2006 by Siemens Aktiengesellschaft sterreich All rights reserved Any type of disclosure and reproduction of this document or of parts thereof is permitted only with consent prior written by Siemens. Technical specifications serve the purpose of describing the products only and do not represent any warranted characteristics in legal terms. Subject to change - also as regards technological aspects.
TM 1703 ACP
ii
DC6-011-2.01
Table of Contents
Table of Contents
1.
Introduction ........................................................................................................1-1
1.1. 1.2. 1.3. Purpose ....................................................................................................................................1-1 Application................................................................................................................................1-1 Target Group and Safety Instructions ......................................................................................1-2
2.
3.
DC6-011-2.01
iii
Table of Contents
Block Diagram and View ......................................................................................................... 3-2 Technical Specifications .......................................................................................................... 3-3 Pin Assignment and Display.................................................................................................... 3-4
4.
5.
6.
7.
8.
9.
iv
DC6-011-2.01
Table of Contents
DC6-011-2.01
Table of Contents
vi
DC6-011-2.01
Table of Contents
A.16. A.17. A.18. A.19. A.20. A.21. A.22. A.23. A.24. A.25. A.26. A.27. A.28. A.29. A.30. A.31.
USIO65/DO_R_SI ................................................................................................................. A-50 USIO65/DO_SC_1POL ......................................................................................................... A-51 USIO65/DO_SI...................................................................................................................... A-55 USIO65/SW_CONTROL_LOCATION................................................................................... A-57 USIO65/SW_CO_INTER ...................................................................................................... A-58 USIO65/SW_CO_SYNC_A ................................................................................................... A-59 USIO65/SW_CO_SYNC_R................................................................................................... A-59 USIO65/SW_CV_SET........................................................................................................... A-60 USIO65/SW_DI ..................................................................................................................... A-61 USIO65/SW_DI_AR .............................................................................................................. A-62 USIO65/SW_DI_BT............................................................................................................... A-62 USIO65/SW_DI_SOR ........................................................................................................... A-63 USIO65/SW_DO ................................................................................................................... A-63 USIO65/SW_LOC_REM ....................................................................................................... A-64 USIO65/SW_REV ................................................................................................................. A-65 label ....................................................................................................................................... A-66
B.
DC6-011-2.01
vii
Table of Contents
B.4. Class Warning ....................................................................................................................... B-12 B.4.1. Class Warning - Record 0 : General.............................................................................. B-12 B.4.2. Class Warning - Record 1 : Firmware............................................................................ B-13 B.4.3. Class Warning - Record 2 : Current and voltage, parameter ........................................ B-13 B.4.4. Class Warning - Record 3 : Error in parameters for set-point command ...................... B-13 B.4.5. Class Warning - Record 4 : Error in parameters for set-point command ...................... B-13
C.
Readers Reactions...........................................................................................C-1
viii
DC6-011-2.01
Table of Contents
Figures
Fig. 3-1 Fig. 3-2 Fig. 4-1 Fig. 4-2 Fig. 5-1 Fig. 5-2 Fig. 6-1 Fig. 6-2 Fig. 6-3 Fig. 6-4 Fig. 7-1 Fig. 7-2 Fig. 7-3 Fig. 7-4 Fig. 8-1 Fig. 8-2 Fig. 8-3 Fig. 8-4 Fig. 9-1 Fig. 9-2 Fig. 9-3 Fig. 10-1 Fig. 10-2 Fig. 10-3 Fig. 11-1 Fig. 11-2 Fig. 11-3 Fig. 12-1 Fig. 12-2 Fig. 12-3 Fig. 13-1 Fig. 13-2 Fig. 13-3 Fig. 14-1 Fig. 14-2 Fig. 14-3 Fig. 15-1 Fig. 15-2 Fig. 15-3 Fig. 15-4 Fig. 16-1 Fig. 16-2 Fig. 16-3 Fig. 17-1 Fig. 17-2 Fig. 17-3 Fig. 18-1 Fig. 18-2 Fig. 18-3 Fig. 19-1 Fig. 19-2 Fig. 19-3
PE-6400 Block Diagram and View ........................................................................................3-2 PE-6400 Pin Assignment and Display...................................................................................3-4 PE-6401 Block Diagram and View ........................................................................................4-2 PE-6401 Pin Assignment and Display...................................................................................4-4 PE-6402 Block Diagram and View ........................................................................................5-2 PE-6402 Pin Assignment and Display...................................................................................5-4 PS-6620 Block Diagram and View ........................................................................................6-2 PS-6620 Interruption bridging................................................................................................6-4 PS-6620 Pin Assignment and Display...................................................................................6-5 PS-6620 External Circuit Elements .......................................................................................6-6 PS-6630 Block Diagram and View ........................................................................................7-2 PS-6630 Interruption bridging................................................................................................7-5 PS-6630 Pin Assignment and Display...................................................................................7-6 PS-6630 External Circuit Elements .......................................................................................7-7 PS-6632 Block Diagram and View ........................................................................................8-2 PS-6632 Interruption bridging................................................................................................8-5 PS-6632 Pin Assignment and Display...................................................................................8-6 PS-6632 External Circuit Elements .......................................................................................8-7 DI-6100 Block Diagram and View..........................................................................................9-2 DI-6100 Pin Assignment and Display ....................................................................................9-5 DI-6100 External Circuit Elements ........................................................................................9-6 DI-6101 Block Diagram and View........................................................................................10-2 DI-6101 Pin Assignment and Display ..................................................................................10-5 DI-6101 External Circuit Elements ......................................................................................10-6 DI-6102 Block Diagram and View........................................................................................11-2 DI-6102 Pin Assignment and Display ..................................................................................11-5 DI-6102 External Circuit Elements ......................................................................................11-6 DI-6103 Block Diagram and View........................................................................................12-2 DI-6103 Pin Assignment and Display ..................................................................................12-5 DI-6103 External Circuit Elements ......................................................................................12-6 DI-6104 Block Diagram and View........................................................................................13-2 DI-6104 Pin Assignment and Display ..................................................................................13-5 DI-6104 External Circuit Elements ......................................................................................13-6 DO-6200 Block Diagram and View......................................................................................14-2 DO-6200 Pin Assignment and Display ................................................................................14-4 DO-6200 External Circuit Elements.....................................................................................14-5 DO-6212 Block Diagram and View......................................................................................15-2 DO-6212 Pin Assignment and Display ................................................................................15-4 DO-6212 External Circuit Elements.....................................................................................15-5 DO-6212 Protection of external Circuitry.............................................................................15-6 AI-6300 Block Diagram and View........................................................................................16-2 AI-6300 Pin Assignment and Display ..................................................................................16-4 AI-6300 External Circuit Elements.......................................................................................16-5 AI-6307 Block Diagram and View........................................................................................17-2 AI-6307 Pin Assignment and Display ..................................................................................17-4 AI-6307 External Circuit Elements.......................................................................................17-5 AI-6310 Block Diagram and View........................................................................................18-2 AI-6310 Pin Assignment and Display ..................................................................................18-4 AI-6310 External Circuit Elements.......................................................................................18-5 AO-6380 Block Diagram and View ......................................................................................19-2 AO-6380 Pin Assignment and Display ................................................................................19-4 AO-6380 External Circuit Elements.....................................................................................19-5
DC6-011-2.01
ix
Table of Contents
DC6-011-2.01
Introduction
1.
Introduction
1.1.
Purpose
This manual describes the function and mode of operation of the PE-640x/USIO65 system element. It is targeted at the designers, and essentially contains Functional descriptions Technical Specifications Descriptions of interfaces to the process and other system elements Possible configurations
1.2.
Application
The PE-640x/USIO65 peripheral element is used in the Error! No property name supplied. system for connecting I/O modules to a basic system element with open-/closed-loop control function (master control element, processing element).
TM 1703 ACP Peripheral element a PE-640x peripheral control module with USIO65 firmware up to 8 I/O modules a power supply PS-6620, PS-6630 or PS-6632 TM 1703 ACP AK 1703 ACP
can be used in
Engineering Mechanics
DC6-011-2.01
1-1
Introduction
1.3.
1-2
DC6-011-2.01
2.
PE-640x/USIO65 is mainly used in telecontrol and automation. The peripheral element is in charge for process data input and output. For this it is supported by I/O modules.
2.1.
System element for interfacing I/O modules via the TM bus up to 8 I/O modules focus on telecontrol acquisition, conditioning and output of process data using I/O modules acc. to IEC 60870-5-101/104 automation open- and closed-loop control (cycle time typically 100ms and slower) function and error indication via LED 16 Mbps Ax 1703 peripheral bus (electrical, optical) Supports I/O modules for process input binary signals analog signals (currents, voltages, temperatures) Supports I/O modules for process output binary signals analog signals (currents, voltages) Power to be supplied by PS-6620, PS-6630 or PS-6632
Common Functions I/O module monitoring, failure management Signaling via LED's Functions for Telecontrol and Automation Acquisition and processing of process data according to IEC 60870-5-101/104 The functions, specific for each I/O module, are listed in the following. Footnotes are used to specify the effect of the functions in detail (they are explained at the bottom of this page) Output of process data according to IEC 60870-5-101/104 The functions, specific for each I/O module, are listed in the following. Footnotes are used to specify the effect of the functions in detail (they are explained at the bottom of this page) Transmission of spontaneous process information to the basic system element for further distribution Transmission of periodical process information, from and to the open-/closed-loop control function in the higher-level basic system element The functions stated above are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
2-1
Telecontrol the function delivers (acquisition) spontaneously transmitted process information or is controlled by such information (output); partly, periodically transmitted information is also created/required Automation the function affects process information which is periodically transmitted
2-2
DC6-011-2.01
2.1.1.
Acqusition Functions in Detail DI-6100 DI-6101 DI-6104 Binary Input 2x8, 24-60VDC Binary Input 2x8, 110/220VDC Binary Input 2x8, 220VDC
single-point information acquisition with a resolution of 10ms t update every 10ms a (or with the same cycle as the open-/closed-loop control function in the basic system element, depending on which cycle is larger) revision ta power monitoring ta inversion ta firmware filter t bounce suppression t determination of the cause of transmission t spontaneous transmission of changes t periodical transmission a double-point information acquisition with a resolution of 10ms t update every 10ms a (or with the same cycle as the open-/closed-loop control function in the basic system element, depending on which cycle is larger) revision ta power monitoring ta inversion ta firmware filter t bounce suppression t monitoring intermediate and faulty positions t determination of the cause of transmission t reporting switching operations in progress t breaker tripping detection t breaker tripping suppression during auto-reclose t spontaneous transmission of changes t periodical transmission a integrated totals via count pulses (via binary inputs of the module) t1 acquisition by firmware with a maximum count frequency of 20Hz pulse length/pause >20ms/>20ms revision power monitoring inversion pulse counting counter value formation count pulse evaluation set counter formation of integrated totals counter request interval control freezed absolute value freezed relative value not power-fail safe integrated total transmission according to IEC 60870-5-101 spontaneous transmission
DC6-011-2.01
2-3
DI-6102 DI-6103
Binary Input 2x8, 24-60VDC 1ms Binary Input 2x8, 110/220VDC 1ms
single-point information acquisition with a resolution of 1ms t update every 10ms a (or with the same cycle as the open-/closed-loop control function in the basic system element, depending on which cycle is larger) revision ta power monitoring ta inversion ta firmware filter t bounce suppression t determination of the cause of transmission t spontaneous transmission of changes t periodical transmission a double-point information acquisition with a resolution of 1ms t update every 10ms a (or with the same cycle as the open-/closed-loop control function in the basic system element, depending on which cycle is larger) revision ta power monitoring ta inversion ta firmware filter t bounce suppression t monitoring intermediate and faulty positions t determination of the cause of transmission t reporting switching operations in progress t breaker tripping detection t breaker tripping suppression during auto-reclose t spontaneous transmission of changes t periodical transmission a integrated totals via count pulses (via binary inputs of the module) t1 acquisition by firmware with a maximum count frequency of 20Hz pulse length/pause >2ms/>2ms revision power monitoring inversion pulse counting counter value formation count pulse evaluation set counter formation of integrated totals counter request interval control freezed absolute value freezed relative value not power-fail safe integrated total transmission according to IEC 60870-5-101 spontaneous transmission
2-4
DC6-011-2.01
AI-6300 AI-6307
currents and voltages settable acquistion grid n*100ms t measurement range settable with a resloution of t 12 bits + sign at fullscale shrinking the range results in decreasing resolution revision t noise rejection t automatic calibration t smoothing t adaptation t linear (normalized, technologically scaled or short floating point) suppression of zero range plausibility check change monitoring t spontaneous transmission of changes t
DC6-011-2.01
2-5
AI-6310
temperatures t1 acquisition of resistance thermometers via analog inputs of a SM-0571 connection of the resistance thermometers: two-, three-, or four-wire technique update every 400ms settable measuring range when transferring temperatures (a) Pt100: -50 .. +350C / -58 .. +662F / (80.31 .. 229.67 ) (b) Pt100: -100 .. +700C / -148 .. +1292F / (60.25 .. 345.13 ) (c) Ni100: -60 .. +250C / -76 .. +482F / (74.18 .. 295.52 ) when transferring resistance values (a) Pt100: 0 .. 230 (b) Pt100: 0 .. 346 (c) Ni100: 0 .. 346 resolution when transferring temperatures (a) Pt100: 0.20C / 0.36F / (90 m) (b) Pt100: 0.35C / 0.63F / (130 m) (c) Ni100: 0.35C / 0.63F / (130 m) when transferring resistance values (a) Pt100: 90 m (b) Pt100: 130 m (c) Ni100: 130 m revision noise rejection automatic calibration calibration for 2-wire technique smoothing adaptation temperature value (C, F) conversion using implemented curves resistance () change monitoring spontaneous transmission of changes
2-6
DC6-011-2.01
2.1.2.
pulse commands t1 checked output of pulse commands 1-pole single, double and regulating step commands command output (OC) basic application functions and procedures according to IEC 60870-5-101/104 formal check direct command select and execute command ("select/execute") retry suppression 1-out-of-n check control location check command locking synchronization revision command output time settable dependent on the process return information monitoring command prolongation switching sequences command output for the auto-reclose function if outputs of the module are used for pulse commands, no outputs of the same module can be used for binary information output binary information output selectable behavior on communication failure ta (deactivation or retention) deactivation on module failure ta spontaneous transmission t or periodical transmission a if outputs of the module are used for binary information output, no outputs of the same module can be used for pulse commands
DC6-011-2.01
2-7
DO-6212
pulse commands t1 checked output of pulse commands 1-pole, 1-pole, 2-pole cannot be mixed single, double and regulating step commands command output (OC) basic application functions and procedures according to IEC 60870-5-101/104 formal check direct command select and execute command ("select/execute") retry suppression 1-out-of-n check control location check command locking synchronization revision command output time settable dependent on the process return information monitoring command prolongation switching sequences command output for the auto-reclose function if outputs of the module are used for pulse commands, no outputs of the same module can be used for binary information output binary information output selectable behavior on communication failure ta (deactivation or retention) deactivation on module failure ta spontaneous transmission t or periodical transmission a if outputs of the module are used for binary information output, no outputs of the same module can be used for pulse commands
2-8
DC6-011-2.01
AO-6380 setpoint values by means of currents and voltages output via analog outputs of a SM-0572 ta output range settable with a resloution of ta 15 bits + sign at 20mA 15 bits + sign at 10V shrinking the range results in decreasing resolution basic application functions and procedures according to IEC 60870-5-101/104 ta formal check direct command select and execute command ("select/execute") adaptation t linear (normalized, technologically scaled or short floating point) t selectable behavior on communication failure and module failure ta (keep value, output substitute value) spontaneous transmission t or periodical transmission a
DC6-011-2.01
2-9
2.1.3.
