WHY TO BE DISCUSSED?
December 10, 1991 North Rhine, Westphalia, Germany
cooler in the high pressure section of the HCU resulted in a release of HC and H2, which subsequently ignited.
Reason
-severe corrosion/erosion in pipeline Result - A substantial part of unit was destroyed by the explosion and subsequent fire. -HCU was shut down for approx. seven months with loss of nearly $90,000,000
Reference-The 100 Largest Losses 1972-2001 Large Property Damage Losses in the Hydrocarbon-Chemical Industries. MARSH-Property Risk Consulting
WHY TO BE DISCUSSED?
A leak in the HP system-A serious emergency , requires immediate action to prevent harm to personnel and equipment. The first moves- Dont panic ,Be decisive and act promptly. In case of leak in the HP reaction system, the entire high pressure system will start to depressurise through the leak. These escaping gases can provide fuel for a serious fire.
Action items...
Normal Operation Reactor Heater Fires Make-up H2 Rate Oil Feed Rate System Pressure Recycle Compressor Reactor Quench F/E Bypass Rate Separator CTL Valves Injection Water Watch Watch Watch Watch Watch Watch Watch Watch Watch Fire/leak Stop Stop Stop Depressurize Maximum Maximum Maximum Watch Stop
Immediate Actions
1.
2.
3. 4. 5.
Depressurize the reactor loop by opening the emergency depressuring valve. Trip (extinguish) all furnace fires (main burners and pilots). Maximize quench to the reactor beds. Stop all make-up hydrogen flow to the unit. Maximize feed/effluent exchanger bypass rate.
Call Refinery Fire Dept. to respond to fire
Immediate Actions
6.
If recycle gas compressor is the source of the leak, trip the machine and close the isolation valves. Follow the procedure for loss of recycle gas compressor.
7.
8.
Close the feed control valves to the 1st,2nd stage HCR & DHT reactors. Verify the chopper valves trip closed. Trip the reactor feed pumps -16-PA-CF-101/201A/B/301A/B
Secondary Actions
9.
Manually block in the fuel gas supply (pilot and main burners),
Open air resister fully of each burners, Stack damper to be kept full open
10.
11.
If possible (depending on the location of the emergency), preparations should be made to operate one of the MUG compressors on nitrogen. If safe to do so, start emergency nitrogen to the discharge of the RGC
Secondary Actions
12.
Monitor the liquid oil levels in the separators and carefully control liquid levels to prevent blowing high pressure gas into the low pressure system. Manually close level valves when levels go low. Stop and secure water injection and amine systems. Block in the fuel gas supply (pilot and main burners) to all furnaces and admit snuffing steam into the fireboxes. (In case of fire inside firebox) If the leak has not been contained, maintain a nitrogen flow out of the leak to prevent pulling air into the system.
13. 14.
15.
140 KBPD.
Incident Summary
in Bed 4 of a 5-bed reactor.
Temperature excursion began with a
hot spot
Hot spot most likely caused by poor flow and misdistribution (cause unidentified). Confusion was due to a variety of factors including:
Fluctuating temperature readings Stopping of make-up flow to second stage Misleading recycle H2 purity analysis Absence of audible high temperature alarms after the
temperatures exceeded maximum levels because they were confused about whether an excursion was actually occurring.
Penal officers were attempting to verify temperatures
in the reactor by having an person obtain temperature readings from the field panels under the reactors readings to the control room.
while field person continued to verify field instrumentation at the panel located at the bottom of the reactor
Unit was still not depressured!!
1400F (7600C), the reactor outlet piping ruptured causing a massive explosion and fire
0 35 :0 7: 0 35 :4 7: 0 36 :2 7: 0 37 :0 7: 0 37 :4 7: 0 38 :2 7: 0 39 :0 7: 0 39 :4 7: 0 40 :2 7: 0 41 :0 7: 0 41 :4 0
7:
7:
7:
7:
Bed 4 outlet Bed 5 inlet Bed 5 outlet Bed 5 Outlet Bed 5 outlet Bed 5 outlet Rx 3 inlet
deg F
0 33 :0
33 :4
34 :2
to support and encourage employees to operate reactors in a safe manner were inadequate. factors were poorly considered in the design and operation of the reactor temperature monitoring system. management was inadequate. readiness and maintenance was inadequate.
and support was inadequate. were outdated and incomplete. Hazard Analysis was flawed.
