Diagrams and charts for

Purchaser
GENERAL INFORMATION : SWITCHBOARD TYPE PROTECTION DEGREE PAINTED BUSBAR SYSTEM MAIN BUS RATED CURRENT SERVICE VOLTAGE MAX. RATED VOLTAGE INSULATION LEVEL (LOW FREQ/IMPULSE) SHORT TIME CURRENT CARRYING POWER CABLE ENTRY POWER CABLE ACCESS CONTROL CABLE ENTRY POWER CABLE GLANDPLATE CONTROL CABLE GLANDPLATE MIMIC DIAGRAM : SIMOPRIME A4 : IP4X : RAL 7035 : BARE COPPER : 2500A : 20kV : 24kV : 50kV / 125kV : 25kA/1s : BOTTOM / TOP : REAR : BOTTOM : ALUMUNIUM, 5mm THICK : ALUMUNIUM, 5mm THICK : BLACK PLASTIC FOIL

CV. SEMBRANI MITRA TEKNIK

User

CV. SEMBRANI MITRA TEKNIK

Plant

JATIM TAMAN STEEL 2

Document Title
WIRE INFORMATION : WIRE TYPE CT WIRE - PHASE 1 CT WIRE - PHASE 2 CT WIRE - PHASE 3 CT WIRE - NEUTRAL VT WIRE - PHASE 1 VT WIRE - PHASE 2 VT WIRE - PHASE 3 VT WIRE - NEUTRAL DC CONTROL CIRCUIT AC CONTROL CIRCUIT (L/N) VCB/VC/TRUCK & E/S AUX. WIRE EARTH/GROUND CIRCUIT : NYAF 0.4/0.7kV : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 2.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm : BLACK (BK) - 1.5mm / BLACK (BK) - 1.5mm : BLACK (BK) - 1.0mm : GREEN YELLOW (GYL) - 4.0mm

20kV SWITCHGEAR GENERAL DOCUMENTS COVER SHEET

Order number

H23336 02.04.12

Date of issue

Identification No.

PT. SIEMENS INDONESIA


Energy Sector Power Distribution Division E D MV Jl. Jendral A. Yani Kav B67-68, Pulomas, Jakarta 13210, Indonesia

Document designation

A / =00_COV / /1 (3)G73012-23336-A1000-A

Producer document No.

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =01_TOC / A / A / 1

Designation
A =00_COV +JZ00 /1

Producer document No.


(3)G73012-23336-A1000-A

Sheet
1-

Sheets
1

Date
02.04.12 GENERAL DOCUMENTS COVER SHEET

Description

Designed by
IC LMV MV AE

2.5 4 C_FB_EN.etr, 04-11-24 BK Archive:

=01_TOC +JZ00

A1

(3)G73012-23336-L1001-A

1-

02.04.12

DOCUMENT LIST

IC LMV MV AE

=02_LGD +JZ00

B1

(3)G73012-23336-S1002-A

1+

02.04.12

GENERAL DOCUMENTS LEGENDS ANSI CODE NUMBER

IC LMV MV AE

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro GY Translate file A: GR Translate file B: YL Translate file C: RD Translate file D:

B
A =02_LGD +JZ00 B2 (3)G73012-23336-S1002-A 2+ 4 02.04.12 GENERAL DOCUMENTS LEGENDS ANSI CODE NUMBER IC LMV MV AE

=02_LGD +JZ00

B3

(3)G73012-23336-S1002-A

3+

02.04.12

GENERAL DOCUMENTS LEGENDS

IC LMV MV AE

=02_LGD +JZ00

B4

(3)G73012-23336-S1002-A

4-

02.04.12

GENERAL DOCUMENTS LEGENDS

IC LMV MV AE

C
A =03_SLD +JZ00 C1 (3)G73012-23336-S1003-A 11 02.04.12 GENERAL DOCUMENT SINGLE LINE DIAGRAM IC LMV MV AE

Project: Symbol library Symbol library Symbol library Symbol library

=04_FVW +JZ00

(3)G73012-23336-B1004-A

1-

02.04.12

GENERAL DOCUMENT PANEL FRONT VIEW

IC LMV MV AE

1: 2: 3: 4:

=05_FLC +JZ00

E1

(3)G73012-23336-B1005-A

1+

02.04.12

GENERAL DOCUMENT PANEL FLOOR CUTOUT

IC LMV MV AE

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

=05_FLC +JZ00

E2

(3)G73012-23336-B1005-A

2+

02.04.12

GENERAL DOCUMENT SWITCHGEAR CLEARANCE

IC LMV MV AE

=05_FLC +JZ00

E3

(3)G73012-23336-B1005-A

3-

02.04.12

GENERAL DOCUMENT FIXING DETAIL

IC LMV MV AE

=06_SEC +JZ00

F1

(3)G73012-23336-B1006-A

1+

02.04.12

GENERAL DOCUMENT PANEL CONFIGURATION =JZ01 - INCOMING FEEDER

IC LMV MV AE

=06_SEC +JZ00

F2

(3)G73012-23336-B1006-A

2-

02.04.12

GENERAL DOCUMENT PANEL CONFIGURATION =JZ02 - CONNECTION PANEL

IC LMV MV AE

F
Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Appr. Name Norm

30.03.2012 CV. SEMBRANI MITRA TEKNIK MEYRI 20kV SWITCHGEAR TRIANGGONO BARE COPPER RAL 7035 24kV 50Hz 20kV (BIL) L2 YUWONO Orig./Repl.f./Repl.by 2 3 4

DOCUMENT LIST SIMOPRIME A4 5 6 (3)G73012-23336-L1001-A 7

=01_TOC +JZ00

A1 Sheet 11 Sh.

