Académique Documents
Professionnel Documents
Culture Documents
N
D1
N'
M3
M4
Figu1. Proposed voltage sag compensation Topology
During the normal voltages the bypass switches are
closed, delivering utility power directly to the load. When
voltage sags occur, the inverters operate; turning off the
bypass switches; the inverters supply the missing voltage and
help to maintain rated voltage at the terminals of the critical
load. During compensation, the inverter continuously draw
power from the incoming source lines, so the capacitors in
the inverters can be much smaller than other voltage
compensators such as DVR in which the compensating
energy is only supplied by energy storage devices. The
analysis of maximum compensation depth is below.
B. Maximum Compensation Depth
A phasor map is shown in Fig. 2 in the case of voltage
sags. In this figure, ijkabc i j k. U
i2
U
j2
U
k2
are the sagged incoming three phase voltages
(U
j2
>U
k2
>U
i2
), U
ij2
is the sagged line-to-line voltage between
phase i and j which charges the inverters capacitors in phase
i, U
iR
is the rated voltage in phase i, and N is the theoretical
neutral. Assume p
i
, p
j
and p
k
are the sagging factors of phase
i, j and k respectively, we have:
=
=
=
kR k k
jR j j
iR i i
U p U
U p U
U p U
2
2
2
(1)
2
2 2
2
2 2
6
sin
6
cos |
.
|
\
|
+ + |
.
|
\
|
=
i j j ij
U U U U
t t
(2)
Further more, take the capacitor voltage drops into
consideration. The capacitance of the capacitors in the
inverter need not be very large. Let q
e
(0,1) a factor of
filtering that denote the fluctuant degree of the voltage in the
capacitors. q is defined as the minimum ratio of the
Figu 2. Phasor map of the sagged voltages and its compensation
minimum voltage to the maximum voltage in the
capacitors during the just said dynamic balance condition.
We can obtain an approximate relation as following (3):
2 2 ij i iR
qU U U + = (3)
Solve the equations of (1), (2), (3), and consider U
iR
= U
jR
=
U
kR
, following result can be derived:
2
2 2
2
1 2
q
p p p p
p p
j j i i
i i
=
+ +
+
(4)
which is the relation of the allowable minimum and
maximum sagging factors and the filtering factor under
which the sags can be compensated.
If the capacitances are large enough; i.e. q~1; (4) becomes
0 1 2
2
= + +
i j i j
p p p p (5)
(4) and (5) is shown in graph chart as Fig.3, where p
i
and
p
j
are the minimum and maximum voltage sagging factors
respectively, case 1 is the case of p
j
=1 in which one of the
three-phase voltage is normal, case 2 is the case of p
i
= p
j
=
p
k
in which the voltage sag is symmetrical. The up-left
shadowed area is not valid because p
i
p
j
.
Fig.3 shows that if at least one of the phase voltage is
maintained normal, the minimum sag voltage which can be
continuously compensated changes with the filtering factor q
as shown in the case 1. If the DC capacitor is large enough
and q=1, the minimum sag voltage can be 0. This means that
the compensator can compensate one or two-phase voltage
sags down to 0 continuously, if one of the phase voltage is
maintained normal and q=1. Symmetrical three-phase voltage
sag down to 37% of the normal voltage can be compensated
continuously, if q=1. The compensated sag voltage increases
with the decrease of filtering factor q as shown by the thick
line of case 2 in Fig.3.
III. TIME OPTIMAL CONTROL STRATEGY
Voltage injection capability is the main factor to consider.
There are two factors to determine the capability of voltage
injection. One is the good performance to compensate a
broaden range of voltage sags. The other is the capability to
persist compensating time during sag. In order to save
storage energy, the energy optimal control was proposed.
In this section, a time optimal control strategy is presented.
It is also compared with energy optimal control.
A. Energy Optimal Control
Fig. 4 is an equivalent circuit of the power system when
voltage sags, where, V
s
is supply voltage, V
1
is supply
voltage before compensation, V
2
is load voltage after
compensation, I is load current. When a fault occurs, V
1
drops and a series voltage V
inject
is injected into power
network, where:
Figu 3. The graph chart of (4).