Further Functions return information to pulse command assignment settable assignment when using the peripheral element on a ACP 1703 platform for messages and pulse commands, which are acquired or output on the peripheral element itself for messages and pulse commands, which are acquired or output on different peripheral elements of the same basic system element predefined assignment for messages and pulse commands, which are acquired or output on the peripheral element itself
Type single information to single command (1pole): DI-610x with DO-6200 Predefined Assignment SI IOMx IND00 ... command IOMy OUT D00 SI IOMx IND01 ... command IOMy OUT D01 SI IOMx IND07 ... command IOMy OUT D07 SI IOMx IND10 ... command IOMy OUT D10 SI IOMx IND11 ... command IOMy OUT D11 SI IOMx IND17 ... command IOMy OUT D17 single information to single command (1pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible) SI IOMx IND00 ... command IOMy OUT D00 SI IOMx IND01 ... command IOMy OUT D01 SI IOMx IND07 ... command IOMy OUT D07 SI IOMx IND10 ... command IOMz OUT D00 SI IOMx IND11 ... command IOMz OUT D01 SI IOMx IND17 ... command IOMz OUT D07 single information to single command (1.5pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible) SI IOMx IND00 ... command IOMy OUT D00 SI IOMx IND01 ... command IOMy OUT D01 SI IOMx IND06 ... command IOMy OUT D06 SI IOMx IND10 ... command IOMz OUT D00 SI IOMx IND11 ... command IOMz OUT D01 SI IOMx IND16 ... command IOMz OUT D06 single information to single command (2pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible) SI IOMx IND00 ... command IOMy OUT D00/D01 SI IOMx IND02 ... command IOMy OUT D02/D03 SI IOMx IND06 ... command IOMy OUT D06/D07 SI IOMx IND10 ... command IOMz OUT D00/D01 SI IOMx IND12 ... command IOMz OUT D02/D03 SI IOMx IND16 ... command IOMz OUT D06/D07 double information to double command (1pole): DI-610x with DO-6200 DI IOMx IND00/D01 ... command IOMy OUT D00/D01 DI IOMx IND02/D03 ... command IOMy OUT D02/D03 DI IOMx IND06/D07 ... command IOMy OUT D06/D07 DI IOMx IND10/D11 ... command IOMy OUT D10/D11 DI IOMx IND12/D13 ... command IOMy OUT D12/D13 DI IOMx IND16/D17 ... command IOMy OUT D16/D17 double information to double command (1pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible) DI IOMx IND00/D01 ... command IOMy OUT D00/D01 DI IOMx IND02/D03 ... command IOMy OUT D02/D03 DI IOMx IND06/D07 ... command IOMy OUT D06/D07 DI IOMx IND10/D11 ... command IOMz OUT D00/D01 DI IOMx IND12/D13 ... command IOMz OUT D02/D03 DI IOMx IND16/D17 ... command IOMz OUT D06/D07
2-10
DC6-011-2.01
double information to double command (1.5pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible)
DI IOMx IND00/D01 ... command IOMy OUT D00/D01 DI IOMx IND02/D03 ... command IOMy OUT D02/D03 DI IOMx IND04/D05 ... command IOMy OUT D04/D05 DI IOMx IND10/D11 ... command IOMz OUT D00/D01 DI IOMx IND12/D13 ... command IOMz OUT D02/D03 DI IOMx IND14/D15 ... command IOMz OUT D04/D05 DI IOMx IND00/D01 ... command IOMy OUT D00..D03 DI IOMx IND04/D05 ... command IOMy OUT D04..D07 DI IOMx IND10/D11 ... command IOMz OUT D00..D03 DI IOMx IND14/D15 ... command IOMz OUT D04..D07
double information to double command (2pole): DI-610x with DO-6212 (two DO-6212 with one DI-610x possible)
x = 0..7 y = x+1 z = x+2
DC6-011-2.01
2-11
2.2.
Architecture
2.2.1.
Mechanical Design The modules of the peripheral element are mounted on a TS35 rail in a specified order. The installation of the TS35 rail takes place on a vertical wall in vertical or horizontal installation position.
Electrical Ax 1703 Peripheral Bus
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . .
The power supply and TM bus are electrically connected during the process of latching together, wherein each module can be individually replaced. Attention The TS35 rail, on which the modules are fastened, must be grounded.
2.2.2.
Connection to the higher-level Basic System Element The connection is made via the serial Ax 1703 peripheral bus using bus interfaces. Several bus interfaces are available:
Type CM-0843 CM-0842 Designation Bus Interface Ax-PE 4x USB Bus Interface Ax-PE 4x optical Connection electrical optical Number of Peripheral Elements up to 16 up to 16
Configurations with CM-0843 and CM-0842 can be found in the respective data sheet.
2-12
DC6-011-2.01
2.2.3.
Power Supply The supply to the peripheral element takes place via one of the following power supply modules.
Module PS-6620 PS-6630 PS-6632 Designation Power Supply Module 24-60 VDC Power Supply Module 24-60 VDC (SIC+) Power Supply Module 110-220 VDC (SIC+) Type ------Available Power 8000 mW 8000 mW 8000 mW
2.2.4.
Designation Peripheral Control Module Ax-PE Bus (electrical) Peripheral Control Module Ax-PE Bus (1x FO) Peripheral Control Module Ax-PE Bus (2x FO)
Type -------
on request only
2.2.5.
I/O Modules The process signals are connected to the I/O modules by detachable screw terminals. Since these screw terminals carry the circuitry, nothing needs to be disconnected when changing out a module. The screw terminals are included with each I/O module. The PE-640x/USIO65 peripheral element supports the following I/O modules:
I/O Module DI-6100 DI-6101 DI-6102 DI-6103 DI-6104 DO-6200 DO-6212 AI-6300 AI-6307 AI-6310 AO-6380 Designation Binary Input 2x8, 24-60VDC Binary Input 2x8, 110/220VDC Binary Input 2x8, 24-60VDC 1ms Binary Input 2x8, 110/220VDC 1ms Binary Input 2x8, 220VDC Binary Output Transistor 2x8, 24-60VDC Binary Output Relays 8x 24-220VDC/230VAC Analog Input 2x2 20mA/10V Analog Input 2x2 5mA/10V Analog Input 2x2 Pt100/Ni100 Analog Output 4x 20mA/10mA/10V Type Digital I/O module Digital I/O module Digital I/O module Digital I/O module Digital I/O module Digital I/O module Digital I/O module Analog I/O module Analog I/O module Analog I/O module Analog I/O module Load 170 mW 170 mW 170 mW 170 mW 170 mW 600 mW 800 mW 480 mW 480 mW 450 mW 1900 mW
DC6-011-2.01
2-13
2.2.5.1.
Configuration Up to 8 I/O modules can be installed in addition to the peripheral control module as long as both the total load of the I/O modules does not exceed 7000 mW the total load of the I/O modules and the peripheral control module does not exceed the power provided by the power supply module If return information monitoring of pulse commands is used direct on USIO65, the DI and DO modules must always follow one another. If the assignment is made on the CPC65 using OPM, the sequence of the DI and DO modules can be choosen arbitrary. AO-6380 modules (max. 3 are possible) must always be installed on the first slots
2.2.6.
System-Busses The PE-640x/USIO65 peripheral element communicates via the TM bus with the I/O modules and through them with the process. Via the Ax 1703 peripheral bus the communication is done with the open-/closed-loop control function according to IEC 61131-3 in the higher-level basic system element.
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . .
2.2.6.1.
TM Bus Communication between the I/O modules and peripheral control module takes place via the TM bus in the master/slave process, wherein the I/O modules are the slaves. The I/O modules are automatically addressed on the TM bus based on the sequence of physical fitting. The I/O module connected directly to the peripheral control module has the least significant address.
2-14
DC6-011-2.01
2.2.6.2.
Ax 1703 Peripheral Bus The peripheral element is connected to the master control element via the Ax 1703 peripheral bus (see chapter 2.2.2, Connection to the higher-level Basic System Element ). The address of the peripheral element on the Ax 1703 peripheral bus is determined in SAT TOOLBOX II, when defining the Ax 1703 peripheral bus configuration. This address is then set by the PBA switch on the peripheral control module.
DC6-011-2.01
2-15
2.3.
System Properties
2.3.1.
LED Display during Startup As soon as the peripheral element is supplied or a startup is triggered by a reset, the ER-LED on the peripheral control module lights up. A test of the program memory takes place. If this test is successful, the ER-LED goes out after approx. 5 seconds. If the ER-LED remains lit, there is an error in the program memory. A diagnosis with SAT TOOLBOX II is not possible. This is followed by additional tests, e.g., RAM test, parameter test, etc. If an error arises in the process, the ER-LED blinks, and startup is terminated. Another test compares the I/O module configuration defined by parameters with the actual physical configuration (the way the I/O module's addresses have been set). If a difference is discovered, startup is terminated. In other words, the peripheral control module gets ready, but no I/O module (even if correctly configured) . This state can only be exited given a matching and therefore correct configuration and a repeated startup. If the startup can be properly terminated, the RY-LED (ready) lights up on all modules.
2.3.2.
Behavior during Startup (Periodic Information) The periodic information about the open-/closed-loop control function is initialized with the value 0 and an I/O module-dependent status "disturbed". After startup of the peripheral element (ready), all periodic information from undisturbed inputs is described with the currently pre-processed value, and the corresponding status "disturbed" is reset. The behavior of the outputs depends on the parameter "failure mode" and the I/O module.
2-16
DC6-011-2.01
2.3.3.
Response Time (Periodic Information) The response time describes the span of time from when an event occurs until information is output to the process by the automation unit. The diagram below shows the chronological relationships of the affected system parts.
t zyk
Master Control
10ms
operating system open-/closed loop control function transmission on Ax PE bus
10ms
10ms
10ms
Peripheral Element
tout t in
tout t in
tout tin
t out t in
t filter
change at input output of response t reakt
t filter
t filter
t tot
Legend: relevant for this example not relevant for this example tzyk tin tout treakt ttot cycle time of open-/Closed loop control function processing time for information acquisition processing time for information output, including hardware setting times response time dead time of controlled system
treakt = 2 x 10ms + 2 tzyk + tout + tfilter treakt = 2 x tin + 2 tzyk + tout + tfilter
The following table indicates the processing time of the I/O modules:
I/O Module DI-6100 DI-6101 DI-6102 DI-6103 DI-6104 DO-6200 DO-6212 Designation Binary Input 2x8, 24-60VDC Binary Input 2x8, 110/220VDC Binary Input 2x8, 24-60VDC 1ms Binary Input 2x8, 110/220VDC 1ms Binary Input 2x8, 220VDC Binary Output Transistor 2x8, 24-60VDC Binary Output Relays 8x 24-220VDC/230VAC tin 1.5 ms 1.5 ms 1.5 ms 1.5 ms 1.5 ms tout 1.4 ms 6.5 ms tfilter 4 ms 4 ms 4 ms 4 ms 4 ms -
DC6-011-2.01
2-17
2.4.
2.4.1.
I/O Module Monitoring The failure of an I/O module is signaled by periodic information for the open-loop and closed-loop function, and by diagnostic information. The "RY" LED goes out on the corresponding I/O module. The following table shows the time (t) from the failure of the I/O module until it is signaled:
I/O Module DI-6100 DI-6101 DI-6102 DI-6103 DI-6104 DO-6200 DO-6212 AI-6300 AI-6307 AI-6310 AO-6380 Designation Binary Input 2x8, 24-60VDC Binary Input 2x8, 110/220VDC Binary Input 2x8, 24-60VDC 1ms Binary Input 2x8, 110/220VDC 1ms Binary Input 2x8, 220VDC Binary Output Transistor 2x8, 24-60VDC Binary Output Relays 8x 24-220VDC/230VAC Analog Input 2x2 20mA/10V Analog Input 2x2 5mA/10V Analog Input 2x2 Pt100/Ni100 Analog Output 4x 20mA/10mA/10V t 40 ms 40 ms 40 ms 40 ms 40 ms 100 ms 100 ms 40 ms 40 ms 400 ms 100 ms
After replacing the I/O module, failed I/O modules are started up again exclusively by running up the peripheral element. Attention Modules may only be replaced if the supply voltage is turned off!
2.4.2.
Ax 1703 Peripheral Bus Monitoring If no bus activity is determined within 49 ms, the peripheral element is switched to the "firmware shut down" state. As a result, the watchdog operates, and the I/O module-specific failure treatments enter into force. If bus activity is again detected, a startup is initiated.
2.4.3.
Behaviour in case of a Configuration Change If the configuration of the I/O modules is changed in SAT TOOLBOX II, e.g., new modules are added or existing ones removed and charged, this change will only go into effect after a startup of the peripheral element.
2-18
DC6-011-2.01
2.5.
Data Points
The data points described in this section do not independ on the I/O module configuration. The data points of the I/O modules are described together with the corresponding I/O module. The data points of this peripheral element are provided to the open-/closed-loop control function exclusively via periodic information.
2.5.1.
Periodic Information Sent to the Open-/Closed-Loop Control Function Updating grid corresponds to time (t) as described in the "I/O Module Monitoring" section.
Data Point (OPM II) IOMx failed x = 0 .. 7, depending on the configuration Value Range binary Failure of an I/O module Meaning
DC6-011-2.01
2-19
2.6.
Data point not spontaneous Format of data point which is exchanged with the open-/closed-loop control function as periodic information analog binary
Data point not periodic Destination value number for detailed routing "Ax1703-PE detailed routing PDS" (only relevant if the system element is used on Ax-platforms) Data point information is sent from the basic system element to the peripheral element Data point information is sent from the peripheral element to the basic system element
2-20
DC6-011-2.01
2.6.1.
Data Point Voltage failure IOMx D00 .. D07 Voltage failure IOMx D10 .. D17 Board failed Acquisition error Revision Sum flutter fault IOMx failed x = 0 .. 7
HW Pin
SW Data Point
Transmission mode spontaneous periodic TI 30 - single-point information binary binary binary binary
Value # 0
Direction BSE PE
2.6.2.
Single-Point Information
Data Point SI IOMx IN D00 ... SI IOMx IN D07 SI IOMx IN D10 ... SI IOMx IN D17 x = 0 .. 7
HW Pin IOMx IN D00 (x:1) ... IOMx IN D07 (x:8) IOMx - IN D10 (x:31) ... IOMx IN D17 (x:38)
SW Data Point
OPM II Link-Category
Value #
Direction BSE PE
USIO65/DI_SI
TI 30 - single-point information
binary
DC6-011-2.01
2-21
2.6.3.