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 1

Master Element is the initiating device, such as a control switch, voltage relay, float switch, etc., which serves either directly, or through such permissive devices as protective and time-delay relays to place an equipment in or out of operation. Time-delay starting, or closing relay is a device which functions to give a desired amount of time delay before or after any point of operation in a switching sequence or protective relay system, except as specifically provided by device functions 48, 62, and 79 descrived later. Checking or interlocking relay is a device which operates in response to the position of a number of other devices, (or to a number of predetermined conditions), in an equipment, to allow an operating sequence to proceed, to stop, or to provide a check of the position of these devices or of these conditions for any purpose. Master contactor is a device, generally controlled by device No. 1 or equivalent, and the required permissive and protective devices, that serves to make and break the necessary control circuits to place and equipment into operation under the desired conditions and to take it out of operation under other or abnormal conditions. Stopping device is a control device used primarily to shut down an equipment and hold it out of operation. [This device may be manually or electrically actuated, but excludes the function of electrical lockout (see device function 86) on abnormal conditions.] Starting circuit breaker is a device whose principal function is to connect a machine to its source of starting voltage.

13

Synchronous-speed device, such as a centrifugalspeed switch, a slip-frequency relay, a voltage relay, an undercurrent relay or any type of device, operates at approximately synchronous speed of a machine. Under-speed device functions when the speed of a machine falls below a predetermined value. Speed or frequency matching device functions to match and hold the speed or the frrequency of a machine or of a system equal to, or approximately equal to, that of another machine, shource or system.

25

Synchronizing or synchronism-check device operates when two ac circuits are within the desired limits of frequency, phase angle or voltage, to permit or to cause the paralleling of these two circuits.

38

Bearing protective device functions on execessive bearing temperature, or on other abnormal mechanical conditions, such as undue wear, which may eventually result in excessive bearing temperature. Mechanical condition monitor is a device that functions upon the occurrence of an abnormal mechanical condition (except that associated with bearings as covered under device function 38), such as excessive vibration, eccentricity, expansion, shock, tilting, or seal failure. Field relay functions on a given or abnormally low value or failure of machine field current, or on an excessive value of the reactive component or armature current in an ac machine indicating abnormally low dield excitation. Field circuit breaker is a device whose functions to apply, or to remove, the field excitation of a machine. Running circuit breaker is a device whose principal function is to connect a machine to its source of running or operating voltage. This function may also be used for a device, such as a contactor, that is used in series with a circuit breaker or other fault protecting means, primarily for frequent opening and closing of the circuit. Manual transfer or selector device transfers the control circuits so as to modify the plan of operation of the switching equipment or of some of the devices. Unit sequence starting relay is a device which functions to start the next available unit in a multiple-unit equipment on the failure or on the non-availability of the normally preceding unit. Atmospheric condition monitor is a device that functions upon the occurence of an abnormal armospheric condition, such as damaging fumes, explosive mixtures, smoke, or fire.

14

26

C_FB_EN.etr, 04-11-24

15

Apparatus thermal device functions when the temperature of the shunt field or the armortisseur winding or a machine, or that of a load limiting or load shifting resistor or of a liquid or other medium exceeds a predetermined value; or if the temperature of the protected apparatus, such as a power rectifier, or of any medium decreases below a predetermined value. Undervoltage relay is a device which functions of a given value of undervoltage. Flame detector is a device that monitors the presence of the pilot or mail flame in such apparatus as a gas turbince or a steam boiler. Isolating contactor is used expressly for disconnecting one circuit from another for the purposes of emergency operation, maintenance, or test. Annunciator relay is a nonautomatically reset device that gives a number of separate visual indications upon the functioning of protective devices and which may also be arranged to perform a lockout function.

Archive:

39

40 16

Reserved for future application.

27

file file file file

17

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

Shunting or discharge switch serves to open or to close a shunting circuit around any piece of apparatus (except a resistor), such as a machine field, a machine armature, a capcitor or a reactor. Notes: this excludes devices which perform such shunting operations as may be necessary in the process of starting a machine by devices 6 or 42, or their equivalent, and also excludes device 73 function which serves for the switching of resistor. Accelerating or decelerating device is used to close or to cause the closing of circuits which are used increase or to decrease the speed of a machine.

