Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated

Medium-Voltage Switchgear Catalog HA 35.41 2010

Answers for energy.

R-HA35-126.tif

Application Public power supply system

R-HA35-109.eps

R-HA35-106.eps

Application Industry

NXPLUS C switchgear 20 kV (example)

R-HA35-123.eps

Application Industry and offshore

2 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

R-HA35-107.eps

Contents Fixed-Mounted CircuitBreaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated


Medium-Voltage Switchgear Catalog HA 35.41 2010
Application Types, typical uses, ratings Requirements Features, safety, technology Technical data Electrical data Room planning Shipping data, classication Dimensions Front views, sections, oor openings, xing points Product range Single-busbar panels Double-busbar panels Design Basic panel design Components Vacuum circuit-breaker Three-position switches HV HRC fuse assembly Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings Vacuum contactor, motor protection Busbars Current and voltage transformers Panel connection Installation possibilities for cable connections and surge arresters Panel connection (commercially available cable sealing ends) Indicating and measuring equipment Protection, control, measuring and monitoring equipment Standards Standards, specications, guidelines 58 and 59 26 and 27 28 and 29 30 31 to 37 38 39 40 to 42 43 44 to 50 51 and 52 53 to 56 57 25 21 to 23 24 12 to 20 8 and 9 10 11 6 and 7 Page 4 and 5

The products and systems described in this catalog are manufactured and sold according to a certied quality and environmental management system (acc. to ISO 9001 and ISO 14001). (DQS Certicate Reg. No. DQS 003473 QM UM). The certicate is accepted in all IQNet countries.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 3

Application
Types
R-HA35-125.eps

Circuit-breaker panel 600 mm

R-HA35-105a.eps

Circuit-breaker panel 900 mm

4 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Application
Typical uses, ratings
Fixed-mounted circuit-breaker switchgear NXPLUS C is a factory-assembled, type-tested, metal-enclosed, metal-clad, SF6-insulated switchgear for single-busbar and double-busbar applications for indoor installation. It is used in transformer and switching substations, e.g., in: Power supply companies Power stations Cement industry Automobile industry Iron and steel works Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshore installations Electrochemical plants Petrochemical plants Shipbuilding industry Diesel power plants Emergency power supply installations Lignite open-cast mines Traction power supply systems. Electrical data (maximum values) and dimensions
Rated voltage Rated frequency Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Rated peak withstand current Rated short-circuit making current Rated short-time withstand current 3 s Rated short-circuit breaking current Rated normal current of the busbar Rated normal current of feeders Width Depth without pressure relief duct at the rear with pressure relief duct at the rear Height 600 mm panels 900 mm panels kV Hz kV 7.2 20 1) 12 28 2) 15 36 17.5 38 24 50 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60

kV kA kA kA kA A A mm

60 1) 80 80 31.5 31.5 2500 2500

75 2) 80 80 31.5 31.5 2500 2500

95 80 80 31.5 31.5 2500 2500

95 63 63 25 25 2500 2000

125 63 63 25 25 2500 2000

600 3) 600 3) 600 3) 600 3) 600 3)

mm mm

1100 1225 2250 2550

1100 1225 2250 2550

1100 1225 2250 2550

1100 1225 2250 2550

1100 1225 2250 2550

1) 32 kV / 60 kV according to some national requirements 2) 42 kV / 75 kV according to some national requirements 3) 900 mm for rated normal feeder currents of 2000 A and 2500 A Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 5

Requirements
Features
Environmental independence Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts of the primary circuit under high voltage of NXPLUS C switchgear Insensitive to certain aggressive ambient conditions, such as: Saline air Air humidity Dust Condensation Tight to ingress of foreign objects, such as: Dust Pollution Small animals Humidity Independent of the site altitude. Compact design Thanks to the use of SF6 insulation, compact dimensions are possible. Thus: Existing switchgear rooms can be used effectively New constructions cost little Costly city-area space is saved. Maintenance-free design Switchgear vessels designed as sealed pressure systems, maintenance-free switching devices and enclosed cable plugs ensure: Maximum supply reliability Personnel safety Sealed-for-life design according to IEC 62271-200 (sealed pressure system) Installation, operation, extension and replacement without SF6 gas work Reduced operating costs Cost-efcient investment No maintenance cycles. Innovation The use of digital secondary systems and combined protection and control devices ensures: Clear integration in process control systems Flexible and highly simplied adaptation to new system conditions and thus to cost-efcient operation. Service life Under normal operating conditions, the expected service life of the gas-insulated switchgear NXPLUS C is at least 35 years, probably 40 to 50 years, taking the tightness of the hermetically welded switchgear vessel into account. The service life is limited by the maximum number of operating cycles of the switching devices installed: For circuit-breakers according to the endurance class dened in IEC 62271-100 For three-position disconnectors and earthing switches according to the endurance class dened in IEC 62271-102 For three-position switch-disconnectors and earthing switches according to the endurance class dened in IEC 60265-1.

Safety
Personal safety Safe-to-touch and hermetically sealed primary enclosure Cable terminations, busbars and voltage transformers are surrounded by earthed layers All high-voltage parts including the cable terminations, busbars and voltage transformers are metal enclosed Capacitive voltage detecting system to verify safe isolation from supply Operating mechanisms and auxiliary switches safely accessible outside the primary enclosure (switchgear vessel) Due to the system design, operation is only possible with closed switchgear enclosure Standard degree of protection IP 65 for all high-voltage parts of the primary circuit, IP 3XD for the switchgear enclosure according to IEC 60529 and VDE 0470-1 High resistance to internal arcs by logical mechanical interlocks and tested switchgear enclosure Panels tested for resistance to internal faults up to 31.5 kA Logical mechanical interlocks prevent maloperation Make-proof earthing by means of the vacuum circuit-breaker. Security of operation Hermetically sealed primary enclosure independent of environmental effects (pollution, humidity and small animals) Maintenance-free in an indoor environment (IEC 62271-1 and VDE 0671-1) Operating mechanisms of switching devices accessible outside the primary enclosure (switchgear vessel) Metal-coated, plug-in inductive voltage transformers mounted outside the SF6 switchgear vessel Current transformers as ring-core current transformers mounted outside the SF6 switchgear vessel Complete switchgear interlocking system with logical mechanical interlocks Welded switchgear vessels, sealed for life Minimum re load Type and routine-tested Standardized, NC production processes Quality assurance in accordance with DIN EN ISO 9001 More than 500,000 switchgear panels of Siemens in operation worldwide for many years Option: Aseismic design. Reliability Type and routine-tested Standardized, NC production processes Quality assurance in accordance with DIN EN ISO 9001 More than 500,000 switchgear panels of Siemens in operation worldwide for many years.

6 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Requirements
Technology
General 3-pole enclosure of the primary part consisting of a switchgear vessel made of stainless steel Insulating gas SF6 Three-position switch as busbar disconnector and feeder earthing switch Make-proof earthing by means of the vacuum circuit-breaker Compact dimensions due to SF6 insulation Hermetically tight, welded switchgear vessel made of stainless steel 1-pole, solid-insulated, screened busbars, plug-in type Cable connection with outside-cone plug-in system, or for connection of solid-insulated bars Wall-standing or free-standing arrangement Cable connection access from front Option: Cable connection access from rear (only circuit-breaker panel 1250 A) Installation and extension of existing switchgear at both ends without gas work and without modication of existing panels. Interlocks According to IEC 62271-200 and VDE 0671-200 Logical mechanical interlocks prevent maloperation Three-position disconnector can only be operated with circuitbreaker in OPEN position Circuit-breaker or contactor can only be operated with threeposition switch in end position and operating lever removed Switch-disconnector, contactor, ring-main and metering panels are not interlocked due to their own switching capacity Three-position disconnector interlocked against the circuitbreaker in circuit-breaker panels and in bus sectionalizers with one panel width Feeder locking device Locking device for three-position switch Cable compartment cover (access to HV HRC fuses) always interlocked against the three-position switch-disconnector in panels with HV HRC fuses (switch-disconnector panel, metering panel and contactor panel with fuses) Option: Cable compartment cover interlocked against the three-position switch (circuit-breaker panel, disconnector panel, contactor panel without fuses, ring-main panel) Option: Electromagnetic interlocks Option: Actuating openings can be padlocked Option: Feeder earthed locking device. Modular design Panel replacement possible without SF6 gas work Low-voltage compartment removable, plug-in bus wires. Instrument transformers Current transformers not subjected to dielectric stress Easy replacement of current transformers designed as ring-core transformers Metal-coated, plug-in and disconnectable voltage transformers. Vacuum circuit-breaker Maintenance-free under normal ambient conditions according to IEC 62271-1 and VDE 0671-1 No relubrication or readjustment Up to 10,000 operating cycles Vacuum-tight for life. Secondary systems Customary protection, measuring and control equipment Option: Numerical multifunction protection relay with integrated protection, control, communication, operating and monitoring functions Can be integrated in process control systems.

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 7

Technical data
Electrical data, lling pressure, temperature for single-busbar switchgear
Common electrical data, lling pressure and temperature kV Rated voltage Ur Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV Hz Rated frequency fr Rated normal current Ir 3) for the busbar up to A Rated lling level pre 4) Minimum functional level pme 4) Ambient air temperature Rated insulation level 7.2 20 1) 23 1) 12 28 2) 32 2) 15 36 39 17.5 38 45 24 50 60 125 145 50 / 60 2500

75 2) 95 95 60 1) 70 1) 85 2) 110 110 50 / 60 50 / 60 50 / 60 50 / 60 2500 2500 2500 2500 150 kPa (absolute) at 20 C 130 kPa (absolute) at 20 C 5 C to +55 C

Data of the switchgear panels


Circuitbreaker panel 630 A for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated short-circuit making current Ima Rated short-circuit breaking current Isc at rated normal current Electrical endurance of vacuum circuit-breakers at rated short-circuit breaking current Rated normal current Ir 3) Rated normal current Ir 3) Rated short-time withstand current Ik A up to kA up to kA up to kA up to kA up to kA 630 630 630 20 | 25 20 | 25 20 | 25 20 | 20 | 20 | 50 | 63 50 | 63 50 | 63 50 | 63 50 | 63 50 | 63 20 | 25 20 | 25 20 | 25 10 000 operating cycles 50 breaking operations 1000 1000 1000 1250 1250 1250 2000 2000 2000 2500 2500 2500 31.5 31.5 31.5 31.5 31.5 31.5 80 80 80 80 80 80 31.5 31.5 31.5 10 000 operating cycles 50 breaking operations 1000 1250 2000 2500 31.5 31.5 80 200 31.5 31.5 80 80 292 8) 630 20 | 25 20 | 50 | 63 50 | 63 1000 1250 2000 2500 31.5 31.5 80 200 31.5 31.5 80 80 292 8) 630 20 | 25 20 | 50 | 63 50 | 63 450 31.5 9) 31.5 9) 80 80 1000 1250 2000 2500 31.5 31.5 80 200 31.5 31.5 80 80 442 630 20 | 25 20 | 50 | 63 50 | 63 450 31.5 9) 31.5 9) 80 80 630 20 | 25 20 | 50 | 63 50 | 63 20 | 25 630 20 | 25 20 | 50 | 63 50 | 63 20 | 25

Circuit-breaker panel and bus sectionalizer, 1000 A 5) 1250 A 6) 2000 A 2500 A

Rated short-time withstand current Ik

for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated short-circuit making current Ima Rated short-circuit breaking current Isc at rated normal current Electrical endurance of vacuum circuit-breakers at rated short-circuit breaking current

A A A A up to kA up to kA up to kA up to kA up to kA

1000 1250 2000 25 25 63 63 25

1000 1250 2000 25 25 63 63 25

Disconnecting Rated normal current Ir 3) panel 1000 A 5) 1250 A 2000 A Rated short-time withstand 2500 A current Ik

for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated normal current Ir 3) Rated short-time withstand current Ik

A A A A up to kA up to kA up to kA A up to kA up to kA up to kA up to kA mm A up to kA up to kA up to kA up to kA

1000 1250 2000 25 25 63 200 25 25 63 63 442 630 20 | 25 20 | 50 | 63 50 | 63 450 25 9) 25 9) 63 63

1000 1250 2000 25 25 63 200 25 25 63 63 442 630 20 20 50 50 450 25 9) 25 9) 63 63

Switchdisconnector panel (with HV HRC fuses)

for feeder 7) for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip 7) Rated short-circuit making current Ima 7) Dimension e of HV HRC fuse-links Rated normal current Ir 3) Rated short-time withstand current Ik for feeder for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated short-circuit making current Ima for feeder 7) for switchgear with tk = 1 s

Ring-main panel (switchdisconnector panel without fuses) Vacuum contactor panel (with HV HRC fuses)

Rated normal current Ir 3) Rated short-time withstand current Ik

A 450 up to kA 31.5 9) up to kA 31.5 9) up to kA 80 up to kA 80

for switchgear with tk = 3 s Rated peak withstand current Ip 7) Rated short-circuit making current Ima 7) Electrical endurance at rated normal current Dimension e of HV HRC fuse-links

100 000 or 500 000 operating cycles mm 292 8) 442 442 442 442 up to kA 31.5 up to kA 31.5 up to kA 80 mm 292 8) 31.5 31.5 80 292 8) 31.5 31.5 80 442 25 25 63 442 25 25 63 442

Metering panel (with HV HRC fuses)

Rated short-time withstand current Ik

for switchgear with tk = 1 s for switchgear with tk = 3 s

Rated peak withstand current Ip 7) Dimension e of HV HRC fuse-links

8 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Technical data
Electrical data, lling pressure, temperature for double-busbar switchgear
Common electrical data, lling pressure and temperature kV Rated voltage Ur Rated short-duration power-frequency withstand voltage Ud: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV Rated lightning impulse withstand voltage Up: phase-to-phase, phase-to-earth, open contact gap kV across the isolating distance kV Hz Rated frequency fr Rated normal current Ir 3) for the busbar up to A Rated lling level pre 4) Minimum functional level pme 4) Ambient air temperature Rated insulation level 7.2 20 1) 23 1) 12 28 2) 32 2) 15 36 39 17.5 38 45 24 50 60 125 145 50 / 60 2500

75 2) 95 95 60 1) 70 1) 85 2) 110 110 50 / 60 50 / 60 50 / 60 50 / 60 2500 2500 2500 2500 150 kPa (absolute) at 20 C 130 kPa (absolute) at 20 C 5 C to +55 C

Data of the switchgear panels


Circuit-breaker panel, bus coupler 10) 1000 A for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated short-circuit making current Ima Rated short-circuit breaking current Isc at rated normal current Electrical endurance of vacuum circuit-breakers at rated short-circuit breaking current Rated normal current Ir 3) Rated short-time withstand current Ik for switchgear with tk = 1 s for switchgear with tk = 3 s Rated peak withstand current Ip Rated short-circuit making current Ima Rated short-circuit breaking current Isc at rated normal current Electrical endurance of vacuum circuit-breakers at rated short-circuit breaking current Rated normal current Ir 3) Rated short-time withstand current Ik A up to kA up to kA up to kA up to kA up to kA 1000 1000 1000 25 25 25 25 25 25 63 63 63 63 63 63 25 25 25 10 000 operating cycles 50 breaking operations 1250 1250 1250 25 25 25 25 25 25 63 63 63 63 63 63 25 25 25 10 000 operating cycles 50 breaking operations 1000 25 25 63 63 25 1000 25 25 63 63 25

Incoming sectionalizer 1250 A

A up to kA up to kA up to kA up to kA up to kA

1250 25 25 63 63 25

1250 25 25 63 63 25

Further panel types

The above-mentioned panel types can on request be combined with panel types of the single-busbar range.

