SL. NO.

LED STATUS

DESCRIPTION

1756-PA72 REDUNDANT POWER SUPPLY STATUS INDICATORS THIS COMBINATION OF STATUS INDICATORS Power-Solid Green 1 Both supplies are operating properly Non red -Off 2 Power-Solid Green This supply is operating properly but is the only supply providing power to the chass 3 Non red -Solid Amber adapter module 4 Power-OFF 5 All possible connections are made, but the redundant power supply is turned OFF Non red -Solid Amber 6 Power- OFF 7 Any of the following conditions may apply: Non red- OFF 8 1.The supply is turned OFF 2. Line voltage is not within the specified range 3. All connections are made, but input power is not supplied 4.All connections are made, including input power, but output cable (1756-CPR2) is 5. The supply is ON but defective 1756-L63 PROCESSOR STATUS INDICATORS
OK INDICATOR

1 2 3 4 5 1 2 3 1 2 1

Off Solid Green Flashing Green Solid Red Flashing Red

No power is applied The controller is OK The controller is storing or loading a project to or from nonvolatile memory The Controller detected a nonrecoverable fault, so it cleared the project from memor A new controller or major fault occurred
BATTERY INDICATOR

Off
Solid Green Solid Red

The battery supports memory If the controller is SERIES-A, The controller does not show this indication If the controller is SERIES-B, During power-down, the controller is saving the proje Either the battery is not installed or 95% or more dischaged
RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

Off

2 3 4 1 2 3

Solid Green Flashing Green Flashing Red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad
FORCE INDICATOR

OFF
Solid Amber Flasing Amber

- No tags contain I/O force values - I/O forces are inactive (disabled) - I/O forces are active (enabled) - I/O force values may or may not exist One or more input or output addresses have been forced to an ON or OFF state, but t forces have not been enabled

One or more input or output addresses have been forced to an ON or OFF state, but t forces have not been enabled 1757-SRM MODULE STATUS INDICATORS
HEALTH LED INDICATOR

1 2 3 4 5 1 2 3 4

Off Solid Green Flashing Green Solid Red Flashing Red Off Red < 1 second Solid Red Green Flash

No power to 1757-SRM The 1757-SRM OK The 1757-SRM OK but not communicating with other modules Powerup self test or 1757-SRM critical failure 1757-SRM NVS update, 1757-SRM non critical falure or 1757-SRM configured imp
COMMUNICATION LED INDICATOR

No power or No inter 1757-SRM comm activity Powerup with 1757-SRM establishing patrner communication Critical communication failure Communication activity present ( Sampled every 250ms)
CHASSIS STATE LED INDICATOR

Off No power or 1757-SRM chassis state is in secondary or failed state 1 Green < 1 second Powerup with patrner 1757-SRM determining primary state 2 Solid Green 1757-SRM chassis state in primary state 3 1757-ENBT- MODULE STATUS INDICATORS

NET (Network) LED STATUS INDICATOR

1 2 3 4 5 1 2 3

Off Solid Green Flashing Green Solid Red Flashing Red Off Solid Green Flashing Green

Not powered, No IP address CIP connections No connections Duplicate IP address Connection time out
LINK LED STATUS INDICATOR

No data transmission Ready Data transmission in progress


OK LED STATUS INDICATOR

Off No power 1 Solid Green In operation 2 Flashing Green Standby 3 Solid Red Major fault 4 Flashing Red Minor fault 5 Flashing Red and Green Test Self 5 COMMUNICATION WITH THE CONTROLNET BRIDGE MODULES CNBR-1 STATUS (OK INDICATOR) Off Module not communicating to a power supply fault or internal fault 1 Red Invalid controlnet address (For 2 -Module has invalid firmware 3 Flashing Red -Flash update in progress Green Noremal operation 4 Flashing Green Controlnet network 5 CNBR-1 CHANNEL STATUS A and B INDICATOR
LED STATUS (A & B)

1 2 3 4

Off No power Steady Red Faulted Unit Alternating Red/Green Test Self Alternating Red/Off In correct node configuration

LED STATUS (A or B)