U
ij2
U
iR
U
ij2
U
j2
U
k2
30
o
N
U
i2
U
i2
qU
ij2
1704
1 2
V V
inject
V = (6)
The corresponding phasor diagram of Fig. 4 is shown in
Fig. 5. Let o, |, o represent load voltage advance angle, load
power factor angle and supply voltage phase angle during
sags, respectively. P
in
, P
out
, P
inject
are the input real power
from the source ,the load real power and injected real power
respectively. P
in
, P
out
, P
inject
are described as:
) cos(
1
o o | + = I V
in
P
(7)
) cos(
2
| I V
out
P =
(8)
( ) o o | | + = cos
1
) cos(
2
I V I V
inject
P
(9)
The energy optimal control is depicted in Fig. 6. Fig. 6a
illustrate the case of that the magnitude of voltage sag is
shallow when inject real power is zero. Fig. 6b means the
level of voltage sag is deeper so that the injected real power
can not be zero, but can be minimized.
B. Proposed Time Optimal Control Strategy
Denote C is DC link capacitance, V
DCMAX
is the maximum
permissible DC link voltage before sags, V
DCMIN
is the
minimum needed DC link voltage to compensate the load
voltage to normal load voltage. During compensating, the
DC link capacitors can provide energy as following:
)
2 2
( *
2
1
DCMIN
V
DCMAX
V C
DC
W = A
(10)
In order to restore load voltage, the DC link voltage must
be larger than the peak magnitude of V
inject
. So,
inject
V
DCMIN
V 2 =
.
If there is no energy loss in converter, p= V
1
/ V
2
is the
voltage sag factor, following result comes out:
\
:
\
!
\
`u_t
\
?
'oud
'`u `mduu
T
:u')
Figu 4. Schematic diagram of a power distribution system when
voltage sags
o
|
o
I
\
?
\
!
\
`u_t
:u_ vo'tu_
Figu 5. Phasor diagram of power distribution system during sags
M
I
CV
I V I V
inject
V
DCMAX
V C
inject
P
DC
W
T
2
2
1
) cos(
1
cos
2
)
2
) 2 (
2
(
2
1
=
+
=
A
=
o o | |
(11)
Where:
) cos( * cos
2
) 2 (
2
o o | | +
=
p
inject
V
DCMAX
V
M (12)
For a given compensator topology, fixed load and a certain
fault, some parameters such as C, V
DCMAX
, V
2
, |, I , p, o are
fixed. So in (11), the compensating time T is only associated
with V
inject
and o.
The time optimal strategy is as shown in Fig. 7, where, let
| =o - o is the advanced angle from load voltage to sag
voltage. In Fig. 7a, T is when shallow sag. It is the same
with T in energy optimal control. In Fig. 7b, V
1,2
is the case in
energy optimal control, and V
1,1
is the case in time optimal
control. Although P
inject
in V
1,1
is larger than that in V
1,2
,
V
inject,1
in V
1,1
is smaller than V
inject,2
in V
1,2
. Which one of the
control strategy can give better performance in compensating
during sags is worth to study.
From (11), the maximum compensating time by using time
optimal control strategy will be:
( ) | o
o o | |
, 0 ,
) cos(
1
cos
2
)
2
) 2 (
2
( *
2
1
max
e
+
=
x
x
I V I V
inject
V
DCMAX
V C
T
For three-phase voltage sags with balance loads, the
compensating time factor M in time optimal control of
typical four-wire DVR ( the typical topology of four-wire
DVR is as show in [10]) is as following:
_
=
+
=
3
1
) cos( * cos 3
2
)]
_
2 [max(
2
y
y y y
p
y inject
V
DCMAX
V
M
o o | |
(13)
Denote T
a
, T
b
, T
c
are respectively the compensating time
of phase a, b and c. M
a
, M
b
, M
c
are respectively the
compensating time factors of phase a, b and c. In reference
[10], T
a
=T
b
=T
c
=T, M
a
=M
b
=M
c
=M. Especially, for
three-phase symmetrical sags, (9) becomes:
c b a y
y y y
p
y inject
V
DCMAX
V
y
M , , ,
) cos( * cos
2
)
_
2 (
2
=
+
=
o o | |
(14)
where, o
a
=o
b
=o
c
, V
inject_a
= V
inject_b
= V
inject_c
, p
a
=p
b
=p
c
and
M
a
=M
b
=M
c
.
|
T T
\
?
\
?
\
!
\
!
\
`u_t
\
`u_t
|
|
u
Figu 6. Phasor diagram of energy optimal control strategy a) zero
active power injection b) minimal active power injection
1705
T T
\
?
\
?
\
!
\
!,!
\
`u_t
\
`u_t,!
|
|
u |
| |
\
!,?
\
`u_t,?