A: B: C: D:

28

41

29

42

30

18

31 19

Starting-to-running transition contactor is a device which operates to initiate or cause the automatic transfer of a machine from the starting to the running power connection. Electrically operated valve is an electrically operated, controlled or monitored valve in a fluid line. Note: the function of the valve may be indicated by the use of the suffixes. Distance relay is a device which functions when the circuit admittance, impedance or reactance increases or decreases beyond predetermined limits. Equalizer circuit breaker is a breaker which serves to control or to make and break the equalizer or the current-balancing connections for a machine field, or for regulating equipment, in a multiple-unit installation.
35 32

Separate excitation device connects a circuit such as the shunt field of a synchronous converter, to a source of separate excitation during the starting sequence; or one which energizes the excitation and ignition circuits or a power rectifier. Directional power relay is one which functions on a desired value of power flow in a given directrion or upon reverse power resulting from arc back in the anode or cathode circuits of a power rectifier. Position switch makes or breaks contact when the main device or piece of apparatus, which has no device function number, reaches a given position. Master sequence device is a device such as a motor operated multi-contact switch, or the equivalent or a programming device, such as a computer that establishes or determines the operating sequence of the major devices in an equipment during starting and stopping or during sequential switching operations. Brush-operating, or slip-ring-short-circuiting, device is used for raising, lowering, or shifting the brushes of a machine, or for short-circuiting its slip rings, or for engaging or disengaging the contactos of a mechanical rectifier. Polarity or polarizing voltage device operates or permits the operation of another device on a predetermined polarity only or verifies the presence of a polarizing voltage in an equipment.

43

44

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

20 7

Anode circuit breaker is one used in the anode circuits of a power rectifier for the primary purpose of interrupting the rectifier circuit if an arc back should occur. Control power disconnecting device is a disconnective device such as a knife switch, circuit breaker or pullout fuse block, used for the purpose of connecting and disconnecting the source of control power to and from the control bus of equipment. Note: control power is considered to include auxiliary power which supplies apparatus as small motors and heaters. Reversing device is used for the purpose of reversing a machine field or for performing any other reversing functions. Unit sequence switch is used to change the sequence in which units may be placed in and out of service in multiple-unit equipments. Reserved for future application.

45

33

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

D
46

21

34

Reverse-phase, or phase-balance, current relay is a relay which functions when the polyphase currents are of reverse-phase sequence, or when the polyphase currents are unbalanced or contain negative phase-sequence components above a given amount. Phase-sequence voltage relay functions upon a predetermined value of polyphase voltage in the desired phase sequence. Incomplete sequence relay is a relay that generally returns the equipment to the normal, or off, position and locks it out if the normal starting, operating or stopping sequence is not properly completed within a predetermined time. If the device is used for alarm purposes only, it should preferably be designated as 48A (alarm). Machine, or transformer, thermal relay is a relay that functions when the temperature of a machine armature, or other load carrying winding or element of a machine, or the temperature of a power rectifier or power transformer (including a power rectifier transformer) exceeds a predetermined value.

22

47

23

10

Temperature control device functions to raise or lower the temperature of a machine or other apparatus or of any medium, when its temperature falls below, or rises above, a predetermided value. Note: an example is a thermostat which switches on a space heater in a switchgear assembly when the temperature falls to a desired value as distinguished from a device which is used to provide automatic temperature regulation between close limits and would be designated as 90T. Reserved for future application.
36

48

11

49 37

12

Over-speed device is usually a direct-connected speed switch which function on machine over-speed.

24

Undercurrent or underpower relay functions when the current or power flow decreases below the predetermined value.

F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENTS LEGENDS ANSI CODE NUMBER 4 5 6

A
SIMOPRIME A4

=02_LGD +JZ00

(3)G73012-23336-S1002-A 7 8

B1 Sheet 1+ 4 Sh.

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 2

50

Instantaneous overcurrent, or rate-of-rise relay is a relay that functions instantaneously on an excessive value of current, or on an excessive rate of current rise, thus indicating a fault in the apparatus or curcuit being protected. Ac time overcurrent relay is a relay with either a definite or inverse time characteristic that functions when the current in an ac circuit exceeds a predetermined value. Ac circuit breaker is a device that is used to close and interrupt an ac power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions. Excite or dc generator relay is a relay that forces the dc machine field excitation to build up during starting or which functions when the machine voltage has built up to a given value. Reserved for future application.

64

Ground protective relay is a relay that functions on failure of the insulation of a machine, transformer or of other apparatus to ground, or on flashover of a dc machine to ground. Note: This function is assigned only to a relay which detects the flow of current from the frame of a machine or enclosing case or structure of a piece of apparatus to ground, or detects a ground on a normally ungrounded winding or circuit. It is not applied to a device connected in the secondary circuit or secondary neutral of a current transformer, on in the secondary neutral of current transformer, connected in the power circuit of a normally grounded system. Governor is the assembly of fluid, electrical, or mechanical control equipment used for regulating the flow of water, steam, or other medium to the prime mover for such purposes as starting, holding speed or load, or stopping. Notching or jogging device functions to allow only a specified number of operations of a given device, or equipment, or a specified number of successive operations within a given time of each other. It also functions to energize a circuit periodically or for fractions of specified time in tervals, or that is used to permit intermittent acceleration or jogging of a machine at low speeds for machanical positioning. Ac directional overcurrent relay is a relay that functions on desired value of ac overcurrent flowing in a predetermined direction. Blocking relay is a relay that initiates a pilot signal for blocking or tripping on external faults in a transmission line or in other apparatus under predetermined conditions, or cooperates with other devices to block tripping or to block reclosing on an our-of-step condition or on power swing. Permissive control deice is generally a twoposition, manually operated switch that in one position permits the closing of a circuit breaker or the placing of an equipment into operation, and in the other position prevents the circuit breaker or the equipment from being operated. Rheostat is a variable resistance device used in an electric circuit, which is electrically operated or has other electrical accessories, such as auxiliary, position, or limit switches. Level switch is a switch which operates on given values, or on a given rate of change, of level.

