Purchaser
GENERAL INFORMATION : SWITCHBOARD TYPE PROTECTION DEGREE PAINTED BUSBAR SYSTEM MAIN BUS RATED CURRENT SERVICE VOLTAGE MAX. RATED VOLTAGE INSULATION LEVEL (LOW FREQ/IMPULSE) SHORT TIME CURRENT CARRYING POWER CABLE ENTRY POWER CABLE ACCESS CONTROL CABLE ENTRY POWER CABLE GLANDPLATE CONTROL CABLE GLANDPLATE MIMIC DIAGRAM : SIMOPRIME A4 : IP4X : RAL 7035 : BARE COPPER : 2500A : 20kV : 24kV : 50kV / 125kV : 25kA/1s : BOTTOM / TOP : REAR : BOTTOM : ALUMUNIUM, 5mm THICK : ALUMUNIUM, 5mm THICK : BLACK PLASTIC FOIL
User
Plant
Document Title
WIRE INFORMATION : WIRE TYPE CT WIRE - PHASE 1 CT WIRE - PHASE 2 CT WIRE - PHASE 3 CT WIRE - NEUTRAL VT WIRE - PHASE 1 VT WIRE - PHASE 2 VT WIRE - PHASE 3 VT WIRE - NEUTRAL DC CONTROL CIRCUIT AC CONTROL CIRCUIT (L/N) VCB/VC/TRUCK & E/S AUX. WIRE EARTH/GROUND CIRCUIT : NYAF 0.4/0.7kV : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm / BLACK (BK) - 1.5mm : BLACK (BK) - 1.0mm : GREEN YELLOW (GYL) - 4.0mm
Order number
H23336 02.04.12
Date of issue
Identification No.
Document designation
A / =00_COV / /1 (3)G73012-23336-A1000-A
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =01_TOC / A / A / 1
Designation
A =00_COV +JZ00 /1
Sheet
1-
Sheets
1
Date
02.04.12 GENERAL DOCUMENTS COVER SHEET
Description
Designed by
IC LMV MV AE
=01_TOC +JZ00
A1
(3)G73012-23336-L1001-A
1-
02.04.12
DOCUMENT LIST
IC LMV MV AE
=02_LGD +JZ00
B1
(3)G73012-23336-S1002-A
1+
02.04.12
IC LMV MV AE
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro GY Translate file A: GR Translate file B: YL Translate file C: RD Translate file D:
B
A =02_LGD +JZ00 B2 (3)G73012-23336-S1002-A 2+ 4 02.04.12 GENERAL DOCUMENTS LEGENDS ANSI CODE NUMBER IC LMV MV AE
=02_LGD +JZ00
B3
(3)G73012-23336-S1002-A
3+
02.04.12
IC LMV MV AE
=02_LGD +JZ00
B4
(3)G73012-23336-S1002-A
4-
02.04.12
IC LMV MV AE
C
A =03_SLD +JZ00 C1 (3)G73012-23336-S1003-A 11 02.04.12 GENERAL DOCUMENT SINGLE LINE DIAGRAM IC LMV MV AE
=04_FVW +JZ00
(3)G73012-23336-B1004-A
1-
02.04.12
IC LMV MV AE
1: 2: 3: 4:
=05_FLC +JZ00
E1
(3)G73012-23336-B1005-A
1+
02.04.12
IC LMV MV AE
=05_FLC +JZ00
E2
(3)G73012-23336-B1005-A
2+
02.04.12
IC LMV MV AE
=05_FLC +JZ00
E3
(3)G73012-23336-B1005-A
3-
02.04.12
IC LMV MV AE
=06_SEC +JZ00
F1
(3)G73012-23336-B1006-A
1+
02.04.12
IC LMV MV AE
=06_SEC +JZ00
F2
(3)G73012-23336-B1006-A
2-
02.04.12
IC LMV MV AE
F
Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Appr. Name Norm
30.03.2012 CV. SEMBRANI MITRA TEKNIK MEYRI 20kV SWITCHGEAR TRIANGGONO BARE COPPER RAL 7035 24kV 50Hz 20kV (BIL) L2 YUWONO Orig./Repl.f./Repl.by 2 3 4
=01_TOC +JZ00
A1 Sheet 11 Sh.
