black green/black yellow/black blue/black white/black violet/black orange/black natur/black grey/black brown/black pink/black turquoise/black red/black/black green/black/black yellow/black/black blue/black/black white/black/black violet/black/black orange/black/black natur/black/black grey/black/black brown/black/black pink/black/black turquoise/black/black

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

The first colour is the basic colour of the fiber, second and third colours are applied as rings on the fiber.

For optical cables with stranded units the following colours are used: > 1. unit: red (counting unit) > 2. unit: green (direction unit) > all other units have natural colour > blinds are black

Technical Appendix

Other

> 212 <

>>> www.faberkabel.de <<<

Technical Appendix

Colour coding of cores

<<<
Power cables 1 up to 30 kV

according to DIN 47 100 & abbreviations acc. to IEC 60757

> Table 1: Core identification acc. to DIN 47 100 Colour stranded cores twisted pairs core N core Paar-Nr. white 1 a 1 b brown 2 green 3 a 2 b yellow 4 grey 5 a 3 b pink 6 blue 7 a 4 b red 8 black 9 a 5 b violet 10 grey pink 11 a 6 b red blue 12 white green 13 a 7 b brown green 14 white yellow 15 a 8 b yellow brown 16 white grey 17 a 9 b grey brown 18 white pink 19 a 10 b pink brown 20 white blue 21 a 11 b brown blue 22 white red 23 a 12 b brown red 24 white black 25 a 13 b brown black 26 grey green 27 a 14 b yellow grey 28 pink green 29 a 15 b yellow pink 30 > Table 2 Abbreviations of colors according to IEC 60757 colour German schwarz braun rot orange gelb grn blau violett grau wei rosa gold trkis silber grn-gelb German abbreviation SW BR RT OR GE GN BL VI GR WS RS TK GG

Colour green blue yellow blue green red yellow red green black yellow black grey blue pink blue grey red pink red grey black pink black blue black red black white brown black yellow green black grey pink black red blue black white green black brown green black white yellow black yellow brown black white grey black grey brown black white pink black pink brown black white blue black brown blue black white red black brown red black black white Colour black brown red orange yellow green blue violet grey white pink gold turquoise silver green-yellow

stranded cores twisted pairs core N core Paar-Nr. 31 a 16 b 32 33 a 17 b 34 35 a 18 b 36 37 a 19 b 38 39 a 20 b 40 41 a 21 b 42 43 a 22 b 44 45 a 23 b 46 47 a 24 b 48 49 a 25 b 50 51 a 26 b 52 53 a 27 b 54 55 a 28 b 56 57 a 29 b 58 59 a 30 b 60 61 English abbreviation BK BN RD OG YE GN BU VT GY WH PK GD TQ SR GNYE

>>> www.faberkabel.de <<<

> 213 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

The colour code according to table 1 without repeating colors from core 46 resp. pair 23 is used for electronic cables LiYY, LiYCY and similar types. Counting of cores starts in the outer layer of the strand and is continued through all layers in the same direction. The first colour in the table is the colour of insulation, the second and third ones are printed rings. Table 2 contains German and English abbreviations for colors acc. to IEC 60757. The table does not correspond to any order of colors/cores in a cable!

>>> Identification of cores


Power cables 1 up to 30 kV

Identification of cores acc. to VDE 0293


1. Cables/cords with gn-ye protective conductor
old DIN VDE 0293 fixed gn-ye, bk, bu flexible gn-ye, bn, bu 3 gn-ye, bk, bu, bn with gn-ye 4 gn-ye, bk, bu, bn, bk (-J) or ... G ...

Technical Appendix

Building Wires

Version

No. of cores

new DIN VDE 0293-308:2003 fixed and flexible gn-ye, bu, bn

Flexible Cables

gn-ye, bn, bk, gy

gn-ye, bu, bn, bk, gy 5

Telecommunication Cables and Cords

bu= blue, bn = brown, gn-ye = green-yellow, gy = grey, bk = black

Control and Electronic Cable

2. Cables/cords without gn-ye protective conductor


old DIN VDE 0293 fixed bk, bu flexible bn, bu 2 bk, bu, bn bn, bk, gy 3 bu, bn, bk, gy 3 1/2 bk, bu, bn, bk (-O) or ... X .. . bu, bn, bk, gy 4 bu, bn, bk, gy, bk 5 new DIN VDE 0293-308:2003 fixed and flexible bu, bn