74

Alarm relay is a device other than an annunciator, as covered under device No. 30, which is used to operate, or to operatein connection with a visual or audible alarm. Position changing mechanism is a mechanism that is used for moving a main device from one position to another in an equipment; as for example, shifting a removable circuit breaker unit to and from the connected, disconnected, and test position. Dc overcurrent relay is arelay that functions when the current in a dc circuit exceeds a given value. Pulse transmitter is used to generate and transmit pulses over a telemetering or pilot-wire circuit to the remote indicating or receiving device.

88

Auxiliary motor or motor generator is one used for operating auxiliary equipment such as pumps, blowers, exciters, rotating magnetic amplifiers, etc. Line switch is used as disconnecting loadinterrupter, or isolating switch in an ac or dc power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc.

Archive:

75

89

51

C_FB_EN.etr, 04-11-24

52

76

90

65

53

77

Regulating device functions to regulate a quantity, or quantities, such as voltage, current, power, speed, frequency, temperature, and load, at a certain value or between certain (generally close) limits for machines, tie lines or other apparatus. Voltage directional relayis a relay that operates when the voltage across an open circuit breaker or contactor exceeds a given value in a given direction. Voltage and power directional relay is a relay that permits or causes the connection of two circuits when the voltage difference between them exceeds a given value in a predetermined direction and causes these two circuits to be disconnected from each other when the power flowing between them exceeds a given value in the opposite direction. Field changing contactor functions to increase or decrease in one step the value of field excitation on a machine. Tripping or trip-free relay functions to trip a circuit breaker, contactor, or equipment, or to permit immediate tripping by other devices; or to prevent immediate reclosure of a circuit interrupter, in case it should open automatically even though its closing circuit is maintained closed.

file file file file

A: B: C: D:

91 78

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

54

66

Phase angle measuring, or out-of-step protective relay is a relay that functions at a predetermined phase angle between two voltages or between two currents or between voltage and current.
92

55

Power factor relay is a relay that operates when the power factor in an ac circuit rises above or below a predetermined value. Field application relay is a relay that automatically controls the application of the field excitation to an ac motor at some predetermined point in the slip cycle. Chort-circuiting or grounding device is primary circuit switching device that functions to shortcircuit or to ground a circuit in response to automatic or manual means. Rectification failure relay is a device that functions if one or more anodes of a power rectifier fail to fire, or to detec an arc-back or on failure of a diode to conduct or block properly. Overvoltage relay is a relay that functions on a given value of overvoltage.
69

79

Ac reclosing relay is a relay that controls the automatic reclosing and locking out of an ac circuit interrupter. Flow switch is a switch which operates on given values, or on a given rate of change, of flow. Frequency relay is a relay that functions on a predetermined value of frequency - either under or over or on normal system frequency or rate of change of frequency. Dc reclosing relay is a relay that controls the automatic closing and reclosing of a dc circuit interrupter, generally in response to load circuit conditions. Automatic selective control or transfer relay is a relay that operates to select automatically between certain cources or conditions in an equipment, or performs a transfer operation automatically. Operating mechanism is the complete electrical mechanism or servo-mechanism, including the operating motor, solenoids, position switches, etc., for a tap changer, induction regulator or any similar piece of apparatus which has no device function number.
93

56

80

67

57

81

68

94

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

58

82

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

59

83

95

D
Used only for specific applications on individual installations where none of the assigned numbered functions from 1 to 94 is suitable.

60

Voltage or current balance relay is a relay that operates on a given difference in voltage, or current input or output of two circuits. Reserved for future applications.

96

70

84

97

61

62

Time-delay stopping or opening relay is a timedelay relay that serves in conjunction with the device that initiates the shutdown, stopping, or opening operation in an automatic sequence. Pressure switch is a switch which operates on given values or on a given rate of change of pressure.

71

85 72

63

Dc circuit breaker is used to close and interrupt dc power circuit under normal conditions or to interrupt this circuit under fault or emergency conditions.
86

Carrier or pilot-wire receiver relay is a relay that operated or restrained by a signal used in connection with carrier-current or dc pilot-wire fault directional relaying. Locking-out relay is an electrically operated, hand or electrically reset, relay that functions to shut down and hold an equipment out of service on the occurence of abnormal conditions. Differential protective relay is a protective relay that functions on a percentage or phase angle or other quantities difference of two currents or of some other electrical quantities.

Special alocated ANSI device number (Siemens Note)


50BF

Breaker failure protection.

74TC

Trip coil supervision relay.

