Académique Documents
Professionnel Documents
Culture Documents
And the standard deviation as:
Where
He found that for structures whose period of vibration is the same or nearly equal
the required separation distance would be small since they would vibrate in phase but
for those with large difference in their period of vibration large seismic gap was
required. Secondly structures that had a long fundamental vibration period would
22
also in turn require larger seismic gap. Another parameter that has to be considered
in future work is that variation in the seismic excitation as it travels from the base of
one structure to the next. Secondly the soil-structure interaction has to be taken into
account.
Lin and Weng, 2001 studied the effect of height and period of vibration on the
pounding probability of adjacent structures subjected to artificial earths generated by
multiplying the response spectra of dense soil and soft rock with a trapezoidal
intensity function. They found that the correlations used in the UBC-97 (ABS and
SRSS) overestimated the separation distance require for no pounding. They proposed
a separation distance for a steel moment resisting framed modeled as a shear type
structure with elastoplastic behavior, the proposed method was base on seismic
hazard analysis for a given peak ground acceleration and conditional pounding
probability. They found that the minimum separation provided by the code varied
with the combination method used, period ratio of adjacent builds and the individual
periods of the structure they also concluded in their work that structures that have
periods of vibration close to that of the soil have greater pounding probability so do
structures of the same height with well separated periods of vibration.
Lopez-Garcia and Soong, 2009 preformed a comparative study on four criterions for
seismic separations between adjacent nonlinear hysteretic structures. All four
criterions were base on the double difference combinations rule but differed in the
method of correlating the displacements responses of the adjacent structural systems.
The separation distance proposed by the double difference method is as given below:
23
where S is the separation distance and
where
and
Where is the displacement ductility of the structures and
Valles calculated the values of empirically through a set of equations.
The errors with all above criterions relates to the fact that they all used the
correlation between a linear systems to depict the correlation between structural
responses of nonlinear hysteretic structures.
Jankowski, 2008 carried out a parametric study on to two equal height 3 dimensional
structures subjected to 3 component El-contra earthquake. The structures were
modeled as inelastic multi-degree-of-freedom lumped mass systems and a non linear
Viscoelastic modeled was used to depict the pounding force during contact of the
two adjacent buildings. Jankowski study how the variation in mass, stiffness, gap and
yield strength would affect the structures response, he found that for the lighter more
flexible building structural pounding during earthquakes had a significant
influence on the structures response and even more so in the longitudinal direction
as compared to the transverse and vertical directions. Structural pounding forced in
the lighter more flexible structure lead to it having preeminent deformations as it
enter into the yielding zone, however the heavier more stiffer structure did not
experience the same behaviour patterns as in the lighter building.
Pantelides and Ma, 1998 carried out a parametric study on effect of pounding on the
response of elastic and inelastic structural response of a single degree of freedom
25
system subjected to earthquake. He modeled the pounding force as a Hertz nonlinear
spring in an impact oscillator subjected to harmonic excitation. The equation of
motion was then written as:
Where m is the mass of the structure, c is the coefficient of damping and k is the
structural stiffness. Here the pounding force is give as
which is expressed as
follows:
Where (a) is the separation distance between adjacent structures and R is the impact
stiffness parameter which depends on the material of the two structures that come
together as well as the surface geometry. The parametric studies considered in their
work were the frequency of the excitation, separation gap, period of structural
vibration and the damping ratio. They found that under the same excitation,
structures with different natural periods of vibration would experience different
magnitudes of pounding. Secondly as they compared the structural response of the
elastic and inelastic case they found that although the overall structural displacement
was larger for the inelastic case the acceleration, velocity and the magnitude of
pounding were lower for the inelastic case. Thirdly the pounding occurrence was
lower for the inelastic case than the elastic case.
Agarwal et al., 2007 investigated how introducing friction bearing base isolation
(Teflon base isolation system) would affect the pounding of adjacent structures
subjected to four different earthquakes. The work showed that although base
isolation might eliminated the chance of base pounding the upper story pounding of
26
structures might still occur depending on structural parameters such as, stiffness,
mass, natural period of vibration and type of seismic excitation consider. They
studied 3 different scenarios, when one of the structures was base isolated, both
structures were based isolated and when both were fixed based structures. For the
case in which one of the two adjacent buildings had a base isolation the overall
deflection of the structure decrease but there was still large lateral displacement and
in case where the gap between the two buildings was equal to the overall structural
drift increase in pounding occurrence increased. While for the case of both structures
being base isolated, the magnitude of the impact force was noted to dependent on
whether the sliding friction coefficient was considered constant or varied with the
velocity. In the latter case the pounding forced was reduced while in the early case
impact force was higher. However for both structures base isolated that are chances
that the structures would move in phase keep the same distance between them.
Komodromos, 2008 carried out parametric investigation on seismic base isolated RC
structure. he model the super structure of the RC build as a shear beam with lumped
mass at the story level while the isolation system considered was modeled as a linear
model with effective damping and stiffness. As for pounding a nonlinear Hertz an
impact model was used by the researcher. The following parameters and their
influence on the pounding effect were studied with the aid of a soft ware generated
by the researcher.
1. Effect of the flexibility of the isolation system
2. Effect of the impact stiffness and damping
3. Effect of the superstructures stiffness
27
The following conclusions were arrived at, the more flexible the isolation system the
greater chances of pounding with the force case being if the fundamental period of
vibration concedes with that of the excitation. An increase in impact stiffness is
associated with decrease in relative displacement at the isolation level while the
maximum floor accelerations and inertia forces increase substantially with the
pounding force, it was also noted that an increase in impact stiffness resulted in an
increase in natural frequency which tends to amplify the seismic loading on the
structure. Lastly it was found that an increase in superstructure flexibility resulted in
an increase in the inter-story deflections.
What the research did not mention in his work is how the above parameters would
affect the structure response when pounding locations varied, for instance if
pounding at the isolation level is prevented this would not mean that the
superstructure would not pounding against fix based neighboring buildings, secondly
researcher does not consider the affect of multi component seismic excitation thirdly
he depicts the structural units to be linear are then considering them nonlinear in
which case u could get better sequence of formations.
2.4.2. RETORFITTING OF ADJACENT BUILDINGS
Lu et al., 2002 the team carried out experimental study on a 5 story and 6 story steel
frames subjected to El centre 1945 earthquake to determine how the installation of
fluid dampers would affect the structural response of the building. They took three
different cases, 1
st
case was two parallel structures with no connections while the 2
nd
case was done for the structures linked with rigid rods and the final case was that of
the structures linked with fluid dampers. In their study they found that fluid dampers
gave the best results in that they did not alter the fundamental periods of the
28
structures but reduced the structural responses of the building more than the rigid
connections.
Benavent-Climent, 2006 preformed experimental (shake table) study on four 6 story-
3 bay reinforcement concrete moment resisting frames with wide beam-column
connection. Of the four samples made two of them were retrofitted with diagonally
braced new dampers developed by Benavent, this diagonal braced dampers consisted
of H-shaped members designed to remain elastic when the brace is axially loaded,
the dampers were design to increase the structural stiffnes by ten fold and reduce the
interstory drift below 0.7%. He then compared the structural responses of an extrior
and interior beam-column retrofitted with braced viscous dampers against their
counter parts with out retrofitting. He conclude that the following findings in his
work:
(i) For same PGA the dampers reduced the interstory drift by 70% and 85% in
the exterior connections, and 60% and 85% in the interior,with the reduction
increasing with increase in peak ground accelerations.
(ii) Dampers increase the UDEC (ultimate energy disipation capacity) for the
exterior and interior wide beam column connections by 12 and 4 holds
respectivly while the maximum lateral force increased by 4 and 2 respectivly.
(iii)Braced dampers reduced the damage to the RC structure by 75%.
(iv) The braced dampers prevent drastic damages to beam column connections
untill one of the dampers yielded.
Zhu et al., 2001 investigated the optimum response reduction of a primary structure
connected to an auxiliary structure through an interconnecting element. Their work
covers two different areas, the first area being how the configuration of the structures
29
would affect the response of the primary structure. Secondly team than studied how
different control techniques (passive, active and semi-active) would affect the
response reduction of interconnect parallel single degree of freedom systems
subjected to the NS component of the EL centre 1940 earthquake. In terms of
structural configuration they conclude effectiveness increases as the mass of the A-
structure increases, and the natural frequency of the A-structure is further from that
of the P-structure. and that a flexible auxiliary structure reduced the absolute
acceleration of primary structure (P-structure) while a rigid auxiliary structure
reduces the relative displacement of P-structure. The team future studied the
effectiveness of passive control, active control and semi active control methods,
finding that the semi-active control technique was more effective in response control
of the structure then the optimum passive control method.
2.5. TORSIONAL RESPONSE OF ASYMMETRICAL STRUCTURES
Through the work of varies researches and case studies conducted on structures
subjected to earthquakes, it was found that symmetrical structures had far lesser
damage then asymmetrical structures of the same strength or even higher. The reason
being that in asymmetrical structure coupling occurs between the lateral response of
the structures and their rotation about the centre of resistance. The torsional aspect of
the response is generated through the eccentricity in the structure resulting from
discontinuity in structural members, differences in stiffness of members and
distribution of mass. As the centre of mass, stiffness and resistance shift further apart
the structure would rotate in the direction of the weak section there by creating a
larger deformation in one section of the building as compared to the other and
ultimately may result in failure of that portion.
30
Thambiratnam and Corderoy, 1994 carried out simple microcomputer procedure
using two different analysis techniques, quasistatic and real time dynamic analysis to
determine the effect of degree of asymmetry and direction of twist on the torsional
response of building. The degree of asymmetry in the building was varied through
the positioning of core walls. The analysis were done on a three dimensional 10 story
rectangular and 15 story L shaped building both with a core wall of stiffness 12
times large then that of all columns combined. Both analysis methods did show that
as the core moves away from the centre of resistance the degree of asymmetry
increase does resulting in large torsional response of the structure, for the quasistatic
method a triangular load applied in y direction was used for modeling the earth
quake. Both the static and dynamic analyses give results which agree qualitatively
and to some extent quantitatively and indicate that the responses are greatly
influenced by the degree of asymmetry in the building.
K. G. Stathopoulosi and S. A. Anagnostopoulos 2004 investigated the inelastic
response (torsional) of asymmetrical structures excited by 10 different artificial earth
quakes generated to match the design spectra. They compared the response of 3 and
5 story RC structures to a simplified shear type structure under bi-axial earth quake
excitations. Their primary objective was to show that the responses for simplified
shear type structures used in code provisions do not give a true picture of actual
response of multi-story real RC structures. The beam and column members of the
two RC models were modelled as nonlinear using plastic hinge model. Asymmetry in
both structures was introduced through dimensioning of the frame members taking
into account the mass eccentricities and thus stiffness eccentricities were also
generated. The top story displacements and rotational ductility demands for the
multi-storey structures show that the flexible side frames severed more
31
displacements and ductility demands then the stiffer side frames, this demands were
more server for the beams on the flexible side than the columns due to the fact that
capacity design limits the column stiffness to be always in the elastic range.