Double-Point Information
Data Point double-point inf. IOMx - IN D00/D01 ... double-point inf. IOMx - IN D06/D07 double-point inf. IOMx - IN D10/D11 ... double-point inf. IOMx - IN D16/D17 SI IOMx IN D00 ... SI IOMx IN D07 SI IOMx IN D10 ... SI IOMx IN D17 reclosing DI IOMx IN D00/D01 reclosing DI IOMx IN D06/D07 reclosing DI IOMx IN D10/D11 reclosing DI IOMx IN D16/D17 switching op. run. DI IOMx IN D00/D01 switching op. run. DI IOMx IN D06/D07 switching op. run. DI IOMx IN D10/D11 switching op. run. DI IOMx IN D16/D17
HW Pin IOMx IN D00 (x:1)/ IOMx IN D01(x:2) ... IOMx IN D06 (x:7)/ IOMx IN D07 (x:8) IOMx IN D10 (x:31)/ IOMx - IN D11 (x: 32) ... IOMx - IN D16 (x:37)/ IOMx IN D17 (x:38) IOMx IN D00 (x:1) ... IOMx IN D07 (x:8) IOMx - IN D10 (x:31) ... IOMx IN D17 (x:38)
SW Data Point
OPM II Link-Category
Value #
Direction BSE PE
USIO65/DI_DI
TI 31 - double-point information
binary 1)
CAEx/Ax-Mode
TI 30 single-point information
binary 2)
USIO65/SW_DI_AR
TI 30 - single-point information
USIO65/SW_DI_SOR
TI 30 - single-point information
2-22
DC6-011-2.01
USIO65/SW_DI_BT
TI 30 - single-point information
binary
5 20
x = 0 .. 7
2.6.4.
Data Point Latching activation Transmission activation counter IOMx IN D00 ... counter IOMx IN D07 counter IOMx IN D10 ... counter IOMx IN D17 counter IOMx IN D00 set ... counter IOMx IN D07 set counter IOMx IN D10 set ... counter IOMx IN D17 set x = 0 .. 7
SW Data Point
Value #
Direction BSE PE
USIO65/DI_CV
TI 37 - integrated totals
DC6-011-2.01
2-23
2.6.5.
Currents
HW Pin IOMx - IN V0 I+ (x:2)/ IOMx - AUX V0+ (x:1)/ IOMx - IN V0 I- (x:3)/ IOMx - AUX V0- (x:4) IOMx - IN V1 I+ (x:6)/ IOMx - AUX V0+ (x:5)/ IOMx - IN V1 I- (x:7)/ IOMx - AUX V0- (x:8) IOMx - IN V2 I+ (x:32)/ IOMx - AUX V1+ (x:31)/ IOMx - IN V2 I- (x:33)/ IOMx - AUX V1- (x:34) IOMx - IN V3 I+ (x:36)/ IOMx - AUX V1+ (x:35)/ IOMx - IN V3 I- (x:37)/ IOMx - AUX V1- (x:38)
SW Data Point
OPM II Link-Category
Value #
Direction BSE PE
USIO65/AI_I
x = 0 .. 7
2-24
DC6-011-2.01
2.6.6.
Voltages
HW Pin IOMx - IN V0 U+ (x:12)/ IOMx - AUX V0+ (x:11)/ IOMx - IN V0 U- (x:13)/ IOMx - AUX V0- (x:14) IOMx - IN V1 U+ (x:16)/ IOMx - AUX V0+ (x:15)/ IOMx - IN V1 U- (x:17)/ IOMx - AUX V0- (x:18) IOMx - IN V2 U+ (x:22)/ IOMx - AUX V1+ (x:21)/ IOMx - IN V2 U- (x:23)/ IOMx - AUX V1- (x:24) IOMx - IN V3 U+ (x:26)/ IOMx - AUX V1+ (x:25)/ IOMx - IN V3 U- (x:27)/ IOMx - AUX V1- (x:28)
SW Data Point
OPM II Link-Category
Value #
Direction BSE PE
USIO65/AI_U
x = 0 .. 7
DC6-011-2.01
2-25
2.6.7.
Temperatures
HW Pin IOMx - IN V0+ (x:12)/ IOMx - IREF0+ (x:11)/ IOMx - IN V0- (x:13)/ IOMx - IREF0,1- (x:14) IOMx - IN V1+ (x:16)/ IOMx IREF1+ (x:15)/ IOMx - IN V1- (x:17)/ IOMx - IREF0,1- (x:18) IOMx - IN V2+ (x:22)/ IOMx IREF2+ (x:21)/ IOMx - IN V2- (x:23)/ IOMx IREF2,3- (x:24) IOMx - IN V3+ (x:26)/ IOMx IREF3+ (x:25)/ IOMx - IN V3- (x:27)/ IOMx IREF2,3- (x:28)
SW Data Point
OPM II Link-Category
Value #
Direction BSE PE
USIO65/AI_T
TI 36 - measured value
Start adjustment AI x = 0 .. 7
USIO65/SW_DO
binary
2-26
DC6-011-2.01
2.6.8.
Data Point Command output busy Sum command output running Sum command output fault Command interlocked Command 1out of N interlocked Sync. enable 1 out of N enable Command state information AR_CB_controllable AR_CB_on Control location
HW Pin
SW Data Point
OPM II Link-Category USIO65/SW_DI USIO65/SW_DI USIO65/SW_DI USIO65/SW_DI USIO65/SW_DI USIO65/SW_DO USIO65/SW_DO USIO65/SW_DO USIO65/SW_DO USIO65/SW_DO USIO65/SW_CONTROL_ LOCATION USIO65/SW_CO_INTER
Transmission mode spontaneous periodic TI 35 measured value TI 45 single command TI 30 - single-point information binary binary binary binary binary binary binary binary binary binary
Value # 20
Direction BSE PE
DC6-011-2.01
2-27
2.6.9.
Data Point command IOMx OUT D00 ... command IOMx OUT D07 command IOMx OUT D10 ... command IOMx OUT D17 command IOMx OUT D00 interlocked ... command IOMx OUT D07 interlocked command IOMx OUT D10 interlocked ... command IOMx OUT D17 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D07 run sync. command IOMx OUT D10 run ... sync. command IOMx OUT D17 run sync. comm. IOMx OUT D00 abort ... sync. comm. IOMx OUT D07 abort sync. comm. IOMx OUT D10 abort ... sync. comm. IOMx OUT D17 abort x = 0 .. 7
HW Pin IOMx OUT D00 (x:11) ... IOMx OUT D07 (x:18) IOMx OUT D10 (x:21) ... IOMx OUT D17 (x:28)
SW Data Point
OPM II Link-Category
Direction BSE PE
USIO65/DO_SC_1POL
TI 45 - single command
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
TI 30 - single-point information
USIO65/SW_CO_SYNC_A
TI 30 - single-point information
2-28
DC6-011-2.01
2.6.10.
Data Point command IOMx OUT D00 command IOMx OUT D01 command IOMx OUT D02 command IOMx OUT D03 command IOMx OUT D04 command IOMx OUT D05 command IOMx OUT D06 command IOMx OUT D07 command IOMx OUT D00 interlocked ... command IOMx OUT D07 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D07 run sync. comm. IOMx OUT D00 abort ... sync. comm. IOMx OUT D07 abort x = 0 .. 7
HW Pin IOMx OUTD00 (x:11) IOMx OUTD01 (x:13) IOMx OUTD02 (x:15) IOMx OUTD03 (x:17) IOMx OUTD04 (x:21) IOMx OUTD05 (x:23) IOMx OUTD06 (x:25) IOMx OUTD07 (x:27)
OPM II Link-Category
USIO65/DO_R_SC_1POL
TI 45 - single command
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
USIO65/SW_CO_SYNC_A
DC6-011-2.01
2-29
2.6.11.
Data Point command IOMx OUT D00 command IOMx OUT D01 command IOMx OUT D02 command IOMx OUT D03 command IOMx OUT D04 command IOMx OUT D05 command IOMx OUT D06 command IOMx OUT D00 interlocked ... command IOMx OUT D06 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D06 run sync. comm. IOMx OUT D00 abort ... sync. comm. IOMx OUT D06 abort x = 0 .. 7
HW Pin IOMx OUTD00 (x:11) IOMx OUTD01 (x:13) IOMx OUTD02 (x:15) IOMx OUTD03 (x:17) IOMx OUTD04 (x:21) IOMx OUTD05 (x:23) IOMx OUTD06 (x:25)
SW Data Point
OPM II Link-Category
Value # 64 65 66 67 68 69 70 + x*16
Direction BSE PE
USIO65/DO_R_SC_1,5POL
TI 45 - single command
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
USIO65/SW_CO_SYNC_A
2-30
DC6-011-2.01
2.6.12.
Data Point command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D04/D05 command IOMx OUT D06/D07 command IOMx OUT D00 interlocked command IOMx OUT D02 interlocked command IOMx OUT D04 interlocked command IOMx OUT D06 interlocked sync. command IOMx OUT D00 run sync. command IOMx OUT D02 run sync. command IOMx OUT D04 run sync. command IOMx OUT D06 run sync. comm. IOMx OUT D00 abort sync. comm. IOMx OUT D02 abort sync. comm. IOMx OUT D04 abort sync. comm. IOMx OUT D06 abort x = 0 .. 7
HW Pin IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13) IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23) IOMx OUTD06 (x:25)/ IOMx OUTD07 (x:27)
SW Data Point
OPM II Link-Category
Value # 64 66
Direction BSE PE
USIO65/DO_R_SC_2POL
TI 45 - single command
68 70 + x*16
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
TI 30 - single-point information
USIO65/SW_CO_SYNC_A
TI 30 - single-point information
DC6-011-2.01
2-31
Peripheral Element PE-640x/USIO65 2.6.13. Pulse Command - Double Command - 1pole (DO-6200)
SW Data Point Transmission mode spontaneous periodic Value # 64 65 ... 67 USIO65/DO_DC_1POL TI 46 - double command TI 47 tap positioning command 68 69 ... 71 + x*8 command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D06/D07 command IOMx OUT D10/D11 command IOMx OUT D12/D13 ... command IOMx OUT D16/D17 IOMx OUT D00 (x:11)/ IOMx OUT D01 (x:12)/ IOMx OUT D02 (x:13)/ IOMx OUT D03 (x:14)/ ... IOMx OUT D06 (x:17)/ IOMx OUT D07 (x:18) IOMx OUT D10 (x:21)/ IOMx OUT D11 (x:22)/ IOMx OUT D12 (x:23)/ IOMx OUT D13 (x:24)/ ... IOMx OUT D16 (x:27)/ IOMx OUT D17 (x:28) 64 66 ... 70 USIO65/DO_DB_1POL TI 45 single command 72 74 ... 78 + x*16 command IOMx OUT D00 interlocked ... command IOMx OUT D07 interlocked command IOMx OUT D10 interlocked ... command IOMx OUT D17 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D07 run Direction BSE PE
Data Point command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D06/D07 command IOMx OUT D10/D11 command IOMx OUT D12/D13 ... command IOMx OUT D16/D17
HW Pin IOMx OUT D00 (x:11)/ IOMx OUT D01 (x:12)/ IOMx OUT D02 (x:13)/ IOMx OUT D03 (x:14)/ ... IOMx OUT D06 (x:17)/ IOMx OUT D07 (x:18) IOMx OUT D10 (x:21)/ IOMx OUT D11 (x:22)/ IOMx OUT D12 (x:23)/ IOMx OUT D13 (x:24)/ ... IOMx OUT D16 (x:27)/ IOMx OUT D17 (x:28)
OPM II Link-Category
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
TI 30 - single-point information
2-32
DC6-011-2.01
USIO65/SW_CO_SYNC_A
TI 30 - single-point information
DC6-011-2.01
2-33
2.6.14.
Data Point command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D04/D05 command IOMx OUT D06/D07 command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D04/D05 command IOMx OUT D06/D07 command IOMx OUT D00 interlocked ... command IOMx OUT D07 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D07 run sync. comm. IOMx OUT D00 abort ... sync. comm. IOMx OUT D07 abort x = 0 .. 7
HW Pin IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13) IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23) IOMx OUTD06 (x:25)/ IOMx OUTD07 (x:27) IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13) IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23) IOMx OUTD06 (x:25)/ IOMx OUTD07 (x:27)
SW Data Point
OPM II Link-Category
Value # 64 65
Direction BSE PE
USIO65/DO_R_DC_1POL
66 67 + x*8 64 66
USIO65/DO_R_DC_1POL
TI 45 single command
68 70 + x*16
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
USIO65/SW_CO_SYNC_A
2-34
DC6-011-2.01
2.6.15.
Data Point command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D04/D05 command IOMx OUT D00/D01 command IOMx OUT D02/D03 command IOMx OUT D04/D05
HW Pin IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13) IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23) IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13) IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23)
SW Data Point
OPM II Link-Category
Value # 64
Direction BSE PE
USIO65/DO_R_DC_1,5POL
65 66 + x*8 64 66
USIO65/DO_R_DC_1,5POL
TI 45 single command
68 + x*16
command IOMx OUT D00 interlocked ... command IOMx OUT D07 interlocked sync. command IOMx OUT D00 run ... sync. command IOMx OUT D07 run sync. comm. IOMx OUT D00 abort ... sync. comm. IOMx OUT D07 abort x = 0 .. 7
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
USIO65/SW_CO_SYNC_A
DC6-011-2.01
2-35
2.6.16.
HW Pin IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13)/ IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17)
SW Data Point
OPM II Link-Category
Value # 64
Direction BSE PE
command IOMx OUT D04..D07 IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23)/ IOMx OUTD06 (x:25)/ IOMx OUTD07 (x:27) IOMx OUTD00 (x:11)/ IOMx OUTD01 (x:13)/ IOMx OUTD02 (x:15)/ IOMx OUTD03 (x:17) command IOMx OUT D04..D07 IOMx OUTD04 (x:21)/ IOMx OUTD05 (x:23)/ IOMx OUTD06 (x:25)/ IOMx OUTD07 (x:27)
USIO65/DO_R_DC_2POL
66 + x*8
64
USIO65/DO_R_DC_2POL
TI 45 single command
68 + x*16
command IOMx OUT D00 interlocked command IOMx OUT D02 interlocked command IOMx OUT D04 interlocked command IOMx OUT D06 interlocked sync. command IOMx OUT D00 run sync. command IOMx OUT D02 run sync. command IOMx OUT D04 run sync. command IOMx OUT D06 run sync. comm. IOMx OUT D00 abort sync. comm. IOMx OUT D02 abort sync. comm. IOMx OUT D04 abort sync. comm. IOMx OUT D06 abort x = 0 .. 7
USIO65/SW_DO
binary
USIO65/SW_CO_SYNC_R
TI 30 - single-point information
USIO65/SW_CO_SYNC_A
TI 30 - single-point information
2-36
DC6-011-2.01
2.6.17.
Data Point Binary inform. output IOMx OUT D00 ... Binary inform. output IOMx OUT D07 Binary inform. output IOMx OUT D10 ... Binary inform. output IOMx OUT D17 x = 0 .. 7
HW Pin IOMx OUT D00 (x:11) ... IOMx OUT D07 (x:18) IOMx OUT D10 (x:21) ... IOMx OUT D17 (x:28)
SW Data Point
OPM II Link-Category
Direction BSE PE
USIO65/DO_SI
TI 30 - single-point information
binary
2.6.18.