73

Load-resistor contactor is used to shunt or insert a step of load limiting, shifting, or indicating resistance in a power circuit, or to switch a space heater in circuit, or to switch a light, or regenerative load resistor of a power rectifier or other machine in and out of circuit.

87

F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENTS LEGENDS ANSI CODE NUMBER 4 5 6

A
SIMOPRIME A4

=02_LGD +JZ00

(3)G73012-23336-S1002-A 7 8

B2 Sheet 2+ 4 Sh.

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 3

METERING AND MEASUREMENT

BASIC REPRESENTATION

BASIC REPRESENTATION

CONTACTS

CONTACTOR

RECTIFIER A
3

AMPERE METER LED 3 UNITS AMPERE METER LAMP

BUSDUCT CONNECTION

A
NORMALLY OPEN CONTACT SOLENOID/COIL

Archive:

NORMALLY CLOSE CONTACT MECHANICAL INTERLOCK NORMALLY OPEN CONTACT (CLOSED CONDITION) MECHANICAL ACTIVATED

OFF-DELAY COIL

C_FB_EN.etr, 04-11-24

V
3

VOLT METER VARISTOR 3 UNITS VOLT METER CAPACITOR

ON-DELAY COIL

B
CHANGE OVER

A: B: C: D:

file file file file

Hz

FREQUENCY METER

P
HEATER

ENERGY-STORED MECHANISM OPERATED BY HANDLE

CONTACT

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

ON-/OFF-DELAY COIL

PF

POWER-FACTOR METER

MAKE CONTACT DELAYED WHEN CLOSING LATCHED COIL

WATT METER

MOTOR OPERATING MECHANISM MAKE CONTACT DELAYED WHEN DIODE OPENING PLUG AND SOCKET BREAK CONTACT

VAR

VAR METER

Wh

WATT-HOUR METER SINGLE-TARIFF

THERMOSTAT

AMPERE/VOLTAGE SELECTOR

DELAYED WHEN CLOSING

VARh

1: 2: 3: 4:

VAR-HOUR METER SINGLE-TARIFF %HO HYGROSTAT

PROVISION FOR PADLOCKING

BREAK CONTACT DELAYED WHEN RECLOSING

Project: Symbol library Symbol library Symbol library Symbol library

Wh

WATT-HOUR METER DOUBLE-TARIFF L/R LOCAL/REMOTE SELECTOR M

THROUGH VENTILATION

CHANGE OVER CONTACT ON-DELAY

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

FORCED VENTILATION CHANGE OVER CONTACT OFF-DELAY SHIPPING SEPARATION

VARh

VAR-HOUR METER DOUBLE-TARIFF

CS

CONTROL SWITCH

Wh

WATT-HOUR METER EXPORT-IMPORT

POTENTIAL DESIGNATION

(PANEL/PACKING)

VARh

VAR-HOUR METER EXPORT-IMPORT TRANSDUCER/ POWER SUPPLY UNIT CABLE CONNECTION BINARY INPUT

PRESSURE ACTIVATOR

EARTHING/GROUNDING

INFORMATION

SURGE ARRESTOR/ LIMITER

F GENERAL DOCUMENTS LEGENDS


SIMOPRIME A4

Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Name Appr. Norm

30.03.2012 MEYRI TRIANGGONO YUWONO

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

A (3)G73012-23336-S1002-A 7

=02_LGD +JZ00

B3 Sheet 3+ 4 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 =02_LGD / A / B / 4

COMPOSITE REPRESENTATION

COMPOSITE REPRESENTATION

COMPOSITE REPRESENTATION

A
-Q01 M 630A 3-POSITION SWITCH CONNECTED DISCONNECTED EARTHED

C_FB_EN.etr, 04-11-24

Archive:

EARTHING SWITCH
3

- WITH OPERATION BLOCKING COIL - WITH PADLOCKING FACILITY


I >

1-POLE MINIATURE CIRCUIT BREAKER (MCB)

A: B: C: D:

file file file file

WITHDRAWABLE CIRCUIT BREAKER - MOTORIZED SPRING CHARGING MECHANISM - WITH TRUCK MOVEMENT BLOCKING COIL - INTEGRATED VOLTAGE TRANSFORMER - VOLTAGE TRANSFORMER WITH PRIMARY FUSE CORE2 CORE1 P1
I > I > I >

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

P2
3

2-POLE MCB 3 UNITS CURRENT TRANSFORMER - TWO CORES - BLOCK TYPE - SECONDARY TERMINAL AT P2 3-POLE MCB
I > I >

P2 CORE1 P1

3 UNITS CURRENT TRANSFORMER - GENERAL REPRESENTATION - APPLICABLE FOR TOROID TYPE CLOSE OPEN - ONE CORES

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

11

10 9

P1

WITHDRAWABLE VACUUM CONTACTOR - WITH PRIMARY FUSES - WITH CONTROL POTENTIAL TRANSFORMER

CONTROL SWITCH S1 PHASE CURRENT TRANSFORMER S2 P2 - USED IN WIRING DIAGRAM - SPRING RETURN TO CENTER - 3 POLES

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

P1 S1 ZERO CURRENT TRANSFORMER (ZCT) S2 P2 - USED IN WIRING DIAGRAM

REM

LOC

LOCAL-REMOTE SELECTOR SWITCH - WITH PADLOCKING FACILITY - 3 POLES

10

11

WITHDRAWABLE BUS METERING VT - WITH PRIMARY FUSES - WITH SINGLE WINDING VOLTAGE TRANSFORMER

F
Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENTS LEGENDS


SIMOPRIME A4

A (3)G73012-23336-S1002-A 7

=02_LGD +JZ00

B4 Sheet 44 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000330 =03_SLD / A / C / 1