Thambiratnam and Corderoy, 1994 studied the effect of varying asymmetry on the
structural response and found that variation in asymmetry affected the shear force,
bending moment and deflection response of the structure. While Mansoori and
Moghadam, 2009 worked on the optimal distribution of dampers so as to control the
degree of asymmetry in the structure, thereby reducing the lateral-torsional response
of the structure.
V.I. Fernandez-Davila1 and E.F. Cruz 2008 preformed Time history response
analysis on 5 story asymmetrical RC frame structures subjected to uni- and bi-
directional earthquake excitations. The models considered took into account
nonlinear behaviour of the structure members with failure occurring at member ends.
Using strong column-weak beam design two different cases where consider a
symmetrical model and an asymmetrical model subject to 20 artificial earthquakes
loads. The aim of the paper was to propose a set of combination rules that could
effectively estimate the response of asymmetrical structures using response spectra
analysis of uni-directional earthquake loading applied in x and y direction separately.
For Time history response analysis a bi-directional earthquake loading was applied
on the 3D asymmetric model and the response of the structure monitored for varying
angle of earthquake incidence and reduction factor. Using SRSS and 100/ ( =40,
60) combination rules, the results of response spectra analysis using unidirectional
earthquake loading applied on the structure gave results that were comparable to
those obtained through time history response analysis which used a bidirectional
earthquake loading.
32
Erduran, 2008 investigated the capability of current nonlinear static analysis in
capturing the effect of torsional response in asymmetric structures. In his work the
author compared the estimate results of N2 and MPA (modal pushover analysis) with
the exact values obtained from response history analysis for two RC frame
structures, one with unidirectional eccentricity introduce through shifting of mass
centre through 1.5m and the other with a bidirectional eccentricity due to plan
asymmetry (moving the mass centre .5m in both horizontal directions).Both
structures were subjected to a set of 30 earthquakes, of which 15 were near fault
earthquakes while the other far fault earthquakes. He also considered two different
versions of first pushover mode for the nonlinear static analysis methods, the tow
methods differed only in point of loading application. On comparing the results of
NS and MPA with response history analysis, the author concludes that with the
following points
(i) The first mode pushover procedure, where the lateral forces are applied at
the mass centre significantly underestimates the torsional rotations resulting
in an underestimation of the displacement demands on the torsional flexible
side for both uni-directionally eccentric and bi- directionally eccentric
systems. For the uni-directionally eccentric system, the underestimation of
torsional rotations results in conservative displacement demand estimates for
the torsional stiff side."
(ii) When the point of load application is change to the shifted mass centre the
first mode push over analysis method gave torsional response estimates. This
being the modified first mode push over analysis employed in current codes
under section of accidental eccentricity design.
33
(iii)The N2 which incorporates response spectra analysis method in estimate
torsional response of asymmetrical structure did give good results that were
comparable with exact values generated through response history analysis.
However this was true for the flexible side but for the stiffer side the result
was more conservative due to the assumption in N2, which assumes that the
displacement of stiffer side is the same as that at centre of mass.
Modal pushover analysis method gives more conservative results for 50% in 50 years
and 10% IN 50 years hazard levels, but a comparable result for 2% in 50 years
hazard level.
2.5.1. TORSIONAL CONTROLE OF ASYMMETRICAL STRUCTURE
Yoshida and Dyke, 2005 investigated the response control capacity of shear mode
MR damper placed in two numerical full scale asymmetrical structures. In first case
of study the structure had a rectangular plan with asymmetry being due to the
location of a shear wall in the 9 story building. While the second case considered 8
story l shaped structure. The mechanical model of the MR damper was that of Bouc-
Wen model force produced in the damper being controlled through variation in
applied voltage to produce the equivalent damping force within the system:
And
And the The functional dependence of the device parameters on the command input
u is modelled as
34
And
In their work they consider three different control systems namely passive-on,
clipped-optimal control, and ideal active control to evaluate performance of the MR
damper. They found that the clipped-optimal control method gave better results than
passive-on while ideal active control method gave pretty much the same results.
Acceleration and inter-story drift reductions for the clipped-optimal control method
where more pronounced from smaller earth quakes.
Shook et al., 2009 carried out experimental and numerical investigation on the affect
of semi-active (magneto rheological) dampers in reducing the torsional response of a
3 story, 9m high asymmetrical structure. The resistance of the MR damper was
controlled by fuzz logic algorithm generated through controlled-elitist genetic
algorithm (GA). Results of numerical evaluation of the FLC showed favorable
performance with respect to 1
st
, 3
rd
and 4
th
mode of vibrations 4 while the
performance was less favorable with respect to 2
nd
mode of vibration. It was
observed that the FLC is effective in decoupling lateral and torsional responses of the
structure.
Garca et al., 2007 investigated the torsional response control of asymmetrical
structures using viscous-elastic dampers and found that visco-elastic dampers were
capable of reducing the torsional response of asymmetrical structure by shifting the
empirical centre of build to coincide with the geometric centre of the building.
Optimal damper eccentricity values tended to increase linearly as the stiffness or
mass eccentricities increased, but their values depended on the input and system
parameters such as the torsional-to lateral stiffness ratio, uncoupled period,
35
eccentricity of the base structure, and stiffness and damping characteristics of the VE
dampers.
2.5.2. PASSIVE CONTROL USING VISCOUS DAMPERS
Through various researches on structures under earthquake excitations revealed that
structures which are asymmetrical suffer more damage as compared to those which
are symmetrical in nature. The asymmetry in the structures could be due to
eccentricities in mass, stiffness, strength or even damping properties. In certain case
it is the distribution of resisting frames within the structures which are also
responsible, for instance structures with soft stories were found to undergo lateral-
torsional couple when subjected to seismic loads, since continuity in structural
members cause alterations in the load path these structures have been classified as
asymmetrical structures.
Goel, 1998 is one of those leading researchers who have studied various aspects of
earthquake loading affects on asymmetrical structures, and in this paper the resercher
examines how using supplemental damping systems could alter the structural
response under seismic excitation. In this work the researcher examines the affect of
centre of mass, centre of rigidity, and centre of the geometry on the structural
response under lateral-torsional coupling. The model considered was idealized single
story structure incorporated with fluid viscous dampers. The author concluded with
the following findings:
i) Asymmetrical distribution of dampers lead to reduction of edge deformations
of up to 2 time that of symmetrical distribution
ii) The largest reduction in edge deformations in the flexible side was noted for
when the CSD (centre of stiffness of damping) was as far away as possible
36
from CM (centre of mass), while for the reduction of edge deformations in
stiffer side the CSD was on the same side as CR.
iii) Also largest reductions in edge deformation on the flexible side were noted
for when supplemental dampers were distributed as far away as possible from
the CSD.
iv) Since the normalized supplemental damping eccentricity and supplemental
damping radius of gyration cannot take up simultaneously largest possible
values an optimal reduction can be obtain through using fewer dampers
placed at the outer most edges or my place dampers in the perpendicular
direction.
v) The effects of supplemental damping on edge deformations were more
pronounced for strongly coupled torsional flexible asymmetrical plan
systems.
Goel, 2000 using modal analysis techniques the author investigated the effect of plan
wise distribution of viscous dampers on the apparent modal periods, apparent
damping ratios, mode shape components, modal participation factors and dynamic
amplification factors of asymmetric-plan buildings with supplemental viscous
damping subjected to harmonic ground motion. He found that the plan wise
distribution of dampers affect the dynamic amplification factor more than any other
factor.
Goel and Booker, 2001 investigated the effects of supplemental viscous damping on
the seismic response of one-storey, asymmetric-plan systems responding in the
inelastic range of behavior. Through this investigation the authors found that the
deformation, ductility and hysteresis demand on the flexible side lateral load
resisting members could be reduce through the implementation of viscous dampers in
37
asymmetrical structure. The amount of reduction depending on the plan wise
distribution of these supplemental dampers, for instance when the dampers had an
eccentricity equal but opposite in direction to that of structural eccentricity maximum
reduction in deformation and ductility demands of the flexible load resisting frame
was registered.
Goel, 2005 the author investigated the effect of viscous damper nonlinearity on the
response of one story uni-eccentric linear and non linear asymmetrical structure.
Following points are the conclusions derived by the author
(i) Damper non-linearity leads to reductions 25% in the flexible edge
deformations of short-period systems while for longer period systems the
reduction is 10%.
(ii) Effect of damper nonlinearity was found to have a small variation for base
shear and torque of linear and non linear systems. However the dampers did
reduce the torque effect considerable while the base shear was only slightly
effect.
(iii)For both linear and nonlinear systems, nonlinearity in the damper did reduce
the damping force and increase the damping torque.
(iv) Reduction in damper force was only for system with periods longer then
0.2sec
(v) The effect of plan distribution of dampers is not influenced by damper non
linearity
(vi) Combination of system nonlinearity and damper nonlinearity might be used
to remove the adverse effects.
The objective of this current work was to study how using energy dissipating devices
in old and new structures would alter their dynamic behavior under seismic
38
excitation. We have all witness the devastations cause by earthquakes in one way or
the other. Recent earth quakes in this modern time of material development and
construction advancement have resulted in loss of lifes tolling hundreds of
thousands and property damage in the billions. Although other factors associated
with earthquakes are also reasonable responsible for the deaths and property
damages, but still this are a second nature out breaks.
Structures under seismic excitation are subjected to a sudden again in energy which
has to be dissipated through inter floor accelerations and displacements. This in turn
causes the structure or parts of the structural units to collapse as they were not design
for such extreme displacements. Although the ductile of the structure does help in
dissipating some portion of the energy absorbed through plastic hinge mechanism.
These plastic hinge formation to an extend are acceptable but when the number of
plastic hinge formations exceed the design limit, the structures gives way and
collapse. There have been various ways that have been investigated in order to
compensate for the large displacement in structures, for example shear walls base
isolation techniques.
Here the method under study is the use of viscous dampers in retrofitting old
structures and new designed structures. The viscous dampers considered in this study
are velocity dependent. The advantages of this type of dampers is that they have
forces that are out of phase with the exciting force and no localized forces are
generated were they are installed secondly since these are passive dampers there is
no requirement of an external power source to control the system.
The use of viscous dampers provides the structure with an alternative route to
dissipate the absorbed energy, hence reducing the amount of plastic hinge formations
within the structural units. There are various dynamic properties that are responsible
39
for the behavior of structures under seismic excitation, due to the vast nature of the
topic few parameters will be covered in this work. The parameters are first categories
according to different areas or factors that arise from structural excitation:
For adjacent buildings one of the most server problems is pounding which results
from lack of proper clearance or seismic gap between the two buildings. Seismic gap
is the distance between the two buildings required to accommodate the displacements
of the two structures, this phenomenon is very apparent in metropolitan cities where
tall structures are constructed with little or no seismic gap. This problem is very
apparent where you have new buildings built close to old existing structures, because
of the difference in their dynamic properties the structures vibrate out of phase
resulting in pounding. Depending on whether the structures are of equal heights or
not the location of pounding will vary so will its severity. For instance structures of
equal height experience floor level pounding which is less severe the mid column
pounding.
In this work the employment of dampers is primarily used to reduce the dynamic
response of structures, such as displacement and shear force but this would in turn
reduce the chance of pounding since the displacements of the structures is reduced.