Data Point Binary inform. output IOMx OUT D00 Binary inform. output IOMx OUT D01 Binary inform. output IOMx OUT D02 Binary inform. output IOMx OUT D03 Binary inform. output IOMx OUT D04 Binary inform. output IOMx OUT D05 Binary inform. output IOMx OUT D06 Binary inform. output IOMx OUT D07 x = 0 .. 7
HW Pin IOMx OUTD00 (x:11) IOMx OUTD01 (x:13) IOMx OUTD02 (x:15) IOMx OUTD03 (x:17) IOMx OUTD04 (x:21) IOMx OUTD05 (x:23) IOMx OUTD06 (x:25) IOMx OUTD07 (x:27)
SW Data Point
OPM II Link-Category
Value # 64 65 66 67 68 69 70 71 + x*16
Direction BSE PE
USIO65/DO_R_SI
TI 30 - single-point information
binary
DC6-011-2.01
2-37
2.6.19.
HW Pin IOMx OUT V0+ (x:1)/ IOMx IC0 (x:2)/ IOMx IC0 (x:3)/ IOMx OUT V0- (x:4)/ IOMx AUX V0+ (x:11)/ IOMx OUT V0+ (x:12)/ IOMx OUT V0- (x:13)/ IOMx AUX V0- (x:14) IOMx OUT V1+ (x:5)/ IOMx IC1 (x:6)/ IOMx IC1 (x:7)/ IOMx OUT V1- (x:8)/ IOMx AUX V0+ (x:15)/ IOMx OUT V1+ (x:16)/ IOMx OUT V1- (x:17)/ IOMx AUX V0- (x:18) IOMx OUT V2+ (x:22)/ IOMx AUX V1+ (x:21)/ IOMx OUT V2- (x:23)/ IOMx AUX V1- (x:24)/ IOMx OUT V2+ (x:31)/ IOMx IC2 (x:32)/ IOMx IC2 (x:33)/ IOMx OUT V2- (x:34) IOMx OUT V3+ (x:26)/ IOMx AUX V1+ (x:25)/ IOMx OUT V3- (x:27)/ IOMx AUX V1- (x:28)/ IOMx OUT V3+ (x:35)/ IOMx IC3 (x:36)/ IOMx IC3 (x:37)/ IOMx OUT V3- (x:38)
SW Data Point
OPM II Link-Category
Value # 64
Direction BSE PE
65
USIO65/AO_I
TI 34 - measured value TI 35 - measured value TI 36 - measured value TI 48 - Setpoint command TI 49 - Setpoint command TI 50 - Setpoint command
66
67 + x*4
x = 0 .. 7
2-38
DC6-011-2.01
2.6.20.
HW Pin IOMx OUT V0+ (x:1)/ IOMx IC0 (x:2)/ IOMx IC0 (x:3)/ IOMx OUT V0- (x:4)/ IOMx AUX V0+ (x:11)/ IOMx OUT V0+ (x:12)/ IOMx OUT V0- (x:13)/ IOMx AUX V0- (x:14) IOMx OUT V1+ (x:5)/ IOMx IC1 (x:6)/ IOMx IC1 (x:7)/ IOMx OUT V1- (x:8)/ IOMx AUX V0+ (x:15)/ IOMx OUT V1+ (x:16)/ IOMx OUT V1- (x:17)/ IOMx AUX V0- (x:18) IOMx OUT V2+ (x:22)/ IOMx AUX V1+ (x:21)/ IOMx OUT V2- (x:23)/ IOMx AUX V1- (x:24)/ IOMx OUT V2+ (x:31)/ IOMx IC2 (x:32)/ IOMx IC2 (x:33)/ IOMx OUT V2- (x:34) IOMx OUT V3+ (x:26)/ IOMx AUX V1+ (x:25)/ IOMx OUT V3- (x:27)/ IOMx AUX V1- (x:28)/ IOMx OUT V3+ (x:35)/ IOMx IC3 (x:36)/ IOMx IC3 (x:37)/ IOMx OUT V3- (x:38)
SW Data Point
OPM II Link-Category
Value # 64
Direction BSE PE
65
USIO65/AO_U
TI 34 - measured value TI 35 - measured value TI 36 - measured value TI 48 - Setpoint command TI 49 - Setpoint command TI 50 - Setpoint command
66
67 + x*4
x = 0 .. 7
DC6-011-2.01
2-39
2-40
DC6-011-2.01
3.
3.1.
Peripheral control module connects I/O modules via the TM bus up to 8 I/O modules connects to the basic system element via electrical Ax 1703 peripheral bus indication of function and errors via LEDs power to be supplied by PS-6620, PS-6630 or PS-6632
DC6-011-2.01
3-1
3.2.
3-2
DC6-011-2.01
3.3.
Technical Specifications
Processor and Memory Processor Program memory Main memory Parameter memory Power Supply Operating voltage 4.7 .. 5.1 VDC, max. 720 mW Power to be supplied by PS-6620, PS-6630 or PS-6632 80C251SQ-16, 16 MHz PE-ROM 256 kByte RAM 64 kByte EEPROM 512 Bytes
Mechanics and Connectors Ax 1703 peripheral bus Connector(s) for den Ax 1703 peripheral bus Dimensions Weight Transmission rate 16Mbps USB / Serie A, 4-pin USB cables, 3 m maximum length 127 x 63 x 72 mm (L x W x H, dimensions w/o DIN rail) Approx. 135 g
DC6-011-2.01
3-3
3.4.
3-4
DC6-011-2.01
4.
4.1.
Peripheral control module connects I/O modules via the TM bus up to 8 I/O modules connects to the basic system element via optical Ax 1703 peripheral bus indication of function and errors via LEDs power to be supplied by PS-6620, PS-6630 or PS-6632
DC6-011-2.01
4-1
4.2.
4-2
DC6-011-2.01
4.3.
Technical Specifications
Processor and Memory Processor Program memory Main memory Parameter memory Power Supply Operating voltage 4.75 .. 5.25 VDC, typ. 1150 mW Power to be supplied by PS-6620, PS-6630 or PS-6632 80C251SQ-16, 16 MHz PE-ROM 256 kByte RAM 64 kByte EEPROM 512 Bytes
Mechanics and Connectors Ax 1703 peripheral bus Connector(s) for den Ax 1703 peripheral bus Dimensions Weight Transmission rate 16Mbps Glass fibre (+) TOCP201 (Toshiba TOSLINK)
DC6-011-2.01
4-3
4.4.
4-4
DC6-011-2.01
5.
5.1.
Peripheral control module connects I/O modules via the TM bus up to 8 I/O modules connects to a redundant basic system element via two optical Ax 1703 peripheral buses indication of function and errors via LEDs power to be supplied by PS-6620, PS-6630 or PS-6632
DC6-011-2.01
5-1
5.2.
5-2
DC6-011-2.01
5.3.
Technical Specifications
Processor and Memory Processor Program memory Main memory Parameter memory Power Supply Operating voltage 4.75 .. 5.25 VDC, typ. 1400 mW Power to be supplied by PS-6620, PS-6630 or PS-6632 80C251SQ-16, 16 MHz PE-ROM 256 kByte RAM 64 kByte EEPROM 512 Bytes
Mechanics and Connectors Ax 1703 peripheral bus Connector(s) for den Ax 1703 peripheral bus Dimensions Weight Transmission rate 16Mbps Glass fibre (+) TOCP201 (Toshiba TOSLINK)
DC6-011-2.01
5-3
5.4.
T M 1 7 0 3
5-4
DC6-011-2.01
6.
6.1.
Power supply module input voltage 24 .. 60 VDC system voltage output U1 5.1 VDC, max. 8 W system voltage output U2 switchable 5.2 VDC, max. 2.5 W or 10 VDC, max. 2.5 W integrated voltage distribution removable screw terminals function indication via LED
DC6-011-2.01
6-1
6.2.
6-2
DC6-011-2.01
6.3.
Technical Specifications
Power Supply Operating voltage Output voltages for TM bus for external modem 2) Output power PU1 PU2 18 .. 78 VDC The voltage is supplied via terminals System voltage outpouts U1 U2 PU1,min PU1,max Output power Output total power Efficiency PU2,max PU1+U2,max PU1+U2,peak switchable 1) 5.1VDC 1% 5.2VDC +2.9% 10VDC 5% (at PU2 = 0 W) TM 1703 ACP and TM 1703 mic TM 1703 mic (CP-6020/CPC60 only)
Power consumption Pin = PU1/U1 + PU2/U2 Bridgeable interruption of the operating voltage
12.3 W 13.8 W @24 VDC 3 ms 4 ms 8.5 ms @48 VDC 18.5 ms 32 ms 63 ms @60 VDC 30 ms 49 ms 190 ms
Reverse voltage protection Overload protection Short-circuit protection Can be connected in parallel
1)
(if required set external fuse) (if required set external fuse)
switching to the higher voltage is induced exclusively by CP-6020/CPC60 and depends on its parameter setting; without switching, only the lower voltage is available via DTR circuit of the CP-6020 master control module's serial interface Internal fuse is blown, change by authorized personnel only
2) 3)
Summary for TM 1703 ACP use Available power U1 Mechanics Terminals Dimensions Weight Removable screw terminals for direct conductor assembly, up to 2.5 mm cross-section 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 245 g PU1,max 8.0 W (U2 not used)
DC6-011-2.01
6-3
6.4.
6.4.1.
Short-Circuit Protection Via the controller on the primary side of the DC/DC-transformer the output voltages 1+2 are fundamentally protected against destruction due to overload or short-circuit (current limitation of the primary current). This however has the consequence that in this case the internal fuse trips in the primary circuit and the PS-6620 fails as a result.
6.4.2.
Interruption bridging The interruption time, in case of a power failure during the diverse operating states, can be taken from following graphic.
Uin=60VDC
0
Abb_02
10
15
20
25
30
65
70
75
80
85 90 Tu [ms]
6-4
DC6-011-2.01
6.5.
DC6-011-2.01
6-5
6.6.
6-6
DC6-011-2.01
7.
7.1.
Power supply module input voltage 24 .. 60 VDC system voltage output U1 5.1 VDC, max. 8 W system voltage output U2 switchable 5.2 VDC, max. 2.5 W or 10 VDC, max. 2.5 W environmental conditions according to SIC+ removable screw terminals function indication via LED can be connected in parallel for redundancy
DC6-011-2.01
7-1
7.2.
7-2
DC6-011-2.01
7.3.
Technical Specifications
Power Supply Operating voltage Output voltages system internal 18 .. 78VDC The voltage is supplied via terminals System voltage outpouts U1 5.15VDC 2% TM 1703 ACP TM 1703 mic Interface modules for external modem 2) Output power PU1 PU2 U2 switchable 1) 5.1 .. 5.4VDC 9 .. 10VDC TM 1703 mic (CP-6020/CPC60 only)
Uin=60VDC
Uin=24VDC
Uin=48VDC
10
20
30
40
50
60
70 80 90 100 110 120 130 140 150 160 170 180 Tu [ms] Interruption Time (typ.)
Reverse voltage protection Overload protection Short-circuit protection Can be connected in parallel
1)
ja no no
3) 3)
yes
switching to the higher voltage is induced exclusively by CP-6020/CPC60 and depends on its parameter setting; without switching, only the lower voltage is available via DTR circuit of the CP-6020 master control module's serial interface Internal fuse is blown, change by authorized personnel only
2) 3)
DC6-011-2.01
7-3
Summary for TM 1703 ACP use Available power U1 Mechanics Terminals Dimensions Weight Removable screw terminals for direct conductor assembly, up to 2.5 mm cross-section 131 x 63 x 73 mm (L x W x H, dimensions w/o DIN rail) Approx. 200g PU1,max 8.0W (U2 not used)
7-4
DC6-011-2.01
7.4.
7.4.1.
Short-Circuit Protection Via the controller on the primary side of the DC/DC-transformer the output voltages 1+2 are fundamentally protected against destruction due to overload or short-circuit (current limitation of the primary current). This however has the consequence that in this case the internal fuse trips in the primary circuit and the PS-6630 fails as a result.
7.4.2.
Interruption bridging The interruption time, in case of a power failure during the diverse operating states, can be taken from following graphic.
Uin=20VDC
Uin=60VDC
0
Abb_02_a
10
20
30
40
50
60
70 80 90 100 110 120 130 140 150 160 170 180 Tu [ms] Interruption time (typical)
DC6-011-2.01
7-5
7.5.
T M 1 7 0 3
7-6
DC6-011-2.01
7.6.
DC6-011-2.01
7-7
7-8
DC6-011-2.01
8.
8.1.
Power supply module input voltage 110 .. 220 VDC system voltage output U1 5.1 VDC, max. 8 W system voltage output U2 switchable 5.2 VDC, max. 2.5 W or 10 VDC, max. 2.5 W environmental conditions according to SIC+ removable screw terminals function indication via LED can be connected in parallel for redundancy
DC6-011-2.01
8-1
8.2.
8-2
DC6-011-2.01
8.3.
Technical Specifications
Power Supply Operating voltage Output voltages system internal 82 .. 275VDC The voltage is supplied via terminals System voltage outpouts U1 5.15VDC 2% TM 1703 ACP TM 1703 mic Interface modules TM 1703 mic (CP-6020/CPC60 only)
U2 PU1,min
switchable 1)
PU1,max Output power Output total power Efficiency PU2,max PU1+U2,max PU1+U2,peak
Power consumption Pin = PU1/U1 + PU2/U2 Inrush peak current Guaranteed interruption time
Uin=220VDC
at P=4W.....T=1000ms (Uin=220VDC)
Uin=110VDC
Reverse voltage protection Overload protection Short-circuit protection Can be connected in parallel
1)
ja no no
3) 3)
yes
at P=2W.....T=1640ms (Uin=220VDC)
0 10 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 Tu [ms] Interruption Time (typ.)
switching to the higher voltage is induced exclusively by CP-6020/CPC60 and depends on its parameter setting; without switching, only the lower voltage is available via DTR circuit of the CP-6020 master control module's serial interface Internal fuse is blown, change by authorized personnel only
2) 3)
DC6-011-2.01
8-3
Summary for TM 1703 ACP use Available power U1 Mechanics Terminals Dimensions Weight Removable screw terminals for direct conductor assembly, up to 2.5 mm cross-section 131 x 63 x 73 mm (L x W x H, dimensions w/o DIN rail) Approx. 230g PU1,max 8.0W (U2 not used)
8-4
DC6-011-2.01
8.4.
8.4.1.
Short-Circuit Protection Via the controller on the primary side of the DC/DC-transformer the output voltages 1+2 are fundamentally protected against destruction due to overload or short-circuit (current limitation of the primary current). This however has the consequence that in this case the internal fuse trips in the primary circuit and the PS-6632 fails as a result.
8.4.2.
Interruption bridging The interruption time, in case of a power failure during the diverse operating states, can be taken from following graphic.
Uin=110VDC
1 0
Abb_02_b
10
20
30
40
50
60
70 80 90 100 110 120 130 140 150 160 170 180 Tu [ms] Interruption time (typical)
DC6-011-2.01
8-5
8.5.
T M 1 7 0 3
8-6
DC6-011-2.01
8.6.
DC6-011-2.01
8-7
8-8
DC6-011-2.01
9.
9.1.
Binary input module 16 inputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return signal voltage 24-60VDC removable screw terminals indication of function and states of the inputs via LEDs one (dedicated) input of each group can be used for power monitoring acquisition functions single-point information double-point information integrated totals via count pulses further functions return information to pulse command assignment
The before mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
9-1
9.2.
9-2
DC6-011-2.01
9.3.
