SL NO.
FEEDER/PANEL NO.
A]
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
REVISION
NO.
O/C(51)
CTU-32
O/C(51)
CTU-32
B]
1
CTU-32
630/1A
150-600%, 0.1-1SEC.
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
C]
1
O/C(51)
CTU-32
O/C(51)
CTU-32
D]
1
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
E]
1
O/G FEEDER TO
BOILER ACDB # 9HC
(PANEL NO.3&17)
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
O/G FEEDER TO
TURBINE MCC # 9KA
(PANEL NO.7&13)
O/C(51)
CTU-32
1 of 29
REMARKS
SL NO.
4
FEEDER/PANEL NO.
CT/VT
RATIO
SETTING RANGE
REVISION
NO.
O/C(51)
CTU-32
630/1A
O/C(51)
CTU-32
250%, 0.6SEC.
BUSCOUPLER (PANEL
NO. 10)
O/C(51)
CTU-32
INCOMER (PANEL
NO.2&18)
O/C(51)
CTU-32
BUS PT(MODULE
NO.01B&19B)
U/V(27-1)
VAGM-23
415/110V 20-80%
70%
U/V(27-2)
VAGM-23
415/110V 20-80%
80%
T1
VTT-11
0.5-5 SEC.
0.5 SEC.
250%, 0.4SEC.
100%, TMS=0.1
100%, 5SEC.
2 SEC.
0
0
20%,
Rstab=600 Ohm
5.4 V, TMS=0.1
70%
110%
100%, TMS=0.1
150-600%, 0.1-1SEC.
RECOMMENDED
SETTINGS
150%, 0.4 SEC.
F)
1
BUSCOUPLER (PANEL
NO. 10)
O/C(51)
CTU-32
0/C(51V)
CDV-62B
2500/1A 50-200%
O/C(51A)
REVERSE
POWER (32)
DIFF.RELAY
(87)
CTU-12
CCUM-21
CAG-34
2500/1A 10-40%
E/F (64)
U/V(27)
0/V(59)
0/C(51V)
VDG-14
VAG-21
VAG-11
CDV-62B
5.4-20V
INCOMER FROM
STANDBY DG (PANEL
NO. 12)
2500/1A 50-200%
2 of 29
0
0
0
0
REMARKS
SL NO.
G]
1
2
H]
1
2
I]
1
2
J]
1
2
FEEDER/PANEL NO.
CT/VT
RATIO
SETTING RANGE
REVISION
NO.
O/C(51A)
REVERSE
POWER (32)
DIFF.RELAY
(87)
CTU-12
CCUM-21
E/F (64)
U/V(27)
0/V(59)
U/V(27)
VDG-14
VAG-21
VAG-11
VAGM-23
N/V (27)
T1
VAG-11
VTT-11
20%
0.5-5 SEC.
20%,
Rstab=600 Ohm
5.4 V, TMS=0.1
70%
110%
70%(27-1) 80%(272)
20%
0.5 SEC.
O/C(51)
CTU-32
O/C(51)
CTU-32
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
CTU-32
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
CAG-34
RECOMMENDED
SETTINGS
100%, 5SEC.
2 SEC.
2500/1A 10-40%
5.4-20V
20-80%
3 of 29
0
0
0
0
0
0
0
0
REMARKS
SL NO.
FEEDER/PANEL NO.
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
REVISION
NO.
K]
1
O/G FEEDER TO
BOILER ACDB # 10HC
(PANEL NO.3&17)
O/G FEEDER TO
TURBINE MCC # 10KA
(PANEL NO.7&13)
O/G FEEDER TO UNIT
SERVICE ACDB # 10QA
(PANEL NO.4&16)
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
O/C(51)
CTU-32
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
TIE TO EMERGENCY
SWBD #10DG (PANEL
NO.8 & 14)
O/C(51)
CTU-32
250%, 0.6SEC.
BUSCOUPLER (PANEL
NO.10)
INCOMER (PANEL
NO.2&18)
BUS PT(MODULE
NO.01B&19B)
O/C(51)
CTU-32
O/C(51)
CTU-32
U/V(27-1)
VAGM-23
415/110V 20-80%
70%
U/V(27-2)
T1
VAGM-23
VTT-11
415/110V 20-80%
0.5-5 SEC.
80%
0.5 SEC.
0
0
250%, 0.4SEC.
150%, 0.6SEC.
2500/1A 50-200%
100%, TMS=0.1
100%, 5SEC.