Footnotes for pages 8 and 9 1) Higher values of the rated short-duration power-frequency withstand voltage available with: 32 kV for phase-to-phase, phase-to-earth and open contact gap, as well as 37 kV across the isolating distance Higher values of the rated lightning impulse withstand voltage: 60 kV for phase-to-phase, phase-to-earth and open contact gap, as well as 70 kV across the isolating distance 2) Higher values of the rated short-duration power-frequency withstand voltage available with: 42 kV for phase-to-phase, phase-to-earth and open contact gap, as well as 48 kV across the isolating distance Higher values of the rated lightning impulse withstand voltage: 95 kV for phase-to-phase, phase-to-earth and open contact gap, as well as 110 kV across the isolating distance 3) The rated normal currents apply to ambient air temperatures of max. 40 C. The 24-hour mean value is max. 35 C (according to IEC 62271-1 / VDE 0671-1) 2500 A with natural ventilation

4) Pressure values for SF6-insulated switchgear vessels 5) Bus sectionalizer panel 1000 A and disconnector panel 1000 A only possible with rated short-time withstand current Ik 25 kA (tk 1 s and 3 s), rated peak withstand current Ip 63 kA and rated short-circuit breaking current ISC 25 kA 6) Bus sectionalizer panel 1250 A in 2 panel widths only possible with rated short-time withstand current Ik 25 kA (tk 1 s and 3 s), rated peak withstand current Ip 63 kA and rated short-circuit breaking current ISC 25 kA 7) Depending on the HV HRC fuse-link, observe max. permissible let-through current ID of the HV HRC fuse-links 8) Extension tube (150 mm long) required additionally 9) Applies to combination of vacuum contactor with HV HRC fuses: Vacuum contactor without HV HRC fuse reaches rated short-time withstand current Ik 8 kA (tk 1 s) and rated peak withstand current Ip 20 kA (applies to the complete switchgear) 10) Bus coupler 1250 A on request

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 9

Technical data
Room planning
Switchgear installation For single-busbar applications: Wall-standing arrangement or Free-standing arrangement Face-to-face arrangement accordingly For double-busbar applications: Back-to-back arrangement (freestanding arrangement). Room dimensions See opposite dimension drawings. Room height 2750 mm NXPLUS C, all technical data, all types of arrangement 2400 mm NXPLUS C, wall-standing arrangement with pressure relief duct, 25 kA 1 s and 3 s, busbar 1250 A, LV compartment 761 mm. Door dimensions The door dimensions depend on the dimensions of the individual panels (see pages 12 to 20). Switchgear xing For oor openings and xing points of the switchgear, see pages 12 to 20 Foundations: Steel girder construction Steel-reinforced concrete with foundation rails, welded or bolted on. Panel dimensions See pages 12 to 20. Weights Single-busbar panels Panels for 1250 A: Approx. 800 kg Panels for > 1250 A: Approx. 1400 kg. Double-busbar panels Panels for 1250 A: Approx. 1600 kg.
HA35-2530f eps

Room planning for single-busbar switchgear


175**** 125*

50

1225

1100

1225

50

HA35-2529h eps

52

52

50***

50***

800**

Wall-standing arrangement (top view) Panels without pressure relief duct

Wall-standing arrangement (same as left side) but panels with pressure relief duct

500

125*

* Rear pressure relief duct: Depth 125 mm ** Depending on national requirements; for extension/panel replacement: Control aisle 1400 mm recommended (600 mm panels) 1600 mm recommended (900 mm panels) *** Lateral wall distances on the left or on the right: 500 mm is recommended **** 125 mm, if there are exclusively 600 mm panels

600

900

600

52

50***

Room height 2800 mm

52

50***

Free-standing arrangement (top view) Panels with pressure relief duct

Room planning for double-busbar switchgear


800**

600

2370

800**

1225

HA35-2531d eps

52

50***

Room height 2800 mm

52

500***

800**

** For panel replacement: Control aisle 1400 mm necessary *** Lateral wall distance 50 mm optionally possible on the left or on the right

Free-standing arrangement (top view)

10 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

1100

600

900

600

600

Technical data
Shipping data, classication
Transport NXPLUS C switchgear is delivered in form of individual panels. Please observe the following: Transport facilities on site Transport dimensions and transport weights Size of door openings in building. In case of double-busbar panels the A and B sides are supplied separately. Packing Place of destination inside Germany or other European countries Means of transport: Rail and truck Type of packing: Panels on pallets Open packing with PE protective foil. Place of destination overseas Means of transport: Ship Type of packing: Panels on pallets In closed crates with sealed upper and lower PE protective foil With desiccant bags With sealed wooden base Max. storage time: 6 months. Transport dimensions, transport weights 1)
Panel widths mm Transport dimensions Width Height Depth mm mm mm Transport weight with packing approx. kg without packing approx. kg

Single-busbar switchgear transport inside Germany or to European countries


1 600 1 900 1 600 (top-rear cable connection) 1100 2470 1450 1450 2470 1450 1100 2470 2100 900 1500 900 800 1400 800

Transport to overseas
1 600 1 900 1 600 (top-rear cable connection) 1130 2650 1450 1480 2650 1450 1130 2650 2100 900 1500 900 800 1400 800

Double-busbar switchgear transport inside Germany or to European countries


1 600 1100 2470 1450 900 800

Transport to overseas
1 600 1130 2650 1450 900 800

Classication of NXPLUS C switchgear according to IEC 62271-200 Design and construction


Partition class Loss of service continuity category 2) Panels with HV HRC fuses Panels without HV HRC fuses Accessibility to compartments (enclosure) Busbar compartment Switching device compartment Low-voltage compartment Cable compartment without HV HRC fuses with HV HRC fuses PM (metallic partition) LSC 2A LSC 2B

Tool-based Non-accessible Tool-based Tool-based Interlock-controlled and tool-based

Internal arc classication


Designation of the internal arc classication IAC IAC class for: Wall-standing arrangement Free-standing arrangement Type of accessibility A F L R Arc test current Test duration 7.2 kV, 12 kV, 15 kV IAC A FL IAC A FLR 31.5 kA, 1 s 31.5 kA, 1 s 17.5 kV, 24 kV IAC A FL IAC A FLR 25 kA, 1 s 25 kA, 1 s

Switchgear in closed electrical service location, access for authorized personnel only according to IEC 62271-200 Front Lateral Rear (for free-standing arrangement) 25 kA, 31.5 kA 1s

1) Average values depending on the degree to which panels are equipped 2) The loss of service continuity category is always referred to the complete switchgear, i.e. the panel with the lowest category determines the loss of service continuity category of the complete switchgear Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 11

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Circuit-breaker panels
409 761 409 761 409 761 732 2) 125 1100
4)

2250 1)

1726

1726

HA35-2574b eps

702

702

1726

584 600 125 125 1100 125 1100

584

50

630 A
420

1000 A

1250 A

280

30

100

100

1200

3
920 46

4
700

1
180

5
30

4
100 600

3
100

25 3)

409 761

Legend and footnotes for pages 12 and 13


2550 1)

1 Floor opening for control cables 2 Option: Pressure relief duct


1726

3 Fixing hole for M8 / M10 4 Fixing hole for M8 / M10 (only for aseismic design)
577

HA35-2604e eps

5 Floor opening for highvoltage cables 6 Cable compartment / pressure relief duct 1) 2650 mm for higher lowvoltage compartment 2) 752 mm for deeper cable compartment cover 3) 45 mm for deeper cable compartment cover 4) 1120 mm for deeper cable compartment cover 5) When only one cable is connected, the dimension is reduced by 275 mm 6) 1245 mm for deeper cable compartment cover

732 900 12256)

2)

50

280

30

1200

3
920 46

4 3
100 700

1
180

5 4
700 900

25 3)

100

12 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

30

420

270

360

270

2000 A and 2500 A

702

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Circuit-breaker panels (cable connection from top rear)
409 761 474 5) 600 750 5) 1100

22501)

HA35-2573b eps

1726 702

1250 A
500

905 5)

30

1825 5)

100

100

3
920 46

4
700

1
180

25

100 600

100

For legend and footnotes, see page 12 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 13

30

1045 5)

750 5)

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Disconnector panels
409 761 409 761 732 2) 125 1100 4)

22501)

1726

HA35-2506g eps

702

1726

584 600 125 125 1100

50

1000 A
420

1250 A

280

30

100

100

1200

3
920 46

4
700

1
180

5
30

4
100 600

3
100

253)

409 761

2550 1)

702

Legend and footnotes for pages 14 and 15 1 Floor opening for control cables
577

HA35-2605e eps

1726

2 Option: Pressure relief duct 3 Fixing hole for M8 / M10 4 Fixing hole for M8 / M10 (only for aseismic design) 5 Floor opening for highvoltage cables 1) 2650 mm for higher lowvoltage compartment 2) 752 mm for deeper cable compartment cover

732 900 1225


6)

2)

50

280 30

1200

3
920 46

4
700

1
180

5 4
700 900

420

270

360

270

2000 A and 2500 A

30

3
100

3) 45 mm for deeper cable compartment cover 4) 1120 mm for deeper cable compartment cover 6) 1245 mm for deeper cable compartment cover

25 3)

100

14 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Bus sectionalizers with one or two disconnectors (1 panel width)
409 761 409 761 1100

22501)

2250

1726

HA35-2575b eps

600

600 125

125

1100

50

1000 A
420

1726 125

1250 A

280

30

100

100

1200

3
920 46

4
700

1
180

25

100 600

100

30

409 761 25501) 25501)


HA35-2606d eps

900

900

1726

1225

50

280 30

1200

3
920 46

4 3
100 700

1
180

25 3)

100

700 900

30

420

270

360

270

2000 A and 2500 A

For legend and footnotes, see page 14 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 15

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Bus sectionalizers with disconnector (2 panel widths)
409 761 1100

22501)

HA35-2511g eps

1200

50

125

1726 125

280 30

1200

3
920 46

4 4 3
100 700

1
180

100

400 1200

400

25

30

420

100

400

400

1250 A
100

Legend and footnotes for pages 16 and 17 1 Floor opening for control cables 2 Option: Pressure relief duct 3 Fixing hole for M8 / M10 4 Fixing hole for M8 / M10 (only for aseismic design) 5 Floor opening for highvoltage cables 7 Option: HV HRC fuses 1) 2650 mm for higher lowvoltage compartment 16 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Dimensions
Front views, sections, oor openings, xing points for single-busbar switchgear
Switch-disconnector panel with HV HRC fuses
409 761

Ring-main panel (switch-disconnector panel without HV HRC fuses)


2
409 761 584 600 125 125 1100 700 420 409 761 1100

22501)

1726

22501)

7
HA35-2514h eps

HA35-2512e eps

1726

584 600 125 125 1100

450

50

280

280

30

420

100

100

30

50

100

100

1200

920

700

46

1200 920

3 1
180

3
46

5
30

180

600

25

100

100

100 600

100

25

Vacuum contactor panel with HV HRC fuses


2
409 761

Metering panel with HV HRC fuses

22501)

1726

22501)

7
HA35-2513f eps HA35-2515f eps

1726

30

5 4 3

584

450

600

125 125

50

125

50

600

125

1100

280

280

30

420

100

100

1200

920

920

180

180

30

4
100 600

3
100

25

25

100 600

100

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 17

30

700

46

For legend and footnotes, see page 16

700

1200

3
46

420

30

100

100

702

Dimensions
Front views, sections, oor openings, xing points for double-busbar switchgear
Circuit-breaker panels
43 409 761 702 732 2) 600 100 100 600 1100 2370 6) 25 30 1100 4)

Side A

Side B

Side B

340

Side A

2
22501) 22501)

HA35-2568e eps

1726

1000 A 1 4 3

920 860

3 4

2318

100

100

30

2
100

100

3
920 860 46

4
700 100 30

1
180

5 4
100 600

25 3)

30

Legend and footnotes for pages 18 and 19 1 Floor opening for control cables 2 Pressure relief duct 3 Fixing hole for M8 / M10 4 Fixing hole for M8 / M10 (only for aseismic design) 5 Floor opening for highvoltage cables 1) 2650 mm for higher lowvoltage compartment 2) 752 mm for deeper cable compartment cover 3) 45 mm for deeper cable compartment cover 4) 1120 mm for deeper cable compartment cover 6) 2390 mm for deeper cable compartment cover 18 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Dimensions
Front views, sections, oor openings, xing points for double-busbar switchgear
Incoming sectionalizer
43 409 702 732 2) 600 100 100 600 1100 2370 6) 25 30 1100 4) 761

Side A

Side B

Side B

Side A

22501)

22501)

HA35-2569e eps

1726

340

1250 A 1 4 3

3 5 4
100 30 100

920 860

2318

100 100

3
920 860 46

4
700 100 30

1
180

5 4
100 600

For legend and footnotes, see page 18 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 19

25 3)

30

700

Dimensions
Front views, sections, oor openings, xing points for double-busbar switchgear
Bus coupler
43 409 761

Side A

Side B

Side B

340

Side A

2
22501) 22501)

HA35-2570d eps

600 100 100

600

1726

1100 2370

1100

25

30

1000 A 1 4 3

920

860

3 4

2318

100 30 100

100

100

3
920 860 46

4
700

1
180

25

100 600

100

30

30

1 Floor opening for control cables 2 Pressure relief duct 3 Fixing hole for M8 / M10 4 Fixing hole for M8 / M10 (only for aseismic design) 1) 2650 mm for higher lowvoltage compartment 20 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Product range
Single-busbar panels
Circuit-breaker panels
Three-position disconnector

Vacuum circuit-breaker

Plug-in voltage transformer


1)

or

and/or

or

or

and/or

or

Disconnectable and plug-in voltage transformer

and/or

or

and/or

and/or

or

Current transformer
HA35-2488g eps

and/or

HA35-2489f eps

and/or

or

Capacitive voltage detecting system 1000 A and 1250 A

630 A

Busbar earthing switch

Surge arrester or limiter


HA35-2541b eps

Cable connection with outside-cone plug (not included in the scope of supply)
or and/or or or or

and/or

or

and/or

or

and/or

or

and/or

Cable connection with outside-cone plug (not included in the scope of supply)

HA35-2608b eps

HA35-2576b eps

2000 A and 2500 A

1250 A, top-rear cable connection

1) Only for 1250 A Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 21

Product range
Single-busbar panels
Bus sectionalizers Disconnector panels
Three-position disconnector

Vacuum circuit-breaker
L1 L2 L3 L3 L2 L1

Inverted phases
HA35-2493e eps

L1 L2 L3 L3 L2 L1

1)

or

or

1250 A, 1 panel width

Plug-in voltage transformer

and/or

or

HA35-2491f eps

and/or

and/or

or

Disconnectable and plug-in voltage transformer

Current transformer 1000 A and 1250 A Capacitive voltage detecting system

Busbar earthing switch


or and/or

Surge arrester or limiter


HA35-2494c eps

1250 A, 2 panel widths

L1 L2 L3 L3 L2 L1

or

or

Cable connection with outside-cone plug (not included in the scope of supply)

and/or

or

HA35-2609c eps

and/or

and/or

or

HA35-2610b eps

2000 A and 2500 A

2000 A and 2500 A, 1 panel width

1) Only for 1250 A

Cable connection with outside-cone plug (not included in the scope of supply)

22 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

HA35-2541b eps

and/or

Product range
Single-busbar panels
Switch-disconnector panel Ring-main panel
Three-position switch-disconnector

Vacuum contactor

HV HRC fuses

Plug-in voltage transformer


or or or and/or or

and/or

or

and/or

or

Disconnectable and plug-in voltage transformer

HA35-2496d eps

and/or

HA35-2498g eps

and/or

Current transformer

Capacitive voltage detecting system

Vacuum contactor panel

Metering panel
2nd earthing switch for fuses
HA35-2541b eps

Surge arrester or limiter

1)

Cable connection with outside-cone plug (not included in the scope of supply)
or

or

or

and/or

and/or

or

and/or

HA35-2497g eps

and/or

HA35-2499d eps

and/or

1) Only possible when vacuum contactor panel is designed without fuse Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 23

Product range
Double-busbar panels
Circuit-breaker panels Incoming sectionalizer
Three-position disconnector

SS1 SS2 SS2

SS1

Vacuum circuit-breaker

Plug-in voltage transformer

or

and/or

or

or

or

or

or

Disconnectable and plug-in voltage transformer

and/or

or

and/or

and/or

or

and/or

1000 A

HA35-2502i eps

and/or

or

and/or

and/or

or

and/or

Plug-in voltage transformer, mounted separately, connected through a short cable

HA35-2500f eps

1250 A

Bus coupler
SS1 SS2

Current transformer

Capacitive voltage detecting system

Panel bars
HA35-2541b eps

Surge arrester or limiter

or

or

and/or

and/or

Cable connection with outside-cone plug (not included in the scope of supply)