Technical Specifications
Binary Inputs 16 binary inputs 2 groups, 8 inputs each Galvanical insulation Each group has a common return of selectable polarity One dedicated input All other inputs 24/48/60 VDC 12 V 16 V 1.01.5 mA (at 18 .. 78 V) 1878 VDC The circuits are operated by means of an external voltage. "logic 0" "logic 1" 2 ms 3 ms
Filter time Nominal voltages Operating points Rated current Input circuits
Power Supply Operating voltage 4.75.1 VDC, 170 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 225 g
DC6-011-2.01
9-3
9.4.
9.4.1.
Power Monitoring Power monitoring is activated by one parameter per group. The last input of a group (IN D07 and IN D17) can be used for power monitoring. When power monitoring is parameterized then this input has a filtertime of 2 ms. If this function isnt parameterized, the input has a filtertime of 3 ms as all other inputs. When using power monitoring, the number of binary inputs for process information is reduced to 7 inputs per group. The fused signalling voltage must be connected to these inputs. If the signalling voltage fails, the accompanying process information for the open-/closed-loop control function is frozen at the last valid state. A signalling voltage failure is signaled by periodic information sent to the open-/closed-loop control function, and by diagnostic information.
9-4
DC6-011-2.01
9.5.
DC6-011-2.01
9-5
9.6.
IN D10IN D17: One-pole input with internal common root (plus or minus)
IN D00IN D07: One-pole input with external common root (plus or minus)
.
Fig. 9-3 DI-6100 External Circuit Elements
9-6
DC6-011-2.01
9.7.
DC6-011-2.01
9-7
9-8
DC6-011-2.01
10.
10.1.
Binary input module 16 inputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return signal voltage 110/220VDC removable screw terminals indication of function and states of the inputs via LEDs one (dedicated) input of each group can be used for power monitoring acquisition functions single-point information double-point information integrated totals via count pulses further functions return information to pulse command assignment
The before mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
10-1
10.2.
10-2
DC6-011-2.01
10.3.
Technical Specifications
Binary Inputs 16 binary inputs 2 groups, 8 inputs each Galvanical insulation Each group has a common return of selectable polarity One dedicated input All other inputs 110/220 VDC 55 V 82.5 V 1.01.7 mA (at 82250 V) 82250 VDC The circuits are operated by means of an external voltage. "logic 0" "logic 1" 2 ms 3 ms
Filter time Nominal voltages Operating points Rated current Input circuits
Power Supply Operating voltage 4.75.1 VDC, 170 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 225 g
DC6-011-2.01
10-3
10.4.
10.4.1.
Power Monitoring Power monitoring is activated by one parameter per group. The last input of a group (IN D07 and IN D17) can be used for power monitoring. When power monitoring is parameterized then this input has a filtertime of 2 ms. If this function isnt parameterized, the input has a filtertime of 3 ms as all other inputs.When using power monitoring, the number of binary inputs for process information is reduced to 7 inputs per group. The fused signalling voltage must be connected to these inputs. If the signalling voltage fails, the accompanying process information for the open-/closed-loop control function is frozen at the last valid state. A signalling voltage failure is signaled by periodic information sent to the open-/closed-loop control function, and by diagnostic information.
10-4
DC6-011-2.01
10.5.
DC6-011-2.01
10-5
10.6.
IN D10IN D17: One-pole input with internal common root (plus or minus)
IN D00IN D07: One-pole input with external common root (plus or minus)
10-6
DC6-011-2.01
10.7.
DC6-011-2.01
10-7
10-8
DC6-011-2.01
11.
11.1.
Binary input module 16 inputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return signal voltage 24-60VDC removable screw terminals indication of function and states of the inputs via LEDs one (dedicated) input of each group can be used for power monitoring acquisition functions single-point information double-point information integrated totals via count pulses further functions return information to pulse command assignment
The before mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
11-1
11.2.
11-2
DC6-011-2.01
11.3.
Technical Specifications
Binary Inputs 16 binary inputs 2 groups, 8 inputs each Galvanical insulation Each group has a common return of selectable polarity one dedicated input all other inputs 24/48/60 VDC 12 V 16 V 1.01.5 mA (at 1878 V) 1878 VDC The circuits are operated by means of an external voltage. "logic 0" "logic 1" 2 ms 3 ms
Filter time Nominal voltages Operating points Rated current Input circuits
Power Supply Operating voltage 4.75.1 VDC, 170 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 225 g
DC6-011-2.01
11-3
11.4.
11.4.1.
Power Monitoring Power monitoring is activated by one parameter per group. The last input of a group (IN D07 and IN D17) can be used for power monitoring. When power monitoring is parameterized then this input has a filtertime of 2 ms. If this function isnt parameterized, the input has a filtertime of 3 ms as all other inputs. When using power monitoring, the number of binary inputs for process information is reduced to 7 inputs per group. The fused signalling voltage must be connected to these inputs. If the signalling voltage fails, the accompanying process information for the open-/closed-loop control function is frozen at the last valid state. A signalling voltage failure is signaled by periodic information sent to the open-/closed-loop control function, and by diagnostic information.
11-4
DC6-011-2.01
11.5.
DC6-011-2.01
11-5
11.6.
IN D10IN D17: One-pole input with internal common root (plus or minus)
IN D00IN D07: One-pole input with external common root (plus or minus)
11-6
DC6-011-2.01
11.7.
DC6-011-2.01
11-7
11-8
DC6-011-2.01
12.
12.1.
Binary input module 16 inputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return signal voltage 110/220VDC removable screw terminals indication of function and states of the inputs via LEDs one (dedicated) input of each group can be used for power monitoring acquisition functions single-point information double-point information integrated totals via count pulses further functions return information to pulse command assignment
The before mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
12-1
12.2.
12-2
DC6-011-2.01
12.3.
Technical Specifications
Binary Inputs 16 binary inputs 2 groups, 8 inputs each galvanical insulation each group has a common return of selectable polarity one dedicated input all other inputs 110/220 VDC 55 V 82.5 V 1.01.7 mA (at 82250 V) 82250 VDC the circuits are operated by means of an external voltage. "logic 0" "logic 1" 2 ms 3 ms
Filter time Nominal voltages Operating points Rated current Input circuits
Power Supply Operating voltage 4.75.1 VDC, 170mW the voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) approx. 225 g
DC6-011-2.01
12-3
12.4.
12.4.1.
Power Monitoring Power monitoring is activated by one parameter per group. The last input of a group (IN D07 and IN D17) can be used for power monitoring. When power monitoring is parameterized then this input has a filtertime of 2 ms. If this function isnt parameterized, the input has a filtertime of 3 ms as all other inputs. When using power monitoring, the number of binary inputs for process information is reduced to 7 inputs per group. The fused signalling voltage must be connected to these inputs. If the signalling voltage fails, the accompanying process information for the open-/closed-loop control function is frozen at the last valid state. A signalling voltage failure is signaled by periodic information sent to the open-/closed-loop control function, and by diagnostic information.
12-4
DC6-011-2.01
12.5.
DC6-011-2.01
12-5
12.6.
IN D10IN D17: One-pole input with internal common root (plus or minus)
IN D00IN D07: One-pole input with external common root (plus or minus)
12-6
DC6-011-2.01
12.7.
DC6-011-2.01
12-7
12-8
DC6-011-2.01
13.
13.1.
Binary input module 16 inputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return signal voltage 220VDC removable screw terminals indication of function and states of the inputs via LEDs one (dedicated) input of each group can be used for power monitoring acquisition functions single-point information double-point information integrated totals via count pulses further functions return information to pulse command assignment
The before mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
13-1
13.2.
13-2
DC6-011-2.01
13.3.
Technical Specifications
Binary Inputs 16 binary inputs 2 groups, 8 inputs each Galvanical insulation Each group has a common return of selectable polarity One dedicated input All other inputs 220 VDC 110 V 165 V 1.11.5 mA (at 165 :: 250V) 165250 VDC The circuits are operated by means of an external voltage. "logic 0" "logic 1" 2 ms 3 ms
Filter time Nominal voltages Operating points Rated current Input circuits
Power Supply Operating voltage 4.75.1 VDC, 170 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 225 g
DC6-011-2.01
13-3
13.4.
13.4.1.
Power Monitoring Power monitoring is activated by one parameter per group. The last input of a group (IN D07 and IN D17) can be used for power monitoring. When power monitoring is parameterized then this input has a filtertime of 2 ms. If this function isnt parameterized, the input has a filtertime of 3 ms as all other inputs. When using power monitoring, the number of binary inputs for process information is reduced to 7 inputs per group. The fused signalling voltage must be connected to these inputs. If the signalling voltage fails, the accompanying process information for the open-/closed-loop control function is frozen at the last valid state. A signalling voltage failure is signaled by periodic information sent to the open-/closed-loop control function, and by diagnostic information.
13-4
DC6-011-2.01
13.5.
DC6-011-2.01
13-5
13.6.
IN D10IN D17: One-pole input with internal common root (plus or minus)
IN D00IN D07: One-pole input with external common root (plus or minus)
13-6
DC6-011-2.01
13.7.
DC6-011-2.01
13-7
13-8
DC6-011-2.01
14.
14.1.
Binary output module 16 transistor outputs (2 groups of 8 each) galvanically insulated by optocouplers each group has a common return switching voltage 24-60VDC all outputs proof against continued short circuit to increase switching capacity 2 outputs can be connected in parallel no impact on other outputs if one is short-circuit removable screw terminals indication of function and states of the outputs via LEDs output functions pulse commands binary information output pulse commands and binary information output cannot be mixed on the same module
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
14-1
14.2.
14-2
DC6-011-2.01
14.3.
Technical Specifications
Binary Outputs 16 binary outputs (transistor) 2 groups, 8 outputs each Galvanical insulation Each group has a common return 24/48/60 VDC 1878 VDC Due to thermal loading capacity of the module: 0.25 A at 24, 48, and 60 VDC (for each output, if 16 outputs are active at the same time) 0.35 A when connecting 2 outputs in parallel (for each pair ot outputs, if 8 pairs of outputs are active at the same time) 6W 12 W 15 W at 24 VDC at 48 VDC at 60 VDC when connecting in parallel: 8.4 W when connecting in parallel: 16.8 W when connecting in parallel: 21 W
Due to electrical ratings of the transistor switch: 0.9 A at 1878 VDC (only 1 output active) 78 VDC 70.2 W no 10 A current limitation if the current limitation operates, current is cut off after 10 s cyclic reclosing break time 300 s make time 10 s at 78 VDC
Maximum switching voltage Maximum switching power Overload proof Proof against continued short-circuit
Switching cycles Switching frequency Output circuit voltage drop Dynamic withstand capability
Unlimited max. 100 Hz < 0.5 V at 0.25 A max. 100 nF at 60V 500 ms (any with external free-wheeling diode ) Z 100 , line length up to 3 km IN 150 mA (ION 1.8 A)
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 260 g
DC6-011-2.01
14-3
14.4.
14-4
DC6-011-2.01
14.5.
OUT D10OUT D17: One-pole input with switched plus and internal common root
OUT D00OUT D07: One-pole input with switched plus and external common root
DC6-011-2.01
14-5
14.6.
14-6
DC6-011-2.01
15.
15.1.
Binary output module 8 relay outputs galvanically insulated switching voltage 24-220VDC/230VAC the outputs can switch DC and AC voltages removable screw terminals indication of function and states of the outputs via LEDs output functions pulse commands binary information output pulse commands and binary information output cannot be mixed on the same module
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
15-1
15.2.
15-2
DC6-011-2.01
15.3.
Technical Specifications
Binary otputs 8 binary outputs (relay) nominal voltage 8 outputs, potential-free Galvanical insulation 24/48/60/110/220 VDC 110/230 VAC maximum continuous current maximum switching voltage switching cycles sitching capacity DC voltage min. 50 mW at 5 VDC max according to diagram 2A 5A 250 VDC 253 VAC 3 x 104 for 1 minute
Mechanics and Connectors terminals dimensions weight removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) approx. 265 g
DC6-011-2.01
15-3
15.4.
15-4
DC6-011-2.01
15.5.
OUT D00 One-pole output with switched plus OUT D01 One-pole output with switched minus OUT D02/OUT D03 2-pole output
DC6-011-2.01
15-5
a)
RL Si
b)
RL
Si
15-6
DC6-011-2.01
b) without protection with protection B-charakteristic 4A/10kA Z-charakteristic 4A/10kA C-charakteristic 2A/10kA
4A 4A 2A
DC6-011-2.01
15-7
15.6.
15-8
DC6-011-2.01
16.
16.1.
Analog input module 4 inputs (2 groups of 2 each) galvanically insulated by optocouplers acquisition of currents 20mA acquisition of voltages 10V removable screw terminals function indication via LED acquisition of currents and voltages cannot be mixed on the same I/O module recognition of open-circuit with acquisition of currents acquisition functions currents and voltages currents and voltages cannot be mixed on the same module
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
16-1
16.2.
16-2
DC6-011-2.01
16.3.
Technical Specifications
Analog Inputs 4 analog inputs 2 groups, 2 inputs each Groups are galvanically insulated from one another Voltage between 2 inputs of a group max. 4 VDC Current measurement Voltage measurement Overrange Resolution Accuracy 0.013% 0.025% 0.15% 0.4% 0.5% 122.5 11.3 k Common mode rejection ratio Current inputs Voltage inputs Normal mode rejection ratio Current inputs Voltage inputs Input circuits -200+20 mA -100+10 V typ. 2% at 20 mA at 10 V at 25 C at 050 C at 2070 C at 20 mA at 10 V min. 70 dB min. 90 dB min. 73 dB min. 90 dB 0 dB +20 dB/decade 0 dB +20 dB/decade (10 Hz1 MHz) (10 Hz500 Hz) (10 Hz1 MHz) (10 Hz500 Hz) (10 Hz7.5 kHz) (7.5 kHz1 MHz) (10 Hz7.5 kHz) (7.5 kHz1 MHz)
Measuring ranges
Input impedance
External sensors, auxiliary voltage 18 VDC78 VDC. The circuits are operated by means of an external voltage.
Power Supply Operating voltage 4.75.1 VDC, max. 480 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 225 g
DC6-011-2.01
16-3
16.4.
16-4
DC6-011-2.01
16.5.
IN V2: Connection of a 2-wire measuring transducer with current output IN V3: Connection of a 4-wire measuring transducer with voltage output, the I/O module feeds the auxiliary supply
IN V0: Connection of a 3-wire measuring transducer with current output, the I/O module feeds the auxiliary supply IN V1: Connection of a 4-wire measuring transducer with current output, the I/O module feeds the auxiliary supply
DC6-011-2.01
16-5
16.6.
16-6
DC6-011-2.01
17.
17.1.
Analog input module 4 inputs (2 groups of 2 each) galvanically insulated by optocouplers acquisition of currents 5mA acquisition of voltages 10V removable screw terminals function indication via LED acquisition of currents and voltages cannot be mixed on the same I/O module recognition of open-circuit with acquisition of currents acquisition functions currents and voltages
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
17-1
17.2.
17-2
DC6-011-2.01
17.3.