7
8
L)
1
BUSCOUPLER (PANEL
NO.10)
INCOMER FROM MAIN
DG (PANEL NO. 8)
O/C(51)
CTU-32
0/C(51V)
CDV-62B
O/C(51A)
CTU-12
REMARKS
SL NO.
M)
1
2
N)
1
2
FEEDER/PANEL NO.
INCOMER FROM
STANDBY DG (PANEL
NO.12 )
CT/VT
RATIO
SETTING RANGE
REVISION
NO.
20%, Rstab=600
Ohm
5.4 V, TMS=0.1
70%
110%
100%, TMS=0.1
100%, 5SEC.
2 SEC.
0
0
0
REVERSE
POWER (32)
DIFF.RELAY
(87)
CCUM-21
CAG-34
2500/1A 10-40%
E/F(64)
U/V(27)
0/V(59)
0/C(51V)
VDG-14
VAG-21
VAG-11
CDV-62B
5.4-20V
2500/1A 50-200%
O/C(51A)
REVERSE
POWER (32)
DIFF.RELAY
(87)
CTU-12
CCUM-21
E/F(64)
U/V(27)
0/V(59)
U/V(27)
VDG-14
VAG-21
VAG-11
VAGM-23
N/V (27)
T1
VAG-11
VTT-11
20%
0.5-5 SEC.
20%, Rstab=600
Ohm
5.4 V, TMS=0.1
70%
110%
70%(27-1) 80%(272)
20%
0.5 SEC.
CTU-32
CTU-32
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
CAG-34
2500/1A 1-10SEC.
RECOMMENDED
SETTINGS
2 SEC.
2500/1A 10-40%
5.4-20V
20-80%
5 of 29
0
0
0
0
0
0
0
0
0
0
REMARKS
SL NO.
O)
1
2
P)
1
2
FEEDER/PANEL NO.
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
REVISION
NO.
CTU-32
CTU-32
CTU-32
CTU-32
Q)
1
O/G FEEDER TO
VENTILATION MCC #
9TA (PANEL NO. 3&12)
O/G FEEDER TO
STATION SERVICE MCC
# 0QA (PANEL NO. 7&10)
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
O/C(51)
CTU-32
O/C(51)
CTU-32
O/C(51)
CTU-32
O/C(51)
CTU-32
U/V(27-1)
VAGM-23
415/110V 20-80%
70%
U/V(27-2)
T1
VAGM-23
VTT-11
415/110V 20-80%
0.5-5SEC.
80%
0.5 SEC.
0
0
5
6
7
6 of 29
REMARKS
SL NO.
R)
1
2
S)
1
2
T)
1
2
FEEDER/PANEL NO.
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
REVISION
NO.
CTU-32
CTU-32
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
CTU-32
U)
1
O/G FEEDER TO
VENTILATION MCC #
10TA (PANEL NO. 3&12)
O/C(51)
CTU-32
630/1A
150-600%, 0.1-1SEC.
O/G FEEDER TO
STATION SERVICE MCC
# 0QB (PANEL NO. 7&10)
O/C(51)
CTU-32
O/C(51)
CTU-32
O/C(51)
CTU-32
O/C(51)
CTU-32
U/V(27-1)
VAGM-23
70%
5
6
7
415/110V 20-80%
7 of 29
REMARKS
SL NO.
FEEDER/PANEL NO.
V)
1
2
W)
1
1
2
3
X)
1
2
3
Y)
1
SETTING RANGE
415/110V 20-80%
0.5-5SEC.
RECOMMENDED
SETTINGS
80%
0.5 SEC.
REVISION
NO.
0
0
CTU-32
CTU-32
CTU-32
CTU-32
O/C(51)
CTU-32
U/V(27-1)
VAGM-23
415/110V 20-80%
70%
U/V(27-2)
T1
VAGM-23
VTT-11
415/110V 20-80%
0.5-5SEC.
80%
0.5SEC.
0
0
VAGM-23
VTT-11
CT/VT
RATIO
CTU-32
CTU-32
70%
80%
0.5SEC.
0
0
VAGM-23
415/110V 20-80%
VAGM-23
VTT-11
415/110V 20-80%
0.5-5SEC.
CTU-32
630/1A
150-600%, 0.1-1SEC.
8 of 29
REMARKS
SL NO.
FEEDER/PANEL NO.
Z)
1
AA)
1
RECOMMENDED
SETTINGS
350%, 0.4 SEC.
REVISION
NO.