Version

No. of cores

Cable with circuit integrity

without gn-ye

bk, bu, bn, bk


LAN cables Conductor ropes

bk, bu, bn, bk, bk

bu= blue, bn = brown, gy = grey, bk = black

Technical Appendix

Other

gn-ge, sw, bl, br, sw

gn-ge, bl, br, sw, gr

> 214 <

>>> www.faberkabel.de <<<

Technical Appendix

Cable drums

<<<
Power cables 1 up to 30 kV

Sizes of cable drums

In addition to the below-listed drums (according to DIN 46 391) we may also use drums made to various manufacturer standards, with dimensions in between the listed values. In such case our calculation of the deposit value will be based on the next DIN size up.

Plastic drums
nominal size 040 050 055 070 080 090 100 flange diameter (mm) 400 500 500 710 800 900 1000 barrel diameter (mm) 125 150 160 355 400 450 500 overall width (mm) 424 456 450 510 510 680 704 drum weight ca. kg 4 4 7 15 16 23 32

Wooden standard drums


nominal size 05 07 08 09 10 12 14 16 18 20 22 24 25 26 28 flange diameter (mm) 500 710 800 900 1.000 1.250 1.400 1.600 1.800 2.000 2.240 2.400 2.500 2.600 2.800 barrel diameter (mm) 150 355 400 450 500 630 710 800 1.000 1.250 1.400 1.400 1.600 1.600 1.800 overall width (mm) 470 520 520 690 710 890 890 1.100 1.100 1.350 1.450 1.450 1.450 1.450 1.635 drum weight ca. kg 8 25 31 47 71 144 175 280 380 550 710 920 900 1.000 1.175

nominal size 07 08 09 10 12 14 16 18 20 20 22 22 25 25 28

>>> www.faberkabel.de <<<

> 215 <

Technical Appendix

flange diameter (mm) 710 800 900 1.000 1.250 1.400 1.600 1.800 2.000 2.000 2.240 2.240 2.500 2.500 2.800

barrel diameter (mm) 355 400 450 500 630 710 800 1.000 1.000 1.250 1.120 1.400 1.400 1.250 1.800

overall width (mm) 520 520 690 710 890 890 1.100 1.100 1.350 1.350 1.350 1.450 1.450 1.350 1.635

drum weight ca. kg 28 35 51 78 165 199 309 413 600 588 750 753 923 925 1.280

Other

Conductor ropes

Wooden drums with armoured flanges

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Legend
Power cables 1 up to 30 kV

Legend of icons used in catalogue

Technical Appendix

cable conform to Low Voltage directive


Building Wires

not for application in power circuits

cable with circuit integrity 30 min

cable to a large extent oil resistant

Flexible Cables

cable with circuit integrity 90 min

cable with low smoke

Telecommunication Cables and Cords

screened cable

cable suitable for drag-chains

cable for direct burial

max. permitted temperature at conductor 70 C

Control and Electronic Cable

cable with function maintainance 180 min

cable for reeling application

Cable with circuit integrity

flame retardant acc. IEC 60332-3

min. installation temperature

flame retardant acc. IEC 60332-1

installation in free air only with UV-protection (cable not UV-resistant)

LAN cables

cable with GOST certification

installation in free air without protection (cable UV-resistant)

Conductor ropes

cable halogen-free

cable with VDE-certification

harmonised cable/wire
Other

cable with VdS-approval

cable metal-free (optical)

cable for use in water

Technical Appendix

cable with rodent protection

> 216 <

>>> www.faberkabel.de <<<

Technical Appendix
B1 BE BL BR BT BW DB DG DH DW GE GG GN GR HB KG MG NT dark blue - white beige blue brown brown-transparent blue-white dark blue dark green dark blue (high-grade) dark blue - white yellow green-yellow green grey light blue pine-green pink natural

Legend

<<<
Power cables 1 up to 30 kV

Abbreviations for colours used in FABER catalogue


OB OF OH OR PT PW R1 RS RT SG SH SW TB TR VI VL WO WS ocean-blue without colour orange (high grade) orange petrol white red-white pink red grey black (high grade) black turquoise clear transparent violet violet white-orange white

>>> www.faberkabel.de <<<

> 217 <

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Index
Power cables 1 up to 30 kV

