Contract Ref.

HPC / 11-<XX>

Appendix-D /Attachement No 1

APPENDIX D ATTACHEMENT N 1

GUARANTEE SCHEDULES AND QUESTIONNATRE OF CONTRACT REF. HPC/11-<XX> for Supply and Erection of Conventional 66/20/6.6 KV Outdoor Substation on Turn Key Basis in Jihar Area

Hayan Petroleum Company, Appendix D Att-1

1 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

INDEX ITEM No. 1 2 2.1 2.2 2.3 2.4 2.5 2.6 3 3.1 3.2 3.3 3.4 3.5 3.6 4 4.1 4.2 4.3 4.4 4.5 4.6 5 5.1 5.2 5.3 5.4 5.5 5.6 6 6.1 6.2 6.3 DESCRIPTION General Guarantee Schedules For Transformers Guarantee Schedule for Power Transformers 66/20 kV Guarantee Schedule for Power Transformers 66/6.6 kV Guarantee Schedule for Earthing Transformers 20/0.4 kV Guarantee Schedule for Earthing Transformers 6.6/20 kV Guarantee Schedule for vacuum type On-Load Tap Changer Guarantee Schedule for Electrical Insulating Oil Guarantee Schedules For 66 Kv Conventional Type Switchgear Guarantee Schedule for (66)kV Circuit Breaker Guarantee Schedule For Disconnecting Switch ( 66 ) kV Guarantee Schedule For Earthing Switches ( 66 ) kV Guarantee Schedule For Voltage Transformers ( 66 ) kV Guarantee Schedules for Current Transformers ( 66 ) kV Guarantee schedule for lightning arrestor Guarantee Schedule for 20 kV Guarantee Schedule for 20 kV Metal Enclosure Guarantee Schedule for Circuit Breaker ( 20 ) kV Guarantee Schedule For Voltage Transformers ( 20 ) kV Guarantee Schedules for Current Transformers ( 20 ) kV Guarantee schedule for lightning arrestor Guaranteed Schedule for ( 20 ) kV Cu Cables Guarantee Schedule for 6.6 kV Guarantee Schedule for 6.6 kV Metal Enclosure Guarantee Schedule for Circuit Breaker ( 6.6 ) kV Guarantee Schedule For Voltage Transformers ( 6.6 ) kV Guarantee Schedules for Current Transformers ( 6.6 ) kV Guarantee schedule for lightning arrestor Guaranteed Schedule for ( 6.6 ) kV Cu Cables Guarantee Schedule For Protection, Control And Metering Equipment Guarantee Schedule For Transformer Numerical Differential Protection Guarantee Schedule For Numerical Over Current Earth Fault Protection 66kV Guarantee For Numerical Over Current Earth Fault Protection for 20 PAGE 5 6 6 10 13 16 18 19 20 20 23 25 26 27 28 29 29 30 33 33 34 35 36 36 38 40 41 41 42 43 43 46 50

Hayan Petroleum Company, Appendix D Att-1

2 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

kV and for 6.6 kv ( high set And low set overcurrent ) 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 7 7.1 7.2 7.3 7.4 8 8.1 8.2 9 9.1 9.2 10 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9 Guarantee For one phase Numerical sensitive Earth Fault Protection 20 kV and 6.6 kv and 66 Kv neutral points Guarantee Schedule For Directional Over current and directional earth fault Protection 66 kV Guarantee Schedule for Numerical Voltage Regulating Relay Guarantee Schedule For Numerical Line Distance Protection Guarantee Schedule For Check Synchronising Instruments(Mesuring center ) Guarantee Schedule for Tripping and control relay ) Guarantee Schedule for lock out relay ) Guarantee Schedule for trip circuit supervision TCS relay ) Guarantee Schedule for Numerical Computer Control, Measuring , Metering and Monitoring System. Guarantee Schedule for General Requirements for Numerical Control and Protection System Guarantee Schedules for Auxiliary Equipment Guarantee Schedule for A.C Cubicle Guarantee Schedule for Diesel Generating Set Guarantee Schedule for D.C. Installation Guarantee Schedule for Substations Fire Fighting Equipment Guarantee schedules for capacitor bank Guarantee Schedule for 20 kV Capacitor Bank Guarantee Schedule for 6.6 kV Capacitor Bank schedules of manufacturers Substations Equipment Control, Metering And Protection Equipment SCHEDULES OF SPARE PARTS : Spare Parts of Power Transformers ( 10 MVA & 12.5 MVA) Spare Parts of Earthing / Auxiliaries Transformers Spare Parts of 66 kV Circuit Breaker Spare Parts of 66KV Disconnecting Switches Spare Parts of Instrument TRs And Lightning Arresters 66 kV Spare Parts for 20 kV Switchgear Spare Parts of 6.6 kV Switchgear Spare Parts of Control, Metering and Protection Equipment Spare Parts of Auxiliary Equipment 53 56 58 59 66 66 67 68 69 70 75 77 77 78 79 80 81 81 84 88 88 89 90 90 91 91 91 92 92 93 94 94

Hayan Petroleum Company, Appendix D Att-1

3 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10.10 10.11 10.12 11 11.1 11.2 11.3 11.4 12 12.1 12.2

Spare Parts list for capacitor Bank for,10 MVA , 66/20 kV Spare Parts list for capacitor Bank for,12.5 MVA , 66/6.6 kV Bus Bar AS Spare Parts Chedules of maintenance and operation tools equipment List of maintenance & operation tools and equipment for 66 kV equipment Schedules of miscellaneous controle devices List of maintenance & operation tools and equipment miscellaneous List of materials for safety operation Technical evaluation for civil work Civil Work Construction Evaluation of Preliminary Drawing for Outdoor Substation

95 95 96 97 97 97 97 98 99 99 100

Hayan Petroleum Company, Appendix D Att-1

4 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

GENERAL

Bidders are requested to fill-in and sign the forms of guarantee schedules given in this section. Bidders are request to fill-in and sign a separate schedule for each equipment type and voltage Any missing data in filling these schedules or in submitting any information or documents requested to prove the offer specification will badly affect the evaluation of the offer during the technical comparison. Bidders are also requested to insert any additional applicable particulars they may find necessary to prove higher technical quality of their offers. The information furnished with the offer shall include (but shall not be limited to) all data called for in the forms of guarantee schedules, drawings called for herein, and any other relevant information called for elsewhere in the specifications.

The values mentioned in HPC requirements is the minimum acceptable

Hayan Petroleum Company, Appendix D Att-1

5 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

GUARANTEE SCHEDULES FOR TRANSFORMERS

2.1 Guarantee Schedule for Power Transformers 66/20 kV


Item Description Unit HPC REQUIRMENTS
OFFER VALUE

1 - Design Data Manufacturers name 1.1 Country of origin 1.2 Type / designation 1.3 ISO certificate 1.4 Standard specifications applied Rated power - ONAF/ONAN 1.5 a) At 50 C ambient temp. b) At IEC conditions 1.6 Rated voltage ratio 1.7 Connection group 1.8 Highest voltages - H.V./L.V. Winding temperature rise by 1.9 resistance above 50C ambient temperature at rated power Top oil temperature rise by 1.10 thermometer above 50C ambient temperature at rated power
1.11 Impedance voltage at 75C and normal ratio and rated power Impulse withstand voltage (1.2x50 u sec.) a) H.V winding 1.12 b) H.V bushing c) Neutral-bushing and winding d) L.V. bushing and winding Power frequency withstand voltage : a) H.V. winding 1.13 b) L.V. winding c) H.V. bushing d) L.V. bushing e) H.V. neutral point 1.14 Rated frequency 2 - Other Particulars

Yes/No IEC MVA 10/7.5 66/20 YN,d11 72.5/24 55 50


10

KV

C C
%

325

KV

325 325 125 140 50

KV

140 50 140

Hz

50

2.1 2.2

Zero sequence impedance under line to ground fault condition at rated MVA and voltage Type of windings :

Ohm/PH

Hayan Petroleum Company, Appendix D Att-1

6 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) H.V. winding b) L.V. winding Cross-section of windings a) H.V. winding b) L.V. winding Ability to withstand short-circuits and duration a) H.V. winding b) L.V. winding No load losses at normal ratio and rated primary voltage Load losses at 75C, normal ratio, rated primary voltage and rated power without coolers. Total losses at 75C, normal ratio and rated power: Voltage drop at rated power and 75C a) at P.F. = 1.0 b) at P.F. = 0.8 No-load current in % of rated current: a) at 95% rated voltage b) at 100% rated voltage c) at 105% rated voltage d) at 110% rated voltage Type of winding insulation ,and class IEC : a) H.V. winding b) L.V. winding Ability to give the rated power at all taps Operation at higher than the rated system voltage (over induction) : a) 105 % b) 110 % c) 120 % Sound level acc. to IEC 551 a) With coolers b) Without coolers Efficiency at : a) 100 % rated power b) 80 % rated power c) 70 % rated power

Unit

HPC REQUIRMENTS

OFFER VALUE

2.3

mm2 mm2

2.4

2.5 2.6 2.7 2.8

KA/Sec KA/Sec KW KW KW

10 60

KV KV % % % % Uniform,Class A

2.9

2.10

2.11

yes duration Hours Hours


Minutes

2.12

Continuous

2.13

dB dB
P.F = 1

< 72 < 70
P.F = 0.8 P.F = 1 P.F = 0.8

2.14

Hayan Petroleum Company, Appendix D Att-1

7 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description d) 60 % rated power e) 50 % rated power f) 40 % rated power g) 25 % rated power Resistances:

Unit

HPC REQUIRMENTS

OFFER VALUE

2.15

2.16

2.17

a) H.V. winding- resistance (at 75C) b) L.V. winding (converted to quivalent star connection) - resistance (at 75C) Hot spot temperature : Rise Absolute Load required by the fans at rated power and ambient air temperature : a) 25 C b) 30 C c) 35 C d) 40 C e) 45 C Permissible duration of overloading at 50C ambient air temperature and at :

/ PH / PH C C < 68 < 118

KW KW KW KW KW After (50%) loading min. min. min. min. min. Yes/No YES After (70%) loading After (50%) loading After (70%) loading

2.18

2.19 2.20 2.21 2.22

2.23

2.24 2.25

a) 10 % overload b) 20 % overload c) 30 % overload d) 40 % overload e) 50 % overload Mixibility of the used insulation oil with Shell Diala B Material of core Thickness of core laminations/type of insulation Material and type of tank construction Thickness of transformer plates : a) Tank cover b) Side c) Bottom d) Coolers plates Maximum flux density at rated voltage current density at rated load H.V./L.V.

mm

mm mm mm mm T
A/mm

> 12 > 1.25

1.7 2.5 / < 2.5

Hayan Petroleum Company, Appendix D Att-1

8 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2.26

Description Fan/Pump motor details : a) Total number b) Rated power (each) c) Full load current d) Voltage e) Type f) Starting current Transformer Bushings Insulator bushing material Manufacturer Rated current Power frequency withstand voltage Impulse withstand voltage Applied standard specifications Creepage distance Acceptable mech. Load Approximate overall length Approximate overall width Approximate overall height Weight of the copper of : a) H.V. winding b) L.V. winding For inspection of windings : a) Description of the part to be lifted b) Height of parts to be lifted c) Weight of parts to be lifted Net weight of transformer : a) Core and windings b) Tank and fittings c) Oil d) Transportation weight e) Total Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit Nos. KW A V A

HPC REQUIRMENTS

OFFER VALUE

380/ 3Ph

2.27 2.27.1 2.27.2 2.27.3 2.27.4 2.27.5 2.27.6 2.27.7 2.27.8 2.28

HV

LV

HV

LV

A KV KV mm N m m m Kg Kg

>150 > 140 >325 >1813 >1000

> 630 > 50 >125 >600 >1000

2.29

2.30

m ton Kg Kg Kg ton ton Yes / No

2.31

Max. 26 ton

2.32

2.33

Hayan Petroleum Company, Appendix D Att-1

9 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

2.2 Guarantee Schedule for Power Transformers 66/6.6 kV


Item Description Unit HPC REQUIRMENTS
OFFER VALUE

1 - Design Data Manufacturers name 1.1 Country of origin 1.2 Type / designation 1.3 ISO certificate 1.4 Standard specifications applied Rated power ONAN 1.5 a) At 50 C ambient temp. : b) At IEC conditions : 1.6 Rated voltage ratio 1.7 Connection group 1.8 Highest voltages - H.V./L.V. Winding temperature rise by 1.9 resistance above 50C ambient temperature at rated power Top oil temperature rise by 1.10 thermometer above 50C ambient temperature at rated power Impedance voltage at 75C and 1.11 normal ratio and rated power Impulse withstand voltage (1.2x50 u sec.) a) H.V winding 1.12 b) H.V bushing c) Neutral-bushing and winding d) L.V. bushing and winding Power frequency withstand voltage : a) H.V. winding 1.13 b) L.V. winding c) H.V. bushing d) L.V. bushing e) H.V. neutral point 1.14 Rated frequency
2 - Other Particulars

Yes/No IEC MVA KV KV C C % 12.5 66/6.6 YN,d11 72.5/7.2 55 50 8.35 (with +10% tolerance)

KV KV KV KV KV KV KV KV KV
Hz

325 325 325 60 140 20 140 20 140 50

2.1 2.2

Zero sequence impedance under line to ground fault condition at rated MVA and voltage Type of windings : a) H.V. winding

/PH

Hayan Petroleum Company, Appendix D Att-1

10 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description b) L.V. winding Cross-section of windings a) H.V. winding b) L.V. winding Ability to withstand short-circuits and duration a) H.V. winding b) L.V. winding No load losses at normal ratio and rated primary voltage Load losses at 75C, normal ratio, rated primary voltage and rated power without coolers. Total losses at 75C, normal ratio and rated power: Voltage drop at rated power and 75C a) at P.F. = 1.0 b) at P.F. = 0.8 No-load current in % of rated current a) at 95% rated voltage b) at 100% rated voltage c) at 105% rated voltage d) at 110% rated voltage Type of winding insulation , and class IEC : a) H.V. winding b) L.V. winding Ability to give the rated power at all taps . Operation at higher than the rated system voltage (over induction) : a) 105 % b) 110 % c) 120 % Sound level acc. to IEC 551 Efficiency at : a) 100 % rated power b) 80 % rated power c) 70 % rated power d) 60 % rated power e) 50 % rated power