Off Channel Disabled 1 Steady Green Normal Operation 2 Flashing Green/Off Temporary errors or Node is not configured to go online 3 Flashing Red/Off Media Fault or No other nodes present on network 4 Flashing Red/Green Incorrect network configuration 4 6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15) MODULE STATUS Off Module not communicating 1 Steady green Connections established 2 Flashing green No connections established 3 Steady red Major fault 4 I/O module removed 4 Flashing Red Wrong I/O module inserted FLASH program update in COMM A & B LED INDICATOR Off No power 1 Alternating red/green The module is performing a self-test 2 Alternating red/off Incorrect node configuration 3 Steady red Faulted module 4 COMM A OR B LED INDICATOR Off Channel disabled 1 Steady green Normal Operation 2 Flashing green/off Temporary network errors 3 Flashing red/off Media fault 4 Flashing red/green Incorrect network configuration 5 1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5VDC OUTPUT THIS COMBINATION OF STATUS INDICATORS Power-Solid Green This supply is operating properly but is the only supply providing power to the chass 3 Power-OFF NO POWER 5 1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A THIS COMBINATION OF STATUS INDICATORS Power-Solid Green This supply is operating properly but is the only supply providing power to the chass 3 Power-OFF NO POWER 5 1769-L35CR: COMPACT LOGIX CONTROL
OK INDICATOR

1 2 3 4

Off Solid Green Flashing Green Solid Red

No power is applied Controller is OK. The controller is storing or loading a project to or from Controller detected a nonrecoverable fault and cleared

5 1 2 1

Flashing Red

If a new controller, the controller requires a firmware


RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

Off

2 3 4 1 3 5 7

Solid Green Flashing Green Flashing Red

Off Steady green Flashing Steady red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad Network Channel Status Indicators A channel is disabled. Program network for redundant Normal operation is occurring. Temporary network errors have occurred. Check media The controller is faulted. Cycle power. If the fault

DESCRIPTION

YES

NO

REMARKS

ATUS INDICATORS THIS COMBINATION OF STATUS INDICATORS

erating properly

ing properly but is the only supply providing power to the chassis

ons are made, but the redundant power supply is turned OFF conditions may apply:

d OFF within the specified range e made, but input power is not supplied e made, including input power, but output cable (1756-CPR2) is not but defective
OK INDICATOR

K ing or loading a project to or from nonvolatile memory ted a nonrecoverable fault, so it cleared the project from memory major fault occurred
BATTERY INDICATOR

memory ERIES-A, The controller does not show this indication ERIES-B, During power-down, the controller is saving the project to its not installed or 95% or more dischaged
RUN INDICATOR

rogram or Test mode Run mode


I/O INDICATOR

evices in the I/O configuration of the controller does not contain a project (controller memory is empty) mmunicating with all the devices in its I/O configuration in the I/O configuration of the controller are not resopnding
FORCE INDICATOR

n I/O force values nactive (disabled) ctive (enabled) s may or may not exist output addresses have been forced to an ON or OFF state, but the enabled

output addresses have been forced to an ON or OFF state, but the enabled
HEALTH LED INDICATOR

RM

but not communicating with other modules 1757-SRM critical failure ate, 1757-SRM non critical falure or 1757-SRM configured improperly
COMMUNICATION LED INDICATOR

r 1757-SRM comm activity SRM establishing patrner communication on failure vity present ( Sampled every 250ms)
CHASSIS STATE LED INDICATOR

RM chassis state is in secondary or failed state er 1757-SRM determining primary state ate in primary state
NET (Network) LED STATUS INDICATOR

address

LINK LED STATUS INDICATOR

progress
OK LED STATUS INDICATOR

ET BRIDGE MODULES CNBR-1 STATUS (OK INDICATOR) Check the Module LED status CNBR-1 CHANNEL STATUS A and B INDICATOR

CONTROLNET ADAPTER MODULE (ACNR15) MODULE STATUS Check the Module LED status
OK INDICATOR

MM A & B LED INDICATOR Check the Module LED status Check the Module LED status

MM A OR B LED INDICATOR

2 AMP 5VDC OUTPUT THIS COMBINATION OF STATUS INDICATORS ing properly but is the only supply providing power to the chassis

