MCCBs and trip-free switches

16 A to 1600 A

MCCBs and trip-free switches 16 to 1600 A


Easy mounting and safety
The new range of MCCBs provides safe and easy solutions for low voltage electrical circuits protection. The state of the art circuit breakers offers both designers and installers wide range of features and benefits. Special attention has been given to ergonomics, especially with the integration of these devices in the TP&N and panelboard.

Your benefits:
Easy to install Quick, easy and safety mounting of accessories Wide range of rated current ratings and breaking capacities Calibrated at 50 Deg centigrade Trip-free switches

Technical data :
Comply with IEC 60947-2 6 frame sizes: x160, x250, h250, h630, h1000, h1600 Breaking capacity: 18, 25, 40, 50, 65, 70 kA Thermal magnetic and electronic trip units 1 pole to 4 poles Current limiting type Complete range of accessories International certification and approvals

Expert tips
1 2 3 4
Design by Hager
In harmony with Hager enclosures and modular products.

5 6 7 8

Visibility of auxiliaries fitted


Indicates type of auxiliary mounted in breaker.

Electronic trip unit (LSI)


Is permitting total selectivity and generator protection.

Integrated padlocking facility


Nice solution for maintenance.

Breaking capacity
18 to 70kA, Icu 415V AC, covers all applications.

Complete range of accessories


Rotary handles, padlocks, motors, terminal covers.

Easy mounting of auxiliaries


Easy opening of secondary cover, clip-on type auxiliaries.

Flexible connection
Collar terminals, front and rear connections, straight connections, spreaders ...

H3 add-on blocks 16 to 1600 A


Easy mounting and safety
Designed to complete the MCCBs and trip-free switches range, the residual current add-on blocks feature: - performance: high immunity A type for standard versions, adjustable product ... - Safety: default current gradually displayed, class II... - Ease of use: drawer system, system avoids the omission of terminal tightening, Quickconnect ...

Your benefits:
Easy to install Safety to use Time saving Design matches with modular protection devices

Technical data :
3 frame sizes: x160, x250, h630 Double isolation class II Type A reinforced immunity Fixed 300mA version for x160 Sensitivity and time delay settings

Expert tips
1 2 3
Drawer system for mounting on x160
Quick and safe to mount, thanks to the system avoiding the terminal tightening omission.

4 5 6

High performance
Gradual display of the default current allows preventive action before tripping.

Connections
for the information report via QuickConnect terminals: fast and long term quality connections.

Safe connection MCCB / add-on block


- Class II: terminal cover avoid direct contacts.

A and HI type are standard


High detection performance product: - detects sinusoidal alternating currents and residual pulsating currents - is protected against nuisance tripping caused by transient voltages

Pre-mounted connection screws


Simplified implementation of the add-on blocks: - time saving - avoid part loosing.

MCCBs : technical characteristics


Frame Product Reference Number of poles [No.] Electrical characteristics Rated current In [A] Current rated range [A] Rated service voltage, (AC) Ue [V] Frequency f [Hz] Rated insulation voltage Ui [V] Rated impulse withstand voltage Uimp [kV] Rated ultimate short-circuit breaking capacity, (Icu) (AC) 50-60 Hz 220/230 V Icu [kA] (AC) 50-60 Hz 380/415 V Icu (AC) 50-60 Hz 480/500/525 V Icu (AC) 50-60 Hz 660/690 V Icu (DC) 250 V - 2 poles in series Icu Rated service short-circuit breaking capacity, (Ics) (AC) 50-60 Hz 220/230 V Ics (AC) 50-60 Hz 380/415 V (AC) 50-60 Hz 480/500/525 V (AC) 50-60 Hz 660/690 V (DC) 250 V - 2 poles in series Rated short-circuit making capacity Rated short-time withstand current for 1s Category of use (EN 60947-2) Calibration temperature Derating Ics Ics Ics Ics Icm Icw [kA] [kA] [kA] [kA] x160 Switch HCA 3-4 160 125-160 220-440 50/60 800 8 MCCB HDA 3-4 x250 Switch HCB 3-4 250 250 220-440 50/60 800 8 MCCB HNB

HHA 3-4

HNA 3-4

16-125 (1P), 16-160 (2,3,4P)

100-250

25 18 10 25

35 25 10 25

85 40 10 40 20

85 40 9 40 20

[kA] [kA] [kA] [kA] [kA] [kA] [kA]

40C 50C 55C 60C 65C

Suitability for isolation Electric endurance in number of cycles Mechanical endurance in number of operations Operating temperature Storage temperature Power loss (at In for 3P) Reference standard Releases: switch Releases: TM (thermomagnetic) T fixed, M fixed T adjustable, M fixed T adjustable, M adjustable Thermal adjustment value Magnetic adjustment value Releases: LSI (electronic) Long delay Short delay Time delay Terminations Standard terminal type Maximum terminal capacity Terminal width Terminal shields Cage terminal Extended connections Rear connections Dimensions Height Width

18 20 5 5 2,8 2 A 50C 100% 100% 95% 93% 90% ok 10000 20000 -25 to +70C -35 to +70C [W] 39 IEC 60947-3 IEC 60947-2 ok ok ok ok 0,63 to 1 x In -

5 -

5 9 3 A 50C 100% 100% 94% 91% 88% ok 10000 20000 -25 to +70C -35 to +70C 60 IEC 60947-3 IEC 60947-2 ok ok ok ok 0,63 to 1 x In 6-8-10-13 x In (200A) 5-7-9-11 In (250A) -

cage 95 mm2 mm ok integrated ok no mm mm mm mm mm mm kg kg kg kg 130 75 100 68 0,715 0,95

lugs 185 mm2 (cage) 25 ok ok ok ok 165 105 140 68 1,3 1,6

1P 2P 3P 4P 1P 2P 3P 4P

25 50

Depth Weight

0,29 0,48

Technical modifications reserved

h250 LSI MCCB HNC 3-4 250 40-125-250 220-690 50/60 800 8 85 50 25 7,5 85 25 10 7,5 -

HEC

h400 MCCB HHD 3-4 400 250-400 220-690 50/60 800 8

HND

h630 Switch HCD 3-4 630 400-630 220-690 50/60 800 8

MCCB HND

HED

h1000 Switch HCE 3-4 1000 800-1000 220-690 50/60 800 8 -

MCCB HNE

HEE

h1600 Switch HCF 3-4 1600 1250-1600 220-690 50/60 800 8

MCCB HNF

HEF

250-630-400

100 70 45 20 100 70 45 15 -

35 25 10 7,5 25 35

85 50 30 20 40 85

85 50 30 20

100 70 30 20

85 (800A) 75 (1000A) 50 30 20 -

100 70 30 20 -

100 50 45 25 75

100 70 65 45 75

85

85

A 40C 100% 95% 90% 80% 80% ok 10000 30000 -25 to +70C -35 to +70C 75 IEC 60947-2 0,4 to 1 x Ir 2,5 to 10 x Ir 0,1 - 0,2s lugs 120 mm2 (cage) 25 ok ok ok ok 165 105 140 97 2,5 3,3

25 50 10 30 7,5 15 25 40 A 50C 100% 100% 95% 92% 89% ok 4500 15000 -25 to +70C -35 to +70C 75 IEC 60947-2 ok ok 0,63 to 1 x In 6-8-10-12 x In lugs 240 mm2 (cage) 30 ok ok ok ok 260 140 185 97 4,2 5,6

50 50 30 30 15 15 9 5 (0,3s) B (250A) - A (630A) 40C 100% 100% 95% 90% 80% ok 4500 15000 -25 to +70C -35 to +70C 150 IEC 60947-3 IEC 60947-2 ok lugs 30 ok integrated ok 260 140 185 97 4,3 5,7 ok 0,4 to 1 x Ir 2,5 to 10 x Ir (250A) 2,5 to 8 x Ir (630A) 0,1 - 0,2s

20 10 (0,3s) ok 4500 15000 -25 to +70C -35 to +70C 150 IEC 60947-3 IEC 60947-2 ok lugs 45 ok integrated ok 273/433 210 280 99,5 11 14,8

85 (800A) 100 (800A) 75 (1000A) 75 (1000A) 50 50 30 30 20 20 B (800A) - A (1000A) 40C 100% 100% 95% 90% 80%

50 50 45 50 25 34 45 20 (0,3s) B 40C 100% 100% 95% 90% 80% ok 4500 15000 -25 to +70C -35 to +70C 170 IEC 60947-3 IEC 60947-2 ok lugs 45 ok integrated ok 370/570 210 280 140 27 31 ok 0,4 to 1 x In 2,5 to 10 x Ir 0,1 - 0,2s

ok 0,4 to 1 x Ir 2,5 to 10 x Ir (800A) 2,5 to 8 x Ir (1000A) 0,1 - 0,2s

Technical modifications reserved

MCCBs : technical characteristics


Product Frame Number of poles Tripping access Standards CEI/EN 60947-2 appendix B Electrical characteristics Mx rated current (40) In A Rated service voltage Ue V AC (50/60Hz) Mechanical characteristics Top and bottom supply For tripping, no additional external electrical sources Possible operating with 2 active phases Settings Sensitivity In In (A) 300mA 0.03, 0.1, 0.3, 1, 3, 6A Time delay t t (s) inst. inst., 0.06, 0.15, 0.3, 0.5, 1 Max. opening time Delay add-on block is not possible if In = 30mA Selective product Mechanical test button Isolating test without cable removal Electrical test button Reset button Sealable setting button Isolation level signaling by led 25 and 50% In runnig signalisation by led Residual default signaling contact Signaling contact 50% Idn Anti-transient Pulsating current High immunity -25C Accessories and connection Steel terminal cage (x3/x4) Connexion by lugs Extended connexions (x4) Spreaders (x4) Terminal covers (3P/4P) Interphase barriers (x3) Rigid cables connection capacity mm Flexible cables connection capacity mm (with terminal) Tightening torque Nm Copper bar (width) in mm Mounting Clips on DIN rail Fixed on mounting plate Fixation type Mounting by customer Dimensions and weight Dimensions (LxHxP) in mm Side mounted 4P L H D Weight 3P 4P 100 165 95 1,4 1,55 100 165 95 1,4 1,55 140 107,5 85 / 1,2 184 133 110 / 2,4 ok no side ok ok no side ok no ok bottom ok no ok bottom ok ok (included) no ok ok no ok 4 - 95 4 - 70 6 no ok (included) no ok ok no ok 4 - 95 4 - 70 6 no accessories ok ok ok ok ok 35-185 35-150 12 25 accessories ok ok ok ok ok 35-240 35-185 22 30 type AC type A type HI ms 10 / no ok ok ok ok no no no ok no ok ok yes ok 10 ok ok ok ok ok ok ok ok ok ok ok ok ok yes ok 0.03, 0.1, 0.3, 1, 3, 6A inst., 0.06, 0.15, 0.3, 0.5, 1 10 ok ok ok ok ok ok ok ok ok ok ok ok ok yes ok 0.03, 0.1, 0.3, 1, 3, 6A inst., 0.06, 0.15, 0.3, 0.5, 1 10 ok ok ok ok ok ok ok ok ok ok ok ok ok yes ok ok ok ok ok ok ok ok ok ok ok ok ok In Ue 125A 240-415V 125 - 160A 240-415V 160 - 250A 240-415V 400A - 500A 240-415V Add-on blocks x160 3, 4 mechanical ok x160 3, 4 mechanical ok x250 4 mechanical ok h630 4 mechanical ok

Technical modifications reserved

MCCBs : references guide


Pole Trip unit Serie In A 16 20 25 32 40 50 63 80 100 125 160 16-20-25 25-32-40 40-50-63 50-63-80 63-80-100 80-100-125 100-125-160 16 20 25 32 40 50 63 80 100 125 160 16-20-25 25-32-40 40-50-63 50-63-80 63-80-100 80-100-125 100-125-160 100 125 160 200 250 63-80-100 80-100-125 100-125-160 125-160-200 160-200-250 HDx 18kA HDA016L HDA020L HDA025L HDA032L HDA040L HDA050L HDA063L HDA080L HDA100L HDA125L HDA160L HHx 25kA HHA016L HHA020L HHA025L HHA032L HHA040L HHA050L HHA063L HHA080L HHA100L HHA125L HHA160L HHA025H HHA040H HHA063H HHA080H HHA100H HHA125H HHA160H HNx 40kA HNx 50kA HEx 65kA - 70kA

TM fix/fix

3P

TM adj/fix

x160

HNA025H HNA040H HNA063H HNA080H HNA100H HNA125H HNA160H

TM fix/fix

4P 100%

HDA017L HDA021L HDA026L HDA033L HDA041L HDA051L HDA064L HDA081L HDA101L HDA126L HDA161L HHA026H HHA041H HHA064H HHA081H HHA101H HHA126H HHA161H HNA026H HNA041H HNA064H HNA081H HNA101H HNA126H HNA161H HNB100H HNB125H HNB160H HNB200H HNB250H HNB100U HNB125U HNB160U HNB200U HNB250U HNB102H HNB127H HNB162H HNB202H HNB252H HNB101H HNB126H HNB161H HNB201H HNB251H HNC040H HNC125H HNC250H HNC041H HNC126H HNC251H HND250H HND400H HND630U HND251H HND401H HND631H HNE800H HNE970H HNE801H HNE971H HNF980H HNF990H HNF981H HNF991H HEC040H HEC125H HEC250H HEC041H HEC126H HEC251H HED250H HED400H HED630H HED251H HED401H HED631H HEE800U HEE970U HEE801H HEE971H HEF980H HEF990H HEF981H HEF991H

TM adj/fix

TM fix/fix 3P TM adj/adj x250 4P 0% - 4P 50%

4P 0% - 4P 100%

TM adj/adj

3P h250 4P 0%

LSI

LSI

3P h400 - h630

LSI

4P 0% - 50% LSI - 100% 3P h1000 LSI

4P 0% - 50% LSI - 100% 3P LSI

h1600

4P 0% - 50% LSI - 100%

63-80-100 80-100-125 100-125-160 125-160-200 160-200-250 16-40 50-125 100-250 16-40 50-125 100-250 100-250 160-400 250-630 100-250 160-400 250-630 800 1000 800 1000 1250 1600 1250 1600

Technical modifications reserved

Trip-free switches and add-on blocks for MCCBs references guide


Serie Product Version Poles 3 poles In A 125 160 125 4 poles 160 3 poles 250 4 poles 250 400 3 poles 630 Trip-free switches 4 poles 630 800 3 poles 1000 800 4 poles 1000 1250 3 poles 1600 1250 4 poles 1600 125 fixed 3 poles Side mounted 125 fixed 4 poles Add-on blocks 160 adjustable 160 adjustable 250 adjustable Bottom mounted 4 poles 400 adjustable 500 adjustable HBD401H HBD631H HBA161H HBB161H HBB251H 125 adjustable HBA128H HBA126H 125 adjustable 160 adjustable HBA127H HBA125H HBA160H HCF991H HCF990H HCF981H HCE971H HCF980H HCE970H HCE801H HCD631H HCE800H 400 HCD630H HCD401H HCB251H HCD400H HCB250H HCA161H HCA125H HCA160H HCA126H x160 x250 h630 h1000 h1600