CTU-32
630/1A
150-600%, 0.1-1SEC.
CTU-32
CT/VT
RATIO
630/1A
SETTING RANGE
150-600%, 0.1-1SEC.
O/G FEEDER TO
SERVICE BLDG A/C &
VENT MCC # 0TB
(PANEL NO.10&13)
O/C(51)
CTU-32
BUSCOUPLER (PANEL
NO.11)
INCOMER (PANEL
NO.8&16)
BUS PT (07B& 15B)
O/C(51)
CTU-32
O/C(51)
CTU-32
U/V(27-1)
U/V(27-2)
T1
VAGM-23
VAGM-23
VTT-11
70%
80%
0.5SEC.
0
0
0
4
5
AB)
1
2
AC)
1
415/110V 20-80%
415/110V 20-80%
0.5-5SEC.
CTU-32
CTU-32
250%
5%
0.1SEC
0
0
CAG-37
RXIG-22
3000/1
250-2000%
3000/1A 5-10%
0.1-1SEC.
9 of 29
REMARKS
SL NO.
FEEDER/PANEL NO.
AD)
1
CT/VT
RATIO
R.B.TIMER-2B
O/C(50)
3000/1
5%
0.1SEC
0.5SEC.
70%
0
0
0
0
20%
0
0
NO VOLT (27N)
VAG-21
20%
TIMER (27T)
VTT 11
0.5 - 5SEC
0.5SEC.
250-2000%
250%
3000/1A 5-10%
0.1-1SEC.
0.1-1SEC.
3000/1 250-2000%
5%
0.1SEC
0.3SEC.
270%
0
0
0
0
3000/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
5%
0.1SEC
0.5SEC.
70%
0
0
0
0
20%
11 KV SWITCHGEAR # 9BA
O/G FEEDER TO
O/C(51)
11/3.5KV, 16MVA TRF
9CATO1 (PANEL NO.3)
E/F(50N2)
CAG-37
RXIG-22
CAG-37
RXIG-22
VAGM-23
3000/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
REVISION
NO.
VAGM-23
RXIG-22
0.1-1SEC.
250-2000%
RECOMMENDED
SETTINGS
0.3SEC.
270%
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
U/V (27M)
TIMER (27T)
AE)
1
CAG-37
SETTING RANGE
3000/1
VAG-21
20%
VTT 11
0.5 - 5SEC
0.5SEC.
CTU-32
100mA
CTUM-15
50/1A
10-160mA
10 of 29
REMARKS
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA
UNIT SER. TRF #9DAT01
(PANEL NO.4)
O/G FEEDER TO
11/.433KV, 1600kVA CT
TRF - 9A (PANEL NO.5)
O/G FEEDER TO
11/.433KV, 1600kVA ESP
SER TRF - 9DBT01,
9DCT01, 9DDT01,
9DET01 (PANEL NO.6,
8, 9, 10)
CT/VT
RATIO
SETTING RANGE
1000/1A 15%
RECOMMENDED
SETTINGS
CURRENT
SETTING=15%
BIAS
SETTING=15%,
REVISION
NO.
150V
5%, 0.5SEC.
1250%
100mA
0
1
DIFFERENTIAL
RELAY (87T)
DTH-31
REF(64R)
FAC-14
3000/1
25-175V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
20%
Rstab=900 ohm
1200%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
20%
Rstab=900 ohm
1200%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
2500/1
10-40%
20%
Rstab=900 ohm
11 of 29
REMARKS
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA ASH
HANDLING SER TRF 9A (PANEL NO.17)
AF)
1
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1500%
REVISION
NO.
100mA
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
200/1A
250-2000%
1250%
O/C(51)
E/F(50N2)
O/C(50)
CTU-32
CTUM-15
CAG-37
260%, 0.5SEC.
100mA
250%
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
INCOMER(PANEL NO. 1)
O/C (50)
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
2500/1A 250-2000%
5%
0.1SEC
0.5SEC
250%
0
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
5%
0.1SEC
0.7SEC
0
0
0
CTU-32
100mA
O/G FEEDER TO
11/2.3KV, 3250kVA VFD
TRF (PANEL NO.15&16)
11 KV SWITCHGEAR # 9BB
O/G FEEDER TO
O/C(51)
11/3.5KV, 16MVA TRF
9CATO2 (PANEL NO.12)
E/F(50N2)
CAG-37
CTUM-15
50/1A
10-160mA
12 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA
UNIT SER. TRF #9DAT02
(PANEL NO.13)
O/G FEEDER TO
11/.433KV, 1600kVA CT
TRF - 9B (PANEL NO.16)
O/G FEEDER TO
11/.433KV, 1600kVA ESP
SER TRF - 9DBT02,
9DCT02, 9DDT02,
9DET02 (PANEL NO.