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 1
Master Element is the initiating device, such as a control switch, voltage relay, float switch, etc., which serves either directly, or through such permissive devices as protective and time-delay relays to place an equipment in or out of operation. Time-delay starting, or closing relay is a device which functions to give a desired amount of time delay before or after any point of operation in a switching sequence or protective relay system, except as specifically provided by device functions 48, 62, and 79 descrived later. Checking or interlocking relay is a device which operates in response to the position of a number of other devices, (or to a number of predetermined conditions), in an equipment, to allow an operating sequence to proceed, to stop, or to provide a check of the position of these devices or of these conditions for any purpose. Master contactor is a device, generally controlled by device No. 1 or equivalent, and the required permissive and protective devices, that serves to make and break the necessary control circuits to place and equipment into operation under the desired conditions and to take it out of operation under other or abnormal conditions. Stopping device is a control device used primarily to shut down an equipment and hold it out of operation. [This device may be manually or electrically actuated, but excludes the function of electrical lockout (see device function 86) on abnormal conditions.] Starting circuit breaker is a device whose principal function is to connect a machine to its source of starting voltage.
13
Synchronous-speed device, such as a centrifugalspeed switch, a slip-frequency relay, a voltage relay, an undercurrent relay or any type of device, operates at approximately synchronous speed of a machine. Under-speed device functions when the speed of a machine falls below a predetermined value. Speed or frequency matching device functions to match and hold the speed or the frrequency of a machine or of a system equal to, or approximately equal to, that of another machine, shource or system.
25
Synchronizing or synchronism-check device operates when two ac circuits are within the desired limits of frequency, phase angle or voltage, to permit or to cause the paralleling of these two circuits.
38
Bearing protective device functions on execessive bearing temperature, or on other abnormal mechanical conditions, such as undue wear, which may eventually result in excessive bearing temperature. Mechanical condition monitor is a device that functions upon the occurrence of an abnormal mechanical condition (except that associated with bearings as covered under device function 38), such as excessive vibration, eccentricity, expansion, shock, tilting, or seal failure. Field relay functions on a given or abnormally low value or failure of machine field current, or on an excessive value of the reactive component or armature current in an ac machine indicating abnormally low dield excitation. Field circuit breaker is a device whose functions to apply, or to remove, the field excitation of a machine. Running circuit breaker is a device whose principal function is to connect a machine to its source of running or operating voltage. This function may also be used for a device, such as a contactor, that is used in series with a circuit breaker or other fault protecting means, primarily for frequent opening and closing of the circuit. Manual transfer or selector device transfers the control circuits so as to modify the plan of operation of the switching equipment or of some of the devices. Unit sequence starting relay is a device which functions to start the next available unit in a multiple-unit equipment on the failure or on the non-availability of the normally preceding unit. Atmospheric condition monitor is a device that functions upon the occurence of an abnormal armospheric condition, such as damaging fumes, explosive mixtures, smoke, or fire.
14
26
C_FB_EN.etr, 04-11-24
15
Apparatus thermal device functions when the temperature of the shunt field or the armortisseur winding or a machine, or that of a load limiting or load shifting resistor or of a liquid or other medium exceeds a predetermined value; or if the temperature of the protected apparatus, such as a power rectifier, or of any medium decreases below a predetermined value. Undervoltage relay is a device which functions of a given value of undervoltage. Flame detector is a device that monitors the presence of the pilot or mail flame in such apparatus as a gas turbince or a steam boiler. Isolating contactor is used expressly for disconnecting one circuit from another for the purposes of emergency operation, maintenance, or test. Annunciator relay is a nonautomatically reset device that gives a number of separate visual indications upon the functioning of protective devices and which may also be arranged to perform a lockout function.
Archive:
39
40 16
27
17
Shunting or discharge switch serves to open or to close a shunting circuit around any piece of apparatus (except a resistor), such as a machine field, a machine armature, a capcitor or a reactor. Notes: this excludes devices which perform such shunting operations as may be necessary in the process of starting a machine by devices 6 or 42, or their equivalent, and also excludes device 73 function which serves for the switching of resistor. Accelerating or decelerating device is used to close or to cause the closing of circuits which are used increase or to decrease the speed of a machine.