10

Technical modifications reserved

Switches and accessories for MCCBs references guide


Products Version pole In A / Ue V 24V DC Shunt trip release 3/4P 48V DC 100-120V AC 200-240V AC 380-450V AC 24V DC 100-120V AC 200-240V AC 380-450V AC 24V DC 24V DC 110-120V AC 110-120V AC 220-240V AC 220-240V AC 380-415V AC 380-415V AC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC Switches and accessories x160 x250 HXA001H HXA002H HXA003H HXA004H HXA005H HXA011H HXA013H HXA014H HXA015H HXA051H HXA053H HXA054H HXA055H HXA021H HXA024H HXA025H HXA026H HXA030H HXA031H HXA039H included included HYA005H HYA006H HYA013H h250 HXC001H HXC002H HXC003H HXC004H HXC005H HXC011H HXC013H HXC014H HXC015H HXC051H HXC053H HXC054H HXC055H HXC021H HXC024H HXC025H HXC026H HXC030H HXC031H HXC039H HXC040H HXC042H HXC065H HYC003H HYC004H HYC010H HXC051H HXD051H HXC053H HXD053H HXC054H HXD054H HXC055H HXD055H h400-h630 h1000 h1600

Undervoltage release

3/4P

HXE011H HXE013H HXE014H HXE015H HXE051H HXE053H HXE054H HXE055H HXF051H HXF053H HXF054H HXF055H

Auxiliaries

Delayed undervoltage release

Auxiliary contact Alarm contact Auxiliary contact - low level Alarm contact - low level Direct rotary handle Extended rotary handle Padlock Motor operator Interlocking wire type

3P 4P 3P 4P 3P 4P 3P 4P 3/4P 3/4P 3/4P 3/4P

HXB030H HXB031H HXB040H HXB042H HXB065H HYB001H HYB002H HYB010H

3/4P 3/4P 3P

24V DC 220V AC

Collar terminal - copper 4P Collar terminal - aluminium Collar terminal multiple - aluminium 3P 4P 3P 4P 3/4P

HXD030H HXD031H HXD039H HXD040H HXD042H HXD065H HYD003H (250-400A) HYD004H (250-400A) HYD005H HYD006H HYD007H HYD008H HYD010H (250-400A) HYD013H (630A integrated) HYD011H (250-400A) HYD014H (630A) HYD012H (250-400A) HYD015H (630A) included HYD021H HYD022H HYD023H HYD024H HYD025H HYD026H HYD027H HYD028H HYD031H (250-400A) HYD033H (630A) HYD032H (250-400A) HYD034H (630A) HYD093H HYD095H HYD096H HYD097H* HYD098H*

HXE030H HXE031H HXE040H HXE042H HXE065H HYE007H (to 800) HYE008H (to 800) included (except 630A)

HXF030H HXF031H HXF039H HXF040H HXF042H included

Extended straight connection

3P Extended spreader connection 4P short long

HYA014H

HYB011H

HYC011H

HYA015H HYA019H HYB019H HYA021H HYA022H HYA023H HYA024H HYA025H HYA026H HYA027H HYA028H

HYB012H

included HYC021H (LSI) HYG021H (TM) HYC022H (LSI) HYG022H (TM) HYC025H (LSI) HYC026H (LSI) HYC027H HYC028H

included HYE021H HYE022H HYE025H HYE026H HYE031H (630-800A) HYE033H (1000A) HYE032H (630-800A) HYE034H (1000A) -

included -

Interphase barrier Terminal cover for extended straight connections Terminal cover large for spreader connection Connections Terminal cover short for rear connections Terminal cover for collar terminal

3/4P 3P 4P 3P 4P 3P 4P 3P 4P

HYB021H HYB022H HYB023H HYB024H HYB025H HYB026H HYB027H HYB028H

3P Rear connections 4P

HYB031H

HYC031H (LSI)

HYB032H

HYC032H (LSI)

DIN rail adaptor Connecting kit (0,75mm2) Rail Din raiser Compact lugs 16mm2 D:8,5 Compact lugs 25mm2 D:8,5 Compact lugs 35mm2 D:8,5 Compact lugs 50mm2 D:8,5 Compact lugs 70mm2 D:8,5 Compact lugs 95mm2 D:8,5 Compact lugs 120mm2 D:8,5 Compact lugs 120mm2 D:10 Compact lugs 150mm2 D:8,5 Compact lugs 150mm2 D:10,5 Compact lugs 185mm2 D:10,5 Compact lugs 185mm2 D:12,8 Compact lugs 240mm2 D:12,8

3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P 3/4P

HYA033H HYA035H HYA036H HYA086H HYA087H HYA088H HYA089H HYA090H HYA091H -

HYB092H HYB094H -

* with spreaders

Technical modifications reserved

11

MCCBs and trip-free switches x160


Moulded case circuit breakers x160 Thermal magnetic trip unit, 2 versions: - L version: fixed thermal and fixed magnetic - H version: adjustable thermal and fixed magnetic 3P and 4P Mechanical test button, lockable settings, integrated padlocking handle 4mm. Connection capacity 95 mm2 rigid cables 70 mm2 flexible cables collar terminals Comply with IEC 60 947-2. Trip-free switches Allows tripping at distance using a voltmetrical trip unit (optional) AC 22/23A. Comply with IEC 60 947-3.

Designation

In

Cat. ref. 3P 4P HDA017L HDA021L HDA026L HDA033L HDA041L HDA051L HDA064L HDA081L HDA101L HDA126L HDA161L

MCCBs x160 18kA breaking capacity Ics : 18 kA (400/415 V AC) fixed thermal 1x In fixed magnetic > 10 x In HDA125L MCCBs x160 25kA breaking capacity Ics : 20 kA (400/415 V AC) adjustable thermal 0,63 - 0,8 - 1 x In fixed magnetic > 10 x In

16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A

HDA016L HDA020L HDA025L HDA032L HDA040L HDA050L HDA063L HDA080L HDA100L HDA125L HDA160L

16-20-25A 25-32-40A 40-50-63A 50-63-80A 63-80-100A 80-100-125A 100-125-160A

HHA025H HHA040H HHA063H HHA080H HHA100H HHA125H HHA160H

HHA026H HHA041H HHA064H HHA081H HHA101H HHA126H HHA161H

HDA161H

12

Technical modifications reserved

MCCBs and trip-free switches x160


Add-on blocks for x160 devices These devices are intended to be fixed on the right side of the devices. Type A and HI For fault component pulsating current. HI (High Immunity): the products with reinforced immunity reduce the unexpected tripping when they protect equipment generating disturbances (micro-processing, electronic ballast...) Fixed version: 300 mA sensitivity and instantaneous tripping Adjustable version: adjustable sensitivity and tripping. Test button for differential functioning check. Mechanical test button LED or at distance signal for tripping or advance warning (25-50% I n). Assembly and disassembly facilitated by the drawer assembly system. The terminal cover is dependent of the add-on block. Connection capacity 95 mm2 rigid cables 70 mm2 flexible cables Comply with IEC 60 947-2 annexe B.

Designation

In

Cat. ref. 3P 4P HNA026H HNA041H HNA064H HNA081H HNA101H HNA126H HNA161H

MCCBs x160 40kA breaking capacity Ics : 20 kA (400/415 V AC) adjustable thermal 0,63 - 0,8 - 1 x In fixed magnetic > 10 x In HNA125H Trip-free switches x160 suitable for AC22A / AC 23A Ue: 415 V AC Icw (1s): 2 kA

16-20-25A 25-32-40A 40-50-63A 50-63-80A 63-80-100A 80-100-125A 100-125-160A

HNA025H HNA040H HNA063H HNA080H HNA100H HNA125H HNA160H

125A 160A

HCA125H HCA160H

HCA126H HCA161H

Add-on blocks

l n 300 mA fixed sensitivity instantaneous tripping sensitivity ln adjustable: 0,03 - 0,1 - 0,3 1 - 3 - 6A adjustable tripping: - instantaneous - time delay 0,06 - 1 sec.

125 A

HBA127H

HBA128H

125A 160A

HBA125H HBA160H

HBA126H HBA161H

HBA161H

Technical modifications reserved

13

Accessories for MCCBs and trip-free switches x160


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or close. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75I flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Designation Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle.

Characteristics

Cat. ref.

Auxiliary contacts AX AL

1 changeover contact (ON/OFF) 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC

HXA021H

HXA024H

HXA021H

HXA024H

Low level contact (ON/OFF) 125 V AC 1 NO + 1 NC Low level alarm contact 125 V AC 1 NO + 1 NC

HXA025H

HXA026H

Shunt trips SH

24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXA001H HXA002H HXA003H HXA004H HXA005H

HXA004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXA011H HXA013H HXA014H HXA015H

HXA014H Delayed undervoltage releases DUVR 24 V DC 110 - 120 V AC 220 - 240 V AC 380 - 450 V AC HXA051H HXA053H HXA054H HXA055H

14

Technical modifications reserved

Accessories for MCCBs and trip-free switches x160


Designation Characteristics Cat. ref. 3P Direct rotary handle padlockable handle max 6 mm HXA030H 4P

HXA030H Extended rotary handle padlockable handle max 8 mm HXA031H

HXA031H Padlock to mount on MCCB for handle locking for 3 padlock max 8 mm HXA039H

Collar terminals

set of 3 or 4 terminals for aluminium conductor

HYA005H

HYA006H

HYA006H Extended connections set of 4 straight connections set of 3 or 4 spreader connections HYA013H HYA013H

HYA014H

HYA015H

HYA015H

Technical modifications reserved

15

Accessories for MCCBs and trip-free switches x160


Designation Characteristics Cat. ref. 3P Interphase barriers set of 3, height: 50 mm set of 3, height: 97 mm HYA019H 4P HYA019H

HYB019H

HYB019H

HYA019H Terminal covers for extended straight connections for extended spreader connections for collar terminal HYA021H HYA023H HYA027H HYA022H HYA024H HYA028H

HYA023H

HYA027H

Din rail adaptor

HYA033H

HYA033H

Connecting kit

0,75 mm2 set of 3 x 2 wires length: 1,30m

HYA035H

HYA035H

Ring lugs

compact lugs 16 mm2 8,5 compact lugs 25 mm2 8,5 compact lugs 35 mm2 8,5 compact lugs 50 mm2 8,5 compact lugs 70 mm2 8,5 compact lugs 95 mm2 8,5

HYA086H HYA087H HYA088H HYA089H HYA090H HYA091H

16

Technical modifications reserved

MCCBs, trip-free switches x160


MCCBs 220/240V AC IEC 60 947-2 HDA Icu Ics HHA Icu Ics
PUSH TO TRIP

380/415V AC IEC 60 947-2 18 kA 18 kA 25 kA 20 kA 40 kA 20 kA

25 kA 25 kA 35 kA 25 kA 85 kA 30 kA

HNA

Icu Ics

Magnetic and thermal settings

TRIP

Magnetic adjustment fixed > 10 x In In Imag 15 - 50 A 600 A 63 - 80 A 1000 A 100 - 125 A 1500 A 160 A 1600 A

Thermal adjustment from 0,63 to 1 x In

Technical modifications reserved

17

MCCBs, trip-free switches x160


Tripping curve MCCB x160 10000

1000 Temps de dclenchement (s) Tripping time (s)

100
Cold start Dclenchement froid

10

160 A 125 A, 50 A 80 A 100 A, 40 A 63 A 32 A

1
Dclenchement Hot start chaud (rated current) (courant nominal)

0.1

0.01

0.001 1 10 100 xIn

Thermal constraint curve (Let-through energy) MCCB x160 104

25 A

Current limiting curve (Let-through pick current) MCCB x160 100


0,25
160 A 125 A 100 A 80 A 63 A 50 A 32 A 40 A 25 A

0,3

10

160A 125A 100A 80A 63A 50A 40A 32A 25A

0,5

10
0,7 0,8 0,9

I2t (x 106 A2 s)

102

101 0,1 1 101 102

Ip (kA) 1 0.1 0,1 1

Icc (kA)

10

100

18

Technical modifications reserved

MCCBs, trip-free switches x160 One line title


Dimensions MCCB x160 A 25 11 96,1

A (mm) 1P 130 114 111 45 2P 3P 4P 24,8 49,5 74,5 99,5

B (mm) 25 25 25 25

C (mm) 111 111 111 111

25

25

15 68

Terminal covers for extended straight connections A C A (mm) B 1P 2P 3P 4P 230 24,4 49,5 74,5 99,5 B (mm) 50 50 50 50 C (mm) 60,5 60,5 60,5 60,5

Terminal cover for extended spreader connections


A 60,5

A (mm) B 3P 4P 106,5 141,5

B (mm) 50 50

C (mm) 60,5 60,5

MCCBs, trip-free switches x160


Connection Connection with end lugs min. 6 mm2 min. 6 mm2 16 maxi 6 4 6 Nm max. 70 mm2 max. 95 mm2

Terminals fo aluminium conductor min. 35 mm2 max. 95 mm2 6 5 10 Nm

Interphase barriers

55 L (mm)
PUSH TO TRIP

HYA019H HYB019H

50 97

L 20

Technical modifications reserved

MCCBs, trip-free switches x160


Extended straight connections 26,8 17 16,8 10

3P
8,3 17,6

12,7 87

122 6 Nm

4P
PUSH TO TRIP

Extended spreader connections 26,8 8 16,8 10

3P
17,6 54 203 mm 35 8,3

12,7 87

6 Nm 122

4P
PUSH TO TRIP

35

35

Direct rotary handle

Extended rotary handle

12

(3 P) 74,5 (4 P) 99,5

127 48,5

(3 P) 74,5 (4 P) 99,5

112 200

101,8

53,7

101,8

45

45

8,5

Technical modifications reserved

21

MCCBs, trip-free switches x160


Auxiliaries Auxiliaries for MCCBs and trip-free switches

TRIP
PUSH TO TRIP

Mounting combination for auxiliaries and releases AX Auxiliary contact

t e

4P 3P

AX

SH Shunt trip

AX

AL

SH / UV

AL Alarm contact

AL

UV UV Undervoltage release

DUVR Delayed undervoltage release

22

Technical modifications reserved

Add-on block x160


Characteristics
Reset button : Signals add-on block tripping and must be acknowledged before switching on the installation. Test button for differential functioning : Allows to check the electrical operating of the MCCB / Add-on block association. Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on block association. LED signaling default current level in the installation: 25% (orange) and 50% (red) In; green light to signal correct operating. When associated with MCCB, the add-on block provides an earth fault protection and protects against electrical shocks by direct or indirect contacts. The add-on blocks are protected against nuisance tripping caused by transient voltages. Its able to detect sinusoidal alternating currents and residual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity). Remote tripping and advanced warning (50% In) signaling thanks to these contacts:

Earth leakage current (In) and delay (t) setting

Add-on block operating

N
0,1 0,03
0,3 1

incoming L1 L2 L3

0,3 1

6 I n (A)

0,1 0,03

10 I n (A)

0,06 Inst.