IT 10A THIS COMBINATION OF STATUS INDICATORS ing properly but is the only supply providing power to the chassis

ing or loading a project to or from nonrecoverable fault and cleared

Check the Module LED status

Check the Module LED status

he controller requires a firmware


RUN INDICATOR

rogram or Test mode Run mode


I/O INDICATOR

evices in the I/O configuration of the controller does not contain a project (controller memory is empty) mmunicating with all the devices in its I/O configuration in the I/O configuration of the controller are not resopnding

Network Channel Status Indicators d. Program network for redundant occurring. errors have occurred. Check media ted. Cycle power. If the fault

1756-PA72 REDUNDANT POWER SUPPLY STATUS INDICATORS -LEFT SL. NO. LED STATUS Power-Solid Green Non red -Off Power-Solid Green Non red -Solid Amber Power-OFF Non red -Solid Amber Power- OFF Non red- OFF DESCRIPTION THIS COMBINATION OF STATUS INDICATORS 1 2 3 4 Both supplies are operating properly This supply is operating properly but is the only supply providing power to the chassis adapter module All possible connections are made, but the redundant power supply is turned OFF Any of the following conditions may apply: 1.The supply is turned OFF 2. Line voltage is not within the specified range 3. All connections are made, but input power is not supplied 4.All connections are made, including input power, but output cable (1756-CPR2) is not connected 5. The supply is ON but defective 1756-PA72 REDUNDANT POWER SUPPLY STATUS INDICATORS -RIGHT SL. NO. LED STATUS Power-Solid Green Non red -Off Power-Solid Green Non red -Solid Amber Power-OFF Non red -Solid Amber Power- OFF Non red- OFF DESCRIPTION THIS COMBINATION OF STATUS INDICATORS 1 2 3 4 Both supplies are operating properly This supply is operating properly but is the only supply providing power to the chassis adapter module All possible connections are made, but the redundant power supply is turned OFF Any of the following conditions may apply: 1.The supply is turned OFF 2. Line voltage is not within the specified range 3. All connections are made, but input power is not supplied 4.All connections are made, including input power, but output cable (1756-CPR2) is not connected 5. The supply is ON but defective STATUS
YES NO

STATUS
YES NO

REMARKS

REMARKS

1756-L63 PROCESSOR STATUS INDICATORS-TOP SL. NO. 1 2 3 4 5 1 2 3 1 2


Off Solid Green Flashing Green Solid Red Flashing Red

LED STATUS

DESCRIPTION
OK INDICATOR

STATUS
YES NO

REMARKS

No power is applied The controller is OK The controller is storing or loading a project to or from nonvolatile memory The Controller detected a nonrecoverable fault, so it cleared the project from memory A new controller or major fault occurred
BATTERY INDICATOR

Off
Solid Green Solid Red

The battery supports memory If the controller is SERIES-A, The controller does not show this indication If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non Either the battery is not installed or 95% or more dischaged
RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

1 2 3 4 1 2 3

Off
Solid Green Flashing Green Flashing Red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad
FORCE INDICATOR

OFF
Solid Amber Flasing Amber

- No tags contain I/O force values - I/O forces are inactive (disabled) - I/O forces are active (enabled) - I/O force values may or may not exist One or more input or output addresses have been forced to an ON or OFF state, but the forces have not been enabled

1756-L63 PROCESSOR STATUS INDICATORS-BOTTOM SL. NO. 1 2 3 4 5 1 2 3 1 2


Off Solid Green Flashing Green Solid Red Flashing Red

LED STATUS

DESCRIPTION
OK INDICATOR

STATUS
YES NO

REMARKS

No power is applied The controller is OK The controller is storing or loading a project to or from nonvolatile memory The Controller detected a nonrecoverable fault, so it cleared the project from memory A new controller or major fault occurred
BATTERY INDICATOR

Off
Solid Green Solid Red

The battery supports memory If the controller is SERIES-A, The controller does not show this indication If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non Either the battery is not installed or 95% or more dischaged
RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

1 2 3 4 1 2

Off
Solid Green Flashing Green Flashing Red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad
FORCE INDICATOR

