Académique Documents
Professionnel Documents
Culture Documents
- Contents -
1.
Introduction
2.
Scope of Work
3.
Product Specification
4.
Product Quality
5.
Inspection / Testing
6.
7.
8.
Film Installation
1.Introduction
CNT heating film is a heating system which is installed under the floor to provide primary heat. CNT heating films shall be installed only by qualified personnel or electricians who are familiar with construction, electrical operation and risks involved. Read the entire manual before installation.
2. Scope of Work
3. Product Specification
3. 01. Size
Length 100m
Width 500mm
Thickness 288
Size of 1 module - 630mm340mm Size of heating portion - 550mm320mm Voltage - 220V 60/50Hz
Length 100m
Width 630mm
Thickness 288
Length 100m
Width 800mm
Thickness 288
NO 1 2
Remarks AC m
3 4 5
3. 03. Materials
NO 1 2 3 4 5 6
PART NAME PET Film PET Film Laminate Film Copper Foil Carbon Paste Silver Paste XB-85 XB-65
PART NO.
4. Product Quality
Rated Voltage
AV 220V
Spread a sheet for Insulation Resistance test on a heating part of the film and apply 75ml of water. The resistance value, measured by DC500V Insulation resistance tester, must be over 50 .
5. Inspection / Testing
5. 01. A visual (total) and electrical (sampling) inspection must be carried out. If any signs of
defective, damage or scratch are found, replace the entire film set.
NO
Inspection item
Test Method Measuring the Resistance value of both ends of each heating stripe of the film. Visual check of scratch or damage on carbon patterns.
Resistance
Pattern Printing
It is required to cut out the insulation sheet where the wires join to make wires lay flat.
The selection and installation of each components shall be in accordance with manufacturer's instructions. Manufacturer will not take any responsibility for troubles cased by usage of unapproved components.
Crimping tool, Striper, Wires, Silicone, OPP tape, Electric tape, Rubber tape, Insulators, Thermostats or Control devices, testing device.
8. Installation
8. 01. Work Preparation
Before work proceeds, all of the materials, components, tools and floor plan drawing must be available at the job site.
Ensure that the sub-floor is clean, dry and free from dust or debris.
Lay out the insulation sheet of more than 5mm thickness to cover the entire floor and tape over the joints with OPP tape to protect the film from cold and moisture.
Cut the films to the size and adjust the positioning of films to get the best floor coverage. Under no circumstance may heating portion of the film overlap.
5. Wiring
5-1. Wiring
Insert the wire into the barrel section of the connector and crimp them using crimping tool.
Place the connector and wire over the copper line and press them with fingers.
Then crimp the connector using the flat part of a crimping tool.
Fill the two halves of insulator cap with Insulate connector with insulation tape. silicone.
Insulate the unconnected ends of the heating film using electric tape.
The wire must be positioned not to cross over any heating part of the film.
Floor Sensor
Position and install the thermostat (each per 16m ) and connect the wires. Tape the thermostat floor sensor between the film and insulation sheet.
Before the initial test activation, visual and electrical inspections should be performed. If any part of the film is damaged, entire film shall be replaced. If the films do not become warm after several minutes of system operation, double-check the wiring and re-perform the electrical test. Check the current and voltage with testers and if system is connected properly, install the laminated flooring (if necessary, film protector as well) and complete the installation.