0,15 0,3

0,5 1 t (s)

0,15 0,3 0,06 0,5 Inst. 1 t (s)

CA 50% ON electronic 125A 250A test button N L1 L2 L3 outgoing

A (In) 0,03 Inst. S (t) 0,06 0,15 0,3 0,5 1 OK no no no no no 0,1 OK OK OK OK OK OK 0,3 OK OK OK OK OK OK 1 OK OK OK OK OK OK 3 OK OK OK OK OK OK 6 OK OK OK OK OK OK

Technical modifications reserved

23

Add-on block x160


Add-on block mounting

OFF

TRIP

PUSH TO TRIP

PUSH TO TRIP

6 Nm

Exclusive drawer assembly system allows quick mounting and makes MCCB and add-on block association a complete monoblock unit. Reinforced insulation connexion (class II) System avoids the omission of terminal tightening

Dimensions

A
3P A (mm) B (mm) 100 174,5 4P 100 199,5

25 B
24

25

37
Technical modifications reserved

165

Technical modifications reserved

25

MCCBs and trip-free switches x250


Moulded case circuit breakers x250, adjustable thermal and magnetic 3P and 4P Mechanical test button, lockable settings, integrated padlocking handle 4mm. Comply with IEC 60 947-2. Connection: Directly on copper cable terminal, with end lug max. width: 25 mm Connection capacity: 185 mm2 rigid cables Comply with IEC 60 947-2. Collar terminals Trip-free switches Allows tripping at distance using a voltmetrical trip unit (optional) Complies with IEC 60 947-3 AC 22/23A Add-on blocks for x250 devices These devices are intended to be fixed at the bottom of the devices. Type A and HI for fault component dc pulsating current and the products with reinforced immunity. Adjustable sensitivity and tripping. Test button for differential functioning check. Mechanical test button LED or at distance signal for tripping or advance warning (25 - 50% In). Comply with IEC 60 947-2 annexe B

Designation

Designation

In

Cat. ref. 3P 4P HNB101H HNB126H HNB161H HNB201H HNB251H

MCCBs x250 40kA

breaking capacity Icu : 40 kA (400/415 V AC) Ics: 20 kA adjustable thermal 0,63 - 0,8 - 1x In adjustable magnetic 6 - 8 - 10 - 13 x In (100 - 200A) 5 - 7 - 9 - 11 x In (250A)

100A 125A 160A 200A 250A

HNB100H HNB125H HNB160H HNB200H HNB250H

HNB100H

3P, 3 trip units 4P, neutral setting: 0 or 100% Trip-free switches x250 capacity suitable for AC 22/23A Icw (1s): 3 kA 250A HCB250H HCB251H

Add-on blocks

adjustable sensitivity In: 0,03 - 0,1 - 0,3 - 1 - 3 - 6A adjustable tripping: - instantaneous - time delay: 0,06 - 0,15 - 0,3 - 0,5 - 1 sec

160A 250A

HBB161H HBB251H

HBB251H

26

Technical modifications reserved

Accessories for MCCBs and trip-free switches x250


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or closed. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75 mm2 flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Designation Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle.

Characteristics

Cat. ref.

Auxiliary contacts AX AL

1 changeover contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC low level contact (ON/OFF) 125 V AC 1 NO + 1 NC low level alarm contact 125 V AC 1 NO + 1 NC

HXA021H

HXA024H

HXA025H

HXA021H

HXA024H

HXA026H

Shunt trips SH

24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXA001H HXA002H HXA003H HXA004H HXA005H

HXA004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXA011H HXA013H HXA014H HXA015H

HXA014H Delayed undervoltage releases DUVR 24 V DC 110 - 120 V AC 220 - 240 V AC 380 - 450 V AC HXA051H HXA053H HXA054H HXA055H

Technical modifications reserved

27

Accessories for MCCBs and trip-free switches x250


Designation Characteristics Cat. ref. 3P Direct rotary handles padlockable handle max 6 mm 4P HXB030H

Extended rotary handles

padlockable handle max 8 mm

HXB031H

Padlocks

to mount on MCCBs for handle locking for 3 padlock max 8 mm

HXA039H

Motor operators

24 V DC 230 - 240V AC

HXB040H HXB042H

Interlocking

wire type

HXB065H

HXB065H

HYB010H

28

Technical modifications reserved

Accessories for MCCBs and trip-free switches x250


Designation Characteristics Cat. ref. 3P Collar terminals 4 aluminium / copper conductors 150 mm2 rigid cables 120 mm2 flexible cables HYB001H 4P HYB002H

HYB002H

Extended connections

set of 4 pieces for straight connections spreader connections

HYB010H

HYB010H

HYB011H

HYB012H

HYB012H Interphase barriers set of 3, height: 97 mm HYB019H HYB019H

Terminal covers

for extended straight connections for extended spreader connections for rear connections for collar terminals

HYB021H HYB023H HYB025H HYB027H

HYB022H HYB024H HYB026H HYB028H

HYB022H

HYB024H

Technical modifications reserved

29

Accessories for MCCBs and trip-free switches x250


Designation Characteristics Cat. ref. 3P Rear connections set of 3 or 4 pieces HYB031H 4P HYB032H

HYB031H Connecting kit 0,75 mm2 set of 3 x 2 wires length: 1,30m HYA035H HYA035H

Ring lugs

compact lugs 35 mm2 8,5 compact lugs 50 mm2 8,5 compact lugs 70 mm2 8,5 compact lugs 95 mm2 8,5 compact lugs 120 mm2 8,5 compact lugs 150 mm2 8,5

HYA088H HYA089H HYA090H HYA091H HYB092H HYB094H

30

Technical modifications reserved

MCCBs, trip-free switches x250


MCCBs 220/240V AC IEC 60 947-2 HNB Icu Ics 85 kA 40 kA 380/415V AC IEC 60 947-2 40 kA 20 kA

PUSH TO TRIP

Magnetic and thermal settings

TRIP
6 5
8
PUSH TO TRIP

1 0,8 0,63

13

10

l i (xIn)

l r (xIn)

Thermal adjustment from 0,63 to 1 x In Magnetic adjustment from 6 to 13 x In (100 - 200A) from 5 to 11 x In (250A)

100 - 200A Ir (x In) Ii (x In) x In/Ii 0,63 - 0,8 - 1 x In 6 - 8 - 10 - 13 x In 0 - 100% 0 - 60%

250A

5 - 7 - 9 - 11 x In

%0

6 5
100%

8 10

1 0,8 0,63

xIn / Ii

13

l i (xIn)

l r (xIn)

Technical modifications reserved

31

MCCBs, trip-free switches x250


Tripping curve MCCB x250 10000

1000 Temps de (s) Tripping timedclenchement (s)

100
Dclenchement Cold start froid

10

1
Dclenchement Hot start chaud (rated current) (courant nominal)

0.1

0.01

0.001 1 10 100 xIn

Thermal constraint curve (Let-through energy) MCCB x250 109


250 A

Current limiting curve (Let-through pick current) MCCB x250

100
0,25

100 A

10

0,3

0,5

10 107
I2t (x 106 A2 s) Ip (kA)
0,8 0,9 0,7

106 1

105

104 102 103 104 105

0.1 0,1 1 Icc (kA) 10 100

32

Technical modifications reserved

MCCBs, trip-free switches x250


Dimensions MCCB x250 105 (3 P) 140 (4 P) 35 35

96 A (mm) 3P 4P 104,5 139,5 B (mm) 35 35 C (mm) 126 126

165 144 126

PUSH TO TRIP

35

22 68

Terminal covers for extended straight connections


A C

45

A (mm)
B

B (mm) 54,5 54,5

C (mm) 64 64

3P 4P

105 140

PUSH TO TRIP

Technical modifications reserved

33

MCCBs, trip-free switches x250


Accessories Terminal cover for extended spreader connections A 64 A (mm) B 3P 4P 147,5 196 B (mm) 54,5 54,5 C (mm) 64 64

PUSH TO TRIP

Terminal cover for rear connections A B C A (mm) 3P 4P 105 140 B (mm) 5 5 C (mm) 64 64

PUSH TO TRIP

Terminal covers for collar terminals A C A (mm) 3P 4P 105 140 B (mm) 28,5 28,5 C (mm) 64 64

34

Technical modifications reserved

MCCBs, trip-free switches x250


Connection Extended straight and spreader connections 23 23

11

6 5

12 Nm

6 5

12 Nm

PUSH TO TRIP

PUSH TO TRIP

48,5 13,5

48,5 11,5 23 35 11

3P
11 29,5

3P
52,5 29,5

11,5

8,5 36,5 23 120 168 226 50

93 226 128

4P
35 35 35

4P
50 50

Rear connections

4P 3P 35 35 35 11

16

57

11

144 mm

92

Technical modifications reserved

35

MCCBs, trip-free switches x250


Connection by collar

20 maxi.

6H 5540.a

min. 35 mm2 min. 35 mm2 8 5

max. 150 mm2 max. 185 mm2

35 mm2 to 50 mm2 = 25 Nm 60 mm2 to 185 mm2 = 25 Nm

Connection with end lugs

25 9 mm max.

25 mm 25 mm Max. max.

6 5

12 Nm

Interphase barriers 55 55

97

36

Technical modifications reserved

MCCBs, trip-free switches x250


Accessories Rotary handle A 116 48,5

101,8

45

PUSH TO TRIP

Extended rotary handle (3 P) 105 (4 P) 140

12 107,5 200

PUSH TO TRIP

101,8

45

8,5

Motor operator
90 90
Rated operating voltage Operating current (A) Starting current (A) 24V DC 230-240V AC 24V DC 230-240V AC 24V DC 230-240V AC ON Operating time (s) OFF RESET Operating switch rating Power supply required Dielectric properties 24V DC 230-240V AC ok ok 18 4 26 8 direct drive 0,1 0,1 0,1 100V, 0.1A, opening voltage 44V, current 4mA 300 VA minimum 1000 V AC 1500 V AC

150 165

Operating method

Technical modifications reserved

53,7

37

MCCBs, trip-free switches x250


Auxiliaries Auxiliaries for MCCBs and trip-free switches

TRIP
PUSH TO TRIP

Mounting combination for auxiliaries and releases

AX Auxiliary contact

t e

4P 3P

AX

SH Shunt trip

AX AX AL

SH / UV

AL Alarm contact

AL

UV UV Undervoltage release

DUVR Delayed undervoltage release

38

Technical modifications reserved

Add-on blocks x250


Characteristics
Reset button : Signals add-on block tripping and must be acknowledged before switching on the installation. Test button for differential operating : Allows to check the electrical operating of the MCCB / Add-on block association. Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on block association. LED signaling default current level in the installation: 25% (orange) and 50% (red) In; green light to signal correct operating. When associated with MCCB, the add-on block provides an earth fault protection and protects against electrical shocks by direct or indirect contacts. The add-on blocks are protected against nuisance tripping caused by transient voltages. Its able to detect sinusoidal alternating currents and residual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity). Remote tripping and advanced warning (50% In) signaling thanks to these contacts:

Earth leakage current (In) and delay (t) setting

Add-on block operating

2
0,3 1

N
0,1 0,03
0,3 1

incoming L1 L2 L3

6 I n (A)

0,1 0,03

10 I n (A)

0,06 Inst.

0,15 0,3

0,5 1 t (s)

0,15 0,3 0,06 0,5 Inst. 1 t (s)

CA 50% ON electronic 125A 250A test button N L1 L2 L3 outgoing

A (In) 0,03 Inst. S (t) 0,06 0,15 0,3 0,5 1 OK no no no no no 0,1 OK OK OK OK OK OK 0,3 OK OK OK OK OK OK 1 OK OK OK OK OK OK 3 OK OK OK OK OK OK 6 OK OK OK OK OK OK

Technical modifications reserved

39

Add-on blocks x250


Add-on block mounting

ON

ON

12 Nm 5 mm 6

Dimensions 70 96 35

270

105 10,5

45

104,5

126

45

35

35 35 139,5

68 93,2

70

40

Technical modifications reserved

PUSH PUSH

TO TR IP TO TR IP PUSH TO TR IP

MCCBs h250
Moulded case circuit breakers h250 Mechanical test button, lockable settings, Electronic trip unit LSI: Long delay (thermal equivalent) adjustable: Ir = 0.4 to 1 x In short delay (magnetic equivalent) adjustable: 2.5 to 10 x Ir time delay: 0,1 - 0,2 s 3P & 4P Mechanical test button, sealable settings, Characteristics In Not for use in TPN and panel boards. Connection: Directly on copper cable terminal, with end lug max. width: 25 mm Comply with IEC 60 947-2. Cat. ref. 3P MCCBs h250 50kA LSI breaking capacity Icu : 50 kA (400/415 V AC) Ics: 25 kA adjustable thermal Ir = 0.4 to 1 x In adjustable magnetic 2.5 to 10 x Ir 3P, 3 trip units & 4P, 3 trip units 16-40A 50-125A HNC040H HNC125H 4P HNC041H HNC126H HNC251H

Designation

100-250A HNC250H

MCCBs h250 70kA LSI

breaking capacity Icu : 70 kA (400/415 V AC) Ics: 70 kA adjustable thermal Ir = 0.4 to 1 x In adjustable magnetic 2.5 to 10 x Ir 3P, 3 trip units & 4P, 3 trip units

16-40A 50-125A

HEC040H HEC125H

HEC041H HEC126H HEC251H

100-250A HEC250H

HEC250H

Technical modifications reserved

41

Accessories for MCCBs h250


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or close. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75 mm2 flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Designation Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle.

Characteristics

Cat. ref.

Auxiliary contacts AX AL

1 changeover contact (ON/OFF) 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC

HXC021H

HXC024H

HXC021H

HXC024H

Low level contact (ON/OFF) 125 V AC 1 NO + 1 NC Low level alarm contact 125 V AC 1 NO + 1 NC Shunt trips SH 24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXA025H

HXA026H

HXC001H HXC002H HXC003H HXC004H HXC005H

HXC004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXC011H HXC013H HXC014H HXC015H

HXC014H Delayed undervoltage releases DUVR 24 V DC 110 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXC051H HXC053H HXC054H HXC055H

42

Technical modifications reserved

Accessories for MCCBs h250


Designation Characteristics Cat. ref.

Direct rotary handles

padlockable handle 5 - 8 mm2 max

HXC030H

Extended rotary handles

padlockable handle 5 - 8 mm2 max

HXC031H

Padlocks

to mount on MCCBs for handle locking for 3 padlock max 5 mm

HXC039H

HXC039H Motor operators 24 V DC 230-240 V AC HXC040H HXC042H

Interlocking

wire type

HXC065H

Technical modifications reserved

43

Accessories for MCCBs h250


Designation Characteristics In Cat. ref. 3P Collar terminals copper HYC003H 4P HYC004H

HYC004H Extended connections spreader connections straight connections HYC011H HYC010H HYC010H

HYC011H Terminal covers for extended straight connections (LSI only) for extended straight connections (TM only) for rear connections for collar terminals HYC22H HYC021H HYC022H

HYG021H

HYG022H

HYC025H HYC027H

HYC026H HYC028H

Rear connections

HYC031H

HYC032H

HYC031H Connecting kit 0,75 mm2 set of 3 x 2 wires length: 1,30m HYA035H HYA035H

44

Technical modifications reserved

MCCBs h250
MCCBs 220/240 V 380/415 V 660/690 V AC AC AC (kA) (kA) (kA) HNC HEC Icu Icu Icu Icu 85 85 100 100 50 25 70 70 7,5 7,5 20 15 Thermal adjustment from 0,63 to 1 x In Magnetic adjustment from 6 to 10 x In (250A) from 6 to 13 x In (160 and 200A) from 6 to 12 x In (32, 63, 100 and 125A)
Ir (x In)

Magnetic and thermal settings

0,63

0,8

8 10

Ii (x In)

Electronic trip unit setting (LSI) L - Long delay - protection against overloads: Ir and tr settings S - Short delay - protection against short circuits: Isd and tsd settings I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short circuit: 2,5 to 10 x Ir.

Use
1
0,8 0,63 0,5 0,4 xIn IR (A) 0,9 0,95 1 3 2 1 9 4 5 6 7 8

Characteristics (*) 3P 4P pos. 1, 4 and 7 pos. 2, 5 and 8 pos. 3, 6 and 9

Ir ajustable 1

Generator protection Standard protection Motor protection

pos. 1 pos. 2 and 3 pos. 4 and 5

Ir (A) PICK UP

Characteristics

x Ir

I
In A

LSI

3P Long Time Delay Ir (x In) tr (s) Short Time Delay isd (xlr) tsd (s) Inst li (xlr) Long Time Delay Ir (x In) OK OK OK OK OK OK OK 11s at 2 xlr 21s at 2 xlr 5 5 s at 6 xlr 7,5 s at 6 xlr 10 0,2 2,5 0,1 14 (max 12 x In) 11 s at 2 xlr 21 s at 2 xlr 7,5 s at 6 xlr 11 s at 2 xlr 21 s at 2 xlr 7,5 s at 6 xlr 11 s at 6 xIr 21 s at 2 xIr 21 s at 2 xIr tr (s)

4P Short Time Delay isd (xlr) tsd (s) Inst li (xlr) Protection Neutral

0,4 0,5

OK OK OK OK OK OK OK

Ir (x In)

0,63 0,8 0,9 0,95 1

1 2

2,5 5 10 2,5 10 2,5 2,5 5 10

0,1

Characteristics

3 4 5 6 7 8 9

0,2 0,1

14 (max 10 x In)

no

50%

0,2 0,1 100%

0,2

Technical modifications reserved

45

MCCBs h250
MCCB h250 3P LSI 10000

1000
Tripping time (s) Temps de dclenchement (s)

100

10

3 4

0.1
1, 2, 3, 4

0.01 100 1000 10000 %Ir

LTD pick-up current Characteristics Standard LTD STD INST

Ir

x In No.