Unit

HPC REQUIRMENTS

OFFER VALUE

2.3

mm2 mm2

2.4

2.5 2.6 2.7 2.8

KA/Sec KA/Sec KW KW KW

12.5 70

KV KV % % % % Uniform Class A yes duration Hours Hours


Minutes

2.9

2.10

2.11

2.12

Continuous

2.13 2.14

< 70
P.F = 1 P.F = 0.8 P.F = 1 P.F = 0.8

Hayan Petroleum Company, Appendix D Att-1

11 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description f) 40 % rated power g) 25 % rated power Resistances, reactances :

Unit

HPC REQUIRMENTS

OFFER VALUE

2.15

2.16

2.17

2.18 2.19 2.20 2.21

2.22

2.23 2.24 2.25 2.25.1 2.25.2 2.25.3 2.25.4 2.25.5

a) H.V. winding - sistance (at 75C) b) L.V. winding (converted to equivalent star connection) - resistance (at 75C) Hot spot temperature : Rise Absolute Permissible duration of overloading at 50C ambient air temperature and at : a) 10 % overload b) 20 % overload c) 30 % overload d) 40 % overload e) 50 % overload Mixibility of the used insulation oil with Shell Diala B Material of core Thickness of core laminations/type of insulation Material and type of tank construction Thickness of transformer plates : a) Tank cover b) Side c) Bottom d) Coolers plates Maximum flux density at rated voltage . current density at rated load H.V./L.V. Transformer Bushings Insulator bushing material Manufacturer Rated current Power frequency withstand voltage Impulse withstand voltage

/ PH / PH C C < 68 < 118 After After (50%) (70%) loading loading

After (50%) oading

After (70%) loading

min. min. min. min. min. Yes/No YES

mm

mm mm mm mm T
A/mm

> 12 > 1.25

1.7 2.5 / < 2.5 HV LV HV LV

A KV KV mm

>150 > 140 >325 >1813

> 3150 > 20 >60

2.25.6 Applied standard specifications 2.25.7 Creepage distance

>180

Hayan Petroleum Company, Appendix D Att-1

12 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description Approximate overall length Approximate overall width Approximate overall height Weight of the copper of : a) H.V. winding b) L.V. winding For inspection of windings : a) Description of the part to be lifted b) Height of parts to be lifted c) Weight of parts to be lifted Net weight of transformer : a) Core and windings b) Tank and fittings c) Oil d) Transportation weight e) Total Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit N m m m Kg Kg

2.25.8 Acceptable mech. Load 2.25

HPC REQUIRMENTS >1000 >1000

OFFER VALUE

2.26

2.27

m ton Kg Kg Kg ton ton Yes / No

2.28

Max. 33 ton

2.29

2.30

2.3 Guarantee Schedule for Earthing Transformers 20/0.4 kV


Item 1 - Design Data 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Manufacturers name Country of origin Type/designation ISO certificate Primary rated voltage Highest primary voltage Secondary voltage Rated capacity of L.V. side a) At 50 C ambient temp. b) At IEC conditions : Description Unit HPC REQUIRMENTS
OFFER

VALUE

Yes/No KV KV V KVA

20 24 400 50

Hayan Petroleum Company, Appendix D Att-1

13 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 1.8 1.9 1.10 1.11

Description

Unit

HPC REQUIRMENTS 125 50 500/30 40

OFFER

VALUE

1.12

1.13 1.14 1.15 1.16 1.17

2.l 2.2 2.3 2.4

2.5

2.6

Impulse withstand voltage of the KV primary winding Power frequency withstand voltage of KV the primary winding Short time current of the primary winding due to a single phase earth Amp/Sec fault current applied at the primary line terminal Rated continuous current of the A primary winding per neutral. Maximum temperature rise above 50C ambient temperature at rated continuous current : a) of the winding C b) of the oil C Off-load tap-changer : a) Number of taps Nos b) size of taps % Method of cooling Connection group Zero-sequence impedance of the / ph primary winding Impedance voltage with rated power, % principal tapping and at 45 C ambient air temperature 2 - Other Particulars No-load current a) at rated voltage A b) at 110% rated voltage A No-load losses at rated voltage KW Load losses at 75 C and rated KW capacity KW Total losses at 75 C at L.V side Efficiency at : % a) 100% rated power % b) 80% rated power % c) 70% rated power % d) 60% rated power % e) 50% rated power % f) 40% rated power % g) 25% rated power Type of winding

55 50 5 2x2.5 ONAN Znyn11 60 6.0

Hayan Petroleum Company, Appendix D Att-1

14 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2.7 2.8 2.9 2.10

Description Impedance at 75 C Type of steel core laminations Maximum flux density at rated voltage current density ( HV / LV ) Thickness of transformer plates : a) Tank cover b) Bottom c) coolers Cross-section of windings a) H.V. winding b) L.V. winding Limits of tolerance for all guaranteed values : a) Impedance b) No-load losses c) Load losses d) Total losses Approximate overall length Approximate overall height Approximate overall width Total wieght of transformer : a) With oil b) Without oil Number of permissible closings on fault with 1,5 min. interval Number of permissible full fault conditions during 24h. Overinduction capability - duration : 105%/110%/120% Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit Ohm
T

HPC REQUIRMENTS

OFFER

VALUE

< 1.7
2.5

A/mm2 mm mm

2.11

>4 >6 > 1.25

2.12

mm2 mm2

5.3 60

2.13

+% +% +% +%

2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21

m m m Kg Kg Nos. Nos. hour Yes / No

2.22

Hayan Petroleum Company, Appendix D Att-1

15 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

2.4 Guarantee Schedule for Earthing Transformers 6.6/0.4 kV


Item Description Manufacturers name Country of Origin Type/designation ISO certificate Primary rated voltage Highest primary voltage Secondary voltage Rated capacity of L.V. side Unit 1 - Design Data 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 HPC REQUIRMENTS
OFFER

VALUE

Yes/No KV KV V

6.6 7.2 400 50 60 20 500/30 40

1.12

1.13 1.14 1.15 1.16 1.17

2.l

a) At 50 C ambient temp. KVA b) At IEC conditions : Impulse withstand voltage of the KV primary winding Power frequency withstand voltage of KV the primary winding Short time current of the primary winding due to a single phase earth Amp/Sec fault current applied at the primary line terminal Rated continuous current of the A primary winding per neutral. Maximum temperature rise above 50C ambient temperature at rated continuous current : a) of the winding C b) of the oil C Off-load tap-changer : a) Number of taps Nos b) size of taps % Method of cooling Connection group Zero-sequence impedance of the / ph primary winding Impedance voltage with rated power, % principal tapping and at 45 C ambient air temperature 2 - Other Particulars No-load current a) at rated voltage A b) at 110% rated voltage A

55 50 5 2x2.5 ONAN Znyn11 20 6.0

Hayan Petroleum Company, Appendix D Att-1

16 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2.2 2.3 2.4

Description No-load losses at rated voltage Load losses at 75 C and rated capacity Total losses at 75 C at L.V side Efficiency at : a) 100% rated power b) 80% rated power c) 70% rated power d) 60% rated power e) 50% rated power f) 40% rated power g) 25% rated power Type of winding Impedance at 75 C Type of steel core laminations Maximum flux density at rated voltage Current density ( HV / LV ) Thickness of transformer plates : a) Tank cover b) Bottom c) coolers Cross-section of windings a) H.V. winding
b) L.V. winding

Unit KW KW KW % % % % % % % T A/mm2 mm mm

HPC REQUIRMENTS

OFFER

VALUE

2.5

2.6 2.7 2.8 2.9 2.10

< 1.7 2.5 >4 >6 > 1.25


5.3 60

2.11

2.12

mm2 mm2

2.13

2.14 2.15 2.16 2.17 2.18 2.19

Limits of tolerance for all guaranteed values : a) Impedance b) No-load losses c) Load losses d) Total losses Approximate overall length Approximate overall height Approximate overall width Total wieght of transformer : a) With oil b) Without oil Number of permissible closings on fault with 1,5 min. interval Number of permissible full fault conditions during 24h.

+% +% +% +% m m m Kg Kg Nos. Nos.

Hayan Petroleum Company, Appendix D Att-1

17 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2.20 2.21 2.22

Description Overinduction capability - duration : 105%/110%/120% Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit hour Yes / No

HPC REQUIRMENTS

OFFER

VALUE

2.5 Guarantee Schedule for vacuum type On-Load Tap Changer


Item Description Unit HPC REQUIRMENTS OFFER VALUE

1 2 3 4 5 6 7 8 9
10 11

Manufacturers name Country of Origin Type/designation ISO certificate Standard specification applied Maximum rated through-current Number of taps
For 10 MVA, 66/20 For 12.5 MVA,66/6.6

vacuum

Yes/No A + V KVA + % >300 9 8 (1500-1700) 600 + 16 + 10


1-19

Rated step voltage Rated switching - capacity


Tapping range (in % of rated voltage) Tapping arrangement For 10 MVA, 66/20 For 12.5 MVA,66/6.6

Connection arrangement Insulation to grounds : a) Insulation class b) Highest voltage c) Power frequency withstand voltage ( 1min. ) d) Impulse withstand voltage ( 1/50 micro sec ) Maximum short-circuit current Rated current at lowest position of OLTC Number of on-load changeovers without changing of contacts Number of switching operations after which a maintenance is required

( Y ) Neutral part of H.V

12

KV KV KV KA/S A Nos. Nos.

72.5 >140 >325

13 14 15 16

Hayan Petroleum Company, Appendix D Att-1

18 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 17

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

17.1

17.2 17.3 17.4 17.5

Technical data of motor drive unit : Motor : a) Rated power b) Rated voltage c) Rated current d) Rated frequency e) Speed Rated torque on drive shaft Running time per switching operation Voltage for control and heater Input of control circuit : a) When energized b) During the running time Insulation level Outdoor design protection Mechanical endurance ( operation ) Weight Copy of the newest edition for relevant IEC

W V A Hz r.p.m Nm V VA

380 ( 3 Ph ) 50

220

17.6 17.7 17.8 17.9 18

KV/ 1 min IP Kg Yes/No

2 54

2.6 Guarantee Schedule for Electrical Insulating Oil


Item 1 2 3 4 5 6 7 8 Description Manufacturers name Country of Origin Disruptive voltage Viscosity : a) at 20 C b) at 50 C Flash point Pour point Tan delta (at 50 Hz) Ash content Acid number/mg KOH/g Unit HPC REQUIRMENTS
OFFER

VALUE

KV

C C % mg

> 140 < -30 < 0.005 < 0.01 < 0.03

Hayan Petroleum Company, Appendix D Att-1

19 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

GUARANTEE SCHEDULES FOR 66 KV CONVENTIONAL TYPE SWITCHGEAR

3.1 Guarantee Schedule for (66)kV Circuit Breaker


Item 1 2 3 4 5 6 7 8 9 10 Description Manufacturer name Country of Origin ISO 9001 certificate Type of circuit breaker Type designation Rated frequency Rated voltages : a) Highest system voltage b) Minimum service voltage Rated normal current at 50C ambient temperature Rated breaking current capacity a) symmetric b) D.C. component Rated peak - making current Rated peak short-circuit current
Rated short-time current 11

Unit

HPC
REQUIRMENTS

OFFER VALUE

Yes/No SF6 Hz KV KV A KA %
KA (peak) KA (peak)

50 66 72.5 1250 31.5 >80 >80

(rms)

a) 1 sec. b) 3 sec.

12 13 14 15

Rated line-charging breaking current Rated cable - charging breaking current Rated small inductive breaking current Rated breaking current under out-ofphase conditions Restricting voltage : a) rate-of-rise (RRRV) b) peak

KA (rms) KA (rms) A A A
KA

> 31.5

16 17

KV/msec KV (peak)

18

First-pole-to-clear factor One minute power frequency withstand voltage : a) Phase to earth b) Across open contacts

KV (rms) KV (rms)

> 140 160

Hayan Petroleum Company, Appendix D Att-1

20 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description Lightning impulse withstand voltage 1,2/50 micro sec Rated operating sequence Capacity to make : High speed three phase auto reclosure Minimum time between each successive break/make operation Opening time (until separation of the arcing contacts) a) Without current b) With 100%rated breaking current Maximum total break time (until total arc-extinction) Maximum time interval between opening of the first and the last phase Maximum time interval between opening of the interrupters of one phase (if any) Make time : a) Without current b) With 100% rated making current Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) Maximum time between closing of first and last phase Maximum time interval between closing of interrupters of one phase. Dead time Maximum peak value of switching over-voltage when interrupting rated line charching current Radio influence voltage (RIV) measured at rated voltage to earth Interrupting units in series per phase: a) Number b) Length of each break Devices used to limit transient recovery voltages Creepage distance : a) To earth b) Across terminals Operating mechanism : a) Type

Unit
kV (peak)

HPC
REQUIRMENTS

OFFER VALUE

19 20 21 22

> 325 O- 0.3S CO3 min CO

sec.

> 0.3

23

ms ms ms ms ms

24 25 26

27

ms ms ms ms ms ms KV (peak) micro V < 300

28 29 30 31 32 33 34 35
36 37

mm

mm mm mm

> 1813

Spring
21 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description b) Operating voltage - Rated - Range ( Min-Max ) c) Rated power d) Operating pressurenormal/max/min. Closing release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power Trip release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power Clearances : a) Between phases b) Between alive part and earth Weight of circuit breaker : a) Total b) Heaviest part to be lifted during maintenance or repair procedure Type test certificate details : a) Testing station/authority b) Certificate number c) Applied standards Quantity of gas required to fill one three phase unit. Quantity of gas required to cover one year losses (per three phase unit). Gas operating pressure at 20 C : a) Normal b) Maximum c) Minimum Low pressure alarm setting : a) First stage b) Second stage Type of pressure monitoring device Copy of the newest edition for relevant IEC

Unit VDC % W bar VDC % % W VDC % % W mm mm Kg Kg

HPC
REQUIRMENTS

OFFER VALUE

110 -20% +10%

38

110 -20% + 10%

39

110 -30% + 10%

40

> 630 > 630

41

42

43 44

Kg % bar bar bar bar bar Yes / No YES YES

45

46 47 48

Hayan Petroleum Company, Appendix D Att-1

22 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit

HPC
REQUIRMENTS

OFFER VALUE

49

3.2 Guarantee Schedule For Disconnecting Switch ( 66 ) kV


Item 1 2 3 4 5 6 7 Description Manufacturer s name Country of Origin ISO certificate Type designation Three-phase or single-phase design Earthing switch incorporated Rated voltage Rated normal current at 45C ambient temperature : a) For bus coupler bay b) For others Lightning impulse withstand voltage 1,2/50 micro sec : a) To earth and between phases b) Across open contacts One minute power frequency withstand voltage : a) To earth and between phases b) Across open contacts Rated short-time current : Disconnecting switch : a) for 1 sec. b) for 3 sec. Earthing switch coupled with D.C. : a) for 1 sec. b) for 3 sec. Rtead peak short circuit current : a) For disconnecting switch b) For earthing switch Unit HPC REQUIRMENTS
OFFER
VALUE

Yes/No

KV

66

A A

> 1600 > 1250

KV (peak) KV (peak)

> 325 > 375

9 10 10.1

KV (rms) KV (rms)

> 140 > 160

KA (rms) KA (rms) KA (rms) KA (rms) KA(peak) KA(peak)

31.5

10.2

> 31.5

11

> 80 > 80

Hayan Petroleum Company, Appendix D Att-1

23 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 12 12.1

Description Operating mechanism for disconnecting switch : Type Operating voltage-rated/min/max for a) Operating coil b) range c) Operating coil (if any) d) Motor Rated power : a) Operating coil (if any) b) Motor Opening time-from the moment when the coil is energized until the complete extinction of arc between opened contacts (under system highest voltage conditions). Operation time-from the moment when the coil is energized until the disconnection of operating motor in limit open disconnector positioning. Operating mechanism for earthing switch : a) Type b) Operating voltage- min/max. c) range d) Rated power Clearances : a) Phase to earth arcing distance b) Phase to phase distance in open position c) Distance between contacts of open disconnector Support insulators : a) Manufacturer / country b) Type designation of unit c) Creepage distance Total weight of complete disconnecting switch (one or three poles) Type test certificate details : a) Testing station b) Certificate numbers

Unit

HPC REQUIRMENTS

OFFER
VALUE

MOTOR VAC %
V

12.2

220 ( -20 , + 10 )

12.3

W W

13

sec.