HA35-2503b eps

and/or

and/or

1000 A Abbreviations: SS1 = Busbar 1 SS2 = Busbar 2 24 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Design
Basic panel design
Insulating system Switchgear vessel lled with SF6 gas Features of SF6 gas: Non-toxic Odorless and colorless Non-inammable Chemically neutral Heavier than air Electronegative (high-quality insulator) Pressure of SF6 gas in the switchgear vessel (absolute values at 20 C): Rated lling level: 150 kPa Design pressure: 180 kPa Design temperature of the SF6 gas: 80 C Operating pressure of bursting disc: 300 kPa Bursting pressure: 550 kPa Gas leakage rate: < 0.1 % per year. Panel design Factory-assembled, type-tested Metal-enclosed, metal-clad Hermetically tight, welded switchgear vessel made of stainless steel 1-pole, solid-insulated, screened busbars, plug-in type Maintenance-free Degree of protection IP 65 for all high-voltage parts of the primary circuit IP 3XD for the switchgear enclosure Vacuum circuit-breaker or vacuum contactor Three-position disconnector for disconnecting and earthing by means of the circuit-breaker Make-proof earthing by means of the vacuum circuit-breaker Three-position switch-disconnector Cable connection with outside-cone plug-in system according to DIN EN 50 181 Wall-standing or free-standing arrangement Installation and possible later extension of existing panels without gas work Replacement of switchgear vessel without gas work Replacement of instrument transformers without gas work, as they are located outside the gas compartments Enclosure made of sendzimir-galvanized sheet steel, front cover, rear cover and end walls powder-coated in color light basic (SN 700) Low-voltage compartment removable, plug-in bus wires Lateral, metallic wiring ducts for control cables. Circuit-breaker panel (example)

1 2

15 16 17 18

19 20

30

3 4 5 6 7

21 22 23 24 25 26 27 28
HA35-2516e eps

31 32 33 36 34

29 35 Front view Side view (cable connection from the front)

Detail Z:
8 9 10 11 12 13 14 1 Low-voltage compartment 2 Multifunction protection relay SIPROTEC 4 (example) 3 Position indicator for circuit-breaker 4 Actuating opening for charging the circuitbreaker springs 5 ON pushbutton for circuit-breaker 6 Spring charged indicator 7 Operations counter for circuit-breaker 8 Position indicator for disconnecting function of three-position switch 9 Ready-for-service indicator 10 Position indicator for ready-to-earth function of three-position switch 11 Control gate and locking device for disconnecting/earthing functions of three-position switch 12 Interrogation lever 13 Actuating opening for disconnecting function of three-position switch 14 Actuating opening for ready-to-earth function of three-position switch 15 Option: Busbar voltage transformer, plug-in type 16 Busbar, 1-pole, fully insulated, plug-in type, earthed on the outside 17 Option: Busbar current transformer 18 Switchgear vessel, hermetically welded, lled with SF6 gas 19 Three-position disconnector 20 OFF pushbutton for circuit-breaker 21 Vacuum interrupter of circuit-breaker 22 Pressure relief (bursting disc) 23 Capacitive voltage detecting system 24 Feeder locking device (suitable for padlocking) 25 Disconnecting facility for feeder voltage transformer 26 Bushing for feeder voltage transformer 27 Option: Feeder voltage transformer 28 Option: Pressure relief duct 29 Cable compartment 30 Operating mechanism for three-position switch 31 Operating mechanism for circuit-breaker 32 Feeder current transformer 33 Cable connection with outside-cone T-plug 34 Operation of disconnecting facility of the feeder voltage transformer 35 Earthing busbar with earthing connection 36 Air guides for cable connection

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 25

Components
Vacuum circuit-breaker
Features According to IEC 62271-100 and VDE 0671-100 (for standards, see page 58) Application in hermetically welded switchgear vessel in conformity with the system Climate-independent vacuum interrupter poles in the SF6-lled switchgear vessel Maintenance-free for indoor installation according to IEC 62271-1 and VDE 0671-1 Individual secondary equipment A metal bellows is used for gasketless separation of the SF6 insulation and the operating mechanism (already used with success for over 2 million vacuum interrupters). Trip-free mechanism The vacuum circuit-breaker is tted with a trip-free mechanism according to IEC 62271 and VDE 0671. Switching duties and operating mechanisms The switching duties of the vacuum circuit-breaker are dependent, among other factors, on its type of operating mechanism. Motor operating mechanism Motor-operating stored-energy mechanism For auto-reclosing (K) For synchronization and rapid load transfer (U) Further operating mechanism features Located outside the switchgear vessel in the operating mechanism box and behind the control board Stored-energy spring mechanism for 10,000 operating cycles. Operating mechanism functions Motor operating mechanism 1) (M1 *) In the case of motor operating mechanism, the closing spring is charged by means of a motor and latched in the charged position (spring charged indication is visible). Closing is effected either by means of an ON pushbutton or a closing solenoid. The closing spring is recharged automatically (for auto-reclosing). Endurance class of circuit-breaker
Function BREAKING Class M2 E2 Standard IEC 62271-100 IEC 62271-100 Property of NXPLUS C 10,000 times mechanically without maintenance 10,000 times rated normal current without maintenance 50 times short-circuit breaking current without maintenance
HA35-2276e eps

Vacuum circuit-breaker
R-HA35-050 eps

1 2 3 4 5 6

8 9 10 11

Open on the side of the operating mechanism 1 2 3 4 5 6 7 8 9 10 11 Gear with motor (M1 *) Position switch (S4 *) Closing spring Closing spring charged indication Closing solenoid (Y9 *) Operations counter Auxiliary switch 6 NO + 6 NC (S1 *), option: 12 NO + 12 NC CLOSED / OPEN position indicator for circuit-breaker Option: 2nd release (Y2 *) 1st release (Y1 *) Feeder locking device

12

13

14

15

16

17

18

C2

IEC 62271-100

Very low probability of restrikes

19

Operating times
Closing time Opening time Arcing time at 50 Hz Break time Dead time Total charging time 1st release 2nd release Closing solenoid 1st release 2nd release < 75 ms < 65 ms < 50 ms < 15 ms < 80 ms < 65 ms 300 ms < 15 s

Section through the vacuum circuit-breaker 12 13 14 15 16 17 18 19 Fixed terminal Pole support Vacuum interrupter Moving terminal Metal bellows Switchgear vessel, SF6-insulated, with vacuum interrupter Operating mechanism box (see gure above) Operating kinematics

Abbreviations for switching duties: U = Synchronization and rapid load transfer (closing time 90 ms) K = Auto-reclosing 1) Motor rating at * Item designation 24 V to 240 V DC: 600 W 100 V and 240 V AC: 750 VA

For further technical data and description of typical applications, please refer also to Catalog HG 11.05 3AH5 Vacuum CircuitBreakers.

26 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Vacuum circuit-breaker
Secondary equipment The scope of the secondary equipment of the vacuum circuitbreaker depends on the type of application and offers a wide range of variations, thus allowing even the highest requirements to be satised: Closing solenoid Type 3AY15 10 (Y9 *) For electrical closing. Shunt releases Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store Tripping by protection relay or electrical actuation. C.t.-operated release Type 3AX11 02 (Y4 *), 0.5 A Type 3AX11 04 (Y6 *) for tripping pulse 0.1 Ws in conjunction with suitable protection systems Used if external auxiliary voltage is missing, tripping via protection relay. Undervoltage release Type 3AX11 03 (Y7 *) Comprising: Energy store and unlatching mechanism Electromagnetic system, which is permanently connected to voltage while the vacuum circuit-breaker is closed; tripping is initiated when this voltage drops Connection to voltage transformers possible. Anti-pumping (mechanical and electrical) Function: If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= pumping) is avoided. Circuit-breaker tripping signal For electrical signaling (as pulse > 10 ms), e.g. to remote control systems, in the case of automatic tripping (e.g. protection) Via limit switch (S6 *) and cut-out switch (S7 *). Varistor module To limit overvoltages to approx. 500 V for protection devices (when inductive components are mounted in the vacuum circuit-breaker) For auxiliary voltages 60 V DC. Auxiliary switch Type 3SV9 (S1 *) Standard: 6 NO + 6 NC, free contacts thereof 1) 3 NO + 4 NC Option: 12 NO + 12 NC, free contacts thereof 1) 9 NO + 6 NC. Position switch Type 3SE4 (S4 *) For signaling closing spring charged. Mechanical interlock Mechanical interlocking to the three-position disconnector During operation of the three-position switch, the vacuum circuit-breaker cannot be operated. Switching rate of the vacuum interrupter
HA35-2539b en eps

20,000

Permissible operating cycles

10,000 5,000 2,000 1,000 500 200 100 50 1 20 10 1 2 5 10 kA 20 2

25 31.5

50

Breaking current (r.m.s. value)

Electrical data (curve 1) Rated voltage 24 kV Rated short-circuit breaking current 25 kA Rated normal current 2000 A Electrical data (curve 2) Rated voltage 15 kV Rated short-circuit breaking current 31.5 kA Rated normal current 2500 A Rated operating sequences Rapid load transfer (U): O-t-CO-t-CO (t 0.3 s, t 3 min) Auto-reclosing (K): O-t-CO-t-CO (t 0.3 s, t 3 min) Multiple-shot reclosing: O-t-CO-t-CO-t-CO-t-CO (t 0.3 s, t 15 s)

O = OPEN operation CO = CLOSE operation with subsequent OPEN operation at the shortest internal close-open time of the vacuum circuit-breaker

Possible release combinations


Release 1st shunt release type 3AY15 10 2nd shunt release type 3AY11 01 C.t.-operated release type 3AX11 02, 0.5 A, or type 3AX11 04, 0.1 Ws Undervoltage release type 3AX11 03 Release combination 1 2

1 unit of each release, a maximum of 2 releases can be combined only.

1) For utilization by the customer * Item designation Abbreviations: NO = normally open contact NC = normally closed contact Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 27

Components
Three-position switches
Common features According to IEC 62271-102 and VDE 0671-102 (for standards, see page 58) Application in hermetically welded switchgear vessel in conformity with the system Climate-independent contacts in the SF6-lled switchgear vessel Maintenance-free for indoor installation according to IEC 62271-1 and VDE 0671-1 Individual secondary equipment A metal bellows is used for gasketless separation of the SF6 insulation and the operating mechanism (already used with success for over 2 million vacuum interrupters) A rotary bushing is used for separation of the SF6 insulation and the operating mechanism (already used with success millions of times in medium-voltage and high-voltage switchgear) Compact design due to short contact gaps in SF6 gas Operation via gas-tight welded-in metal bellows or rotary bushing at the front of the switchgear vessel Reliable mechanical switch position up to the operating front of the panel (in double-busbar switchgear, the position indication for side B is done on side A via electrical position indicators). Three-position disconnector Application in: Circuit-breaker panel 1000 A to 2500 A (with interlock against the circuit-breaker) Disconnector panel 1000 A to 2500 A Bus sectionalizer 1000 A to 2500 A 2000 mechanical operating cycles for CLOSED / OPEN / READY-TO-EARTH. Three-position switch-disconnector Application in: Circuit-breaker panel 630 A (as disconnector with interlock against the circuit-breaker) Switch-disconnector panel Ring-main panel Contactor panel Metering panel 2000 1) mechanical operating cycles for CLOSED / OPEN / EARTHED Switching functions as general-purpose switchdisconnector according to: IEC 60265-1 VDE 0670-301 IEC 62271-102 VDE 0671-102 (for standards, see page 58) Designed as a multi-chamber three-position switch with the functions: Switch-disconnector and Make-proof earthing switch. Switch positions of the three-position switches
HA35-2518a eps

CLOSED

1 2 3 4

OPEN

R-HA35-040a eps

Feeder EARTHED

Switch positions Three-position disconnector (in OPEN position) with vacuum circuit-breaker arranged below (view into the switchgear vessel opened at the rear) 1 2 3 4 Fixed contact at the busbar Swivel-mounted contact blade Fixed contact for feeder EARTHED Operating shaft

9
HA35-2519a eps

CLOSED

R-HA35-047 eps

OPEN

Feeder EARTHED

8 Switch positions

Three-position switch-disconnector (exploded view) 5 6 7 8 9 Fixed contacts to earth Rotary contact blade Operating shaft Fixed contact to the feeder Fixed contact to the busbar

1) For switch-disconnector panel: 1000 mechanical operating cycles for CLOSED / OPEN / EARTHED 28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Three-position switches
Interlocks Selection of permissible switching operations by means of a control gate with mechanically interlocked vacuum circuitbreaker Corresponding operating shafts are not released at the operating front until they have been pre-selected with the control gate Operating lever cannot be removed until switching operation has been completed Circuit-breaker cannot be closed until control gate is in neutral position again Switchgear interlocking system also possible with electromechanical interlocks if switchgear is equipped with motor operating mechanisms (mechanical interlocking for manual operation remains). Switch positions CLOSED, OPEN, EARTHED or READY-TO-EARTH In circuit-breaker panels, earthing and short-circuiting the cable connection is completed by closing the vacuum circuit-breaker. Operating mechanism Spring-operated mechanism, used in: Circuit-breaker panels 630 A to 1250 A Bus sectionalizers 1000 A, 1250 A Disconnector panels 1000 A, 1250 A Vacuum contactor panel Metering panel Ring-main panel Slow motion mechanism, used in: Circuit-breaker panels 2000 A, 2500 A Bus sectionalizers 2000 A, 2500 A Disconnector panels 2000 A, 2500 A Spring-operated / stored-energy mechanism, used in: Switch-disconnector panel Spring-operated and spring-operated / stored-energy and slow motion mechanism actuated via operating lever at the operating front of the panel Separate operating shafts for the DISCONNECTING and EARTHING or READY-TO-EARTH functions Option: Motor operating mechanism for the DISCONNECTING and EARTHING or READY-TO-EARTH functions Spring-operated/stored-energy mechanism for the switch-disconnector function with fuses: Opening spring precharged (after closing) Maintenance-free due to non-rusting design of parts subjected to mechanical stress Bearings which require no lubrication. Transmission principle for operating mechanisms (see illustration) Transmission of operating power from outside into the gas-lled switchgear vessel by means of a metal bellows or a rotary bushing Gas-tight Maintenance-free.
HA35-2521a eps

Transmission principle for operating mechanisms


HA35-2520a eps

Three-position disconnector

2 1 Gas-lled switchgear vessel 2 Gas-tight welded-in metal bellows or rotary bushing Three-position switch-disconnector

Endurance class of three-position disconnector


Function DISCONNECTING READY-TO-EARTH EARTHING E2 1) IEC 62271-102 Class M1 Standard IEC 62271-102 Property of NXPLUS C 2000 times mechanically without maintenance 1000 times mechanically without maintenance 50 times rated shortcircuit making current Ima without maintenance

Endurance class of three-position switch-disconnector


Function DISCONNECTING LOAD BREAKING Class M1 2) M1 E3 Standard IEC 62271-102 IEC 60265-1 IEC 60265-1 Property of NXPLUS C 2000 times mechanically without maintenance 1000 times mechanically without maintenance 100 times rated mainly active load breaking current I1 without maintenance 5 times rated short-circuit making current Ima without maintenance 5 times rated short-circuit making current Ima without maintenance

EARTHING

E2

IEC 62271-102

1) By closing the circuit-breaker 2) For switch-disconnector panel: M0 1000 times mechanically without maintenance Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 29

Components
HV HRC fuse assembly
Features Application in: Switch-disconnector panel Contactor panel Metering panel HV HRC fuse-links according to DIN 43 625 (main dimensions) with striker in medium version according to IEC 60282 / VDE 0670-4 As short-circuit protection before transformers in the switch-disconnector panel As short-circuit protection before motors in the contactor panel As short-circuit protection before voltage transformers in the metering panel With selectivity (depending on correct selection) to upstream and downstream connected equipment 1-pole insulated Requirements according to IEC 62271-105 and VDE 067-105 fullled by combination of HV HRC fuses with the threeposition switch-disconnector Climate-independent and maintenance-free, with fuse boxes made of cast resin Fuse assembly connected to the three-position switchdisconnector via welded-in bushings and connecting bars Arrangement of fuse assembly below the switchgear vessel Fuses can only be replaced if feeder is earthed Option: Fuse tripped indication for remote electrical indication with 1 normally open contact. Mode of operation In the event that an HV HRC fuse-link has tripped, the switch is tripped via an articulation which is integrated into the cover of the fuse box (see gure). In the event that the fuse tripping fails, e.g. if the fuse has been inserted incorrectly, the fuse box is protected by thermal protection. The overpressure generated by overheating trips the switch via the diaphragm in the cover of the fuse box and via an articulation. This breaks the current before the fuse box incurs irreparable damage. This thermal protection works independently of the type and design of the HV HRC fuse used. Like the fuse itself, it is maintenance-free and independent of any outside climatic effects. Furthermore, the SIBA HV HRC fuses release the striker depending on the temperature and trip the three-position switch-disconnector as early as in the fuse overload range. Impermissible heating of the fuse box can be avoided in this way. Replacement of HV HRC fuse-links The transformer feeder has to be isolated and earthed. Subsequent manual replacement of the HV HRC fuse-link after removing the cable compartment cover.
Schematic sketches for fuse tripping