0,4 1 11 2,5 0,1

0,5 2 21

0,63

0,8 3 21 5 0,1 14 (max 13 x In)

0,9 4 5

0,95 5

Tr Isd tsd li

(s) x Ir (s) x Ir

7,5 600 % x Ir 10 0,2

200 % x Ir 2,5 0,1

10 0,1

46

Technical modifications reserved

MCCBs h250
MCCB h250 4P LSI 10000

1000 Temps de dclenchement (s) Tripping time (s)

100

10

1, 4, 7

2, 5, 8

3, 6, 9

0.1

0.01 100 1000 10000 %Ir

LTD pick-up current Characteristics LTD STD INST

Ir

x In No.

0,4 1 11 s 2,5 0,1 2 21 s 5

0,5 3 7,5 s 600% x Ir 10 0,2

0,63 4 11 s 2,5 0,1

0,8 5 21 s 5 14 (max 13 x In) 6

0,9 7 11 s 2,5

0,95 8 21 s 5 0,1

1 9 7,5 s 600% x Ir 10 0,2

Tr Isd

(s) x Ir (s) x Ir

7,5 s 600% x Ir 10 0,2

200 % x Ir

200 % x Ir

200 % x Ir

Neutral protection

no

0,5

Technical modifications reserved

47

MCCBs h250
Thermal constraint curve (Let-through energy) MCCB h250 109

108

107 I2t (x 106 A2 s)

HNC... upto 50kA HEC... upto 70kA

106

105

104 102 103 104 105

Current limiting curve (Let-through peak current) MCCB h250 100


0,25

0,3

0,5

10
0,7 0,8 0,9

Ip (kA) 1

HNC... upto 50kA HEC... upto 70kA

0.1 0,1 1 Icc (kA) 10 100

48

Technical modifications reserved

MCCBs h250
Dimensions MCCBs

125,5 A (mm) 3P 105 140

165 144

PUSH TO TRIP

35

35

96

Accessories Terminal covers for extended straight connections A 89 A (mm) 55 3P 4P 105 140

Terminal cover for rear connections 7,5 A 96 A (mm) 3P 4P 170 105 140

275

Technical modifications reserved

45 102

4P

49

MCCBs h250
Connection Extended straight and spreader connections
48,5 48,5 23 23 11 120

P
29,5

6 5

12,7 Nm

Connection with end lugs

22

6 5

12,7 Nm

Connection by collar

20 max.

19 Nm min.

35 mm2

max. 120 mm2 max. 120 mm2

min. 35 mm2 5 19 Nm

50

Technical modifications reserved

MCCBs h250
Rear connections

4P 3P 35 35 35 10 15 56

144

11,8 Nm

Accessories Direct rotary handle C 193 97 C (mm) 3P 4P 102 72 102 105 140

Technical modifications reserved

10

91

51

MCCBs h250
Extended rotary handle 44 19,5 (3 P) 105 (4 P) 140 171

101,8

21,5 358

Motor operator
90 205

Rated operating voltage Operating current (A) Starting current (A) Operating method Operating time (s) Operating switch rating Power supply required Dielectric properties

24V DC 230-240V AC 24V DC 230-240V AC 24V DC 230-240V AC ON OFF RESET

155

24V DC 230-240V AC

ok ok 18 4 26 8 direct drive 0,1 0,1 0,1 100V, 0.1A, opening voltage 44V, current 4mA 300 VA minimum 1000 V AC 1500 V AC

52

Technical modifications reserved

70

MCCBs h250
Auxiliaries Auxiliaries for MCCBs and trip-free switches

1
TRIP

Mounting combination for auxiliaries and releases 4P 3P AX Auxiliary contact AX

SH Shunt trip SH

HXC 021 H HXC 025 H

AX

AL

SH / UV

AL

HXC 024 H HXC 026 H

UV UV Undervoltage release

AL Alarm contact

DUVR DUVR Delayed undervoltage release

Technical modifications reserved

53

MCCBs and trip-free switches h400-h630


Moulded case circuit breakers h400, h630 Electronic trip unit LSI: - long delay ( thermal equivalent) adjustable: Ir = 0.4 to 1 x In - short delay (magnetic equivalent) adjustable: 2.5 to 10 x Ir (400A) 2.5 to 8 x Ir (630A) - time delay: 0,1 - 0,2 s 3P & 4P (adjustable neutral 0 50% - 100%). Mechanical test button, lockable settings Connection: Directly on copper cable terminal, with end lug max. width: 30 mm Comply with IEC 60 947-2. Trip-free switches Allows tripping at distance using a voltmetrical trip unit (optional) Comply with IEC 60 947-3. AC 23A / DC 22A Add-on blocks For h630 (LSI) devices These devices are intended to be fixed at the bottom of the devices. Characteristics Fixed version: 300mA sensitivity and instantaneous tripping Adjustable version: sensitivity from 30mA to 6A, tripping from instantaneous to 1s delay. Test button for differential functioning check. Mechanical test button. LED or remote signal for tripping or advance warning (25-50% l n). Type A (for fault component DC pulsating current) and HI (reinforced immunity against unexpected tripping). Comply with IEC 60 947-2.

Designation

In

Cat. ref. 3P 4P

MCCBs h630 50kA LSI

breaking capacity Icu : 50 kA (400/415 V AC) Ics: 50 kA

250A 400A 630A

HND250H HND251H HND400H HND401H HND630H HND631H

HND630H MCCBs h630 70kA LSI breaking capacity Icu : 70 kA (400/415 V AC) Ics: 50 kA 250A 400A 630A HED250H HED400H HED630H HED251H HED401H HED631H

Trip-free switches

suitable for AC 22A / AC 23A Ue: 415 V AC Icw (0,3s) = 5kA

400A 630A

HCD400H HCD401H HCD630H HCD631H

Add-on blocks (only for h630)

adjustable sensitivity l n: 0,03 - 0,1 - 0,3 - 1 - 3 - 6A adjustable tripping instantaneous time delay: 0,06s - 0,15s - 0,3s - 0,5s - 1s

400A 500A

HBD401H HBD631H

HBD401H 54 Technical modifications reserved

Accessories for MCCBs and trip-free switches h400-h630


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or close. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75 mm2 flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Designation Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle.

Characteristics

Cat. ref.

Auxiliary contacts AX AL

1 changeover contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC

HXC021H

HXC024H

HXC021H

HXC024H

low level contact (ON/OFF) 125 V AC 1 NO + 1 NC low level alarm contact 125 V AC 1 NO + 1 NC

HXC025H

HXC026H

Shunt trips SH

24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXC001H HXC002H HXC003H HXC004H HXC005H

HXC004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXC011H HXC013H HXC014H HXC015H

HXC014H Delayed undervoltage releases DUVR Characteristics 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC Cat. ref. 3P HXC051H HXC053H HXC054H HXC055H

4P HXD051H HXD053H HXD054H HXD055H

Technical modifications reserved

55

Accessories for MCCBs and trip-free switches h400-h630


Designation Characteristics Cat. ref.

Direct rotary handle

padlockable handle max 6 mm

HXD030H

HXD030H Extended rotary handle padlockable handle max 8 mm HXD031H

Padlock

to mount on MCCBs for handle locking for 3 padlock 5 - 8 mm2 max

HXD039H

HXD039H Motor operators 24-48 V DC 100-240 V AC HXD040H HXD042H HXD040H HXD042H

HXD042H Interlocking wire type HXD065H HXD065H

56

Technical modifications reserved

Accessories for MCCBs and trip-free switches h400-h630


Designation Characteristics In Cat. ref. 3P Collar terminals set of 3 or 4 terminals for copper conductors 240 mm2 set of 3 or 4 terminals for aluminium conductors 1 x 35 - 240 mm2 set of 3 or 4 terminals for multiple aluminium conductors 2 x 35 - 240 mm2 250 - 400A HYD003H 4P HYD004H

250 - 400 630A

HYD005H

HYD006H

HYD003H

250 - 400 630A

HYD007H

HYD008H

HYD006H

HYD008H

HYD010H Extended connections set of 4 pieces for straight connections spreader connections 250 - 400A 630A 250 - 400A 630A HYD010H HYD013H HYD011H HYD014H HYD010H HYD013H HYD012H HYD015H

HYD015H Terminal covers for extended straight connections for extended spreader connections for rear connections for collar terminals HYD021H HYD023H HYD025H HYD027H HYD022H HYD024H HYD026H HYD028H

HYD022H

Technical modifications reserved

57

Accessories for MCCBs and trip-free switches h400-h630


Designation Characteristics In Cat. ref. 3P Rear connections 250 - 400A 630A HYD031H HYD033H 4P HYD032H HYD034H

HYD033H

Connecting kit

0,75 mm2 set of 3 x 2 wires length: 1,30m

HYA035H

HYA035H

Designation

Characteristics

Cat. ref.

Ring lugs

compact lugs 120 mm2 10 compact lugs 150 mm2 10,5 compact lugs 185 mm2 10,5 compact lugs 185 mm2 12,8 suitable with spreader compact lugs 240 mm2 12,8 suitable with spreader

HYD093H HYD095H HYD096H HYD097H HYD098H

58

Technical modifications reserved

MCCBs, trip-free switches h400 - h630


MCCBs

220/240 V AC (kA) Icu Ics Icu Ics Icm Icw 85 85 100 85 _ _

380/415 V AC (kA) 50 50 70 50 9 5 kA-0,3 s

660/690 V AC (kA) 20 15 20 15 _ _

H400/H630 HND H630 HED H630 HCD

Settings

B A

Magnetic and thermal settings


TM 400 A
0,63 0,8 1 6 12 8 10

Ir (x In)

Ii (x In)

Thermal adjustment from 0,63 to 1 x In Magnetic adjustment from 6 to 12 x In

Technical modifications reserved

59

MCCBs, trip-free switches h400 - h630


Electronic trip unit setting (LSI) L - Long delay - protection against overloads: Ir and tr settings S - Short delay - protection against short circuits: Isd and tsd settings I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short circuit: 2,5 to 10 x Ir (250 - 400A) and 2,5 to 8 x Ir (630A).

LSI 250/400/630 A

1
Ir (A)
0,8 0,63 0,5 0,4 0,85 0,9 0,95 1 ON 1xIR 3 2 4 5 6 7 1

2 B
Characteristics

Neutral settings:

Long delay current Ir setting Other curve characteristics setting (tr, Isd, tsd) Neutral protection against overloads setting

NP

PICK UP

OFF 0,5xIR

TEST IN

In A
Ir ajustable

250 A / 400 A
7 6 5 4 1 2 5,6,7 3

630 A Inst Long Time Delay Short Time Delay Inst

LSI

Long Time Delay Ir (x In) tr (s)

Short Time Delay isd (xlr)

tsd (s) li (xlr) Ir (x In) tr (s) OK OK OK OK OK OK OK OK

isd (xlr) tsd (s) li (xlr)

0.2S 0.1S

Ir (x In)
1,2
2.5 5

0,4 0,5 0,63 0,8

OK OK OK OK _ OK OK OK 11s at 2 xlr 21s at 2 xlr 5 5 s at 6 xlr 10 s at 6 xlr 19 s at 6 xlr 29 s at 6 xlr 10 0,2 2,5 0,1 14 (max 13 x In)

0,85
10 14 x Ir
I

0,9 0,95 1

Characteristics

1 2 3 4 5 6 7

11s at 2 xlr 21s at 2 xlr

2,5

0,1

5 5 s at 6 xlr 10 s at 6 xlr 16 s at 6 xlr _ _ 8 0,2

14 (max 10 x In)

Neutral protection

0% 50% 100%

(*) Characteristic 1 : use for generators protection. Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

60

Technical modifications reserved

MCCBs, trip-free switches h400 - h630


Tripping curve MCCB h630 LSI (250A and 400A) 10000

1000 Temps de dclenchement (s) Tripping time (s)

100

10

6 7

1
5, 6

0.1
1, 2, 3, 4

0.01 100 1000 10000 %Ir

Electronic trip unit setting (LSI) MCCB h630 LSI (250A and 400A) IR (A) LTD Pick-up current Characteristics Standard LTD tR IR xIn 0,4 0,5 2 21 0,63 3 21 0,8 4 5 600% x I R 5 10 0,2 0,9 5 10 0,95 6 19 1 7 29

No. 1 (s) 11 200% x I R STD Isd tsd INST Ii IN tN xIR (s) xIR xIn (s) 2,5 0,1

14 (max : 13 x In) 0 - 0,5 - 1 tN=tR

Optional

Technical modifications reserved

61

MCCBs, trip-free switches h400 - h630


Tripping curve MCCB h630 LSI (630A electronic) 10000

1000
Tripping time (s) Temps de dclenchement (s)

100

10

1 2

1
5, 6

0.1
1, 2, 3, 4

0.01 100 1000 10000 %Ir

Electronic trip unit setting (LSI) MCCB h630 LSI (630A electronic) IR (A) LTD Pick-up current Characteristics Standard LTD tR IR xIn 0,4 0,5 2 21 0,63 3 21 0,8 4 5 600% x I R 5 8 0,2 0,85 5 10 0,9 6 16 0,95 1

No. 1 (s) 11 200% x I R STD Isd tsd INST Ii IN tN xIR (s) xIR xIn (s) 2,5 0,1

14 (max : 13 x In) 0 - 0,5 - 1 tN=tR

Optional

62

Technical modifications reserved

MCCBs, trip-free switches h400 - h630


Thermal constraint curve (Let-through energy) MCCB h400 TM (400A)

108

107

I2t (x A2 s)

106

105

HHD... upto 25kA HND... upto 50kA

104

103 1 10

102
(kA)

103

104

105

MCCB h630LSI (250A and 400A) 102

MCCB h630 LSI (630A) 102

101

101

I2t (x 106 A2 s)

1
HND... upto 50kA HED... upto 70kA

I2t (x 106 A2 s) 1
HND... upto 50kA HED... upto 70kA

0,1 0,1 1
(kA)

0,1 101 102 0,1 1


(kA)

101

102

Technical modifications reserved

63

MCCBs, trip-free switches h400 - h630


Current limiting curve (Let-through peak current) MCCB h630 LSI (250A and 400A) MCCB h400 TM 100
0,25

MCCB h630 LSI (630A)

100
0,25

0,3

0,3

0,5

0,5

10
0,7 0,8 0,9

10
0,7 0,8 0,9

Ip (kA)

HHD... upto 25kA HND... upto 50kA HED... upto 70kA

Ip (kA)

1
HND... upto 50kA HED... upto 70kA

0.1 0,1 1 Icc (kA) 10 100

0.1 0,1 1 Icc (kA) 10 100

64

Technical modifications reserved

MCCBs, trip-free switches h400 - h630


Dimensions MCCBs
A 145

A (mm) 3P 4P
260 228 90

B (mm) 45 45

C (mm) 214 214

140 185

45

45

97

Terminal covers for extended straight connections A D C

Terminal covers for extended spreader connections A C

480

A (mm) 3P 4P 140 185

B (mm) 85 85

C (mm) 97 97

D (mm) 94,5 94,5 3P 4P

A (mm) 180 240

B (mm) 110 114

C (mm) 97 98

Terminal covers for rear connections and collar terminal


A C D

A (mm) 3P 4P 140 185

B (mm) 3 3

B (mm) 4,5 4,5

C (mm) 97 97

D (mm) 93 93

B' B

Technical modifications reserved

65

MCCBs, trip-free switches h400 - h630


Connection Cable connection (h400 TM 250 - 400A, h630 LSI 250 - 400A) max. 240 mm2 58
25 maxi.

