Analog Input/Output Module SM 334; AI4/AO2 12 Bit

EWA 4NEB 710 6751 02

S7-300 Programmable Controller

This product information is part of the following documentation packages, which have the order numbers shown below: S7300 Programmable Controller ET 200M Distributed I/O Device 6ES7 3988AA028BA0 6ES7 1531AA008BA0

Safety Guidelines

This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: Danger indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken.

Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.

Caution indicates that minor personal injury or property damage can result if proper precautions are not taken.

Note draws your attention to particularly important information on the product, handling the product, or to a particular part of the documentation.

Qualified Personnel

The device/system may only be set up and operated in conjunction with this manual. Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards.

Correct Usage

Note the following:

Warning This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.

Trademarks

SIMATICR and SIMATIC NETR are registered trademarks of SIEMENS AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners.

Copyright E Siemens AG 1997 All rights reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Siemens AG Automation Group Industrial Automation Systems Postfach 4848, D-90327 Nrnberg Siemens Aktiengesellschaft

Disclaimer of Liability We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. Technical data subject to change. E Siemens AG 1997

Analog Input/Output Module SM 334; AI4/AO2 12 Bit


Contents In this description you will get to know:

S The characteristic features of the SM 334 S The technical specifications of the SM 334
You will learn:

S How to start up the SM 334 S Which measuring and output ranges the SM 334 has S With which parameters you can modify the features of the SM 334.
Note The connection and wiring of the SM 334 are described in the Module Specifications Reference Manual.

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-1

Analog Input/Output Module SM 334

1.1

Characteristic Features and Technical Specifications of the SM 334

Order No.

6ES7 3340KE000AB0

Characteristic Features

The SM 334 has the following characteristic features:

S 4 inputs in two groups S 2 outputs (voltage outputs) S Measured value resolution of 12 bits + sign S Type of measurement selectable
Voltage Resistance Temperature

S Isolated from CPU S Isolated from load voltage

Note Below the rated load voltage range, incorrect intermediate values occur at the output when the rated load voltage supply is switched on/off.

1-2

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

Analog Input/Output Module SM 334

Terminal Connection Diagram

Figure 1-1 shows the module view and the block diagram for the SM 334. You will find the detailed technical specifications of the SM 334 on the following pages.
Resistance measurement

Voltage input

L+ 24V
Current source Internal supply

IC01+ M0 + M0*

CH0

Multiplexer

Logic and backplane bus interface

MANA M2+

M1 + CH1 M1* IC01* IC23+ CH2 M2 +

M2* M3 + M3* MANA


DAC

M2* M3 + M3* IC23* CH0 CH1 CH3

MANA MANA M

V V M

QV0 MANA QV1 MANA

Voltage output

Bild 1-1

Module View and Block Diagram of the SM 334

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-3

Analog Input/Output Module SM 334

Dimensions and Weight Dimensions W H D (mm) Weight Module-Specific Data Number of inputs Number of outputs Cable length, shielded Voltages, Currents, Potential Rated load voltage L + 24 V DC Yes 4 2 Max. 100 m 40 125 120 (1.56 x 4.88 x 4.68 in.) Approx. 200 g

Status, Interrupts, Diagnostics Interrupts Diagnostic functions No No

Analog Value Generation for the Inputs Measuring principle Integration/conversion time (per channel) Integrating

S Configurable Yes S Integration time in ms 162/3 S Basic conversion time incl. 72


integration time in ms Additional conversion time for temperature measurement in ms 72

20 85 85

S Polarity protection
Power supply to the transducers

S Short-circuit-proof S Constant current


Resistance measurement

Yes Typ. 400 mA

S Resolution in bits (incl.


overcontrol range) unipolar measuring range bipolar measuring range 12 12+ Sign 60 12 12+ Sign 50

Galvanic isolation

S Between channels and


backplane bus voltage L+

S Interference suppression
Yes for interference frequency f1 in Hz

S Between channels and load Yes


Permiss. potential difference

S Between the inputs and


MANA (UCM)

1V 75 V DC 60 V AC Max. 60 mA Max. 80 mA Typ. 2 W

S Between MANA and


Minternal-(UISO) Current drawn

S From the backplane bus S From load voltage L +


(without load) Module power losses

1-4

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

Analog Input/Output Module SM 334

Interference Suppression, Error Limits for the Inputs Interference suppression for f=n (f1 " 1 %) (f1 = interference frequency)

Sensor Selection Data Input ranges (rated values)/input resistance

S Common-mode interference (USS < 1 V)

> 38 dB

S Resistance thermometer S Resistance S Voltage


Permissible input voltage (destruction limit)