The second agenda in this work is that of asymmetrical structures under seismic
excitation. Asymmetrical structures are structures that have eccentricity in mass,
stiffness or damper locations due to irregular construction or discontinuity in
structural members. Due to eccentricity of stiffness and mass the structure undergoes
uneven lateral deformation. Due to the uneven lateral deformation demand of the
resisting structures there is a couple of lateral and torsional response of the structure.
For this it was suggested using viscous dampers to compensate for the difference in
stiffness in order to reduce the torsional response of the structure.
40
The key difference between this work and the vast amount of research on the topic is
that:
i) Structure is subjected to 3 dimensional earth quake
ii) Plastic hinge formation in damper and structure members are studied for
iii) 3D, multi- story structures are considered with nonlinear structural elements
and dampers.
2.5.3. CONCLUDING REMARKS
Through the literature reviewed and remarks of researchers the following points were
seen as points that require further research
i) Soil structure interaction
ii) Lateral-torsion coupling pounding
iii) Mid column pounding in soft story structures
iv) Use of more detail and as close as possible to actual structural models
41
3. METHODOLOGY
3.1. INTRODUCTION
Although it is not practical or even possible to have structures that are 100% seismic
resistant structures but these structures can be designed to have ductility response
during earthquakes. The ductility of structures is important in the sense that failure is
not sudden and explosive but rather undergoes large deflections which are indicative
of near structural failure. This is the criterion in which most currently seismic
building codes are based on and structures that follow these codes come out with
better performance under seismic excitations compared to the earlier counterparts.
The study of structures under Seismic excitation has come a long way in the last
couple of decade. Developments in technology made it permissible to measure the
intensity, depth and direction of earthquakes. These technological developments and
vast amount of research on the topic have presented new era in the ways structures
can dissipate energy resulting for seismic excitations.
Due to the vast nature of the topic there are two major areas that are going to be
examined here.
i. Retrofitting of adjacent structures to reduce dynamic response
ii. Retrofitting of asymmetrical structures in order to reduce torsional
response.
In the first case researches such as Jankowski, 2008 studied the effect of the
difference of stiffness and mass on the vibration of two equal height structures. He
found that variations in mass, stiffness and gap size does affect the longitudinal
pounding of the lighter building then it does the heavier building. Furthermore
Pantelides and Ma, 1998 investigated the effect that seismic gap and the inelastic
42
structural behavior will have on the magnitude of the pounding force generated
during pounding. The structure was models as a nonlinear single degree of freedom
with one side pounding. On comparison he found that inelastic structure had lower
peak velocity, acceleration and pounding force then the elastic structure.
FIGURE3. 1. Overall schematic view of the methodology of the study
There are various models that can be used for seismic study, but the model employed
here is that of a reinforced concrete framed with added on viscous dampers.
LITERATURE REVIEW
PHYSICAL MODELING CONSITUTIVE
MODELING
FORMULATION AND EXCUTION OF F.E CODE
APPLICATION ON REINFORCE
CONCRETEC STRUCTURES
STOP
START
43
Nonlinearity was considered in both the reinforced concrete frame and the viscous
dampers allowing for plastic hinge formations within the two materials. This chapter
gives the detail account of the material and structural properties and the modeling
aspects of it.
3.2. PHSICAL MODELLING
Three dimensions, nonlinear analytical model of frame element and the developed
viscous damper element are presented in the following sub sections.
3.2.1. PHYSICAL MODELING OF FRAME ELEMENT
The analytical model for RC frame members used in this investigation was
developed by Thanoon (1993-2004). It consists of three different zones as shown in
figure 3.2, the first zone is the rigid block zone located at each end of the member,
the second zone is the 3D plastic hinge zone at each end assumed to have zero length
and the remaining intermediate part of the member represents the third zone which is
assumed to remain elastic. These zones represent the finite width of the beam-
column joints, the plastic hinge zones give the inelastic properties of the member
while the central part of the member (located between two plastic hinges) is assumed
to reflect the elastic behavior of the member.
In constructing an inelastic element for a reinforced concrete section, the following,
basic assumptions, have been made: (Thanoon 1993-2004)
i) The generalized force-deformation relation of the element follows an elasto-
plastic model, having yield strengths corresponding to the ultimate capacities of
the member.
44
FIGURE3.2 Physical model of beam-column element
3.2.2. PHSICAL MODELING OF DAMPER ELEMENT
The analytical model of damper that is used here is the 3 dimensional nonlinear
damper model proposed by F. Hejazi (2008). The model consists of three zones as
shown in figure 3.2 shown below; each zone translates the different behaviors of the
damper. Rigid zone indicates the structural joint, while the hinge zone gives the
inelastic behavior of the damper (plastic hinge formation within the damper) during
inelastic analysis. The intermediate portion gives the elastic stage of the damper
therefore when the damper is still in functionality with therefore analysis within the
elastic limit.
FIGURE3.3 Real Viscous Dampers and 3-D Nonlinear Damper Element Model
Constitutive (F. Hejazi, 2008)
45
3.3. MECHANICAL PROPERTY OF DAMPER
The dampers employed in this work are viscous dampers with the basic layout o the
damper system show in figure 3.8. It consists of cylinders with silicon fluids being
forced through orifices by a stainless steel rode. The damping forced generated is
developed through the pressure difference at the ends of the piston and can be
adjusted by varying the size of orifice or even the viscous fluid used. The damping
force generated by forcing the viscous fluid through orifice is one that is in phase
with velocity although in certain case the restoring force could result in a damping
force that is rather in face with displacement than velocity.
The force-velocity relation is given by Goel, 2005:
Where
Force
Iceint
Ends of the dampers
is a positive exponent that varies from 0 to 2, but for most structural engineering
the upper limit is usually 1. When =1 the damping force varies linearly with
velocity while if <1 the damping force varies nonlinearly with the velocity. sgn( )
is the signum function and is usually taken to be 1.
46
Figure3.4 fluid viscous damper
3.4. DYNAMIC F.E FORMULATION FOR R/C FRAME STRUCTURE
The basic equation for structures under earthquake excitations considering the
equilibrium of forces is give as:
(3.9)
Where M is the mass of the structure, C is its inherent damping and K the stiffness of
the structure.
(3.10)
Where
(3.11)
Where q is the internal resisting force and depends on the displacement (x) and the
velocity ( ,
t t t t
e d
F F
A + A +
,
are imposed control force (Viscous damper) and
applied earthquake load vector in time (t+t) respectively. Also
t t
x
A +
and
t t
x
A +
are
displacement and velocity of system in time of t+At and defined as follow
( Hejazi, 2008):
t t t t t t
u t u u
A + A + A +
A + = |
2
) (
(3.12)
t t t t t t
u t u u
A + A + A +
A + =
(3.13)
Where
t t
u
A +
and
t t
u
A +
) 1 ( A + =
A +
( 3.15)
Here and are the parameters that control the accuracy and stability of the method.
The quantities
t t
u
A +
and
t t
u
A +
are
corrector values (Hejazi, 2008).
48
3.5. CONSITUTITIVE RELATIONSHIP FOR CONCRETE AND STEEL
3.5.1. STRESS-STRAIN RELATIONSHIP OF CONCRETE
The inelastic behavior of reinforced concrete beam-column element requires the
simulation of the interaction between axial forces and bending moments. In the
present study the effect of interaction between these forces is considered in
developing the yield surface for each element. The yield function employed here is
based on the fourth order polynomial first proposed by Medland and Taylor. The
stress-strain curve is shown in Figure 3.. and the Stress
c
in concrete corresponding
to strain is given in equation (3.1).
) ( 85 . 0
2 3 4
c c c c c c
D C B A f c c c c o + + + ' = ( 3.1)
Where
c
f '
is compressive strength (cylinder) of concrete and A, B, C and D are
constant values and given as:
A = 0.292E+10, B = 0.1583E+08, C = - 0.3229E+06, D = 1.0593E+03
Figure 3.5. Stress-Strain Relation for Concrete (Medland and Taylor (1971))
Strain
S
t
r
e
s
s
U
p
0.002
f
c
c
49
3.5.2. STRESS-STRAIN RELATIONSHIP FOR STEEL
The behavior of steel in both compression and tension is a well documented behavior
through great deal of experiments steel was found to show three distinct behaviors
under loading. In the initial loading it showed an elastic behavior in which increase
in load resulted in increase in strain, this help true until the yield point where an
increase in load resulted in an increase in strain but not stress. After this stage steel
For the section a stress-strain relation for steel developed by (Thanoon, 1993) is
employed.
Material properties of steel are well known in static and dynamic loading conditions.
A typical stress-strain curve for high yield steel reinforcing bars loaded in direct
tension is as shown in
Idealization of these curves by suitable linear segments, which closely approximate
the experimental stress-strain curve, would have obvious advantages. The initial
elastic part extends up to the yield stress, followed by strain hardening part extending
up to failure. Further, for dynamic analysis, elasto-plastic approximation to the
stress-strain curve of steel is widely used for its simplicity. In the present study, an
elasto-plastic or strain hardening approximation of the behavior of the stress-strain
relation for steel is adopted as shown in
Figure 3.6.
50
(a) Uniaxial (b) Idealized
Figure 3.6. stress-strain graphs for steel
Accordingly, the stress in steel as, corresponding to strain
b
can be expressed as
follows:
Elastic state;
s s s
E c o =
( 3.2)
Elasto-Plastic;
) (
y s st y s
E f c c o + =
( 3.3)
3.6. REINFORCED CONCRETE FRAME WITH EARTHQUAKE ENERGY
DISSIPATION SYSTEM
The simulation of a reinforced concrete frame structure with added energy
dissipating devices requires an idealization of the structure that exhibits a close
approximation to actual structural behavior under seismic excitation. For this
reinforce concrete structure is idealized as a frame element consisting of beams and
columns. The reason for this idealization is that different structural member exhibit
s
f
y
51
different behaviors under seismic loading, for instance reinforce concrete structure
with an infill frame would behave differently from a frame structure with a shear
wall under seismic loading. The other structural member considered here is that of a
damper (energy dissipating device), this is the seismic response controller of the
structure and as such a proper selection for the member presentation is required in
order to generate as close as possible the actual control property of the damper.
The structural members considered in this work for modeling the reinforced concrete
structure are:
(i) Frame element
(ii) Viscous damper element
3.6.1. FRAME ELEMENT
Frame elements are models as beams and columns. The mathematical model of the
structural elements is 3 dimensional real space state representations of the structural
units (beams and columns). However since there are two different areas that are
covered here namely retrofitting of adjacent structures and the torsional response
reduction of the asymmetrical structure the layouts of the reinforced buildings varies.
In the case of the adjacent structures a 2 dimensional adjacent buildings with 3
dimensional structural members is used will in the case of asymmetrical reinforce
concrete frame structures a 3 dimensional building structure is considered.
The 3 dimensional structural members modeling give a more actual presentation of
the formation of plastic hinges within the structural members during the inelastic
analysis. Figure 3.7 shows the presentation of structural members (beams and
columns)
52
Figure 37: structural members of frame element
3.6.2. VISCOUS DAMPER ELEMENT
The model for dampers employed in this work is that which was developed by Hejazi
(2008) and shown below.
Figure 38: damper frame elements with added damper element
The model that was proposed for the damper by Hejazi (2008) was a 3 dimensional
nonlinear element that is compatible with the mathematical model initial generated
for the reinforced concrete frame.