Figu 7. Phasor diagram of time optimal control strategy
C. Time Optimal Control for the Proposed Topology
For the proposed topology in Fig. 1, The maximum lasting
compensating time factor of each phase is as the same as (14),
but where V
inject_k
, p
k
, o
k
, k=a, b, c may be different to
different phase, respectively:
c b a y
y y y
p
y inject
V
DCMAX
V
y
M , , ,
) cos( * cos
2
)
_
2 (
2
=
+
=
o o | |
(15)
The maximum compensating time of the device , that is
the optimal compensating time, will be:
T
max
=
I
C
*max (min (T
a
, T
b
, T
c
)), o
a
, o
b
, o
c
(0,|) (16)
When symmetrical sags occur, p
a
=p
b
=p
c
, o
a
=o
b
=o
c
, so
V
inject_a
=V
inject_b
=V
inject_c
, o
a
=o
b
=o
c
, (15) can be equal to (14).
So (14) is a special case in (15).
The way to realize the time optimal control is : for a fixed
set of parameters, to find a set of {o
a
-
, o
b
-
, o
c
-
} which can
get the maximum of (16).
IV. SIMULATION
Fig. 8 shows the advantages of time optimal control
compared to energy optimal control. The three phases are
symmetrical sags. The magnitude of rated load voltage is 1
p.u. The horizontal axis is V
DCMAX
in p.u, denoted as V
DCMAX
*
.
The vertical axis is the percent of At/T. T is the compensating
time by using energy optimal control. At =T
max
-T is the
excessive time by using the time optimal control than that of
energy optimal control. The other axis that is perpendicular
to both the horizontal axis and the vertical axis is the
magnitude of symmetrical voltage sags in p.u.
Fig. 8a shows the At/T when the load angle |=pi/6.
Definitely, the deeper the magnitude of voltage sags and the
lower the V
DCMAX
*
, the larger the percent of At/T is. Fig.8b
shows the percent of At/T when the load angle |=pi/3. In Fig.
8, V
DCMAX
*
is larger than 1 p.u. If V
DCMAX
*
becomes smaller
than 1 p.u, the At/T can be several times larger than that of
this case.
Fig. 9 gives simulated waveforms of using the time
optimal control and the energy optimal control in the
proposed topology, where the voltages symmetrical sags
down to 10% with balance loads, the V
DCMAX
*
is 1 p.u, the
load impedance angle is |=pi/3, p
i
= p
j
= p
k
=0.09and voltage
sags occurred at 0.1s. Fig. 9(a) is the compensating waves by
using the energy optimal control. E
a2
, E
b2
, E
c2
are supply
voltages. The peak magnitude of them are 0.157kV. E
a
, E
b
,
E
c
are the three-phase voltage in load. Consider the load
voltage in l p.u is normal. The load voltage went down at
about 0.24s. The compensating time T is about 0.19s. Fig.
9(b) is the compensating waves by using the time optimal
control. Consider the load voltage in l p.u is normal. The load
voltage went down at about 0.42s. The compensating time
T
max
is about 0.38s. Clearly, time optimal control is better in
compensating time than energy optimal control. In this
situation, At/T is 100%.
(a) load angle |=pi/6
(b) load angle |=pi/3
Figu 8. The advantage of time optimal control compared to energy
optimal control when symmetrical sags
(a) energy optimal control
At/T
p
a
=p
b
=p
c
V
DCMAX
*
At/T
V
DCMAX
*
p
a
=p
b
=p
c
1706
(b) time optimal control
Figu 9. Simulating comparison of the time optimal control and the
energy optimal control in the proposed compensating topology
V. EXPERIMENTAL RESULTS
The experimental circuit parameters are: C
1k
=C
2k
= 500F,
k=a, b, c. The loads are balanced resistances and inductances
that R
k
=180O, L
k
=0.8H, k=a, b, c. At this case | =54
. The
switch frequency is 20kHZ. The voltage sag duration is
300ms. The nominal load voltage is 110V (rms, line-neutral).
Three-phase voltage symmetrical sags down to 30% (rms,
33V). DC link voltage is controlled at V
DCMAX
*
=1.
In Fig.10. This Fig is one phase of the loads voltages
compensating with the energy optimal control. As shown in
Fig.10(a), the loads voltage can only be sustained at rated
nearly 80ms. As shown in Fig.10(b), At this case, the
operation mode is minimal active power injection, |=|
=54
.
In Fig.11. This Fig is one phase of the loads voltages
compensating with the time optimal control. As shown in
Fig.11(a), the loads voltage can be sustained at rated nearly
150ms. As shown in Fig.11(b), At this case | = 21.2
.
(a) loads voltage
(b) | when operation at the energy optimal control
Figu 10. One phase of the loads voltages compensating
with the energy optimal control.