OFF
Solid Amber

- No tags contain I/O force values - I/O forces are inactive (disabled) - I/O forces are active (enabled) - I/O force values may or may not exist One or more input or output addresses have been forced to an ON or OFF state, but the forces have not been enabled

Flasing Amber

1757-SRM MODULE STATUS INDICATORS-TOP SL. NO. LED STATUS DESCRIPTION


HEALTH LED INDICATOR

STATUS
YES NO

REMARKS

1 2 3 4 5 1 2 3 4 1 2 3 4

Off Solid Green Flashing Green Solid Red Flashing Red Off Red < 1 second Solid Red Green Flash
Off Green < 1 second Solid Green Display

No power to 1757-SRM The 1757-SRM OK The 1757-SRM OK but not communicating with other modules Powerup self test or 1757-SRM critical failure 1757-SRM NVS update, 1757-SRM non critical falure or 1757-SRM configured improperly
COMMUNICATION LED INDICATOR

No power or No inter 1757-SRM comm activity Powerup with 1757-SRM establishing patrner communication Critical communication failure Communication activity present ( Sampled every 250ms)
CHASSIS STATE LED INDICATOR

No power or 1757-SRM chassis state is in secondary or failed state Powerup with patrner 1757-SRM determining primary state 1757-SRM chassis state in primary state Display showing as PRIM [Primary]

1757-SRM MODULE STATUS INDICATORS-BOTTOM SL. NO. 1 2 3 4 5 1 2 3 4 1 2 3 4 LED STATUS Off Solid Green Flashing Green Solid Red Flashing Red Off Red < 1 second Solid Red Green Flash
Off Green < 1 second Solid Green Display

DESCRIPTION
HEALTH LED INDICATOR

STATUS
YES NO

REMARKS

No power to 1757-SRM The 1757-SRM OK The 1757-SRM OK but not communicating with other modules Powerup self test or 1757-SRM critical failure 1757-SRM NVS update, 1757-SRM non critical falure or 1757-SRM configured improperly
COMMUNICATION LED INDICATOR

No power or No inter 1757-SRM comm activity Powerup with 1757-SRM establishing patrner communication Critical communication failure Communication activity present ( Sampled every 250ms)
CHASSIS STATE LED INDICATOR

No power or 1757-SRM chassis state is in secondary or failed state Powerup with patrner 1757-SRM determining primary state 1757-SRM chassis state in primary state Display showing as SYNC [Synchronised with Primary]

1757-ENBT- MODULE STATUS INDICATORS-TOP SL. NO. 1 2 3 4 5 1 2 3 1 2 3 4 5 6 7 LED STATUS Off Solid Green Flashing Green Solid Red Flashing Red Off Solid Green Flashing Green Off Solid Green Flashing Green Solid Red Flashing Red Flashing Red and Green Display Not powered, No IP address CIP connections No connections Duplicate IP address Connection time out
LINK LED STATUS INDICATOR

DESCRIPTION
NET (Network) LED STATUS INDICATOR

STATUS
YES NO

REMARKS

No data transmission Ready Data transmission in progress


OK LED STATUS INDICATOR

No power In operation Standby Major fault Minor fault Self Test Display indication 192.168.0.X1-PWQS-OK

1757-ENBT- MODULE STATUS INDICATORS-BOTTOM SL. NO. 1 2 3 4 5 1 2 3 1 2 3 4 5 6 7 LED STATUS Off Solid Green Flashing Green Solid Red Flashing Red Off Solid Green Flashing Green Off Solid Green Flashing Green Solid Red Flashing Red Flashing Red and Green Display Not powered, No IP address CIP connections No connections Duplicate IP address Connection time out
LINK LED STATUS INDICATOR

DESCRIPTION
NET (Network) LED STATUS INDICATOR

STATUS
YES NO

REMARKS

No data transmission Ready Data transmission in progress


OK LED STATUS INDICATOR

No power In operation Standby Major fault Minor fault Self Test Display indication 192.168.0.X2-QS-OK