Damper element
Beam element
Beam e Beam
element
Beam
element
Column element
53
3.7. COMPUTER PROGRAM
The computer program employed in this work is a finite element program code
which was developed by F. Hejazi (2010). This program analysis reinforced concrete
frame structures equipped with earthquake energy dissipation system in the elastic
and inelastic state. The developed program is capable of performing the following
analyses:
(i) Linear static
(ii) Nonlinear static
(iii)Linear dynamic
(iv) Nonlinear dynamic
The program is couple of giving the following results (F. Hejazi, 2008):
(i) It checks yielding that may occur at the ends of any element.
(ii) It calculates the inelastic forces to be redistributed in the next iteration.
(iii)It calculates the plastic deformations.
(iv) It calculates the stiffness matrix, considering current state of stress resultants
It calculates damper damping force and modifies it in each iteration base on the
optimum control system.
3.8. WORK LAYOUT CHART
Although the affects of earthquake on man built environment is an extensive field of
study, this work here is only limited to two parameters namely that of pounding
between two adjacent structures and torsional response of asymmetrical structures.
Both of these parameters have great catastrophic affects on how a structure
performance during and after earth quakes. For instance pounding between two
adjacent structures of different dynamic properties could lead to floor or mid column
54
pounding, with the latter case being more destructive since the top floor of a shorter
structure pounds against the column of the taller building which in turn leads to
failure of load resisting members in that region. This localized damage if extensive
could cause ultimately the failure of structure.
Since it his apparent that simplified models were not adequate enough to capture the
true structural response of reinforced concrete structures under earthquake loading, it
was seen as fit that a more actual R/C structure models should be used. This work is
a continuation of the work done by (Thanoon 1998) and further extended by (Hejazi
2010). The following chart shows the layout of the work plan for (Hejazi 2010).
Figure 3.9 Overall schematic view of present study (Hejazi 2010).
55
Through literature review three R/C frame models are selected to study pounding
affect in adjacent buildings the lateral-torsional couple in asymmetrical structures.
For the pounding case two adjacent R/C frame buildings were selected for the case
study, a 6 story building adjacent to a 12 story building. The separation distance
between the two buildings is 2 cm which was not sufficient to accommodate
structural displacements. Damper where then applied to reduce the displacement of
the structures (findings will be discussed in the results).
For the asymmetrical structures two 3D buildings where examined one with uni-
eccentricity in stiffness and the other bi-direction eccentricity in the plan of the
building. It was found that using the bi-eccentric model subjected to a 3 dimensional
earthquake excitation did give better structural performance picture of building
response under seismic excitation.
In both all three models use of viscous dampers reduced the structural response under
seismic excitation. Finding will be discussed in the following chapter (results)
.
56
4. RESULTS AND DISCUSSIONS
4.1. INTRODUCTION
In chapter 3 the choice of elements to represent the R/C frame structures equipped
with energy dissipation devices has been covered. Furthermore the material
constitutive modeling and program code were also covered in chapter 3.
The application of the proposed methodology will be cover in this chapter using
three different structural models. Following are the examples that are investigated in
this work:
i) Two adjacent structures separated by a seismic gap of 2cm
ii) A uni-asymmetrical 6 story RC frame structures
iii) A bi-asymmetrical RC structures
The response of the structures with respect to displacement, shear force, moment and
plastic hinge formations are plotted and discussed technically.
Figure 4.1 layout of analysis procedure
Define material, geometry and section
properties of RC frame building
Define damper section and
geometric properties
Apply uniform and concentrated static
load and perform static analysis to gain
member forces
Perform dynamic analysis to determine
dynamic response
Earthquake load
57
4.2. DEFINE RC FRAME MODEL PARAMETERS
Through the literature reviewed, actual structural models were selected along with
their actual dimensions. On selecting the desire model the material, section and
geometric properties were then feed into the F.E code.
In this work there are three models that were selected from papers that were viewed,
first model is of two adjacent structures one of 6 stories and the other of 12 stories.
The two structures were separated by a gap of 2 cm. in this model the effect of
placing viscous dampers was investigated. The second and the third models were
both used to investigate how viscous dampers would alter the response of
asymmetrical structures under seismic excitation. Second model was a uni-
asymmetrical 6 story 3D RC structure while the forth model was of a bi-
asymmetrical 3 story RC structure.
4.3. DEFINED DAMPER PARAMETERS
This work investigated the performance of viscous dampers placing in RC structures,
there are two major areas in which the damper performance was investigated, and
first being on pounding mitigation of adjacent structures and the second investigation
was on torsional response reduction in asymmetrical structures. The dampers
considered here are nonlinear and the damping coefficient was varied in order to pick
out the best damping coefficient for the dampers. In the F.E code the damper length
and damping coefficients where both defined.
4.4. PREFROM STATIC ANALYSIS
Static analysis was preformed foremost; this was done so what the member force
could be determined. Before performing the static analysis the model structures were
58
subjected to super imposed dead and live static loads which were imposed at all floor
levels.
4.5. SELECT EARTHQUAKE RECORD
All the investigations carried out in this work were subjected to El centre earthquake
record, for the 2D pounding problem of the adjacent structures were subjected to a 2
component (one horizontal record and one vertical record) El centre earth quake.
While for the torsional problem in asymmetrical structures both models were
subjected to 3 component EL centre earthquake record with T= 53 sacs. On selecting
the earthquake record dynamic analysis was preformed. The layouts of investigation
are as given below.
i. Use actual dimensions of models from literature review.
ii. Apply the static dead and live load to the buildings and carry out static
analysis in order to determine member forces which will be as initial
loadings in dynamic analysis.
iii. Subject the structure to seismic excitation using the earthquake records.
iv. Perform nonlinear seismic analysis for the structure.
v. The seismic response of structures is plotted as displacements (translation
and rotations) and plastic hinges. If these plots are within the code
acceptance then the analysis is terminated. If however the design does not
meet the code requirement, supplemental dampers are installed ( viscous
dampers)
vi. Perform dynamic analysis again with dampers in place, if can the code
provisions are not met change damper properties such as damping
coefficient
59
vii. Steps 2 to 6 are repeated until the design criteria are satisfied in step 4 and
the suitable design is obtained.
Based on the final decision, the properties of suitable viscous damper are
recommended.
4.6. APPLICATION OF VISCOUS DAMPERS
This chapter considers the performance of the proposed control system when applied
to full scale RC buildings. There are three different cases investigated in this chapter,
the first case investigates pounding of two adjacent structures and examines how
implementing the proposed control system reduces the pounding of two structures.
The second and third cases examine the torsional response affect on two
asymmetrical structures. In case 2 a uni-asymmetrical systems is investigated for
torsional response and then retrofitted with viscous dampers first in 3 sides and then
in four sides. The results of 3 side retrofitting and 4 side retrofitting are then
compared. For the third case a bi-asymmetrical system retrofitted with viscous
dampers is excited by a 3 component earth quake.
4.7. CASE 1 POUNDING MITIGATION OF ADJACENT STRUCTURES
In this case two adjacent structures of 6-story and 12-story were investigated for
pounding. The two buildings were separated by a gap of 2 cm which during the
analysis of the two structures under El. Centro earthquake was found to be
inadequate to accommodate the relative displacements of the structures. Viscous
dampers were then introduced in to the two buildings being distributed through the
full height of the short building and the same goes for the tall structure except the
middle bay was not retrofitted. Figure 4.2 shows the layout of two adjacent structures
60
along with the tabulated section properties of member elements and the distribution
of dampers is as shown in figure 4.3:
Fig 4.2 model plot for 2D adjacent RC structures
Table 4.1 cross-section and reinforcement of structural members
SECTION AREA
(CM)
MAIN REINFORCEMENT
BEAM 30*50
TOP 2 NO 6 DIA BOTTOM 6 NO16 DIA
COLUMN 30*50
8 NO 16 DIA
COLUMN 30*80
12 NO 16 DIA
COLUMN 30*140
22 NO 16 DIA
61
Figure 4.3: distribution of dampers (blue colored elements)
The following figures highlight the displacements of the two adjacent structures
without damping (dampers were place in the structures but had zero damping
coefficients). Their relative displacements were found to be greater than the gap
provided between the structures hence resulting in pounding of the structures.
Figure 4.4 pounding in adjacent structures
Now since increasing the gap between the buildings is not possible the damper
damping coefficient was increased until there was no pounding. The following
displacement time history responses are plotted for nodes 21 for the first building and
62
node 7 for the second building. Both nodes are at the same height level and this is the
point of contact between the two buildings during pounding. The shorter building in
this work is denoted as building 1 while the taller is denoted as the building 2.
Without damper With damper Amount of reduction
Max: 3.18E+01 1.02E+00 97.03%
Min: -4.63E+01 -1.30E+00
X direction for building 1
Without damper With damper Amount of reduction
Max: 3.52E+01 2.82E+00 90.4%
-50
-40
-30
-20
-10
0
10
20
30
40
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
With out damper
With Damper
-40
-30
-20
-10
0
10
20
30
40
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
With out damper
With Damper
63
Min: -3.67E+01 -4.09E+00
X direction for building 2
Figure 4.5 lateral displacements for building 1 and 2
From the above plots of displacement in x direction for building 1 and 2, increasing
the damping coefficient of the dampers from zero to 800KN.sec/m resulted in
displacement reductions of 97.03% and 90.4% respectively. This meant that the
pounding effect which resulted for the large lateral displacement of the two
structures was no longer present since both structures had displacements much less
then 5mm.
Without damper With damper reduction
Max: 2.45E+03 2.19E+03 41%
Min: 1.67E+03 1.73E+03
Axial Force
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0 10 20 30 40 50
Time (Sec)
A
x
i
a
l
F
o
r
c
e
(
k
N
)
With out damper
With Damper
-40
-30
-20
-10
0
10
20
0 10 20 30 40 50
Time (Sec)
S
h
e
a
r
i
n
Y
d
i
r
e
c
t
i
o
n
(
k
N
) With out damper
With Damper
64
Without damper With damper reduction
Max: 1.42E+01 -3.68E+00 73%
Min: -3.86E+01 -1.73E+01
Shear Force in Y direction
Without damper With damper reductions
Max: 6.04E+02 7.42E+00 76%
Min: -1.12E+03 -4.10E+02
Moment in Z direction
Figure 4.6 axial and shear force reductions
In terms of stress, viscous dampers did reduce them considerable. The axial force
was reduced by 41% while the shear force and moment were reduced by 73% and
76% respectively. One key area to not is that pounding effect in adjacent structures
increase the shear forces, the above force were plotted for element 31 which is the
first column in the tall structure.
