ATS - Automatic transfers of switches

AS

Technical applications Automatic systems for commutations of sources

A.S.S. 1

March 2002

e
When takes place a shut down in the electric net, the automatic transfers of sources allow to assure the continuity of service of an installation, with a minimum time of interruption, by means of the disconnection of the circuits fed by the source of Normal supply, and their immediate connection to another source that is available. The connection and disconnection maneuver of the sources can be carried out by means of contactors, switches or breakers. An advantage for the breakers are that allows to protect appropriately the lines that they feed. Usually, the installation is connected to the net that is the Normal source, by means of a breaker, while, by means of another breaker it can be connected to the Auxiliary source or of aid that is usually another net or a generator. Some times, the Normal supply is carried out by means of two transformers, for what its are three the breakers that must intervene in the maneuver. The auxiliary source not always has enough power to feed all the services, in this case the breakers can be of different sizes to proceeds feed only the preferable circuits. Usually the automatic transfer begins when a voltage monitor relay detects a failure in the Normal supply, if the Auxiliary source is a generator, it should start. An automatic controller takes charge of making all the necessary manoeuvre. The controller will only carry out the manoeuvre when the Auxiliary tension is available, according to the pre-established program, in the possible briefer cheats, not being able to be in some moment connected both , a mechanical interlock among the switches impedes this possibility, that makes unavoidable the step for a zero of tension. Besides the mechanical interlock, the controller incorporates an electrical interlock among the drives, to prevent that a mistaken order can be carried out. The Automatic Transfers Switches are indicated in Hospitals, industrial facilities, commercial buildings, public buildings, shows, etc, where a supply lack can causes serious damages to people, economic losses or panic situations. Delivery: The system can be delivered: - As a totally assembled rack with all its accessories, totally wired to terminal connections numbered and ready to be connected to the automatic Controller. - As a totally assembled rack, included the Controller, into an enclosure for wall or floor mounting, according to the size. Each switch is delivered with identifying tags as Normal Source and Auxiliary Source. Up to 1250A, the Normal Source is mounted on the left, and on the top for ACB delivered into an enclosure, other configurations can be delivered upon request.

ATS - Automatic transfers of switches


Index
3 4 5 9 15 General characteristics Types of mechanical interlocks Description and wiring Dimensions Codes & Prices

AS

A.S.S. 2

March 2002

e
The switches

ATS - Automatic transfers of switches


The controllers

AS

The breaking capacity and the thermo-magnetic protection of the breakers should be chosen in function of the characteristics of the feeder sources and the circuits to be protected. E.g.: A high breaking capacity breaker, with standard trip unit can be used for the transformer side, while a standard breaker with low magnetic trip unit can be used for the generator side, or without trip unit, for the connection of distribution bars. Any combination among them is available. To avoid that, during the net supply, microcuts and small incidences may causes an unnecessary disconnection, the switch in the Normal source opens by means of shunt trip (coil with mechanical-latch in the case of contactors), to assure that the manoeuvre only begins when the alternative source is really available; while, if the auxiliary source is a group, the generator switch is disconnected by means of undervoltage coil to assure that is disconnected when the generator is stopped or when some alarm is activated (oil pressure, temperature, etc). The transfers carried out by means of switches Dilos dont incorporate thermo-magnetic protection, neither they require opening coils for their maneuver. Characteristics: Breakers Record, standard delivery Ratings In A 160 250 400/630 800 Max. operating voltage V 690 690 690 690 Breaking capacity (1) kA 30 35 35 50 Control tension 110 or 230V 50/60 Hz Max. consum. of drives VA 460 460 250 250 Total switching time S 0,7 0,7 0,7 0,7
(1) Other breaking capacity under request.

To assure that the manoeuvre is carried out with success, it is necessary to keep in mind the mechanical characteristics and necessary times for the manoeuvre of the electric controls that drives the switches, to verify that they can complete the order, to avoid overlaps and to repeat them if takes place a failure. These, and other complementary functions, the automatic controller carries out them according to an established program. Three types of controllers exist according to the type of switches and necessity of complementary functions. The model EPlus allows controlling the state of the generator and the disconnection of non-priority loads. It also exists a model EPlus for the manoeuvre of three switches Characteristics Models E & A Model EPlus Control tension the same as that of the switches Consumption 18 VA 18 VA Main voltage monitor Optional Optional Adjust start delay Optional 0,1 to 60 sec. Adjust of gen cooling time 0,1 to 60 min. Adjust retransfer delay Fixed: 10 sec. 0,1 to 15 min. Remote stop order Incorporate Incorporate Remote transfer order Optional Incorporate Rem. Retrans. retained order Optional Incorporate Voltage for disconnect loads Incorporate Voltage for restore loads Incorporate Communication RS 232/ASCII, 485/SNP