14

sec.

15

VAC % W mm mm mm

220 (-20% +10)%

16

> 630 > 630 > 630

17

mm Kg

> 1813

18 19

Hayan Petroleum Company, Appendix D Att-1

24 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description c) Applied standard specifications Capacity of lifting equipment necessary for repair or maintenance of one pole of disconnecting switch, or three poles

Unit

HPC REQUIRMENTS

OFFER
VALUE

20

Kg

3.3 Guarantee Schedule For Earthing Switches ( 66 ) kV


Item 1 2 3 4 5 6 Description Manufacturer Country of Origin ISO certificate Type designation Type of contacts Materials of contact surface Rated short-time current : a) for 1 sec. b) for 3 sec. Rated peak short circuit current Gap between poles One minute power frequency withstand voltage across open gap Lightning impulse withstand voltage across open gap Operating mechanism : a) Type b) Operating voltage: - Rated - Range c) Rated power Main dimensions Total weight Type test certificate details : a) Testing station/authority b) Certificate number C) Applied standards Creepage distance Yes/No Unit HPC REQUIRMENTS OFFER VALUE

Silver
KA (rms)

31.5
KA (rms) KA(peak)

7 8 9 10

80 > 140 > 325

mm KV KV (peak)

11

12 13

VAC % W mm Kg

220 ( -20%,+10% )

14

15

mm

> 1813*

Hayan Petroleum Company, Appendix D Att-1

25 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

3.4 Guarantee Schedule For Voltage Transformers ( 66 ) kV


Item 1 2 3 4 5 6 7 7.1 7.2 8 8.1 8.2 9 10 11 12 Description Manufacturer Country of Origin ISO certificate Type designation Insulation material Rated frequency Highest system voltage Rated insulation level Power frequency withstand voltage Impulse 1,2/50 micro-sec withstand voltage Rated voltages : Rated primary voltage Rated secondary voltage Rated output/accuracy class Two coils Voltage factor Rated ratio Ratio error with rated output and : a) 105% normal primary voltage b) 5% normal primary voltage Ratio angle error with rated output at a) 105% normal primary voltage b) 5% normal primary voltage Method of suppressing ferroresonance Creepage distance Flash-over distance Main dimensions Total weight Applied standard specifications Unit HPC REQUIRMENTS
OFFER

VALUE

Yes/No Porcelain 50 72.5 > 140 > 325 66/ 3 100/ 3 > 50 / 0.5- 3P

Hz KV KV KV (peak) V V

< 1%

13 14 15 16 17 18 19

Degree

mm mm mm Kg

> 1813 > 630

Hayan Petroleum Company, Appendix D Att-1

26 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

3.5 Guarantee Schedules for Current Transformers ( 66 ) kV


Item 1 2 3 4 5 6 6.1 6.2 Description Manufacturer Country of Origin ISO certificate Type designation Highest system voltage Insulation material Rated insulation levels : Lightning impulse withstand voltage 1,2/50 micro-sec One minute power frequency withstand voltage Rated primary current : a) For incoming feeder b) For transformers feeders (12.5 MVA) c) For transformer feeder (10 MVA) Rating of secondary windings : a) Rated current b) Rated output/accuracy class - core 1 (measuring) - core 2 (protection) - core 3 (protection) 9 10 11 12 13 14 Overload capacity at 45 C ambient temperature Creepage distance Flash-over distance Dimensions Total weight Applied standard specifications VA VA VA % mm mm mm Kg CLX , VK>500V , RCT<4 5P20 , 20VA CL 0.5 , FS=5 , 20VA > 120 > 1813 > 630 Yes/No KV Should be submitted 72.5 Porcelain > 325 > 140 600 - 300 400 - 200 200 - 100 1 Unit HPC REQUIRMENTS OFFER VALUE

KV (peak) KV (rms) A A A A

Hayan Petroleum Company, Appendix D Att-1

27 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

3.6 Guarantee schedule for lightning arrestor ( Zinc Oxide Type ) ( 66 ) kV


Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 16 17 18 19 20 21 22 23 24 Description Manufacturer Country of Origin ISO certificate Type reference Rated frequency Highest System voltage Max Continuous operating voltage Power frequency withstand voltage for ( 1 min ) ( empty housing ) Lightning impulse withstand voltage ( 1.2/50 s ) ( empty housing Temporary over voltage capability for ( 1 sec ) . Arrester current rating Outdoor type Type of mounting Radio influence voltage measured at rated voltage to earth Maximum peak residual voltage of complete arresters at : Lightning impulse (8/20 s) 10 KA Discharge current withstand strength High current ( 4/10 s ) Low current ( 2000 s ) Energy impulse capability Pressure relief capability for 0.2 sec. Leakage current through the complete arrester at rated system phase voltage Creepage distance Discharge class Max safe load canti lever to one terminal Mass of each complete arrester Maximum arrest of the long time impulse current which the series resistance blokes will withstand Type of surge counter Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz KV KV KV KV KV/S KA > 10 Yes Pedestal 50 5% 72.5 App. 60

v KV Peak < 220

KA Peak KA Peak KJ/kV KA A mm N.m Kg A Yes/No

> 100 > 0.4 > 40

> 1813 Class 3

< 600

Hayan Petroleum Company, Appendix D Att-1

28 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Guarantee Schedule for 20 kV

4.1 Guarantee Schedule for 20 kV Metal Enclosure


Item 1 2 3 4 5 6 7 Description Manufacturer Country of Origin ISO 9001 certificate Type Rated voltage Standard specifications Material of cubicles Thickness of sheet Dimensions of the cubicles : a) Width b) Depth c) Height Bus bars : a) Material b) Cross-section per phase c) Minimum clearance between phases d) Minimum clearance to earth e) Space between bus-bars supports f) basbar insulation Connectors : a) Material b) Cross-section per phase : - incoming feeder - Outgoing feeder C) Minimum clearance between fases d) Clearance to earth Maximum allowable current density at site worst conditions (for maximum ambient temperature 50C) : a) For busbars b) For connectors : Dynamic short-circuit current Thermal short-circuit current Segregated compartments per cubicle ( 20 ) kV equipment Unit HPC REQUIRMENTS OFFER VALUE

Yes/No KV AIS 20 Steel >2

mm mm mm mm

Copper Sq.mm mm mm mm

10

sq.mm sq.mm mm mm

11

12 13 14

A/sq.mm A/sq.mm KA KA Yes/No

> 62.5 > 16

Hayan Petroleum Company, Appendix D Att-1

29 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 15

Description The cubicle with well protection against fire risks and contact with live parts Enclosures : a) Phase egregated or three phase b) Material c) Overall diameter d) Wall thickness Rated insulation levels at normal pressure Power frequency ( 1 ) minute withstand voltage Lighting impulse withstand voltage Degree of protection a) Internal high voltage equipment, gas enclosure b) External enclosure Does the cubicle have plug in or Bolted cable termination Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit Yes/NO
Yes/NO

HPC REQUIRMENTS YES

OFFER VALUE

16

17

KV KV IP IP Yes/NO

50 125 42 2x Should be provided

18

19 20

Yes / No

21

Hayan Petroleum Company, Appendix D Att-1

30 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

4.2 Guarantee Schedule for Circuit Breaker ( 20 ) kV


Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Manufacturer Country of Origin ISO 9001 certificate Type of circuit breaker Type designation Rated frequency Rated voltages : a) Highest system voltage b) Minimum service voltage Rated normal current at 40C ambient temperature : Rated breaking current capacity a) symmetric (rms) b) D.C. component Rated peak making current Rated peak short-circuit current Rated short-time current a) 1 sec. b) 3 sec. Rated line-charging breaking current Rated cable - charging breaking current Rated small inductive breaking current Rated breaking current under out-ofphase conditions Restricting voltage : a) rate-of-rise (RRRV) b) peak 17 First-pole-to-clear factor One minute power frequency withstand voltage : a) Phase to earth b) Across open contacts 19 20 Lightning impulse withstand voltage 1,2/50 micro sec Rated operating sequence KV (rms) KV (rms)
KV (peak) KA (rms) KA (rms)

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No vacuum Hz KV KV 50 24 20 800 KA (rms) %


KA (peak) KA (peak)

16 >62.5 >62.5 > 16

A A A
KA KV / micro sec KV (peak)

16

18

> 50

> 125

Hayan Petroleum Company, Appendix D Att-1

31 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 21

Description Capacity to make : a) High speed three phase auto


extinguishing

Unit

HPC REQUIRMENTS

OFFER VALUE

22 23

24 25 26

Minimum time between each successive break/make operation Opening time (until separation of the arcing contacts) a) Without current b) With 100%rated breaking current Maximum total break time (until total arc-extinction) Maximum time interval between opening of the first and the last phase Maximum time interval between opening of the interrupters of one phase (if any) Make time : a) Without current b) With 100% rated making current Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) Maximum time between closing of first and last phase Maximum time interval between closing of interrupters of one phase. Dead time Operating mechanism : a) Type b) Operating voltage c) Rated d) Range e) Rated power Closing release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power Trip release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power

sec.

> 0.3

ms ms ms ms ms

27

ms ms ms ms ms ms

28 29 30 31

32

VDC % W VDC % % W VDC % % W

110 ( -20% +10% )

33

110 -20% + 10%

34

110 -30% + 10%

Hayan Petroleum Company, Appendix D Att-1

32 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 35

Description Type test certificate details : a) Testing station/authority b) Certificate number c) Applied standards

Unit

HPC REQUIRMENTS

OFFER VALUE

4.3 Guarantee Schedule For Voltage Transformers ( 20 ) kV


Item 1 2 3 4 5 6 Description Manufacturer Country of Origin Type designation ISO 9001 certificate Rated frequency Highest system voltage Rated insulation level: a) Power frequency withstand voltage b) Impulse 1,2/50 micro-sec withstand voltage Rated voltages : a) Rated primary voltage b) Rated secondary voltage Rated output/accuracy class Two coils Voltage factor Rated ratio Ratio error with rated output and : a) 105% normal primary voltage b) 5% normal primary voltage Ratio angle error with rated output and : a) 105% normal primary voltage b) 5% normal primary voltage Total weight Applied standard specifications Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz KV KV KV (peak) kV V

50 24 > 50 > 125 20/ 3 100/ 3 > 50 / 0.5- 3P

7 8 9 10 11

Degree 1 Kg

12 13 14

Hayan Petroleum Company, Appendix D Att-1

33 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

4.4 Guarantee Schedules for Current Transformers ( 20 ) kV


Item 1 2 3 4 5 6 6.1 6.2 7 Description Manufacturer Country of Origin ISO 9001 certificate Type designation Highest system voltage Insulation material Rated insulation levels : Lightning impulse withstand voltage 1,2/50 micro-sec One minute power frequency withstand voltage Rated primary current : Rating of secondary windings : a) Rated current b) Rated output/accuracy class : 8 - core 1 (measuring) - core 2 (protection) - core 3 (protection) 9 10 11 Overload capacity at 45 C ambient temperature Total weight Applied standard specifications VA VA VA % Kg CLX , VK>400V , RCT<4 5P20 , 20VA CL 0.5 , FS=5 , 15VA > 120 Unit HPC REQUIRMENTS OFFER VALUE

Yes/No KV
24

KV (peak) KV (rms) A A

125 50

400 - 800 1

4.5 Guarantee schedule for lightning arrestor ( Zinc Oxide Type ) ( 20 ) kV


Item 1 2 3 4 5 6 Description Manufacturer Country of Origin Type reference ISO certificate Rated frequency system voltage Rated voltage Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz KV KV

50 5% 24 20 5%

Hayan Petroleum Company, Appendix D Att-1

34 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

7 8 9 10 11 12 13 14

Power frequency withstand voltage for ( 1 min ) ( empty housing ) Lightning impulse withstand voltage ( 1.2/50 s ) ( empty housing ) Temporary over voltage capability for ( 3 sec ) . Arrester current rating Outdoor type Type of mounting Radio influence voltage measured at rated voltage to earth Maximum peak residual voltage of complete arresters at : Lightning impulse (8/20 s) 10 KA Discharge current withstand strength a) High current ( 4/10 s ) b) Low current ( 2000 s ) Energy impulse capability Pressure relief capability for 0.2 sec. Leakage current through the complete arrester at rated system phase voltage Creepage distance Discharge class as per IEC Max safe load canti lever to line Mass of each complete arrester Dimensions Maximum crest of the long time impulse current which the series resistance blokes will withstand Type of surge counter

KV KV KV/S KA

Acc. to IEC 125 > 21/3 > 10 Yes Pedestal

v KV Peak < 80

15 16 17 18 19 20 21 22 23 24 25

KA Peak KA Peak KJ/kV KA A mm N.m Kg

> 0.25

> 600 Class 3

< 600

4.6 Guaranteed Schedule for ( 20 ) kV Cu Cables


Item 1 2 3 4 4.1 4.2 Description Manufacturer Country of Origin Type ISO 9001 certificate Cross-section ( Each phase ) For cable between 20 kV Switchgear and Power Transformer
For cables between the 20 KV outgoing feeder and the existing 20 KV distribution