HV HRC fuse assembly


1 2

HA35-2522a eps

5 Basic design

Bushing Switchgear vessel Sealing cover with seal Tripping pin for spring-operated / stored-energy mechanism 5 Fuse box 6 HV HRC fuse-link 7 Striker of the HV HRC fuse-link and articulation for tripping the spring-operated / stored-energy mechanism 1 2 3 4

HA35-2523 eps

Fuse-link in service condition

Fuse tripping through striker

Fuse tripping through overpressure, e.g. if HV HRC fuse-link has been inserted incorrectly

30 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
The table shows the recommended HV HRC fuse-links make SIBA (electrical data valid for ambient air temperatures of up to 40 C) for fuse protection of transformers. Recommendation The three-position switch-disconnector in the transformer feeder (transformer switch) was combined with HV HRC fuse-links and tested in accordance with IEC 62271-105. Higher transformer ratings on request. Standards HV HRC fuse-links with striker in medium version according to IEC 60282 VDE 0670-4 and 402 DIN 43 625 main dimensions. Note: The exact selection of the SIBA fuse to be used is given in the NXPLUS C operating and installation instructions. Dimension e = 292 mm with extension tube SIBA 3400601

Transformer Operating voltage U kV 3.3 to 3.6 Rated power SN kVA 20 30 50 75 100 125 160 200 250 315 400 20 30 50 75 100 125 160 200 250 315 400 500 20 30 50 75 100 125
(continued on next page)

HV HRC fuse Relative impedance voltage uk % 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 Rated current I1 A 3.5 5.25 8.75 13.1 17.5 21.9 28 35 43.7 55.1 70 2.9 4.4 7.3 11 14.5 18.1 23.1 28.7 36.1 45.5 57.8 72.2 2.3 3.4 5.7 8.6 11.5 14.4 Rated normal current of fuse Ifuse A 6.3 10 10 16 16 20 20 25 31.5 40 31.5 40 40 50 50 63 63 80 80 100 100 6.3 10 16 16 20 20 25 25 31.5 31.5 40 40 50 50 63 63 80 80 100 100 6.3 6.3 10 10 16 16 20 16 20 20 25 Operating voltage Ufuse kV 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 Dimension e mm 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 30 098 13.6,3 30 098 13.10 30 098 13.10 30 098 13.16 30 098 13.16 30 098 13.20 30 098 13.20 30 098 13.25 30 098 13.31,5 30 098 13.40 30 098 13.31,5 30 098 13.40 30 098 13.40 30 098 13.50 30 098 13.50 30 099 13.63 30 099 13.63 30 099 13.80 30 099 13.80 30 099 13.100 30 099 13.100 30 098 13.6,3 30 098 13.10 30 098 13.16 30 098 13.16 30 098 13.20 30 098 13.20 30 098 13.25 30 098 13.25 30 098 13.31,5 30 098 13.31,5 30 098 13.40 30 098 13.40 30 098 13.50 30 098 13.50 30 099 13.63 30 099 13.63 30 099 13.80 30 099 13.80 30 099 13.100 30 099 13.100 30 098 13.6,3 30 098 13.6,3 30 098 13.10 30 098 13.10 30 098 13.16 30 098 13.16 30 098 13.20 30 098 13.16 30 098 13.20 30 098 13.20 30 098 13.25 Order No. Make SIBA

4 to 4.8

5 to 5.5

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 31

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 5 to 5.5 Rated power SN kVA 160 200 250 315 400 500 630 6 to 7.2 20 Relative impedance voltage uk % 4 4 4 4 4 4 4 4 Rated current I1 A 18.4 23 28.8 36.3 46.1 57.7 72.74 1.9 HV HRC fuse Rated normal current of fuse Ifuse A 31.5 40 40 50 40 50 50 63 63 80 80 100 63 6.3 6.3 6.3 6.3 6.3 6.3 10 10 10 16 16 16 16 16 16 16 16 16 20 20 20 20 20 20 25 25 25 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 50 50 50 50 50 50 63 63 63 63 63 80 80 Operating voltage Ufuse kV 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 3 to 7.2 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 Dimension e mm 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 442 292 292 292 442 292 292 442 30 098 13.31,5 30 098 13.40 30 098 13.40 30 098 13.50 30 098 13.40 30 098 13.50 30 098 13.50 30 099 13.63 30 099 13.63 30 099 13.80 30 099 13.80 30 099 13.100 30 099 13.100 30 004 13.6,3 30 098 13.6,3 30 101 13.6,3 30 004 13.6,3 30 098 13.6,3 30 101 13.6,3 30 098 13.10 30 004 13.10 30 101 13.10 30 098 13.16 30 004 13.16 30 101 13.16 30 098 13.16 30 004 13.16 30 101 13.16 30 098 13.16 30 004 13.16 30 101 13.16 30 098 13.20 30 004 13.20 30 101 13.20 30 098 13.20 30 004 13.20 30 101 13.20 30 098 13.25 30 004 13.25 30 101 13.25 30 098 13.31,5 30 004 13.31,5 30 101 13.31,5 30 098 13.31,5 30 004 13.31,5 30 101 13.31,5 30 098 13.40 30 004 13.40 30 101 13.40 30 098 13.40 30 004 13.40 30 101 13.40 30 098 13.50 30 004 13.50 30 101 13.50 30 098 13.50 30 004 13.50 30 101 13.50 30 012 43.63 30 099 13.63 30 012 13.63 30 102 13.63 30 012 43.63 30 012 43.80 30 102 43.80 Order No. Make SIBA

30

2.8

50

4.8

75

7.2

100

9.6

125

12

160

15.4

200

19.2

250

24

315

30.3

400

38.4

(continued on next page)

32 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 6 to 7.2 Rated power SN kVA 500 Relative impedance voltage uk % 4 Rated current I1 A 48 HV HRC fuse Rated normal current of fuse Ifuse A 80 80 80 80 80 100 100 100 100 100 100 100 125 125 125 6.3 6.3 5 6.3 6.3 10 10 16 16 16 16 20 20 31.5 31.5 31.5 31.5 40 40 50 50 63 63 80 80 100 100 6.3 6.3 5 6.3 6.3 10 10 16 16 16 16 20 20 25 25 31.5 31.5 40 40 50 50 Operating voltage Ufuse kV 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 6 to 12 6 to 12 3 to 7.2 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 Dimension e mm 292 442 292 292 442 292 442 292 292 442 292 442 292 442 442 292 442 292 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 292 442 30 012 43.80 30 102 43.80 30 099 13.80 30 012 13.80 30 102 13.80 30 012 43.100 30 102 43.100 30 099 13.100 30 012 13.100 30 102 13.100 30 012 43.100 30 102 43.100 30 020 43.125 30 103 43.125 30 103 43.125 30 004 13.6,3 30 101 13.6,3 30 004 13.5 30 004 13.6,3 30 101 13.6,3 30 004 13.10 30 101 13.10 30 004 13.16 30 101 13.16 30 004 13.16 30 101 13.16 30 004 13.20 30 101 13.20 30 004 13.31,5 30 101 13.31,5 30 004 13.31,5 30 101 13.31,5 30 004 13.40 30 101 13.40 30 004 13.50 30 101 13.50 30 012 13.63 30 102 13.63 30 012 43.80 30 102 43.80 30 012 43.100 30 102 43.100 30 004 13.6,3 30 101 13.6,3 30 004 13.5 30 004 13.6,3 30 101 13.6,3 30 004 13.10 30 101 13.10 30 004 13.16 30 101 13.16 30 004 13.16 30 101 13.16 30 004 13.20 30 101 13.20 30 004 13.25 30 101 13.25 30 004 13.31,5 30 101 13.31,5 30 004 13.40 30 101 13.40 30 004 13.50 30 101 13.50 Order No. Make SIBA

630

61

800 7.6 to 8.4 20 30

5 to 6 4 4

77 1.5 2.27

50 75 100 125 160 200 250 315 400 500 630 8.9 20 30

4 4 4 4 4 4 4 4 4 4 4 4 4

3.7 5.7 7.6 9.5 12.1 15.2 19 23.9 30.3 37.9 47.8 1.3 2

50 75 100 125 160 200 250 315

4 4 4 4 4 4 4 4

3.3 4.9 6.5 8.1 10.4 13 16.2 20.5

(continued on next page)

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 33

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 8.9 Rated power SN kVA 400 500 630 10 to 12 20 30 50 Relative impedance voltage uk % 4 4 4 4 4 4 Rated current I1 A 26 32.5 41 1.15 1.7 2.9 HV HRC fuse Rated normal current of fuse Ifuse A 63 63 80 80 100 100 4 6.3 10 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 16 16 16 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 40 40 50 50 50 50 50 Operating voltage Ufuse kV 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 Dimension e mm 292 442 292 442 292 442 292 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 30 012 13.63 30 102 13.63 30 012 43.80 30 102 43.80 30 012 43.100 30 102 43.100 30 004 13.4 30 101 13.6,3 30 004 13.10 30 101 13.10 30 255 13.10 30 231 13.10 30 006 13.10 30 004 13.10 30 101 13.10 30 255 13.10 30 231 13.10 30 006 13.10 30 004 13.16 30 101 13.16 30 255 13.16 30 231 13.16 30 006 13.16 30 004 13.16 30 101 13.16 30 255 13.16 30 231 13.16 30 006 13.16 30 004 13.20 30 101 13.20 30 221 13.20 30 231 13.20 30 006 13.20 30 004 13.25 30 101 13.25 30 221 13.25 30 231 13.25 30 006 13.25 30 004 13.25 30 101 13.25 30 221 13.25 30 231 13.25 30 006 13.25 30 004 13.31,5 30 101 13.31,5 30 221 13.31,5 30 231 13.31,5 30 006 13.31,5 30 004 13.31,5 30 101 13.31,5 30 221 13.31,5 30 231 13.31,5 30 006 13.31,5 30 004 13.40 30 101 13.40 30 221 13.40 30 231 13.40 30 006 13.40 30 004 13.40 30 101 13.40 30 221 13.40 30 231 13.40 30 006 13.40 30 004 13.50 30 101 13.50 30 221 13.50 30 232 13.50 30 014 13.50 Order No. Make SIBA

75

4.3

100

5.8

125

7.2

160

9.3

200

11.5

250

14.5

315

18.3

400

23.1

(continued on next page)

34 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 10 to 12 Rated power SN kVA 500 Relative impedance voltage uk % 4 Rated current I1 A 29 HV HRC fuse Rated normal current of fuse Ifuse A 50 50 50 50 50 63 63 63 63 63 63 63 80 80 80 63 63 80 80 100 100 100 125 125 4 6.3 6.3 10 10 10 10 16 16 16 16 16 16 20 20 25 31.5 25 31.5 31.5 31.5 40 40 50 50 63 63 80 3.15 4 6.3 6.3 6.3 10 10 10 16 16 10 16 16 Operating voltage Ufuse kV 6 to 12 6 to 12 10 to 17.5 10 to 17.5 10 to 24 6 to 12 10 to 24 6 to 12 6 to 12 10 to 17.5 6 to 12 10 to 24 6 to 12 6 to 12 10 to 24 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 6 to 12 10 to 24 6 to 12 6 to 12 10 to 24 10 to 24 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 24 10 to 24 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 Dimension e mm 292 442 292 442 442 292 442 292 442 442 292 442 292 442 442 292 442 292 442 292 442 442 292 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 30 004 13.50 30 101 13.50 30 221 13.50 30 232 13.50 30 014 13.50 30 012 43.63 30 014 43.63 30 012 13.63 30 102 13.63 30 232 13.63 30 012 43.63 30 014 43.63 30 012 43.80 30 102 43.80 30 014 43.80 30 012 13.63 30 102 13.63 30 012 43.80 30 102 43.80 30 012 43.100 30 102 43.100 30 022 43.100 30 020 43.125 30 103 43.125 30 006 13.4 30 006 13.6,3 30 231 13.6,3 30 231 13.10 30 006 13.10 30 231 13.10 30 006 13.10 30 231 13.16 30 006 13.16 30 231 13.16 30 006 13.16 30 231 13.16 30 006 13.16 30 231 13.20 30 006 13.20 30 231 13.25 30 231 13.31,5 30 006 13.25 30 006 13.31,5 30 231 13.31,5 30 006 13.31,5 30 231 13.40 30 006 13.40 30 232 13.50 30 014 13.50 30 232 13.63 30 014 13.63 30 014 43.80 30 006 13.3,15 30 006 13.4 30 231 13.6,3 30 006 13.6,3 30 231 13.6,3 30 231 13.10 30 006 13.10 30 231 13.10 30 231 13.16 30 006 13.16 30 231 13.10 30 231 13.16 30 006 13.16 Order No. Make SIBA

630

36.4

800

5 to 6

46.2

1000

5 to 6

58

1250 12.4 to 13.4 20 30 50 75 100 125 160 200 250

5 to 6 4 4 4 4 4 4 4 4 4

72 0.94 1.4 2.4 3.5 4.7 5.9 7.5 9.4 11.7

315 400 500 630 800 20 30 50 75

4 4 4 4 5 to 6 4 4 4 4

14.7 18.7 23.3 29.4 37.3 0.8 1.25 2.1 3.2

13.8

100

4.2

125
(continued on next page)

5.3

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 35

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 13.8 Rated power SN kVA 160 200 Relative impedance voltage uk % 4 4 Rated current I1 A 6.7 8.4 HV HRC fuse Rated normal current of fuse Ifuse A 16 16 20 20 20 25 25 25 31.5 31.5 31.5 31.5 40 40 50 50 63 63 63 80 100 3.15 3.15 6.3 6.3 6.3 6.3 10 16 16 10 16 16 16 16 16 16 20 20 20 20 25 25 20 20 25 25 31.5 31.5 40 40 50 50 63 80 100 3.15 3.15 6.3 6.3 6.3 10 16 16 16 20 20 Operating voltage Ufuse kV 10 to 17.5 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 17.5 10 to 24 10 to 17.5 10 to 17.5 10 to 24 Dimension e mm 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 30 231 13.16 30 231 13.16 30 231 13.20 30 006 13.20 30 231 13.20 30 231 13.25 30 006 13.25 30 231 13.25 30 231 13.31,5 30 006 13.31,5 30 231 13.31,5 30 006 13.31,5 30 231 13.40 30 006 13.40 30 232 13.50 30 014 13.50 30 232 13.63 30 014 13.63 30 014 43.63 30 014 43.80 30 022 43.100 30 006 13.3,15 30 006 13.3,15 30 231 13.6,3 30 006 13.6,3 30 231 13.6,3 30 006 13.6,3 30 231 13.10 30 231 13.16 30 006 13.16 30 231 13.10 30 231 13.16 30 006 13.16 30 231 13.16 30 006 13.16 30 231 13.16 30 006 13.16 30 231 13.20 30 006 13.20 30 231 13.20 30 006 13.20 30 231 13.25 30 006 13.25 30 231 13.20 30 006 13.20 30 231 13.25 30 006 13.25 30 231 13.31,5 30 006 13.31,5 30 231 13.40 30 006 13.40 30 232 13.50 30 014 13.50 30 014 43.63 30 014 43.80 30 022 43.100 30 006 13.3,15 30 006 13.3,15 30 231 13.6,3 30 006 13.6,3 30 231 13.6,3 30 231 13.10 30 231 13.16 30 006 13.16 30 231 13.16 30 231 13.20 30 006 13.20 Order No. Make SIBA

250

10.5

315

13.2

400 500 630 800

4 4 4 5 to 6

16.8 21 26.4 33.5

14.4

1000 1250 20 30 50 75 100

5 to 6 5 to 6 4 4 4 4 4

41.9 52.3 0.8 1.2 2 3 4

125

160 200

4 4

6.5 8

250

10

315

12.6

400 500 630 800 1000 1250 20 30 50 75 100 125 160 200

4 4 4 5 to 6 5 to 6 5 to 6 4 4 4 4 4 4 4 4

16.1 20.1 25.3 32.1 40.1 50.2 0.77 1.15 1.9 2.9 3.9 4.8 6.2 7.7

15 to 17.5

(continued on next page)

