TI135R/09/en 71084968
TMT111
Input
Measured variable Measuring range Temperature (temperature linear), resistance and voltage. Depending upon the sensor connection and input signal. The transmitter evaluates a number of different measurement ranges.
Designation Pt100 Pt500 Pt1000 Pt100 Ni100 Ni500 Ni1000 Ni120 Resistance transmitter Measurement range limits -200 to 850 C (-328 to 1562 F) -200 to 250 C (-328 to 482 F) -200 to 250 C (-328 to 482 F) -200 to 649 C (-328 to 1200 F) -60 to 250 C (-76 to 482 F) -60 to 150 C (-76 to 302 F) -60 to 150 C (-76 to 302 F) -70 to 270 C (-94 to 518 F) Minimum measurement range 10 K 10 K 10 K 10 K 10 K 10 K 10 K 10 K
Type of input Resistance thermometer (RTD) as per IEC 60751 ( = 0.00385) as per JIS C 1604-81 ( = 0.003916) as per DIN 43760 ( = 0.006180)
Connection type: 2-wire, 3-wire or 4-wire connection For 2-wire circuit, compensation for wire resistance possible (0 to 20 ) Sensor cable resistance max. 40 per cable Sensor current: 0.6 mA 10 to 400 10 to 2000 0 to +1820 C -270 to +1000 C -210 to +1200 C -270 to +1372 C -270 to +1300 C -50 to +1768 C -50 to +1768 C -270 to +400 C 0 to +2320 C 0 to +2495 C (32 to 3308 F) (-454 to 1832 F) (-346 to 2192 F) (-454 to 2501 F) (-454 to 2372 F) (-58 to 3214 F) (-58 to 3214 F) (-454 to 752 F) (32 to 4208 F) (32 to 4523 F) 10 100 500 K 50 K 50 K 50 K 50 K 500 K 500 K 50 K 500 K 500 K 50 K 50 K
Resistance B (PtRh30-PtRh6) E (NiCr-CuNi) J (Fe-CuNi) K (NiCr-Ni) N (NiCrSi-NiSi) R (PtRh13-Pt) S (PtRh10-Pt) T (Cu-CuNi) C (W5Re-W26Re) D (W3Re-W25Re) L (Fe-CuNi) U (Cu-CuNi)
Internal cold junction (Pt100) or external 0 C to +80 C (32 to 176 F) Cold junction accuracy: 1 K Voltage transmitters (mV) Millivolt transmitter (mV) -10 to 75 mV 5 mV
Endress+Hauser
TMT111
Output
Output signal Signal on alarm Analog 4 to 20 mA, 20 to 4 mA Underranging: Linear drop to 3.8 mA Overranging: Linear rise to 20.5 mA Sensor breakage; Sensor short circuit1: 3.6 mA or 21.0 mA (for configuration 21.0 mA, output 21.5 mA is guaranteed) Max. (VPower supply - 12 V) / 0.022 A (Current output) Temperature linear, resistance linear, voltage linear
Load Linearization / transmission behavior Filter Galvanic isolation Min. current consumption Current limit Switch-on delay
Digital filter 1st degree: 0 to 8 s U = 2 kV AC (Input/output) 3.5 mA 23 mA 4 s (during power up Ia 3.8 mA)
Power supply
Electrical connection
T09-TMT111-04-10-XX-en-000
Connection terminal
Supply voltage
Ub = 12 to 35 V, polarity protected
1.
Endress+Hauser
TMT111
Residual ripple
Performance characteristics
Response time Reference operating conditions 1s Calibration temperature: +25 C 5 K (77 F 9 F) Supply voltage: 24 V DC 4-wire circuit for resistance adjustment The accuracy data are typical values and correspond to a standard deviation of 3 (normal distribution), i.e. 99.8% of all the measured values achieve the given values or better values.
Type Resistance thermometer RTD Pt100, Ni100 Pt500, Ni500 Pt1000, Ni1000 K, J, T, E, L, U N, C, D S, B, R Measurement accuracy3 0.2 K or 0.08% 0.5 K or 0.20% 0.3 K or 0.12% typ. 0.5 K or 0.08% typ. 1.0 K or 0.08% typ. 2.0 K or 0.08% Measurement accuracy3 0.1 or 0.08% 1.5 or 0.12% 20 V or 0.08%
Thermocouple TC
Measurement range Resistance transmitter () Voltage transmitter (mV) 10 to 400 10 to 2000 -10 to 75 mV
0.01%/V deviation from 24 V1 Resistance thermometer (RTD): Td = (15 ppm/K * max. meas. range + 50 ppm/K * preset meas. range) * Resistance thermometer Pt100: Td = (15 ppm/K * (range end value + 200) + 50 ppm/K * preset meas. range) * Thermocouple (TC): Td = (50 ppm/K * max. meas. range + 50 ppm/K * preset meas. range) * = Deviation of the ambient temperature according to the reference condition +25 C 5 K (77 F 9 F).