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No sq.mm sq.mm

Hayan Petroleum Company, Appendix D Att-1

35 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item
center

Description

Unit

HPC REQUIRMENTS > 12/20

OFFER VALUE

5 6

Rated voltage Uo/U Current carrying capacity at : a) 30 C ambient air temperature b) 45 C ambient air temperature Rated short-time current a) 1 sec. b) 3 sec. Resistances : a) DC resistance at 20 C (per phase) b) AC resistance at 75 C (per phase) Kind of insulation compound Kind of conductors Weight for each section Other particulars

KV (rms) A A A A

>16000

9 10 12 13

XLPE Cu Kg/m

Guarantee Schedule for 6.6 kV

5.1 Guarantee Schedule for 6.6 kV Metal Enclosure


Item 1 2 3 4 5 6 7 Description Manufacturer Country of Origin ISO 9001 certificate Type Rated voltage Standard specifications Material of cubicles Thickness of sheet Dimensions of the cubicles : a) Width b) Depth c) Height Bus bars : a) Material b) Cross-section per phase c) Minimum clearance between
Hayan Petroleum Company, Appendix D Att-1

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No KV

Should be submitted

AIS 6.6 Steel >2

mm mm mm mm

Copper Sq.mm mm
36 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item phases

Description d) Minimum clearance to earth e) Space between bus-bars supports f) basbar insulation Connectors : a) Material b) Cross-section per phase : - incoming feeder - Outgoing feeder C) Minimum clearance between phases d) Clearance to earth Maximum allowable current density at site worst conditions (for maximum ambient temperature 50C) : a) For busbars b) For connectors : Dynamic short-circuit current Thermal short-circuit current Segregated compartments per cubicle ( 6.6 ) kV equipment The cubicle with well protection against fire risks and contact with live parts Enclosures : a) Phase egregated or three phase b) Material c) Overall diameter d) Wall thickness Rated insulation levels at norm pressure : Power frequency ( 1 ) minute withstand voltage Lighting impulse withstand voltage Degree of protection a) Internal high voltage equipment, gas enclosure b) External enclosure

Unit mm mm

HPC REQUIRMENTS

OFFER VALUE

10

sq.mm mm mm

11

A/sq.mm A/sq.mm

12 13 14 15

KA KA Yes/No Yes/NO
Yes/NO

> 125 > 50

YES

16

17

KV KV

20 60

18

IP IP Yes/NO Yes / No

42 2x Should be provided

19 20

Does the cubicle have plug in or Bolted cable termination Copy of the newest edition for

Hayan Petroleum Company, Appendix D Att-1

37 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item relevant IEC

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

21

Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

5.2 Guarantee Schedule for Circuit Breaker ( 6.6 ) kV


Item 1 2 3 4 5 6 7 8 9 10 Description Manufacturer Country of Origin ISO 9001 certificate Type of circuit breaker Type designation Rated frequency Rated voltages : a) Highest system voltage b) Minimum service voltage Rated normal current at 40C ambient temperature : Rated breaking current capacity a) symmetric b) D.C. component Rated peak making current Rated peak short-circuit current Rated short-time current 11 a) 1 sec. b) 3 sec. 12 13 14 15 16 Rated line-charging breaking current Rated cable - charging breaking current Rated small inductive breaking current Rated breaking current under out-ofphase conditions Restricting voltage : KA (rms) KA (rms) A A A
KA

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No vacuum Hz KV KV A KA (rms) %


KA (peak) KA (peak)

50 7.2 6.6 2000 50 >125 >125

(rms)

> 50

Hayan Petroleum Company, Appendix D Att-1

38 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) rate-of-rise (RRRV) b) peak

Unit
kV / micro sec KV (peak)

HPC REQUIRMENTS

OFFER VALUE

17 18

First-pole-to-clear factor One minute power frequency withstand voltage : a) Phase to earth b) Across open contacts KV (rms) KV (rms) KV (peak) > 20 > 23 > 60

19 20 21 22

Lightning impulse withstand voltage 1,2/50 micro sec Rated operating sequence Capacity to make : High speed three phase auto
extinguishing

23

Minimum time between each successive break/make operation Opening time (until separation of the arcing contacts) a) Without current b) With 100%rated breaking current Maximum total break time (until total arc-extinction) Maximum time interval between opening of the first and the last phase Maximum time interval between opening of the interrupters of one phase (if any) Make time : a) Without current b) With 100% rated making current Maximum total make time (closing initiation to latching of circuit breaker in fully closed position) Maximum time between closing of first and last phase Maximum time interval between closing of interrupters of one phase. Dead time Operating mechanism : a) Type b) Operating voltage c) Rated

sec.

> 0.3

ms ms ms ms ms

24 25 26

27

ms ms ms ms ms ms

28 29 30 31 32

VDC

110

Hayan Petroleum Company, Appendix D Att-1

39 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description d) Range e) Rated power Closing release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power Trip release coil : a) Rated operating voltage b) Minimum operating voltage c) Maximum operating voltage d) Rated power Type test certificate details : a) Testing station/authority b) Certificate number c) Applied standards

Unit % W VDC % % W VDC % % W

HPC REQUIRMENTS ( -20% +10% )

OFFER VALUE

33

110 -20% + 10%

34

110 -30% + 10%

35

5.3 Guarantee Schedule For Voltage Transformers ( 6.6 ) kV


Item 1 2 3 4 5 6 6.1 6.2 7 7.1 7.2 8 9 10 11 Description Manufacturer Country of Origin Type ISO 9001 certificate Rated frequency Highest system voltage Rated insulation level Power frequency withstand voltage Impulse 1,2/50 micro-sec withstand voltage Rated voltages : Rated primary voltage Rated secondary voltage Rated output/accuracy class Two coils Voltage factor Rated ratio Ratio error with rated output and : Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz KV KV KV (peak) kV V

50 7.2 > 20 > 60 6.6/ 3 100/ 3 > 50 / 0.5- 3P

Hayan Petroleum Company, Appendix D Att-1

40 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) 105% normal primary voltage b) 5% normal primary voltage Ratio angle error with rated output and :

Unit % %

HPC REQUIRMENTS

OFFER VALUE

12

a) 105% normal primary voltage b) 5% normal primary voltage

Degree

13 14

Total weight Applied standard specifications

Kg

5.4 Guarantee Schedules for Current Transformers ( 6.6 ) kV


Item 1 2 3 4 5 6 6.1 6.2 7 Description Manufacturer Country of Origin Type ISO 9001 certificate Highest system voltage Insulation material Rated insulation levels : Lightning impulse withstand voltage 1,2/50 micro-sec One minute power frequency withstand voltage Rated primary current : Rating of secondary windings : a) Rated current b) Rated output/accuracy class : - core 1 (measuring) - core 2 (protection) - core 3 (protection) 9 10 11 Overload capacity at 45 C ambient temperature Total weight Applied standard specifications Unit HPC REQUIRMENTS OFFER VALUE

Yes/No KV

7.2

KV (peak) KV (rms) A A VA VA VA % Kg

60 20

1000 - 2000 1 CLX , VK>400V , RCT<4 5P20 , 20VA CL 0.5 , FS=5 , 15VA > 120

Hayan Petroleum Company, Appendix D Att-1

41 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

5.5 Guarantee schedule for lightning arrestor ( Zinc Oxide Type ) ( 6.6 ) kV
Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15.1 15.2 16 17 18 19 20 21 22 23 24 25 Description Manufacturer Country of Origin Type ISO certificate Rated frequency system voltage Rated voltage Power frequency withstand voltage for ( 1 min ) ( empty housing ) Lightning impulse withstand voltage ( 1.2/50 s ) ( empty housing ) Temporary over voltage capability for ( 3 sec ) . Arrester current rating Outdoor type Type of mounting Radio influence voltage measured at rated voltage to earth Maximum peak residual voltage of complete arresters at : Lightning impulse (8/20 s) 10 KA Discharge current withstand strength High current ( 4/10 s ) Low current ( 2000 s ) Energy impulse capability Pressure relief capability for 0.2 sec. Leakage current through the complete arrester at rated system phase voltage Creepage distance Discharge class as per IEC Max safe load canti lever to line Mass of each complete arrester Dimensions Maximum crest of the long time impulse current which the series resistance blokes will withstand Type of surge counter Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz KV KV KV KV KV/S KA

50 5% 7.2 20 5% Acc. to IEC 60

> 10 Yes Pedestal

v KV Peak < 80

KA Peak KA Peak KJ/kV KA A mm N.m Kg

> 0.25

> 600 Class 3

< 180

Hayan Petroleum Company, Appendix D Att-1

42 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

5.6 Guaranteed Schedule for ( 6.6 ) kV Cu Cables


Item 1 2 3 4 4.1 4.2 5 6 Description Manufacturer Country of Origin ISO 9001 certificate Type Cross-section ( Each phase ) For cables between 66 kV Switchgear and Power Transformer
For cables between the 6.6 KV outgoing feeders and the existing 6.6 KV generation center

Uite

HPC REQUIRMENTS

OFFER VALUE

Yes/No XLPE sq.mm sq.mm kV (rms) A A A A Ohm Ohm XLPE Cu Kg/m >50000

Rated voltage Uo/U Current carrying capacity at : a) 30 C ambient air temperature b) 45 C ambient air temperature Rated short-time current a) 1 sec. b) 3 sec. Resistances : a) DC resistance at 20 C (per phase) b) AC resistance at 75 C (per phase) Kind of insulation compound Kind of conductors Weight for each section Other particulars

8 9 10 11 12

Hayan Petroleum Company, Appendix D Att-1

43 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Guarantee Schedule For Protection, Control And Metering Equipment

6.1 Guarantee Schedule For Transformer Numerical Differential Protection


Item 1 2 3 4 5 6 7 Description Manufacturer Country of Origin Type ISO 9001 certificate Numerical type relay. Rated current Relay burden Setting range -Setting of magnetizing current filtering. - availability of the second harmonic current content setting is preferred . Amplitude and phase matching is to be integrated in the relay , even that the rated currents of winding inputs are different ( for eg 1A for H.V and 5A for L.V winding ). Does the offered relay include the function of self monitoring . Local signal data: a) Relay in operation. b) internal relay fault. c) faulted phase (R,S,T) Power supply consumption Min.sensitivity to earth faults Min.sensivity to phase fault Continuous thermal rating : a) Continuous b) For 1 sec. Operating times; including tripping relay: a) At 3 times minimum operating current b) At 10 times min. operating current Tripping contact rating : a) Number Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Yes/No A VA xIn xIn Yes

Yes

Adjustment ( 0.2 In 0.5 ) with precies steps .

Yes/No

10

Yes/No Yes/No Yes/No Yes/No W xIn xIn xIn xIn xIn

Yes Yes Yes Yes

11

12 13 14 15

16

ms ms No.

17

Hayan Petroleum Company, Appendix D Att-1

44 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description b) Making current c) Continuous current Operational temperature range 1 minute power frequency withstand voltage Impulse withstand voltage Degree of protection Period of proven reliability. Number of years of guaranteed parts manufacturing and supports. Reference catalogue Facility of measuring the input and differential current is required ( front test sockets or display ) . Over current function on high or low voltage sides . Does the relay include an integral fault recorder a) Fault recording memory capacity b) number of analogue channels

Unit A A C KV KV IP Years Years

HPC REQUIRMENTS

OFFER VALUE

18 19 20 21 22 23 24 25 26

( -5, +55 ) 2 5kV peak value 1.2/50s, 0.5J 50

Yes /No Yes /No Yes/No integrated

27

c) number of digital channels d) pre fault time e) fault time f) software identification GBS system inputs for real time synchronizing existance

28 29

Does the relay include a selfdiagnostic feature. Does the relay include an integral event recorder. Does the relay include facilities for remote communication, preferable relevant IEC 870 Does the relay include two R.E.F

Yes/No Yes/No

Yes

yes

30

Yes/No

yes

31

function for H V and L.V side of power transformer or separated

Yes/No

Preferably integrated

Hayan Petroleum Company, Appendix D Att-1

45 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 32 33 33.1

Description Supply voltage and tolerance . Other data related to numerical relays : Sample rate of measuring element Method of communicating the relay: a) manually (M.M.C unit) b) by PC c) port for central control system.

Unit

HPC REQUIRMENTS

OFFER VALUE

HZ

Yes/No

33.2

33.3

d) Local communication on front panel (Front panel foil keypad, LCD and USB for PC software support ) Remote: Back system interfaces (system interface FO1 (SCADA system) and service interface FO2) - Supported communication protocol: IEC 60870-5-103 or IEC 61850 Number of load parameters that can be read out at the front of the disolay of distance protection (to be detailed) Number of fault data that can be read out at the front display ( to be detailed) Number of faults that can be stored and their total time ( detail are Required) Over load function included or not ? HV & LV over current function Included or not? hardware properties: a) NO of optically isolated inputs b) NO of output relays+ watchdog output relay c) NO of fixed function LEDs and programmable LEDs e) NO of setting groups f) NO of front EIA(RS) 232 communication port (choice of protocol) g) NO of Rear EIA (RS)485 communication port (choice of protocol) h) Predefined binary inputs (52a, Yes/No Yes/No

33.4

33.5 33.6 33.7 34

Hayan Petroleum Company, Appendix D Att-1

46 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) i) time synchronization

Unit

HPC REQUIRMENTS

OFFER VALUE

6.2 Guarantee Schedule For Numerical Over Current Earth Fault Protection
66kV ( high set And low set overcurrent )
Item 1 2 3 4 5 6 7-1 Description Manufacturer Country of Origin ISO 9001 certificate Numerical Rated current Rated frequency Setting range for pick up value Reset ratio: Reset time: a) for inverse time element . b) for definite time elements. c) for high set instantaneous element Accuracy of current element (s) Accuracy of time element (s) Current reset ratio Drop - out time Consumption of measuring inputs Overload rating : a) continuously b) for 1 sec. Setting range of the current (ranges and steps) : a) for inverse time O/C elements. b) for definite time overcurrent c) for high set instantaneous O/C elements. Setting range of the time (ranges and
47 - 99

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No A Hz A % % ms ms ms % % % m.s VA xIn xIn 2 40 yes 1 50 Adjustable


( <0.5, >40 )In

7-2

8 9 10 11 12 13

14

xIn xIn xIn

15

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item steps)

Description a) for inverse time multiplier factor . b) for definite time setting range. c) operating time of high set instantaneous O/C relay at 5 IN Contacts number : a) tripping b) alarming at starting Tripping contact rating : a) making current b) continuous current c) breaking capacity Consumption on auxiliary supply Degree of protection Local signaling : a) starting per phase b) tripping per phase Operational temperature range a) minimum temperature b) maximum temperature Test voltages : a) impulse withstand voltage 1.2/50 u sec b) power frequency withstand voltage Reference catalogue Does the relay include an integral fault recorder a) fault recording memory capacity b) number of analogue channels

Unit Sec Sec ms No. No. A A A W IP Yes/No Yes/No


o o

HPC REQUIRMENTS

OFFER VALUE

16 17

18 19 20

> 51

21

C C

-5 +55 5kV peak value 1.2/50s, 0.5J >2

22 23

KV peak KV rms No. Yes/No

24

c) number of digital channels d) pre fault time e) fault time f) software identification g) GBS system inputs for real time synchronizing existance

25

Does the relay include a self-

Yes/No
48 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description monitoring feature .