4.8. CASE 2 TORSIONAL RESPONSE REDUCTION OF UNI-ASYMMETRICAL
STRUCTURE
In this case a 6 story RC asymmetrical structure was examined. Asymmetry in the
structure was due to the distribution of stiffness in the lateral resisting frames, with
one side frames having columns of large stiffness as compared to the other three side
-1200
-1000
-800
-600
-400
-200
0
200
400
600
800
0 10 20 30 40 50
Time (Sec)
M
o
m
e
n
t
a
r
o
u
n
d
Z
d
i
r
e
c
t
i
o
n
(
k
N
.
m
)
With out damper
With Damper
65
frames. This distribution of stiffness resulted in asymmetry along the x-axis. Due to
this difference in stiffness distribution it was found that when the structure was
excited with El centre earth quake record the less stiff side experience a large
torsional response as compared to the stiffer side. This larger lateral- torsional couple
leads to large ductility demand on the less stiff side frames(Thambiratnam and
Corderoy, 1994),(Garca et al., 2007). For this reason dampers were installed in the
model. The dampers were first place in 3 less stiff sides of the model and then
distributed symmetrical throughout the model (all four side frames retrofitted). The
layout of the model along with section properties and damper distributions are shown
in the following figures:
Figure 4.7 model front view and top view
66
Figure 4.8 damper distributions in 3 side frame
Retrofitting the above asymmetrical structure with viscous dampers did reduce the
displacement, shear force and torsion in the structure. On comparing the result of
asymmetrical and symmetrical distributed dampers it was found that symmetrical
distribution resulted in better reductions of all three parameters. Following are
displacement comparison for 3 side and 4s damper distributions for node 18 on the
less stiff side.
Displacement in X direction
-50
-40
-30
-20
-10
0
10
20
30
40
50
C
=
0
(
3
S
)
C
=
0
(
4
S
)
C
=
2
0
(
3
S
)
C
=
2
0
(
4
S
)
C
=
4
0
(
3
S
)
C
=
4
0
(
4
S
)
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
D
i
s
p
l
a
c
e
m
e
n
t
i
n
X
d
i
r
e
c
t
i
o
n
(
m
m
)
67
Displacement in Y direction
Displacement in Z direction
Figure 4.9 nodal displacements in x, y and z directions
As seen from above figures the displacement in both x and z directions were reduce
in both 3 and 4 side damper distributions, with the 4 side distribution have larger
reductions comparatively. However the displacements in the y direction were
increased slightly for 4 side distribution as compared with the 3 side distribution.
Following are the time history responses for node 18. Distributing the dampers
symmetrical in the model resulted in better performance in terms of response
reduction; one reason could be due to the affect of damper distribution which was an
asymmetrical distributed when the dampers were placed in 3 sides only (side with
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
C
=
0
(
3
S
)
C
=
0
(
4
S
)
C
=
2
0
(
3
S
)
C
=
2
0
(
4
S
)
C
=
4
0
(
3
S
)
C
=
4
0
(
4
S
)
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
D
i
s
p
l
a
c
e
m
e
n
t
i
n
Y
d
i
r
e
c
t
i
o
n
(
m
m
)
-60
-50
-40
-30
-20
-10
0
10
20
30
40
50
C
=
0
(
3
S
)
C
=
0
(
4
S
)
C
=
2
0
(
3
S
)
C
=
2
0
(
4
S
)
C
=
4
0
(
3
S
)
C
=
4
0
(
4
S
)
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
D
i
s
p
l
a
c
e
m
e
n
t
i
n
Z
d
i
r
e
c
t
i
o
n
(
m
m
)
68
less stiff frames). Although the dampers did reduce the displacements in the x
direction, they did however increase the displacement in y direction.
Without Damper 3S 4S
Amount of reduction
3S 4S
Min -37.8758 -28.2515 -25.4617 25% 34%
Max 36.4405 27.6917 23.6974
Displacement in X direction
Without Damper 3S 4S
Amount of reductions
3S 4S
Min -0.41403 -0.40834 -0.405464 39.84% 50.23%
Max 0.356844 0.669674 0.752697
-40
-30
-20
-10
0
10
20
30
40
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
With out damper
3 Side Damper
4 Side Damper
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
0 5 10 15 20 25 30 35 40 45 50 55
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
With out damper
3 Side Damper
4 Side Damper
69
Displacement in Y direction
W.O Damper 3S 4S
Amount of reduction
3S 4S
Min -50.7354 -37.9151 -30.8801 23% 36%
Max 38.7954 31.4585 26.8319
Displacement in Z direction
Figure 4.10 time history displacements x in z direction
The displacements in Z direction were found to be reduced on the structure was
retrofitted with viscous dampers. The reductions were found to be 23% and 36% for
3 side 4 side damper distributions respectively. Although the magnitudes of rotations
in all three directions were very small, installing viscous dampers in either 3 sides or
four sides did further reduce the torsional response in y direction while increasing the
rotations in x and z. the following table shows the displacement and rotations for
increased damper damping coefficient.
Displacement
X Y Z
C=0 Max 36.44 0.357 38.8
Min -37.9 -0.41 -50.7
-60
-50
-40
-30
-20
-10
0
10
20
30
40
50
0 5 10 15 20 25 30 35 40 45 50 55
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
With out damper
3 Side Damper
4 Side Damper
70
RESULTS FOR DAMPER DISTRIBUTION IN 3 SIDES
C=20 Max 29.39 0.694 35.09
Min -32.9 -0.41 -43.5
AMOUNT OF REDUCTION 16% 43.9% 12%
C=40 Max 27.69 0.67 31.46
Min -28.3 -0.41 -37.9
AMOUNT OF REDUCTION 25% 41% 23%
RESULTS OF DAMPER DISTRIBUTION IN ALL FOUR SIDES
C=20 Max 27.09 0.622 32.09
Min -31 -0.41 -38.9
AMOUNT OF REDUCTION 22% 35% 21%
C=40 Max 23.7 0.753 26.83
Min -25.5 -0.41 -30.9
AMOUNT OF REDUCTION 34% 52% 35%
Table 4.2 displacements and rotations for varying damper coefficients
During the investigation it was found that placing viscous dampers in the modeled
structure the displacement in X and Z directions were reduced. The amount of
reduction depended on the damping coefficient of the damper and the arrangement of
the viscous dampers. For instance when the damping coefficient was kept constant at
20KN.sec/m the 3 side damper distribution reduced the displacement in the X and Z
directions by 16% and 12 % respectively while the 4 side damper distribution reduce
the same displacement components by 22% and 21% respectively. However for both
damper damping coefficient and distribution the Y displacement component was
increased.
71
Both 3 and 4 side damper distributions did in fact reduce the axial, shear and,
torsional forces in the model. Moment response of the modeled structured was also
reduce for both damper distributions considered; however the results are only given
for 4 side damper distributions since the amount of reductions in said parameters
were larger in the considered case of damper distribution. For asymmetrical
structures retrofitting was done to reduce the torsional response of the structure,
which in this case was reduced by 63%.
Without damper 4s damper distribution Reduction
Max: 3.60E+02 3.44E+02 20%
Min: -3.96E+00 5.27E+01
Axial Force
-50
0
50
100
150
200
250
300
350
400
0 10 20 30 40 50
Time (Sec)
A
x
i
a
l
F
o
r
c
e
(
k
N
)
With out damper
With Damper
72
Without damper 4s damper distribution Reduction
Max: 1.52E+01 7.33E+00 80.4%
Min: -3.54E+01 -2.60E+01
Shear Force in Y direction
Without damper 4s damper distribution Reduction
Max: 7.32E+01 5.14E+01 35%
Min: -9.31E+01 -5.71E+01
Shear Force in Z direction
Figures 4.11 shear force in x, y and z directions
-40
-30
-20
-10
0
10
20
0 10 20 30 40 50
Time (Sec)
S
h
e
a
r
i
n
Y
d
i
r
e
c
t
i
o
n
(
k
N
) With out damper
With Damper
-100
-80
-60
-40
-20
0
20
40
60
80
0 10 20 30 40 50
Time (Sec)
S
h
e
a
r
i
n
Z
d
i
r
e
c
t
i
o
n
(
k
N
)
With out damper
With Damper
73
Without damper 4s damper distribution Reduction (%)
Max: 1.24E+02 5.00E+01 63%
Min: -1.59E+02 -5.49E+01
Torsion
Without damper Damper in 4 sides Reduction (%)
Max: 6.02E+03 3.94E+03 24%
Min: -5.69E+03 -5.00E+03
Moment in Y direction
-200
-150
-100
-50
0
50
100
150
0 10 20 30 40 50
Time (Sec)
T
o
r
s
i
o
n
(
k
N
.
m
)
With out damper
With Damper
-6000
-4000
-2000
0
2000
4000
6000
0 10 20 30 40 50
Time (Sec)
M
o
m
e
n
t
a
r
o
u
n
d
Y
d
i
r
e
c
t
i
o
n
(
k
N
.
m
)
With out damper
With Damper
74
Without damper Damper in 4 sides
Reduction
(%)
Max: 7.83E+02 4.53E+02 37%
Min: -1.16E+03 -7.72E+02
Moment in Z direction
Figure 4.12 torsion and moments in x, y and z directions respectively
Retrofitting the structure with viscous dampers increased both the section plastic
hinges and the total number of plastic hinges formed within the model
4.9. CASE 3 TORSIONAL RESPONSE REDUCTION OF BI-ASYMMETRICAL
STRUCTURE
The most serve case of lateral-torsional couple occurs when a bi-asymmetrical
structure model is excited by 3 component earthquake. For this reason a three-storey
building with plan bi- asymmetrical rectangular cross-section, shown in Figure 4.11
is investigated for torsional response. All the columns in this building are symmetric
with 450 mm x450mm cross-section and have a height of 3.5 m between floor
levels the modeled structure was excited with 3 component EL centre earthquake
with T = 53 secs. In the analysis of the model for zero damping it was found that it
experience large torsional responses when excited. Dampers were than places in the
wide side frames. The displacements and rotations are plotted for nodes 20 were as
the stresses are plotted for element 1.
-1200
-1000
-800
-600
-400
-200
0
200
400
600
800
0 10 20 30 40 50
Time (Sec)
M
o
m
e
n
t
a
r
o
u
n
d
Z
d
i
r
e
c
t
i
o
n
(
k
N
.
m
)
With out damper
With Damper
75
Figure 4.13 plan bi-asymmetrical 3 story RC frame structure
Displacement in X direction
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
C
=
0
C
=
2
5
0
C
=
5
0
0
C
=
7
5
0
C
=
1
0
0
0
C
=
1
2
5
0
C
=
1
5
0
0
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
D
i
s
p
l
a
c
e
m
e
n
t
i
n
X
d
i
r
e
c
t
i
o
n
(
m
m
)
76
Displacement in Z direction
Figure 4.12 displacements in X and Z directions
From the above plots of displacement in two horizontal directions for the bi
asymmetrical model, it was found that retrofitting the model with viscous dampers
did reduce the displacements in both directions considerably. Although not shown
here the y displacements were also reduced though not as significant as the other two
directions. However it is these two directional displacements that are responsible for
the lateral torsional coupling response of the structural modal and hence their
reductions are of importance. The rotational displacements of the structural modal in
all three directions were found to be very small and placement of the dampers did
further reduce those values in to insignificant numbers.