0.1K/year2 ( 0.18 F/year) or 0.05%/year2 3 0.02%/100 1 Pt100 DIN IEC 60751 Cl. B (internal reference junction for thermocouples TC)
1. 2. 3.
All data is related to a measurement end value According to reference conditions % is related to the adjusted measurement range (the value to be applied is the greater one).
Endress+Hauser
TMT111
Installation conditions
Installation instructions Mounting location:
T09-TMT111-17-10-06-xx-000
Installation on DIN rail according to IEC 60715, TH35 - follow sequence 1 and 2
Orientation: No restrictions
Environmental conditions
Ambient temperature Storage temperature Climate class Degree of protection Electromagnetic compatibility (EMC) Humidity 40 to +85 C (-40 to 185 F) - for Ex-areas see Ex-certification -40 to +100 C (-40 to 212 F) According to IEC 60654-1, Class C IP20 (NEMA 1) Interference immunity and interference emission according to IEC 61326 and NAMUR NE 21
Condensation as per IEC 60 068-2-33 permitted Max. rel. humidity: 95% as per IEC 60068-2-30
Mechanical construction
Design, dimensions Installation on DIN rail according to IEC 60715, TH35
T09-TMT111-06-10-XX-XX-000
Dimensions in mm (inches)
Endress+Hauser
TMT111
Approx. 90 g (3.17 oz) Housing: Plastic PC/ABS, UL 94V0 Keyed plug-in screw terminals, core size max. 2.5 mm (16 AWG) solid, or strands with ferrules
Human interface
Display elements Operating elements A yellow illuminated LED signalizes: Device is operational. No operating elements are available on the temperature transmitter. The temperature transmitter will be configured by remote operation with the PC software ReadWin 2000. Available configuration kits see chapter accessorieson page 10.
Operation via PC
Menu Standard settings Configurable parameters Service functions Sensor type Connection (2-, 3- or 4-wire connection) Units C, F Measurements range limits (depends on selected sensor type) Cold junction compensation (internal/external on TC connection) Temperature external (on TC with cold junction compensation external) Compensation resistance (0 to 20 ) on RTD 2-wire connection Fault condition reaction ( 3.6 mA or 21.0 mA), for configuration 21.0 mA, output 21.5 mA is guaranteed Analog output: 4 to 20 mA (standard) or 20 to 4 mA (inverse) Filter, optional from 0 to 8 s Zero point, offset (-9.9 to +9.9 K / -18 to +18 F) TAG (Measurement point description)
Expanded settings
Temperature range
Endress+Hauser
TMT111
Application: Equipment Category: Explosive gas-air mixtures (G) Category 1 Zone 1 or 2, Apparatus with external circuits for connection to equipment in category 1
Note! For Zone 0: This apparatus may be installed in Zones 1, 2 and the sensor circuit can be fed into Zone 0. FM approval
TMT111 IS / Class I / Division 1 / Groups ABCD / T4/T5/T6 Class I / Zone 0 / AEx ia IIC / T4/T5/T6 NI / Class I / Division 2 / Groups ABCD / T4/T5/T6 Ui 30 V DC Ii 100 mA Pi 750 mW Ci = negligible small Li = negligible small U0 2.5 V DC I0 2.2 mA P0 1.4 mW Group A, B Group C Group D T6 T5 T4 IIC IIB IIA La = L0 = 1000 mH La = L0 = 1000 mH La = L0 = 1000 mH Ta = -40 C ... +50 C Ta = -40 C ... +65 C Ta = -40 C ... +85 C Ca = C0 = 100 F Ca = C0 = 1000 F Ca = C0 = 1000 F
Temperature range
Labeling: IS / Class I / Division 1 / Groups ABCD / T4/T5/T6 Class I / Zone 0 / AEx ia IIC / T4/T5/T6 NI / Class I / Division 2 / Groups ABCD / T4/T5/T6 Application: Intrinsic Safety Non-Incendive CSA (Canadian Standard Association)
TMT111 IS / Class I / Division 1 / Groups ABCD / T4/T5/T6 Ex ia IIC / T4/T5/T6 NI / Class I / Division 2 / Groups ABCD / T4/T5/T6 Ui 30 V DC Ii 100 mA Pi 750 mW Ci = negligible small Li = negligible small U0 4.4 V DC I0 9.6 mA P0 10.2 mW Group A, B Group C Group D T6 T5 T4 IIC IIB IIA La = L0 = 100 mH La = L0 = 100 mH La = L0 = 100 mH Ta = -40 C ... +50 C Ta = -40 C ... +65 C Ta = -40 C ... +85 C Ca = C0 = 100 F Ca = C0 = 1000 F Ca = C0 = 1000 F
Temperature range
Endress+Hauser
TMT111
Labeling: Class I / Div. 1 / Groups ABCD / T4/T5/T6 Class I / Div. 2 / Groups ABCD / T4/T5/T6 Application: Intrinsically safe Non-Incendive For further details on the available Ex versions (ATEX, CSA, FM, etc.), please contact your nearest Endress+Hauser sales organization. All relevant data for hazardous areas can be found in separate Ex documentation. If required, please request copies from your Endress+Hauser sales organization. UL CSA GP Other standards and guidelines Recognized component to UL 3111-1 CSA General Purpose according to C22.2 No. 1010.1-92 IEC 60529: Degrees of protection by housing (IP code) IEC 61010: Safety requirements for electrical measurement, control and laboratory instrumentation IEC 61326: Electromagnetic compatibility (EMC requirements) NAMUR: International user association of automation technology in process industries (www.namur.de).