A: B: C: D:
28
41
29
42
30
18
31 19
Starting-to-running transition contactor is a device which operates to initiate or cause the automatic transfer of a machine from the starting to the running power connection. Electrically operated valve is an electrically operated, controlled or monitored valve in a fluid line. Note: the function of the valve may be indicated by the use of the suffixes. Distance relay is a device which functions when the circuit admittance, impedance or reactance increases or decreases beyond predetermined limits. Equalizer circuit breaker is a breaker which serves to control or to make and break the equalizer or the current-balancing connections for a machine field, or for regulating equipment, in a multiple-unit installation.
35 32
Separate excitation device connects a circuit such as the shunt field of a synchronous converter, to a source of separate excitation during the starting sequence; or one which energizes the excitation and ignition circuits or a power rectifier. Directional power relay is one which functions on a desired value of power flow in a given directrion or upon reverse power resulting from arc back in the anode or cathode circuits of a power rectifier. Position switch makes or breaks contact when the main device or piece of apparatus, which has no device function number, reaches a given position. Master sequence device is a device such as a motor operated multi-contact switch, or the equivalent or a programming device, such as a computer that establishes or determines the operating sequence of the major devices in an equipment during starting and stopping or during sequential switching operations. Brush-operating, or slip-ring-short-circuiting, device is used for raising, lowering, or shifting the brushes of a machine, or for short-circuiting its slip rings, or for engaging or disengaging the contactos of a mechanical rectifier. Polarity or polarizing voltage device operates or permits the operation of another device on a predetermined polarity only or verifies the presence of a polarizing voltage in an equipment.
43
44
1: 2: 3: 4:
20 7
Anode circuit breaker is one used in the anode circuits of a power rectifier for the primary purpose of interrupting the rectifier circuit if an arc back should occur. Control power disconnecting device is a disconnective device such as a knife switch, circuit breaker or pullout fuse block, used for the purpose of connecting and disconnecting the source of control power to and from the control bus of equipment. Note: control power is considered to include auxiliary power which supplies apparatus as small motors and heaters. Reversing device is used for the purpose of reversing a machine field or for performing any other reversing functions. Unit sequence switch is used to change the sequence in which units may be placed in and out of service in multiple-unit equipments. Reserved for future application.
45
33
D
46
21
34
Reverse-phase, or phase-balance, current relay is a relay which functions when the polyphase currents are of reverse-phase sequence, or when the polyphase currents are unbalanced or contain negative phase-sequence components above a given amount. Phase-sequence voltage relay functions upon a predetermined value of polyphase voltage in the desired phase sequence. Incomplete sequence relay is a relay that generally returns the equipment to the normal, or off, position and locks it out if the normal starting, operating or stopping sequence is not properly completed within a predetermined time. If the device is used for alarm purposes only, it should preferably be designated as 48A (alarm). Machine, or transformer, thermal relay is a relay that functions when the temperature of a machine armature, or other load carrying winding or element of a machine, or the temperature of a power rectifier or power transformer (including a power rectifier transformer) exceeds a predetermined value.
22
47
23
10
Temperature control device functions to raise or lower the temperature of a machine or other apparatus or of any medium, when its temperature falls below, or rises above, a predetermided value. Note: an example is a thermostat which switches on a space heater in a switchgear assembly when the temperature falls to a desired value as distinguished from a device which is used to provide automatic temperature regulation between close limits and would be designated as 90T. Reserved for future application.
36
48
11
49 37
12
Over-speed device is usually a direct-connected speed switch which function on machine over-speed.
24
Undercurrent or underpower relay functions when the current or power flow decreases below the predetermined value.
F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A
SIMOPRIME A4
=02_LGD +JZ00
(3)G73012-23336-S1002-A 7 8
B1 Sheet 1+ 4 Sh.
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 2
50
Instantaneous overcurrent, or rate-of-rise relay is a relay that functions instantaneously on an excessive value of current, or on an excessive rate of current rise, thus indicating a fault in the apparatus or curcuit being protected. Ac time overcurrent relay is a relay with either a definite or inverse time characteristic that functions when the current in an ac circuit exceeds a predetermined value. Ac circuit breaker is a device that is used to close and interrupt an ac power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions. Excite or dc generator relay is a relay that forces the dc machine field excitation to build up during starting or which functions when the machine voltage has built up to a given value. Reserved for future application.