-10
-8
-6
-4
-2
0
2
4
6
8
10
C
=
0
C
=
2
5
0
C
=
5
0
0
C
=
7
5
0
C
=
1
0
0
0
C
=
1
2
5
0
C
=
1
5
0
0
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
D
i
s
p
l
a
c
e
m
e
n
t
i
n
Z
d
i
r
e
c
t
i
o
n
(
m
m
)
77
Rotation in X direction
Rotation in Z direction
Figure 4.14 rotations in X and Z directions
DAMPING
COEFFICIENT
(KN.sec/m)
DISPLACEMENT(mm)
X Y Z
C=0 Max 4.2082 0 8.739
Min -4.7554 -0.2897 -7.6292
C=250 Max 2.2313 0 3.4987
-0.0003
-0.0002
-0.0001
0
0.0001
0.0002
0.0003
C
=
0
C
=
2
5
0
C
=
5
0
0
C
=
7
5
0
C
=
1
0
0
0
C
=
1
2
5
0
C
=
1
5
0
0
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
R
o
t
a
t
i
o
n
a
r
r
o
u
n
d
X
d
i
r
e
c
t
i
o
n
(
R
a
d
)
-0.00015
-0.0001
-0.00005
0
0.00005
0.0001
0.00015
0.0002
C
=
0
C
=
2
5
0
C
=
5
0
0
C
=
7
5
0
C
=
1
0
0
0
C
=
1
2
5
0
C
=
1
5
0
0
Di fferent Damper Dampi ng Coeffi ci ent
M
A
X
&
M
I
N
R
o
t
a
t
i
o
n
a
r
r
o
u
n
d
Z
d
i
r
e
c
t
i
o
n
(
R
a
d
)
78
Min -3.028 -0.2799 -5.1991
REDUCTIONS 41% 3.4% 47%
C=500 Max 1.5079 0 2.4716
Min -2.2335 -0.2781 -4.4948
REDUCTIONS 58% 4% 57%
C=750 Max 1.2978 0 2.1378
Min -1.803 -0.2766 -3.8206
REDUCTIONS 65% 4.5% 64%
C=1000 Max 1.1561 0 1.8689
Min -1.5538 -0.2751 -3.3068
REDUCTIONS 70% 5% 68%
C=1250 Max 1.0617 0 1.64
Min -1.3963 -0.2739 -2.8722
REDUCTIONS 73% 5% 72%
C=1500 Max 0.9793 0 1.4431
Min -1.2719 -0.2738 -2.5412
REDUCTIONS 75% 5.5% 76%
Table 4.3 displacement reductions in X, Y and Z for node 20
From the above table it is seen that retrofitting of the modeled structure did in fact
reduce the displacement in all directions. Move horizontal displacements (X and Z)
which are the main contributors to the lateral-torsional couple of the structure are
considerable reduced. As the damper damping coefficient was increase the amount of
reduction for displacements increased.
The following graphs are the displacement time history response of node 20. The
dark line indicates the displacement time history responses of the structure when
retrofitted with viscous damper of 1500KN.sec/m were as the broken line represents
zero damping coefficients.
79
Without damper With damper reduction
Max: 4.21E+00 9.79E-01 75%
Min: -4.76E+00 -1.27E+00
Displacement in X direction
Without damper With damper reduction
Max: -5.88E-02 -4.52E-02 1%
Min: -2.90E-01 -2.74E-01
Displacement in Y direction
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
-0.25
-0.23
-0.21
-0.19
-0.17
-0.15
-0.13
-0.11
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
80
Without damper With damper reduction
Max: 8.74E+00 1.44E+00 76%
Min: -7.63E+00 -2.54E+00
Displacement in Z direction
Figure 4.15 displacement time history responses for node 20
Following graphs are plots of stress for element one, again the result follows the
same pattern as previous results except for the for the x component. In the initial few
seconds of stress time history response of the element 1 in the x-direction viscous
damper were found to have increase the axial force, however for time 3 sec the result
started to decrease considerable until final reduction of 14% was noted for damping
coefficient of 1500KN.sec/m. The largest shear force reduction was found to be 60%
which was in the z direction
-10
-8
-6
-4
-2
0
2
4
6
8
10
0 10 20 30 40 50
Time (Sec)
D
i
s
p
l
a
c
e
m
e
n
t
(
m
m
)
81
Without damper With damper reduction
Max: 6.49E+02 6.59E+02 14%
Min: 4.23E+02 4.02E+02
Axial Force
Without
damper With damper
Reduction
Max: -3.46E+01 -4.49E+01 44%
Min: -7.04E+01 -6.49E+01
Shear Force in Y direction
400
450
500
550
600
650
700
0 10 20 30 40 50
Time (Sec)
A
x
i
a
l
F
o
r
c
e
(
k
N
)
With out damper
With Damper
-80
-75
-70
-65
-60
-55
-50
-45
-40
-35
-30
0 10 20 30 40 50
Time (Sec)
S
h
e
a
r
i
n
Y
d
i
r
e
c
t
i
o
n
(
k
N
) With out damper
With Damper
82
Without damper With damper reduction
Max: 3.00E+01 1.08E+01 60%
Min: -3.39E+01 -1.48E+01
Shear Force in Z direction
Figure 4.16 axial and shear force time history response for element one
In this work the key investigation was determining how viscous dampers install in
the structure would reduce the torsional response of bi-asymmetrical structure
subjected to a 3 component earthquake. The following graphs are the time history
response for torsion and moments. As was expected install viscous dampers in the
system did reduce the torsional response of the bi-asymmetrical modeled system by a
factor of 85%.
-40
-30
-20
-10
0
10
20
30
40
0 10 20 30 40 50
Time (Sec)
S
h
e
a
r
i
n
Z
d
i
r
e
c
t
i
o
n
(
k
N
)
With out damper
With Damper
-100
-80
-60
-40
-20
0
20
40
0 10 20 30 40 50
Time (Sec)
T
o
r
s
i
o
n
(
k
N
.
m
)
With out damper
With Damper
83
Without damper With damper reduction
Max: 3.94E+01 -7.59E+00 85%
Min: -8.24E+01 -2.59E+01
Torsion
Without
damper With damper
Reduction
Max: 8.40E+02 2.87E+02 63%
Min: -8.51E+02 -3.34E+02
Moment in Y direction
Without damper With damper Reductions
Max: -2.09E+02 -4.36E+02 44%
Min: -9.97E+02 -8.79E+02
Moment in Z direction
Figure 4.17 torsion and moment time history response of element 1
-1000
-800
-600
-400
-200
0
200
400
600
800
1000
0 10 20 30 40 50
Time (Sec)
M
o
m
e
n
t
a
r
o
u
n
d
Y
d
i
r
e
c
t
i
o
n
(
k
N
.
m
)
With out damper
With Damper
-1000
-900
-800
-700
-600
-500
-400
-300
-200
0 10 20 30 40 50
Time (Sec)
M
o
m
e
n
t
a
r
o
u
n
d
Z
d
i
r
e
c
t
i
o
n
(
k
N
.
m
)
With out damper
With Damper
84
5. CONCLUSION
5.1. INTRODUCTION
The aim of this work was to investigate certain short comings of the previous works
review in the literature. Two key areas are investigated and the results obtained from
the investigation agree with those found in the literature reviews of the same
problems solved using simplified models and analysis methods. The aim of this work
was to get more realistic results that would agree with actual real structure behaviors
under seismic load. Hence three actual structural models were selected and time
history analysis was preformed. This investigation is limited to pounding and
torsional response reductions of RC frame structures using viscous dampers.
5.2. LITERATUREEIVEW
Based on the literature reviewed on seismic performance of adjacent and
asymmetrical structures under seismic excitations for 2D and 3D RC frame structures
the following points following points lead to this work
i. Pounding mitigation of adjacent structures using viscous dampers
ii. Torsional response reduction in asymmetrical structures
5.3. CASE 1 POUNDING MITIGATION OF ADJACENT STRUCTURES
The first case examined two adjacent structures one of 6 stories and the other of 12
stories separated by a gap of 2 cm. when the structures were excited by El centre
earthquake record with T = 53 sec it was found that both structures displaced more
than the gap between them could accommodate. Hence structural pounding occurred
at the roof top of the shorter building and the corresponding floor level of taller
building. The pounding of the structures lead to larger shear forces which lead,
although no localized failure was noted for this specific model and gap, it might be
85
possible for taller structural models. In order to prevent such structural poundings
viscous dampers were installed in the adjacent buildings and time history analysis
was perform for the same earthquake loading.
It was found that by retrofitting the short and tall buildings (referred to as building 1
and 2 respectively) with viscous dampers the displacement in the x direction were
reduce by 90.4% and 97% respectively. Hence limiting the horizontal displace of the
two adjacent buildings within 5mm which is easily accommodated by the provided
gap between the buildings. Due to the difficult of handling large data obtained from
the analysis only a single element shear force could be plotted in this case a column
of the tall building was selected. Viscous dampers used were not only capable of
reducing the displacement of the structures but also reduced the shear forces of the
structures considerable, for the selected column the shear force was reduced by 73%
while the axial force and moment reduced by 41% and 76% respectively.
5.4. CASE 2 TORSIONAL RESPONSE REDUCTIONS OF
UNIASYMMETRICAL STRUCTURES
In this case a 3D 6 story RC frame structure was investigated for torsional response
under seismic excitation. The asymmetry in the structure was due to the stiffness
distribution in the load resisting members. The stiffer sides, being the side whose
columns are highlighted in blue in figure 4.7. Due to the asymmetrical distribution of
stiffness, it was found that there was a large torsional demand on the less stiff side
(columns on the edges opposite to the stiff side). In order to control these effect
viscous dampers were distributed in the structure first in the 3 less stiff sides than
distributed in all four sides. The 3 side and 4 side damper distributions are then
compared to see which produce larger reductions in torsional response of the
structure. The 3 side damper distribution will be referred to as asymmetrical
86
distribution while the 4 side distribution will be referred to as symmetrical
distribution. For the asymmetrical distribution the two horizontal displacements X
and Z were found to be reduced by 25% and 23% respectively for the asymmetrical
distribution while for the symmetrical distribution the reductions were larger and
found to be 34% and 36% respectively. For both asymmetrical and symmetrical
distributions the Y displacement component were reduced by 39.84% and50.23%.
hence symmetrical distribution of dampers did result in better displace response
reductions, this could be due to the fact that the dampers do not enhance the stiffness
of the structure so by distributing them asymmetrical would in turn lead to a second
eccentricity in the structure this time it would be due to damper distribution.
Since symmetrical damper distribution preformed better of displacement reductions
the stress reductions give here would be only for the symmetrical distribution which
were again here then their counterpart.
The axial force of the structure was reduced by 20% while the shear forces in the y
and z axis were reduced by 80.4% and 35% respectively. However the key response
that is being investigated is the torsional response of the structure and it was found
by placing dampers the torsional force was reduced by 63% while the moments in y
and z directions were reduced by 24% and 37% respectively. Hence dampers did
actual reduced the lateral-torsional response of the structures. Although the above
percentages are for damper damping coefficient of 800KN.sec/m the amount of
reductions provide by this elements is really remarkable.
5.5. CASE 3 TORISONAL RESPONSE REDUCTIONS OF BI-ASYMMETRICAL
STRUCRURES
This case investigated the torsional response of a bi-asymmetrical structure subjected
to 3 component earthquakes. This is a more server case as compared to the first in
87
which a uni-asymmetrical real structural model was excited by 3 component El
centre earthquake. The real structure model investigated in this case is of 3 stories
with symmetrical columns of 450mm*45omm cross-sections, the beams are of
350mm*450mm. the floor heights of the structure are uniform and are of 3.5 meters,
the structure is made up to 2 bays in each orthogonal directional the short bay being
of 3.5m while the longer bay is of 6.5m. on exciting the structure with El centre
earthquake record it was found that large torsional response were noted for the longer
bays. The dampers were provided in these bays in order to reduce the displacements
and stress in these bays. The following percentage reductions in displacements are
given for node 20 each is on the most effected side while the stress are for element 1
this are highlighted in figure 4.11.