1250 690 60 250 0,7

Functional diagram
In 3 ATS the diagram is adapted to selected type Automatic OL/SC trip
AT stays on stand-by blinking lit

Breakers M-PACT Ratings In A 400/630 800/2500 3200/4000 Max. operating voltage V 690 690 690 Breaking capacity kA S 50 50 50 N 65 65 65 H 80 80 Control tension 110 or 230V 50/60 Hz Max. consum. of drives W 760 760 750 Total switching time S 0,7 0,7 0,7 Switches Dilos Ratings In Max. operating voltage Making capacity Icm Control tension Max. consum. of drives Total switching time

Blocked

Manual

Mains Voltage available Gen. breaker "ON" Waits 10" Opens Gen. breaker
Mains b. "ON" waits 300" Stops Gen

Start Generator

Mains voltage defaults Gen voltage available

P. B. "Open Mains"

P. B. "Open Gen"

P. B. "Close Mains"

P. B. "Close Gen"

waits 0,5" Gen. breaker "OFF" Closes Mains breaker Opens Mains b. Mains b. "OFF" Closes Gen breaker. Open Open Mains Gen breaker. breaker. Gen Mains breaker. breaker. "OFF" "OFF" Closes Mains breaker. Closes Gen breaker.

V kA W S

800/1250 1600 2000/2500 690 690 690 73,5 105 105 110 230V 50/60 Hz 800 800 800 3 3 3

Three trials

Fault blinkin lit

Three trials

Fault blinkin lit

A.S.S. 3

March 2002

e
Mechanical interlocks
The automatic controller incorporates an electric interlock among the drives and coils of the switches, however, if during a lack of tension is carried out an incorrect manual manoeuvre, a coupling of the sources could take place. The mechanical interlock among the switches impedes this possibility. The mechanical interlock depends of the type of wanted manoeuvre and the number of switches: two or tree.

ATS - Automatic transfers of switches

The moulded case switches are delivered with the mechanical interlock mounted, according to the type of wanted manoeuvre. The transfers by means of contactors or switches Dilos only admit the type A. The controller is delivered programmed according to the type of wanted manoeuvre. The charts show the open state (0) or closed (1) of the switches (B), as there is or not tension (+U; -U) in the sources, when the controller works in Automatic mode. In Manual position, any closed switch can be open up.

AS

U1

G U2

B1

B2

Type A Feed from a transformer and a generator or emergency transformer. Only can close the switch whose tension is available, being that of the Normal Net the preferable one. So that to closes a switch it is necessary that the other one is open.

B1 Stop + U1 - U1 + U2

B2

0 1 0

0 0 1

U1

U2

G U3

B1

B2

B3

Type B Feed from a transformer, with another of emergency and another one generator or emergency transformer. The sources cannot be set in parallel. Only can close the switch whose tension is available, being that of the Normal Net the preferable one. So that to closes a switch it is necessary that the other both are open. Type C Feed independent from two transformers that cannot be set in parallel. Each transformer can also feed to the other circuit. The switch of coupling bars only can close when some of the other two is open.

B1 Stop + U1 - U1 + U2 -U1-U2+U3

B2

B3

0 1 0 0

0 0 1 0

0 0 0 1

B1 Stop + U1 + U2 - U1 + U2 + U1 - U 2

B2

B3

U1

U2

B1 B3

B2

0 1 0 1

0 1 1 0

0 0 1 1

U1

U2

B1

B3

B2

Type D 1) Independent supplies that cannot be set in parallel. One of the transformers can succour to the other circuit. The coupling bars switch only can close when the other ones are both open.

B1 Stop + U1 + U2 - U1 + U2 + U1 - U 2

B2

B3

0 1 1 0

0 1 1 0

0 0 0 1

U1

U2

G U3

B1

B2

B3

2) Feed from two transformers that can be set in parallel, and a generator or emergency transformer. The emergency switch only can close when the other ones are both open.