Technical Specifications
Analog Inputs 4 analog inputs 2 groups, 2 inputs each Groups are galvanically insulated from one another Voltage between 2 inputs of a group max. 4 VDC Current measurement Voltage measurement Overrange 0.013% 0.025% 0.15% 0.4% 0.5% 490 11.3 k Current inputs Voltage inputs Normal mode rejection ratio Current inputs Voltage inputs Input circuits -50+5 mA -100+10 V typ. 2% at 5 mA bei 10 V at 25C at 050C at 2070C at 5 mA at 10 V min. 70 dB min. 90 dB min. 73 dB min. 90 dB 0 dB +20 dB/decade 0 dB +20 dB/decade (10 Hz1 MHz) (10 Hz500 Hz) (10 Hz1 MHz) (10 Hz500 Hz) (10 Hz7.5 kHz) (7.5 kHz1 MHz) (10 Hz7.5 kHz) (7.5 kHz1 MHz)
Measuring ranges
Resolution Accuracy
External sensors, auxiliary voltage 1878 VDC. The circuits are operated by means of an external voltage.
Power Supply Operating voltage 4.75.1 VDC, max. 480 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73mm (LxWxH, dimensions w/o DIN rail) Approx. 225g
DC6-011-2.01
17-3
17.4.
17-4
DC6-011-2.01
17.5.
IN V2: Connection of a 2-wire measuring transducer with current output IN V3: Connection of a 4-wire measuring transducer with voltage output, the I/O module feeds the auxiliary supply
IN V0: Connection of a 3-wire measuring transducer with current output, the I/O module feeds the auxiliary supply IN V1: Connection of a 4-wire measuring transducer with current output, the I/O module feeds the auxiliary supply
DC6-011-2.01
17-5
17.6.
17-6
DC6-011-2.01
18.
18.1.
Analog input module 4 inputs (2 groups of 2 each) galvanically insulated by optocouplers acquisition of temperatures via Pt100/Ni100 resistance measurement in two-, three- or four-wire technology for resistance measurement one current source is assigned to each input noise rejection removable screw terminals function indication via LED acquisition functions temperatures
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
18-1
18.2.
18-2
DC6-011-2.01
18.3.
Technical Specifications
Analog Inputs 4 analog inputs 2 groups, 2 inputs each Groups are galvanically insulated from one another Voltage between 2 inputs of a group max. 20 VDC Resistance measurement Overrange Input impedance Resolution Noise rejection Conversion time Approx. 2 M 11 m 16.7 Hz, 50 Hz, 60 Hz Noise rejection for 50 Hz Noise rejection for 60 Hz Noise rejection for 16.7 Hz Accuracy settable for each group 120 ms 100 ms 180 ms 50400 typ. 20% (Pt100, Ni100)
Measuring range
0.19% at 25 C 0.21% at 050 C (because of the measuring method there is no dependence on the accuracy of the constant-current source) 2 mA Sum of go-and-return line 16.7 Hz, 50 Hz, 60 Hz20 kHz 10 Hz1 MHz max. 40 > 100 dB > 70 dB > 100 dB
Normal mode rejection ratio Input circuits Current Outputs 4 current outputs (constant-current source) Accuracy Power Supply Operating voltage
4.75.1 VDC, max. 450 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 235 g
DC6-011-2.01
18-3
18.4.
18-4
DC6-011-2.01
18.5.
DC6-011-2.01
18-5
18.6.
18-6
DC6-011-2.01
19.
19.1.
Analog output module 4 outputs galvanically insulated by optocouplers output of currents 20mA, 10mA output of voltages 10V removable screw terminals function indication via LED output functions setpoint values by means of currents and voltages
The above mentioned functions are described in detail in the document SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104
DC6-011-2.01
19-1
19.2.
19-2
DC6-011-2.01
19.3.
Technical Specifications
Analog Outputs 4 analog outputs Current output All outputs galvanically insulated max. 20 mA on max. 500 load max. 10 mA on max. 1 k load Voltage output Resolution Settling time Accuracy max. 10 V on min. 1 k load 0.025% 1 ms 0.3% 0.4% 0.7% at 25 C at 050 C at -2070 C at 20 mA, 10 mA, 10 V
4.75.1 VDC, max. 1900 mW The voltage is picked off at the TM bus
Mechanics and Connectors Terminals Dimensions Weight Removable screw terminals (grid size 5.08) 131x63x73 mm (LxWxH, dimensions w/o DIN rail) Approx. 300 g
DC6-011-2.01
19-3
19.4.
19-4
DC6-011-2.01
19.5.
OUT V2: 2-wire connection of a load with current output OUT V3: 3-wire connection of a load with current output
OUT V0: 4-wire connection of a load with current output OUT V1: 2-wire connection of loads in series with current output
DC6-011-2.01
19-5
19.6.
19-6
DC6-011-2.01
System Components
20.
System Components
20.1.
Modules
GC6-630
GC6-632
GC6-400
DC6-011-2.01
20-1
System Components
GC6-402
DI-6100
GC6-100
DI-6101
GC6-101
DI-6102
GC6-102
20-2
DC6-011-2.01
System Components
DI-6104
GC6-104
GC6-200
GC6-212
AI-6300
GC6-300
DC6-011-2.01
20-3
System Components
AI-6310
GC6-310
GC6-380
20-4
DC6-011-2.01
System Components
20.2.
Accessories
20.2.1.
Designation USB-Cable for Peripheral Controller (1,5m) USB-Cable for Peripheral Controller (2,0m) USB-Cable for Peripheral Controller (3,0m)
20.2.2.
Connecting Cable: Peripheral Control Module PE-6401(2) Components for fiber optic cable (0 .. 200m)
Designation FO-INDOORCABLE-200-DUP-BREAK-ROUND
FO-OUTDOORCABLE-200-2FIB-ARM
TF7-036--
TF7-066
FO-CONNECTOR-ODLP-200
TF7-015--
DC6-011-2.01
20-5
System Components
20.2.3.
Miscellaneous
Designation PHOENIX CR-MSTB/ Zack-Strip 10 pces Item Number PHO+0807216
PHO+1734401
TC6-055-
WEI+147220
WAG+249-117
Bus Terminator
TC6-050
Labeled screw terminal (1-10); without coding Labeled screw terminal (11-20); without coding Labeled screw terminal (21-30); without coding Labeled screw terminal (31-40); without coding
WEI+168551
20-6
DC6-011-2.01
Further Documents
21.
Further Documents
System Data Sheet TM 1703 ACP SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104 Data Sheet CM-0842 Data Sheet CM-0843
DC6-011-2.01
21-1
Further Documents
21-2
DC6-011-2.01
A.
Process-technical Parameters
USIO65 Revision 07
A.1.
USIO65/AI_I
AI_I - current value acquisition
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicMeasured value 15 bit + sign normalized (34) Measured value 15 bit + sign scaled (35) Measured value short floating point (36) String 100 Char Float [###.##] -50.0 to 50.0 Float [###.##] -50.0 to 50.0 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] NO [1] YES [0] NO Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Nominal range in the physical unit of the input/output (0%) (S) Nominal range in the physical unit of the input/output (100%) Technological or normalized value 0% (S)
--20 20 -32000
Y_100%
32000
Normal
Zero range suppression (and check of the plausibility limits) (S) Blocking (=not used) (S)
NO NO
Normal Normal
DC6-011-2.01
A-1
[1] YES label With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin The noise rejection takes place for the parametrized line frequency Change threshold in % of X_100% (S) AI_T: % of temperature range Limit of not plausible range. Parameter is only effective, if the parameter zero_range_a_MV_conv is set to free parametrizable (in the physical unit of the input) (S) OV suppression time in seconds, 0=no OV suppression Processing grid in seconds 0 - 99 in %. 0% = no smoothing, 99% = highest possible smoothing The measuring range can be adapted with changing the load (S) Change threshold in % of X_100% (S) AI_T: % of temperature range lower limit of zero range in % of X_100% (S) upper limit of zero range in % of X_100% (S) Technological or normalized value of zero range (S) see Label -Normal
line frequency
[0] 50Hz [1] 60Hz [2] 16.7Hz Float [####.#] 0 to 1000.0 Float [####.##] -103.00 to 103.00 Integer [###] 0 to 255 Float [##.#] 0.1 to 25.5 Integer [##] 0 to 99 [0] NO [1] YES Float [###.##] 0 to 103.00 Float [####.##] -103.00 to 103.00 Float [####.##] -103.00 to 103.00 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] standard [1] free configurable
50Hz
Normal
thresh_additive MV_conv_free_Xl
150 -103
Normal Expert
OV_suppr_t Processing grid Smoothing standard load thresh_uncond zero_range_Xzl zero_range_Xzu zero_range_Yz
0 0.1 0 YES 2 -5 5 0
zero_range_a MV_conv
Zero range suppression (and check of the plausibility limits) either standard or free parametrizable (S)
standard
Expert
A.2.
USIO65/AI_T
AI_T - Temperature Input
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
A-2
DC6-011-2.01
TI Connection techn.
Type identification according to IEC 60870-5-101/104 Connection technique for temperature acquisition (S)
dynamicMeasured value short floating point (36) [0] 2 wire [1] 3 wire [2] 4 wire String 100 Char [0] PT100: -50 to 350 degrees celsius [1] PT100: -100 to 700 degrees celsius [2] NI100: -60 to 250 degrees celsius [0] NO [1] YES see Label
-4 wire
Normal Normal
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Measuring range
Normal Normal
block label
Blocking (=not used) (S) With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin The noise rejection takes place for the parametrized line frequency Change threshold in % of X_100% (S) AI_T: % of temperature range 0 - 99 in %. 0% = no smoothing, 99% = highest possible smoothing Change threshold in % of X_100% (S) AI_T: % of temperature range Value selection. Either the resistance value or the temperature value is transferred.
NO --
Normal Normal
line frequency
[0] 50Hz [1] 60Hz [2] 16.7Hz Float [####.#] 0 to 1000.0 Integer [##] 0 to 99 Float [###.##] 0 to 103.00 [0] temperature (C) [1] temperature (F) [2] resistor
50Hz
Normal
A.3.
USIO65/AI_U
AI_U - voltage value acquisition
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
DC6-011-2.01
A-3
TI
dynamicMeasured value 15 bit + sign normalized (34) Measured value 15 bit + sign scaled (35) Measured value short floating point (36) Float [###.##] -10.0 to 10.0 Float [###.##] -10.0 to 10.0 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] NO [1] YES [0] NO [1] YES [0] 50Hz [1] 60Hz [2] 16.7Hz Float [####.#] 0 to 1000.0 Float [####.##] -103.00 to 103.00 Integer [###] 0 to 255 Float [##.#] 0.1 to 25.5 Integer [##] 0 to 99 [0] NO [1] YES Float [###.##] 0 to 103.00 Float [####.##] -103.00 to 103.00 Float [####.##] -103.00 to 103.00 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] standard [1] free configurable
--
Normal
Nominal range in the physical unit of the input/output (0%) (S) Nominal range in the physical unit of the input/output (100%) Technological or normalized value 0% (S)
-10 10 -32000
Y_100%
32000
Normal
Zero range suppression (and check of the plausibility limits) (S) Blocking (=not used) (S) The noise rejection takes place for the parametrized line frequency Change threshold in % of X_100% (S) AI_T: % of temperature range Limit of not plausible range. Parameter is only effective, if the parameter zero_range_a_MV_conv is set to free parametrizable (in the physical unit of the input) (S) OV suppression time in seconds, 0=no OV suppression Processing grid in seconds 0 - 99 in %. 0% = no smoothing, 99% = highest possible smoothing The measuring range can be adapted with changing the load (S) Change threshold in % of X_100% (S) AI_T: % of temperature range lower limit of zero range in % of X_100% (S) upper limit of zero range in % of X_100% (S) Technological or normalized value of zero range (S)
NO NO 50Hz
thresh_additive MV_conv_free_Xl
150 -103
Normal Expert
OV_suppr_t Processing grid Smoothing standard load thresh_uncond zero_range_Xzl zero_range_Xzu zero_range_Yz
0 0.1 0 YES 2 -5 5 0
zero_range_a MV_conv
Zero range suppression (and check of the plausibility limits) either standard or free parametrizable (S)
standard
Expert
A-4
DC6-011-2.01
A.4.
USIO65/AO_I
AO_I - Analog Output Current
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicMeasured value 15 bit + sign normalized (34) Measured value 15 bit + sign scaled (35) Measured value short floating point (36) Setpoint value positioning command stand. (48) Setpoint value positioning command scaled (49) Setpoint value positioning command short floating point (50) [0] keep [2] Substitute value String 100 Char Float [###.##] -20.0 to 20.0 Float [###.##] -20.0 to 20.0 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] NO [1] YES see Label Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
Behavior at failure This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Nominal range in the physical unit of the input/output (0%) (S) Nominal range in the physical unit of the input/output (100%) Technological or normalized value 0% (S)
Y_100%
32000
Normal
block label
Blocking (=not used) (S) With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
NO --
Normal Normal
SID-BSE
[0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU
Automatic
Expert
DC6-011-2.01
A-5
[5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [1] spontaneous Float [####.#] 0 to 6553.5 Automatic/ R-SID Expert
SID-ST
Expert
fail_subst value
Expert
Source of datapoint Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission)
spontaneo us 0
Expert Expert
A-6
DC6-011-2.01
A.5.
USIO65/AO_U
AO_U - Analog Output Voltage
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicMeasured value 15 bit + sign normalized (34) Measured value 15 bit + sign scaled (35) Measured value short floating point (36) Setpoint value positioning command stand. (48) Setpoint value positioning command scaled (49) Setpoint value positioning command short floating point (50) [0] keep [2] Substitute value String 100 Char Float [###.##] -20.0 to 20.0 Float [###.##] -20.0 to 20.0 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [0] NO [1] YES see Label Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
Behavior at failure This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Nominal range in the physical unit of the input/output (0%) (S) Nominal range in the physical unit of the input/output (100%) Technological or normalized value 0% (S)
Y_100%
32000
Normal
block label
Blocking (=not used) (S) With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
NO --
Normal Normal
SID-BSE
[0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU
Automatic
Expert
DC6-011-2.01
A-7
[5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Float [#################.###] -1000000000000000.000 to 1000000000000000.000 [1] spontaneous Float [####.#] 0 to 6553.5 Automatic/ R-SID Expert
SID-ST
Expert
fail_subst value
Expert
Source of datapoint Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission)
spontaneo us 0
Expert Expert
A-8
DC6-011-2.01
A.6.
USIO65/DI_CV
DI_CV - Counter Value
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Inversion (S) This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Pulse value (S) Conditioned value type (S) Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicCount 31 bit + sign with sequence no. (37) [0] NO [1] YES String 100 Char Float [####.####] 0.0001 to 9999 [0] latched absolute value [1] latched relative value [0] 31Bit Integer [1] 24Bit Integer [2] 2 decades [3] 3 decades [4] 4 decades [5] 5 decades [6] 6 decades [7] 7 decades [8] 8 decades [9] 9 decades [0] NO [1] YES [0] 1 minute [1] 2 minutes [2] 3 minutes [3] 5 minutes [4] 10 minutes [5] 15 minutes [6] 30 minutes [7] 60 minutes [0] 1 minute [1] 2 minutes [2] 3 minutes [3] 5 minutes [4] 10 minutes [5] 15 minutes [6] 30 minutes [7] 60 minutes Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
Value range
Normal
block interval_time_0
Blocking (=not used) (S) Interval time. As transmission trigger or latch trigger of the counts it is also possible to set an interval. The belonging time is to configure here.
NO 1 minute
Normal Normal
interval_time_1
Interval time. As transmission trigger or latch trigger of the counts it is also possible to set an interval. The belonging time is to configure here.