Unit

HPC REQUIRMENTS

OFFER VALUE

26

Does the relay include an integral event recorder. Does the relay include facilities for communication with DCS equipment and what is the protocol .

Yes/No

27

Local communication on front panel (Front panel foil keypad, LCD and USB for PC software support ) Remote: Back system interfaces (system interface FO1 (SCADA system) and service interface FO2) - Supported communication protocol: IEC 60870-5-103 or IEC 61850 How maney stage dose this relay has for O/C (I>,I>>,I>>>) How maney stage dose this relay has E/F (I E >,IE>>,IE>>>). Does the relay have inverse characteristic for over current and earth fault :

Yes/No

Yes

28 29

30

Yes/ No

31 32 33

Does the relay have separate contact for self-monitoring function Does the relay have instantaneous function for EF and OC Supply voltage and tolerance Type test certificate details :

Yes/No Yes/No

34

a) Testing station b) Certificate numbers c) Applied standard specifications

35

hardware properties: a) No. of optically isolated inputs b) No. of output relays+ watchdog output relay

Hayan Petroleum Company, Appendix D Att-1

49 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description c) No. of fixed function LEDs and programmable LEDs d) No. of setting groups e) No. of front EIA(RS) 232 communication port (choice of protocol) f) No. of Rear EIA (RS)485 communication port (choice of protocol) g) h) Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) h) time synchronization

Unit

HPC REQUIRMENTS

OFFER VALUE

6.3 Guarantee For Numerical Over Current Earth Fault Protection for 20 kV
and for 6.6 kv ( high set And low set overcurrent )
Item Description Unit HPC REQUIRMENTS OFFER VALUE

1 2 3 4 5 6 7-1

Manufacturer Country of Origin ISO 9001 certificate Numerical type Rated current Rated frequency Setting range for pick up value Reset ratio: Reset time: a) for inverse time element . b) for definite time elements. c) for high set instantaneous element Accuracy of current element (s) Accuracy of time element (s) Current reset ratio Drop - out time Consumption of measuring inputs

Yes/No Yes/No A Hz A % ms ms ms % % % msec VA

yes 1 50 Adjustable ( <0.5, >40 )In >95%

7-2

8 9 10 11 12

Hayan Petroleum Company, Appendix D Att-1

50 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

13

14

15

16

17

18 19 20

21

22 23 24 25 26

Overload rating : a) continuously b) for 1 sec. Setting range of the current (ranges and steps) a) for inverse time O/C elements. b) For definite time overcurrent c) For high set instantaneous O/C elements. Setting range of the time (ranges and steps)O/C relay at 5 IN . a) for inverse time multiplier factor . b) for definite time setting range. c) operating time of high set instantaneous Contacts number : a) tripping b) alarming at starting Tripping contact rating : a) making current b) continuous current c) breaking capacity Degree of protection Consumption on auxiliary supply Local signaling : a) starting per phase b) tripping per phase Operational temperature range a) minimum temperature b) maximum temperature Test voltages : a) impulse withstand voltage 1.2/50 u sec b) power frequency withstand voltage Reference catalogue How money stage dose this relay has for O/C (I>,I>>,I>>>) How money stage dose this relay has E/F (I E >,IE>>,IE>>>). Does the relay include an integral fault

x In x In

x In x In x In

Sec Sec ms No. No. A A A IP W Yes/No Yes/No Co


-5 +55 5kV peak value 1.2/50s, 0.5J >2

> 50

KV peak KV rms No.

Yes/No

Hayan Petroleum Company, Appendix D Att-1

51 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

recorder 27 28 Does the relay include a selfmonitoring feature . Does the relay include an integral event recorder. Does the relay include facilities for communication with DCS equipment and what is the protocol . 29 Local communication on front panel (Front panel foil keypad, LCD and USB for PC software support ) Remote: Back system interfaces (system interface FO1 (SCADA system) and service interface FO2) - Supported communication protocol: IEC 60870-5-103 or IEC 61850 Does the relay have inverse characteristic for over current and earth fault : Does the relay have separate contact for self-monitoring function Does the relay have instantaneous function for EF and OC Supply voltage and tolerance Type test certificate details : 34 a) Testing station
b) Certificate numbers c) Applied standard specifications 35 hardware properties: a) No. of optically isolated inputs b) No. of output relays+ watchdog output relay c) No. of fixed function LEDs and programmable LEDs d) No. of setting groups e) No. of front EIA(RS) 232 communication port (choice of
Hayan Petroleum Company, Appendix D Att-1

Yes/No Yes/No

Yes/No

Yes

30

Yes/No

31 32 33

Yes/No Yes/No

52 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item protocol)

Description f) N0. of Rear EIA (RS)485 communication port (choice of protocol

Unit

HPC REQUIRMENTS

OFFER VALUE

g) Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) h) time synchronization

6.4 Guarantee For one phase Numerical sensitive Earth Fault Protection
20 kV and 6.6 kv and 66 Kv neutral points ( high set And low set overcurrent )
Item 1 2 3 4 5 6 7-1 Description Manufacturer Country of Origin ISO 9001 certificate Numerical type Rated current Rated frequency Setting range for pick up value Reset ratio: Reset time: a) for inverse time element . b) for definite time elements. c) for high set instantaneous element
Accuracy of current element (s) Accuracy of time element (s) Current reset ratio

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No Yes/No A Hz A % ms ms ms
% % %

yes 1 50 Adjustable
( <0.5, >40 )In

>95%

7-2

8 9 10

11 12 13 14

Drop - out time Consumption of measuring inputs Overload rating : a) continuously b) for 1 sec. Setting range of the current (ranges and steps)

msec VA x In x In

Hayan Petroleum Company, Appendix D Att-1

53 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) for inverse time O/C elements. b) for definite time overcurrent c) for high set instantaneous O/C elements. Setting range of the time (ranges and steps)O/C relay at 5 IN . a) for inverse time multiplier factor . b) for definite time setting range. c) operating time of high set instantaneous Contacts number : a) tripping b) alarming at starting Tripping contact rating : a) making current b) continuous current c) breaking capacity Degree of protection Consumption on auxiliary supply Local signaling : a) starting per phase b) tripping per phase Operational temperature range a) minimum temperature b) maximum temperature Test voltages : a) impulse withstand voltage 1.2/50 u sec b) power frequency withstand voltage Reference catalogue How maney stage dose this relay has for O/C (I>,I>>,I>>>) How maney stage dose this relay has E/F (I E >,IE>>,IE>>>). Does the relay include an integral fault recorder Does the relay include a selfmonitoring feature .

Unit x In x In x In

HPC REQUIRMENTS

OFFER VALUE

15

Sec Sec ms No. No. A A A IP W Yes/No Yes/No Co -5 +55 KV peak KV rms No. 5kV peak value 1.2/50s, 0.5J >2 > 50

16

17

18 19 20

21

22 23 24 25 26 27

Yes/No Yes/No

Hayan Petroleum Company, Appendix D Att-1

54 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 28

Description Does the relay include an integral event recorder. Does the relay include facilities for communication with DCS equipment and what is the protocol .

Unit Yes/No

HPC REQUIRMENTS

OFFER VALUE

29

Local communication on front panel (Front panel foil keypad, LCD and USB for PC software support ) Remote: Back system interfaces (system interface FO1 (SCADA system) and service interface FO2) - Supported communication protocol: IEC 60870-5-103 or IEC 61850
Does the relay have inverse characteristic for over current and earth fault : Does the relay have separate contact for self-monitoring function Does the relay have instantaneous function for EF and OC

Yes/No

Yes

30

Yes/No

31 32

Yes/No Yes/No

33

Supply voltage and tolerance


hardware properties: a) No. of optically isolated inputs b) No. of output relays+ watchdog output relay c) No. of fixed function LEDs and programmable LEDs d) No. of setting groups

34

e) No. of front EIA(RS) 232 communication port (choice of protocol) f) No. of Rear EIA (RS)485 communication port (choice of protocol)

g) Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) h) time synchronization 35 Type test certificate details :
55 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) Testing station b) Certificate numbers c) Applied standard specifications

Unit

HPC REQUIRMENTS

OFFER VALUE

6.5 Guarantee Schedule For Directional Over current and directional earth
fault Protection 66 kV
Item
1 2 3 4 5 6

Description Manufacturer Country of Origin Type Rated current Rated voltage Thermal rating of current circuit a) continuos . b) for 1 sec. Thermal rating of voltage circuit Consumtion a) in current circuit b) in voltage circuit c) in aux supply circuit Setting range of residual pick up power or current Reset ratio Accuracy of pick up value Response time for meas. element Reset time for meas. element Inverse time or definite time or both characteristic Accuracy of current element (s) Accuracy of time element (s) Current reset ratio Auxiliary voltage ( Un ) Range Tripping contact

Unit

HPC REQUIRMENTS

OFFER VALUE

A V xIn xIn xIn VA VA W

1 100 2 40

8 9 10 11 12 13 14 15 16 17 18 19

% % m sec. m sec.

% % % V % 110 +10 -20

Hayan Petroleum Company, Appendix D Att-1

56 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) max. service voltage b) making current c) continuos current Local signal: a) starting b) tripping Signaling contact for : a) starting b) tripping Operational temperature range Test voltages : a ) Impulse withstand voltage b) Power frequency withstand voltage Weight
Does the relay include an integral fault recorder a) fault recording memory capacity b) number of analogue channels c) number of digital channels

Unit
V.D.C. A/Sec. A Yes/No Yes/No Yes/No Yes/No

HPC REQUIRMENTS
110 10/1 2

OFFER VALUE

20

21 22

23

KV KV Kg Yes/No

5kV peak value 1.2/50s, 0.5J 2

24

25 d) pre fault time e) fault time f) software identification g) GBS system inputs for real time synchronizing existance 26

a) hardware properties: b) No. of optically isolated inputs c) No. of output relays+ watchdog output relay d) No. of fixed function LEDs and programmable LEDs e) No. of setting groups f) No. of front EIA(RS) 232 communication port (choice of protocol) g) No. of Rear EIA (RS)485 communication port (choice of protocol)
57 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description h) Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) i) time synchronization Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit

HPC REQUIRMENTS

OFFER VALUE

27

6.6
Item 1 2 3 4 5 6 7 8

Guarantee Schedule for Numerical Voltage Regulating Relay


Description Unit HPC REQUIRMENTS OFFER VALUE

10 11 12 13 14 15 16 17

Manufacturer Country of Origin Type ISO 9001 certificate Principle of operation Rated value of circuit : a) current b) voltage Zone of insensibility, % of Un Time setting range Duration of the control signal Output contacts rating : a) making current b) continuous current c) breaking current Consumption Degree of protection Mass Dimensions Circuit diagram, terminals Is this relay equipped with over current blocking feature . Is this relay equipped with under voltage blocking feature . Is this relay equipped with impedance compensation feature for O.H.L

Yes/No yes A v % sec. sec. A A A VA IP Kg mm Yes/No Yes/No Yes/No

Should be submitted

Numerical 1

0-120

> 50

Hayan Petroleum Company, Appendix D Att-1

58 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description

Unit

HPC REQUIRMENTS

OFFER VALUE

18

19 20

Does the relay have facility for parallel operating : a) Master and slave b) Circulating current c) Negative reactance Does the relay have self monitoring feature Does the relay have separate contact for self monitoring function hardware properties: d) No. of optically isolated inputs e) No. of output relays+ watchdog output relay f) No. of fixed function LEDs and programmable LEDs g) No. of setting groups h) No. of front EIA(RS) 232 communication port (choice of protocol) i) No. of Rear EIA (RS)485 communication port (choice of protocol) j) Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB TRIP, CB CLOSE, IRF) k) time synchronization Does the relay have facility for communication with DCS equipment and what is the protocol

Yes/No Yes/No Yes/No Yes/No Yes/No

Yes/No

Yes

6.7 Guarantee Schedule For Numerical Line Distance Protection


Item 1 2 3 4 Description Manufacturer Country of Origin ISO 9001 certificate Type reference Principle of operation Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Yes/No Numerical

Hayan Petroleum Company, Appendix D Att-1

59 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 5 5.1 5.2 5.3 5.4 5.5 5.6

Description Input characteristics Rated voltage Un Rated current In Minimum operating current Rated frequency Overload rating : a) Continuously b) For 1 sec. Admissible sustained voltage Internal consumption : a) Current circuit, max. b) Voltage circuit, max. c) Supply circuit, max. d) Auxiliary inputs, max. Measuring Data Number of directional and final steps Operating current : a) Phase current b) Residual current Setting range for the line phase angle in steps of Setting range of the residual compensation factor Ko = xo-x1 in steps of 3x1 Does the relay have separate phase indication or starting element for initiation of the measuring loops . - in case of starting element. a) No. of impedance starting element b) reset ratio of impedance starting element . c) setting range of impedance starting elements : - in forwad dection . - in reverse direction How many processor or micro controller is considered in the relay. Measuring elements : measuring principle (Z,X or X and R) - measuring characteristic (circle, lens or quadrilateral a) Zone 1 setting range

Unit V A x In Hz x In x In x Un VA/ph VA/ph W mA

HPC REQUIRMENTS 100 1 50

OFFER VALUE

5.7

6 6.1 6.2 6.3 6.4

3F + 1R x In x In

Yes/No

6.5

6.6 7 7.1 7.2

ohm/ ph

Hayan Petroleum Company, Appendix D Att-1

60 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description b) Zone 2 setting range c) Zone 3 setting range d) Measuring accuracy e) Directional sensitivity Tripping time : a) min. tripping time b) max. reset time Step timing setting ranges : a) 2nd step b) 3rd step c) 4th step Accuracy of the time step relay in % of the full scale value (respective fault) Temperature error In the range of -5C to +50C (referred to 25C and full scale value) Output Characteristics Tripping contacts ( for each function ) : a) Making current b) Continuous current c) Breaking capacity d) Number and type of contacts Indication contacts : for each function a) Making current b) Continuous current c) Breaking capacity d) Nos. and type of contacts Does the relay have separate contact for self-monitoring function