B1 Stop + U1 + U2 + U1 + U 2 -U1-U 2+U3

B2

B3

0 1 1 1 0

0 1 1 1 0

0 0 0 0 1

A.S.S. 4

March 2002

e
Automatic controller
Description

ATS - Automatic transfers of switches

1 2 3 4

U1 B1

U2 B2

5 6 7

The controllers rack is mounted on a plate colour RAL 7032, it is designed to be mounted, directly or by means of a hinged cover, in our enclosures Modula and VP. The controllers components are standard products of our catalogue, what makes them compatible with another pushbuttons and signalling lights of the panel. The Plc, of the series VersaMax Micro, allows the access to the big control benefits and communication of this series. The frontal includes the schema of the commutation and tags in the pushbuttons indicating its function and basic instructions. The schema and the texts in the tags can be delivered according to the users necessities. 1) and 5) Orange light that indicate respectively that the tension U1 in Net, or U2 in the auxiliary source, is available. 2) and 6) Green illuminated push-button that indicate: Light permanently on: The corresponding switch B1 or B2 is open. Blinking light: Breaker unable to close, mechanical failure, or transfer from generator to Mains under way. 3) and 7) Red illuminated push-button that indicate: Light permanently on: The corresponding switch B1 or B2 is closed. Blinking light: Breaker tripped on OL. 4 Selector with key that allows to chose the operation mode: Automatic, Manual or Blocked. The key can be extracted in any of the three positions, what allows avoiding unauthorised persons the manipulation if the key was extracted in automatic or blocked position. In anyone of the three positions: - An overload (OL) or short-circuit (ST) trip of any breaker prevents any operation until the failure is acknowledged manually and erased from the memory of the controller. -The controller can admit an Stop Emergency remote order by means a contact free of potential of an alarm pushbutton or on an Rcd relay, the system maintains open all the breakers as long as this contact is closed. EPlus: A green Led in the Automatic position indicates that the Plc is running correctly.

Operation Automatic mode: It ignores the orders coming from the pushbuttons - Transfer Normal (or Mains) to Aux (or Gen) When a failure is detected on net tension, system will remain on standby mode with B1 closed (ON) and B2 open (OFF). EPlus, when the Mains voltage disappears, give the start order to the generator. This order can be delayed up to 60 seconds. As soon as the auxiliary voltage is available, lights 5) and the transfer begins at B2. If closing of B2 is not successful, the system will repeat the reset/close order to this breaker up to three times. If the breaker cannot close after these attempts, the fault is memorized and signalled by a blinking lit on 6). - Retransfer to Normal: While running with generator power, when the Mains voltage returns, the system waits for 10 sec. before starting the retransfer to Mains. EPlus: allows a delay of this order up to 15 minutes, to avoid frequent run-stop and to assure a minimum of time working with generator. This delay is signalled by means of blinking lit on 2) and 7), to indicate that B2 will open up, and B1 will close. The timing is restarted after a new failure of U1, and if disappears U2, the transfer is carried out immediately. After the delay, the controller gives the order to open B2 and later that of closing B1. If this didnt close, the system will repeat the reset/close order to this breaker up to three times. If the breaker cannot close after these attempts, the fault is memorized and signalled by a blinking lit on 2), and the system will be connected to the Auxiliary source again while it is available EPlus keep the generator running during the whole process, until a security and cooling time, adjustable up to 60 minutes after the retransfer has been completed. Manual mode: It accepts the orders of the pushbutton, maintaining the electric interlock. 2) and 6) Pushbuttons to open up and resets breakers B1 or B2. 3) and 7) Pushbuttons to close breaker B1 or B2, if the other one is open and the corresponding tension is available. - Transfer Normal (or Mains) to Aux (or Gen): Pressing 7), the breaker B2 will close if 5) is lighting and breaker B1 is open. EPlus: Pressing 7) will take care of giving the order to start the generator, and wait for the generator to start. As soon as the generator voltage becomes available, opening the Mains breaker (if it is closed) and close Generator breaker. During waiting time, the operation can be cancelled placing the selector key 4) in blocked mode. - Retransfer to Normal: Pressing 3), the breaker of Net only will close if the breaker B2 is open. The manoeuvre can be carried out if U1 or U2 are available. EPlus will take care of previously opening the breaker B2 (if it is closed), before closing B1. Blocked mode: It ignores the orders coming from the pushbuttons and the switches dont carry out manoeuvre some, maintaining the thermomagnetics protections. All the alarms, memories and timers are set to zero.

AS

A.S.S. 5

March 2002

e
Wiring

ATS - Automatic transfers of switches

10

EPlus, besides these functions, can incorporate a voltage monitor relay of the net tension and activate some functions by means of incorporate terminals that are relative to the emergency source: - Terminals 23 and 24: Return to Net in wait: EPlus allows to adjust, up to 15 minutes, the time of wait before the return to Net. However, if the control of the moment of retransfer is wanted, to avoid that the retransfer take place in an unwanted moment (with the rising step for zero : public shows, hospitals, calculus centres), or to maintains the connection to the group a time, determined by a timer, in order to avoid transfers and retransfer too followed. The Return to Net in wait stays while the connection 23-24 exists and the auxiliary tension is available.
+
7

AS

9) Protection mcb marked as Normal and Aux, to incoming tension (127 or 220V, 50/ 60Hz) respectively from up stream of Normal and Auxiliary breakers, to feed the system and to carry out the manoeuvres.