36 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Allocation of three-position switch-disconnector with HV HRC fuses, transformer ratings
Transformer Operating voltage U kV 15 to 17.5 Rated power SN kVA 250 315 400 500 Relative impedance voltage uk % 4 4 4 4 Rated current I1 A 9.7 12.2 15.5 19.3 HV HRC fuse Rated normal current of fuse Ifuse A 25 25 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 50 50 63 63 63 80 100 3.15 3.15 6.3 6.3 10 10 16 16 20 25 31.5 31.5 40 40 50 63 50 63 63 80 3.15 3.15 6.3 6.3 6.3 10 10 16 16 16 20 20 25 25 31.5 31.5 40 31.5 50 50 63 80 100 100 Operating voltage Ufuse kV 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 17.5 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 10 to 24 Dimension e mm 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 30 231 13.25 30 006 13.25 30 231 13.31,5 30 006 13.31,5 30 231 13.31,5 30 006 13.31,5 30 231 13.31,5 30 006 13.31,5 30 231 13.40 30 006 13.40 30 231 13.40 30 006 13.40 30 232 13.50 30 014 13.50 30 014 43.63 30 014 43.63 30 014 43.63 30 014 43.80 30 022 43.100 30 006 13.3,15 30 006 13.3,15 30 006 13.6,3 30 006 13.6,3 30 006 13.10 30 006 13.10 30 006 13.16 30 006 13.16 30 006 13.20 30 006 13.25 30 006 13.31,5 30 006 13.31,5 30 006 13.40 30 006 13.40 30 006 13.50 30 014 43.63 30 014 13.50 30 014 43.63 30 014 43.63 30 014 43.80 30 006 13.3,15 30 006 13.3,15 30 006 13.6,3 30 006 13.6,3 30 006 13.6,3 30 006 13.10 30 006 13.10 30 006 13.16 30 006 13.16 30 006 13.16 30 006 13.20 30 006 13.20 30 006 13.25 30 006 13.25 30 006 13.31,5 30 006 13.31,5 30 006 13.40 30 006 13.31,5 30 014 13.50 30 014 13.50 30 014 43.63 30 014 43.80 30 022 43.100 30 022 43.100 Order No. Make SIBA

630

24.3

800 1000 1250 20 30 50 75 100 125 160 200 250 315 400 500 630

5 to 6 5 to 6 5 to 6 4 4 4 4 4 4 4 4 4 4 4 4 4

30.9 38.5 48.2 0.64 0.96 1.6 2.4 3.2 4 5.1 6.4 8.1 10.1 12.9 16.1 20.2

18 to 19

800 1000 1250 20 30 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000

4 to 5 5 to 6 5 to 6 4 4 4 4 4 4 4 4 4 4 4 4 4 5 to 6 5 to 6 5 to 6 5 to 6 5 to 6

25.7 32.1 40.1 0.57 0.86 1.5 2.2 2.9 3.6 4.7 5.8 7.3 9.2 11.6 14.5 18.2 23.1 29 36 46.5 57.8

20 to 23

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 37

Components
Vacuum contactor, motor protection
Features According to IEC 60470 and VDE 0670-501 (for standards, see page 58) Application in hermetically welded switchgear vessel in conformity with the system Climate-independent vacuum interrupter poles in the SF6lled switchgear vessel Maintenance-free for indoor installation according to IEC 62271-1 and VDE 0671-1 Individual secondary equipment A metal bellows is used for gasketless separation of the SF6 insulation and the operating mechanism (already used with success for over 2 million vacuum interrupters) Magnet coil for operation located outside the switchgear vessel 100,000 or 500,000 operating cycles at rated normal current. Short-circuit and overload protection in connection with motors In circuits subjected to shortcircuit currents, HV HRC fuse-links protect switching devices without short-circuit breaking capacity (e.g. vacuum contactors). The instant when the motor starts represents the maximum stress for the HV HRC fuse-links (starting currents, starting time and starting frequency). Motor starting must neither operate nor pre-damage the fuses. Vacuum contactor (open on the side of the operating mechanism)
1

R-HA35-110 eps

2 3 4

10

11

12

13

1 2 3 4 5 6 7 8 9 10

Section through the vacuum contactor

11 12 13

Metal bellows Pole support Vacuum interrupter Operating mechanism box with magnet coil Base plate (welded into the switchgear vessel) Fixed terminal Pole support Vacuum interrupter Moving terminal Switchgear vessel, SF6-insulated, with vacuum interrupter Metal bellows Operating mechanism box (see illustration above) Operating kinematics

Motor protection table (see also note on page 31)


HA35-2525 eps

M 3~

Number of starts per hour 3.3 to 7.2 kV >7.2 to 12 kV >12 to 23 kV

Maximum permissible motor starting current in A at rated normal current of HV HRC fuse 40 A Yes Yes Yes 95 85 75 70 63 90 80 70 65 60 85 75 70 60 55 50 A Yes Yes Yes 115 105 95 85 75 105 95 85 75 70 100 90 80 75 65 63 A Yes Yes Yes 135 120 110 95 85 120 110 100 90 80 115 105 95 85 75 80 A Yes Yes Yes 160 145 130 115 105 145 130 120 105 95 140 125 115 100 90 100 A Yes Yes Yes 210 190 170 150 140 190 170 155 140 125 185 165 150 135 120 125 A Yes Yes No 415 370 340 300 270 335 300 270 240 220 300 265 245 210 190 160 A Yes Yes No 560 500 455 405 370 445 400 360 325 290 390 350 320 285 260 200 A Yes Yes No 765 705 640 575 520 625 560 510 455 410 555 500 450 405 365 224 A Yes No No 860 840 760 680 615 730 655 595 535 485 645 575 525 470 425 250 A Yes No No 960 960 960 925 840 960 890 805 720 655 865 780 705 630 570

HV motors with starting times up to 5 s

2 4 8 16 32

HV motors with starting times up to 15 s

2 4 8 16 32

HV motors with starting times up to 30 s

2 4 8 16 32

38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

HA35-2524b eps

Components
Busbars
Features 1-pole, plug-in and bolted design Consisting of round-bar copper, insulated by means of silicone rubber Busbar joints with cross and end adapters, insulated by means of silicone rubber Field control by means of electrically conductive layers on the silicone-rubber insulation (both inside and outside) Touchable as the external layers are earthed with the switchgear vessel Insensitive to pollution and condensation Safe-to-touch due to metal cover Switchgear extension or panel replacement is possible without SF6 gas work. Possible components Current transformers Voltage transformers Surge arresters Cables with straight plug or T-plug Fully-insulated bars (e.g. make Duresca). Busbars (example)
R-HA35-051 eps

Busbars 1250 A, plug-in type, fully insulated (as front view of three panels, without low-voltage compartments)

1 2 3 4 5 7
HA35-2595b eps

8 9

11 10

Section of 1250 A busbar (basic design) Panel width 600 mm

1 2 3 4 5 Legend 1 Cap 2 Busbar insulation made of silicone rubber 3 Clamps 4 Busbar (round-bar copper) 5 End adapter or coupling end adapter 6 Connection bolt 7 Switchgear vessel 8 Metal cover of busbars 9 Cross adapter or coupling cross adapter 10 Bushing 11 Earthing connection 6 2 3 4 5
HA35-2517b eps

8 9

10 11

Section of 1600 A, 2000 A or 2500 A busbar (basic design) Panel width 600 mm Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 39

Components
Current transformers
Features According to IEC 60044-1 and VDE 0414-1 Designed as ring-core current transformers, 1-pole Free of dielectrically stressed cast-resin parts (due to design) Insulation class E Inductive type Certiable Climate-independent Secondary connection by means of a terminal strip in the low-voltage compartment of the panel. Installation Arranged outside the primary enclosure (switchgear vessel). Mounting locations At the busbar (1) At the panel connection (2) Around the cable (3). Current transformer types Busbar current transformer (1): Inside of transformer 56 mm / 1250 A and 55 355 mm / > 1250 A Usable height max. 160 mm at 1250 A max. 130 mm at > 1250 A Feeder current transformer (2): Inside of transformer 106 mm / 1250 A and 100 200 mm / > 1250 A Max. usable height 205 mm Cable-type current transformer (3) for shielded cables: Inside of transformer 55 mm Max. usable height 170 mm Zero-sequence current transformer (4) underneath the panels (included in the scope of supply); on-site installation. Current transformers
R-HA35-052a eps

1 Busbar current transformer 2 Feeder current transformer at the panel connection 3 Cable-type current transformer 4 Zero-sequence current transformer

Side views:

1 Busbar current transformers Example 1250 A Front views:

Panel with busbar 1250 A

3 4 630 A, 1000 A and 1250 A

3 4 2000 A and 2500 A

3 4 Panel with busbar 2500 A

Current transformer installation (basic scheme)

Electrical data
Designation Operating voltage Rated short-duration power-frequency withstand voltage (winding test) Rated frequency Rated continuous thermal current Rated thermal short-time current, max. 3 s Rated current dynamic primary secondary Type 4MC max. 0.8 kV 3 kV Core data according to rated primary current: Measuring core Rating Class Overcurrent factor Rating Class Overcurrent factor Designation Multiratio (secondary) Type 4MC 200 A 100 A to 2500 A 1250 A max. 3 cores 2.5 VA to 30 VA 0.2 to 1 FS 5, FS 10 2.5 VA to 30 VA 5 P or 10 P 10 to 30 max. 60 C E

50 / 60 Hz max. 1.2 rated current (primary) max. 31.5 kA unlimited 40 A to 2500 A 1 A and 5 A

Protection core

Permissible ambient air temperature Insulation class

40 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

HA35-2611b eps

HA35-2577b eps

Components
Voltage transformers
Features According to IEC 60044-2 and VDE 0414-2 1-pole, plug-in design Connection system with plug-in contact Inductive type Safe-to-touch due to metal cover Certiable Climate-independent Secondary connection by means of plugs inside the panel Cast-resin insulated Arranged outside the primary enclosure (switchgear vessel) Mounting locations: At the busbar At the panel connection. Voltage transformer types Busbar voltage transformer 4MT2: Pluggable in the cross adapters of the busbar 1250 A using additional adapters (> 1250 A on request) No separate metering panel required Suitable for 80 % of the rated short-duration power-frequency withstand voltage at rated frequency Repeat test at 80 % of the rated short-duration power-frequency withstand voltage possible with mounted voltage transformer (also valid for higher insulation ratings according to GOST and GB standards) Feeder voltage transformer 4MT3 at the panel connection: Switchable through an SF6insulated disconnecting facility in the switchgear vessel Positions: CLOSED and Transformer bushing EARTHED Operation of the disconnecting facility from outside through a metal bellows welded in the switchgear vessel Voltage testing of switchgear and cables possible with mounted and earthed voltage transformer Feeder voltage transformer 4MU2 at the panel connection of the incoming sectionalizer (side B) Connection to bushing with short, exible cable. Voltage transformer
R-HA35-120 eps

Feeder voltage transformer (metal-coated)

Front view:

Side view: CLOSED 1 5 4

OPEN and EARTHED Z 5


HA35-2527c eps HA35-2528c eps

2 3

Voltage transformer installation (basic design)

Disconnecting facility for feeder voltage transformer (detail Z)

1 Busbar voltage transformer 2 Feeder voltage transformer at the panel connection 3 Operating lever for disconnecting facility 4 Panel connection 5 Switchgear vessel wall (earthed)

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 41

Components
Voltage transformers
Electrical data Primary data For types 4MT3, 4MT2 and 4MU2 For operating voltages from 3.3 kV to 23 kV, rated voltage factor Un / 8h = 1.9; Un / continuous = 1.2
Rated voltage kV kV 3.6 7.2 10 20 32 12 28 42 42 17.5 24 38 50 kV 20 60 60 75 75 75 95 125 IEC IEC GOST IEC GOST GB IEC IEC kV 3.3 / 3 3.6 / 3; 4.8 / 3; 5.0 / 3; 6.0 / 3; 6.3 / 3; 6.6 / 3 6.0 / 3; 6.3 / 3; 6.6 / 3 7.2 / 3; 10 / 3; 11 / 3 10 / 3; 11 / 3 10 / 3; 11 / 3 13.2 / 3; 13.8 / 3; 15 / 3 17.5 / 3; 20 / 3; 23 / 3 Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Standard Operating voltage

Secondary data
For type Operating voltage V 4MT3 4MU2 100 / 3; 110 / 3; 120 / 3 Auxiliary winding V 100 / 3; 110 / 3; 120 / 3 Thermal limit current (measuring winding) A 6 Rated longtime current 8h A 4 Rating at accuracy class 0.2 VA IEC 10, 15, 20, 25, 30 10, 15, 20, 25, 30, 45, 50, 60, 75, 90 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150, 180 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150, 180 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150 10, 15, 20, 25, 30, 45, 50, 60, 75 10, 15, 20, 25, 30 10, 15, 20, 25, 30, 45, 50, 60 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150, 180 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150, 180 10, 15, 20, 25, 30, 45, 50, 60, 75, 90, 100, 120, 150 10, 15, 20, 25, 30, 45, 50, 60, 75 10, 15, 20, 25, 30 10, 15, 20, 25, 30, 45, 50, 60 0.5 VA 1 VA 3 VA

GOST 32 / 60 kV 10, 15, 20, 25, 30 10, 15, 20, 25, 30, 45, 50, 60, 75, 90

GOST 42 / 75 kV, GB 42 / 75 kV 10, 15, 20, 25 10, 15, 20, 25, 30, 45, 50, 60, 75

4MT2

100 / 3; 110 / 3; 120 / 3

100 / 3; 110 / 3; 120 / 3

IEC 5, 10, 15, 20, 25 10, 15, 20, 25, 30, 45

GOST 32 / 60 kV 5 10, 15

GOST 42 / 75 kV, GB 42 / 75 kV 5, 10 10, 15, 20, 25, 30

GOST : Russian standard GB : Chinese standard

42 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Panel connection
Features Bushings with outside cone With bolted contact (M16) as interface type C according to EN 50 180 / EN 50 181 For cable connection heights, see table on the right Max. connection depth: 584 mm or 732 mm with standard cable compartment cover, 752 mm with deep cable compartment cover With cable bracket, e.g. type C40 according to DIN EN 50 024 Option: Access to the cable compartment only if the feeder has been isolated and earthed For thermoplastic-insulated cables For shielded cable T-plugs or cable elbow plugs with bolted contact For connection cross-sections up to 630 mm2 Larger cross-sections on request Cable routing downwards, cable connection from the front Option: Cable routing upwards to the rear, cable connection from the rear (only for circuitbreaker panel 1250 A) For rated normal currents up to 2500 A Cable plugs and cable sealing ends are not included in the scope of supply. Surge arresters Pluggable on cable T-plug Surge arresters recommended if, at the same time, the cable system is directly connected to the overhead line, the protection zone of the surge arrester at the end tower of the overhead line does not cover the switchgear. Surge limiters Pluggable on cable T-plug Surge limiters recommended when motors with starting currents < 600 A are connected. Cable compartment

500 (280*)

702 (450*)

L1
105 195

L2
195

L3
577 105 1000 (780*) 400 1200 (950*)
HA35-2607b eps

HA35-2597a eps

L1
105 195

L2
195

L3
105

L1

L2

L3

115 100 185 100 185 100 115

Panel width 600 mm * Cable connection height for switchdisconnector and contactor panels with HV HRC fuses
HA35-2625 eps

Panel width 900 mm

Cable connection heights


250 250

Panels

Panel width 600 mm

Height of cable compartment mm

Distance between bushing and cable bracket mm 500 400

600 mm 900 mm

702 577

Connectable cables Cable T-plug with coupling insert


3

Switch-disconnector panel and 450 contactor panel with fuse

280

HA35-2599a eps

Connection with 1 cable per phase Connection with 2 cables per phase

Connection with 2 cables per phase Connection with 4 cables per phase

HA35-2600a eps

Connection with 3 cables per phase Connection with 6 cables per phase

Cable T-plug with coupling T-plug

HA35-2602a eps

HA35-2601a eps

HA35-2603a eps

Connection with 2 cables per phase Connection with 4 cables per phase

Connection with 3 cables per phase Connection with 6 cables per phase

Connection with 4 cables per phase Connection with 8 cables per phase Legend 1 Cable T-plug 2 Coupling T-plug 3 Screw-type coupling insert

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 43

HA35-2626 eps

Components
Number Make of cables per panel and phase Conductor crosssection 1) mm2