Unit ohm/ ph ohm/ ph % V msec msec sec. sec. sec. %

HPC REQUIRMENTS

OFFER VALUE

7.3 7.4

7.5 7.6 7.7 7.8 8

8.1

A A A nos. A A VA Nos Yes/No

8.2

8.3

HF output contacts a) Operating voltage b) Making current c) Breaking capacity Local Signalling : a) Starting on phases R, S, T b) E/F c) Tripping of phases R, S, T VDC A VA Yes/No Yes/No Yes/No
61 - 99

110 ( +10%, -30%)

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item d) e)

Description Tripping time T2,T3, T4, T5 Tripping by signal received from other end f) Protection in operation g) Internal circuit monitor operated h) Others Blocking Unit For Power Swings Type reference Is the operation independent on the starting elements or not : Setting range Does the relay have over-riding feature for power swing blocking when simultaneous fault and power swing happens General Data Operational temperature range Guarantee data maintained Test voltage : a) Impulse withstand voltage 1,2/50s b) Power frequency withstand voltage, 1min Weight Testing and Monitoring Facilities : a) Built in test feature b) Built in self monitoring c) Built in self testing d) Means for rapid functional test Method of ensuring operation for close-up three phase faults Accuracy of impedance settings for: system impedance ratios 30 system impedance ratios 30-60 Operating Times In Accordance With Table :

Unit Yes/No Yes/No Yes/No Yes/No

HPC REQUIRMENTS

OFFER VALUE

10

Yes/No

Yes/No

11 11.1 11.2

( -5 , + 55 )

11.3

KV KV Kg yes/No yes/No yes/No yes/No

5kV peak value 1.2/50s, 0.5J

11.4

12

Yes Yes Yes Yes

13

14

15.1

15.2

system impedance ratio = 10 system impedance ratio = 30 system impedance ratio = 60 Tripping Schemes Included:

ms ms ms

Hayan Petroleum Company, Appendix D Att-1

62 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item a) b) c) d) e) f) 16 17

Description acceleration permissive under rich permissive over rich blocking transient cording back up overcurrent protection

Unit Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No IP

HPC REQUIRMENTS

OFFER VALUE

Is shaping for load encroachment provided Degree of protection VT supervision: a) Is VT supervision provided

> 50

Yes/No Yes/No Yes/No Yes/No

Yes Yes Yes

18

b) VT supervision blocked during single pole autoreclose c) Is VT supervision blocked during line deenergization d) Dos the operating time of fuse failure is less than Zone 1 operating time .

19 20

Is a switch-onto-fault feature provided Is integral or separate directional earth fault protection provided a) residual current or power setting rang . b) reset ratio c) accuracy of pick up value d) response time for measuring element e) reset time for measuring element f) inverse time characteristics g) accuracy of time element h) tele-protection tripping scheme that the DEF is applied for .

Yes/No Yes/No

Yes Yes

Hayan Petroleum Company, Appendix D Att-1

63 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description I ) does the DEF function include time delay as backup feature in case of tele protection scheme failure?

Unit

HPC REQUIRMENTS

OFFER VALUE

21

Does DEF operate in permissive overreach transfer trip mode Is over and under voltage protection function inciuded in distance protection Does the relay include an integral fault locator. a) is fualt location affected by : arc resistance in case of phase to earth fault?

Yes/No

22

Yes/No

Yes/No

Yes

23

high resistance earth faults with remot end in feed. ? Load current ? b) distance to fault is displayed on the front panel in the form of Kilometers, percent of line length or booth : c) fault location measuring error. Does the relay include an integral fault recorder a) fault recording memory capacity b) number of analogue channels Yes/No Yes

24

c) number of digital channels d) pre fault time e) fault time f) software identification g) GBS system inputs for real time synchronizing existance.

25

Does the relay include a self-

Yes/No

Hayan Petroleum Company, Appendix D Att-1

64 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description diagnostic feature?.

Unit

HPC REQUIRMENTS

OFFER VALUE

26

Does the relay include an integral event recorder?. Does the relay include facilities for remote communication with DCS?

Yes/No Yes/No

yes yes

27

and what is the protocol? (preferable IEC 870 ) How many processor or micro controller is considered in the relay? Number of setting groups that can be set independently . Number of fualt data that can be read out at the front display of distance protection ( to be secified ). Number of fualt data that can be stored in distance protection and the total time of them ( to be secified ). Number Al gorithems used for discriminating the faults( to be secified ). . Method of communicating the relay BY both methods :

28

30

a) Manually (M.M.C) unit b) By P.C c) port for central control system

Yes/No Yes/No Yes/No

Yes yes yes

31

hardware properties: - No. of optically isolated inputs - No. of output relays+ watchdog output relay - No. of fixed function LEDs and programmable LEDs - No. of setting groups - No. of front EIA(RS) 232 communication port (choice of

Hayan Petroleum Company, Appendix D Att-1

65 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description protocol) No. of Rear EIA (RS)485 mmunication port (choice of protocol Predefined binary inputs (52a, 52b, IRIG) Programmable binary inputs Predefined relay outputs (CB RIP, CB CLOSE, IRF) time synchronization Type test certificate details :

Unit

HPC REQUIRMENTS

OFFER VALUE

32

a) Testing station b) Certificate numbers c) Applied standard specifications

6.8 Guarantee Schedule For Check Synchronising


Item 1 2 3 4 5 6 7 Description Manufacturer Country of Origin Type of reference Descriptive leaflet reference number Range of phase angle settings Range of voltage lockout setting Range of time setting Range of slip frequency settings Unit HPC REQUIRMENTS OFFER VALUE

Deg S Hz/s

6.9 Instruments(Mesuring center )


Item 1 2 3 4 Description Manufacturer Country of Origin Type ISO 9001 certificate Rated value : a) Frequency Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz 50

Hayan Petroleum Company, Appendix D Att-1

66 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description b) Voltage c) Current Overload capacity ( continuous ) Measuring accuracy Temperature range Test voltage : a) Impulse b) Power frequency ( 1 min. ) Power consumption : a) Voltage circuit b) Current circuit Dimensions With remote communication facilities with SCADA level and switchgear level . Does the M.C have tariff ( at least 3 tarriff ) . Does the M.C have output pulse . The measuring center should measure the following quantities (at least) : a) current , three phase b) voltage , three phase c) active power } ( import and export ) d) reactive power} ( import and export ) e) active energy f) reactive energy g) power factor h) power quality ( up to 15 th harmonic voltage and current input i) Load profile Number of quantities which can be measured Accuracy for active energy measuring

Unit V A % Yes/No C KV KV VA VA mm Yes/No Yes/No Yes/No

HPC REQUIRMENTS 100/ 3 1 cl. 0.5 ( -5, +50 ) 5 2

OFFER VALUE

5 6 7 8 9

10 11 12 13

Yes Yes Yes

Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No No. Yes/No

Yes Yes Yes Yes Yes Yes Yes Yes Yes > 10 0.5

14

15 16

6.10 Guarantee Schedule for Tripping and control relay )


67 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 1 2 3

Description Manufacturer name Country of Origin Type ISO 9001 certificate Rated value : a) Frequency b) Voltage c) Current Burdens : a) Burden at higher rated voltage b) Minimum operating current Operate time: Operate time (Standard flag ) Operate time (Following flag ) Reset time Operation indicator Contacts: Contacts ratings Make and carry for 3 seconds Make and carry continuously Current breaking Number of contact Overload capacity ( continuous ) Temperature range Test voltage : a) Impulse b) Power frequency ( 1 min. ) Power consumption : a) Voltage circuit b) Current circuit Self reset weight

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No Hz V A W mA msec. msec msec < 20 50 110

6 7 8

15 A No. % C KV KV VA VA Yes/No kg 5 4 ( -5, +50 ) 5 2

10 11 12

13 14 15

Hayan Petroleum Company, Appendix D Att-1

68 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

6.11 Guarantee Schedule for lock out relay )


Item 1 2 3 Description Manufacturer Country of Origin Type ISO 9001 certificate Rated value : a) Frequency b) Voltage c) Current Burdens : a) Burden at higher rated voltage b) Minimum operating current Operate time Operate time (Standard flag ) Operate time (Following flag ) Reset time Operation indicator Contacts: Contacts ratings Make and carry for 3 seconds Make and carry continuously Current breaking Number of contact Overload capacity ( continuous ) Temperature range Test voltage : a) Impulse b) Power frequency ( 1 min. ) Power consumption : a) Voltage circuit b) Current circuit Electrical/ hand reset weight Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz V A W mA msec. msec msec <30 50 110

6 7 8

10 15 A No. % C KV KV VA VA Yes/No kg 3 4 ( -5, +50 ) 5 2

10 11 12

13 14 15

Hayan Petroleum Company, Appendix D Att-1

69 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

6.12 Guarantee Schedule for trip circuit supervision TCS relay )


Item 1 2 3 Description Manufacturer Country of Origin Type ISO 9001 certificate Rated value : a) Frequency b) Voltage c) Current Burdens : a) Burden at higher rated voltage b) Minimum operating current Operate time Operate time (Standard flag ) Operate time (Following flag ) Reset time Operation indicator Contacts: Contacts ratings Make and carry for 3 seconds Make and carry continuously Overload capacity ( continuous ) Temperature range Test voltage : a) Impulse b) Power frequency ( 1 min. ) Power consumption : a) Voltage circuit b) Current circuit weight Unit HPC REQUIRMENTS OFFER VALUE

Yes/No Hz V A W mA msec. msec msec 50 110

6 7 8

10 15 % C KV KV VA VA kg ( -5, +50 ) 5 2

10 11 12

13 14

Hayan Petroleum Company, Appendix D Att-1

70 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

6.13 Guarantee Schedule for Numerical Computer Control, Measuring ,


Metering and Monitoring SYSTEM.
Item 1 2 Description Manufacturer`s name\country Country of Origin ISO 9001/2000 certificate The operator workstation will be considered as substation control point which provide complete monitoring and control facility for whole substation . CONTROL DESCRIBTION : DCS system should be suitable for the automatded real time monitoring, control , measuring ,Data ,logging and fault recording , and fault analysis. DCS system should be able for peer to peer communication The DCS system should be capable of future extenssion for the Hardware by adding I/O modules if needed.Three levels for control system should be supplied ( coventional , local control units, and computr) All hardware components of DCS system should be comply with the EMC tests according to the IEC 25522-4 standard . Each substation should have individual systems , one for the control and the other for protection . DCS system should be able to Trans/ Receive information of all substation level with accessabilities To/ From remote control center by mean of standard telecomunication protocols ( i.e IEC 870-5-101 ) which shall be finalized according to the client remote center specification and request for trans\ receive equipment and protocole converter ( if needed) are under scope of this work . -Standard communication protocol has to be used for direct communication between SCADA and DCS Computers : the substation should contain / 3 / computers and one laptop Unit HPC REQUIRMENTS OFFER VALUE

Yes/No

Yes/No

Yes

4 4.1 4.2

Complete digital control system according to technical Specification supplied with all equipments

Yes/No Yes/No

Yes Yes

4.3

Yes/No

Yes

4.4 4.5

Yes/No

Yes

Yes/No

Yes

4.6

Yes/No

Yes

4.7

Yes/No

Yes

Hayan Petroleum Company, Appendix D Att-1

71 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description Two computers : the first is called hot computer , the second is called the stand by computer. These two computers have fucilities for monitoring and control the whole substation. The third computer shall be dedicated to the following tasks: a- DCS configuration b- Programme development c- Alarms threshold modification d- Faults/ alarm inhibitation e- Counters, registers , and time delays modification f- Chart and logs view , data storage. g- Data Base ,programme,and configuration parameters back up . h- DCS date/ time adjustment. ( These computers and laptop should be presented from first class companies like: IBM, COMPAQ,DELL, HP ,..etc.) all interlockings should be built up in DCS : a - Logical by control system . b- Wiring by conventional way GPS system should be considered , all the system should be time synchronised via the station computer. -Communications between GPS and SCADA diagrams shall be available. One set of converter to supply DCS cubicle and control desk should be considered . The input power for converter from main Batteries(110 VDC) the output power supply for (computers,printer .) one laser jet color printer for printing of reports, logs and alarm

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No

Yes

Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No

Yes Yes Yes Yes Yes Yes Yes Yes

4.8

4.9

4.10

4.11

4.12

A thorough and complete one page DCS architecture plan should be submitted by the bidders showing the control and protection system and the LAN NET taking into considration Hayan Petroleumthe following D Att-1 to Company, Appendix :

72 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 1234-

Description high speed reliability . less complicated design . easy maitenance . security .

Unit

HPC REQUIRMENTS

OFFER VALUE

5 - less series connection . 6 - DCS should be manufactured by first class companys ( hard ware parts ). 7 - protection against electro magnetic field affect should be take into considration when 8 - desiegn the DCS . 9 - description should be attached with the offer for the DCS and protection .brief SOFT WARE CHARACTARISTICS Should be dedicated to the following tasks: 1 - Capacity and architecture of data base and communication media should be adequate and capable together . Transfer and record all measuring , alarms events and disturbance data of any during normal or abnormal conditions. Measurings alarms and events data should be transmit in real time. 2- The programme should work on modern data base . 3- The data base design documents should be offered by the bidders as follow: a- Entity relation diagram b- Description of the data base structure ( schedules , annexes , main key , denotes , conditions,) . c- Fault location ,explanation for fault and alarm maseges ,giving soluotions . Bidders should provide soft ware package (CD MASTER ,USER GUID BOOK ).