25 Nm

13 7,0-9,5 Nm 7,0 - 9,5 Nm

Extended straight and spreader connections 148 60 3P 60 30 4P 30 163 45

14 30

14 349

30

4P 60 60 208 60 85 22,5 Nm

Rear connections 4P 3P 45 45 45 15 55 (250-400A) 45 15 (630A)

15

228

115 (250-400 A) 95 (630 A)

66

30

Technical modifications reserved

MCCBs, trip-free switches h400 - h630


Connection with end lugs

2
12 max.

M 10

30 max.

85

22,5 Nm

Accessories Direct rotary handle 140 200 103 Extended rotary handle 140 180,5 44 19,5

241,5 127

27

x+46,5

Motor operator 139,5 220 123


Rated operating voltage Operating current (A) Starting current (A) 24-48V DC 100-240V AC 24-48V DC 100-240V AC 24-48V DC 100-240V AC ON OFF RESET ok ok 4,3 0,9 9,8 3,8 spring charging 0,1 1,5 1,5 100V, 0.1A, opening voltage 48V, current 1mA 300 VA minimum 24-48V DC 100-240V AC 1000 V AC 1500 V AC

244 160

Operating method Operating time (s) Operating switch rating Power supply required Dielectric properties

Technical modifications reserved

67

125

MCCBs, trip-free switches h400 - h630


Auxiliaries Auxiliaries for MCCBs and free tripping switches

TRIP

Mounting combination for auxiliaries and releases

t e
AX Auxiliary contact
X

SH Shunt trip SH

AX

AL

SH / UV

AL Alarm contact

UV UV Undervoltage release

DUVR DUVR Delayed undervoltage release

68

Technical modifications reserved

Add-on block h630


Characteristics
Reset button : Signals add-on block tripping and must be acknowledged before switching on the installation. Test button for differential functioning : Allows to check the electrical operating of the MCCB / Add-on block association. Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on block association. LED signaling default current level in the installation: 25% (orange) and 50% (red) In; green light to signal correct operating. When associated with MCCB, the add-on block provides an earth fault protection and protects against electrical shocks by direct or indirect contacts. The add-on blocks are protected against nuisance tripping caused by transient voltages. Its able to detect sinusoidal alternating currents and residual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity). Remote tripping and advanced warning (50% In) signaling thanks to these contacts:
V

Earth leakage current (In) and delay (t) setting

Add-on block operating

N
0,1 0,03
0,3 1

incoming L1 L2 L3

0,3 1

6 I n (A)

0,1 0,03

10 I n (A)

0,06 Inst.

0,15 0,3

0,5 1 t (s)

0,15 0,3 0,06 0,5 Inst. 1 t (s)

CA 50% ON electronic 125A 250A test button N L1 L2 L3 outgoing

A (In) 0,03 Inst. S (t) 0,06 0,15 0,3 0,5 1 OK no no no no no 0,1 OK OK OK OK OK OK 0,3 OK OK OK OK OK OK 1 OK OK OK OK OK OK 3 OK OK OK OK OK OK 6 OK OK OK OK OK OK

Technical modifications reserved

69

Add-on block h630


Add-on block mounting

ON

ON

8 22,5 Nm

Association / Compatibility 250 - 400A HBD401H 400A 630A x 0,8 HBD631H 500A (Ie: 630A x 0,8)

5 mm

Dimensions

16

45

45 185

45

97 120,5

70

Technical modifications reserved

45 119,5

MCCBs and trip-free switches h1000


Moulded case circuit breakers h1000 Electronic trip unit LSI: - long delay (thermal equivalent) adjustable: Ir= 0,4 to 1 x In - short delay (magnetic equivalent) adjustable: 2,5 to 10 x Ir (630-800A) and 2,5 to 8 x Ir (1000A) - time delay: 0,1-0,2 s 3P & 4P (adjustable neutral 0 - 50% - 100%). Mechanical test button, lockable settings. Connection: Directly on copper cable terminal, with end lug max. width: 50 mm Comply with IEC 60 947-2. Trip-free switches Allows tripping at distance using a voltmetrical trip unit (optional) Comply with IEC 60 947-3. AC 23A / DC 22A

Designation

Designation

In

Cat. ref. 3P 4P HNE801H HNE971H

MCCBs h1000 50kA LSI

breaking capacity Icu : 50 kA (400/415 V AC) Ics: 50 kA

800A 1000A

HNE800H HNE970H

HNE970H MCCBs h1000 70kA LSI breaking capacity Icu : 70 kA (400/415 V AC) Ics: 50 kA 800A 1000A HEE800H HEE970H HEE801H HEE971H

Trip-free switches

suitable for AC 22A / AC 23A Ue : 415 V AC Icw (0,3 s) = 10 kA

800A 1000A

HCE800H HCE970H

HCE801H HCE971H

Technical modifications reserved

71

Accessories for MCCBs and trip-free switches h1000


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or close. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75 mm2 flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un

Designation

Characteristics

Cat. ref.

Auxiliary contacts AX AL

1 changeover contact (ON/OFF) 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC

HXC021H

HXC024H

HXC021H

HXC024H

Low level contact (ON/OFF) 125 V AC 1 NO + 1 NC Low level alarm contact 125 V AC 1 NO + 1 NC Shunt trips SH 24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXA025H

HXA026H

HXC001H HXC002H HXC003H HXC004H HXC005H

HXC004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXC011H HXC013H HXC014H HXC015H

HXC014H

72

Technical modifications reserved

Accessories for MCCBs and trip-free switches h1000


Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle.

Designation

Characteristics

In

Cat. ref. 3P 4P HXE051H HXE053H HXE054H HXE055H

Delayed undervoltage releases DUVR

24 V DC 110 - 120 V AC 220 - 240 V AC 380 - 415 V AC

HXE051H HXE053H HXE054H HXE055H

Collar terminals

set of 3 or 4 terminals for 630-800A conductors 4 x 35 - 240 mm2

HYE007H

HYE008H

Connecting kits

0,75 mm2 set of 3 x 2 wires length: 1,30m

HYA035H

HYA035H

Terminal covers

for extended connections for rear connections

HYE021H HYE025H

HYE022H HYE026H

Rear connections

630-800A 1000A

HYE031H HYE033H

HYE032H HYE034H

HYE031H

Technical modifications reserved

73

Accessories for MCCBs and trip-free switches h1000


Designation Characteristics Cat. ref.

Direct rotary handles

padlockable handle

HXE030H

Extended rotary handles

padlockable handle

HXE031H

Padlocks

to mount on MCCB for handle locking for 3 padlock max 8 mm

HXD039H

HXD039H Motor operators


24 - 48V DC 100 - 240V AC

HXE040H HXE042H

Interlocking

wire type

HXE065H

74

Technical modifications reserved

MCCBs, trip-free switches h1000


MCCBs

220/240 V AC (kA) Icu HNE Ics Icu HEE Ics 85 (630-800A), 75 (1000A) 85 (630-800A), 75 (1000A) 100

380/415 V AC (kA) 50 50 70

660/690 V AC (kA) 20 20 20 20 _

100 (630-800A), 75 (1000A) 50 17

Icm _ HCE Icw _

10 kA-0,3 s _

Electronic trip unit settings (LSI)

Ir (A)
0,8 0,63 0,5 0,4 0,85 0,9 0,95 1

Characteristics
4 3 2 5 6 7

NP
ON 1xIR

PICK UP

OFF 0,5xIR

TEST IN

L - Long delay - protection against overloads: Ir and tr settings S - Short delay - protection against short circuits: Isd and tsd settings I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short circuit: 2,5 to 10 x Ir (630-800A) and 2,5 to 8 x Ir (1000A).
Ir ajustable 1
T

In A 630-800 A 1000 A Inst Long Time Delay Short Time Delay isd (xlr) tsd (s) Inst li (xlr)

7 6 5 4 1 2 5,6,7 0,2S 0,1S 3

LSI
2

Long Time Delay Ir (x In) tr (s)

Short Time Delay isd (xlr) tsd (s)

li (xlr) Ir (x In) tr (s) OK OK OK OK OK OK OK

Ir (x In)
1,2 2,5 3 4

0,4 0,5 0,63 0,8

OK OK OK OK OK OK OK 11s at 2 xlr 21s at 2 xlr 5 5 s at 6 xlr 10 s at 6 xlr 19 s at 6 xlr 29 s at 6 xlr 10 0,2 2,5 0,1 14 (max 12 x In)

5 10 14

x Ir

0,9 0,95 1 1 2

11s at 2 xlr 21s at 2 xlr

2,5

0,1

Characteristics* 3 4 5 6 7 Neutral protection 0% 50% 100%

5 5 s at 6 xlr 10 s at 6 xlr 16 s at 6 xlr _ _ 8 0,2

14 (max 10 x In)

(*) Characteristic 1 : use for generators protection. Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

Technical modifications reserved

75

MCCBs, trip-free switches h1000


Tripping curve MCCB h1000 LSI (630-800A)

Electronic trip unit setting (LSI) MCCBs 630-800A electronic IR (A) LTD Pick-up current Characteristics Standard LTD tR IR xIn 0,4 0,5 2 21 0,63 3 21 0,8 4 5 600% x I R 5 10 0,2 0,9 5 10 0,95 6 19 1 7 29

No. 1 (s) 11 200% x I R STD Isd tsd INST Ii IN tN xIR (s) xIR xIR (s) 2,5 0,1

14 (max : 12 x In) 0,5 or 1 or NON (IN x 105% NT, IN x 120% T) IN=tR

Optional

NP

76

Technical modifications reserved

MCCBs, trip-free switches h1000


Tripping curve MCCB h1000 LSI (1000A)

Electronic trip unit setting (LSI) MCCBs 1000A electronic

IR (A) LTD Pick-up current Characteristics Standard LTD tR IR xIn 0,4 0,5 2 21 0,63 3 21 0,8 4 5 600% x I R 5 8 0,2 0,9 5 10 0,95 6 16 1

No. 1 (s) 11 200% x I R STD Isd tsd INST Ii IN tN xIR (s) xIR xIn (s) 2,5 0,1

14 (max : 10 x In) 0,8 IN=tR

Optional

NP

Technical modifications reserved

77

MCCBs, trip-free switches h1000


Thermal constraint curve (Let-through energy) MCCB h1000

Current limiting curve (Let-through peak current) MCCB h1000

78

Technical modifications reserved

MCCBs, trip-free switches h1000


Dimensions MCCBs
A B 145

A (mm) 3P 4P 210 280

B (mm) 180 250

D (mm) 243 243

243 331 403

433 273

40

70

35

10 99,5

Terminal covers for extended straight connections A C A (mm) 3P 4P B 215 285 B (mm) 130 130 C (mm) 99,5 99,5

534

Technical modifications reserved

90

79

MCCBs, trip-free switches h1000


Terminal covers for rear connections A B C A (mm) 3P 4P 210 280 B (mm) 14 18 C (mm) 101 99

Connection Extended straight connections

1
13 36

2
19 5 65,7 Nm

40

Direct cable connection on terminal Copper with conductor max. width: 50 mm

80

Technical modifications reserved

MCCBs, trip-free switches h1000


Rear connections

630-800A: vertical or horizontal position. 90 1000A: vertical only.

800 A 1000 A

10

60

10

60

10

12

58

12

58

12

122

20 36 288 (1000 A) 285 (800 A) 243

13

Connection with end lugs

Technical modifications reserved

81

MCCBs, trip-free switches h1000


Accessories Direct rotary handle 120 200 103

Extended rotary handle 120 115115 92 19,5 180,5 45

127 127

27 322

Motor operator 115 115 140 213 113,5


Rated operating voltage Operating method Power supply required 24-48V DC 100-240V AC ok ok spring charging 300 VA minimum 1000 V AC 1500 V AC

160

125

Dielectric properties

24-48V DC 100-240V AC

82

Technical modifications reserved

MCCBs, trip-free switches h1000


Auxiliaries Auxiliaries for MCCBs and free tripping switches

2 1
TRIP

Mounting combination for auxiliaries and releases


4P 3P

X AX Auxiliary contact HXC 021 H HXC 025 H

SH Shunt trip SH

AX

AL

SH / UV

AL Alarm contact

HXC 024 H HXC 026 H

UV UV Undervoltage release

DUVR DUVR Delayed undervoltage release

Technical modifications reserved

83

MCCBs and trip-free switches h1600


Moulded case circuit breakers h1600, selection and protection Electronic trip unit LSI - Long delay (thermal equivalent) adjustable: Ir = 0,4 to 1 x In - short delay (magnetic equivalent) adjustable: 2,5 to 10 x Ir - time delay: 0,1-0,2 s 3 pole, 3 trip units, 4 pole, 4 trip units, adjustable neutral 0 - 50% 100% Mechanical test button, lockable settings. Connection: Directly on copper cable terminal, with end lug max. width: 60 mm Comply with IEC 60 947-2. Trip-free switches Allows tripping at distance using a voltmetrical trip unit (optional) Comply with IEC 60 947-3.
AC 23A / DC 22A

Designation

Designation

In

Cat. ref. 3P 4P HNF981H HNF991H

MCCBs h1600 50kA LSI

breaking capacity Icu : 50 kA (400/415 V AC) Ics: 50 kA

1250A 1600A

HNF980H HNF990H

HNF990H MCCBs h1600 70kA LSI breaking capacity Icu : 70 kA (400/415 V AC) Ics: 50 kA 1250A 1600A HEF980H HEF990H HEF981H HEF991H

Trip-free switches

suitable for AC 22A / AC 23A Ue : 415 V AC Icw (0,3 s) = 20 kA

1250A 1600A

HCF980H HCF990H

HCF981H HCF991H

84

Technical modifications reserved

Accessories for MCCBs and trip-free switches h1600


Indication contacts - 1 changeover switch (ON/OFF): indicates the position of the MCCB is open or close. - 1 changeover alarm contact: indicates MCCB tripping. Coil connection Connection capacity: 0,75 mm2 flexible or rigid cables Optional connection cables. The cable capacity of the terminals is 0,5 to 1,25 mm2. Designation Shunt trip Remotes tripping of MCCBs or trip-free switches. Operating voltage: 0,7 to 1,1 x Un Under voltage release Allows the tripping of MCCBs or trip-free switches when voltage level drop between 35 and 70% of Un. Pick up voltage 0,85 x Un Direct rotary handle - padlockable - equipped with front cover and handle - fixing without any additional screw. Extended rotary handle - IP 55 - supplied complete with shaft and handle. Rear connection: included Characteristics Cat. ref.