1 minute
Normal
DC6-011-2.01
A-9
label
With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Transmission prompting. The initiating for the transfer of the latched count can happen through a counter interrogation message (group), through adjustable intervals, or through the function diagramm. (S)
see Label
--
Normal
transm_prompting
[0] counter group 1 [1] counter group 2 [2] counter group 3 [3] counter group 4 [4] function diagram [5] Interval 0 [6] Interval 1 [0] NO [1] YES [0] counter group 1 [1] counter group 2 [2] counter group 3 [3] counter group 4 [4] function diagram [5] Interval 0 [6] Interval 1 [8] with initiation of transmission Float [####.#] 0.1 to 6553.5 0
counter group 1
Normal
SVM_monitoring latch_prompting
Power monitoring. The sensor voltage is monitored by an own power monitoring input (S) Latch prompting can be different to the transmission prompting (S)
Expert Expert
message_blocking_t
Message blocking time in seconds. During this time period, identical messages will be discarded without error information.
Expert
A.7.
USIO65/DI_DI
DI_DI - Digital Input - Double Point Information
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Inversion (S) Inversion (S) This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Blocking (=not used) (S) Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicD.-point information (31) [0] NO [1] YES [0] NO [1] YES String 100 Char [0] NO [1] YES Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
-NO NO -NO
A-10
DC6-011-2.01
command_assessment_t
Command assessment time in seconds. 0=switch is not controlled by a command. After a given command during this time all reaction to the command are attributed. (S) Faulty position suppression time in seconds. 0= no faulty position suppression (S) Intermediate position suppression time in seconds. 0=no intermediate position suppression (S) With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N) Time for signalling the automatic reclosure in seconds 0=no signalling of autom. reclosure (S) Number of transients for flutter suppression (S) Datapoint quality discriptor for fluttery binary information Flutter time in seconds. 0=no fluttersuppression (S)
Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 see Label
Normal
faulty_pos_t
Normal
int_posit_t
Normal
label
--
Normal
use_CAEx_plus AR_sign_t
[0] No [1] Yes Float [##.#] 0.1 to 25.5 0 Integer [###] 1 to 255 [0] BL [1] IV Float [####.#] 0.1 to 6553.5 0 [0] NO [1] YES Float [##.###] 0.001 to 16.383 0
No 0
Normal Expert
1 BL 0
SVM_monitoring SW_Filter_t
Power monitoring. The sensor voltage is monitored by an own power monitoring input (S) Software filter-time in s (S)
NO 0.000
Expert Expert
A.8.
USIO65/DI_SI
DI_SI - Digital Input - Single Point Information
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Inversion (S) Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) [0] NO [1] YES Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Inversion
-NO
Normal Normal
DC6-011-2.01
A-11
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Blocking (=not used) (S) With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N) Number of transients for flutter suppression (S) Datapoint quality discriptor for fluttery binary information Flutter time in seconds. 0=no fluttersuppression (S)
-NO --
[0] No [1] Yes Integer [###] 1 to 255 [0] BL [1] IV Float [####.#] 0.1 to 6553.5 0 [0] NO [1] YES Float [##.###] 0.001 to 16.383 0 [0] Standard [1] blocking for revision
No 1 BL 0
SVM_monitoring SW_Filter_t
Power monitoring. The sensor voltage is monitored by an own power monitoring input (S) Software filter-time in s (S)
NO 0.000
Expert Expert
input function
Functionality of the binary input This parameterization permits to disable the information input for revision handling.
Standard
Expert
A.9.
USIO65/DO_DC_1POL
DO_DC_1POL - Double Command Output 1-pole
Parameter Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) Double command (46) Tap positioning command (47) String 100 Char String 100 Char Default 255 Mode Normal
CASDU1
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
Longtext RS_Image
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Parameter works only with ACP 1703 platform
---
Normal Normal
A-12
DC6-011-2.01
label
With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
see Label
--
Normal
output_t_0
Float [###.##] 0.01 to 327.67 Float [###.##] 0.01 to 327.67 Float [##.#] 0.1 to 25.5 0 Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted [0] Peripherals [1] open-/closed loop control function [2] both (logical or) [0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU
0.01
Normal
output_t_1
0.01
Normal
1_out_of_n_t_0
Expert
1_out_of_n_t_1
Expert
Command_prolong_t
Expert
QOC>8 RS_Mon_Source_0
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0. Source of state information for state information monitoring
Expert Expert
RS_Mon_Source_1
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state_0
Expert
RS_outp_same_state_1
Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
DC6-011-2.01
A-13
[10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 Automatic/ R-SID Expert
SID-ST
Expert
Sw_Seq_addtl_com_0
no command
Expert
A-14
DC6-011-2.01
[662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11
DC6-011-2.01
A-15
[730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_addtl_com_1 Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 no command Expert
A-16
DC6-011-2.01
[668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17
DC6-011-2.01
A-17
[736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_command_seq _0 Sw_Seq_command_seq _1 Sync_Input_t_0 Switching sequence: output additional command before or after the command Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after after 0 Expert Expert Expert
Sync_Input_t_1
Expert
Sync_t_0
Expert
Sync_t_1
Expert
select_execute_t
Expert
A-18
DC6-011-2.01
A.10.
USIO65/DO_R_DC_1,5POL
DO_R_DC_1,5POL - Double Command Output 1,5-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) Double command (46) Tap positioning command (47) String 100 Char String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
----
output_t_0
Float [###.##] 0.01 to 327.67 Float [###.##] 0.01 to 327.67 Float [##.#] 0.1 to 25.5 0 Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted [0] Peripherals [1] open-/closed loop control function [2] both (logical or) [0] Peripherals [1] open-/closed loop control function [2] both (logical or)
0.01
Normal
output_t_1
0.01
Normal
1_out_of_n_t_0
Expert
1_out_of_n_t_1
Expert
Command_prolong_t
Expert
QOC>8 RS_Mon_Source_0
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0. Source of state information for state information monitoring
Expert Expert
RS_Mon_Source_1
Peripherals
Expert
DC6-011-2.01
A-19
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID
Expert
RS_outp_same_state_0
Expert
RS_outp_same_state_1
Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
A-20
DC6-011-2.01
SID-ST
Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned
[0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07
Expert
Sw_Seq_addtl_com_0
no command
Expert
DC6-011-2.01
A-21
[696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13
A-22
DC6-011-2.01
[764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_addtl_com_1 Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 no command Expert
DC6-011-2.01
A-23
[702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_command_seq Switching sequence: output additional command before [0] after after Expert
A-24
DC6-011-2.01
_0 Sw_Seq_command_seq _1 Sync_Input_t_0
or after the command Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission)
[1] before [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after 0 Expert Expert
Sync_Input_t_1
Expert
Sync_t_0
Expert
Sync_t_1
Expert
select_execute_t
Expert
A.11.
USIO65/DO_R_DC_1POL
DO_R_DC_1POL - Double Command Output 1-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) Double command (46) Tap positioning command (47) String 100 Char String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
----
DC6-011-2.01
A-25
output_t_0
Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
Float [###.##] 0.01 to 327.67 Float [###.##] 0.01 to 327.67 Float [##.#] 0.1 to 25.5 0 Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted [0] Peripherals [1] open-/closed loop control function [2] both (logical or) [0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU
0.01
Normal
output_t_1
0.01
Normal
1_out_of_n_t_0
Expert
1_out_of_n_t_1
Expert
Command_prolong_t
Expert
QOC>8 RS_Mon_Source_0
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0. Source of state information for state information monitoring
Expert Expert
RS_Mon_Source_1
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state_0
Expert
RS_outp_same_state_1
Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
A-26
DC6-011-2.01
[14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 Automatic/ R-SID Expert
SID-ST
Expert
Sw_Seq_addtl_com_0
no command
Expert
DC6-011-2.01
A-27
[666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15
A-28
DC6-011-2.01
[734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_addtl_com_1 Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 no command Expert
DC6-011-2.01
A-29
[672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03
A-30
DC6-011-2.01
[740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_command_seq _0 Sw_Seq_command_seq _1 Sync_Input_t_0 Switching sequence: output additional command before or after the command Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after after 0 Expert Expert Expert
Sync_Input_t_1
Expert
Sync_t_0
Expert
Sync_t_1
Expert
select_execute_t
Expert
A.12.
USIO65/DO_R_DC_2POL
DO_R_DC_2POL - Double Command Output 2-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission
Default 255
Mode Normal
DC6-011-2.01
A-31
CASDU2
Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104
Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) Double command (46) Tap positioning command (47) String 100 Char String 100 Char see Label
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
----
output_t_0
Float [###.##] 0.01 to 327.67 Float [###.##] 0.01 to 327.67 Float [##.#] 0.1 to 25.5 0 Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted [0] Peripherals [1] open-/closed loop control function [2] both (logical or) [0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM-
0.01
Normal
output_t_1
0.01
Normal
1_out_of_n_t_0
Expert
1_out_of_n_t_1
Expert
Command_prolong_t
Expert
QOC>8 RS_Mon_Source_0
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0. Source of state information for state information monitoring
Expert Expert
RS_Mon_Source_1
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state_0
Expert
A-32
DC6-011-2.01
[5] CON- /no output RS_outp_same_state_1 Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself CON+ /output (com_prolo ng_t)/TER MExpert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
SID-ST
Expert
DC6-011-2.01
A-33
Sw_Seq_addtl_com_0
[0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02
no command
Expert
A-34
DC6-011-2.01
[707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_addtl_com_1 Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 no command Expert
DC6-011-2.01
A-35
[645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10
A-36
DC6-011-2.01
[713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_command_seq _0 Sw_Seq_command_seq _1 Sync_Input_t_0 Switching sequence: output additional command before or after the command Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 [0] after [1] before [0] after [1] before Float [####.#] 0.1 to 6553.5 0 after after 0 Expert Expert Expert
DC6-011-2.01
A-37
Sync_Input_t_1
Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission)
Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5
Expert
Sync_t_0
Expert
Sync_t_1
Expert
select_execute_t
Expert
A.13.
USIO65/DO_R_SC_1,5POL
DO_R_SC_1,5POL - Single Command Output 1,5-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) String 100 Char Float [###.##] 0.01 to 327.67 String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext Output_t
--0.01
RS_Image label
---
Normal Normal
1_out_of_n_t
Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted
Expert
Command_prolong_t
Expert
QOC>8
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0.
not accepted
Expert
A-38
DC6-011-2.01
RS_Mon_Source
[0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
SID-ST
Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned
Automatic/ point-topoint/BSE
Expert
DC6-011-2.01
A-39
[252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Sw_Seq_addtl_com Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12
itself
no command
Expert
A-40
DC6-011-2.01
[699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16
DC6-011-2.01
A-41
[767] IOM7 - OUT D17 Sw_Seq_command_seq Sync_Input_t Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after 0 Expert Expert
Sync_t
Expert
select_execute_t
Expert
A.14.
USIO65/DO_R_SC_1POL
DO_R_SC_1POL - Single Command Output 1-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) String 100 Char Float [###.##] 0.01 to 327.67 String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext Output_t
--0.01
RS_Image label
---
Normal Normal
1_out_of_n_t
Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted
Expert
Command_prolong_t
Expert
QOC>8
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0.
not accepted
Expert
A-42
DC6-011-2.01
RS_Mon_Source
[0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
SID-ST
Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned
Automatic/ point-topoint/BSE
Expert
DC6-011-2.01
A-43
[252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Sw_Seq_addtl_com Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12
itself
no command
Expert
A-44
DC6-011-2.01
[699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16
DC6-011-2.01
A-45
[767] IOM7 - OUT D17 Sw_Seq_command_seq Sync_Input_t Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after 0 Expert Expert
Sync_t
Expert
select_execute_t
Expert
A.15.
USIO65/DO_R_SC_2POL
DO_R_SC_2POL - Single Command Output 2-pole (Relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) String 100 Char Float [###.##] 0.01 to 327.67 String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext Output_t
--0.01
RS_Image label
---
Normal Normal
1_out_of_n_t
Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted
Expert
Command_prolong_t
Expert
QOC>8
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0.
not accepted
Expert
A-46
DC6-011-2.01
RS_Mon_Source
[0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID
Peripherals
Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
SID-ST
Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned
Automatic/ point-topoint/BSE
Expert
DC6-011-2.01
A-47
[252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Sw_Seq_addtl_com Switching sequence: Select the additional command [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 [669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12
itself
no command
Expert
A-48
DC6-011-2.01
[699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00 [737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16
DC6-011-2.01
A-49
[767] IOM7 - OUT D17 Sw_Seq_command_seq Sync_Input_t Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after 0 Expert Expert
Sync_t
Expert
select_execute_t
Expert
A.16.
USIO65/DO_R_SI
DO_R_SI - Single-pt inform. output (relay)
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Behavior at failure This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N)
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) [0] keep [1] terminate String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
-terminate ---
use_CAEx_plus SID-BSE
[0] No [1] Yes [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU
No Automatic
Normal Expert
A-50
DC6-011-2.01
[10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] periodical [1] spontaneous Automatic/ R-SID Expert
SID-ST
Expert
receive format
Source of datapoint
spontaneo us
Expert
A.17.