Installation possibilities for cable connections and surge arresters, single-core PE and XLPE-insulated
Cable T-plugs bolted 12 kV 24 kV Coupling inserts / coupling plugs bolted 12 kV 24 kV Surge arresters with coupling inserts Arresters Coupling inserts additionally According to standard GOST for Russia & GUS GB / DL for China

Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)
1 Euromold 35 to 300 1 400TB / G 1 K400TB / G 1 K400TB / G-CSxxx 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 1 440TB / G 1 K440TB / G 1 K440TB / G-CSxxx 1 SET 12 1 SET 24 1 SEHDT 13 1 SEHDT 23 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 1 RSTI-36Lxx 1 RSTI-56Lxx 1 RSTI-36Lxx-CEE01 1 RSTI-56Lxx-CEE01 1 93-EE 705-6 1 93-EE 705-6 1 93-EE 715-6 1 93-EE 715-6 2 400TB / G 2 K400TB / G 2 K400TB / G-CSxxx 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 2 440TB / G 2 K440TB / G 2 K440TB / G-CSxxx 1 SET 12 1 SET 24 2 SET 12 2 SET 24 2 SEHDT 13 2 SEHDT 23 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 2 CB 12-630 2 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 2 CB 36-630(1250) 2 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 400CP 1 K400CP 1 K400CP 400PB-5(10)-SA-xxx RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC

35 to 300

300SA-5(10)SA

400 to 630

400PB-5(10)-SA-xxx

Sdkabel

50 to 300 25 to 240 400 to 500 300 to 500

MUT 23 MUT 23 CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx

nkt cables

25 to 300 25 to 500 25 to 300 400 to 630

Tyco Electronics Raychem

25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630

3M

50 to 240 25 to 240 300 to 400

Euromold

35 to 300

35 to 300

1 300PB-630A 300SA-5(10)SA 1 K300PB-630A 1 K300PB-630A-CSxxx 1 440CP 1 K440CP 1 K440CP 1 SEHDK 13.1 1 SEHDK 23.1 1 KU 23.2 1 KU 23.2 1 KU 23 1 KU 23 1 CC 12-630 1 CC 17.5-630 1 CC 24-630 1 CP 630-C 1 CP 630-C 1 CC 36-630(1250) 1 CC 36-630(1250) 1 CP 630-M16 1 CP 630-M16 1 RSTI-CC-L56xx 1 RSTI-CC-L56xx CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx

400 to 630

Sdkabel

50 to 300 25 to 240 50 to 300 25 to 240 400 to 500 300 to 500

nkt cables

25 to 300 25 to 500 25 to 300 25 to 300 400 to 630 400 to 630

Tyco Electronics Raychem

25 to 300 25 to 300 25 to 300

1 RSTI-CC-L56xx-CEE01 RSTI-CC-L56SAxxxx 1 RSTI-CC-L56xx-CEE01 RSTI-CC-66SAxxxx 1 RSTI-CC-58xx 1 RSTI-CC-58xx RSTI-CC-58SAxxxx

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required 44 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Installation possibilities for cable connections and surge arresters, single-core PE and XLPE-insulated
Number Make of cables per panel and phase Conductor crosssection 1) mm2 Cable T-plugs bolted 12 kV 24 kV Coupling inserts / coupling plugs bolted 12 kV 24 kV Surge arresters with coupling inserts Arresters Coupling inserts additionally According to standard GOST for Russia & GUS GB / DL for China

Components

Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel with top-rear cable connection 1250 A 2)
2 Tyco Electronics Raychem 25 to 300 400 to 630 400 to 630 3M 50 to 240 25 to 240 240 150 to 240 300 to 400 3 Euromold 35 to 300 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 2 RSTI-36Lxx 2 RSTI-56Lxx 2 RSTI-36Lxx-CEE01 2 RSTI-56Lxx-CEE01 2 93-EE 705-6 2 93-EE 705-6 1 93-EE 705-6 1 93-EE 705-6 2 93-EE 715-6 2 93-EE 715-6 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 1 RSTI-CC-58xx-CEE01 RSTI-CC-58SAxxxx 1 RSTI-CC-58xx-CEE01 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 KU 23.2 1 KU 23.2 1 93-EE 718-6 1 93-EE 718-6 1 KU 23.2 1 KU 23.2 GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST

2 300PB-630A 2 K300PB-630A 2 K300PB-630A-CSxxx 2 CC 12-630 2 CC 17.5-630 2 CC 24-630 2 CC 36-630(1250) 2 CC 36-630(1250) 2 RSTI-CC-L56xx 2 RSTI-CC-L56xx

nkt cables

25 to 300 25 to 500 25 to 300 400 to 630

Tyco Electronics Raychem

25 to 300 25 to 300 25 to 300 25 to 300

2 RSTI-CC-L56xx-CEE01 2 RSTI-CC-L56xx-CEE01 2 RSTI-CC-58xx 2 RSTI-CC-58xx

2 RSTI-CC-58xx-CEE01 2 RSTI-CC-58xx-CEE01

Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
1 Euromold 35 to 300 35 to 300 400 to 630 Sdkabel 50 to 300 25 to 240 400 to 500 300 to 500 nkt cables 25 to 300 25 to 500 25 to 300 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630 3M 50 to 240 25 to 240 300 to 400 2 Euromold 35 to 300 1 400TB / G 1 K400TB / G 1 430TB-630A 1 K430TB-630A 1 440TB / G 1 K440TB / G 1 SET 12 1 SET 24 1 SEHDT 13 1 SEHDT 23 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 1 RSTI-36Lxx 1 RSTI-56Lxx 1 RSTI-36Lxx-CEE01 1 RSTI-56Lxx-CEE01 1 93-EE 705-6 1 93-EE 705-6 1 93-EE 715-6 1 93-EE 715-6 2 400TB / G 2 K400TB / G 1 400CP 1 K400CP 400PB-5(10)-SA-xxx 300SA-5(10)SA 400PB-5(10)-SA-xxx MUT 23 MUT 23 CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx 400PB-5(10)-SA-xxx RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 45

Components
Number Make of cables per panel and phase Conductor crosssection 1) mm2

Installation possibilities for cable connections and surge arresters, single-core PE and XLPE-insulated
Cable T-plugs bolted 12 kV 24 kV
1 430TB-630A 1 K430TB-630A 2 440TB / G 2 K440TB / G 1 SET 12 1 SET 24 2 SET 12 2 SET 24 2 SEHDT 13 2 SEHDT 23 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 2 CB 12-630 2 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 2 CB 36-630(1250) 2 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 2 RSTI-36Lxx 2 RSTI-56Lxx 2 RSTI-36Lxx-CEE01 2 RSTI-56Lxx-CEE01 2 93-EE 705-6 2 93-EE 705-6 1 93-EE 705-6 1 93-EE 705-6 2 93-EE 715-6 2 93-EE 715-6 3 400TB / G 3 K400TB / G 1 430TB-630A 1 K430TB-630A 3 440TB / G 3 K440TB / G 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 CB 36-630(1250) 1 CB 36-630(1250) 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 3x RSTI-36Lxx 3x RSTI-56Lxx 3x RSTI-36Lxx-CEE01 3x RSTI-56Lxx-CEE01 1 430TB-630A 1 K430TB-630A

Coupling inserts / coupling plugs bolted 12 kV 24 kV


1 300PB-630A 1 K300PB-630A 1 440CP 1 K440CP 1 SEHDK 13.1 1 SEHDK 23.1 1 KU 23.2 1 KU 23.2 1 KU 23 1 KU 23 1 CC 12-630 1 CC 17.5-630 1 CC 24-630 1 CP 630-C 1 CP 630-C 1 CC 36-630(1250) 1 CC 36-630(1250) 1 CP 630-M16 1 CP 630-M16 1 RSTI-CC-L56xx 1 RSTI-CC-L56xx 1 RSTI-CC-L56xx-CEE01 1 RSTI-CC-L56xx-CEE01 1 RSTI-CC-58xx 1 RSTI-CC-58xx

Surge arresters with coupling inserts Arresters Coupling inserts additionally

According to standard GOST for Russia & GUS GB / DL for China


IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL

Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
2 Euromold 35 to 300 400 to 630 Sdkabel 50 to 300 25 to 240 50 to 300 25 to 240 400 to 500 300 to 500 nkt cables 25 to 300 25 to 500 25 to 300 25 to 300 400 to 630 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630 3M 50 to 240 25 to 240 240 150 to 240 300 to 400 3 Euromold 35 to 300 3) 35 to 300 400 to 630 3) nkt cables 25 to 300 25 to 500 25 to 300 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630 4 Euromold 35 to 300 300SA-5(10)SA 400PB-5(10)-SA-xxx MUT 23 MUT 23 MUT 23 CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16

1 RSTI-CC-58xx-CEE01 RSTI-CC-58SAxxxx 1 RSTI-CC-58xx-CEE01 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 RSTI-66CP-M16 1 KU 23.2 1 KU 23.2 1 93-EE 718-6 1 93-EE 718-6 1 KU 23.2 1 KU 23.2 2 400CP 2 K400CP 2 300PB-630A 2 K300PB-630A 2 440CP 2 K440CP 2 CC 12-630 2 CC 17.5-630 2 CC 24-630 2 CC 36-630(1250) 2 CC 36-630(1250) 2 RSTI-CC-L56xx 2 RSTI-CC-L56xx RSTI-L56SAxxxx RSTI-66SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx 300SA-5(10)SA CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx

2 RSTI-CC-L56xx-CEE01 RSTI-CC-L56SAxxxx 2 RSTI-CC-L56xx-CEE01 RSTI-CC-66SAxxxx 2 RSTI-CC-58xx 2 RSTI-CC-58xx 2 RSTI-CC-58xx-CEE01 2 RSTI-CC-58xx-CEE01 2 RSTI-66CP-M16 2 RSTI-66CP-M16 2 RSTI-66CP-M16 2 RSTI-66CP-M16 3x 300PB-630A 3x K300PB-630A RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required 3) Only possible with deep cable compartment cover 46 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Installation possibilities for cable connections and surge arresters, single-core PE and XLPE-insulated
Number Make of cables per panel and phase Conductor crosssection 1) mm2 Cable T-plugs bolted 12 kV 24 kV
1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE1 1 RSTI-58xx-CEE1

Components
According to standard GOST for Russia & GUS GB / DL for China
IEC IEC GOST GOST

Coupling inserts / coupling plugs bolted 12 kV 24 kV


3x RSTI-CC-58xx 3x RSTI-CC-58xx 3x RSTI-CC-58xx-CEE1 3x RSTI-CC-58xx-CEE1

Surge arresters with coupling inserts Arresters Coupling inserts additionally

Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
4 Tyco Electronics Raychem 25 to 300 25 to 300

Circuit-breaker and disconnector panel 2000 A, 2500 A


2 Euromold 35 to 300 35 to 300 400 to 630 Sdkabel 50 to 300 25 to 240 400 to 500 300 to 500 nkt cables 25 to 300 25 to 500 25 to 300 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630 3M 50 to 240 25 to 240 300 to 400 4 Euromold 35 to 300 35 to 300 400 to 630 Sdkabel 50 to 300 25 to 240 50 to 300 25 to 240 400 to 500 300 to 500 nkt cables 25 to 300 25 to 500 25 to 300 25 to 300 400 to 630 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 2 400TB / G 2 K400TB / G 2 430TB-630A 2 K430TB-630A 2 440TB / G 2 K440TB / G 2 SET 12 2 SET 24 2 SEHDT 13 2 SEHDT 23 2 CB 12-630 2 CB 17.5-630 2 CB 24-630 2 CB 36-630(1250) 2 CB 36-630(1250) 2 RSTI-L56xx 2 RSTI-L56xx 2 RSTI-L56xx-CEE01 2 RSTI-L56xx-CEE01 2 RSTI-58xx 2 RSTI-58xx 2 RSTI-58xx-CEE01 2 RSTI-58xx-CEE01 2 RSTI-36Lxx 2 RSTI-56Lxx 2 RSTI-36Lxx-CEE01 2 RSTI-56Lxx-CEE01 2 93-EE 705-6 2 93-EE 705-6 2 93-EE 715-6 2 93-EE 715-6 4 400TB / G 4 K400TB / G 2 430TB-630A 2 K430TB-630A 4 440TB / G 4 K440TB / G 2 SET 12 2 SET 24 4 SET 12 4 SET 24 4 SEHDT 13 4 SEHDT 23 2 CB 12-630 2 CB 17.5-630 2 CB 24-630 4 CB 12-630 4 CB 24-630 2 CB 36-630(1250) 2 CB 36-630(1250) 4 CB 36-630(1250) 4 CB 36-630(1250) 2x RSTI-L56xx 2 RSTI-L56xx 2 RSTI-L56xx-CEE01 2 RSTI-L56xx-CEE01 2 400CP 2 K400CP 2 300PB-630A 2 K300PB-630A 2 440CP 2 K440CP 2 SEHDK 13.1 2 SEHDK 23.1 2 KU 23.2 2 KU 23.2 2 KU 23 2 KU 23 2 CC 12-630 2 CC 12-630 2 CC 24-630 2 CP 630-C 2 CP 630-C 2 CC 36-630(1250) 2 CC 36-630(1250) 2 CP 630-M16 2 CP 630-M16 2 RSTI-CC-L56xx 2 RSTI-CC-L56xx 2 RSTI-CC-L56xx-CEE01 2 RSTI-CC-L56xx-CEE01 400PB-5(10)-SA-xxx 300SA-5(10)SA 400PB-5(10)-SA-xxx MUT 23 MUT 23 CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx 400PB-5(10)-SA-xxx 300SA-5(10)SA 400PB-5(10)-SA-xxx MUT 23 MUT 23 MUT 23 CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 47

Components
Number Make of cables per panel and phase Conductor crosssection 1) mm2

Installation possibilities for cable connections and surge arresters, single-core PE and XLPE-insulated
Cable T-plugs bolted 12 kV 24 kV
2 RSTI-58xx 2 RSTI-58xx 2 RSTI-58xx-CEE01 2 RSTI-58xx-CEE01 4 RSTI-36Lxx 4 RSTI-56Lxx 4 RSTI-36Lxx-CEE01 4 RSTI-56Lxx-CEE01 4 93-EE 705-6 4 93-EE 705-6 2 93-EE 705-6 2 93-EE 705-6 4 93-EE 715-6 4 93-EE 715-6 6 400TB / G 6 K400TB / G 2 430TB-630A 2 K430TB-630A 6 440TB / G 6 K440TB / G 2 CB 12-630 2 CB 17.5-630 2 CB 24-630 2 CB 36-630(1250) 2 CB 36-630(1250) 2 RSTI-L56xx 2 RSTI-L56xx 2 RSTI-L56xx-CEE01 2 RSTI-L56xx-CEE01 2 RSTI-58xx 2 RSTI-58xx 2 RSTI-58xx-CEE01 2 RSTI-58xx-CEE01 6 RSTI-36Lxx 6 RSTI-56Lxx 6 RSTI-36Lxx-CEE01 6 RSTI-56Lxx-CEE01 2 430TB-630A 2 K430TB-630A 2 RSTI-58xx 2 RSTI-58xx 2 RSTI-58xx-CEE1 2 RSTI-58xx-CEE1

Coupling inserts / coupling plugs bolted 12 kV 24 kV


2 RSTI-CC-58xx 2 RSTI-CC-58xx

Surge arresters with coupling inserts Arresters Coupling inserts additionally

According to standard GOST for Russia & GUS GB / DL for China


IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST

Circuit-breaker and disconnector panel 2000 A, 2500 A


4 Tyco Electronics Raychem 25 to 300 25 to 300 400 to 630 400 to 630 3M 50 to 240 25 to 240 240 150 to 240 300 to 400 6 Euromold 35 to 300 3) 35 to 300 400 to 630 3) nkt cables 25 to 300 25 to 500 25 to 300 400 to 630 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 400 to 630 400 to 630 8 Euromold Tyco Electronics Raychem 35 to 300 25 to 300 25 to 300 RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16 RSTI-66CP-M16

2 RSTI-CC-58xx-CEE01 RSTI-CC-58SAxxxx 2 RSTI-CC-58xx-CEE01 2 RSTI-66CP-M16 2 RSTI-66CP-M16 2 RSTI-66CP-M16 2 RSTI-66CP-M16 2 KU 23.2 2 KU 23.2 2 93-EE 718-6 2 93-EE 718-6 2 KU 23.2 2 KU 23.2 4 400CP 4 K400CP 4 300PB-630A 4 K300PB-630A 4 440CP 4 K440CP 4 CC 12-630 4 CC 12-630 4 CC 24-630 4 CC 36-630(1250) 4 CC 36-630(1250) 4 RSTI-CC-L56xx 4 RSTI-CC-L56xx RSTI-L56SAxxxx RSTI-66SAxxxx RSTI-L56SAxxxx RSTI-66SAxxxx 300SA-5(10)SA CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx

4 RSTI-CC-L56xx-CEE01 RSTI-CC-L56SAxxxx 4 RSTI-CC-L56xx-CEE01 RSTI-CC-66SAxxxx 4 RSTI-CC-58xx 4 RSTI-CC-58xx 4 RSTI-CC-58xx-CEE01 4 RSTI-CC-58xx-CEE01 4 RSTI-66CP-M16 4 RSTI-66CP-M16 4 RSTI-66CP-M16 4 RSTI-66CP-M16 6 300PB-630A 6 K300PB-630A 6 RSTI-CC-58xx 6 RSTI-CC-58xx 6 RSTI-CC-58xx-CEE1 6 RSTI-CC-58xx-CEE1 RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 3) Only possible with deep cable compartment cover 48 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Installation possibilities for cable connections and surge arresters, three-core PE and XLPE-insulated
Number Make of cables per panel and phase Conductor crosssection 1) mm2 Cable T-plugs bolted 12 kV 24 kV Coupling inserts / coupling plugs bolted 12 kV 24 kV Distribution kit for three-core cables Surge arresters According to standard GOST for Russia & GUS GB / DL for China

Components

Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
1 Euromold 35 to 300 1 400TB / G 1 K400TB / G 1 K400TB / G-CSxxx 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 1 SET 12 1 SET 24 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 1 93-EE 705-6 1 93-EE 705-6 1 93-EE 715-6 1 93-EE 715-6 2 400TB / G 2 K400TB / G 2 K400TB / G-CSxxx 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 1 SET 12 1 SET 24 2 SET 12 2 SET 24 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 2 CB 12-630 2 CB 24-630 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 2 93-EE 705-6 2 93-EE 705-6 1 93-EE 705-6 1 93-EE 705-6 2 93-EE 715-6 2 93-EE 715-6 1 430TB-630A 1 K430TB-630A 1 K430TB-630A-CSxxx 1 CB 12-630 1 CB 17.5-630 1 CB 24-630 1 400CP 1 K400CP 1 K400CP 1 300PB-630A 1 K300PB-630A 1 K300PB-630A-CSxxx 1 SEHDK 13.1 1 SEHDK 23.1 1 KU 23.2 1 KU 23.2 1 CC 12-630 1 CC 17.5-630 1 CC 24-630 1 CP 630-C 1 CP 630-C 1 RSTI-CC-L56xx 1 RSTI-CC-L56xx 1 RSTI-CC-L56xx-CEE01 1 RSTI-CC-L56xx-CEE01 1 RSTI-CC-58xx 1 RSTI-CC-58xx 1 RSTI-CC-58xx-CEE01 1 RSTI-CC-58xx-CEE01 1 KU 23.2 1 KU 23.2 1 93-EE 718-6 1 93-EE 718-6 1 KU 23.2 1 KU 23.2 2 300PB-630A 2 K300PB-630A 2 K300PB-630A-CSxxx 2 CC 12-630 2 CC 17.5-630 2 CC 24-630 1 distribution kit 1 distribution kit 1 distribution kit 1 distribution kit 1 distribution kit 1 distribution kit 1 distribution kit SAT 1 distribution kit SAT 1 distribution kit ATS 1 distribution kit ATS 1 distribution kit ATS 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit RSTI-TRF0x 1 distribution kit 1 distribution kit 1 distribution kit 1 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit SAT 2 distribution kit SAT 2 distribution kit SAT 2 distribution kit SAT 2 distribution kit ATS 2 distribution kit ATS 2 distribution kit ATS 2 distribution kit ATS 2 distribution kit ATS 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit RSTI-TRF0x 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 2 distribution kit 3x distribution kit 3x distribution kit 3x distribution kit 3x distribution kit ATS 3x distribution kit ATS 3x distribution kit ATS 400PB-5(10)-SA-xxx 300SA-5(10)SA MUT 23 CSA 12-x CSA 17.5-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx 300SA-5(10)SA CSA 12-x CSA 17.5-x CSA 24-x CSA 12-x CSA 24-x RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-L56SAxxxx RSTI-CC-66SAxxxx RSTI-CC-58SAxxxx RSTI-CC-58SAxxxx IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL IEC IEC, GOST, GB / DL IEC IEC GOST GOST IEC IEC GOST GOST IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC GOST, GB / DL IEC GOST, GB / DL IEC, GOST, GB / DL

35 to 300

Sdkabel nkt cables

50 to 300 25 to 240 25 to 300 25 to 500 25 to 300 25 to 300 25 to 300 25 to 300 25 to 300

Tyco Electronics Raychem

3M

50 to 240 25 to 240 300 to 400

Euromold

35 to 300

35 to 300

Sdkabel

50 to 300 25 to 240 50 to 300 25 to 240

nkt cables

25 to 300 25 to 500 25 to 300 25 to 300

Tyco Electronics Raychem

25 to 300 25 to 300 25 to 300 25 to 300

3M

50 to 240 25 to 240 240 150 to 240 300 to 400

Euromold

35 to 300

nkt cables

25 to 300 25 to 500 25 to 300

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 49

Components
Number Make of cables per panel and phase Conductor crosssection 1) mm2

Installation possibilities for cable connections and surge arresters, three-core PE and XLPEinsulated, paper-insulated non-draining cables and paper-insulated mass-impregnated cables
Cable T-plugs bolted 12 kV 24 kV Coupling inserts / coupling plugs bolted 12 kV 24 kV Distribution kit for three-core cables Surge arresters According to standard GOST for Russia & GUS GB / DL for China

Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
3 Tyco Electronics Raychem 25 to 300 25 to 300 25 to 300 25 to 300 1 RSTI-L56xx 1 RSTI-L56xx 1 RSTI-L56xx-CEE01 1 RSTI-L56xx-CEE01 1 RSTI-58xx 1 RSTI-58xx 1 RSTI-58xx-CEE01 1 RSTI-58xx-CEE01 2 RSTI-CC-L56xx 2 RSTI-CC-L56xx 3x distribution kit RSTI-TRF0x 3x distribution kit RSTI-TRF0x IEC IEC GOST GOST IEC IEC GOST GOST

2 RSTI-CC-L56xx-CEE01 3x distribution kit RSTI-TRF0x 2 RSTI-CC-L56xx-CEE01 3x distribution kit RSTI-TRF0x 2 RSTI-CC-58xx 2 RSTI-CC-58xx 2 RSTI-CC-58xx-CEE01 2 RSTI-CC-58xx-CEE01 3x distribution kit RSTI-TRF0x 3x distribution kit RSTI-TRF0x 3x distribution kit RSTI-TRF0x 3x distribution kit RSTI-TRF0x

Paper-insulated non-draining cables


Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
1 Euromold 35 to 300 35 to 300 nkt cables 25 to 120 1 400TB / G 1 430TB-630A 1 SEV10-120CUxxxx-CB24 1 SEV10-240CUxxxx-CB24 2 400TB / G 1 430TB-630A 1 SEV10-120CUxxxx-CB24 1 SEV10-240CUxxxx-CB24 3x 400TB / G 1 430TB-630A 1 400CP 1 300PB-630A 1 distribution kit MIND 1 distribution kit MIND 2 distribution kit MIND 2 distribution kit MIND CSA 12-x IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL CSA 12-x IEC, GOST, GB / DL 400PB-5(10)-SA-xxx 300SA-5(10)SA CSA 12-x IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL

150 to 240

Euromold

35 to 300 35 to 300

nkt cables

25 to 120

1 SEV10-120CU-xxxx- CC24 1 SEV10-240CU-xxxx- CC24 2 400CP 2 300PB-630A 3x distribution kit MIND 3x distribution kit MIND

150 to 240

CSA 12-x

IEC, GOST, GB / DL

Euromold

35 to 300 3) 35 to 300

IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL

Paper-insulated mass-impregnated cables


Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Contactor panel Circuit-breaker panel 1250 A 2) Disconnector panel 1250 A 2) DBB circuit-breaker panel 1000 A DBB incoming sectionalizer 2)
1 nkt cables 25 to 120 1 SEV10-120CUxxxx-CB24 1 SEV10-240CUxxxx-CB24 1 SEV10-120CUxxxx-CB24 1 SEV10-240CUxxxx-CB24 1 SEV10-120CU-xxxx- CC24 1 SEV10-240CU-xxxx- CC24 CSA 12-x IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL IEC, GOST, GB / DL CSA 12-x IEC, GOST, GB / DL IEC, GOST, GB / DL CSA 12-x IEC, GOST, GB / DL IEC, GOST, GB / DL

150 to 240

nkt cables

25 to 120

150 to 240

CSA 12-x

1) Observe the actual short-circuit and current carrying capacity of the cables and sealing ends 2) At a normal current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required 3) Only possible with deep cable compartment cover 50 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Panel connection (commercially available cable sealing ends)
Cable type Cable sealing end Make Type Cross-section mm2
35 to 300 35 to 300 400 to 630 25 to 300 25 to 500 400 to 630 50 to 300 400 to 500 25 to 300 25 to 300 400 to 630 50 to 240 300 to 400 35 to 300 35 to 300 25 to 300 25 to 500 50 to 300 400 to 500 EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer Silicone with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) EPDM with semi-conductive layer, in combination with distribution kit EPDM with semi-conductive layer, in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer, in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit EPDM with semi-conductive layer EPDM with semi-conductive layer EPDM with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer, with capacitive measuring point Silicone with semi-conductive layer (optionally with metal housing) Silicone with semi-conductive layer (optionally with metal housing) EPDM with semi-conductive layer, in combination with distribution kit EPDM with semi-conductive layer, in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x Silicone with semi-conductive layer, with capacitive measuring point, in combination with distribution kit RSTI-TRF0x Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit Silicone with semi-conductive layer (optionally with metal housing), in combination with distribution kit

Comment

Thermoplastic-insulated cables 12 kV according to IEC 60502-2 and VDE 0276-620


Single-core cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) or NA2YSY (Al) and NA2XSY (Al) Euromold 400TB / G 430TB-630A 440TB / G CB 12-630 CB 17.5-630 CB 36-630(1250) SET 12 SEHDT 13 RSTI-L56xx RSTI-58xx RSTI-36Lxx 93-EE 705-6 93-EE 715-6 400TB / G 430TB-630A CB 12-630 CB 17.5-630 SET 12 SEHDT 13

nkt cables

Sdkabel Tyco Electronics Raychem 3M Three-core cable PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) or NA2YSY (Al) and NA2XSY (Al) Euromold nkt cables

Sdkabel

Tyco Electronics Raychem

RSTI-L56xx RSTI-58xx

25 to 300 25 to 300 50 to 240 300 to 400

3M

93-EE 705-6 93-EE 715-6

Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC 60502-2 and VDE 0276-620


Single-core cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) or NA2YSY (Al) and NA2XSY (Al) Euromold K400TB / G K430TB-630A K440TB / G CB 24-630 CB 36-630(1250) SET 24 SEHDT 23 RSTI-L56xx RSTI-58xx RSTI-56Lxx 93-EE 705-6 93-EE 715-6 K400TB / G K430TB-630A CB 24-630 SET 24 SEHDT 23 35 to 300 35 to 300 400 to 630 25 to 300 400 to 630 50 to 300 400 to 500 25 to 300 25 to 300 400 to 630 25 to 240 300 to 400 35 to 300 35 to 300 25 to 300 50 to 300 400 to 500

nkt cables Sdkabel Tyco Electronics Raychem 3M

Three-core cable, PE and XLPE-insulated N2YSY (Cu) and N2XSY (Cu) or NA2YSY (Al) and NA2XSY (Al)

Euromold nkt cables Sdkabel

Tyco Electronics Raychem

RSTI-L56xx RSTI-58xx

25 to 300 25 to 300 25 to 240 300 to 400

3M

93-EE 705-6 93-EE 715-6

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 51

Components
Panel connection (commercially available cable sealing ends)
Cable type Cable sealing end Make Type Cross-section mm2
35 to 300 35 to 300 25 to 240 EPDM with semi-conductive layer, in combination with distribution kit MIND EPDM with semi-conductive layer, in combination with distribution kit MIND Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SEV 10

Comment

Paper-insulated belted cables (non-draining cables) 12 kV according to IEC 60055 and VDE 0255
Three-core cable paper-insulated NKBA (Cu), NKBY (Cu), NKRA (Cu) and NKFA (Cu) or NAKBA (Al), NAKBY (Al), NAKRA (Al) and NAKFA (Al) Three-core cable paper-insulated ASB and ASBL Euromold 400TB / G 430TB-630A nkt cables CB 24-630

Paper-insulated belted cables (non-draining cables) 12 kV according to GOST 18410-73


Euromold 400TB / G 430TB-630A nkt cables CB 24-630 35 to 300 35 to 300 25 to 240 EPDM with semi-conductive layer, in combination with distribution kit MIND EPDM with semi-conductive layer, in combination with distribution kit MIND Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SEV 10 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SEV 10

Paper-insulated belted cables (mass-impregnated cables) 12 kV according to IEC 60055 and VDE 0255
Three-core cable paper-insulated NKBA (Cu), NKBY (Cu), NKRA (Cu) and NKFA (Cu) or NAKBA (Al), NAKBY (Al), NAKRA (Al) and NAKFA (Al) Three-core cable paper-insulated ASB and ASBL nkt cables CB 24-630 25 to 240

Paper-insulated belted cables (mass-impregnated cables) 12 kV according to GOST 18410-73


nkt cables CB 24-630 25 to 240 Silicone with semi-conductive layer (optionally with metal housing), in combination with transition sealing end type SEV 10

52 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Indicating and measuring equipment
Voltage detecting systems according to IEC 61243-5 or VDE 0682-415 To verify safe isolation from supply LRM detecting systems with plug-in indicator with integrated indicator, type VOIS+, VOIS R+, WEGA, ZERO with integrated indicator, with integrated repeat test of the interface, with integrated function test, type CAPDIS-S1+, WEGA 1.2, and additionally with integrated signaling relays type CAPDIS-S2+, WEGA 2.2. Plug-in voltage indicator Verication of safe isolation from supply phase by phase Indicator suitable for continuous operation Measuring system and voltage indicator can be tested Voltage indicator ashes if high voltage is present. VOIS+, VOIS R+ Integrated display, without auxiliary power With indication A1 to A3 (see legend) Maintenance-free, repeat test required With integrated 3-phase LRM test socket for phase comparison With integrated signaling relays (only VOIS R+). CAPDIS-Sx+ Common features Maintenance-free Integrated display, without auxiliary power Integrated repeat test of the interfaces (self-monitoring) With integrated function test (without auxiliary power) by pressing the DisplayTest pushbutton With integrated 3-phase LRM test socket for phase comparison. CAPDIS-S1+ Without auxiliary power With indication A1 to A5 (see legend) Without ready-for-service monitoring Without signaling relays (thus without auxiliary contacts). CAPDIS-S2+ With indication A0 to A6 (see legend) Only by pressing the Display-Test pushbutton: ERROR indication (A6), e.g. in case of missing auxiliary voltage With ready-for-service monitoring (external auxiliary power required) With integrated signaling relay for signals (auxiliary power required) With signal-lead test. Indicators and detecting systems
R-HA40-103 eps

Symbols shown VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+


L1 L2 L3 L1 L2 L3 L1 L2 L3

Plug-in voltage indicator per phase at the panel front

A0 A1 A2 A3

R-HA40-104 eps

A4
HA35-2579a eps

A5 A6
ERROR

Integrated voltage indicator VOIS+, VOIS R+


R-HA35-154 eps R-HA35-155 eps

A0 CAPDIS-S2+: Operating voltage not present A1 Operating voltage present A2 Operating voltage not present For CAPDIS-S2+: Auxiliary power not present A3 Failure in phase L1, operating voltage at L2 and L3 (for CAPDIS-Sx+ also earth-fault indication) A4 Voltage (not operating voltage) present A5 Indication Display-Test passed A6 Indication ERROR, e.g.: in case of missing auxiliary voltage

Integrated voltage detecting system CAPDIS-S1+, -S2+

HA35-2537a eps

C1 C2 U2

L1 L2 L3

U LE

LRM system CAPDIS / VOIS plugged in installed Voltage indication via capacitive voltage divider (principle) C1 Capacity integrated into bushing C2 Capacity of the connection leads and the voltage indicator to earth ULE = UN / 3 during rated operation in the three-phase system U2 = UA = Voltage at the capacitive interface of the switchgear or at the voltage indicator

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 53

Components
Indicating and measuring equipment
WEGA ZERO Voltage detecting system according to IEC 61958 or VDE 0670-502 With indication A1 to A3 (see legend) Maintenance-free, repeat test required With integrated 3-phase test socket for phase comparison. WEGA 1.2 Voltage detecting system according to IEC 61243-5 or VDE 0682-415 With indication A1 to A5 (see legend) Maintenance-free Integrated repeat test of the interface (self-monitoring) With integrated function test (without auxiliary power) by pressing the Display-Test pushbutton With integrated 3-phase LRM test socket for phase comparison Without integrated signaling relay Without auxiliary power. WEGA 2.2 Voltage detecting system according to IEC 61243-5 or VDE 0682-415 With indication A0 to A6 (see legend) Maintenance-free Integrated repeat test of the interface (self-monitoring) With integrated function test (without auxiliary power) by pressing the Display-Test pushbutton With integrated 3-phase LRM test socket for phase comparison With integrated signaling relay Auxiliary power required With signal-lead test.