Auxiliary contacts AX AL

1 changeover contact (ON/OFF) 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC 1 changeover alarm contact 250 V AC / 3A 125 V DC / 0,4A 1 NO + 1 NC

HXC021H

HXC024H

HXC021H

HXC024H

Low level contact (ON/OFF) 125 V AC 1 NO + 1 NC Low level alarm contact 125 V AC 1 NO + 1 NC Shunt trips SH 24 V DC 48 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC

HXA025H

HXA026H

HXC001H HXC002H HXC003H HXC004H HXC005H

HXC004H Undervoltage releases UV 24 V DC 100 - 120 V AC 200 - 240 V AC 380 - 450 V AC HXC011H HXC013H HXC014H HXC015H

HXC014H

Technical modifications reserved

85

Headline 1 Headline 2
Undervoltage releases UV 24 V DC 110 - 120 V AC 220 - 240 V AC 380 - 415 V AC HXE011H HXE013H HXE014H HXE015H

Direct rotary handle

padlockable handle, max 8 mm

HXF030H

Extended rotary handle

padlockable handle, max 8 mm

HXF031H

Padlock

to mount on MCCB for handle locking for 3 padlock max 8 mm

HXF039H

Motor operators

24 V DC 200 - 230 V AC

HXF040H HXF042H

86

Technical modifications reserved

Headline 1 Headline 2
Interphase barriers 3/4 P HYF019H

Connection kit

0,75 mm2 set of 3 x 2 wires length: 1,30m

HYA035H

Delayed undervoltage releases DUVR

24 V DC 110 - 120 V AC 220 - 240 V AC 380 - 415 V AC

HXF051H HXF053H HXF054H HXF055H

Technical modifications reserved

87

MCCBs, trip-free switches h1600


MCCBs

220/240 V AC (kA) Icu HNF Ics Icu HEF Ics Icm HCF Icw 100 75 100 75

380/415 V AC (kA) 50 50 70 50 45 kA 20 kA-0,3 s

660/690 V AC (kA) 25 25 45 34

Electronic trip unit settings (LSI)

Ir (A)
0,8 0,63 0,5 0,4 0,9 0,95 1

Characteristics
4 3 2 1 5 6 7

ON

PICK UP
OFF

TEST IN

L - Long delay - protection against overloads: Ir and tr settings S - Short delay - protection against short circuits: Isd and tsd settings I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short circuit: 2,5 to 10 x Ir.
In A 1250 - 1600 A LSI Long Time Delay Ir (x In) Ir (x In) 0,4 0,5 0,63 0,8 0,9 0,95 1 Characteristics* 1 2 3 4 5 6 5 s at 6 xlr 10 s at 6 xlr 19 s at 6 xlr 29 s at 6 xlr OK OK OK OK OK OK OK 11s at 2 xlr 21s at 2 xlr 5 10 0,2 2,5 0,1 14 (max 12 x In) tr (s) Short Time Delay isd (xlr) tsd (s) Inst li (xlr)

Ir(A) LSI

Im

N 0% 50% 100 %

7 Neutral protection 0% 50% 100%

0,4 - 1 2,5 In 10 Ir

(*) Characteristic 1 : use for generators protection. Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products. Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.

88

Technical modifications reserved

MCCBs, trip-free switches h1600


Tripping curve MCCB h1600 LSI
4 3

hour minute

1 50 40 30 20

10 8 6 5 4 3 2

5 6 7

1 50 40 30 20

10 8 6 5 4 3

1 2

time second

3 4 5,6,7

1 0.8 0.6 0.5 0.4 0.3 0.2

0.1 0.08 0.06 0.05 0.04 0.03 0.02

1,2,3,4

0.01

1500

3000

2000

4000

5000

IR [%]

Electronic trip unit setting (LSI) MCCBs 1250A and 1600A electronic IR (A) LTD Pick-up current Characteristics Standard LTD tR IR xIn 0,4 0,5 2 21 0,63 3 21 0,8 4 5 600% x I R 5 10 0,2 0,9 5 10 0,95 6 19 1 7 29

No. 1 (s) 11 200% x I R STD Isd tsd INST Ii IN tN xIR (s) xIR xIR (s) 2,5 0,1

14 (max : 12 x In) 0,5 or 1 or NON (IN x 105% NT, IN x 120% T) IN=tR

Optional

NP

Technical modifications reserved

6000

7000 8000

700 800 900 1000

2500

80 90 100

125

150

200

250

500

600

0.005

89

MCCBs, trip-free switches h1600


Thermal constraint curve (Let-through energy) MCCB h1600 1010

109

I2t (x 106 A2 s)

HNF... upto 50kA HEF... upto 70kA

108

107 102 103 104 105

Current limiting curve (Let-through peak current) Max. L et-thr ough peak cur r ent 3 MCCB h1600 TYPE h1600
1000

100

Max. Let- through peak current (kA)

10

HNEup to 50kA HEEup to 70kA


1

0.1 1

10

100

1000

Prospective short- circuit current in RMS sym. (kA)

90

Technical modifications reserved

MCCBs, trip-free switches h1600


Dimensions MCCBs
A B 11

191

A (mm) 3P 4P 210 280

B (mm) 185 255

570 370

476 541

44,5

70

46

20 140

Connection Connection with end lugs

95

65 19 Nm 5

65,7 Nm

Technical modifications reserved

91

MCCBs, trip-free switches h1600


Accessories Direct rotary handle Extended rotary handle

115 140

268 136

115 140

257

45 19,5

165

165

27 322

Motor operator

210

260,5 130

173,5

Rated operating voltage

24V DC

ok

200-230V AC ok

Operating current (A) 200-230V AC 1 Starting current (A) Operating method ON Operating time (s) OFF RESET Power supply required Dielectric properties 24V DC 200-230V AC 3,2 spring charging 0,06 3 3 300 VA minimum 500 V AC

200-230V AC 1500 V AC

92

Technical modifications reserved

125

MCCBs, trip-free switches h1600


Auxiliaries Auxiliaries for MCCBs and free tripping switches

TRIP

Mounting combination for auxiliaries and releases


4P 3P

AX Auxiliary contact AX
HXC 021 H HXC 025 H

SH Shunt trip SH

AX

AL

AL Alarm contact

AL

HXC 024 H HXC 026 H


SH / UV

UV UV Undervoltage release

DUVR DUVR Delayed undervoltage release

Technical modifications reserved

93

Cascading according to CEI 60947-2 MCCBs x160, x250, h250, h630, h1000, h1600
Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 380V - 415V AC
Upstream x160 TM HDA 18 kA HDA x160 TM HHA HNA x250 TM HHB HNB HHG h250 TM Downstream HNG HEG h250 LSI HNC HEC HHD HND HND HED HNE HEE HNF HEF 18 kA 25 kA 40 kA 25 kA 40 kA 25 kA 50 kA 65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA HHA 25 kA 25 kA 30 kA HNA 40 kA 40 kA 40 kA 40 kA x250 TM HHB 25 kA 25 kA 30 kA 25 kA HNB 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA h250 TM HHG 25 kA 25 kA 25 kA 25 kA 25 kA HNG 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA -

h400 TM

h630 LSI

h1000 LSI

h1600 LSI

Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 220V - 240V AC
Upstream x160 TM HDA 25 kA HDA x160 TM HHA HNA x250 TM HHB HNB HHG h250 TM Downstream HNG HEG h250 LSI HNC HEC HHD HND HND HED HNE HEE HNF HEF 25 kA 35 kA 85 kA 35 kA 85 kA 35 kA 85 kA 85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA HHA 35 kA 35 kA 50 kA HNA 85 kA 85 kA 85 kA 85 kA x250 TM HHB 35 kA 35 kA 50 kA 35 kA HNB 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA h250 TM HHG 35 kA 35 kA 35 kA 35 kA 35 kA HNG 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA -

h400 TM

h630 LSI

h1000 LSI

h1600 LSI

94

Technical modifications reserved

h250 LSI HEG 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA 65 kA HNC 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA HEC 70 kA 40 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA -

h400 TM HHD 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA HND 50 kA 30 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA -

h630 LSI HND 50 kA 30 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA HED 70 kA 40 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA 70 kA 70 kA 70 kA 50 kA 70 kA 70 kA 70 kA -

h1000 LSI HNE 50 kA 30 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA HEE 70 kA 40 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA -

h1600 LSI HNF 50 kA 30 kA 50 kA 50 kA 50 kA 50 kA 25 kA 50 kA 50 kA 25 kA 50 kA 50 kA 50 kA 50 kA HEF 70 kA 40 kA 50 kA 50 kA 50 kA 50 kA 25 kA 70 kA 70 kA 70 kA 70 kA 25 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA 70 kA

h250 LSI HEG 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA HNC 85 kA 50 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA HEC 100 kA 85 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA -

h400 TM HHD 35 kA 35 kA 35 kA 35 kA 35 kA 35 kA 35 kA 35 kA HND 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA -

h630 LSI HND 85 kA 50 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA HED 100 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA -

h1000 LSI HNE 85 kA 50 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA HEE 100 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA -

h1600 LSI HNF 85 kA 50 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA HEF 100 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA

Technical modifications reserved

95

Cascading MCCBs / MCBs


Cascading MCCBs / MCBs
Range Breaking capacity IEC 60898 / 61009-1 Breaking capacity IEC 60947-2 Curve Ax8xx Ax9xx AC1xx, AD1xx, AE1xx, AF1xx, ACx1xx, ADx1xx, AEx1xx MV, MW MU, MT, MV NB, NC, ND MHN, MJN MLN MBN, MCN MB, MC, NGN NBN, NCN, NDN 4,5 kA 6 kA 6 kA 10 kA 3 kA 6 kA 10 kA 4,5 kA 6 kA 6 kA 6 kA 10 kA NQN, NRN, NSN MMN 2xx, MMN 3xx MMN 2xx, MMN 3xx HLE, HLF, HLS HMB, HMC, HMD HMJ, HMK HMX 6 kA 10 kA 10 kA 20 kA 30 kA 6 kA 7,5 kA 20 kA 30 kA 50 kA 40 kA 30 kA 50 kA 40 kA 20 kA 30 kA 60 kA 100 kA B, C B, C B, C B, C B, C B, C B, C, D B, C B, C B, C B, C, D B, C, D B, C, D B, C, D B, C, D magn. magn. B, C B, C, D B, C C

1PP+N / 2PP

230V - 240 V

IEC 947-2
x160 TM HDA 25 KA 10 kA 15 kA 25 kA 20 kA 25 kA 10 kA 15 kA 25 kA 25 kA 25 kA HHA 35 kA 10 kA 15 kA 30 kA 35 kA 20 kA 30 kA 35 kA 10 kA 15 kA 30 kA 30 kA 35 kA 35 kA 30 kA 35 kA HNA 85 kA 10 kA 15 kA 50 kA 85 kA 30 kA 50 kA 85 kA 10 kA 15 kA 50 kA 50 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 50 kA 85 kA 85 kA x250 TM HHB 35 kA 10 kA 15 kA 30 kA 35 kA 20 kA 30 kA 35 kA 10 kA 10 kA 30 kA 30 kA 35 kA 35 kA 30 kA 35 kA HNB 85 kA 10 kA 15 kA 40 kA 50 kA 20 kA 40 kA 50 kA 10 kA 10 kA 40 kA 40 kA 50 kA 85 kA 70 kA 50 kA 85 kA 70 kA 40 kA 60 kA 85 kA h250 TM HHG 35 kA 7,5 kA 12,5 kA 30 kA 35 kA 20 kA 30 kA 35 kA 7,5 kA 10 kA 30 kA 30 kA 35 kA 35 kA 30 kA 35 kA -

Cascading MCCBs / MCBs

1PP 230V - 240 V

2PP / 3PP / 3PP+N / 4PP 400 - 415 V


x160 TM HDA HHA -

IEC 947-2
x250 TM HNA 40 kA 15 kA 30 kA 40 kA 15 kA 30 kA 30 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA 40 kA 40 kA HHB 25 kA 10 kA 20 kA 25 kA 10 kA 20 kA 20 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 25 kA HNB 40 kA 10 kA 20 kA 30 kA 10 kA 20 kA 25 kA 30 kA 40 kA 35 kA 30 kA 40 kA 35 kA 25 kA 30 kA 40 kA h250 TM HHG 25 kA 10 kA 20 kA 25 kA 10 kA 20 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 25 kA -

Range Breaking capacity IEC 60898 Breaking capacity IEC 60947-2 Curve MV, MW MU, MT, MV NB, NC, ND MVN, MWN MBN, MCN MB, MC, NGN NBN, NCN, NDN 3 kA 6 kA 10 kA 3 kA 6 kA 6 kA 10 kA NQN, NRN, NSN MMN 2xx, MMN 3xx MMN 2xx, MMN 3xx HLE, HLF, HLS HMB, HMC, HMD HMJ, HMK HMX 10 kA 15 kA 4,5 kA 10 kA 15 kA 10 kA 15 kA 25 kA 20 kA 15 kA 25 kA 30 kA 10 kA 15 kA 30 kA 50 kA B, C B, C B, C, D B, C B, C B, C, D B, C, D B, C, D B, C, D B, C, D magn. magn. B, C B, C, D B, C C

18 KA 10 kA 18 kA 18 kA 10 kA 18 kA 18 kA 18 kA 18 kA 18 kA 18 kA -

25 kA 10 kA 20 kA 25 kA 10 kA 20 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 25 kA -

96

Technical modifications reserved

h250 LSI HNG 85 kA 7,5 kA 12,5 kA 40 kA 50 kA 20 kA 40 kA 50 kA 7,5 kA 10 kA 40 kA 40 kA 50 kA 85 kA 70 kA 50 kA 85 kA 70 kA 40 kA 60 kA 85 kA HEG 85 kA 7,5 kA 12,5 kA 40 kA 50 kA 20 kA 40 kA 50 kA 7,5 kA 10 kA 40 kA 40 kA 50 kA 85 kA 70 kA 50 kA 85 kA 70 kA 40 kA 60 kA 85 kA HNC 85 kA 10 kA 15 kA 40 kA 50 kA 20 kA 40 kA 50 kA 10 kA 10 kA 40 kA 40 kA 50 kA 85 kA 70 kA 50 kA 85 kA 70 kA 40 kA 60 kA 85 kA HEC 100 kA 7,5 kA 12,5 kA 40 kA 50 kA 20 kA 40 kA 50 kA 7,5 kA 10 kA 40 kA 40 kA 50 kA 85 kA 70 kA 50 kA 85 kA 70 kA 40 kA 60 kA 85 kA -

h400 LSI HHD 35 kA 10 kA 15 kA 25 kA 35 kA 15 kA 25 kA 35 kA 10 kA 10 kA 25 kA 25 kA 35 kA 35 kA 25 kA 35 kA HND 85 kA 10 kA 15 kA 30 kA 40 kA 15 kA 30 kA 40 kA 10 kA 10 kA 30 kA 30 kA 40 kA 65 kA 50 kA 40 kA 65 kA 50 kA 30 kA 40 kA 85 kA -

h630 LSI HND 85 kA 6 kA 10 kA 30 kA 40 kA 15 kA 30 kA 40 kA 6 kA 7,5 kA 30 kA 30 kA 40 kA 65 kA 50 kA 40 kA 65 kA 50 kA 30 kA 40 kA 85 kA HED 100 kA 6 kA 10 kA 30 kA 40 kA 15 kA 30 kA 40 kA 6 kA 7,5 kA 30 kA 30 kA 40 kA 65 kA 50 kA 40 kA 65 kA 50 kA 30 kA 40 kA 85 kA 100 kA

h1000 LSI HNE 85 kA 6 kA 10 kA 20 kA 30 kA 10 kA 20 kA 30 kA 6 kA 7,5 kA 20 kA 20 kA 30 kA 50 kA 40 kA 30 kA 50 kA 40 kA 30 kA 40 kA 85 kA HEE 100 kA 6 kA 10 kA 20 kA 30 kA 10 kA 20 kA 30 kA 6 kA 7,5 kA 20 kA 20 kA 30 kA 50 kA 40 kA 30 kA 50 kA 40 kA 30 kA 40 kA 85 kA 100 kA