USIO65/DO_SC_1POL
DO_SC_1POL - Single Command Output 1-pole
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
DC6-011-2.01
A-51
IOA2
Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. Command output time in seconds (S). Attention: The time comes into effect only, if in the message is not defined any time. Parameter works only with ACP 1703 platform With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Within this time (in sec) the 1 out of n enabling must occur on the command. 0=no 1 out of n enabling necessary. Attention: Function only active if sync_t=0 Command prolongation time in seconds (S)
Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle command (45) String 100 Char Float [###.##] 0.01 to 327.67 String 100 Char see Label
255
Normal
IOA3
255
Normal
TI Longtext Output_t
--0.01
RS_Image label
---
Normal Normal
1_out_of_n_t
Float [##.#] 0.1 to 25.5 0 Float [###.##] 0.01 to 327.67 0 to [0] not accepted [1] accepted [0] Peripherals [1] open-/closed loop control function [2] both (logical or) Float [###.##] 0.01 to 655.35 0 [0] CON+ /output (com_prolong_t)/TERM[1] CON+ /output (com_prolong_t)/TERM+ [2] CON+ /output/TERM[3] CON+ /output/TERM+ [4] CON+ /no output/TERM[5] CON- /no output Float [####.#] 0.1 to 6553.5 0 [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU
Expert
Command_prolong_t
Expert
QOC>8 RS_Mon_Source
If QOC>8 (Qualifier of Command) is accepted, so all QOC > 8 will be interpreted as QOC=0. Source of state information for state information monitoring
Expert Expert
RS_Mon_t
Return state information monitoring time in seconds (S). 0=no return state information monitoring Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is unequal 0
Expert
RS_outp_same_state
Expert
Retry_suppression_T
Command retry suppression time in seconds. Within this time a command with same address is discarded without error information (s)
Expert
SID-BSE
Automatic
Expert
A-52
DC6-011-2.01
[20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] no command [640] IOM0 - OUT D00 [641] IOM0 - OUT D01 [642] IOM0 - OUT D02 [643] IOM0 - OUT D03 [644] IOM0 - OUT D04 [645] IOM0 - OUT D05 [646] IOM0 - OUT D06 [647] IOM0 - OUT D07 [648] IOM0 - OUT D10 [649] IOM0 - OUT D11 [650] IOM0 - OUT D12 [651] IOM0 - OUT D13 [652] IOM0 - OUT D14 [653] IOM0 - OUT D15 [654] IOM0 - OUT D16 [655] IOM0 - OUT D17 [656] IOM1 - OUT D00 [657] IOM1 - OUT D01 [658] IOM1 - OUT D02 [659] IOM1 - OUT D03 [660] IOM1 - OUT D04 [661] IOM1 - OUT D05 [662] IOM1 - OUT D06 [663] IOM1 - OUT D07 [664] IOM1 - OUT D10 [665] IOM1 - OUT D11 [666] IOM1 - OUT D12 [667] IOM1 - OUT D13 [668] IOM1 - OUT D14 Automatic/ R-SID Expert
SID-ST
Expert
Sw_Seq_addtl_com
no command
Expert
DC6-011-2.01
A-53
[669] IOM1 - OUT D15 [670] IOM1 - OUT D16 [671] IOM1 - OUT D17 [672] IOM2 - OUT D00 [673] IOM2 - OUT D01 [674] IOM2 - OUT D02 [675] IOM2 - OUT D03 [676] IOM2 - OUT D04 [677] IOM2 - OUT D05 [678] IOM2 - OUT D06 [679] IOM2 - OUT D07 [680] IOM2 - OUT D10 [681] IOM2 - OUT D11 [682] IOM2 - OUT D12 [683] IOM2 - OUT D13 [684] IOM2 - OUT D14 [685] IOM2 - OUT D15 [686] IOM2 - OUT D16 [687] IOM2 - OUT D17 [688] IOM3 - OUT D00 [689] IOM3 - OUT D01 [690] IOM3 - OUT D02 [691] IOM3 - OUT D03 [692] IOM3 - OUT D04 [693] IOM3 - OUT D05 [694] IOM3 - OUT D06 [695] IOM3 - OUT D07 [696] IOM3 - OUT D10 [697] IOM3 - OUT D11 [698] IOM3 - OUT D12 [699] IOM3 - OUT D13 [700] IOM3 - OUT D14 [701] IOM3 - OUT D15 [702] IOM3 - OUT D16 [703] IOM3 - OUT D17 [704] IOM4 - OUT D00 [705] IOM4 - OUT D01 [706] IOM4 - OUT D02 [707] IOM4 - OUT D03 [708] IOM4 - OUT D04 [709] IOM4 - OUT D05 [710] IOM4 - OUT D06 [711] IOM4 - OUT D07 [712] IOM4 - OUT D10 [713] IOM4 - OUT D11 [714] IOM4 - OUT D12 [715] IOM4 - OUT D13 [716] IOM4 - OUT D14 [717] IOM4 - OUT D15 [718] IOM4 - OUT D16 [719] IOM4 - OUT D17 [720] IOM5 - OUT D00 [721] IOM5 - OUT D01 [722] IOM5 - OUT D02 [723] IOM5 - OUT D03 [724] IOM5 - OUT D04 [725] IOM5 - OUT D05 [726] IOM5 - OUT D06 [727] IOM5 - OUT D07 [728] IOM5 - OUT D10 [729] IOM5 - OUT D11 [730] IOM5 - OUT D12 [731] IOM5 - OUT D13 [732] IOM5 - OUT D14 [733] IOM5 - OUT D15 [734] IOM5 - OUT D16 [735] IOM5 - OUT D17 [736] IOM6 - OUT D00
A-54
DC6-011-2.01
[737] IOM6 - OUT D01 [738] IOM6 - OUT D02 [739] IOM6 - OUT D03 [740] IOM6 - OUT D04 [741] IOM6 - OUT D05 [742] IOM6 - OUT D06 [743] IOM6 - OUT D07 [744] IOM6 - OUT D10 [745] IOM6 - OUT D11 [746] IOM6 - OUT D12 [747] IOM6 - OUT D13 [748] IOM6 - OUT D14 [749] IOM6 - OUT D15 [750] IOM6 - OUT D16 [751] IOM6 - OUT D17 [752] IOM7 - OUT D00 [753] IOM7 - OUT D01 [754] IOM7 - OUT D02 [755] IOM7 - OUT D03 [756] IOM7 - OUT D04 [757] IOM7 - OUT D05 [758] IOM7 - OUT D06 [759] IOM7 - OUT D07 [760] IOM7 - OUT D10 [761] IOM7 - OUT D11 [762] IOM7 - OUT D12 [763] IOM7 - OUT D13 [764] IOM7 - OUT D14 [765] IOM7 - OUT D15 [766] IOM7 - OUT D16 [767] IOM7 - OUT D17 Sw_Seq_command_seq Sync_Input_t Switching sequence: output additional command before or after the command Within this time (in sec) the enabling over the syncronisation input must occur on the command. 0=no syncronisation over syncronisation input. Attention: Function only active if sync_t=0 Within this time (in sec) the interlock enabling must occur on the command. 0=no syncronisation over interlocking Max. time between select and execute (in seconds). After this time a recent select command is necessary. 0 = no select command is expected (direct command transmission) [0] after [1] before Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.1 to 6553.5 0 Float [####.#] 0.0 to 25.5 after 0 Expert Expert
Sync_t
Expert
select_execute_t
Expert
A.18.
USIO65/DO_SI
DO_SI - Digital Output - Single Point Information
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
DC6-011-2.01
A-55
IOA2
Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 Behavior at failure This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N)
Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) [0] keep [1] terminate String 100 Char see Label
255
Normal
IOA3
255
Normal
-terminate ---
use_CAEx_plus SID-BSE
[0] No [1] Yes [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID
No Automatic
Normal Expert
SID-SSE
Automatic/ R-SID
Expert
SID-ST
Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID
Automatic/ point-topoint/BSE
Expert
A-56
DC6-011-2.01
will be learned
[252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself [0] periodical [1] spontaneous
itself
receive format
Source of datapoint
spontaneo us
Expert
A.19.
USIO65/SW_CONTROL_LOCATION
SW_CONTROL LOCATION - control location
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicMeasured value 15 bit + sign scaled (35) Single command (45) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
Longtext label
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Sending of ACTCON and ACTTERM
---
Normal Normal
ACTCON_yes_no SID-BSE
[0] NO [1] YES [0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU
YES Automatic
Expert Expert
DC6-011-2.01
A-57
[30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Automatic/ R-SID Expert
SID-ST
Expert
A.20.
USIO65/SW_CO_INTER
SW_CO_INTER - command interlocked
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30)
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI
--
Normal
A-58
DC6-011-2.01
Longtext label
This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
---
Normal Normal
A.21.
USIO65/SW_CO_SYNC_A
SW_CO_SYNC_A - command synchronization abortion
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
A.22.
USIO65/SW_CO_SYNC_R
SW_CO_SYNC_R - command synchronisation is running
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
DC6-011-2.01
A-59
IOA3
Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
255
Normal
TI Longtext label
----
A.23.
USIO65/SW_CV_SET
SW_CV_SET - counter set
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicCount 31 bit + sign with sequence no. (37) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
SID-BSE
[0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID
Automatic
Expert
A-60
DC6-011-2.01
[254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Automatic/ R-SID Expert
SID-ST
Expert
A.24.
USIO65/SW_DI
SW_DI - Software Data Point Digital Input
Description IOM - Name for the periodical use of this data point in CAEx II IOM1- Name (global marker) for the periodical use of this data point in CAEx II Project name for the periodical use of this data point in CAEx II Longtext for the periodical use of the data point in CAEx II This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N)
Values/Ranges String 14 Char String 16 Char String 8 Char String 40 Char String 100 Char see Label -------
Default
use_CAEx_plus
No
Normal
DC6-011-2.01
A-61
A.25.
USIO65/SW_DI_AR
SW_DI_AR -automatic reclosing
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
A.26.
USIO65/SW_DI_BT
SW_DI_BT - Breaker tripping
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
A-62
DC6-011-2.01
A.27.
USIO65/SW_DI_SOR
SW_DI_SOR - switching operation running
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
A.28.
USIO65/SW_DO
SW_DO - Software Data Point Digital Output
Description IOM - Name for the periodical use of this data point in CAEx II IOM1- Name (global marker) for the periodical use of this data point in CAEx II Project name for the periodical use of this data point in CAEx II Longtext for the periodical use of the data point in CAEx II This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin Periodical use of this data point for CAEx plus (Y/N)
Values/Ranges String 14 Char String 16 Char String 8 Char String 40 Char String 100 Char see Label -------
Default
use_CAEx_plus
No
Normal
DC6-011-2.01
A-63
A.29.
USIO65/SW_LOC_REM
SW_LOC_REM - local remote criterion
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
SID-BSE
[0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU [13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13
Automatic
Expert
SID-SSE
Automatic/ R-SID
Expert
A-64
DC6-011-2.01
[14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID SID-ST Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Automatic/ point-topoint/BSE itself Expert
A.30.
USIO65/SW_REV
SW_REV - Revision
Parameter CASDU1
Description Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Address of the datapoint. The complete address consists of CASDU1, CASDU2, IOA1, IOA2 and IOA3. CASDU1 and CASDU2 = 255 means no spontaneous transmission Type identification according to IEC 60870-5-101/104 This longtext is displayed in the assembly-technical documentation and used when creating the ELCAD file. With this parameter is it possible to make a statustext in the assembly-technical documentation for data points assinged on more than on HW-pin
Values/Ranges Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 Integer [###] 0 to 255 dynamicSingle-point information (30) String 100 Char see Label
Default 255
Mode Normal
CASDU2
255
Normal
IOA1
255
Normal
IOA2
255
Normal
IOA3
255
Normal
TI Longtext label
----
SID-BSE
[0] C0-CPU [1] C1-CPU [2] C2-CPU [3] C3-CPU [4] C4-CPU [5] C5-CPU [6] C6-CPU [7] C7-CPU [8] C8-CPU [9] C9-CPU [10] C10-CPU [11] C11-CPU [12] C12-CPU
Automatic
Expert
DC6-011-2.01
A-65
[13] C13-CPU [14] C14-CPU [15] C15-CPU [16] C16-CPU [20] M-CPU [30] R-SID [254] own BSE [255] Automatic SID-SSE [0] PE00 [1] PE01 [2] PE02 [3] PE03 [4] PE04 [5] PE05 [6] PE06 [7] PE07 [8] PE08 [9] PE09 [10] PE10 [11] PE11 [12] PE12 [13] PE13 [14] PE14 [15] PE15 [128] PRE0 [129] PRE1 [130] PRE2 [131] PRE3 [254] BSE itself [255] Automatic/R-SID Source identification station number if multipoint traffic mode 0-99 if R-SID 0-254 If automatic then the source ID will be learned [0] 0 [1] 1 [2] 2 [252] 252 [253] 253 [254] 254/SSE itself [255] Automatic/point-topoint/BSE itself Automatic/ R-SID Expert
SID-ST
Expert
A.31.
label
Selectable elements
Element Values/Ranges + I+ IIN IN AUX V OUT OUT AUX V U+ U-
A-66
DC6-011-2.01
deeper/higher higher/deeper local/normal operation local/remote normal/local operation off/on on/off open/shut remote/local shut/open
deeper higher higher deeper local operation normal operation local remote normal operation local operation off on on off on shut remote local shut on
DC6-011-2.01
A-67
A-68
DC6-011-2.01
Diagnostics Information
B.
Diagnostics Information
USIO65 Revision 07
USIO65 Diagnosis
B.1.
Class Internal
B.1.1.
B.1.2.
B.1.3.
B.1.4.
DC6-011-2.01
B-1
Diagnostics Information
07
I/O module 7
B.1.5.
B.1.6.
B-2
DC6-011-2.01
Diagnostics Information
B.1.7.
B.1.8.
B.1.9.
DC6-011-2.01
B-3
Diagnostics Information
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
IOM0 - OUT V1 IOM0 - OUT V2 IOM0 - OUT V3 IOM1 - OUT V0 IOM1 - OUT V1 IOM1 - OUT V2 IOM1 - OUT V3 IOM2 - OUT V0 IOM2 - OUT V1 IOM2 - OUT V2 IOM2 - OUT V3 IOM3 - OUT V0 IOM3 - OUT V1 IOM3 - OUT V2 IOM3 - OUT V3
B.1.10.
B.1.11.
B-4
DC6-011-2.01
Diagnostics Information
04 05 06 07
B.1.12.
Class Internal - Record 14 : Pulse command, firmware error of the control circuit check
Bit 03 Control circuit busy Description
B.1.13.
B.1.14.
DC6-011-2.01
B-5
Diagnostics Information
10 11 12 13 14 15
B.1.15.
B.1.16.
B-6
DC6-011-2.01
Diagnostics Information
13 14 15
B.2.
Class External
B.2.1.
B.2.2.
DC6-011-2.01
B-7
Diagnostics Information
13 14 15
B.2.3.
B.2.4.
B-8
DC6-011-2.01
Diagnostics Information
B.2.5.
B.2.6.
B.2.7.
DC6-011-2.01
B-9
Diagnostics Information
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
OUT D01 OUT D02 OUT D03 OUT D04 OUT D05 OUT D06 OUT D07 OUT D08 OUT D09 OUT D10 OUT D11 OUT D12 OUT D13 OUT D14 OUT D15
B.2.8.
B.2.9.
B-10
DC6-011-2.01
Diagnostics Information
04 05 06 07 08 09 10 11 12 13 14 15
OUT D04 OUT D05 OUT D06 OUT D07 OUT D08 OUT D09 OUT D10 OUT D11 OUT D12 OUT D13 OUT D14 OUT D15
B.2.10.
B.2.11.
DC6-011-2.01
B-11
Diagnostics Information
07 08 09 10 11 12 13 14 15
B.3.
Class Test
B.3.1.
B.4.
Class Warning
B.4.1.
B-12
DC6-011-2.01
Diagnostics Information
B.4.2.
B.4.3.
B.4.4.
B.4.5.
DC6-011-2.01
B-13
Diagnostics Information
11 12 13 14 15
IOM6 - OUT V3 IOM7 - OUT V0 IOM7 - OUT V1 IOM7 - OUT V2 IOM7 - OUT V3
B-14
DC6-011-2.01
Readers Reactions
C.
Readers Reactions
We designed and compiled this manual with great care and a high degree of responsibility. It was - and still is - our goal to design it in a way that it will be of greatest possible use at your work. In order to reach this goal, we also rely on your cooperation - especially where maintenance and care of the manual are concerned. To make this cooperation easier for you, we added a form to this section. Please make use of it. We will try to consider your comments already in the next update of the manual. Thank you very much for your cooperation!
DC6-011-2.01
C-1
Readers Reactions
C-2
DC6-011-2.01
Readers Reactions
What is your impression of this manual? Do you think it is complete, correct and accurate, wellstructured, written in a comprehensible language, etc.? ...................................................................................................................................................................... ...................................................................................................................................................................... Which parts, characteristics, aspects are particularly useful? ...................................................................................................................................................................... ...................................................................................................................................................................... Does this manual meet the requirements that may reasonably be demanded? Does it come up to your expectations? ...................................................................................................................................................................... ...................................................................................................................................................................... Did you find any mistakes in this manual? If so, please use form on the backside.
Please send a copy of this sheet (front and back) to the below address.
DC6-011-2.01
C-3
Readers Reactions
Correction Sheet
Sender: .............................................................................................. .............................................................................................. .............................................................................................. Date: Name of the document: Version of the document: .............................................................................................. .............................................................................................. ..............................................................................................