+
15 MIN 0,1

30

0,1

60 MIN

TIME FOR RETURN TO NET

TIME FOR STOP GEN

AUX

17 18 19 20 NORMAL

DELAY ORDER FOR START GENERATOR

This controller doesnt need auxiliary source. The loss of tension of Net doesnt imply the opening of the switch that will remain closed until the beginning of the transfer. The system keeps standby transferring the load to the first available source. 10) Terminals connection box: - Terminals 1 to16: Signalling and manoeuvres of the switches. The switches are delivered with all their accessories connected to terminals numbered for their connection to those of same numeration in the box. See following pages. - Terminals 17, 18 and 19, 20: Tension of Net available and Auxiliary Tension available They are delivered connected by means of a black and red wire. This connection should be removed and connect to the contacts of a voltage control relays of Tension of Net and of Auxiliary Tension, respectively.

Generator alarms Monitor Volt Generator Monitor Volt. Net

17 18 19 20

When the auxiliary source is a generator, usually, these relays are incorporated in the automatic system of starting generator. Usually its also included the systems for control of frequency, generator excitation, oil pressure, temperature, and other mechanical securities. These relays are accessible by means two contacts free of potential that closes or opens up as they are or not available the respective tensions. - Terminals 21 and 22: Remote Stop order. To connect the contact of a pushbutton (with retention) of Stop, or an Rcd relay. The breakers will stay open while the terminals 21-22 were connected.

- Terminals 23 and 25: Transfer to Generator: EPlus allows to temporise, up to 1 minute, the order of start the generator after a failure of the Net. But sometimes, in case of critical moments, before a possible failure in the supply (Net too loaded, public shows, connections in live), it is preferable to feed the installation by means of the group. If the terminals 23-25 are connected, the system gives the start generator order and carries out the transfer as soon as its tension is available. This forced step to the auxiliary supply maintains while the connection 23-25 exists and the auxiliary tension is available. - Terminals 23 and 26: Reconnection of non high-priority loads: Some times it is wanted transfer to the auxiliary source with reduced load. The breakers that feed to the non-priority loads can be disconnected, before the transfer, by means of trip coils connected to the terminals 30 and 31. However, if the lack of normal supply is prolonged, it can be necessary to reconnect these loads (cooling cameras), in function of a temperature indicator, a timer, a consumption monitor, etc., the connection 23-26 makes that a voltage pulse appears in the terminals 32-33 to feed the electric controls of closing of the breakers that it is wanted to reconnect. - Terminals 23 and 27: Reserved for special applications. - Terminals 28 and 29: Start and stop the generator. These terminals correspond to a contact (0,6A/240V maxi.) that the system closes or opens up when needs that the generator is in progress or not. The groups usually equip some terminals to allow this remote starting. The start, before a failure of Net, can be temporised up to 1 minute, and the stop up to 1 hour, to prevent possible new faults of the Net, and to assure a cooling time. - Terminals 30 and 31: Tension for auxiliary devices." Terminals with same tension that those input by AUX and NORMAL, to feed auxiliary devices: Rcd relays, signalling lights, etc. - Terminals 30 and 32: Pulse of tension for disconnection of non prioritary loads. Before closing generator breaker, in these terminals appears, during 5 seconds, same tension that of feeding, to feed tripping coils in the switches that feed non prioritary loads, to disconnect them before the transfer. - Terminals 30 and 33: Pulse of tension for reconnection of non prioritary loads. Five minutes after retransfer to Net, in these terminals appears, during 5 seconds, same tension to that of feeding, for to close the switches that feed the non prioritary loads that were disconnected before the transfer. + Optional: - Terminals 34 and 35: to feed the system by means of an external source (UPS, batteries, etc). To consult.

A.S.S. 6

March 2002

e
Wiring to Record , Spectronic and M-PACT breakers

ATS - Automatic transfers of switches

12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11

The breakers are delivered with their accessory wired to a terminal block to connect those of same numeration of the box of connections of the controller. The terminals 17/18 and 19/20, are delivered connected, the bridge should be removed to connect the contacts of respective monitor of the Normal and Auxiliary tension, or the contacts of available tension in the generator. The terminals 23 at the 33, in the shady area, correspond to the automatism type Eplus.