(a) load s voltage
(b) | when operation at the time optimal control
Figu 11. One phase of the loads voltages compensating
with the time optimal control.
VI. CONCLUSIONS
A transformer-less series voltage sag compensator
without energy storage capacitors was proposed as a
cost-effective way of series sag compensation. Theoretical
analysis indicate that the proposed topology can compensate
symmetrical three-phase voltage sags down to 37%, or
asymmetrical one or two-phase voltage sags down to zero if
at least one phase is in normal. This topology can be used in
three-phase four-line system and three-phase line system too.
A new time optimal control strategy has been proposed for
the control of series voltage sag compensator. Analysis and
Time (50ms/div)
Time (50ms/div)
Time (50ms/div)
Time (50ms/div)
sag
sag sag end
sag end
V
o
l
t
a
g
e
(
5
0
V
/
d
i
v
)
/
V
o
l
t
a
g
e
(
5
0
V
/
d
i
v
)
/
V
o
l
t
a
g
e
(
5
0
V
/
d
i
v
)
/
V
o
l
t
a
g
e
(
5
0
V
/
d
i
v
)
/
1707
simulation results show that in deeper voltage sags using the
time optimal control strategy can compensate voltage during
sags much longer time than using energy optimal control.
Using the time optimal strategy to the proposed topology,
experiment results validated the good performance.
The unsymmetrical voltage sags is now under
investigation.
REFERENCES
[1] William E. Brumsickle, Robert S. Schneider, Glen A. Luckjiff,
Deepak M. Divan and Mark F. McGranaghan. Dynamic Sag
Correctors: Cost-effective Industrial Power Line Conditioning,
IEEE Trans. Ind. Applicat., vol.37, pp.212-217, Jan./Feb. 2001.
[2] Po-Tai Cheng, Chian-Chung Huang, Chun-Chiang Pan and
subhashish Bhattacharya. Design and Implementation of a Series
Voltage Sag Compensator Under Practical Utility Conditions, IEEE
Trans. Ind. Applicat., vol.39, pp.844-853, May./June. 2001.
[3] Seyed Hossein HOSSEINI and Mohammad Reza BANAEI. A New
Minimal Energy Control of the DC Link Energy in Four-Wire
Dynamic Voltage Restorer., The 30th Annual Conference of the
IEEE Industrial Electronics Society, pp.3048-3053, November 2-6,
2004.
[4] Abraham J. Visser, Johan H. R. Ensllin and Hendrik du T. Mouton.
Transformerless Series Sag Compensastion With a Cascaded
Multilevel Inverter, IEEE Trans. Ind. Electr., vol.49, pp.824-831,
August.2002.
[5] A.J. Visser, H. du T. Mouton and J.H.R. Enslin. Driect-coupled
Cascaded Multilevel Sag Compensator, Power Electronics
Specialists Conference, 2000. PESC 00. 2000 IEEE 31st
Annual ,Volume: 1 ,18-23 June 2000 , pp:463 469, vol.1.
[6] W.E, Brumsickle,R.S, Schneider, G..A. Luckjiff, D.M. Divan and
M.F. McGranaghan, Dynamic sag correctors:cost-effective
industrial power line conditioning,IEEE Trans.IA,Vol.37,
pp.212-217, 2001.
[7] T. Jauch, A. Kara, M.Rahmani and D. Westermann. Power Quality
Ensured by Dynamic Voltage Correction., ABB Rev.,Vol.4, 1998.
[8] D. Mahinda Vilathgamuwa, A.A.D. Ranjith Perera and S.S. Choi.
Voltage Sag Compensation With Energy Optimized Dynamic
Voltage Restorer, IEEE. Trans. on Power Delivery.,Vol.18,
pp.928-936, July.2003.
[9] Mahinda Vilathgamuwa, A.A.D. Ranjith Perera, S.S.Choi and K.J.
Tseng. Control of Energy Optimized DynamicVoltage Restore,
IEEE Conference Records on IECON99, vol.2, 1999, pp.873-878.
[10] B.H.Li, S.S. Choi and D.M. Vilathgamuwa. A New Control Strategy
for Energy-saving Dynamic voltage Restoration, Power Engineering
Society Summer Meeting C. Seattle, WA, USA; IEEE Press, 2000, 2.
1103-1108.
[11] Chen Zenglu and ISE Toshifimi. Transformer-less Series Voltage
Sag Compensator Without Energy Storage Capacitor for Three-phase
three-line Systems, IEEJ. Trans. IA.,Vol.127, pp.693-700, 2007.