COMMUNICATION WITH THE CONTROLNET BRIDGE MODULES-TOP SL. NO. 1 2 3 4 5 Off Red Flashing Red Green Flashing Green LED STATUS DESCRIPTION CNBR-1 STATUS (OK INDICATOR) Module not communicating to a power supply fault or internal fault Invalid controlnet address (For a redundant system this may be a temporary condition during chassis -Module has invalid firmware -Flash update in progress Noremal operation Controlnet network configuration error, Network cabling error, or no other active nodes on the network CNBR-1 CHANNEL STATUS A and B INDICATOR No power Faulted Unit Self Test In correct node configuration Channel Disabled Normal Operation Temporary errors or Node is not configured to go online Media Fault or No other nodes present on network Incorrect network configuration Display indication PWQS-%CXX-KPAV-nC20-A#04-OK STATUS
YES NO

REMARKS

LED STATUS (A & B)

1 2 3 4 1 2 3 4 4 5

Off Steady Red Alternating Red/Green Alternating Red/Off Off Steady Green Flashing Green/Off Flashing Red/Off Flashing Red/Green Display

LED STATUS (A or B)

COMMUNICATION WITH THE CONTROLNET BRIDGE MODULES-BOTTOM SL. NO. 1 2 3 4 5 Off Red Flashing Red Green Flashing Green LED STATUS DESCRIPTION CNBR-1 STATUS (OK INDICATOR) Module not communicating to a power supply fault or internal fault Invalid controlnet address (For a redundant system this may be a temporary condition during chassis -Module has invalid firmware -Flash update in progress Noremal operation Controlnet network configuration error, Network cabling error, or no other active nodes on the network CNBR-1 CHANNEL STATUS A and B INDICATOR No power Faulted Unit Self Test In correct node configuration Channel Disabled Normal Operation Temporary errors or Node is not configured to go online Media Fault or No other nodes present on network Incorrect network configuration Display indication QS-%CXX-KPIV-nC16-A#05-OK STATUS
YES NO

REMARKS

LED STATUS (A & B)

1 2 3 4 1 2 3 4 5 6

Off Steady Red Alternating Red/Green Alternating Red/Off Off Steady Green Flashing Green/Off Flashing Red/Off Flashing Red/Green Display

LED STATUS (A or B)

6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-TOP SL. NO. 1 2 3 4 5 LED STATUS Off Steady green Flashing green Steady red Flashing Red DESCRIPTION MODULE STATUS Module not communicating due to a powersupply fault or internal fault. Connections established No connections established Major fault I/O module removed Wrong I/O module inserted FLASH program update in progress COMM A & B LED INDICATOR No power The module is performing a self-test Incorrect node configuration Faulted module COMM A OR B LED INDICATOR Channel disabled Normal Operation Temporary network errors Media fault Incorrect network configuration STATUS
YES NO

REMARKS

1 2 3 4 1 2 3 4 5

Off Alternating red/green Alternating red/off Steady red Off Steady green Flashing green/off Flashing red/off Flashing red/green

6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-MIDDLE SL. NO. 1 2 3 4 5 LED STATUS Off Steady green Flashing green Steady red Flashing Red DESCRIPTION MODULE STATUS Module not communicating due to a powersupply fault or internal fault. Connections established No connections established Major fault I/O module removed Wrong I/O module inserted FLASH program update in progress COMM A & B LED INDICATOR No power The module is performing a self-test Incorrect node configuration Faulted module COMM A OR B LED INDICATOR Channel disabled Normal Operation Temporary network errors Media fault Incorrect network configuration STATUS
YES NO

REMARKS

1 2 3 4 1 2 3 4 5

Off Alternating red/green Alternating red/off Steady red Off Steady green Flashing green/off Flashing red/off Flashing red/green

6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-BOTTOM SL. NO. 1 2 3 4 5 LED STATUS Off Steady green Flashing green Steady red Flashing Red DESCRIPTION MODULE STATUS Module not communicating due to a powersupply fault or internal fault. Connections established No connections established Major fault I/O module removed Wrong I/O module inserted FLASH program update in progress COMM A & B LED INDICATOR No power The module is performing a self-test Incorrect node configuration Faulted module COMM A OR B LED INDICATOR Channel disabled Normal Operation Temporary network errors Media fault Incorrect network configuration STATUS
YES NO

REMARKS

1 2 3 4 1 2 3 4 5

Off Alternating red/green Alternating red/off Steady red Off Steady green Flashing green/off Flashing red/off Flashing red/green