When the structure was retrofitted with dampers in the above said manner the two
horizontal displacements (X and Z) which were responsible of the torsional affect
were reduced by 75% and 76% respectively while the y component was reduced by
1% only. As for the stresses the axial forces was reduced by 145 while the shear
force in Y and Z were reduced by 44% and 60% respectively. The torsional force
was reduced by 85% while moments in Y and Z directions were reduce by 63% and
44% respectively.
5.6. OVER ALL RESPONSE OF RC FRAME STRUCTURES RETROFITTED
ITH VISCOUS DAMPERS
By retrofitting RC frame structures with viscous dampers in both adjacent and
asymmetrical structures the response of the structures were reduce. For the case of
pounding the adjacent structures were separated by a gap of 2cm which was
insufficient to accommodate the relative displacements of the structures. But by
install viscous dampers in the two adjacent buildings the displacements of the two
88
structures were considerable reduced thereby preventing structural pounding. Second
all the stresses within the structures were also reduce. As for the uni-asymmetrical
and bi-asymmetrical structures, the torsional response which was due to stiffness
distribution in the first case and plan asymmetry for the second was reduced with the
aid of viscous dampers. For the case of asymmetrical structures the amount of
reductions in structural response was found to be dependent on the distribution of
dampers in structures, for this reason it is important to select a proper distribution of
dampers to achieve effective reduction without having to employ large number of
dampers.
5.7. SUGGESTIONS FOR FURTHER STUDIES
For better understanding the actual behavior of real RC frame structures under
seismic excitations we have to look into model system that we used to study them,
simplified models and simplified analysis I not give actual site problems faced with
RC frame structures under earthquake loads.
Secondly parameters such as soil structure interactions are very important problems
that need to be studied, so far in the literature reviewed investigation of soil structure
interactions have not be explored. The behavior of structures under different soil
systems will greatly affect how the structure will respond once excited
Thirdly lateral torsional couple of adjacent buildings with insufficient seismic gap
could lead to a more server case then just lateral pounding between adjacent
structures. Special since now multi-story structures with eccentricities in stiffness
due to discontinued structural members are visible in all our major cities.
89
6. REFERENCES
(1995). "Analytical prediction of experimental building pounding : A. Filiatrault, P.
Wagner & S. Cherry, Earthquake Engineering & Structural Dynamics, 24(8), 1995,
pp 1131-1154." International Journal of Rock Mechanics and Mining Science &
Geomechanics Abstracts 32(8): A407-A407.
Agarwal, V. K., J. M. Niedzwecki, et al. (2007). "Earthquake induced pounding in
friction varying base isolated buildings." Engineering Structures 29(11): 2825-2832.
Aydin, E., M. H. Boduroglu, et al. (2007). "Optimal damper distribution for seismic
rehabilitation of planar building structures." Engineering Structures 29(2): 176-185.
Bailey, J. and E. Allen (1991). "Seismic isolation retrofitting of the Salt Lake City
and County Building." Nuclear Engineering and Design 127(3): 367-374.
Basili, M. and M. De Angelis (2007). "Optimal passive control of adjacent structures
interconnected with nonlinear hysteretic devices." Journal of Sound and Vibration
301(1-2): 106-125.
Benavent-Climent, A. (2006). "Influence of hysteretic dampers on the seismic
response of reinforced concrete wide beam-column connections." Engineering
Structures 28(4): 580-592.
Bharti, S. D., S. M. Dumne, et al. (2010). "Seismic response analysis of adjacent
buildings connected with MR dampers." Engineering Structures 32(8): 2122-2133.
Chandler, A. M. and G. L. Hutchinson (1986). "Torsional coupling effects in the
earthquake response of asymmetric buildings." Engineering Structures 8(4): 222-236.
Chandler, A. M. and P. A. Mendis (2000). "Performance of reinforced concrete
frames using force and displacement based seismic assessment methods."
Engineering Structures 22(4): 352-363.
Chen, X.-W., J.-X. Li, et al. (2010). "Seismic performance analysis of Wenchuan
Hospital structure with viscous dampers." The Structural Design of Tall and Special
Buildings 19(4): 397-419.
Constantinou, M. C. and M. D. Symans (1993). "Experimental study of seismic
response of buildings with supplemental fluid dampers." The Structural Design of
Tall Buildings 2(2): 93-132.
Curadelli, R. O. and J. D. Riera (2004). "Reliability based assessment of the
effectiveness of metallic dampers in buildings under seismic excitations."
Engineering Structures 26(13): 1931-1938.
Dai, J., Y.-L. Wong, et al. (2002). Torsional effect of asymmetric R/C building
structure. Advances in Building Technology. M. Anson, J. M. Ko and E. S. S. Lam.
Oxford, Elsevier: 281-288.
90
Dolce, M., D. Cardone, et al. (2007). "Shaking-table tests on reinforced concrete
frames with different isolation systems." Earthquake Engineering & Structural
Dynamics 36(5): 573-596.
Durucan, C. and M. Dicleli (2010). "Analytical study on seismic retrofitting of
reinforced concrete buildings using steel braces with shear link." Engineering
Structures 32(10): 2995-3010.
Erduran, E. (2008). "Assessment of current nonlinear static procedures on the
estimation of torsional effects in low-rise frame buildings." Engineering Structures
30(9): 2548-2558.
Garcia, D. L. (2005). "Discussion on: Critical building separation distance in
reducing pounding risk under earthquake excitation." Structural Safety 27(4): 393-
396.
Garca, M., J. C. de la Llera, et al. (2007). "Torsional balance of plan asymmetric
structures with viscoelastic dampers." Engineering Structures 29(6): 914-932.
Goel, R. K. (1998). "Effects of supplemental viscous damping on seismic response of
asymmetric-plan systems." Earthquake Engineering & Structural Dynamics 27(2):
125-141.
Goel, R. K. (2000). "Seismic behaviour of asymmetric buildings with supplemental
damping." Earthquake Engineering & Structural Dynamics 29(4): 461-480.
Goel, R. K. (2001). "Simplified analysis of asymmetric structures with supplemental
damping." Earthquake Engineering & Structural Dynamics 30(9): 1399-1416.
Goel, R. K. (2005). "Seismic response of linear and non-linear asymmetric systems
with non-linear fluid viscous dampers." Earthquake Engineering & Structural
Dynamics 34(7): 825-846.
Goel, R. K. and C. A. Booker (2001). "Effects of supplemental viscous damping on
inelastic seismic response of asymmetric systems." Earthquake Engineering &
Structural Dynamics 30(3): 411-430.
Hong-Nan, L. and L. Xiu-Ling (2009). "Experiment and analysis of torsional seismic
responses for asymmetric structures with semi-active control by MR dampers."
Smart Materials and Structures 18(7): 075007.
This paper focuses on the mitigation of the coupled translation and torsion
responses of an asymmetric structure by a magnetorheological (MR) damper.
A double-sigmoid model of the MR damper is presented on the basis of the
experimental results, and the validity of this proposed model for predicting
the hysteretic behavior of the MR damper is favorably proved by comparing
the simulation results with the experimental data. A multi-state control
strategy (MSC) which uses the velocity response as the state-switch
parameter is developed for the torsional seismic response control of the
asymmetric structure. The parameters of this control strategy are optimized
91
by a genetic algorithm (GA) method. Finally, a shaking table test is carried
out to evaluate the effectiveness of
Hong, H. P., S. S. Wang, et al. (2003). "Critical building separation distance in
reducing pounding risk under earthquake excitation." Structural Safety 25(3): 287-
303.
Ibrahim, R. A. (2008). "Recent advances in nonlinear passive vibration isolators."
Journal of Sound and Vibration 314(3-5): 371-452.
Iervolino, I., G. Manfredi, et al. (2007). "Seismic risk of R.C. building classes."
Engineering Structures 29(5): 813-820.
Jankowski, R. (2005). "Non-linear viscoelastic modelling of earthquake-induced
structural pounding." Earthquake Engineering & Structural Dynamics 34(6): 595-
611.
Jankowski, R. (2008). "Earthquake-induced pounding between equal height
buildings with substantially different dynamic properties." Engineering Structures
30(10): 2818-2829.
Jeng, V. and W. L. Tzeng (2000). "Assessment of seismic pounding hazard for
Taipei City." Engineering Structures 22(5): 459-471.
Jiang, W., G. L. Hutchinson, et al. (1993). "Definitions of static eccentricity for
design of asymmetric shear buildings." Engineering Structures 15(3): 167-178.
Kasai, K. and B. F. Maison (1997). "Building pounding damage during the 1989
Loma Prieta earthquake." Engineering Structures 19(3): 195-207.
Kim, J. and S. Bang (2002). "Optimum distribution of added viscoelastic dampers for
mitigation of torsional responses of plan-wise asymmetric structures." Engineering
Structures 24(10): 1257-1269.
Kim, J., J. Ryu, et al. (2006). "Seismic performance of structures connected by
viscoelastic dampers." Engineering Structures 28(2): 183-195.
Komodromos, P. (2008). "Simulation of the earthquake-induced pounding of
seismically isolated buildings." Computers & Structures 86(7-8): 618-626.
Krlik, J. and J. Krlik Jr (2009). "Seismic analysis of reinforced concrete frame-wall
systems considering ductility effects in accordance to Eurocode." Engineering
Structures 31(12): 2865-2872.
Lee, H.-S. and D.-W. Ko (2007). "Seismic response characteristics of high-rise RC
wall buildings having different irregularities in lower stories." Engineering Structures
29(11): 3149-3167.
92
Li, C. and W. Qu (2006). "Optimum properties of multiple tuned mass dampers for
reduction of translational and torsional response of structures subject to ground
acceleration." Engineering Structures 28(4): 472-494.
Li, W., Q.-n. Li, et al. (2011). "Seismic performance of composite reinforced
concrete and steel moment frame structures - state-of-the-art." Composites Part B:
Engineering 42(2): 190-206.
Lin, J.-H. (1997). "SEPARATION DISTANCE TO AVOID SEISMIC POUNDING
OF ADJACENT BUILDINGS." Earthquake Engineering & Structural Dynamics
26(3): 395-403.
Lin, J.-H. and C.-C. Weng (2001). "Probability analysis of seismic pounding of
adjacent buildings." Earthquake Engineering & Structural Dynamics 30(10): 1539-
1557.
Lin, W.-H. and A. K. Chopra (2003). "Asymmetric one-storey elastic systems with
non-linear viscous and viscoelastic dampers: Earthquake response." Earthquake
Engineering & Structural Dynamics 32(4): 555-577.
Lopez-Garcia, D. and T. T. Soong (2009). "Assessment of the separation necessary
to prevent seismic pounding between linear structural systems." Probabilistic
Engineering Mechanics 24(2): 210-223.
Lopez-Garcia, D. and T. T. Soong (2009). "Evaluation of current criteria in
predicting the separation necessary to prevent seismic pounding between nonlinear
hysteretic structural systems." Engineering Structures 31(5): 1217-1229.