4.13

4.14

Hayan Petroleum Company, Appendix D Att-1

73 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

-The bidder should specify details of all functional requirements in the offer as below

Item 1

System function Mode of operation

Sub function Monitoring control Dcs engineering System manager The format of Display curser Page Single line diagram display Select of display Menu bar Alarm icon System clock and date Import/export power Import / export energy Event processing Alarm processing Analoge measurment handling Controls Logging Plant database Manaual updating of station informatiom Dcs equipment status display Plant numbering Fault incident records Operator defined format Transfer of control facilities Transformer top position indication For completing data base Format modification Configration tools Safety tagging Interlocking Synchrocheack Automatic sequence control ( Raise Lower ) Automatic tap changer control Communication with protection relays and fault recorders Load shedding restoration Design System design requirem Technology ents System capacity System configration Integrated database Design precautions

offer description

VDU Display

3 4 5 6

System window area Use of colour Power flow convention Man Machine Interface ( MMI ) functions

7 8

Engineering facilities Substation facilities

DCS hardware and software

Hayan Petroleum Company, Appendix D Att-1

74 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

System function Dcs master system

Sub function Station computer Work station Operator work station Engineering facility Labtop work station Dial in fault analysis facilitys Printers Master clock Furniture Load area network ( Lan ) Message structure and security Communication with load dispatch center Communication circuits Modems

offer description

Commun ication with bay unit and load dispatch center 10 11 12 BCU.S System software DCS system facilities

13

Performance and availability

14

Power supply equipment

15 16 17 18

Interfacing to substation plant equipment Inspection and test Drawings Spare & test equipment

Operating system and DCS software Communication software DCS data SCADA data ( type, revision.) SCADA shall be Compatible with control system and open software is preferred. SCADA privilege shall be available to make calibrations , configuration . System performance Time for data question and man machine interface Time tagging DCS system Capacity Availability Converter Static switch by pass Main bypass transformer Inverter distribution Housing AC main power transformer transient protction Substation plant / scsinterface Interposing relay Transdueer Factory acceptance test Site acceptance test

Hayan Petroleum Company, Appendix D Att-1

75 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

6.14 Guarantee Schedule for General Requirements for Numerical Control and
Protection System
Item Description * Communications port spec ( for digital numerical relays)
1- Language 2- Transmission mode 3- Signal levels 4- Message format

Unit

HPC REQUIRMENTS

OFFER VALUE

5- Data rate 6- Connection 7- Cable type 8- Cable length 9- Connector 10- Isolation

Specification of offer should be confirmed with HPC requirement and material by offer

* High Voltage Withstand 2


Dielectric withstand IEC 255-5 : 1977 IEC 255-5 : 1977 High voltage impulse Insulation resistance IEC 255-5 : 1977

KV KV KOhm

* Electrical Environment
1- High frequency disterbance IEC 255-22 -1 : 1988 Class III 2- Fast transient disterbanc IEC 801-41988 Level 3 IEC 255-22-4:1992 Class III IEC 255-22-2 : 1989 Class III IEC 801-2 : 1991 Level 2 IEC 255-11 : 1979 5- AC ripple on DC supply IEC 255-11 : 1979 EMC compliance 89/336/EEC EN50082-2 : 1995- EN50081-2 : 1994

3- Electrostatic discharge

4- DC supply interruptions

Hayan Petroleum Company, Appendix D Att-1

76 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description
6- Product safety EN61010-1 : 1993/A2 : 1995 EN60950 : 1992/A3 : 19

Unit

HPC REQUIRMENTS

OFFER VALUE

Atmospheric Environment 1- Temperature

IEC 68-2-2 : 1974 IEC 68-2-1 : 1990 IEC 255-6 : 1988

2- Humidity IEC 68-2-3 : 1969 nclosure protection-IEC529:1989

Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications The above items should be filled and signed for each protection or protections unit

GUARANTEE SCHEDULES FOR AUXILIARY EQUIPMENT

7.1 Guarantee Schedule for A.C Cubicle


Item 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Description Cubicle Manufacturer Country of Origin ISO certificate Type Degree of protection Rated current of busbar Short-time current to busbar and connections Material and cross-section of busbar Insulation of busbar Unit HPC REQUIRMENTS OFFER VALUE

Yes/No IP A KA/S mm2 KV copper 1


77 - 99

4 1

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2 2.1 2.2 2.3 2.4 2.5 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 4.1 4.2

Description Circuit Breaker Manufacturer Country of Origin ISO certificate Rated current for main C.B Rated voltage Short-time current Automatic Switch-Over Device Manufacturer Country of Origin ISO certificate Type Rated current Rated voltage Reclosing time Short-time current Contactors Manufacturer Country of Origin ISO certificate

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No A V KA/S

Yes/No A V sec. KA/S

Yes/No

7.2 Guarantee Schedule for Diesel Generating Set


Item 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 Description Diesel engine Manufacturer Country of Origin Type ISO certificate Rating Overload rating Speed Type of cooling Efficiency No. of stroke Fuel consumption Unit HPC REQUIRMENTS OFFER VALUE

Yes/No HP % rpm % Nos. gr/kW

> 50 > 10 1500 WATER 90 4 < 240

Hayan Petroleum Company, Appendix D Att-1

78 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 2 2.1 2.2 2.3 2.4 2.5 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 4 4.1 4.2 4.3 4.4 4.5

Description Governor : Manufacturer Country of Origin ISO certificate Type Electrical/hydraulic Generator : Manufacturer Country of Origin ISO certificate Type Rated voltage Rated power Rated power factor Rated speed Overload rating Temperature rise above 45C ambient Automatic voltage regulator : Manufacturer Country of Origin ISO certificate Type Overall efficiency

Unit

HPC REQUIRMENTS

OFFER VALUE

Yes/No

Yes/No V KW rpm KVA C 380/220 40 0.8 1500 >5 < 55

Yes/No % > 90

7.3 Guarantee Schedule for D.C. Installation


Item 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Description Accumulator Batterry Manufacturer Country of Origin Type ISO certificate Rated voltage of battery Capacity at ( 5 ) hours Voltage after discharge period Rated discharge capacity : Unit HPC REQUIRMENTS OFFER VALUE

Ni -Ca

Yes/No V A.H V

110 200 90

Hayan Petroleum Company, Appendix D Att-1

79 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 1.9 1.10 1.11 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4 4.1 4.2 4.3 4.5

Description 1- Discharge current ( 250m. sec. impulse )At 1 hour rate 2- For discharge period 10 h Number of cells constituting complete battery Charging Rectifier Manufacturer Country of Origin Type ISO certificate Power output Rated voltage Charging current Floating current Rated input voltage Rated input current Time required to recharge battery from min. 80% to max. voltage utilising float charger D.C. Cubicle Manufacturer Country of Origin Type ISO certificate Degree of protection Rated current of busbar Material and cross-section of busbar Insulation of busbar Circuit Breaker Manufacturer Country of Origin ISO certificate Rated voltage

Unit A A

HPC REQUIRMENTS

OFFER VALUE

Yes/No KW V A A V A hrs.

110

400/230

Yes/No A mm2 IP41 200 Copper 150 > 1kV

Yes/No V

Should be submitted

> 110

Hayan Petroleum Company, Appendix D Att-1

80 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

7.4 Guarantee Schedule for Substations Fire Fighting Equipment


Item 1 2 3 4 5 6 7 8 9 Description Manufacturer Country of Origin Type designation Extinguishing medium Quantity of the extinguishing medium Propellant Operating pressure ( Max. ) Spraying range Spraying height Operating te mperature range Dimensions : a) Height b) Width c) Depth Unit HPC REQUIRMENTS OFFER VALUE

kg bar m m

10

mm mm mm

GUARANTEE SCHEDULES FOR CAPACITOR BANK

8.1 GUARANTEE SCHEDULES FOR 20 kV CAPACITOR BANK


Item Description Unit HPC REQUIRMENTS OFFER VALUE

A. Capacitor Bank
A.1 A.2 A.3 A.4 A.5 A.6 A.7 Manufacturer Country of Origin ISO certificate Output at 20 KV No of Sub Banks Overall Layout Drawing Copy of the newest edition for relevant IEC Type test certificate details : Yes/No Drawing No.----(Should be submitted)

Yes/No MVAr (2.5) (for traf 10 MVA)

Hayan Petroleum Company, Appendix D Att-1

81 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description a) Testing station b) Certificate numbers c) Applied standard specifications

Unit

HPC REQUIRMENTS

OFFER VALUE

B. Sub Capacitor Bank


B.1 B.2 B.3 B.4 B.5 B.6 B.7 B.8 B.9 B.10 B.11 B.12 B.13 B.14 B.15 B.16 B.17 B.18 B.19 B.20 C.1 C.2 C.3 C.4 C.5 C.6 C.7 C.8 Rated output at 20 kV , Qn Rated Voltage Un Rated Current Rated Inrush Current Rated Frequency Rated Capacitance Per Phase Capacitance Tolerance Variation in Capacitance Over Temperature Range Losses Variation in Losses Over Temperature Range Phase Connection Double Star or Split Phase Neutral Point No of Capacitor Units in Parallel / Ph No of Capacitor Units in Series / Ph Value of Current Limiting / Filter Reactor Total Weight of Sub Bank Arrangement Drawing Electrical Connection Drawing Number of Capacitor Bank Nos. kV rms A rms kApeak Hz KVAr f % > 2.5 kV rms A kApeak Hz f Yes/No

50 0%,+10% Curve

W/kVar Curve Star Double Unearthed Nos. Nos. mH kg Drawing No.----(Should be submitted)

Drawing No.----(Should be submitted)

C. Capacitor Unit
Rated Voltage Un Rated Current Rated Inrush Current Rated Frequency Rated Output Qn Rated Capacitance Capacitance Tolerance Variation in Capacitance Over Temperature Range

50

( -5 , +15 ) Curve

Hayan Petroleum Company, Appendix D Att-1

82 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item C.9 C.10 C.11

Description Losses at Rated Output Variation in Losses Over Temperature Range Internal Element fusing a) Upper limit U2 b) Withstand c) Operation at minimum voltage Single/Double Bushing Fusing No. of Fuses to Operate (Alarm) No. of Fuses to Operate (Trip) No. of Capacitor Elements in Parallel No. of Capacitor Elements in Series Value of Discharge Resistor Time to Discharge to 75 Volts Impregnate Case Material Weight of Unit

Unit W/kVar

HPC REQUIRMENTS Curve

OFFER VALUE

C.12 C.13 C.14 C.15 C.16 C.17 C.18 C.19 C.20 C.21 C.22

Internal

K Ohm Mins Non PCB Bio Degradable Stainless Steel kg

D. Protective Equipment
D.1 D.2 D.3 D.4

Short Circuit Protection. ( 2 phase) Internal Element Fuses Overvoltage Protection Overcurrent Protection (Excessive RMS current) Earth Fault Protection. Unbalance Protection Other protections

D.5 D.6 D.7

E. Reactive power controller


E.1 E.2 Standard specification IEC (688-1) Setting ranges expressed as percentage of the monitored quantity : 1- inductive range 2- capacitance range

Hayan Petroleum Company, Appendix D Att-1

83 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item E.3

Description Input ratings: 1- frequency 2- current IN 3- voltage UN 4- tan of the load

Unit

HPC REQUIRMENTS 50 2% 1 100 (+10% -20%) 0,33 cap, + 0.75 ind

OFFER VALUE

Hz A V

E.4

Auxiliary supply voltage -min -max

VDC

110 -20% +10%,

E.5 E.6 E.7 E.8 E.9 E.10 E.11

Test voltage Impulse voltage Ambient temperature ranges Time delay from step to step Are input circuits equipped with harmonic suppression elements Enclosure class IEC529 - 1976 Minimum wire cross section for external connections

KV KV
C

2 5 - 5 , + 55

mm

2.5

8.2 GUARANTEE SCHEDULES FOR 6.6 kV CAPACITOR BANK


Item Description Unit HPC REQUIRMENTS OFFER VALUE

A. Capacitor Bank
A.1 A.2 A.3 A.4 Manufacturer Country of Origin ISO certificate Output at 20 KV No of Sub Banks Yes/No MVAr (2.5) (for traf 12.5 MVA)

Hayan Petroleum Company, Appendix D Att-1

84 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item A.5 A.6

Description Overall Layout Drawing Copy of the newest edition for relevant IEC Type test certificate details : a) Testing station b) Certificate numbers c) Applied standard specifications

Unit

HPC REQUIRMENTS Drawing No.----(Should be submitted)

OFFER VALUE

Yes/No

A.7

B. Sub Capacitor Bank


B.1 B.2 B.3 B.4 B.5 B.6 B.7 B.8 B.9 B.10 B.11 B.12 B.13 B.14 B.15 B.16 B.17 B.18 B.19 B.20 Rated output at 20 kV , Qn Rated Voltage Un Rated Current Rated Inrush Current Rated Frequency Rated Capacitance Per Phase Capacitance Tolerance Variation in Capacitance Over Temperature Range Losses Variation in Losses Over Temperature Range Phase Connection Double Star or Split Phase Neutral Point No of Capacitor Units in Parallel / Ph No of Capacitor Units in Series / Ph Value of Current Limiting / Filter Reactor Total Weight of Sub Bank Arrangement Drawing Electrical Connection Drawing Number of Capacitor Bank Nos. > 2.5 kV rms A kApeak Hz f Yes/No

50 0%,+10% Curve

W/kVar Curve Star Double Unearthed Nos. Nos. mH kg Drawing No.----(Should be submitted)

Drawing No.----(Should be submitted)

C. Capacitor Unit
C.1 C.2 C.3 C.4 Rated Voltage Un Rated Current Rated Inrush Current Rated Frequency kV rms A rms kApeak Hz

50
85 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item C.5 C.6 C.7 C.8 C.9 C.10 C.11

Description Rated Output Qn Rated Capacitance Capacitance Tolerance Variation in Capacitance Over Temperature Range Losses at Rated Output Variation in Losses Over Temperature Range Internal Element fusing d) Upper limit U2 e) Withstand f) Operation at minimum voltage Single/Double Bushing Fusing No. of Fuses to Operate (Alarm) No. of Fuses to Operate (Trip) No. of Capacitor Elements in Parallel No. of Capacitor Elements in Series Value of Discharge Resistor Time to Discharge to 75 Volts Impregnate Case Material Weight of Unit

Unit KVAr f %

HPC REQUIRMENTS

OFFER VALUE

( -5 , +15 ) Curve

W/kVar Curve

C.12 C.13 C.14 C.15 C.16 C.17 C.18 C.19 C.20 C.21 C.22

Internal

K Ohm Mins Non PCB Bio Degradable Stainless Steel kg

D. Protective Equipment
D.1 D.2 D.3 D.4

Short Circuit Protection. ( 2 phase) Internal Element Fuses Overvoltage Protection Overcurrent Protection (Excessive RMS current) Earth Fault Protection. Unbalance Protection Other protections

D.5 D.6 D.7

E. Reactive power controller


E.1 Standard specification IEC (688-1)

Hayan Petroleum Company, Appendix D Att-1

86 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item E.2

Description Setting ranges expressed as percentage of the monitored quantity : 1- inductive range 2- capacitance range

Unit

HPC REQUIRMENTS

OFFER VALUE

E.3

Input ratings: 1- frequency 2- current IN 3- voltage UN 4- tan of the load Hz A V 50 2% 1 100 (+10% -20%) 0,33 cap, + 0.75 ind VDC 110 -20% +10%, KV KV
C