In the terminal board attached to the breakers, there are also terminals O, A, C. There are auxiliary volt free contacts in the Main (Net) and Aux. (Generator) breakers.
C A

AS

2 3

4 5

6 7

8 9

10 11 12 13 14

15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

30 31

30 32

30 33

U. AUX.

U. NORMAL

12

14 98

2 4

1 C1 C2

3 4

12

14 98

D1

1 C1

3
RECONNECTION OF NONPRIORITARY LOADS

M EA C
11 95 11 95

MV*
D2

M
4

EA* C
MONITOR TENSION NORMAL MONITOR TENSION AUXILIAR STOP
TRANSFER TO GEN VOLTAGE FOR AUXILIARY DEVICES START AND KEEP RUNNING GENERATOR ORDER RECONNECTION OF NON PRIORITARY LOADS

C2

MAINS BREAKER

GENERATOR BREAKER

* If EA instead of MV No connect 5 and 14 in sizes 160 y 250A

Breakers Record

2 3

4 5

6 7

8 9

10 11 12 13 14

15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

30 31

DISCONNECTION OF NON PRIORITARY LOADS

RETRANSFER RETAINED

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

30 32

30 33

U. AUX.

U. NORMAL

12

14 98

G H F

C1 C2

E F

12

14 98

D1

G H

C1

E
RECONNECTION OF NONPRIORITARY LOADS

M EA C
11 95 11 95

MV*
D2

M
F

EA* C
MONITOR TENSION NORMAL MONITOR TENSION AUXILIAR STOP
TRANSFER TO GEN VOLTAGE FOR AUXILIARY DEVICES START AND KEEP RUNNING GENERATOR ORDER RECONNECTION OF NON PRIORITARY LOADS

C2

MAINS BREAKER

GENERATOR BREAKER * If EA instead of MV

Breakers Spectronic SP

2 3

4 5

6 7

8 9

10 11 12 13 14

15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

30 31

DISCONNECTION OF NON PRIORITARY LOADS

RETRANSFER RETAINED

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

30 32

30 33

U. AUX.

U. NORMAL

12

14 98

U1 U2

C1 A1

12

14 98

D1

U1

C1 A1

M EA EE
11 95 C2 A2 11 95

MV*
D2

M
U2

EA* EE
RECONNECTION OF NONPRIORITARY LOADS

MONITOR TENSION NORMAL

MONITOR TENSION AUXILIAR

STOP

TRANSFER TO GEN

VOLTAGE FOR AUXILIARY DEVICES

MAINS BREAKER

GENERATOR BREAKER * If EA instead of MV

Breakers Spectronic S y L

1 2

3 4

5 6

7 8

9 10 11 12 13 14

15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

START AND KEEP RUNNING GENERATOR ORDER

30 31

30 32

30 33

RECONNECTION OF NON PRIORITARY LOADS

C2 A2

DISCONNECTION OF NON PRIORITARY LOADS

RETRANSFER RETAINED

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

U. AUX.

U. NORMAL

C2

C8 B8

B9 B12 B14

C2

C8 B8

B15

B9

B12 B14

M ST CC
C1 C7 B7 B10 B11 B13 C1 C7

MV*
B7 B16 B10

ST* CC
RETRANSFER RETAINED

STOP

VOLTAGE FOR AUXILIARY DEVICES

MONITOR TENSION NORMAL

MAINS BREAKER

GENERATOR BREAKER * If EA instead of MV

Breakers M-PCT

START AND KEEP RUNNING GENERATOR ORDER

A.S.S. 7

RECONNECTION OF NON PRIORITARY LOADS

MONITOR TENSION AUXILIAR

TRANSFER TO GEN

B11 B13

RECONNECTION OF NONPRIORITARY LOADS

DISCONNECTION OF NON PRIORITARY LOADS

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

March 2002

e
Wiring Wiring to switches Dilos CO-MO
The switch has a numbered connector 1 to 24, for the wiring to terminals of the controllers with same numeration. The tension of standard feeding is 220Vca, for other tensions (110, 380 Vca, or 24Vcc), to consult.

ATS - Automatic transfers of switches

AS

13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12

MONITOR TENSION AUXILIAR

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

MONITOR TENSION NORMAL

Terminals 2, 3 and 4, are of contacts with exit at 220 (or 127) Vca (maxi. 1A), for, if wants, to connect a state signalling, at distance.