8,6,5 & 9)
CT/VT
RATIO
SETTING RANGE
DIFFERENTIAL
RELAY (87T)
DTH-31
1000/1A 15%
REF(64R)
FAC-14
3000/1
25-175V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
100/1A
O/C(51)
CTU-32
E/F(50N2)
REF(64R)
RECOMMENDED
SETTINGS
CURRENT
SETTING=15%
BIAS
SETTING=15%,
REVISION
NO.
150V
5%, 0.5SEC.
1250%
100mA
Rstab=900
ohm
1200%
20%
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
100mA
0
1
250-2000%
20%
Rstab=900 ohm
1200%
100/1A
150-600%, 0.3-3SEC.
CTUM-15
50/1A
10-160mA
100mA
CAG-14
2500/1
10-40%
20%
Rstab=900 ohm
13 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA ASH
HANDLING SER TRF 9B (PANEL NO.10)
AG)
1
O/G FEEDER TO
11/2.3KV, 3250kVA VFD
TRF-ID FAN 9B (PANEL
NO.1&2)
INCOMER(PANEL NO.
19)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1500%
REVISION
NO.
100mA
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
200/1A
250-2000%
1250%
O/C(51)
E/F(50N2)
O/C(50)
CTU-32
CTUM-15
CAG-37
260%, 0.5SEC.
100mA
250%
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
O/C (50)
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
2500/1A 250-2000%
5%
0.1SEC
0.5SEC
250%
0
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
5%
0.1SEC
0.7SEC
0
0
0
CTU-32
100mA
11 KV SWITCHGEAR # 10BA
O/G FEEDER TO
O/C(51)
11/3.5KV, 16MVA TRF
10CATO1 (PANEL NO.3)
E/F(50N2)
CAG-37
CTUM-15
50/1A
10-160mA
14 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA
UNIT SER. TRF
#10DAT01 (PANEL
NO 4)
O/G FEEDER TO
11/.433KV, 1600kVA CT
TRF - 10A (PANEL NO.5)
O/G FEEDER TO
11/.433KV, 1600kVA ESP
SER TRF - 10DBT01,
10DCT01, 10DDT01,
10DET01 (PANEL NO.6,
8, 9, 10)
CT/VT
RATIO
SETTING RANGE
1000/1A 15%
RECOMMENDED
SETTINGS
CURRENT
SETTING=15%
BIAS
SETTING=15%,
REVISION
NO.
150V
5%, 0.5SEC.
1250%
100mA
0
1
DIFFERENTIAL
RELAY (87T)
DTH-31
REF(64R)
FAC-14
3000/1
25-175V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
20%
Rstab=900 ohm
1200%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
20%
Rstab=900 ohm
1200%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
2500/1
10-40%
20%
Rstab=900 ohm
15 of 29
REMARKS
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA ASH
HANDLING SER TRF 10A (PANEL NO.17)
AH)
1
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1500%
REVISION
NO.
100mA
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
200/1A
250-2000%
1250%
O/C(51)
E/F(50N2)
O/C(50)
CTU-32
CTUM-15
CAG-37
260%, 0.5SEC.
100mA
250%
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
INCOMER(PANEL NO. 1)
O/C (50)
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
2500/1A 250-2000%
5%
0.1SEC
0.5SEC
250%
0
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
5%
0.1SEC
0.7SEC
0
0
0
CTU-32
100mA
O/G FEEDER TO
11/2.3KV, 3250kVA VFD
TRF (PANEL NO.15&16)
11 KV SWITCHGEAR # 10BB
O/G FEEDER TO
O/C(51)
11/3.5KV, 16MVA TRF
10CATO2 (PANEL
NO 12)
E/F(50N2)
CAG-37
CTUM-15
50/1A
10-160mA
16 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA
UNIT SER. TRF
#10DAT02 (PANEL
NO 13)
O/G FEEDER TO
11/.433KV, 1600kVA CT
TRF - 10B (PANEL
NO.16)
O/G FEEDER TO
11/.433KV, 1600kVA ESP
SER TRF - 10DBT02,
10DCT02, 10DDT02,
10DET02 (PANEL NO.