Procedures Process
Hydrocracker Unit
Sequence of Events
ascending reactor profile.
Plant running normally at maximum feed and Hydrogen make-up system started to sag. Only token feed cuts made (1000 Recycle loop starts to sag. Increased quenching robbed recycle hydrogen. Reactors start to overheat, temperature waves start.
B/P
(649C).
steam ring on the reactor bottom. at the bottom head. the piping to fail.
A small flange fire found and extinguished with a A second small fire was observed under the reactor Flame impingement on the quench piping caused A large fire erupted and the unit was subsequently
shutdown.
Lessons Learned
moved more aggressively in decreasing feed to stay within the available hydrogen make-up.
Operator moves were The Panel officers should have
proactive,
Running
Sequence of Events
Plant running normally at moderate rates 2:25-
potential fire
Sounded local evacuation in plant Field team used SCBAs and set fire monitor on
volunteers respond.
2:30
Isolation Block Valve on Pressure Drop Control Valve From Combined First-Stage and Second-Stage Effluent Stream (From Low Pressure Separators) to the Distillation Section Failed
Isolation Block Valve Bonnet
runs for instrumentation and other electrical equipment lasted approximately 15 minutes before collapse.
Conduit
Lessons Learned
Key items that led to safe shutdown and evacuation of unit:
Training, Training, Training Utilization of emergency shutdown devices Sequential dump system utilized to depressure units Make-up hydrogen choppers activated Remote shutdowns of all feed pumps. Site specific training of ALL
run failed.
line carrying hydrogen gas at 3,000 psi failed at a weld, resulting in a high pressure hydrogen fire. fire resulted in flame impingement on the calcium silicate insulation of the skirt for a 100-foot high reactor in a HCU. steel skirt for this reactor, which was 10 to 12 feet in diameter and had a wall thickness of seven inches, subsequently failed.
The The The
A 2-inch
falling reactor damaged air coolers and other process equipment, greatly increasing the size of the loss
for maintenance and the reactor was in a hydrogen purge cycle. percent of the refinery throughput capacity, including the complete HCU production, was lost for a period of five months.
Restoration of Approx. 25
two years.
the failure of a valve bonnet in a HP section of a 60,000 barrels-per-day HCU cloud formed from the release, ignited, and was followed by a large fire fed by escaping hydrocarbons at high pressure.
The explosion resulted in the A vapor
collapse of a large section of pipe rack and destruction of a large fin fan cooler mounted above the rack.
Many pumps were destroyed and a separator was badly damaged. Approximately 300 fire-fighters and 33 fire trucks participated in the two and a half hour effort to control the fire. Foam concentrate consumed totalled 3,200 gallons. The hydro cracker was out of service for 12 months.
excessively high temperatures, & the failure to depressurize the unit upon detection of high temperature.
The hydrocarbons apparently auto-ignited shortly after
failure, indicated that the pipe had expanded in circumference by approximately 5 inches. This caused a localized bulge in the pipe prior to rupture
Loss:Approx.$80,000,000
9:43 p.m.
in this 75,000 barrels-per-day refinery six-inch carbon steel 90-degree elbow (outside radius) and release of a hydrocarbon/hydrogen mixture to the atmosphere.
The vapour cloud ignited within seconds after The explosion resulted from the rupture of a
the rupture
shattered windows several miles away, was recorded as a sonic boom at the California Institute of Technology in Pasadena, approximately 20 miles from this 350-acre refinery.
An inspection after the failure found the line at
nearly full design thickness a short distance away from the failure.
the result of the thinning of the Schedule 120 carbon steel elbow due to long term erosion/corrosion.
The fire was finally extinguished at
11.(Approx.52 hrs.)
Loss: $96,000,000