STOP

22 21 20 19 15 13 10 9 8 7 6 5 1

31

U. AUX.

U. NORMAL

33 32 31 30 29 28 27 26 25 22 21 20 19 15 13 10 9 8 7 6 5 1

Mains Closed

Open

Aux Closed

Controller type A

Wiring to contactors CL
33

A1

A2 01 01

A1

A2 33 31
BRLL11

The switch has a terminals block numbered 1 at 22, for the wiring to the terminals of the controllers same numeration. The tension of standard feeding is of 220Vca, for other tensions (110, 380 Vca, or 24Vcc), to consult.

31
BRLL11

E1

RMLFN

CL

E2 BEL02 02 02 A2

CL AUX.
A2

1 6 8 10 20 5 7 9 21 22

32 34

MAINS

32 34

MONITOR TENSION AUXILIAR

INCOMING VOLTAGE FROM AUX. SOURCE

INCOMING VOLTAGE FROM MAINS SOURCE

STOP

MONITOR TENSION NORMAL

22 21 20

9 8 7 6 5 1

U. AUX.

U. NORMAL

33 32 31 30 29 28 27 26 25 22 21 20 19 15 13 10 9 8 7 6 5 1

Controller type A

A.S.S. 8

March 2002

2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 210987654321098765432109876543212109876543210987654321098765432 2109876543210987654321098765432121098765432109876543210987654321 2109876543210987654321098765432121098765432109876543210987654321 1 2109876543210987654321098765432121098765432109876543210987654321

Controller: Dimensions

Controller IDS, front view

6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 654321098765432109876543212109876543210987654321098765432 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 6543210987654321098765432121098765432109876543210987654321 1 6543210987654321098765432121098765432109876543210987654321

Controller 3IDS, up view

Controller 3IDS, front view

Controller IDS type E, up view

Controller IDS type E Plus, up view

430

520

170

110

195

170

195

ATS - Automatic transfers of switches

Cut-out for panel or door mounting

A.S.S. 9

Cut-out for panel or door mounting

504

414

4x

4x

March 2002
179 179

AS

e
IDS Record : Dimensions

ATS - Automatic transfers of switches

D160 3P D250 3P
8 40 200 160 40 21 8 8 40 200 160 40 8 8 8 21

D160 4P D250 4P

AS

10

9,5 114,5 165,5 270,5 280 300

44,5

149,5 165,5 270,5 296 335

35

85 232

112

D400 3P D400 4P
21 6,5

275 210 140 6,5

66

196 214 410 430

11

113,5 274,5

150

D400 3P D400 4P

D250 3P D250 4P

275

240 200

78 40

146 461 600 630

40

113,5 303,5

150

A.S.S. 10

March 2002

e
IDS Record : Dimensions
D630/800 3P D630/800 4P
6,5

ATS - Automatic transfers of switches

AS

11

275 210 140 6,5

125

291 309 600 620

11

113,5 274,5

150

D630/800 3P D630/800 4P
6,5

D400 3P D400 4P

275 210 140 6,5

125

291 380 600 620

11

113,5 274,5

150

D630/800 3P D630/800 4P

D250 3P D250 4P

275

240 200

78 40

111

461 600 630

40

113,5 303,5

150

A.S.S. 11

March 2002

e
Interruptores Record : Dimensions
D1250 3P D1250 4P

ATS - Automatic transfers of switches

AS

12
13

351 236 136

13 7 140

312 318 630 670

55 28

141,5 400,5

176

D1250 3P D1250 4P

D400 4P D630/800 3P D630/800 4P

351 240 200

40

40

130

291 305

287 600 630

40

141,5 357,5

176

D1250 3P D1250 4P

D250 3P D250 4P

351 240 200

78 40

130 291 426

287 40 600 630 141,5 357,5

176

A.S.S. 12

March 2002

e
Breakers M-PACT : Dimensions

ATS - Automatic transfers of switches

AS
Fixed

13

Radio mnimum: 120

Radio mnimum: 120

Witdrawable

Min. betwen breakers: 600

Min. free under the cardwell

Min. free under the cardwell

Radio mnimum: 120

Radio mnimum: 120

A.S.S. 13

Min. betwen breakers: 600

March 2002

e
Switches Dilos CO-MO : Dimensions

ATS - Automatic transfers of switches

AS
Dilos 6S MO 800/1250A Dilos 7S MO 1600A

14

Dilos 8S MO 2000A

Dilos 8S MO 2500A

A.S.S. 14

March 2002

e
Automatics transfers with Record: Ordering codes / prices
1)

ATS - Automatic transfers of switches

2 or 3 switches that intervene in the transfer: breakers or switches, with all the
electric accessories and interlocks included.