E.4

Auxiliary supply voltage -min -max

E.5 E.6 E.7 E.8 E.9 E.10 E.11

Test voltage Impulse voltage Ambient temperature ranges Time delay from step to step Are input circuits equipped with harmonic suppression elements Enclosure class IEC529 - 1976 Minimum wire cross section for external connections

2 5 - 5 , + 55

mm

2.5

Hayan Petroleum Company, Appendix D Att-1

87 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

SCHEDULES OF MANUFACTURERS

9.1 Substations Equipments


(For each voltage separately)
Item 1 Description Power transformers 66/20kV, 10 MVA 66/6.6 KV , 12.5 MVA Earthing transformers 20/0.4 kV 6.6/0.4 KV Circuit breaker 66 kV Disconnecting switches without earthing switches 66kV Disconnecting switches with earthing switches 66 kV Voltage transformers 66kV Current transformers 66kV Lightning arrestors 66 kV Busbars : 66 kV, tubes..../ ....... mm, conductors.... Post type insulators 66 kV Tension strings 66 kV Suspension strings 66 kV Steel structures 20 kV cubicles 6.6 KV cubicles 20 kV Circuit breaker 6.6 kV Circuit breaker AC DC Diesel generator set LV C.b 20kV, 6.6 kV capacitor banks etc 20 kV & 6.6 KV cables LV cables ,control and protection cables Type Manufacturer Place Of Manufacturer Place Of Testing

2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

17 18 19

Hayan Petroleum Company, Appendix D Att-1

88 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

9.2 Control, Metering and Protection Equipments


(To be filled-in for each voltage separately)
Item Description Type Manufacturer Place Of Manufacturer Place Of Testing

1 1-1

Control unit/ panel with the following facilities: Facilities available in the control unit Combined digital , Ameter, V meter, with digital power factor meter Indicators, push buttons, annunciators, test lamps selector switches discrepancy switches, . Active and reactive power meters . Protection and metering unite Distance relays Restricted earth fault protection Directional earth-fault over current relay ... Independent/ dependent Overcurrent protection with definite time delay
Under frequency load shedding device... Earth-fault overcurrent protection Transformer differential protection Overcurrent relay (tank protection) Earth-fault protection for the neutral of earthing tr-r Automatic voltage regulation relay

1-2

1-3 1-4 2 2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9
2-10

2-11 2-12

Trip circuit supervision Plug test unit

All FAT certificates for DCS , SCADA instruments shall be provided

Hayan Petroleum Company, Appendix D Att-1

89 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10 SCHEDULES OF SPARE PARTS : 10.1 Spare Parts of Power Transformers ( 10 MVA & 12.5 MVA)
Item 1 2 3 Description H.V. bushing complete H.V. neutral bushing complete M.V. bushing: 20 KV bushing complete 6.6 KV bushing complete Set of Transformer gaskets for 66/20 kV Transformer Set of Transformer gaskets for 66/6.6 kV Transformer Filling of air dehydrating medium ( silkajial ) Oil level indicator Buchholz relay for main transformer Buchholz relay for OLTC Pressure relay for OLTC. complete diverter switch for OLTC Complete set of thermometers each including (Thermometer sensor ,temperature transmission pipe ,temperature indicator complete motor drive unit for OLTC . (bevel gear) on the top cover for OLTC (bevel gear) which connects horizontal and vertical arms for OLTC Tap changer remote position indicator ( digital type ) with all accessories Gasket For O L T C. O L T C comp. Cooler each set including one body cooler ,two pieces of butterfly valves. Fan motor each including 17 18 1-Fan 2-motor Winding temperature Nos. Nos. Nos. 2 2 1 Nos. Nos. Set Set Kg Nos. Nos. Nos. Nos. Nos. set Nos. Nos. Nos. 2 2 1 1 3 1 1 1 1 1 1 1 1 1 1 Nos. Nos. set 1 1 2 Unit Nos. Nos. Qty. 2 1

4 5 6 7.1 7.2 7.3 8 9 10 11 12 13 14 15 16

indicator

Hayan Petroleum Company, Appendix D Att-1

90 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10.2 Spare Parts of Earthing / Auxiliaries Transformers


Item 1 2 3 4 5 6 Description H.V. 2 0 KV bushing complete H.V. 6.6 KV bushing complete L.V. bushing complete with joints Thermometers complete set Buchholz relay Oil level indicator Set of transformer gaskets Unit Pcs. Pcs. Pcs. set No. No. set Qty. 2 3 2 1 1 1 1

10.3 Spare Parts of 66 kV Circuit Breaker


Item 1 2 3 4 5 6 Description Complete C.B -1250 A Auxiliary switches of each type a) Closing coils b) tripping coils Sealing gaskets for 3 poles Complete driving mechanism for circuit breaker with all the auxiliaries. (Details to be given by bidder) One bottle of 40 kg sf6 Unit No. set No No set Nos. Qty. 1 1 1 1 1

10.4 Spare Parts of 66KV Disconnecting Switches


Item 1 2 3 4 5 6 Description Complete disconnecting switch Isolator for one complete disconnecting switch
Top hamper assembly including fixed and moving contacts for one complete D.S.

Unit set set set Nos. set Nos.

Qty. 1 1 1 1 1 1

Auxiliary switches for Interlock unit


Aux. relays and contactors

Drive motor

Hayan Petroleum Company, Appendix D Att-1

91 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10.5 Spare Parts of Instrument TRs And Lightning Arresters 66 kV :


Item 1 Description A - Conventional Type Current tr-r single phase Core 1 600-300/1 ClX , VK > 500 V Rct < 4 Core 2 600-300/1 5P20,20VA Core 3 600-300/1 Cl 0.5,FS = 5, 20 VA Core 1 400-200/1 ClX , VK >500 Rct<4 Core 2 400-200/1 5P20, 20 VA Core 3 400-200/1 Cl 0.5,FS = 5,20 VA Core 1 200-100/1 ClX , VK >500 Rct<4 Core 2 200-100/1 5P20, 20 VA Core 3 200-100/1 Cl 0.5,FS = 5,20 VA Voltage tr-r single phase of H.V. B - Lightning Arresters Single phase unit complete with surge counter . Unit Qty.

1.1

Nos.

1.2

Nos.

1.3

Nos. Nos. Nos.

1 1 1

2 3

10.6 Spare Parts for 20 kV Switchgear


Item 1 1 2 3 4 Complete C.B C.B. tripping coil C.B. closing coil Voltage tr-r Current transformer : Core 1 400-800/1 ClX , VK >400 V Rct < 4 Core 2 400-800/1 5P20 , 20 VA Core 3 400-800/1 Description Unit Nos. Nos. Nos. Nos. Qty. 1 1 1 1

4.1

Nos.

Hayan Petroleum Company, Appendix D Att-1

92 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item

Description Cl 0.5,FS=5,15VA Core 1 400-800/1 5P10 , 20 VA Core 2 400-800/1 Cl 0.5,FS=5,15VA 20 K V lightning arrester Measuring center Relay (of each type) Signaling and intermediate relay Auxiliary switches miniature C.B. Signaling lamps for control and indicating switches Terminals (of each type) Auxiliary relay Sealing end boxes pluging

Unit

Qty.

4.2 5 6 7 8 9 10 11 12 13

Nos. set. Nos. Nos. Nos. Nos. Nos. Nos. Nos. No

1 1 1 1 1 2 10 3 2 2

10.7 Spare Parts of 6.6 kV Switchgear


Item 1 1 2 3 4 Description Complete C.B C.B. tripping coil C.B. closing coil Voltage tr-r Current transformer : Core 1 1000-2000/1 ClX , VK >400 V Rct < 4 Core 2 1000-2000/1 5P20 , 20 VA Core 3 1000-2000/1 Cl 0.5,FS=5,15VA Core 1 1000-2000/1 5P10 , 20 VA Core 2 1000-2000/1 Cl 0.5,FS=5,15VA 10 K V lightning arrester Measuring center Relay (of each type) Signaling and intermediate relay Auxiliary switches miniature C.B. Signaling lamps for control and indicating switches Unit Nos. Nos. Nos. Nos. Qty. 1 1 1 1

4.1

Nos.

4.2 5 6 7 8 9 10

Nos. set. Nos. Nos. Nos. Nos. Nos.

1 1 1 1 1 2 10
93 - 99

Hayan Petroleum Company, Appendix D Att-1

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

Item 11 12 13

Description Terminals (of each type) Auxiliary relay Sealing end boxes plug in

Unit Nos. Nos. No

Qty. 3 2 2

10.8 Spare Parts of Control, Metering and Protection Equipment


Item
1

Description

Unit

Qty.

Equipment as Spare Parts for Control, Metering and 1 SET Protection Note : Quantities and description of the a.m. spare parts set should be specified in the following schedules : Item 1 2 3 4 5 6 7 8 9 10 11 Description Each type of discrepancy switch Each type of push button Each type of selector switch Each type of indicator Lamps for indication , alarm discrepancy Each type of timer and auxiliary without the base Each type of alarm card Each type of windows lamp Protection of each relay type offered Metering of each type offered Synchronizing switch Unit Set Set Set Set No. No. Set No. Set Set Qty. 2 2 2 2 2 2 2 2 2 1 1

10.9 Spare Parts of Auxiliary Equipment


Item 1 2 3 4 Description One complete air circuit breaker of each size offered one set of contacts for each size of air circuit breaker offered Sets of M.C.B, switches and lamps used with the auxiliary equipment each type . Complet charging rectifier set Unit set. set set set Qty. 1 1 2 1

Bidder should submit detailed list for each item

Hayan Petroleum Company, Appendix D Att-1

94 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10.10
tem 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Spare Parts list for capacitor Bank for,10 MVA , 66/20 kV


Description Capacitor unit single phase 50 HZ insulation level 24 KV Unbalance transformer Damping reactor 50 uH 250 A Heating resistor 270 W/230 v Discharge VT { 20000/3 / 100/ 3V ( If any ) Insulator 24 kV A meter Thermostat Heating reactor 20 W Power factor relay Auxiliary relay 110 DC LV MCB Push botton Switch Capacitance meter Quantity 1 1 1 1 1 1 1 1 2 1 2 2 1 1 1

10.11 Spare Parts list for capacitor Bank for,12.5 MVA , 66/6.6 kV
Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description Capacitor unit single phase 50 HZ insulation level 7.2 KV Unbalance transformer Damping reactor 50 uH 250 A Heating resistor 270 W/230 v Discharge VT { 6600 /3 / 100/ 3V ) ( If any ) Insulator 7.2 kV A meter Thermostat Heating reactor 20 W Power factor relay Auxiliary relay 110 DC LV MCB Push botton Switch Capacitance meter Quantity 1 1 1 1 1 1 1 1 2 1 2 2 1 1 1

Hayan Petroleum Company, Appendix D Att-1

95 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

10.12 Bus Bar AS Spare Parts


Item 1 2 3 4 Description Each size of conductor and tube used Each type of clamps and fitting PI for each voltage level Complete string insulator for each voltage level Unit % % No. No. Qty. 5 5 3 3

11 CHEDULES OF MAINTENANCE AND OPERATION TOOLS AND EQUIPMENT :


(Bidder should submit: Company Name's, Country of Origin, Type, and technical details for each item)

11.1 LIST OF MAINTENANCE & OPERATION TOOLS AND


EQUIPMENT FOR 66 kV EQUIPMENT
Item 1 Description leakage gas detector gas refilling , tapping up evacuating device with all 2 the associated fittings, with filter to use in case of evacuating to atmosphere. Set 1 Unit No. Qty. 1

11.2 Schedule of Miscellaneous Control Devices


Item Description Relay testing equipment :digital computer added universal type test equipment for all relays completed with lap top and necessary soft wars and programs and 1 the relay testing equipment should deal with fault recording and the rely functions of the tested relay . set 1 Unit Qty.

Hayan Petroleum Company, Appendix D Att-1

96 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

11.3 LIST OF MAINTENANCE & OPERATION TOOLS AND


EQUIPMENT MISCELLANEOUS
Item 1 2 3 4 5 6 7 Description AC primary injection test set 2400 Volt motor-driven megger insulation tester AVO - multimeter 500 Volt hand-driven megger insulator tester 5000 Volt electronic megger insulator tester Temporary earthing device with all accessories . Earthing grid resistance digital meter Unit Set No. Nos. No. No. Set No. Qty 1 1 1 1 1 1 1

11.4 LIST OF MATERIALS FOR SAFETY OPERATION


Item 1 2 3 Description Single ph 66 kV earthling rod Safety helmet 66, 20, 6.6 kV voltage detector Unit Nos. Nos. Nos. Quantity 3 1 1

Hayan Petroleum Company, Appendix D Att-1

97 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

12

TECHNICAL EVALUATION FOR CIVIL WORK 12.1 Civil Work Construction :


The following items are to evaluate the bidders civil work constructor: Item 1 2 Specification Full time civil work constructor site engineer Number of electrical projects executed civil work with name and location The cost of the projects executed within the last ( 5 ) years Civil necessary machineries and equipments belong to civil work constructor Number of civil engineers (officially registed) belong to civil work constructor Unit Required specific. More than ( 5 ) years experience
Not less than one project

Offerer Data

Not less than ( 0.5 ) m $

Not less than ( 4 ) civil engineer

Hayan Petroleum Company, Appendix D Att-1

98 - 99

Contract Ref. HPC / 11-<XX>

Appendix-D /Attachement No 1

12.2 Evaluation of Preliminary Drawing for Outdoor Substation:


Item 1 1.1 1.2 1.3 Specification General layout : Building placing Submitted levels between substation parts Switchyard roads Suitable curves for cars movement , reach to all switchyards equipment easily , roads Outdoor ,enclosure supplied with steel structure brick slope roof for sun protection purpose Designed in a simple way to keep the switchyard dry all time Small section , in a fit way to avoid having water inside the trench To allow easy moving and available control within substation Unit Required Specification Offerer Data

1.4

Placing capacitor bank

1.5 1.6 1.7 1.8 1.9 2 2.1 2.2

Drainage system for switchyard Cable trench Placing of control cables and power cables Connection between auxiliary / earthing trans. and power trans. Transporting , erection and replacement of power trafo. easily Control building : Height Structural design

2.3

Architectural external tile Equipment erection and connection between control building parts

2.4

Considering the earthquake requirement , with small extent between columns (< 6 ) Should respect the (Urban Tissue) and acc. appendix D, attachment-2 Easy to be controlled , maintained , erected and moved in and out of the building

Hayan Petroleum Company, Appendix D Att-1

99 - 99