9,8,4 & 5)
CT/VT
RATIO
SETTING RANGE
DIFFERENTIAL
RELAY (87T)
DTH-31
1000/1A 15%
REF(64R)
FAC-14
3000/1
25-175V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
100/1A
O/C(51)
CTU-32
E/F(50N2)
REF(64R)
RECOMMENDED
SETTINGS
CURRENT
SETTING=15%
BIAS
SETTING=15%,
REVISION
NO.
150V
5%, 0.5SEC.
1250%
100mA
Rstab=900
ohm
1200%
20%
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
100mA
0
1
250-2000%
20%
Rstab=900 ohm
1200%
100/1A
150-600%, 0.3-3SEC.
CTUM-15
50/1A
10-160mA
100mA
CAG-14
2500/1
10-40%
20%
Rstab=900 ohm
17 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA ASH
HANDLING SER TRF 10B (PANEL NO.10)
AI)
1
O/G FEEDER TO
11/2.3KV, 3250kVA VFD
TRF-ID FAN 10B (PANEL
NO.1&2)
INCOMER(PANEL NO.
19)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1500%
REVISION
NO.
100mA
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
200/1A
250-2000%
1250%
O/C(51)
E/F(50N2)
O/C(50)
CTU-32
CTUM-15
CAG-37
260%, 0.5SEC.
100mA
250%
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
O/C (50)
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
2500/1A 250-2000%
5%
0.1SEC
0.5SEC
250%
0
0
0
1
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
5%
0.1SEC
0.7SEC
0
0
0
CAG-37
125/1A
250-2000%
1250%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
11 KV SWITCHGEAR # 0BA
O/G FEEDER TO
O/C(50)
11/.433KV, 2000kVA STN
SER. TRF #0DAT01
(PANEL NO.4)
CAG-37
18 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA OFF
SITE SER. TRF
#0DDT01 (PANEL
NO 12)
O/G FEEDER TO
11/.433KV, 1600kVA CHP
TRF 3 & 5 (PANEL
NO.14 & 17)
O/G FEEDER TO
11/.433KV, 1250kVA CHP
TRF - 7 (PANEL NO.13)
O/G FEEDER TO
11/.433KV, 1000kVA ASH
WATER TAC TRF - 1
(PANEL NO.7)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
20%
Rstab=900 ohm
1250%
REVISION
NO.
100mA
0
1
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
100/1A
250-2000%
20%
Rstab=900 ohm
1200%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
20%
Rstab=900 ohm
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
1600/1
10-40%
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
1500%
19 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
SL NO.
FEEDER/PANEL NO.
INCOMER(PANEL NO. 1)
RECOMMENDED
SETTINGS
210%, 0.5 SEC.
REVISION
NO.
100mA
20%
Rstab=1000 ohm
1200%
100mA
10%
Rstab=1000 ohm
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
50/1A
250-2000%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
O/C(50)
CAG-37
2500/1
250-2000%
250%
E/F(50N3)
O/C(50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1 250-2000%
5%
250%
0
0
E/F(50N3)
O/C (50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1A 250-2000%
5%
250%
0
0
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
U/V(27M)
N/V(27N)
TIMER
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
20%
0.5-5SEC
5%
0.1SEC
0.7SEC
70%
20%
0.5SEC
0
0
0
0
0
0
SETTING RANGE
O/C(51)
O/G FEEDER TO
11/.433KV, 500kVA
SWYD SER TRF - 1
(PANEL NO.8)
CT/VT
RATIO
10
AJ)
11 KV SWITCHGEAR # 0BB
VAGM-23
VAG-21
VTT 11
20 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/3.5KV, 5MVA CHP HT
TRF -1 (PANEL NO.2)
O/G FEEDER TO
11/3.5KV, 4.5MVA AHP
HT TRF -1 (PANEL NO.6)
O/G FEEDER TO
11/.433KV, 2000kVA STN
SER. TRF #0DBT01
(PANEL NO.12)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
260%, 0.5 SEC.
REVISION
NO.
100mA
CURRENT
SETTING=15%
BIAS
SETTING=15%,
0
0
125V
5%, 0.5SEC.
O/C(51)
CTU-32
300/1A
150-600%, 0.3-3SEC.
E/F(50N2)
DIFFERENTIAL
RELAY (87T)
CTUM-15
DTH-31
50/1A
300/1A
10-160mA
15%
REF(64R)
FAC-14
1000/1
25-175V
BACK UP
E/F(51N)
O/C(51)
CTU 15
300/1
1-16%, 0.3-3SEC.