Pt 100 10 kW 0 to 10 V

10 M W 10 M W 100 K W

> 36 dB (peak value of interference < rated value of input range) > 88 dB Crosstalk between the inputs Operational limit (in the total temperature range, referred to the input range)

S Series-mode interference

Max. 20 V continuously; 75 V for max. 1 s (duty factor 1:20) Possible

Connection of signal sensors

S For voltage measurement S For resistance measure"0.7 % "0.7 % "3.0 % ment with 2-wire connection with 3-wire connection with 4-wire connection Characteristic linearization

S Pt 100 S 0 to 10 V S 10 k W
Basic error limit (operational limit at 25_C, referred to the input range)

Possible Possible Possible Yes Pt 100 (climate range)

S Thermal resistance
"0.5 % "0.5 % "2.0 % "0.01 %/K " 0.05 %

S Pt 100 S 0 to 10 V S 10 k W
Temperature error (referred to the input range) Linearity error (referred to the input range)

Repeat accuracy (in the steady " 0.05 % state at 25_C, referred to the input range)

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-5

Analog Input/Output Module SM 334

Analog Value Generation for the Outputs Resolution (incl. overcontrol range) Cycle time (all output channels) Settling time 12 bits 85 ms

Actuator Selection Data Output range (rated value) Impedance (in rated output range) 0 to 10 V

S for resistive load S for capacitive load


Injection of substitute values

S with voltage outputs


0.8 ms 0.8 ms No with capacitive load Voltage output

Min. 2.5 kW Max. 1.0 mF Yes Max. 10 mA

Interference Suppression, Error Limits for the Outputs Crosstalk between the outputs Operational limit (in the total temperature range, referred to the output range) Basic error limit (operational error limit at 25_C, referred to the output range) > 88 dB "1.0 %

S Short-circuit protection S Short-circuit current


Destruction limit for voltages/ currents connected from outside

S Voltage at outputs to
MANA Connection of actuators 2-wire connection 4-wire connection (measuring line)

Max 15 V continuously

"0.85 % Possible Not possible

Temperature error (referred to "0.01 %/K the output range) Linearity error (referred to the output range) " 0.01 %

Repeat accuracy (in the steady " 0.01 % state at 25_C, referred to the output range) Output ripple; bandwidth 0 to 50 kHz (referred to the output range) " 0.1 %

1-6

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

Analog Input/Output Module SM 334

1.2

Starting Up the SM 334

STEP 7 V 4.0

Analog input/output module SM 334 AI4/AO2 12Bit is only contained in the module catalog of STEP 7 V 4.0 and higher.

Configuration

You set the prescribed function parameters of the SM 334:

S with STEP 7 before start-up (see User Manual STEP 7 or the online help
in STEP 7 ).

S in the user program with SFCs (see Reference Manual STEP 7 System and
Standard Functions).

Default Settings

The SM 334 has the following default settings:

S for the analog inputs: Pt 100 climate range S for the analog outputs: 0 to 10 V
Wiring Versions You can wire the channels of the SM 334 for the following combinations:

S S Channels 2 and 3 S S S S S
Channels 0 and 1

2 2 2 2 2 1 1

Pt 100 resistance voltage resistance Pt 100 Pt 100, 1 voltage voltage resistance, 1

Unused Input Channels

You must short-circuit unused channels of the SM 334 and connect them to MANA. You thus obtain optimum interference protection for your analog module. You should also deactivate unused channels during configuration with STEP 7 (see Section 4.3.4 in the Module Specifications Reference Manual), in order to reduce the cycle time of the module.

Unused Output Channels

To ensure that unused output channels of the SM 334 are voltage-free, you must deactivate them and leave them open. You deactivate an output channel during configuration with STEP 7 in the Output parameter block (see Section 4.3.4 in the Module Specifications Reference Manual).

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-7

Analog Input/Output Module SM 334

1.3

Analog Value Representation

Analog Values

The digitized analog value is the same for input and output values with the same rated range. The analog values are represented in twos complement. Table 1-1 shows the analog value representation of the analog modules:

Tabelle 1-1

Analog Value Representation Analog Value 15 S. 14 214 13 213 12 212 11 211 10 210 9 29 8 28 7 27 6 26 5 25 4 24 3 23 2 22 1 21 0 20

Resolution Bit number Significance of the bits

Analog Value Representation


Tabelle 1-2

Table 1-2 contains the analog value representation for the measuring ranges 10 kW and 0 to 10 V.