h1600 LSI HNF 100 kA 6 kA 10 kA 20 kA 30 kA 10 kA 20 kA 30 kA 6 kA 7,5 kA 20 kA 20 kA 30 kA 50 kA 40 kA 30 kA 50 kA 40 kA 20 kA 30 kA 60 kA 100 kA HEF 100 kA 6 kA 10 kA 20 kA 30 kA 10 kA 20 kA 30 kA 6 kA 7,5 kA 20 kA 20 kA 30 kA 50 kA 40 kA 30 kA 50 kA 40 kA 20 kA 30 kA 60 kA 100 kA

h250 LSI HNG 50 kA 10 kA 20 kA 30 kA 10 kA 20 kA 20 kA 30 kA 40 kA 35 kA 30 kA 40 kA 35 kA 25 kA 30 kA 50 kA 50 kA HEG 65 kA 10 kA 20 kA 30 kA 10 kA 20 kA 20 kA 30 kA 40 kA 35 kA 30 kA 40 kA 35 kA 25 kA 30 kA 50 kA 50 kA HNC 50 kA 10 kA 20 kA 30 kA 10 kA 20 kA 25 kA 30 kA 40 kA 35 kA 30 kA 40 kA 35 kA 25 kA 30 kA 50 kA 50 kA HEC 70 kA 10 kA 20 kA 30 kA 10 kA 20 kA 20 kA 30 kA 40 kA 35 kA 30 kA 40 kA 35 kA 25 kA 30 kA 50 kA 50 kA

h400 LSI HHD 25 kA 6 kA 15 kA 20 kA 6 kA 15 kA 20 kA 20 kA 25 kA 25 kA 20 kA 25 kA 25 kA 15 kA 20 kA HND 50 kA 6 kA 15 kA 20 kA 6 kA 15 kA 20 kA 20 kA 40 kA 25 kA 20 kA 40 kA 25 kA 15 kA 20 kA 50 kA 50 kA

h630 LSI HND 50 kA 6 kA 15 kA 20 kA 6 kA 15 kA 20 kA 20 kA 40 kA 25 kA 20 kA 40 kA 25 kA 15 kA 20 kA 50 kA 50 kA HED 70 kA 6 kA 15 kA 20 kA 6 kA 15 kA 20 kA 20 kA 40 kA 25 kA 20 kA 40 kA 25 kA 15 kA 20 kA 50 kA 50 kA

h1000 LSI HNE 50 kA 4,5 kA 10 kA 20 kA 4,5 kA 10 kA 10 kA 20 kA 30 kA 25 kA 20 kA 30 kA 25 kA 15 kA 20 kA 50 kA 50 kA HEE 70 kA 4,5 kA 10 kA 20 kA 4,5 kA 10 kA 10 kA 20 kA 30 kA 25 kA 20 kA 30 kA 25 kA 15 kA 20 kA 50 kA 50 kA

h1600 LSI HNF 50 kA 4,5 kA 10 kA 15 kA 4,5 kA 10 kA 10 kA 15 kA 25 kA 20 kA 15 kA 25 kA 20 kA 10 kA 15 kA 35 kA 50 kA HEF 70 kA 4,5 kA 10 kA 15 kA 4,5 kA 10 kA 10 kA 15 kA 25 kA 20 kA 15 kA 25 kA 20 kA 10 kA 15 kA 35 kA 50 kA

Technical modifications reserved

97

Selectivity chart
Limits (kA) x160 TM 18/25/40kA In 6A 10A B curve MHN 16A 20A 25A 32A 40A 1A 2A 6A C curve 10A 16A 20A 25A 32A 40A 6A 10A 13A MB, MU, MV 16A B curve 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A MC, MN, MW, MT 6A C curve 10A 13A 16A 20A 25A 32A 40A 50A 63A 6A 10A 13A 16A B curve MBN 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A 6A C curve MCN 10A 13A 16A 20A 25A 32A 40A 50A 63A 16A 1,6 1,4 1,5 1,5 1,3 1,1 1,4 1,2 1,3 1,3 1,3 1,1 1,1 1,1 1,1 0,95 1,05 1,05 1,05 0,9 0,9 0,9 0,8 20A 1,7 1,5 1,6 1,6 1,4 1,2 1,5 1,3 1,2 1,4 1,4 1,4 1,2 1,2 1,2 1,1 1 1,2 1,05 0,95 1,1 1,1 1,1 1 1 1 0,9 0,8 25A 1,8 1,6 1,5 1,8 1,8 1,6 1,4 1,2 1,6 1,4 1,3 1,3 1,6 1,6 1,6 1,4 1,4 1,4 1,25 1,1 1,1 1,3 1,2 1,05 1,05 1,3 1,3 1,3 1,1 1,1 1,1 1 0,9 0,9 32A 2,1 1,9 1,7 1,7 2,3 2,3 1,9 1,7 1,5 1,5 1,9 1,7 1,5 0 0 2 2 2 1,7 1,7 1,7 1,5 1,3 1,3 1,3 1,5 1,4 1,2 1,2 1,2 1,6 1,6 1,6 1,4 1,4 1,4 1,2 1,05 1,05 1,05 40A 2,6 2,3 2 2 1,9 2,9 2,9 2,3 2 1,8 1,8 1,6 2,3 2 1,8 1,8 1,8 1,7 2,5 2,5 2,5 2 2 2 1,8 1,6 1,6 1,6 1,4 1,8 1,6 1,4 1,4 1,4 1,3 2 2 2 1,6 1,6 1,6 1,4 1,3 1,3 1,3 1,1 50A 3,4 2,7 2,3 2,3 2,1 2,1 4 4 2,9 2,4 2 2 1,8 1,8 3 2,4 2,1 2,1 2,1 1,9 1,9 3,5 3,5 3,5 2,5 2,5 2,5 2,1 1,8 1,8 1,8 1,6 1,6 2,4 1,9 1,7 1,7 1,7 1,5 1,5 2,8 2,8 2,8 2 2 2 1,7 1,5 1,5 1,5 1,3 1,3 63A 4,6 3,2 2,7 2,7 2,3 2,3 1,6 T T 3,9 2,8 2,3 2,3 2 2 1,4 4 2,8 2,4 2,4 2,4 2,1 2,1 1,6 5,6 5,6 5,6 3,4 3,4 3,4 2,5 2,1 2,1 2,1 1,8 1,8 1,3 3,2 2,2 1,9 1,9 1,9 1,7 1,7 1,3 4,5 4,5 4,5 2,7 2,7 2,7 2 1,7 1,7 1,7 1,4 1,4 1,05 80A T 3,8 3,1 3,1 2,6 2,6 1,9 T T 5,5 3,4 2,7 2,7 2,2 2,2 1,7 5,5 3,4 2,8 2,8 2,8 2,3 2,3 1,7 1,4 8,8 8,8 8,8 4,8 4,8 4,8 3 2,4 2,4 2,4 2 2 1,5 1,1 4,4 2,7 2,2 2,2 2,2 1,8 1,8 1,4 1,1 T T T 3,8 3,8 3,8 2,4 1,9 1,9 1,9 1,6 1,6 1,2 1 100A T 4,5 3,6 3,6 2,8 2,8 2,1 T T T 4 3 3 2,4 2,4 1,9 6,7 4 3,2 3,2 3,2 2,5 2,5 1,9 1,5 1,5 T T T 5,8 5,8 5,8 3,5 2,7 2,7 2,7 2,2 2,2 1,7 1,5 1,5 5,4 3,2 2,6 2,6 2,6 2 2 1,5 1,5 1,5 T T T 4,6 4,6 4,6 2,8 2,1 2,1 2,1 1,8 1,8 1,5 1,5 1,5 125A T 5,5 4,1 4,1 3,2 3,2 2,4 T T T 4,9 3,6 3,6 2,9 2,9 2,2 8,6 4,9 3,7 3,7 3,7 2,9 2,9 2,2 1,8 1,5 T T T 6,8 6,8 6,8 4,3 3,2 3,2 3,2 2,6 2,6 2 1,5 1,5 T 3,9 3 3 3 2,3 2,3 1,8 1,5 1,5 T T T 5,4 5,4 5,4 3,4 2,6 2,6 2,6 2,1 2,1 1,6 1,5 1,5 160A T T 5,2 5,2 4 4 3,1 T T T T 4,6 4,6 3,6 3,6 2,8 T 6,4 4,6 4,6 4,6 3,6 3,6 2,8 2,3 1,8 T T T 8,5 8,5 8,5 5,6 4,1 4,1 4,1 3,2 3,2 2,5 2 1,6 T 5,1 3,7 3,7 3,7 2,9 2,9 2,2 1,8 1,6 T T T T T T 4,5 3,3 3,3 3,3 2,6 2,6 2 1,7 1,6 x250 TM 25/40kA 100A T 5,3 4,3 4,3 3,3 3,3 2,5 T T T 4,6 3,6 3,6 2,9 2,9 2,2 7,8 4,7 3,8 3,8 3,8 3 3 2,3 1,8 1,4 T T T 6,8 6,8 6,8 4,1 3,2 3,2 3,2 2,6 2,6 2 1,5 1,3 T 3,8 3 3 3 2,4 2,4 1,8 1,4 1,3 T T T 5,4 5,4 5,4 3,3 2,6 2,6 2,6 2,1 2,1 1,6 1,3 1,3 125A T T 5,3 5,3 4,1 4,1 3,1 T T T T 4,6 4,6 3,6 3,6 2,8 T 6,2 4,7 4,7 4,7 3,7 3,7 2,8 2,3 1,8 T T T 8,6 8,6 8,6 5,4 4,1 4,1 4,1 3,2 3,2 2,5 1,9 1,6 T 5 3,8 3,8 3,8 3 3 2,2 1,8 1,625 T T T T T T 4,3 3,3 3,3 3,3 2,6 2,6 2 1,625 1,625 160A T T T T 5,4 5,4 4,2 T T T T T T 4,8 4,8 3,7 T 8,6 6,2 6,2 6,2 4,9 4,9 3,8 3,2 2,4 T T T T T T 7,6 5,6 5,6 5,6 4,3 4,3 3,4 2,7 2,2 T T 5 5 5 3,9 3,9 3 2,6 2,1 T T T T T T T 4,5 4,5 4,5 3,4 3,4 2,7 2,2 2,1 200A T T T T T T T T T T T T T T T 5,5 T T 9,9 9,9 9,9 7,4 7,4 5,9 4,9 4,2 T T T T T T T 8,3 8,3 8,3 6,3 6,3 5 4,2 3,8 T T T T T 5,9 5,9 4,7 3,9 3,4 T T T T T T T T T T 5 5 4 3,4 3 250A T T T T T T T T T T T T T T T T T T T T T T T 9,9 8,6 7,7 T T T T T T T T T T 9,9 9,9 8,5 7,3 6,7 T T T T T T T T T T T T T T T T T T T T T T T 5,8 5,4 h250 TM 25/50/65 kA 32A 2,9 2,5 2,2 2,2 2 3 3 2,5 2,3 1,9 1,9 1,8 2,5 2,2 2 2 2 1,8 2,6 2,6 2,6 2,2 2,2 2,2 2 1,7 1,7 1,7 1,6 2 1,6 1,6 1,6 1,6 1,4 2,1 2,1 2,1 1,8 1,8 1,8 1,6 1,4 1,4 1,4 1,3 -

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs. All values are given with MCCB at the maximum setting.

MJN, MLN

98

Technical modifications reserved

h250 LSI 50/70 kA 63A 5,9 4,1 3,5 3,5 3 3 2,3 T T 5 3,6 2,9 2,9 2,4 2,4 2,3 5,2 3,6 3,1 3,1 3,1 2,7 2,7 2,1 1,7 7,3 7,3 7,3 4,4 4,4 4,4 3,2 2,6 2,6 2,6 2,2 2,2 2,1 1,3 4,2 2,9 2,5 2,5 2,5 2,2 2,2 1,7 1,4 5,8 5,8 5,8 3,5 3,5 3,5 2,6 2,1 2,1 2,1 1,8 1,8 1,7 1 100A T 5,9 4,7 4,7 3,7 3,7 2,8 T T T 5,2 3,9 3,9 3,2 3,2 2,4 8,7 5,2 4,2 4,2 4,2 3,3 3,3 2,5 2 1,6 T T T 7,5 7,5 7,5 4,6 3,5 3,5 3,5 2,9 2,9 2,2 1,7 1,3 T 4,2 3,4 3,4 3,4 2,6 2,6 2, 1,6 1,3 T T T T T T 3,7 2,8 2,8 2,8 2,3 2,3 1,8 1,4 1,3 125A T T 5,8 5,8 4,6 4,6 3,4 T T T T 5 5 4 4 3,1 T 6,9 5,2 5,2 5,2 4,1 4,1 3,1 2,5 2 T T T 9,5 9,5 9,5 6 4,5 4,5 4,5 3,6 3,6 2,8 2,1 1,6 T 5,5 4,2 4,2 4,2 3,3 3,3 2,5 2 1,625 T T T T T T 4,8 3,6 3,6 3,6 2,9 2,9 2,2 1,7 1,625 160A T T T T 6 6 4,6 T T T T T T 5,3 5,3 4,2 T 9,6 6,9 6,9 6,9 5,4 5,4 4,2 3,5 2,7 T T T T T T 8,4 6,2 6,2 6,2 4,8 4,8 3,8 3 2,4 T T 5,5 5,5 5,5 4,3 4,3 3,4 2,8 2,2 T T T T T T T 5 5 5 3,8 3,8 3 2,4 2,1 200A T T T T T T T T T T T T T T T T T T T T T 8,2 8,2 6,5 5,4 4,7 T T T T T T T 9,2 9,2 9,2 7 7 5,6 4,7 4,2 T T T T T T T 5,2 4,3 3,8 T T T T T T T T T T 5,6 5,6 4,5 3,8 3,4 250A T T T T T T T T T T T T T T T T T T T T T T T T 9,6 8,5 T T T T T T T T T T T T 9,4 8,1 7,4 T T T T T T T T T T T T T T T T T T T T T T T T 5,9 40A 3,1 2,6 2,4 2,4 2,2 3,3 3,3 2,6 2,4 2,1 2,1 1,9 2,7 2,3 2,1 2,1 2,1 2 2,9 2,9 2,9 2,3 2,3 2,3 2,1 1,9 1,9 1,9 1,7 2,2 1,8 1,7 1,7 1,7 1,6 2,3 2,3 2,3 1,8 1,8 1,8 1,7 1,5 1,5 1,5 1,4 125A T T 5,3 5,3 4,1 4,1 3,1 T T T T 4,6 4,6 3,6 3,6 2,8 T 6,2 4,7 4,7 4,7 3,7 3,7 2,8 2,3 1,8 T T T 8,6 8,6 8,6 5,4 4,1 4,1 4,1 3,2 3,2 2,5 1,9 1,75 T 5 3,8 3,8 3,8 3 3 2,2 1,8 1,75 T T T T T T 4,3 3,3 3,3 3,3 2,6 2,6 2 1,75 1,75 250A T T T T T T T T T T T T T T T T T T T T T T T 9,9 8,6 7,7 T T T T T T T T T T 9,9 9,9 8,5 7,3 6,7 T T T T T T T T T T T T T T T T T T T T T T T 5,8 5,4

h400 TM 25/50 kA 250A T T T T T T T T T T T T T T T T T T T T T T T T T 9,4 T T T T T T T T T T T T T 8,9 8,2 T T T T T T T T T T T T T T T T T T T T T T T T T 400A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h630 LSI 50/70 kA 250A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h1000 LSI 50/70 kA 630A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h1600 LSI 50/70 kA 1250A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Technical modifications reserved