Endress+Hauser
TMT111
Ordering information
Product structure
TMT111 iTEMP TMT111 DIN rail PC programmable temperature transmitter; Application: RTD, TC, and mV; 2-wire 4 to 20 mA, galvanic isolation; Fault reaction: NAMUR NE 43; Rail according to IEC 60715 TH35; Width: 12.6 mm Factory setup: Pt100, 3-wire, 0...100 C, sensor type/connection optional selectable Approval: A1 Non-hazardous area B1 ATEX II 2(1)G Ex ia IIC T4/T5/T6 C1 FM IS, NI I/1+2/ABCD C2 CSA IS, NI I/1+2/ABCD TMT111 Order code (Part 1 - one attribute must be selected)
Additional selection (as option - no selection or multiple selection is possible) Configuration sensor type: EA Resist. transmitter 10...400 Ohm, min. span 10 Ohm EB Resist. transmitter 10...2000 Ohm, min. span 100 Ohm E1 Pt100, -200...850 C, min. span 10 K, IEC60751 (a = 0,00385) E2 Pt500, -200...250 C, min. span 10 K E3 Pt1000, -200...250 C, min. span 10 K E4 Ni100, -60...180 C, min. span 10 K E5 Ni120, -70...270 C, min. span 10 K E6 Ni500, -60...150 C, min. span 10 K E7 Ni1000, -60...150 C, min. span 10 K FA Type N, -270...1300 C, min. span 50 K FB Type R, -50...1768 C, min. span 500 K FC Type S, -50...1768 C, min. span 500 K FD Type T, -200...400 C, min. span 50 K FE Type U, -200...600 C, min. span 50 K FF Voltage transmitter -10...100 mV, min. span 5 mV F1 Type B, 0...1820 C, min. span 500 K F2 Type C, 0...2320 C, min. span 500 K F3 Type D, 0...2495 C, min. span 500 K F4 Type E, -200...1000 C, min. span 50 K F5 Type J, -200...1200 C, min. span 50 K F6 Type K, -200...1370 C, min. span 50 K F7 Type L, -200...900 C, min. span 50 K Connection: RTD 2-wire RTD 3-wire RTD 4-wire Calibration: Works calibration certificate, 6-point (fixed points) Marking: Tagging (TAG), metal Tagging (TAG), on device Commissioning label, paper Tagging (TAG), Fieldbus Tagging (TAG), by customer Order code, complete (Part 1 + additional selection as option)
G1 G2 G3
H1
Z1 Z2 Z3 Z4 Z6 TMT111+
This ordering information can give an overview about the available order options. The Endress+Hauser sales organization can provide detailed ordering information and information on the order code.
Endress+Hauser
TMT111
Accessories
Configuration kits for PC programmable transmitters FXA291 Commubox: PC-interface cable with 4-pin USB-plug; Order-Code: 51516983 TMT121A-VK: Setup-program ReadWin 2000 and PC-interface cable (TTL/RS232C); Order-Code: TMT121A-VK TXU10-AA: Setup-program ReadWin 2000 and PC-interface cable with 4-pin USB-plug; Order-Code: TXU10-AA The operating software ReadWin 2000 can be downloaded free of charge from the Internet from the following address: www.endress.com/readwin
Documentation
Operating Instructions "iTEMP TMT111 DIN rail" (BA159R/09/a3) Ex supplementary documentation: ATEX II 2(1) G EEx ia IIC (XA021R/09/a3)
Instruments International
Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel. +41 61 715 81 00 Fax +41 61 715 25 00 www.endress.com info@ii.endress.com