AS
Switch

15

Breaker
In (A) 40 63
Ratings 160 250 400 630 800 Tension maxi. Ue V 690V Breaking capacity kA 30 35 35 35 50 Adjust thermal to Ir 0,75 at 1 0,8 at 1 Adjust magnetic 40 8 at 12 63 7 at 12 100/125 6 at 12 160 5 at 12 200 5 at 12 250 5 at 10 320 6 at 12 400 5 at 12 500 5 at 10 630 5 at 8 800 5 at 8 1000/1250 Other breaking capacity, or trip units, under request 1250 60 0,8 at 1

3P - 3D 872252 1016,34 872254 1016,34 872256 1052,88 872258 1077,22 872260 1119,84 872264 1492,70 872266 1593,91 872270 2354,83 872272 2480,38 872276 2733,73 872278 2851,53 872282 3741,03 872286 4863,98 872288 5180,65 Overprices:

4P - 3D 872253 872255 872257 872259 872261 872265 872267 872271 872273 872277 872279 872283 872287 872289 1076,62 1076,62 1124,10 1155,78 1211,13 1709,43 1843,03 2690,43 2815,98 3135,45 3253,25 4322,57 5658,39 5977,23

3 Poles

4 poles

100 125 160 200 250 320 400 500 630 800

872262 872268 872274 872280 872284 872290

1010,33 1399,31 2173,86 2477,34 2983,09 4116,92

872263 872269 872275 872281 872285 872291 872220 872221 872222 872223

1068,81 1586,10 2509,47 2879,06 3564,63 4913,50 770,56 1795,16 2262,93 to consult

5 at 10

1000 1250

Standard schemas. It can be delivered with the auxiliary source as a transformer, or on the left, if it is indicated when ordering. Types B and D2 Type A N G T1 R1 T2 R2 TG G

2)

Witdrawable execution Witdrawable execution Witdrawable execution Other types or trip unit:

Up to 250 A: 400 A: 630 A:

Controller. According to the type and control voltage:


Control E Plus Tipo 220V 872140 1362,79 872230 2044,19 110V 872141 872235 1362,79 2044,19 872052 150,00 220V 872240 1093,84 Control E 110V 872241 1093,64

Type D1 T1 R1 Ac T2 R2 T1 R1

Type C T2 R2

A B, C, D

Overprice: Controller with Main monitor control voltage incorporated


Ac

Options:
Hinged cover. For mounting in Modula enclosures Modula IP 43 Modula IP 55 Enclosure. Equipped with all the previous components installed and wired. Up to 400 TO: Up to 1250 TO: Up to 2500 TO: Overprices: Wall mounting polyester cabinet: 750 x 750 x 320. Wall mounting metal cabinet 1250 x 800 x 400. Metal enclosure 2000 x 800 x 750. Interlock among door and Main switch Generator starter and monitoring equipment Glazed door in metal enclosure 872136 872137 872143 872188 872146 935,05 1322,17 2878,97 275,62 881,14 90,00 883508 872350 33,24 33,24

A.S.S. 15

March 2002

e
Automatic transfers with M-Pact breakers: Codes
1)

ATS - Automatic transfers of switches

2 or 3 switches:
The code includes the switch without protection (the protection unit is requested separated), with all the electric accessories and mechanical interlock (1).

AS

Fixed
In (A) Icu: 50 kA
800 1000 1250 1600 2000 2500 3200
600 mm

Withdrawable
4 Poles 3 Poles 4 poles

16

3 Poles

872304 872306 872310 872314 872318 872322 872326 872330

4.518 4.869 4.999 5.455 6.783 8.567 10.528 12.920

872305 872307 872311 872315 872319 872323 872327 872331

5.434 5.810 6.104 6.738 8.335 10.022 12.930 16.039

872334 872308 872312 872316 872320 872324 872328 872332

5.369 5.702 6.037 6.903 8.556 10.224 13.559 15.541

872335 872309 872313 872317 872321 872325 872329 872333

6.496 6.972 7.534 8.496 10.547 12.396 16.129 19.250

4000

Icu: 65 kA
800 1000 1250 1600 2000 2500 3200 4000
(1): For transfers Type A, the standard delivery includes a rod mechanical interlock for breakers placed in vertical position at a distance of 600mm. For other dispositions or types, when ordering it should be indicated the distances and position of the switches to calculate the longitude of the cables interlock. Protection unit M-PRO 17 LT pickup adjust, class 20 ST adjustST ST delay seg.
Other protection units under request