Lu, X., Z. Gong, et al. (2007). "The application of a new structural control concept
for tall building with large podium structure." Engineering Structures 29(8): 1833-
1844.
Lu, X. L., Y. L. Xu, et al. (2002). Seismic control of adjacent buildings using fluid
dampers: Experimental study. Advances in Building Technology. M. Anson, J. M.
Ko and E. S. S. Lam. Oxford, Elsevier: 985-992.
Mansoori, M. R. and A. S. Moghadam (2009). "Using viscous damper distribution to
reduce multiple seismic responses of asymmetric structures." Journal of
Constructional Steel Research 65(12): 2176-2185.
Marko, J., D. Thambiratnam, et al. (2004). "Influence of damping systems on
building structures subject to seismic effects." Engineering Structures 26(13): 1939-
1956.
Munshi, J. A. (1997). "Effect of viscoelastic dampers on hysteretic response of
reinforced concrete elements." Engineering Structures 19(11): 921-935.
Ok, S.-Y., J. Song, et al. (2008). "Optimal design of hysteretic dampers connecting
adjacent structures using multi-objective genetic algorithm and stochastic
linearization method." Engineering Structures 30(5): 1240-1249.
93
Oviedo A, J. A., M. Midorikawa, et al. (2010). "Earthquake response of ten-story
story-drift-controlled reinforced concrete frames with hysteretic dampers."
Engineering Structures 32(6): 1735-1746.
Pantelides, C. P. and X. Ma (1998). "Linear and nonlinear pounding of structural
systems." Computers & Structures 66(1): 79-92.
Paulay, T. (1997). "Displacement-based design approach to earthquake-induced
torsion in ductile buildings." Engineering Structures 19(9): 699-707.
Petti, L. and M. De Iuliis (2008). "Torsional seismic response control of asymmetric-
plan systems by using viscous dampers." Engineering Structures 30(11): 3377-3388.
Pinkaew, T., P. Lukkunaprasit, et al. (2003). "Seismic effectiveness of tuned mass
dampers for damage reduction of structures." Engineering Structures 25(1): 39-46.
Pinnington, R. J. (2003). "Collision dynamics of two adjacent oscillators." Journal of
Sound and Vibration 268(2): 343-360.
Polycarpou, P. C. and P. Komodromos (2010). "Earthquake-induced poundings of a
seismically isolated building with adjacent structures." Engineering Structures 32(7):
1937-1951.
Rai, D. C. (1999). "Supplemental damping for seismic strengthening: a case study."
Engineering Structures 21(7): 603-614.
Sadjadi, R., M. R. Kianoush, et al. (2007). "Seismic performance of reinforced
concrete moment resisting frames." Engineering Structures 29(9): 2365-2380.
Scholl, R. E. (1989). "Observations of the performance of buildings during the 1985
Mexico earthquake, and structural design implications." Geotechnical and Geological
Engineering 7(1): 69-99.
Shih, M. H., W. P. Sung, et al. (2006). "DEVELOPMENT AND SEISMIC
REDUCTION PERFORMANCE OF VELOCITY AND DISPLACEMENT
DEPENDENT HYDRAULIC DAMPER." Experimental Techniques 30(3): 41-45.
Shook, D. A., P. N. Roschke, et al. (2009). "Semi-active control of a torsionally-
responsive structure." Engineering Structures 31(1): 57-68.
Soong, T. T. and B. F. Spencer (2002). "Supplemental energy dissipation: state-of-
the-art and state-of-the-practice." Engineering Structures 24(3): 243-259.
Stathopoulos, K. G. and S. A. Anagnostopoulos (2010). "Accidental design
eccentricity: Is it important for the inelastic response of buildings to strong
earthquakes?" Soil Dynamics and Earthquake Engineering 30(9): 782-797.
Tezcan, S. S. and O. Uluca (2003). "Reduction of earthquake response of plane
frame buildings by viscoelastic dampers." Engineering Structures 25(14): 1755-1761.
94
Thambiratnam, D. P. and H. J. B. Corderoy (1994). "Effects of asymmetry on the
response of multistorey buildings to earthquakes." Engineering Structures 16(3):
210-221.
Thanoon, W. A., D. K. Paul, et al. (2004). "Influence of torsion on the inelastic
response of three-dimensional r.c. frames." Finite Elements in Analysis and Design
40(5-6): 611-628.
Wang, S. S. and H. P. Hong (2006). "Quantiles of critical separation distance for
nonstationary seismic excitations." Engineering Structures 28(7): 985-991.
Wilkinson, S. M. and R. A. Hiley (2006). "A non-linear response history model for
the seismic analysis of high-rise framed buildings." Computers & Structures 84(5-6):
318-329.
Wolf, J. P. and P. E. Skrikerud (1980). "Mutual pounding of adjacent structures
during earthquakes." Nuclear Engineering and Design 57(2): 253-275.
Xu, Y. L., Q. He, et al. (1999). "Dynamic response of damper-connected adjacent
buildings under earthquake excitation." Engineering Structures 21(2): 135-148.
Ying, Z. G., Y. Q. Ni, et al. (2003). "Stochastic optimal coupling-control of adjacent
building structures." Computers & Structures 81(30-31): 2775-2787.
Yoshida, O. and S. J. Dyke (2005). "Response Control of Full-Scale Irregular
Buildings Using Magnetorheological Dampers." Journal of Structural Engineering
131(5): 734-742.
Zhu, H., Y. Wen, et al. (2001). "A study on interaction control for seismic response
of parallel structures." Computers & Structures 79(2): 231-242.
Zhu, H. P., D. D. Ge, et al. (2011). "Optimum connecting dampers to reduce the
seismic responses of parallel structures." Journal of Sound and Vibration 330(9):
1931-1949.
Zou, X. K. and C. M. Chan (2005). "Optimal seismic performance-based design of
reinforced concrete buildings using nonlinear pushover analysis." Engineering
Structures 27(8): 1289-1302.
AGARWAL, V. K., NIEDZWECKI, J. M. & VAN DE LINDT, J. W. 2007.
Earthquake induced pounding in friction varying base isolated buildings.
Engineering Structures, 29, 2825-2832.
BENAVENT-CLIMENT, A. 2006. Influence of hysteretic dampers on the seismic
response of reinforced concrete wide beam-column connections. Engineering
Structures, 28, 580-592.
95
CHEN, X.-W., LI, J.-X. & CHEANG, J. 2010. Seismic performance analysis of
Wenchuan Hospital structure with viscous dampers. The Structural Design of
Tall and Special Buildings, 19, 397-419.
ERDURAN, E. 2008. Assessment of current nonlinear static procedures on the
estimation of torsional effects in low-rise frame buildings. Engineering
Structures, 30, 2548-2558.
GARCA, M., DE LA LLERA, J. C. & ALMAZN, J. L. 2007. Torsional balance of
plan asymmetric structures with viscoelastic dampers. Engineering
Structures, 29, 914-932.
GOEL, R. K. 1998. Effects of supplemental viscous damping on seismic response of
asymmetric-plan systems. Earthquake Engineering & Structural Dynamics,
27, 125-141.
GOEL, R. K. 2000. Seismic behaviour of asymmetric buildings with supplemental
damping. Earthquake Engineering & Structural Dynamics, 29, 461-480.
GOEL, R. K. 2005. Seismic response of linear and non-linear asymmetric systems
with non-linear fluid viscous dampers. Earthquake Engineering & Structural
Dynamics, 34, 825-846.
GOEL, R. K. & BOOKER, C. A. 2001. Effects of supplemental viscous damping on
inelastic seismic response of asymmetric systems. Earthquake Engineering &
Structural Dynamics, 30, 411-430.
HONG, H. P., WANG, S. S. & HONG, P. 2003. Critical building separation distance
in reducing pounding risk under earthquake excitation. Structural Safety, 25,
287-303.
JANKOWSKI, R. 2008. Earthquake-induced pounding between equal height
buildings with substantially different dynamic properties. Engineering
Structures, 30, 2818-2829.
JENG, V. & TZENG, W. L. 2000. Assessment of seismic pounding hazard for Taipei
City. Engineering Structures, 22, 459-471.
KASAI, K. & MAISON, B. F. 1997. Building pounding damage during the 1989
Loma Prieta earthquake. Engineering Structures, 19, 195-207.
KOMODROMOS, P. 2008. Simulation of the earthquake-induced pounding of
seismically isolated buildings. Computers & Structures, 86, 618-626.
LIN, J.-H. 1997. SEPARATION DISTANCE TO AVOID SEISMIC POUNDING
OF ADJACENT BUILDINGS. Earthquake Engineering & Structural
Dynamics, 26, 395-403.
LIN, J.-H. & WENG, C.-C. 2001. Probability analysis of seismic pounding of
adjacent buildings. Earthquake Engineering & Structural Dynamics, 30,
1539-1557.
LOPEZ-GARCIA, D. & SOONG, T. T. 2009. Evaluation of current criteria in
predicting the separation necessary to prevent seismic pounding between
nonlinear hysteretic structural systems. Engineering Structures, 31, 1217-
1229.
LU, X. L., XU, Y. L. & YANG, Z. 2002. Seismic control of adjacent buildings using
fluid dampers: Experimental study. In: ANSON, M., KO, J. M. & LAM, E. S.
S. (eds.) Advances in Building Technology. Oxford: Elsevier.
MANSOORI, M. R. & MOGHADAM, A. S. 2009. Using viscous damper
distribution to reduce multiple seismic responses of asymmetric structures.
Journal of Constructional Steel Research, 65, 2176-2185.
MUNSHI, J. A. 1997. Effect of viscoelastic dampers on hysteretic response of
reinforced concrete elements. Engineering Structures, 19, 921-935.
96
PANTELIDES, C. P. & MA, X. 1998. Linear and nonlinear pounding of structural
systems. Computers & Structures, 66, 79-92.
PINKAEW, T., LUKKUNAPRASIT, P. & CHATUPOTE, P. 2003. Seismic
effectiveness of tuned mass dampers for damage reduction of structures.
Engineering Structures, 25, 39-46.
SCHOLL, R. E. 1989. Observations of the performance of buildings during the 1985
Mexico earthquake, and structural design implications. Geotechnical and
Geological Engineering, 7, 69-99.
SHOOK, D. A., ROSCHKE, P. N., LIN, P.-Y. & LOH, C.-H. 2009. Semi-active
control of a torsionally-responsive structure. Engineering Structures, 31, 57-
68.
TEZCAN, S. S. & ULUCA, O. 2003. Reduction of earthquake response of plane
frame buildings by viscoelastic dampers. Engineering Structures, 25, 1755-
1761.
THAMBIRATNAM, D. P. & CORDEROY, H. J. B. 1994. Effects of asymmetry on
the response of multistorey buildings to earthquakes. Engineering Structures,
16, 210-221.
YOSHIDA, O. & DYKE, S. J. 2005. Response Control of Full-Scale Irregular
Buildings Using Magnetorheological Dampers. Journal of Structural
Engineering, 131, 734-742.
ZHU, H., WEN, Y. & IEMURA, H. 2001. A study on interaction control for seismic
response of parallel structures. Computers & Structures, 79, 231-242.