2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL =J02 +J02 =JZ01 =J02 INCOMING PANEL 1

3
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2

4
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3

DESIGNATION LOCATION TYPICAL NAME PLATE

C_FB_EN.etr, 04-11-24

Archive:

BARE COPPER RAL 7035 24kV 50Hz 20kV (BIL) L2

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

file file file file

A: B: C: D:

-Q1

-Q1

-Q1

4 M

-Q0

1250A 25kA

4 M

-Q0

1250A 25kA

4 M

-Q0

1250A 25kA

-F5 L1,L2,L3 3,15A

-F5 L1,L2,L3 3,15A

-F5 L1,L2,L3 3,15A

C
-T5L1,L2,L3 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1:
3

-T5L1,L2,L3 kV 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1: 700/5A 10VA, 5P20
3

-T5L1,L2,L3 kV 20 0.11 0.11 3 3 3 50VA CL.0.5 30VA CL.3P P2 -T1L1,L2,L3 CORE2: 700/5A 10VA, CL.0.5 CORE1: 700/5A 10VA, 5P20 -Y8 P1 CT SECONDARY TERMINAL BOX POSITION LEGEND
3

kV

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

700/5A 10VA, 5P20 P1

CABLE EARTHING SWITCH BLOCKING COIL. (EARTHING CANNOT BE CLOSED OR OPENED WHEN THIS COIL IS NOT ENERGIZED).

P1

PADLOCK FACILITY FOR INDEPENDENT SHUTTER OPERATION HOLE PADLOCK FACILITY FOR EARTHING SWITCH OPERATION HOLE PADLOCK FACILITY FOR TRUCK WITHDRAWABLE OPERATION HOLE PADLOCK FACILITY FOR HV DOOR KEY OPERATION HOLE PADLOCK FACILITY FOR CB (OPEN - CLOSE) OPERATION HOLE

-Q8 2

-Q8 2

-Q8 2

-Y8

-Y8

-Y8

CABLE

12X1Cx500mm CU/XLPE/PVC Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

6X1Cx500mm CU/XLPE/PVC

6X1Cx500mm CU/XLPE/PVC

6X1Cx500mm CU/XLPE/PVC

F GENERAL DOCUMENT SINGLE LINE DIAGRAM


SIMOPRIME A4

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

A (3)G73012-23336-S1003-A 7

=03_SLD +JZ00

C1 Sheet 11 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000267 =04_FVW / A / D / 1

2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL

3
=J02 +J02 =JZ01 =J02 INCOMING PANEL 1

4
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2

5
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3

DESIGNATION LOCATION TYPICAL NAME PLATE

Archive:

140.0

140.0 55.0 55.0

140.0 55.0

140.0 55.0

C_FB_EN.etr, 04-11-24

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

2250

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

file file file file

A: B: C: D:

35

630

800

800
OVERALL LENGTH = 3270

800

800

35
E

WEIGHT (KGs) APPROXIMATELY

725

1095

1095

1095

SCALE 400 200 600 800

NOTES: 1. MEANS PANEL/PACKING FOR SHIPPING SEPARATION.

F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT PANEL FRONT VIEW


SIMOPRIME A4

A (3)G73012-23336-B1004-A 7

=04_FVW +JZ00

D Sheet 11 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000519 =05_FLC / A / E / 1

2
=J01 +J01 =JZ02 =J01 CONNECTION PANEL

3
=J02 +J02 =JZ01 =J02 INCOMING PANEL 1

4
=J03 +J03 =JZ01 =J03 INCOMING PANEL 2

5
=J04 +J04 =JZ01 =J04 INCOMING PANEL 3

DESIGNATION LOCATION TYPICAL NAME PLATE

Archive:

C_FB_EN.etr, 04-11-24

25

file file file file

A: B: C: D:

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

25

C2

LEGEND: C1 PANEL FIXING HOLES ( 22 x 46mm SOCKET )

Project: Symbol library Symbol library Symbol library Symbol library

2500

1: 2: 3: 4:

C2

OPENING AREA FOR POWER CABLE ENTRY FOR REAR ACCESS

1900

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

C3

FLOOR OPENING AREA FOR CONTROL CABLE - BOTTOM ENTRY

C4 C1

SWITCHGEAR END WALL

C3

C1

800

800
OVERALL LENGTH = 3200

800

800 38.5

POWER CABLE

38.5

12X1Cx500mm CU/XLPE/PVC

6X1Cx500mm CU/XLPE/PVC

6X1Cx500mm CU/XLPE/PVC

6X1Cx500mm CU/XLPE/PVC ALL DIMENSIONS ARE IN MILLIMETER.