CTU-32
300/1A
150-600%, 0.3-3SEC.
E/F(50N2)
DIFFERENTIAL
RELAY (87T)
CTUM-15
DTH-31
50/1A
300/1A
10-160mA
15%
100mA
CURRENT
SETTING=15%
BIAS
SETTING=15%,
0
0
REF(64R)
FAC-14
1000/1
25-175V
125V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
5%, 0.5SEC.
CAG-37
125/1A
250-2000%
1250%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
3000/1
10-40%
20%
Rstab=900 ohm
21 of 29
REMARKS
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
SL NO.
4
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 2000kVA
FIRE WATER PH TRF
#0DCT01 (PANEL
NO 13)
O/G FEEDER TO
11/.433KV, 1250kVA
MAKE-UP/RAW WATER
PH TRF - 1 (PANEL
NO 7)
O/G FEEDER TO
11/.433KV, 1000kVA CHP
TRF - 1 (PANEL NO.3)
O/G FEEDER TO
11/.433KV, 1000kVA CW
SER TRF - 1 (PANEL
NO.9)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1250%
REVISION
NO.
100mA
0
1
O/C(50)
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
20%
Rstab=900 ohm
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
1600/1
10-40%
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
1600/1
10-40%
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
22 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
SL NO.
10
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA
FUEL OIL PH TRF 0DET01 (PANEL NO.15)
O/G FEEDER TO
11/.433KV, 750kVA WTP
SER TRF - 1 (PANEL
NO.11)
O/G FEEDER TO
11/.433KV, 500kVA SILO
SER TRF - 1 (PANEL
NO.11)
CT/VT
RATIO
SETTING RANGE
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
50/1A
250-2000%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
O/C(50)
CAG-37
50/1A
250-2000%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
23 of 29
RECOMMENDED
SETTINGS
100mA
REVISION
NO.
20%
Rstab=1000 ohm
1500%
100mA
20%
Rstab=1000 ohm
1600%
100mA
10%
Rstab=1000 ohm
1200%
100mA
10%
Rstab=1000 ohm
REMARKS
0
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
SL NO.
FEEDER/PANEL NO.
11
12
13
14
AK)
1
INCOMER(PANEL NO.
18)
250-2000%
RECOMMENDED
SETTINGS
250%
REVISION
NO.
CAG-37
E/F(50N3)
O/C(50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1 250-2000%
5%
250%
0
0
E/F(50N3)
O/C (50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1A 250-2000%
5%
250%
0
0
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
U/V(27M)
N/V(27N)
TIMER
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
20%
0.5-5SEC
5%
0.1SEC
0.7SEC
70%
20%
0.5SEC
0
0
0
0
0
0
CAG-37
125/1A
250-2000%
1250%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
125/1A
250-2000%
20%
Rstab=900 ohm
1250%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
3000/1
10-40%
20%
Rstab=900 ohm
VAGM-23
VAG-21
VTT 11
2500/1
SETTING RANGE
O/C(50)
11 KV SWITCHGEAR # 0BC
O/G FEEDER TO
O/C(50)
11/.433KV, 2000kVA STN
SER. TRF #0DAT02
(PANEL NO.4)
O/G FEEDER TO
11/.433KV, 2000kVA OFF
SITE SER. TRF
#0DDT02 (PANEL
NO 12)
CT/VT
RATIO
24 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1600kVA CHP
TRF 4& 6 (PANEL NO.13
& 17)
O/G FEEDER TO
11/.433KV, 1250kVA CHP
TRF - 8 (PANEL NO.14)
O/G FEEDER TO
11/.433KV, 1000kVA ASH
WATER TAC TRF - 2
(PANEL NO.7)
O/G FEEDER TO
11/.433KV, 500kVA
SWYD SER TRF - 2
(PANEL NO.8)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1200%
REVISION
NO.
100mA
0
1
O/C(50)
CAG-37
100/1A
250-2000%
O/C(51)
CTU-32
100/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
2500/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
20%
Rstab=900 ohm
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
1600/1
10-40%
20%
Rstab=1000 ohm
O/C(50)
CAG-37
75/1A
250-2000%
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
1600/1
10-40%
20%
Rstab=1000 ohm
O/C(50)
CAG-37
50/1A
250-2000%
1200%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
25 of 29
REMARKS
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
SL NO.
FEEDER/PANEL NO.