Technical Appendix
20 22 58 25 56 19 161 98 152 Copper conductor CY-JB CY-JZ 600 CY-JZ CY-OZ 600 CY-OZ E Electronic cable ESUY F 114 114 110 111 112 113 115 155 154 194 195 194 115 116 FACAB dataline 1000 outdoor FACAB dataline 1000 FACAB dataline 100 FACAB dataline 200 FACAB SOLAR 125 FACAB SOLAR PV1-F FACAB SOLAR VE FACAB THERM 145 FACAB THERM 400 F-CY-JZ F-CY-OZ Fire resistant communication cable Fire resistant power cable Fire signalisation cable FZLSi 184 174 G GGSG H 189 191 190 139 141 204 128 198 H01N2-D H03VV-F H03VVH2-F H05BQ-F H05RNH2-F H05RR-F H05SJ-K H05SS-F 72 65 67 99 78 68 94 97 89 191 191 189 190 81 82 83 202 203 145 146 184 178 106 98 163 198 198 136 149 134 150 135

(N)2XY-J (N)2XY-O

Building Wires

(N)HXMH(St)-J (N)Y(Zg)2Y (N)YM(St)-J (N)YYk-J

Flexible Cables

05VV2SV 2GTL 13,8/15,0 kV 2YSL(St)CYv A A-02YSOF(L)2Y 0,6 mm A-02YSOF(L)2Y 0,8 mm A-2Y(L)2Y nx2x0,6 A-2Y(L)2Y nx2x0,8 A-2YF(L)2Y nx2x0,6 A-2YF(L)2Y nx2x0,8 A-2YF(L)2YB2Y St III Bd AD 100 F-CP AD 100 P A-DQ(ZN)2Y A-DQ(ZN)B2Y ... 1,2 kN A-DQ(ZN)B2Y AJ-Y(St)YDY Bd A-Y(St)Y B

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Brandmeldekabel Bus cables C Cables up to 100 MHz Cables up to 1000 MHz

Other

Cables up to 200 MHz CH-JZ

Technical Appendix

CH-OZ Coaxial cable Control cable Copper conductor

> 218 <

>>> www.faberkabel.de <<<

Technical Appendix
H05V2V2D3-F (NYPLYw) H05V-K H05V-U H05VV5-F H05VVC4V5-K H05VV-F H05Z-K H07BN4-F H07BQ-F H07RN-F H07V-K H07V-R H07V-U H07VVH6-F H07Z-K H07ZZ-F Heat resistant cable H-JZ H-OZ I I-D(ZN)H - High Grade I-D(ZN)H - Standard Immersion pump cable (-J) Indoor telecommunication cable Industrial electronic cable Industrial Ethernet Instrumentation cable Insulated wires I-V(ZN)H - High Grade I-V(ZN)H - Standard I-Y(St)Y .. Lg I-YY J J-2Y(St)H St III Bd J-2Y(St)Y St III Bd JE-H(St)H E30-E90 BMK 109 106 185 193 193 77 104 123 188 117 126 192 192 105 104 101 60 61 141 143 66 85 71 99 69 61 64 63 153 86 71 202 137 139 JE-H(St)H E30-E90 JE-H(St)H FE180/E30 JE-H(St)H FE180/E30 JE-H(St)HRH FE180/E90 JE-LiHCH JE-LiYCY JE-Y(St)Y ... FR JE-Y(St)Y J-H(St)H BMK J-H(ST)H L LAS-JZ Li12YC11Y Li2GYw (SiHYw PV/P) Li2YCY PiMF Li2YCYv LiHCH Livz6YYw LiYCY/EB LiYCY LIYY/EB LiYY Low voltage cable L-STN M Medium voltage cable N N2XCH N2XH-J N2XH-O N2XS(F)2Y 12/20 kV N2XS(F)2Y 18/30 kV N2XS(F)2Y 6/10 kV N2XS(FL)2Y 12/20 kV N2XS(FL)2Y 6/10 kV N2XS2Y 12/20 kV

Index

<<<
Power cables 1 up to 30 kV

185

184 186 125 124 124 123 108 107

201 171 102 170 170 172 101 169 165 165 163 10 80

31

29 26 27 41 42

43 43 38
> 219 <

>>> www.faberkabel.de <<<

Technical Appendix

40

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Index
Power cables 1 up to 30 kV