1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5VDC OUTPUT-LEFT SL. NO. LED STATUS DESCRIPTION STATUS
YES NO

REMARKS

THIS COMBINATION OF STATUS INDICATORS Power-Solid Green This supply is operating properly but is the only supply providing power to the chassis adapter module 1 Power-OFF NO POWER 2 1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5VDC OUTPUT-RIGHT SL. NO. 1 2 LED STATUS Power-Solid Green Power-OFF DESCRIPTION THIS COMBINATION OF STATUS INDICATORS This supply is operating properly but is the only supply providing power to the chassis adapter module NO POWER STATUS
YES NO

REMARKS

1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A-LEFT SL. NO. LED STATUS DESCRIPTION STATUS
YES NO

REMARKS

THIS COMBINATION OF STATUS INDICATORS Power-Solid Green This supply is operating properly but is the only supply providing power to the chassis adapter module 1 Power-OFF NO POWER 2 1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A-RIGHT SL. NO. 1 2 LED STATUS Power-Solid Green Power-OFF DESCRIPTION THIS COMBINATION OF STATUS INDICATORS This supply is operating properly but is the only supply providing power to the chassis adapter module NO POWER STATUS
YES NO

REMARKS

1769-L35CR: COMPACT LOGIX CONTROL-LEFT SL. NO. 1 2 3 4 5 1 2


Off Solid Green Flashing Green Solid Red Flashing Red

LED STATUS

DESCRIPTION
OK INDICATOR

STATUS
YES NO

REMARKS

No power is applied Controller is OK. The controller is storing or loading a project to or from Controller detected a nonrecoverable fault and cleared If a new controller, the controller requires a firmware
RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

1 2 3 4 1 2 3 4 1 2 3 1 2 3

Off
Solid Green Flashing Green Flashing Red

Off Steady green Flashing Steady red Off


Solid Green Solid Red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad Network Channel Status Indicators A channel is disabled. Program network for redundant Normal operation is occurring. Temporary network errors have occurred. Check media The controller is faulted. Cycle power. If the fault
BATTERY INDICATOR

The battery supports memory If the controller is SERIES-A, The controller does not show this indication If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non Either the battery is not installed or 95% or more dischaged
FORCE INDICATOR

OFF
Solid Amber Flasing Amber

- No tags contain I/O force values - I/O forces are inactive (disabled) - I/O forces are active (enabled) - I/O force values may or may not exist One or more input or output addresses have been forced to an ON or OFF state, but the forces have not been enabled

1769-L35CR: COMPACT LOGIX CONTROL-RIGHT SL. NO. 1 2 3 4 5 1 2


Off Solid Green Flashing Green Solid Red Flashing Red

LED STATUS

DESCRIPTION
OK INDICATOR

STATUS
YES NO

REMARKS

No power is applied Controller is OK. The controller is storing or loading a project to or from Controller detected a nonrecoverable fault and cleared If a new controller, the controller requires a firmware
RUN INDICATOR

Off
Solid Green

The controller is in Program or Test mode The Controller is in Run mode


I/O INDICATOR

1 2 3 4 1 2 3 4 1 2 3 1 2 3

Off
Solid Green Flashing Green Flashing Red

Off Steady green Flashing Steady red Off


Solid Green Solid Red

Either: - There are no devices in the I/O configuration of the controller - The controller does not contain a project (controller memory is empty) The controller is communicating with all the devices in its I/O configuration One or more devices in the I/O configuration of the controller are not resopnding The Chassis bad Network Channel Status Indicators A channel is disabled. Program network for redundant Normal operation is occurring. Temporary network errors have occurred. Check media The controller is faulted. Cycle power. If the fault
BATTERY INDICATOR

The battery supports memory If the controller is SERIES-A, The controller does not show this indication If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non Either the battery is not installed or 95% or more dischaged
FORCE INDICATOR

OFF
Solid Amber Flasing Amber

- No tags contain I/O force values - I/O forces are inactive (disabled) - I/O forces are active (enabled) - I/O force values may or may not exist One or more input or output addresses have been forced to an ON or OFF state, but the forces have not been enabled