INCOMER(PANEL NO. 1)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
100mA
REVISION
NO.
10%
Rstab=1000 ohm
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
O/C(50)
CAG-37
2500/1
250-2000%
250%
E/F(50N3)
O/C(50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1 250-2000%
5%
250%
0
0
E/F(50N3)
O/C (50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1A 250-2000%
5%
250%
0
0
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
U/V(27M)
N/V(27N)
TIMER
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
20%
0.5-5SEC
5%
0.1SEC
0.7SEC
70%
20%
0.5SEC
0
0
0
0
0
0
10
AL)
1
11 KV SWITCHGEAR # 0BD
O/G FEEDER TO
O/C(51)
11/3.5KV, 5MVA CHP HT
TRF -2 (PANEL NO.2)
VAGM-23
VAG-21
VTT 11
CTU-32
300/1A
150-600%, 0.3-3SEC.
E/F(50N2)
DIFFERENTIAL
RELAY (87T)
CTUM-15
DTH-31
50/1A
300/1A
10-160mA
15%
100mA
CURRENT
SETTING=15%
BIAS
SETTING=15%,
0
0
REF(64R)
FAC-14
1000/1
25-175V
125V
BACK UP
E/F(51N)
CTU 15
300/1
1-16%, 0.3-3SEC.
5%, 0.5SEC.
26 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/3.5KV, 4.5MVA AHP
HT TRF -2 (PANEL NO.1)
O/G FEEDER TO
11/.433KV, 2000kVA STN
SER. TRF #0DBT02
(PANEL NO.11)
O/G FEEDER TO
11/.433KV, 2000kVA
FIRE WATER PH TRF
#0DCT02 (PANEL
NO 12)
O/G FEEDER TO
11/.433KV, 1250kVA
MAKE-UP/RAW WATER
PH TRF - 2 (PANEL
NO 5)
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
240%, 0.5 SEC.
REVISION
NO.
100mA
CURRENT
SETTING=15%
BIAS
SETTING=15%,
0
0
125V
5%, 0.5SEC.
1250%
100mA
0
1
O/C(51)
CTU-32
300/1A
150-600%, 0.3-3SEC.
E/F(50N2)
DIFFERENTIAL
RELAY (87T)
CTUM-15
DTH-31
50/1A
300/1A
10-160mA
15%
REF(64R)
FAC-14
1000/1
25-175V
BACK UP
E/F(51N)
O/C(50)
CTU 15
300/1
1-16%, 0.3-3SEC.
CAG-37
125/1A
250-2000%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
125/1A
250-2000%
20%
Rstab=900 ohm
1250%
O/C(51)
CTU-32
125/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
100mA
REF(64R)
CAG-14
3000/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
20%
Rstab=900 ohm
1500%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
27 of 29
REMARKS
CT located in 3.3kV
swgr & trfr neutral
CT located in
transformer neutral
CT located in 415V
swgr & trfr neutral
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 1000kVA CHP
TRF - 2 (PANEL NO.3)
O/G FEEDER TO
11/.433KV, 1000kVA CW
SER TRF - 2 (PANEL
NO.9)
O/G FEEDER TO
11/.433KV, 1000kVA
FUEL OIL PH TRF 0DET02 (PANEL NO.14)
CT/VT
RATIO
SETTING RANGE
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
O/C(50)
CAG-37
75/1A
250-2000%
O/C(51)
CTU-32
75/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1600/1
10-40%
28 of 29
RECOMMENDED
SETTINGS
100mA
REVISION
NO.
20%
Rstab=1000 ohm
1500%
100mA
20%
Rstab=1000 ohm
1500%
100mA
20%
Rstab=1000 ohm
1500%
100mA
20%
Rstab=1000 ohm
REMARKS
0
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 12 ohm.
CT located in 415V
swgr & trfr neutral
SL NO.
FEEDER/PANEL NO.
O/G FEEDER TO
11/.433KV, 750kVA WTP
SER TRF - 2 (PANEL
NO. 10)
10
11
O/G FEEDER TO
11/.433KV, 500kVA SILO
SER TRF - 2 (PANEL
NO.4)
12
13
INCOMER(PANEL NO.
17)
14
CT/VT
RATIO
SETTING RANGE
RECOMMENDED
SETTINGS
1600%
REVISION
NO.