64
Ground protective relay is a relay that functions on failure of the insulation of a machine, transformer or of other apparatus to ground, or on flashover of a dc machine to ground. Note: This function is assigned only to a relay which detects the flow of current from the frame of a machine or enclosing case or structure of a piece of apparatus to ground, or detects a ground on a normally ungrounded winding or circuit. It is not applied to a device connected in the secondary circuit or secondary neutral of a current transformer, on in the secondary neutral of current transformer, connected in the power circuit of a normally grounded system. Governor is the assembly of fluid, electrical, or mechanical control equipment used for regulating the flow of water, steam, or other medium to the prime mover for such purposes as starting, holding speed or load, or stopping. Notching or jogging device functions to allow only a specified number of operations of a given device, or equipment, or a specified number of successive operations within a given time of each other. It also functions to energize a circuit periodically or for fractions of specified time in tervals, or that is used to permit intermittent acceleration or jogging of a machine at low speeds for machanical positioning. Ac directional overcurrent relay is a relay that functions on desired value of ac overcurrent flowing in a predetermined direction. Blocking relay is a relay that initiates a pilot signal for blocking or tripping on external faults in a transmission line or in other apparatus under predetermined conditions, or cooperates with other devices to block tripping or to block reclosing on an our-of-step condition or on power swing. Permissive control deice is generally a twoposition, manually operated switch that in one position permits the closing of a circuit breaker or the placing of an equipment into operation, and in the other position prevents the circuit breaker or the equipment from being operated. Rheostat is a variable resistance device used in an electric circuit, which is electrically operated or has other electrical accessories, such as auxiliary, position, or limit switches. Level switch is a switch which operates on given values, or on a given rate of change, of level.
74
Alarm relay is a device other than an annunciator, as covered under device No. 30, which is used to operate, or to operatein connection with a visual or audible alarm. Position changing mechanism is a mechanism that is used for moving a main device from one position to another in an equipment; as for example, shifting a removable circuit breaker unit to and from the connected, disconnected, and test position. Dc overcurrent relay is arelay that functions when the current in a dc circuit exceeds a given value. Pulse transmitter is used to generate and transmit pulses over a telemetering or pilot-wire circuit to the remote indicating or receiving device.
88
Auxiliary motor or motor generator is one used for operating auxiliary equipment such as pumps, blowers, exciters, rotating magnetic amplifiers, etc. Line switch is used as disconnecting loadinterrupter, or isolating switch in an ac or dc power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc.
Archive:
75
89
51
C_FB_EN.etr, 04-11-24
52
76
90
65
53
77
Regulating device functions to regulate a quantity, or quantities, such as voltage, current, power, speed, frequency, temperature, and load, at a certain value or between certain (generally close) limits for machines, tie lines or other apparatus. Voltage directional relayis a relay that operates when the voltage across an open circuit breaker or contactor exceeds a given value in a given direction. Voltage and power directional relay is a relay that permits or causes the connection of two circuits when the voltage difference between them exceeds a given value in a predetermined direction and causes these two circuits to be disconnected from each other when the power flowing between them exceeds a given value in the opposite direction. Field changing contactor functions to increase or decrease in one step the value of field excitation on a machine. Tripping or trip-free relay functions to trip a circuit breaker, contactor, or equipment, or to permit immediate tripping by other devices; or to prevent immediate reclosure of a circuit interrupter, in case it should open automatically even though its closing circuit is maintained closed.
A: B: C: D:
91 78
54
66
Phase angle measuring, or out-of-step protective relay is a relay that functions at a predetermined phase angle between two voltages or between two currents or between voltage and current.
92
55
Power factor relay is a relay that operates when the power factor in an ac circuit rises above or below a predetermined value. Field application relay is a relay that automatically controls the application of the field excitation to an ac motor at some predetermined point in the slip cycle. Chort-circuiting or grounding device is primary circuit switching device that functions to shortcircuit or to ground a circuit in response to automatic or manual means. Rectification failure relay is a device that functions if one or more anodes of a power rectifier fail to fire, or to detec an arc-back or on failure of a diode to conduct or block properly. Overvoltage relay is a relay that functions on a given value of overvoltage.