Technical Appendix
39 37 51 32 33 31 48 49 47 50 51 50 45 46 44 35 36 34 17 18 188 52 79 78 180 182 178 181 56 57 87 75 88 73 74 16 NYCY NYFGY 3,6/6 kV NYIF-J NYL NYM-J NYM-O NYRY-J NYY-J NYY-JZ NYY-O NYY-OZ O Optical cables - indoor Optical Cables - outdoor Overhead line P PUR-insulated cords PVC-insulated wires and cords R RD-Y(St)Y RE-2X(St)Y FR RE-2X(St)Yv FR PiMF RE-2X(St)Yv FR RE-2Y(St)Yv 0,5 qmm RE-2Y(St)Yv 0,75 qmm RE-2Y(St)Yv 1,3 qmm RG-cables Roller blind cable Rubber Insulated Cables Rubber insulated wires S SAT, CATV Sheathed Building Wire SiD SiF/GL SiF 205 54 90 93 90 117 118 119 118 120 121 122 204 68 68 85 99 60 192 194 52 15 24 58 102 54 55 24 10 13 11 14

N2XS2Y 18/30 kV N2XS2Y 6/10 kV

Building Wires

N2XSEY 6/10 kV N2XSY 12/20 kV N2XSY 18/30 kV N2XSY 6/10 kV

Flexible Cables

NA2XS(F)2Y 12/20 kV NA2XS(F)2Y 18/30 kV NA2XS(F)2Y 6/10 kV NA2XS(FL)2Y 12/20 kV NA2XS(FL)2Y 18/30 kV NA2XS(FL)2Y 6/10 kV NA2XS2Y 12/20 kV NA2XS2Y 18/30 kV NA2XS2Y 6/10 kV NA2XSY 12/20 kV NA2XSY 18/30 kV NA2XSY 6/10 kV NAYY-J NAYY-O Network-cable NFA2X NGFLCGOU NGFLGOEU NHXCH E30

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

NHXCH E90 NHXH-J/-O E30 NHXH-J/-O E90 NHXMH-J NHXMH-O

Other

NSGAFu NSHTu

Technical Appendix

NSHXAF NSSHu-J NSSHu-O NYCWY

> 220 <

>>> www.faberkabel.de <<<

Technical Appendix
SiHF/GLS-P SiHFCSi-J SiHFCSi-O SiHF-J SiHF-O Silicone insulated wires and cords SL AD 300 CP SL AD 300 CY SL AD 300 P SL AD 300 Y SL AD 400 CP Speaker cable Special Versions Subersible pump cable (-O) Subscriber line cable SY-JZ T Trailing cables/British Standard U U-DQ(ZN)BH X X03VH-H X07BQ-F Y YFAZ Ultraflat YFAZ Y-JB Y-JZ 600 Y-JZ Y-OB Y-OZ 600 Y-OZ YR YSLTOE-J (Korbflex) 200 200 130 147 128 133 148 132 67 100 195 84 96 94 95 92 93 90 159 157 158 156 160 200 101 77 110 150