F A
SIMOPRIME A4

Date Drawn A Rev. FOR APPROVAL Remarks 02.04.12 Date MH Name Appr. Norm

30.03.2012 MEYRI TRIANGGONO YUWONO

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT PANEL FLOOR CUTOUT (3)G73012-23336-B1005-A 7

=05_FLC +JZ00

E1 Sheet 1+ 3 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000419 =05_FLC / A / E / 2

Archive:

500

500 NOTES:

MOST BACK PANEL LINE


C_FB_EN.etr, 04-11-24

1. 2.

DIMENSIONS SHOWN ARE MINIMUM VALUES. MINIMUM ROOM HEIGHT: 2850mm

B
MOST LEFT PANEL MOST RIGHT PANEL

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

file file file file

A: B: C: D:

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

2000

F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT SWITCHGEAR CLEARANCE


SIMOPRIME A4

A (3)G73012-23336-B1005-A 7

=05_FLC +JZ00

E2 Sheet 2+ 3 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000097 =05_FLC / A / E / 3

6
HEXAGON SCREW M10 WASHER 10.5-St-A3L HEXAGON NUT M10-8-A4L

BASEFRAME OF SWITCHGEAR WELDING IN FIXING OPENING OF SWGR BASE FRAME TOP OF FLOOR FINISH U50 PROFILE TOP OF FALSE FLOOR

BASE FRAME OF THE SWITCHGEAR

Archive:

SCREED

MOUNTING PLATE

MIN. 55mm

FLOOR PLATE APPROX. 36mm

C_FB_EN.etr, 04-11-24

BASE CONCRETE MIN. 90mm

MOUNTING CHANNEL (e.p. PROFILE 70x40x2)

EXPANDING ANCHOR WITH HEXAGON CREW & WASHER

file file file file

A: B: C: D:

80.0

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

TYPE 1 FLOOR FIXING WELDED

TYPE 4 FIXING ON FALSE FLOOR

BASEFRAME OF SWITCHGEAR HAMMER HEAD SCREW M16x35-4.6-A3L, WASHER R18 OR PLATE 6x55x70 (18mm DRILLING), HEXAGON NUT M16-8-A4L TOP OF FLOOR FINISH C PROFILE CB 50x30

60.0 50.0

40.0

35.0

NOTE FOR FLOOR FIXING


THE METAL FIXING RAIL SHOULD BE LEVEL AND FLAT IN ACCORDANCE WITH THE TOLERANCE LAID DOWN , THAT IS, 1mm PER M, BUT A MAXIMUM OF 2mm OVER THE TOTAL SWITCHBOARD LENGTH WHERE FOUNDATION RAILS BUTT GAINST EACH OTHER, THEY SHOULD BE WELDED TOGETHER OVER FULL CROSS-SECTION IN ORDER TO SATISFY THE EARTH CONTINUITY REQUIREMENTS. BEFORE LAYING THE FINAL FLOOR SCREED, ENSURE THAT THE RAILS ARE PROPERLY ALIGNED LEVELLED WITH WATER GAUGE (OR SIMILAR DEVICE) BY LAYING UNDER OF STEEL SHEETS AND WELDED TOGETHER THE SUPPPORTING CEMENT FOR FOUNDATION RAILS MUST BE CONTINUOUS AND LOAD BEARING OVER THE TOTAL RAIL LENGTH. IF EARTHQUAKE RESISTENT INSTALLATION IS REQUIRED, THE COMPENSATING PLATES, FOUNDATION RAILS AND THE SWITCHBOARD STRUCTURE MUST BE WELDED TO ONE ANOTHER AND TO A FLAT STEEL PLATE ANCHORED INTO THE BASE CONCRETE (NELSON ANCHOR) AS DESCRIBED THE DETAILS RELATING TO FOUNDATION RAILS, COMPENSATION PLATES AND METHOD OF SECURING THE SWITCHBOARD ARE NOT THEN VALID, THEY SHOULD BE MODIFIED TO SUIT THE METHOD OF FIXING FLOOR FINISH : THE FLOOR FINISH SHOULD BE SUCH THAT IT WILL WITHSTAND THE LOADS STATED THE SPECIFICATIONS. FOR SWITCHGEAR ROOMS A FLOOR FINISH, LOAD BEARING QUALITY AT LEAST RATED COMPRESSIVE STREGTH 45N/mm, FLEXURALE TENSIDE, GRINDING WEAR 9cm/50cm IS NECESSARY. THE UPPER SURFACE OF THE FLOOR FINISH OR SCREED SHOULD NOT BE HIGHER THAN THE UPPER SURFACE OF THE FOUNDATION RAILS.