69
79
Ac reclosing relay is a relay that controls the automatic reclosing and locking out of an ac circuit interrupter. Flow switch is a switch which operates on given values, or on a given rate of change, of flow. Frequency relay is a relay that functions on a predetermined value of frequency - either under or over or on normal system frequency or rate of change of frequency. Dc reclosing relay is a relay that controls the automatic closing and reclosing of a dc circuit interrupter, generally in response to load circuit conditions. Automatic selective control or transfer relay is a relay that operates to select automatically between certain cources or conditions in an equipment, or performs a transfer operation automatically. Operating mechanism is the complete electrical mechanism or servo-mechanism, including the operating motor, solenoids, position switches, etc., for a tap changer, induction regulator or any similar piece of apparatus which has no device function number.
93
56
80
67
57
81
68
94
1: 2: 3: 4:
58
82
59
83
95
D
Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable.
60
Voltage or current balance relay is a relay that operates on a given difference in voltage, or current input or output of two circuits. Reserved for future applications.
96
70
84
97
61
62
Time-delay stopping or opening relay is a timedelay relay that serves in conjunction with the device that initiates the shutdown, stopping, or opening operation in an automatic sequence. Pressure switch is a switch which operates on given values or on a given rate of change of pressure.
71
85 72
63
Dc circuit breaker is used to close and interrupt dc power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions.
86
Carrier or pilot-wire receiver relay is a relay that operated or restrained by a signal used in connection with carrier-current or dc pilot-wire fault directional relaying. Locking-out relay is an electrically operated, hand or electrically reset, relay that functions to shut down and hold an equipment out of service on the occurence of abnormal conditions. Differential protective relay is a protective relay that functions on a percentage or phase angle or other quantities difference of two currents or of some other electrical quantities.
74TC
73
Load-resistor contactor is used to shunt or insert a step of load limiting, shifting, or indicating resistance in a power circuit, or to switch a space heater in circuit, or to switch a light, or regenerative load resistor of a power rectifier or other machine in and out of circuit.
87
F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A
SIMOPRIME A4
=02_LGD +JZ00
(3)G73012-23336-S1002-A 7 8
B2 Sheet 2+ 4 Sh.
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 3
BASIC REPRESENTATION
BASIC REPRESENTATION
CONTACTS
CONTACTOR
RECTIFIER A
3
BUSDUCT CONNECTION
A
NORMALLY OPEN CONTACT SOLENOID/COIL
Archive:
NORMALLY CLOSE CONTACT MECHANICAL INTERLOCK NORMALLY OPEN CONTACT (CLOSED CONDITION) MECHANICAL ACTIVATED
OFF-DELAY COIL
C_FB_EN.etr, 04-11-24
V
3
ON-DELAY COIL
B
CHANGE OVER
A: B: C: D:
Hz
FREQUENCY METER
P
HEATER
CONTACT
ON-/OFF-DELAY COIL
PF
POWER-FACTOR METER
WATT METER
MOTOR OPERATING MECHANISM MAKE CONTACT DELAYED WHEN DIODE OPENING PLUG AND SOCKET BREAK CONTACT
VAR
VAR METER
Wh
THERMOSTAT
AMPERE/VOLTAGE SELECTOR
VARh
1: 2: 3: 4:
Wh
THROUGH VENTILATION
VARh
CS
CONTROL SWITCH
Wh
POTENTIAL DESIGNATION
(PANEL/PACKING)
VARh
VAR-HOUR METER EXPORT-IMPORT TRANSDUCER/ POWER SUPPLY UNIT CABLE CONNECTION BINARY INPUT
PRESSURE ACTIVATOR
EARTHING/GROUNDING
INFORMATION
Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Name Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-S1002-A 7
=02_LGD +JZ00