Index

<<<
Power cables 1 up to 30 kV

76

>>> www.faberkabel.de <<<

> 221 <

Technical Appendix

126

Other

Conductor ropes

LAN cables

Cable with circuit integrity

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

>>> Delivery and payment terms


Power cables 1 up to 30 kV

Technical Appendix
5.3. A sale in the normal course of business is not considered to have been made if the purchaser assigns the retained goods to a third party, transfers them as security and/or makes them the object of factoring and/or sale-and-lease-back transactions. The same applies in the event that the purchaser delivers the retained goods to a customer whose terms of business exclude the relinquishment of the claims due to the purchaser. In cases such as the above, the purchaser is at all times obliged to obtain our written consent before conducting such business. In the event of the further reworking and/or processing of the retained goods, this is carried out at our request and on our behalf as the manufacturer in the sense of 950 ff. BGB (German civil code). In this event, we retain ownership of the items created by the reworking and/or processing of the retained goods in the same ratio of the value of the retained goods to the new items created at the time of reworking and/or processing. If other goods not belonging to the purchaser are also processed at the same time, we are entitled to joint ownership of the new items created in the same ratio of the invoice value of the individually processed goods to the total finished value. If the purchaser then resells the new items manufactured by him, the claims arising to the purchaser are also hereby relinquished in our favour, for the purposes of security, up to the value of the retained goods. If the retained goods are damaged, destroyed, or if claims accrue to the purchaser on the grounds of reduction in value of the retained goods against third parties, and especially against insurance companies, these claims are also relinquished in our favour, in accordance with the above and the following stipulations, as security for our claims. We must be notified immediately and in writing if such claims arise. If the value of the securities given to us - the value being calculated on the basis of the relevant resale value, less value-added tax and any prior claims by third parties - consistently exceeds our outstanding claims by more than 50%, we are obliged, at the request of the purchaser, to release any securities no longer required at our own discretion. If a cheque/foreign exchange transaction is carried out, payment of the claims due to us is only considered to have been made on the definitive and unreserved fulfilment of all obligations arising in connection with the above payment method, and in the case of a cheque/foreign exchange transaction only after full processing and conversion of the foreign exchange provided. Payment terms: Our invoices are payable 30 days after invoice date, without deduction. The purchaser may only deduct settlement discount if we have agreed this with him in advance and in writing. A further requirement for claiming settlement discount is that the purchaser is not in arrears with any of his other payment obligations, and that the invoice amount due to us is either transferred within the agreed period or we receive relevant notification of payment within the agreed period. In the event of failure to observe the above payment terms, we are entitled to charge interest at a rate of 8% above the basic interest rate. This does not affect our right to claim further damages, particularly in the event of demonstrably higher interest rates. Irrespective of any other payment agreements, all our outstanding claims become due for immediate payment if circumstances occur in the person of the purchaser which give grounds to assume that the payment agreements made cannot be observed (for example insolvency, application for bankruptcy proceedings etc.). In this event, we are also entitled to make delivery of further goods subject to the provision of the appropriate securities and/or advance payment.

Delivery and payment terms


1. 1.1. General: The following terms - subject to the stipulations of Point 16 - refer exclusively to business transactions with contractors. Our terms apply for all contracts, deliveries and other services that we provide to the purchaser. General terms and conditions of the purchaser which vary from our terms are hereby rejected; such terms and conditions do not obligate us even if we do not again expressly reject them. We are only bound by such terms and conditions if we declare ourselves in agreement with their application in writing. Subsidiary agreements, reservations, additions etc. require our written confirmation in order to be valid. This also applies to such agreements by which the agreed written form requirement is to be lifted. Quotations, contracts: Unless specified otherwise, our quotations are made without commitment. Prices: All prices stated by us are subject to value-added tax at the applicable prevailing rate. Unless agreed otherwise, prices will be based on the price list issued by us, and which is in effect at the time of the conclusion of the contract. Prices include freight charges within the Federal Republic of Germany (mainland), although without unloading and to the loading bay or door of the purchaser. For orders below 1,200.-- total invoice value (without VAT and before metal surcharge), delivery is chargeable. The same applies in the event that, on the instructions of the purchaser, part-deliveries are made to different addresses provided by the purchaser, and these part-deliveries or parts thereof do not exceed the amount of 1,200.--. Metal rates and calculation: Raw material rates will be calculated on the basis of the rates published by the NE metalworkers. Unless agreed otherwise, the rates published in the daily press on the date of receipt of the order will apply for electrolyte copper for conduction purposes (DEL notice) plus purchasing costs incurred, aluminium for conduction purposes and lead in cables to DIN 17640. List prices will be adjusted by the product of the NE metal price difference (EURO/kg). The NE metal price difference is obtained from the difference between the basic metal price and the DEL rate including purchasing costs. Retention of ownership We retain ownership of the goods supplied by us - hereafter referred to as the retained goods - until full settlement of all claims arising from the business relationship with the purchaser. The retention of ownership also remains in effect if individual claims are included in a current invoice. The purchaser is entitled to resell the retained goods in the normal course of business. For the purposes of security, the purchaser hereby relinquishes in our favour his claims arising from the sale against his customer, up to the value of the retained goods. As long as the purchaser fulfils his obligations toward us, he remains authorised to collect such claims, even though they have been relinquished in our favour. In the case of justifiable grounds however, and especially if the purchaser culpably fails to fulfil his contractual obligations toward us, we are entitled to cancel the above authorisation and disclose the relinquishment that has been made in our favour. In such a case, the purchaser is obliged to provide us immediately will all information and documentation necessary to make such disclosure.

Building Wires

1.2. 1.3.

Flexible Cables

5.4.

1.4.