99

Selectivity chart
Limits (kA) x160 TM 18/25/40kA In 6A 10A 13A NQN, NBN 16A B curve 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A 6A NRN, NCN C curve 10A 13A 16A 20A 25A 32A 40A 50A 63A 0,5A 1A 2A 3A 4A NGN, NSN, NDN 6A D curve 10A 13A 16A 20A 25A 32A 40A 50A 63A 0,63A 1,25A 1,6A 2,5A MMN 4A 6,3A 10A 12,5A 16A 20A 25A
HLE, HMB, HMJ

x250 TM 25/40kA 25A 1,6 1,4 1,3 1,3 -1,6 1,6 1,6 1,4 1,4 1,4 1,25 1,1 1,1 1,3 1,3 1,3 1,1 1,1 1,1 1 0,95 1,2 1,2 1,1 1,1 1 2,3 2 32A 1,9 1,7 1,5 1,5 1,5 2 2 2 1,7 1,7 1,7 1,5 1,3 1,3 1,3 1,6 1,6 1,6 1,3 1,3 1,3 1,2 1,1 1,1 1,35 1,35 1,2 1,2 1,1 3 2,6 2,1 40A 2,3 2 1,8 1,8 1,8 1,7 2,5 2,5 2,5 2 2 2 1,8 1,6 1,6 1,6 1,4 2 2 2 1,6 1,6 1,6 1,4 1,3 1,3 1,3 1,5 1,5 1,4 1,4 1,3 1,3 3,7 3,2 2,7 2,4 50A 3 2,4 2,1 2,1 2,1 1,9 1,9 3,5 3,5 3,5 2,5 2,5 2,5 2,1 1,8 1,8 1,8 1,6 1,6 3 3 3 2,1 2,1 2,1 1,7 1,5 1,5 1,5 1,2 1,8 1,8 1,7 1,7 1,5 1,5 4,6 4 3,4 3,1 2,9 63A 4 2,8 2,4 2,4 2,4 2,1 2,1 1,6 5,6 5,6 5,6 3,4 3,4 3,4 2,5 2,1 2,1 2,1 1,8 1,8 1,3 4,5 4,5 4,5 2,7 2,7 2,7 2 1,7 1,7 1,7 1,4 1,4 2,7 2,7 2,1 2,1 1,9 1,9 1,7 5,6 4,9 4,3 3,9 3,6 3,3 80A 5,5 3,4 2,8 2,8 2,8 2,3 2,3 1,7 1,4 8,8 8,8 8,8 4,8 4,8 4,8 3 2,4 2,4 2,4 2 2 1,5 1,1 7,4 7,4 7,4 3,8 3,8 3,8 2,4 1,9 1,9 1,9 1,6 1,6 1,2 4,9 4,9 2,7 2,7 2,4 2,4 2,1 2,1 6,7 5,9 5,2 4,9 4,5 4,2 3,9 100A 6,7 4 3,2 3,2 3,2 2,5 2,5 1,9 1,5 1,5 12 12 12 5,8 5,8 5,8 3,5 2,7 2,7 2,7 2,2 2,2 1,7 1,5 1,5 10 10 10 4,7 4,7 4,7 2,8 2,2 2,2 2,2 1,8 1,7 1,5 1,5 8 8 3,3 3,3 3 3 2,7 2,7 2,5 7,7 6,9 6,2 5,8 5,4 5,1 4,8 4,5 125A 8,6 4,9 3,7 3,7 3,7 2,9 2,9 2,2 1,8 1,5 16 16 16 6,8 6,8 6,8 4,3 3,2 3,2 3,2 2,6 2,6 2 1,5 1,5 13 13 13 5,7 5,7 5,7 3,4 2,6 2,6 2,6 2 2 1,5 1,5 1,5 13 13 4,5 4,5 4,1 4,1 3,7 3,7 3,3 3,3 7,8 8,6 7,8 7 6,7 6,3 6 5,7 5,4 7,4 160A 12 6,4 4,6 4,6 4,6 3,6 3,6 2,8 2,3 1,8 23 23 23 8,5 8,5 8,5 5,6 4,1 4,1 4,1 3,2 3,2 2,5 2 1,6 18 18 18 7,3 7,3 7,3 4,4 3,3 3,3 3,3 2,5 2,5 1,8 1,6 1,6 22 22 7 7 5,6 5,6 4,5 4,5 4 4 4 8,6 8,6 9,5 8,6 7,8 7,5 7,1 6,8 6,5 6,2 8,2 8,2 100A 7,8 4,7 3,8 3,8 3,8 3 3 2,3 1,8 1,4 14 14 14 6,8 6,8 6,8 4,1 3,2 3,2 3,2 2,6 2,6 2 1,5 1,3 12 12 12 5,5 5,5 5,5 3,3 2,6 2,6 2,6 2,1 2,1 1,5 9 9 3,9 3,9 3,5 3,5 3,2 3,2 9 8,1 7,3 6,8 6,3 5,9 5,6 5,3 125A 11 6,2 4,7 4,7 4,7 3,7 3,7 2,8 2,3 1,8 20 20 20 8,6 8,6 8,6 5,4 4,1 4,1 4,1 3,2 3,2 2,5 1,9 1,625 16 16 16 7,2 7,2 7,2 4,3 3,2 3,2 3,2 2,5 2,5 1,9 1,9 16 16 5,7 5,7 5,1 5,1 4,7 4,7 4,1 6,9 11 9,9 8,8 8,5 7,9 7,6 7,2 6,8 6,6 160A 16 8,6 6,2 6,2 6,2 4,9 4,9 3,8 3,2 2,4 T T T 12 12 12 7,6 5,6 5,6 5,6 4,3 4,3 3,4 2,7 2,2 24 24 24 9,9 9,9 9,9 5,9 4,5 4,5 4,5 3,4 3,4 2,4 2,4 2,08 T T 9,9 9,9 7,6 7,6 6,1 6,1 5,4 5,4 7,7 7,7 13 12 11 11 9,9 9 8,6 8,4 7,3 7,3 200A T 14 9,9 9,9 9,9 7,4 7,4 5,9 5,9 4,2 T T T 17 17 17 12 8,3 8,3 8,3 6,3 6,3 5 4,2 3,8 T T T 14 14 14 8,6 6,8 6,8 6,8 5,3 5,3 4,1 4,1 3,1 T T 17 17 12 12 8,8 8,8 7,8 7,8 7,8 8,8 8,8 8,8 16 15 14 14 13 12 11 11 8,6 8,6 8,6 8,9 250A T 23 17 17 17 13 13 9,9 8,6 7,7 T T T T T T 20 14 14 14 11 11 8,5 7,3 6,7 T T T 23 23 23 14 11 11 11 8,6 8,6 6,8 6,8 5,3 T T T T 20 20 14 14 13 13 13 11 11 11 23 21 20 20 18 17 16 16 11 11 11 12 10 -

h250 TM 25/50/65 kA 32A 2,5 2,2 2 2 2 1,8 2,6 2,6 2,6 2,2 2,2 2,2 2 1,7 1,7 1,7 1,6 2,1 2,1 2,1 1,7 1,7 1,7 1,6 1,4 1,8 1,8 1,6 1,6 1,4 3,9 3,4 2,7 2,4 -

16A 1,4 1,2 1,3 1,3 1,3 1,1 1,1 1,1 1 1 1 1 0,9 0,9 0,9 1,1 1,1 1 1 1,6 -

20A 1,5 1,3 1,2 --1,4 1,4 1,4 1,2 1,2 1,2 1,1 1 1,1 1,1 1,1 1 1 1 0,9 1,15 1,15 1,05 1,05 1,9 -

B curve C curve D curve

80A 100A 125A 10A 16A

HLF, HMC, HMK, HMX

20A 25A 32A 40A 50A 63A 80A 100A 125A 80A 100A 125A

T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs. All values are given with MCCB at the maximum setting.

HMD

100

Technical modifications reserved

h250 LSI 50/70 kA 63A 5,2 3,6 3,1 3,1 3,1 2,7 2,7 2,1 1,7 7,3 7,3 7,3 4,4 4,4 4,4 3,2 2,6 2,6 2,6 2,2 2,2 2,1 1,3 5,9 5,9 5,9 3,5 3,5 3,5 2,6 2,2 2,2 2,2 1,8 3,5 3,5 2,7 2,7 2,5 2,5 2,2 7,3 6,4 5,6 5,1 4,7 4,3 4 100A 8,7 5,2 4,2 4,2 4,2 3,3 3,3 2,5 2 1,6 16 16 16 7,5 7,5 7,5 4,6 3,5 3,5 3,5 2,9 2,9 2,2 1,7 1,3 13 13 13 6,1 6,1 6,1 3,7 2,9 2,9 2,9 2,3 2,3 1,7 10 10 4,3 4,3 3,9 3,9 3,5 3,5 3,3 7,7 10 9 8,1 7,5 7 6,6 6,2 5,9 7,3 125A 12 6,9 5,2 5,2 5,2 4,1 4,1 3,1 2,5 2 22 22 22 9,5 9,5 9,5 6 4,5 4,5 4,5 3,6 3,6 2,8 2,1 1,625 18 18 18 8 8 8 4,8 3,6 3,6 3,6 2,8 2,8 2,1 1,7 18 18 6,3 6,3 5,7 5,7 5,2 5,2 4,6 4,6 8,5 8,5 12 11 9,8 9,4 8,8 8,4 8 7,6 8,1 8,1 160A 18 9,6 6,9 6,9 6,9 5,4 5,4 4,2 3,5 2,7 T T T 13 13 13 8,4 6,2 6,2 6,2 4,8 4,8 3,8 3 2,4 T T T 11 11 11 6,6 5 5 5 3,8 3,8 2,7 2,2 2,08 T T 11 11 8,4 8,4 6,8 6,8 6 6 6 9,8 9,8 9,8 14 13 12 12 11 10 9,6 9,3 9,6 9,6 9,6 200A T 15 11 11 11 8,2 8,2 6,5 5,4 4,7 T T T 19 19 19 13 9,2 9,2 9,2 7 7 5,6 4,7 4,2 T T T 16 16 16 9,6 7,5 7,5 7,5 5,9 5,9 4,5 3,9 3,4 T T 19 19 13 13 9,8 9,8 8,7 8,7 8,7 12 12 12 18 16 15 15 14 13 12 12 12 12 12 9,8 250A T T 19 19 19 14 14 11 9,6 8,5 T T T T T T 22 16 16 16 12 12 9,4 8,1 7,4 T T T T T T 16 12 12 12 9,5 9,5 7,6 6,5 5,9 T T T T 22 22 16 16 14 14 14 16 16 16 26 23 22 22 20 19 18 18 16 16 16 13 11 40A 2,7 2,3 2,1 2,1 2,1 2 2,9 2,9 2,9 2,3 2,3 2,3 2,1 1,9 1,9 1,9 1,7 2,3 2,3 2,3 1,9 1,9 1,9 1,6 1,5 1,5 1,5 1,8 1,8 1,6 1,6 1,5 4,3 3,7 3,2 2,8 125A 11 6,2 4,7 4,7 4,7 3,7 3,7 2,8 2,3 1,8 20 20 20 8,6 8,6 8,6 5,4 4,1 4,1 4,1 3,2 3,2 2,5 1,9 1,75 16 16 16 7,2 7,2 7,2 4,3 3,2 3,2 3,2 2,5 2,5 1,9 1,9 1,75 16 16 5,7 5,7 5,1 5,1 4,7 4,7 4,1 6,9 11 9,9 8,8 8,5 7,9 7,6 7,2 6,8 6,6 250A T 23 17 17 17 13 13 9,9 8,6 7,7 T T T T T T 20 14 14 14 11 11 8,5 7,3 6,7 T T T 23 23 23 14 11 11 11 8,6 8,6 6,8 6,8 5,3 T T T T 20 20 14 14 13 13 13 11 11 11 23 21 20 20 18 17 16 16 11 11 11 12 10 8,7

h400 TM 25/50 kA 250A T T 21 21 21 15 15 12 11 9,4 T T T T T T 24 18 18 18 13 13 10 8,9 8,2 T T T T T T 18 13 13 13 10 10 8,4 7,2 6,5 T T T T 24 24 18 18 15 15 15 18 18 18 19 25 24 24 22 21 20 20 18 18 18 14 12 10 400A T T T T T T T T T T T T T T T T T T T T T T T 24 22 T T T T T T T T T T T T 23 20 18 T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h630 LSI 50/70 kA 250A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 630A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h1000 LSI 50/70 kA 630A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1000A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

h1600 LSI 50/70 kA 1250A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Technical modifications reserved

101

Selectivity chart
Icc (kA) Upstream x160 TM 16 - 50 63 2 2 2 1,8 1,6 1,6 80 2 2 2 1,8 1,6 1,6 100 2,9 2,9 2,9 2,6 2,35 2,35 2,15 2,15 125 2,9 2,9 2,9 2,6 2,35 2,35 2,15 2,15 160 3 3 3 2,7 2,4 2,4 2,2 2,2 2,1 2,1 x250 TM 100 2,15 2,15 2,15 2 1,8 1,8 1,7 1,7 1,55 1,55 1,55 125 2,9 2,9 2,9 2,6 2,35 2,35 2,15 2,15 1,95 1,95 1,95 1,95 1,95 1,95 1,95 1,95 160 4,1 4,1 4,1 3,6 3,3 3,15 3 2,9 2,75 2,65 2,6 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 200 5,6 5,6 5,6 5 4,3 4,25 4,05 3,9 3,7 3,5 3,45 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 250 5,4 5,4 5,4 4,8 4,2 4,15 3,9 3,8 3,6 3,4 3,35 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 3,3 h250 TM 32 63 1,2 1,2 1,2 1,15 1,1 1,1 1 1 100 2,15 2,15 2,15 2 1,8 1,8 1,7 1,7 1,55 1,55 1,55 -

Downstream (A) 16 20 25 32 40 x160 TM 50 18/25/40 kA 63 80 100 125 160 100 125 x250 TM 25/40 kA 160 200 250 32 63 100 h250 TM 125 25/50/65 kA 160 200 250 40 h250 LSI 50/70 kA h400 TM 25/50 kA h630 LSI 50/70 kA 125 250 250 400 250 400 630 630 h1000 LSI 50/70 kA h1600 LSI 50/70 kA 800 1000 1250 1600

Breaking capacity according to IEC 947-2. Network : 3 phasis + neutral 220/380 ~ 240/415 V AC notes : T = total discrimination (up to the breaking capacity of the downstream device) - = no discrimination

102

Technical modifications reserved

h250 LSI 125 2,9 2,9 2,9 2,6 2,35 2,35 2,15 2,15 1,95 1,95 1,95 1,95 1,95 1,95 1,95 1,95 160 4,1 4,1 4,1 3,6 3,3 3,15 3 2,9 2,75 2,65 2,6 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 200 5,6 5,6 5,6 5 4,3 4,25 4,05 3,9 3,7 3,5 3,45 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 3,15 250 5,4 5,4 5,4 4,8 4,2 4,15 3,9 3,8 3,6 3,4 3,35 3 3 3 3 3 3 3 3 3 3 3 40 T 125 T T T T T T T T T T T T T T T 1,65 250 T T T T T T T T T T T T T T T T T T T T T T T 3,25 3,25 3,25 -

h400 TM 250 6,5 6,5 6,5 5,6 4,95 4,8 4,6 4,35 4,15 4 3,9 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 3,6 400 13 13 13 10,5 9,2 8,8 8,3 7,9 7,5 7 6,6 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 5,75 -

h630 LSI 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 5,2 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 6,3 6,3 -

h1000 LSI 630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 800 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 9,6 1000 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 10 10 -

h1600 LSI 1250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 1600 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 19,2 -

Technical modifications reserved

103

Hager Vertriebsgesellschaft mbH & Co. KG Zum Gunterstal 66440 Blieskastel Telefon 06842 945-0 Telefax 06842 945-7666 www.hager.com

10NC0589