B3 Sheet 3+ 4 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 4
COMPOSITE REPRESENTATION
COMPOSITE REPRESENTATION
COMPOSITE REPRESENTATION
A
-Q01 M 630A 3-POSITION SWITCH CONNECTED DISCONNECTED EARTHED
C_FB_EN.etr, 04-11-24
Archive:
EARTHING SWITCH
3
A: B: C: D:
WITHDRAWABLE CIRCUIT BREAKER - MOTORIZED SPRING CHARGING MECHANISM - WITH TRUCK MOVEMENT BLOCKING COIL - INTEGRATED VOLTAGE TRANSFORMER - VOLTAGE TRANSFORMER WITH PRIMARY FUSE CORE2 CORE1 P1
I > I > I >
P2
3
2-POLE MCB 3 UNITS CURRENT TRANSFORMER - TWO CORES - BLOCK TYPE - SECONDARY TERMINAL AT P2 3-POLE MCB
I > I >
P2 CORE1 P1
3 UNITS CURRENT TRANSFORMER - GENERAL REPRESENTATION - APPLICABLE FOR TOROID TYPE CLOSE OPEN - ONE CORES
1: 2: 3: 4:
11
10 9
P1
WITHDRAWABLE VACUUM CONTACTOR - WITH PRIMARY FUSES - WITH CONTROL POTENTIAL TRANSFORMER
CONTROL SWITCH S1 PHASE CURRENT TRANSFORMER S2 P2 - USED IN WIRING DIAGRAM - SPRING RETURN TO CENTER - 3 POLES
REM
LOC
10
11
WITHDRAWABLE BUS METERING VT - WITH PRIMARY FUSES - WITH SINGLE WINDING VOLTAGE TRANSFORMER
F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-S1002-A 7
=02_LGD +JZ00
B4 Sheet 44 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000330 =03_SLD / A / C / 1
2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL =J02 +J02 =JZ01 =J02 INCOMING PANEL 1
3
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2
4
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3
C_FB_EN.etr, 04-11-24
Archive:
A: B: C: D:
-Q1
-Q1
-Q1
4 M
-Q0
1250A 25kA
4 M
-Q0
1250A 25kA
4 M
-Q0
1250A 25kA
C
-T5L1,L2,L3 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1:
3
-T5L1,L2,L3 kV 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1: 700/5A 10VA, 5P20
3
-T5L1,L2,L3 kV 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1: 700/5A 10VA, 5P20 -Y8 P1 CT SECONDARY TERMINAL BOX POSITION LEGEND
3
kV
1: 2: 3: 4:
CABLE EARTHING SWITCH BLOCKING COIL. (EARTHING CANNOT BE CLOSED OR OPENED WHEN THIS COIL IS NOT ENERGIZED).
P1
PADLOCK FACILITY FOR INDEPENDENT SHUTTER OPERATION HOLE PADLOCK FACILITY FOR EARTHING SWITCH OPERATION HOLE PADLOCK FACILITY FOR TRUCK WITHDRAWABLE OPERATION HOLE PADLOCK FACILITY FOR HV DOOR KEY OPERATION HOLE PADLOCK FACILITY FOR CB (OPEN - CLOSE) OPERATION HOLE
-Q8 2
-Q8 2
-Q8 2
-Y8
-Y8
-Y8
CABLE
6X1Cx500mm CU/XLPE/PVC
6X1Cx500mm CU/XLPE/PVC
6X1Cx500mm CU/XLPE/PVC
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-S1003-A 7
=03_SLD +JZ00
C1 Sheet 11 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000267 =04_FVW / A / D / 1
2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL
3
=J02 +J02 =JZ01 =J02 INCOMING PANEL 1
4
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2
5
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3
Archive:
140.0
140.0 55.0
140.0 55.0
C_FB_EN.etr, 04-11-24
1: 2: 3: 4:
2250
A: B: C: D:
35
630
800
800
OVERALL LENGTH = 3270
800
800
35
E
725
1095
1095
1095
F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-B1004-A 7
=04_FVW +JZ00
D Sheet 11 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000519 =05_FLC / A / E / 1
2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL
3
=J02 +J02 =JZ01 =J02 INCOMING PANEL 1
4
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2
5
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3
Archive:
C_FB_EN.etr, 04-11-24
25
A: B: C: D:
25
C2
2500
1: 2: 3: 4:
C2
1900
C3
C4 C1
C3
C1
800
800
OVERALL LENGTH = 3200
800
800 38.5
POWER CABLE
38.5
12X1Cx500mm CU/XLPE/PVC
6X1Cx500mm CU/XLPE/PVC
6X1Cx500mm CU/XLPE/PVC
F A
SIMOPRIME A4
Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Name Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
=05_FLC +JZ00
E1 Sheet 1+ 3 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000419 =05_FLC / A / E / 2
Archive:
500
500 NOTES:
1. 2.