Telecommunication Cables and Cords

2. 2.1.

3. 3.1. 3.2.

Control and Electronic Cable

5.5.

3.3.

3.4.

Cable with circuit integrity

5.6.

4. 4.1.

5.7.

LAN cables

4.2.

Conductor ropes

6. 6.1. 6.2.

5. 5.1.

5.2.

Other

6.3.

6.4.

Technical Appendix

> 222 <

>>> www.faberkabel.de <<<

Technical Appendix
6.5. The claiming of any rights of retention and/or reconciliation of claims against us is excluded, unless such claims are undisputed and/or have been established in law. Delivery reservations: All delivery commitments on our part, unless specifically agreed otherwise in writing, are subject to correct and timely delivery of goods to us. If delivery cannot be made for reasons which are the responsibility of our suppliers, both we and the purchaser may withdraw from the contract, if the agreed delivery date has been, or in all probability will be, exceeded by three months. We reserve the right at all times to make part-deliveries. In this case, no additional costs will be charged to the purchaser. We also reserve the right to make the normal, accepted over- or under-deliveries of up to 10% of the quantity ordered. Delivery schedules Goods will only be supplied to fixed delivery schedules if these have been confirmed in advance in writing. If we fail to meet agreed delivery schedules and/or times, the purchaser is first obliged to grant us, in writing, an appropriate supplementary period to make delivery. This supplementary period should be not less than 4 weeks. If we also fail to meet this delivery period, the purchaser is entitled to with draw from the contract. In the event of force majeure and/or unforeseeable and extraordinary circumstances and/or other events beyond our control, even if they occur to our suppliers, any delivery date agreed by us is extended until the problems mentioned above are rectified. If this time cannot be forecast, and especially if such problems are expected to last for more than 3 months, both we and the purchaser are entitled to withdraw from the contract. In this case, claims for compensation for damages by either party are excluded. We undertake to notify the purchaser immediately if we become aware of any of the above circumstances. If the observation of a particular delivery date is subject to our being provided with certain information and/or plans, approval declarations etc. by the purchaser, the agreed delivery time begins only from the time when the complete written information from the purchaser has been made available to us. If delivery is postponed at the request of the purchaser beyond the contractually agreed delivery date, we are entitled, beginning 10 working days at the earliest from notification that the goods are ready for delivery, to charge the purchaser storage costs of 0.5% of the invoice amount for every month or part of a month, up to a maximum of 5% of the total invoice amount. Return deliveries that have not been confirmed in advance by us, are made at the sole risk of the purchaser. Call-off orders: If the purchaser places a call-off order with us, and if no separate written agreements are made with respect to the call-off dates, the purchaser is obliged to notify us of the call-off dates in such a way that we have at least 14 working days between receipt of the calloff notification and delivery, and the last delivery is made 90 days after our order confirmation. Size and weight information: All information on diameter, weight, technical design, manufacture and extent of the goods to be delivered by us are subject to the reservation of variance within the normal, permitted tolerances. We also reserve the right to make technical changes at any time in the interests of technical improvement. Colour variations and/ or variances in the outer properties of goods delivered by us, which do not however impair the quality or technical features, do not constitute grounds for guarantee claims by the purchaser.

Delivery and payment terms

<<<
Power cables 1 up to 30 kV

7.2.

7.3. 7.4.

8. 8.1. 8.2.

8.3.

8.5.

8.6.

10.

11. Transfer of risk: 11.1. Place of fulfilment for our delivery obligations is the delivery warehouse from which the goods are dispatched to the purchaser,

>>> www.faberkabel.de <<<

> 223 <

Technical Appendix

14. Cable drums: 14.1. If cable drums are delivered which were supplied by Kabeltrommel GmbH & Co. KG based in Cologne (hereinafter referred to as "KTG"), the delivery of these cable drums supplied by KTG (hereinafter referred to as KTG drums) is at all times subject to KTG's "Terms and Conditions of the Provision of Cable Drums". KTG drums are recognisable by the KTG emblem affixed to them. Moreover, the delivery of KTG drums is indicated in the order confirmation

Other

Conductor ropes

9.