872336 872340 872344 872376 872380 872384 872388 872416

5.286 5.466 5.738 6.174 7.153 8.286 11.009 13.526

872337 872341 872345 872377 872381 872385 872389 872417

6.211 6.445 6.798 7.366 8.608 10.160 13.538 16.810

872338 872342 872346 872378 872382 872386 872414 872418

6.726 6.931 7.241 7.705 8.886 10.533 14.203 16.286

872339 872343 872347 872379 872383 872387 872415 872419

7.955 8.225 8.633 9.431 11.033 12.508 16.905 20.190

Icu: 80 kA
800 1000 1250 1600 2000 2500 3200 4000 872473 872477 872481 872485 872489 872493 872526 872530 5.559 5.751 6.042 6.509 7.557 8.769 11.682 14.376 872474 872478 872482 872486 872490 872494 872527 872531 6.549 6.799 7.177 7.784 9.114 10.773 14.388 17.889 872475 872479 872483 872487 872491 872495 872528 872532 7.100 7.319 7.651 8.147 9.411 11.173 15.099 17.329 872476 872480 872484 872488 872492 872496 872529 872533 8.415 8.703 9.140 9.994 11.707 13.286 17.991 21.506

from 0,4 to 1In from 2 at 12 Ir from 0,1 at 1

Types of transfers: Can be delivered with the auxiliary source as transformer, or to the left, if it is indicated when ordering. Type A Types B and D2 N G T1 B1 T2 B2 TG B3

2) Protection units for breakers: 3)


M-PRO 17 872390 656
Over price: For different protection unit or with optional functions

872223 Consult

Automatic controller
Control E Plus Tipo 220V 872140 1362,79 872230 2044,19

according to Type and the wanted control tension:

Control E 110V 220V 1362,79 2044,19 872240 1093,84 110V 872241 1093,84

Type D1 T1 B1 B3 T2 B2 T1 B1

Type C T2 B2

A B, C, D

872141 872235

Over price: Controller with monitor tension of Net incorporated. B3

872052 150,00

Options: See page 15


A.S.S. 16 March 2002

e
Automatic transfers with Mcb: Ordering codes and prices

ATS - Automatic transfers of switches

Can be ordered in two ways:

A) Mounted kit without breakers:

Unit with all the accessories and mechanical interlock included. The wanted breakers, ( series EP), and the automatic control 872033, must be ordered separated.

Unit for ATS mcb.

872300

323,62

AS

17

B) Mounted system without breakers:

A totally assambled rack with all the accessories, mechanical interlocks, automatic control system and Net & Aux monitor voltage, in wall mounting metal cabinet of 500x400x200. The wanted breakers, ( series EP), must be ordered separated.

Cabinet ATS mcb.

872301

1267,3

Automatic transfers with contactors CL: Ordering codes and prices


1) Unit with all the accessories and mechanical
interlock included. The contactor of Net incorporates a mechanical latch. On request, can be delivered other sizes without mechanical latch. In (A) 32 60 110 140 3 Poles 872643 872645 872647 872649 240,96 360,82 652,63 760,88 4 Poles 872644 872646 872648 872650 245,00 415,92 752,23 848,65

Automatic transfers with switches Dilos CO-MO: Ordering codes and prices
1) Unit with all the accessories and mechanical In (A)
interlock included. 800 1000 1250 1600 2000 2500 3 Poles 731576 731590 731608 731625 731639 731649 2425,00 2778,00 3219,00 4466,00 4887,00 5124,00 4 Poles 731669 731683 731697 731712 731756 2612,00 3069,00 3457,00 4642,00 5064,00

731763* 6438,00
* Neutral pole reduced 50%

Type A

2) Automatic controller :
According to the wanted control tension: Tipo A 220V 872033

Control ler A 110V 820,00 872034 820,00

Over price: Controller with monitor tension of Net incorporated.

872052 150,00

Options: Hinged cover. For assembly the control plate in Modula enclosures
IP 43 Modula IP 55 Modula Enclosure for transfers: With all the equipment installed. Up to 63 A: Wall mounting metallic cabinet: 500 x 400 x 200. Up to 400 A: Wall mounting polyester cabinet: 750 x 750 x 320. Up to 1250 A: Wall mounting metallic cabinet: 1250 x 800 x 400. Up to 2500 A: Metal enclosure: 2000 x 800 x 750. A.S.S. 17 883508 872350 872128 872136 872137 872143 33,24 33,24 224,83 935,05 1322,17 2878,97 March 2002

Vous aimerez peut-être aussi