MIN. 55mm

SCREED

80.0 30.0

MOUNTING PLATE BASE CONCRETE MIN. 90mm

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

EXPANDING ANCHOR WITH HEXAGON CREW & WASHER

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved


80.0

13.0

30.0

145.0

MOUNTING PLATE DETAIL TYPE 2 FLOOR FIXING SCREWED

FLOOR LEVEL

+0mm -0.5mm M12 SPRING NUT

44

NOTE FOR FIXING ON FALSE FLOOR


THE SUPPORT FRAME SHOULD BE LEVEL AND FLAT WITH TOLERANCE 1mm PER M, BUT A MAXIMUM 2mm OVER THE TOTAL SWITCHBOARD LENGTH IF EARTHQUAKE RESISTENT INSTALLATION IS REQUIRED, THE SUPPORT FRAME AND THE SYSTEM PORT MUST BE WELDED TOGETHER. EVEN IT WILL BE CONSIDERED THE DIAGONAL STAYS FROM THE SUPPORT FRAME. THE DETAILS RELATING TO SUPPORT FRAME AND SYSTEM FIXING ARE NOT THEN VALID, THEY SHOULD BE MODIFIED TO SUIT THE METHOD OF FIXING.

44

CEMENT FILLING FOUNDATION CHANNEL (UNISTRUT)

THIS DRAWING IS FOR REFERENCE ONLY. ACTUAL CIVIL WORK IS NOT SCOPE OF PT. SIEMENS INDONESIA

TYPE 3 FLOOR FIXING SCREWED WITH SPRING NUT


Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

F
ALL DIMENSIONS ARE IN MILLIMETER.

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT FIXING DETAIL


SIMOPRIME A4

A (3)G73012-23336-B1005-A 7

=05_FLC +JZ00

E3 Sheet 33 Sh. 8

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000337 =06_SEC / A / F / 1

LEGEND
A1 PANEL NAMEPLATE

A
A2 TRUCK INSPECTION WINDOW

Archive:

FRONT VIEW

SIDE VIEW
395

A3

HV-DOOR LOCK ACCESS HOLE

C_FB_EN.etr, 04-11-24

A4

MANUAL SPRING CHARGING ACCESS HOLE

140.0 55.0

A1 A5
B2

MANUAL CB ON / OFF ACCESS HOLES HANDLE FOR OPENING OF CB-COMPARTMENT DOOR INSPECTION WINDOW FOR SPRING CHARGING INDICATOR AND OPERATING COUNTER TRUCK MOVEMENT ACCESS HOLES

B1

697.5

A6

A: B: C: D:

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

file file file file

A7

A8 A2 A3 FRONT OF A6 A7 A9

CABLE EARTHING SWITCH ACCESS HOLE

2250

A5

A4

B3

PANELS

C
A8

B4

B1

LOW-VOLTAGE COMPARTMENT

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

A9

B2

BUSBAR COMPARTMENT

B3

CIRCUIT BREAKER COMPARTMENT

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

800

25

1900

38.5

B4

CABLE COMPARTMENT

PANEL OPENING

C1

PANEL FIXING POINTS (46 x 20mm SOCKET)

50

310

290

445 105

775

30

C2

OPENING AREA FOR BOTTOM POWER CABLE ENTRY

400

C3 FRONT OF

OPENING AREA FOR BOTTOM CONTROL CABLE ENTRY

590

C1

C2

C1

C1 C3

40

25

105

180

50

1900 1963.5

38.5

800

PANELS

F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT PANEL CONFIGURATION =JZ01 - INCOMING FEEDER 4 5 6

A
SIMOPRIME A4

=06_SEC +JZ00

(3)G73012-23336-B1006-A 7 8

F1 Sheet 1+ 2 Sh.

1
ELCAD-Version 7.3.2 SP2 Last used: 02.04.12 File name: 000216 =06_SEC / A / F / 2

LEGEND
A1 PANEL NAMEPLATE

A
A2 -

Archive:

FRONT VIEW

SIDE VIEW 396.5

A3

C_FB_EN.etr, 04-11-24

A4

140.0 55.0

A1 A5 -

B4

B2

B1

A6

A: B: C: D:

F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro Translate Translate Translate Translate

file file file file

A7

A8

FRONT OF PANELS

A9

B1

LOW-VOLTAGE COMPARTMENT

Project: Symbol library Symbol library Symbol library Symbol library

1: 2: 3: 4:

B2

BUSBAR COMPARTMENT

B3

D CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved

800

25

600

1900

38.5

B4

CABLE COMPARTMENT TOP ENTRY

PANEL OPENING 50

C1

PANEL FIXING POINTS (46 x 20mm SOCKET)

50 105

290

1045

775

30

C2

OPENING AREA FOR TOP POWER CABLE ENTRY

400

C3 FRONT OF

OPENING AREA FOR BOTTOM CONTROL CABLE ENTRY

590

C2

C1

C1

C1 C3

40

105

180

50

25

600 2563.5

1900

38.5

800

PANELS

F
ALL DIMENSIONS ARE IN MILLIMETER. Date Drawn 30.03.2012 MEYRI TRIANGGONO YUWONO

A Rev.

FOR APPROVAL Remarks

02.04.12 Date

MH Name

Appr. Norm

JATIM TAMAN STEEL 2 CV. SEMBRANI MITRA TEKNIK 20kV SWITCHGEAR Orig./Repl.f./Repl.by 3

GENERAL DOCUMENT PANEL CONFIGURATION =JZ02 - CONNECTION PANEL 4 5 6

A
SIMOPRIME A4

=06_SEC +JZ00

(3)G73012-23336-B1006-A 7 8

F2 Sheet 22 Sh.