13. Compensation for damages/liability: 13.1. Liability for damages on our part, on whatever legal grounds, is excluded in cases of only simple negligence. This restriction does not apply if the damage occurs in or as a result of the fulfilment of any of our principal contractual obligations. 13.2. The amount of compensation for damages is restricted to instances of damage typical in such contracts and which might reasonably have been foreseen by us. Liability for atypical and/or unforeseeable damages, on whatever legal grounds, is excluded. Our liability, on whatever legal grounds, is further restricted to 30% of the goods value invoiced, provided that the damage was caused by an occurrence which can typically result from business of the type in question. 13.3. The stipulations of Points 13.1 and 13.2 do not apply to claims under 1.4 of product liability laws. The same applies for initial inability or culpable impossibility.

LAN cables

Cable with circuit integrity

8.4.

12. Guarantee: 12.1. Guarantee claims by the purchaser first require that the goods delivered are checked immediately to ensure they are in order, that any obvious faults are notified to us immediately in writing, and that any concealed faults are notified to us as soon as they are detected. 12.2. If the fault is our responsibility, we are entitled, at our own discretion, to either rectify the fault or provide a replacement delivery. 12.3. If we are not prepared or not in a position to rectify the fault or provide a replacement delivery, or if such rectification is delayed beyond a reasonable time for reasons which are our responsibility, or if rectification/replacement proves unsuccessful for any reason, the purchaser is entitled, at his discretion, either to withdraw from the contract or require an appropriate reduction in the purchase price. 12.4. Unless specified otherwise below, any further claims by the purchaser, on whatever legal grounds, are excluded. We are consequently not liable for damages not sustained to the actual goods delivered; we are in particular not liable for loss of profits or other financial damages sustained by the purchaser. 12.5. The above limitation of liability does not apply if the damage is caused by deliberate or gross negligence. Nor does it apply if the purchaser claims compensation for damages due to non-fulfilment because of the lack of an assured property. If we infringe our contractual obligations due to negligence, our liability for material and personal damages is limited to the coverage amount of our product liability insurance. The purchaser may inspect this insurance policy at his request. 12.6. The guarantee period is in accordance with legal requirements.

Control and Electronic Cable

Telecommunication Cables and Cords

Flexible Cables

Building Wires

7. 7.1.

and in the event of delivery ex-works, the works from which the deliveries are made. 11.2. The risk of the accidental damage and/or loss of the goods is transferred to the purchaser as soon as the goods are handed over to the person carrying out the delivery and/or have left our premises or the manufacturers works for the purposes of delivery. 11.3. If the goods ordered are made ready by us for delivery, and/or delivery and/or call-off is delayed for reasons beyond our control, the risk is transferred to the purchaser on his receipt of notification that the goods are ready for delivery. 11.4. We are entitled, although not obligated, to take out separate insurance against the risks associated with transport, on behalf of and on the account of the purchaser.

>>> Delivery and payment terms


Power cables 1 up to 30 kV
and in the delivery note. When KTG drums are delivered by Klaus Faber AG, KTG offers the purchaser of KTG drums a contract subject to KTG's "Terms and Conditions of the Provision of Cable Drums". By accepting the KTG drum, the purchaser accepts the aforementioned offer of concluding a contract with KTG. The KTG "Terms and Conditions of the Provision of Cable Drums" are available for inspection on the premises of Klaus Faber AG and will be supplied by Klaus Faber AG or KTG, Schanzenstr. 6-20, 51063 Cologne-Mlheim, upon request. We expressly point out that in the event of delivery of KTG drums, these remain the property of KTG and Klaus Faber AG supplies these KTG drums on behalf and on the instructions of KTG. With regard to these KTG drums, KTG makes a rental charge (drum rental), which is to be borne by the purchaser (party receiving the KTG drums), should the relevant drums not be returned within the appointed time. The purchaser undertakes to Klaus Faber AG and by way of contract in favour of third parties also to KTG that it will only supply KTG drums to third parties exclusively at KTG's "Terms and Conditions of the Provision of Cable Drums" (with no modifications whatsoever). Unless agreed otherwise, all cable drums not supplied by the firm of Kabeltrommel GmbH & Co. KG, are supplied under the following conditions, and where these do not apply, under the conditions of the firm of Kabeltrommel GmbH & Co. KG, as is normal commercial practice. Drums which do not become the property of the purchaser are supplied under the following conditions: a) During the first 12 months following delivery, or notification of readiness for delivery, the drums are left with the purchaser free of charge. b) From the 13th to the 17th month inclusive, the purchaser will be charged 15% of the deposit value of the drums per month. c) If the purchaser retains the drums beyond the 17th month, the full deposit value will be charged, and the drums then become the property of the purchaser on settlement of the relevant invoice. These charges are subject to value-added tax at the prevailing rate. d) The charge to be paid by the purchaser within the period from the 13th to the 17th month is cancelled from the time that the purchaser requests collection of the drums in writing, stating the cable drum No. Up to the time of collection, and at the latest up to 3 months after receipt of the collection request, the purchaser remains obliged to store the cable drums with the same care as if they were his own property. e) In the event of insolvency, liquidation, closure of the company etc. of the purchaser, Klaus Faber AG shall be entitled to charge a security for the deposit value. In case of the return of drums not belonging to us or to Kabeltrommel GmbH & Co. KG, we are liable only for the care that we would apply to our own affairs. The return of empty cable drums will be handled by us and at our cost. If the purchaser returns a cable drum to us without our prior agreement, he acts at his own risk and cost. On collection, the purchaser undertakes to provide the necessary loading assistance and to pay any such costs incurred. The purchaser is further obliged to insure the cable drums against the normal risks and with all due businesslike care until the end of the period defined in Point 14.2 d). Irrespective of the above conditions, we expressly reserve the right to supply non-returnable cable drums. If non-returnable cable drums are supplied, the purchaser will be notified accordingly, and at the latest by the time of delivery. Unless otherwise agreed, nonreturnable cable drums become the property of the purchaser on delivery.