B
MOST LEFT PANEL MOST RIGHT PANEL
A: B: C: D:
1: 2: 3: 4:
2000
F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-B1005-A 7
=05_FLC +JZ00
E2 Sheet 2+ 3 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000097 =05_FLC / A / E / 3
6
HEXAGON SCREW M10 WASHER 10.5-St-A3L HEXAGON NUT M10-8-A4L
BASEFRAME OF SWITCHGEAR WELDING IN FIXING OPENING OF SWGR BASE FRAME TOP OF FLOOR FINISH U50 PROFILE TOP OF FALSE FLOOR
Archive:
SCREED
MOUNTING PLATE
MIN. 55mm
C_FB_EN.etr, 04-11-24
A: B: C: D:
80.0
BASEFRAME OF SWITCHGEAR HAMMER HEAD SCREW M16x35-4.6-A3L, WASHER R18 OR PLATE 6x55x70 (18mm DRILLING), HEXAGON NUT M16-8-A4L TOP OF FLOOR FINISH C PROFILE CB 50x30
60.0 50.0
40.0
35.0
MIN. 55mm
SCREED
80.0 30.0
1: 2: 3: 4:
13.0
30.0
145.0
FLOOR LEVEL
44
44
THIS DRAWING IS FOR REFERENCE ONLY. ACTUAL CIVIL WORK IS NOT SCOPE OF PT. SIEMENS INDONESIA
F
ALL DIMENSIONS ARE IN MILLIMETER.
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A (3)G73012-23336-B1005-A 7
=05_FLC +JZ00
E3 Sheet 33 Sh. 8
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000337 =06_SEC / A / F / 1
LEGEND
A1 PANEL NAMEPLATE
A
A2 TRUCK INSPECTION WINDOW
Archive:
FRONT VIEW
SIDE VIEW
395
A3
C_FB_EN.etr, 04-11-24
A4
140.0 55.0
A1 A5
B2
MANUAL CB ON / OFF ACCESS HOLES HANDLE FOR OPENING OF CB-COMPARTMENT DOOR INSPECTION WINDOW FOR SPRING CHARGING INDICATOR AND OPERATING COUNTER TRUCK MOVEMENT ACCESS HOLES
B1
697.5
A6
A: B: C: D:
A7
A8 A2 A3 FRONT OF A6 A7 A9
2250
A5
A4
B3
PANELS
C
A8
B4
B1
LOW-VOLTAGE COMPARTMENT
1: 2: 3: 4:
A9
B2
BUSBAR COMPARTMENT
B3
800
25
1900
38.5
B4
CABLE COMPARTMENT
PANEL OPENING
C1
50
310
290
445 105
775
30
C2
400
C3 FRONT OF
590
C1
C2
C1
C1 C3
40
25
105
180
50
1900 1963.5
38.5
800
PANELS
F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A
SIMOPRIME A4
=06_SEC +JZ00
(3)G73012-23336-B1006-A 7 8
F1 Sheet 1+ 2 Sh.
1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000216 =06_SEC / A / F / 2
LEGEND
A1 PANEL NAMEPLATE
A
A2 -
Archive:
FRONT VIEW
A3
C_FB_EN.etr, 04-11-24
A4
140.0 55.0
A1 A5 -
B4
B2
B1
A6
A: B: C: D:
A7
A8
FRONT OF PANELS
A9
B1
LOW-VOLTAGE COMPARTMENT
1: 2: 3: 4:
B2
BUSBAR COMPARTMENT
B3
800
25
600
1900
38.5
B4
PANEL OPENING 50
C1
50 105
290
1045
775
30
C2
400
C3 FRONT OF
590
C2
C1
C1
C1 C3
40
105
180
50
25
600 2563.5
1900
38.5
800
PANELS
F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO
A Rev.
02.04.12 Date
MH Name
Appr. Norm
JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3
A
SIMOPRIME A4
=06_SEC +JZ00
(3)G73012-23336-B1006-A 7 8
F2 Sheet 22 Sh.