100mA
10%
Rstab=1000 ohm
1200%
100mA
10%
Rstab=1000 ohm
O/C(50)
CAG-37
50/1A
250-2000%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
O/C(50)
CAG-37
50/1A
250-2000%
O/C(51)
CTU-32
50/1A
150-600%, 0.3-3SEC.
E/F(50N2)
CTUM-15
50/1A
10-160mA
REF(64R)
CAG-14
1000/1
10-40%
O/C(50)
CAG-37
2500/1
250-2000%
250%
E/F(50N3)
O/C(50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1 250-2000%
5%
250%
0
0
E/F(50N3)
O/C (50)
RXIG-22
CAG-37
2500/1A 5-10%
2500/1A 250-2000%
5%
250%
0
0
E/F(50N3)
R.B.TIMER-2A
R.B.TIMER-2B
U/V(27M)
N/V(27N)
TIMER
RXIG-22
2500/1A 5-10%
0.1-1SEC.
0.1-1SEC.
20-80%
20%
0.5-5SEC
5%
0.1SEC
0.7SEC
70%
20%
0.5SEC
0
0
0
0
0
0
VAGM-23
VAG-21
VTT 11
29 of 29
REMARKS
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
CT located in 415V
swgr & trfr neutral . Rct
assumed as 7 ohm.
0.9 VA
18 ohm
10 %
2000
1.732 x 0.433 x 0.9 x 0.1
29.63 kA
Voltage across relay (Vr) =
29.63 x 1000 x 18
3000
=
Rr
Rstab
177.78
0.2
866.4
Selected Rstab
2)
177.78 V
22.5 Ohm
22.5 Ohm
22.5
900 ohm
1600
KVA Transformer
CT Ratio =
2500 /1 A
Relay selected to be set at 20%
VA burden of relay at 20% setting =
CT resistance (RCT) <=
Transformer impedance =
0.9 VA
15 ohm
8%
1600
1.732 x 0.433 x 0.9 x 0.08
29.63 kA
Voltage across relay (Vr) =
29.63 x 1000 x 15
2500
177.78 V
Page 1 of 4
Rstab
177.78
0.2
866.4
Selected Rstab
3)
22.5
900 ohm
1250
KVA Transformer
CT Ratio =
1600 /1 A
Relay selected to be set at 20%
VA burden of relay at 20% setting =
CT resistance (RCT) <=
12 ohm
Transformer impedance =
6.25 %
0.9 VA
(assumed)
1250
1.732 x 0.433 x 0.9 x 0.063
29.63 kA
Voltage across relay (Vr) =
29.63 x 1000 x 12
1600
222.225 V
222.225
0.2
1088.625
Selected Rstab
4)
22.5
1000 ohm
1000
KVA Transformer
CT Ratio =
1600 /1 A
Relay selected to be set at 20%
VA burden of relay at 20% setting =
CT resistance (RCT) <=
12 ohm
Transformer impedance =
5.00 %
Fault current considering 10% negative tolerance
1000
1.732 x 0.433 x 0.9 x 0.05
29.63 kA
Page 2 of 4
0.9 VA
(assumed)
22.5 Ohm
29.63 x 1000 x 12
1600
222.225 V
222.225
0.2
1088.625
Selected Rstab
5)
22.5 Ohm
22.5
1000 ohm
500
KVA Transformer
(Same is applicable for 630/750 KVA Trf)
CT Ratio =
1000 /1 A
Relay selected to be set at 10%
VA burden of relay at 10% setting =
0.9 VA
CT resistance (RCT) <=
7 ohm
(assumed)
Transformer impedance =
5.00 %
Fault current considering 10% negative tolerance
500
1.732 x 0.433 x 0.9 x 0.05
14.82 kA
Voltage across relay (Vr) =
14.82 x 1000 x 7
1000
103.74 V
103.74
0.1
947.4
Selected Rstab
90
1000 ohm
Page 3 of 4
90 Ohm
B)
CT ratio
=
2500 /1 A
CAG 34
10-40%
Ralay to be set at 20%
DG FLC =
1500
1.732 x 0.415
2086.87 =
0.12
Fault current =
CT secondary current =
2086.87 A
17390.58 A
17390.58 '=
2500
6.956 A
RCT =
15 ohm
Lead resistance 2 Rl =
VR =
RR =
2 x 8.87 x 150
=
1000
6.956 (15+2.661) =
122.854 V
0.9 =
(0.2)
Rstab=
22.5 ohm
122.854 - 22.5
0.2
Set at 600 ohm , 20%
591.77 ohm
Page 4 of 4
2.661 ohm