Technical Appendix
under public law or has no general seat of adjudication within Germany. 15.3. If any of the above stipulations are or become invalid, this shall not affect the validity of the remaining stipulations. In this case, and instead of the invalid stipulations, those legal stipulations shall apply which most closely approximate the commercial intent of the initial stipulation. These terms and conditions of business replace all earlier versions. 16. Area of application for consumers: If the purchaser is not a contractor, the above conditions apply accordingly, with the exception of the binding clause on prices quoted by us. In the latter case, we will be bound by the prices quoted (before the metal surcharge) for a period of 4 months. After the end of this period, our relevant list prices apply accordingly, unless scheduled delivery within the 4-month period could not be made for reasons that are our responsibility. The interest rate as defined in Point 6.3 and late payment interest for consumers in general is 5% above the basic interest rate. In addition, the terms and conditions of delivery and payment published in the Internet apply at all times.

Flexible Cables

Building Wires

Telecommunication Cables and Cords

14.2.

Date: May 2009 In addition, the terms and conditions of delivery and payment with the revision status published in the Internet (www. faberkabel.de) apply at all times.

LAN cables

Cable with circuit integrity

Control and Electronic Cable

14.3.

14.4.

Conductor ropes

14.5.

14.6.

Other

Technical Appendix

15. Miscellaneous: 15.1. This contract is subject exclusively to the law of the Federal Republic of Germany. In case of international orders, the application of the stipulations of the uniform law on the international purchase of movable goods is expressly excluded. 15.2. Seat of adjudication is, at our discretion, either Saarbrcken or the court responsible for the purchasers head offices, if the purchaser is a businessman, legal person under public law or special asset

> 224 <

>>> www.faberkabel.de <<<

Technical Appendix

>>> www.faberkabel.de <<<


LAN cables Cable with circuit integrity Control and Electronic Cable Telecommunication Cables and Cords Flexible Cables Building Wires Power cables 1 up to 30 kV

> 225 <

Technical Appendix

Other

Conductor ropes

Technical Appendix

Other

Conductor ropes

LAN cables

Cable with circuit integrity Flexible Cables Building Wires

Control and Electronic Cable

Telecommunication Cables and Cords

Power cables 1 up to 30 kV

> 226 <

>>> www.faberkabel.de <<<

Technical Appendix

Klaus Faber AG Management & Sales Lebacher Str. 152-156 66113 Saarbrcken Phone: +49 681 9711-0 Fax: +49 681 9711-289 info@faberkabel.de www.faberkabel.de Klaus Faber AG Distribution Centre Hedemnden Kirchweg 12-14 34346 Hann.Mnden Klaus Faber AG Export & Logistic Centre Fichtenau Grtnerstr. 1 74579 Fichtenau

Not all items listed in this catalogue are permanently on stock. FABER KABEL reserves the right to modify specifications an materials in the light of later technical developement. Issue 02.2010

Vous aimerez peut-être aussi