Representation of the Digitized Measured Value for Measuring Ranges 10 kW and 0 to 10 V Measuring Range Units Decimal 32767 32511 : 27649 27648 : 20736 : 0 Hexadecimal 7FFFH 7EFFH : 6C01H 6C00H : 5100H : 0 Undercontrol range Underflow Rated range Overcontrol range Range Overflow

10 kW > 11.7589 11.7589 : 10.0004 10.0000 : 7.50000 : 0 Negative value not possible

0 to 10 V > 11.7589 11.7589 : 10.0004 10.0000 : 7.50000 : 0 Not possible

1-8

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

Analog Input/Output Module SM 334

Climate Temperature Range, Pt 100

Table 1-3 contains the representation of the digitized measured value for the climate temperature range of the Pt 100 sensor.
Tabelle 1-3 Representation of the Digitized Measured Value for the Climate Temperature Range, Pt 100 Decimal Hexadecimal Range

Climate Temperature Range Pt 100 130 _C > 155.00 155.00 : 130.01 130.00 : 120.00 120.01 : 145.00 < 145.00

32767 15500 : 13001 13000 : 12000 12001 : 14500 32768

7FFFH 3C8CH : 32C9H 32C8H : D120H D11FH : C75CH 8000H

Overflow Overcontrol range

Rated range

Undercontrol range Underflow

Analog Value Representation

Table 1-4 contains the representation of the 0 to 10 V output range.


Tabelle 1-4 Representation of the analog output range from 0 to 10 V Units Output Range 0 to 10 V 0 11.7589 : 10.0004 10.0000 : 0 0 Decimal >32511 32511 : 27649 27648 : 0 Hexadecimal >7EFFH 7EFFH : 6C01H 6C00H : 0H Undercontrol range Rated range Overcontrol range Range Overflow

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-9

Analog Input/Output Module SM 334

1.4

Parameters

Structure of Record 1

Figure 1-2 shows you the structure of record 1 of the parameters for SM 334.
7 Byte 0 7 Byte 1 0 Interference suppression Set the same parameters for all channels. Channel 0 Channel 1 See Table 1-5 Channel 2 Channel 3 7 Byte 2 Byte 3 Byte 4 Byte 5 4 3 0 Meas. channel 0 Meas. channel 1 Meas. channel 2 Meas. channel 3 0 Bit no. Not relevant

Meas. type 7 Byte 6 Byte 7 4 3

Meas. range 0

See Table 1-6

Output channel 0 Output channel 1

Output type Byte 8 : Byte 13 :

Output range

See Table 1-7

Not relevant

Bild 1-2

Record 1 of the SM 334 parameters

1-10

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

Analog Input/Output Module SM 334

Interference Suppression

Table 1-5 contains the codes for the various frequencies which you enter in byte 1 of record 1 (see Figure 1-2). You must count the resulting integration time separately for each channel! Note You must set the same interference suppression for all channels of the SM 334.

Tabelle 1-5

Codes for Interference Suppression

Interference Suppression Frequency 60 Hz 50 Hz

Integration Time

Code

16.7 ms 20 ms

2#01 2#10

Type of Measurement and Measuring Ranges

Table 1-6 contains the measuring ranges of the SM 334 analog input/output module. The table shows the codes for the type of measurement and for the corresponding measuring range. You must enter these codes in bytes 2 to 5 of record 1, according to the desired measuring range (see Figure 1-2).
Tabelle 1-6 Codes for the Measuring Ranges of the Analog Inputs Code (Bits 4 to 7) 2#0000 2#0001 2#0100 Measuring Range Deactivated 0 to 10 V 10 kW Code (Bits 0 to 3) 2#0000 2#1000 2#1001

Type of Measurement Deactivated Voltage Resistance 4-wire connection Thermal resistance + linearization 4-wire connection

2#1000

Pt 100 climate

2#0000

Note The simultaneous connection of the PT 100 and a resistance to channels 0 and 1, or to channels 2 and 3, is not permitted. Reason: common current source for both channels.

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02

1-11

Analog Input/Output Module SM 334

Output Type and Output Ranges

Table 1-7 contains the output ranges of the SM 334 analog input/output module. The table shows the codes for the output type and for the corresponding output range. You must enter these codes in bytes 6 and 7 of record 1, according to the desired output range (see Figure 1-2).
Tabelle 1-7 Codes for the Output Ranges

Output Type

Code (Bits 4 to 7) 2#0000 2#0001

Output Range

Code (Bits 0 to 3) 2#0000 2#1000

Deactivated Voltage

Deactivated 0 to 10 V

1-12

SM 334; AI4/AO2 12Bit EWA 4NEB 710 6751-02