Symbols shown WEGA ZERO WEGA 1.2 WEGA 2.2

R-HA35-151.eps

A0 A1 A2 A3 A4 A5 A6
R-HA35-144.eps

Integrated voltage indicator WEGA ZERO

R-HA35-152.eps

LC display gray: not illuminated LC display white: illuminated

Integrated voltage detecting system WEGA 1.2

Integrated voltage detecting system WEGA 2.2

HA35-2537a eps

C1 C2 U2

L1 L2 L3

A0 For WEGA 2.2: Operating voltage not present, auxiliary power present, LCD illuminated A1 Operating voltage present For WEGA 2.2: Auxiliary power present, LCD illuminated A2 Operating voltage not present For WEGA 2.2: Auxiliary power not present, LCD not illuminated A3 Failure in phase L1, operating voltage at L2 and L3 For WEGA 2.2: Auxiliary power present, LCD illuminated A4 Voltage present, current monitoring of coupling section below limit value For WEGA 2.2: Auxiliary power present, LCD illuminated A5 Indication Display-Test passed For WEGA 2.2: Auxiliary power present, LCD illuminated A6 For WEGA 2.2: LCD for missing auxiliary voltage is not illuminated

U LE

R-HA35-153.eps

LRM system WEGA plugged in installed Voltage indication via capacitive voltage divider (principle) C1 Capacity integrated into bushing C2 Capacity of the connection leads and the voltage indicator to earth ULE = UN / 3 during rated operation in the three-phase system U2 = UA = Voltage at the capacitive interface of the switchgear or at the voltage indicator

54 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Indicating and measuring equipment
Verication of correct terminal-phase connections Verication of correct terminalphase connections possible by means of a phase comparison test unit (can be ordered separately) Safe-to-touch handling of the phase comparison test unit by inserting it into the capacitive taps (socket pairs) of the switchgear. Phase comparison test units according to IEC 61243-5 or VDE 0682-415
R-HA40-059 eps R-HA40-089 eps

Phase comparison test unit make Psterer, type EPV Phase comparison test unit make Horstmann, type ORION 3.0 as combined test unit for: Phase comparison Interface testing at the switchgear Voltage detection for LRM systems Integrated self-test Indication via LED and acoustic alarm

Phase comparison test unit make Kries, type CAP-Phase as combined test unit (HR and LRM) for: Voltage detection Repeat test Phase comparison Phase sequence test Self-test The unit does not require a battery

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 55

R-HA35-127.eps

Components
Indicating and measuring equipment
Ready-for-service indicator Gas monitoring Features Self-monitoring; easy to read Independent of temperature and pressure variations Independent of the site altitude Only responds to changes in gas density Option: Alarm switch 1NO + 1NC for remote electrical indication. Mode of operation For the ready-for-service indicator, a gas-tight measurement box is installed inside the switchgear vessel. A coupling magnet, which is tted to the bottom end of the measurement box, transmits its position to an outside armature through the non-magnetizable switchgear vessel. This armature moves the ready-for-service indicator of the switchgear. While changes in the gas density during the loss of gas, which are decisive for the dielectric strength, are displayed, temperature-dependent changes in the gas pressure are not. The gas in the measurement box has the same temperature as that in the switchgear. The temperature effect is compensated via the same pressure change in both gas volumes. Low-voltage compartment For accommodation of protection, control, measuring and metering equipment Partitioned safe-to-touch from the high-voltage part of the panel Low-voltage compartment can be removed, bus wires and control cables are plugged in Option: Higher low-voltage compartment (1161 mm instead of 761 mm) possible.
R-HA35-112b eps

Low-voltage compartment
R-HA35-105 eps

Control board (detail) with red / green ready-for-service indicator

Low-voltage compartment with multifunction protection relay SIPROTEC 4 7SJ61 (example) For description of the SIPROTEC 4 multifunction protection relays, see page 57

HA35-2538a eps

2 3 4

5 ReadyStainless-steel vessel lled with SF6 gas, relative pressure forservice 50 kPa at 20 C indicator Principle of operation of gas monitoring with readyfor-service indicator Ready-for-service indicator Measurement box Magnetic coupling Red indication: not ready for service 5 Green indication: Ready for service 1 2 3 4

56 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

Components
Protection, control, measuring and monitoring equipment
The low-voltage compartment can accommodate all customary protection, control, measuring and monitoring equipment available on the market (e.g.): Multifunction protection relay SIPROTEC 4 7SJ600 / 7SJ602 User-friendly operating program DIGSI 4 for conguration and analysis Communications and bus capability Functions: Protection, control, signaling, communication and measuring LC text display (2 lines) and keyboard for local operation, conguration and indication Four freely programmable LEDs for displaying any desired data Operation and fault indication memory Fault recorder Circuit-breaker control. Multifunction protection relay SIPROTEC 4 7SJ61 / 7SJ62 For stand-alone or master operation Communications and bus capability Functions: Protection, control, signaling, communication and measuring LC text display (4 lines) for process and equipment data, as text, e.g. for Measuring and metering values Information on status of switchgear and switching device Protection data General indications Alarms Four freely programmable function keys for frequently performed functions Seven freely programmable LEDs for displaying any desired data Keys for navigation in menus and for entering values Fault recorder. Multifunction protection relay SIPROTEC 4 7SJ63 For stand-alone or master operation Communications and bus capability Functions: Protection, control, signaling, communication and measuring LC display for process and equipment data in the form of a feeder control diagram and as text, e.g. for Measuring and metering values Information on status of switchgear and switching device Protection data General indications Alarms Four freely programmable function keys for frequently performed functions Fourteen freely programmable LEDs for displaying any desired data Two key-operated switches to switch between local and remote control and interlocked and non-interlocked operation Keys for navigation in menus and for entering values Integrated motor control by special relays with enhanced performance Fault recorder. Multifunction protection relays SIPROTEC 4
1 2 3 4 5 6 7 LC display LEDs Key-operated switches Navigation keys Control keys Function keys LC text display

2 7 4

R-HA35-104 eps

Multifunction protection relay SIPROTEC 4 7SJ600 / 7SJ602

4 2

6
R-HA35-103 eps

Multifunction protection relay SIPROTEC 4 7SJ61 / 7SJ62

1 4 2

3
R-HA35-102 eps

Multifunction protection relay SIPROTEC 4 7SJ63

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 57

Standards
Standards, specications, guidelines
Type of service location The switchgear can be used as indoor installation according to IEC 61936 (Power installations exceeding 1 kV AC) and VDE 0101 Outside lockable electrical service locations at places which are not accessible to the public. Enclosures of switchgear can only be removed with tools In lockable electrical service locations. A lockable electrical service location is a place outdoors or indoors that is reserved exclusively for housing electrical equipment and which is kept under lock and key. Access is restricted to authorized personnel and persons who have been properly instructed in electrical engineering. Untrained or unskilled persons may only enter under the supervision of authorized personnel or properly instructed persons. Terms Make-proof earthing switches are earthing switches with short-circuit making capacity according to IEC 62271-102 and VDE 0671-102 / EN 62 271-102. Dielectric strength The dielectric strength is veried by testing the switchgear with rated values of short-duration power-frequency withstand voltage and lightning impulse withstand voltage according to IEC 62271-1 / VDE 0671-1 (see table Dielectric strength). The rated values are referred to sea level and to normal atmospheric conditions (1013 hPa, 20 C, 11g/m3 humidity according to IEC 60071 and VDE 0111). The gas insulation at a relative gas pressure of 50 kPa permits switchgear installation at any desired altitude above sea level without the dielectric strength being adversely affected. This also applies to the cable connection when plug-in sealing ends are used. A decrease (reduction) of the dielectric strength with increasing site altitude must only be considered for panels with HV HRC fuses. For site altitudes above 1000 m, a higher insulation level must be selected. It results from the multiplication of the rated insulation level for 0 to 1000 m with the altitude correction factor Ka (see illustration and example). Standards NXPLUS C switchgear complies with the relevant standards and specications applicable at the time of type tests. In accordance with the harmonization agreement reached by the countries of the European Union, their national specications conform to the IEC standard. Table Dielectric strength
Rated voltage (r.m.s. value) Between phases and to earth Across isolating distances Between phases and to earth Across isolating distances kV kV kV kV kV 7.2 20 23 60 70 12 28 32 75 85 15 35 39 95 105 17.5 38 45 95 110 24 50 60 125 145 Rated short-duration power-frequency withstand voltage (r.m.s. value)

Rated lightning impulse withstand voltage (peak value)

Altitude correction factor Ka


For site altitudes above 1000 m, the altitude correction factor Ka is recommended, depending on the site altitude above sea level. Curve m = 1 for rated short-duration power-frequency withstand voltage and rated lightning impulse withstand voltage according to IEC 62271-1
Ka 1.50

Altitude correction factor

m=1 1.40 1.30 1.20 1.10

1.00 1,000 1,500 2,000 2,500 3,000 3,500 4,000

Site altitude in m above sea level

(Only for panels with HV HRC fuse)

Example: 3000 m site altitude above sea level (Ka = 1.28), 17.5 kV switchgear rated voltage, 95 kV rated lightning impulse withstand voltage Rated lightning impulse withstand voltage to be selected = 95 kV 1.28 = 122 kV Result: According to the above table, a switchgear for a rated voltage of 24 kV with a rated lightning impulse withstand voltage of 125 kV is to be selected.

Overview of standards (May 2010)


IEC standard Switchgear Devices NXPLUS C Circuit-breakers Vacuum contactors Disconnectors and earthing switches Switch-disconnectors Switch-disconnector / fuse combination HV HRC fuses Voltage detecting systems Degree of protection Insulation Instrument transformers Installation, erection IP code IK code Current transformers Voltage transformers IEC 62271-1 IEC 62271-200 IEC 62271-100 IEC 60470 IEC 62271-102 IEC 60265-1 IEC 62271-105 IEC 60282 IEC 61243-5 IEC 60529 IEC 62262 IEC 60071 IEC 60044-1 IEC 60044-2 IEC 61936-1 VDE standard VDE 0671-1 VDE 0671-200 VDE 0671-100 VDE 0670-501 VDE 0671-102 VDE 0670-301 VDE 0671-105 VDE 0670-4 VDE 0682-415 VDE 0470-1 VDE 0470-100 VDE 0111 VDE 0414-1 VDE 0414-2 VDE 0101 EN standard EN 62 271-1 EN 62 271-200 EN 62 271-100 EN 60 470 EN 62 271-102 EN 60 265-1 EN 62 271-105 EN 60 282 EN 61 243-5 EN 60 529 EN 50 102 EN 60 071 EN 60 044-1 EN 60 044-2

58 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010

HA35-2634a en eps

Standards
Standards, specications, guidelines
Current carrying capacity According to IEC 62271-200 or IEC 62271-1, VDE 0671-200 or VDE 0671-1, the rated normal current refers to the following ambient air temperatures: Maximum of 24-hour mean + 35 C Maximum + 40 C The current carrying capacity of the panels and busbars depends on the ambient air temperature outside the enclosure. Internal arc classications Protection of operating personnel by means of tests for verifying the internal arc classication Internal arcing tests must be performed in accordance with IEC 62271-200 or VDE 0671-200 Denition of criteria: Criterion 1: Correctly secured doors and covers do not open, limited deformations are accepted. Criterion 2: No fragmentation of the enclosure, no projection of small parts above 60 g Criterion 3: No holes in accessible sides up to a height of 2 m Criterion 4: No ignition of indicators due to hot gases Criterion 5: The enclosure remains connected to its earthing point. Resistance to internal faults Due to the single-pole enclosure of external components and the SF6 insulation of switching devices, the possibility of faults in SF6-insulated switchgear is improbable and a mere fraction of that typical of earlier switchgear types: There are no effects due to external inuences, such as: Pollution layers Humidity Small animals and foreign objects Maloperation is practically excluded due to logical arrangement of operating elements Short-circuit-proof feeder earthing by means of the circuitbreaker or the three-position switch-disconnector. In the unlikely event of a fault within the switchgear vessel, the energy conversion in the case of an internal arc fault is minor thanks to the SF6 insulation and the shorter arc length, i.e. approximately only 1/3 compared to air. The escaping gases are discharged upwards through a pressure relief duct (option). Aseismic capacity (option) NXPLUS C switchgear can be upgraded for regions at risk from earthquakes. For upgrading, earthquake qualication testing has been carried out in accordance with the following standards: IEC 60068-3-3 Guidance seismic test methods for equipment IEC 60068-2-57 Test Ff: Vibration Time-history method IEC 60068-2-59 Test Fe: Vibration Sine-beat method IEEE 693-2005 Recommended Practice for Seismic Design of Substations. For installation on even and rigid concrete or steel structure (without considering building inuences), the tested ground accelerations meet the following requirements: Uniform Building Code 1997 (UBC) Zone 4 California Building Code 1998 (CBC) Zone 4 IEEE 693-2005 High required response spectrum (Figure A.1). Color of the panel front Siemens standard (SN) 47 030 G1, color no. 700 / light basic (similar to RAL 7047 / gray).
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kV, Gas-Insulated Siemens HA 35.41 2010 59

Climate and environmental inuences The parts of the primary circuit of NXPLUS C switchgear under high voltage are completely enclosed and insensitive to climatic inuences. All medium-voltage devices (except for HV HRC fuses) are installed in a gas-tight, welded stainless-steel switchgear vessel which is lled with SF6 gas Live parts outside the switchgear vessel are provided with single-pole enclosure At no point can creepage currents ow from high-voltage potentials to earth Operating mechanism parts which are functionally important are made of corrosion-resistant materials Bearings in the operating mechanism are designed as dry-type bearings and do not require lubrication. The NXPLUS C switchgear is suitable for application in indoor installations under normal operating conditions as dened in the standard IEC 62271-1. Furthermore, the high-voltage part of the NXPLUS C switchgear can be used in environmental conditions of the climatic category 3C2 according to the standard IEC 60721-3-3. Protection against solid foreign objects, electric shock and water NXPLUS C switchgear fullls according to the standards
IEC 62271-1 IEC 62271-200 IEC 60529 IEC 62262 VDE 0671-1, EN 62 271-1 VDE 0671-200, EN 62 271-200 VDE 0470-1, EN 60 529 VDE 0470-100, EN 50 102

the following degrees of protection:


Degree of protection IP IP 65 IP 3XD IP 31D IP 32D IP 34D Degree of protection IK IK 07 Type of protection for parts of the primary circuit under high voltage for switchgear enclosure for switchgear enclosure (optional) for switchgear enclosure (optional) for switchgear enclosure (optional) Type of protection for switchgear enclosure

Type approval NXPLUS C switchgear has been type-approved by the following classication societies: Lloyds Register of Shipping (LRS) Det Norske Veritas (DNV) Germanischer Lloyd (GL) Russian Maritime Register of Shipping (RMR) The switchgear is therefore also approved for application on ships and platforms.

Published by and copyright 2010: Siemens AG Energy Sector Freyeslebenstrae 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Medium Voltage Postfach 3240 91050 Erlangen, Germany www.siemens.com/medium-voltage-switchgear For more information, please contact our Customer Support Center. Phone: +49 180 / 524 70 00 Fax: +49 180 / 524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com KG 0610 0.0 60 En 3600 / 27312
All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.

www.siemens.com/energy