DESCRIPTION
These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage and/or shipping. The compact design, clean styling, low silhouette, and quiet operation make these condensing units suitable for almost any outdoor location. On rooftopsbecause they weigh much less than a single package unit of similar capacity and are much easier to rig and support. At ground level because their ample sub-cooling capacity allows them to be located 60 feet below the evaporator coil. All sheet metal parts are constructed of commercial grade (G90) galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are coated with a powder paint to assure a quality finish for many years. This coating system has surpassed the 500 hour, 5% salt spray test per ASTM Standard B117. All models include a 1-year limited warranty on the complete unit. The compressor carries an additional 4-year warranty. A complete line of Evaporator Blower units is also offered to meet your precise capacity and air handling requirements. Refer to Form 036-21300-001 for more information on this air side equipment.

TECHNICAL GUIDE
SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000

MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER

FEATURES
Condenser coil constructed of copper tubes and aluminum fins for durability and long lasting efficient operation. Permanently attached base rails with fork-lift slots and lifting holes. This design allows for 3-way fork-lift access and overhead rigging. Both high and low pressure controls. Since these controls are self-contained, there are no capillary lines to be damaged. Compressor line-break motor protection and crankcase heat- ers. (No crankcase heater on H*CE150 compressors.) Anti-short cycle timer to protect the compressor. A lockout circuit to prevent the unit from cycling on safety control. A 24-volt temperature control circuit. Low ambient operation to 45F accessories for 0F low ambient operation are available. A filter-drier (shipped in the unit's compressor compart- ment for field installation near the evaporator coil). Service valves with a back-seating access port for pressure testing the system. Copper stub-outs are factory mounted on the suction and liquid service valves to simplify the field piping connections. Separate panel for easy access to the control box without affecting air flow across the condenser coil. Gauge lines extend out from cabinet to facilitate servicing. Packaging suitable for outdoor storage Optional coil guard accessory protect coils with a decora- tive grille.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21083-007-A-0404

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 GUIDE SPECIFICATION . . . . . . . . . . . . . . . . . . . . . 11 LIST OF FIGURES
Fig# 1 2 7 3 4 Pg# TYPICAL FIELD WIRING WITH AIR HANDLER . . . . . 7 4 POINT LOADS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 UNIT DIMENSIONS & CLEARANCES - HCE090, 120 & 150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

LIST OF TABLES
Tbl# 1 2 3 4 5 6 7 Pg# ARI RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 UNIT COOLING CAPACITIES AND POWER REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 NOMINAL EVAPORATOR DATA FOR G2FD090S35 W/HCE090 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

PRODUCT NOMENCLATURE H PRODUCT CATEGORY H = Split-System Condensing Unit PRODUCT GENERATION 1 2 3 4 = 1st Generation = 2nd Generation = 3rd Generation = 4th Generation NOMINAL COOLING CAPACITY PRODUCT IDENTIFIER CE = Condensing Section 090 = 7-1/2 Tons 120 = 10 Tons 150 = 12-1/2 Tons VOLTAGE CODE 25 = 208/230-3-60 46 = 460-3-60 58 = 575-3-60 4 C E 0 9 0 A 2 5

FACTORY INSTALLED HEAT A = Not Applicable

Unitary Products Group

036-21083-007-A-0404

TABLE 1: ARI RATINGS*


CONDENSING UNIT MODEL INDOOR BLOWER UNIT MODEL SYSTEM MBH SYSTEM EER CONDENSING UNIT SOUND LEVEL(bels)

H5CE090A25, 46

K4EU090A33 K3EU120A33 K3EU120A33 K3EU180A33 K3EU180A33

85 91

9.2 9.4 9.0 9.5 9.0

8.4 9.0 -

H2CE120A25, 46 H1CE150A25, 46

117** 124
**

140**

*. Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard 340/ 360 . Rated in accordance with ARI Standard 270. . Deduct 0.5 MBH for units operating at 208 volts. **. Deduct 1.0 MBH for units operating at 208 volts.

TABLE 2: APPLICATION DATA


LIMITATION MIN. MAX.

208/230-3-60 Voltage Variation * 460-3-60 575-3-60 380/415-3-50 Ambient Air on Condenser Coil

187V 432V 540V 342V 45F

252V 504V 630V 456V 115F

*. Rated in accordance with ARI Standard 110, utilization range A. . Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0F. . These units can operate at a maximum ambient temperature of 120F providing the wet bulb temperature of the air entering the evaporator coil does not exceed 67F. Note: Refer to Form 035-15407-002 for refrigerant piping limitations.

TABLE 3: PHYSICAL DATA


Compressor (Tandem on 150 only) Rating (Tons) 7-1/2 10 12-1/2 Condenser Fan (Propeller) Fan Motor* HP 3/4 1/2 1/2 Rotation CW CCW CCW Coils Unit Weight (Lbs.) Charge, Lbs,Oz. (Refrigerant-22) Oper.** 12-0 18-6 19-5

Model HCE

090 120 150

Blades Cap. Dia. NormQty. Qty. RPM (Stages) (in.) CFM Qty Pitch (Deg.) 1 1 24 4677 3 29 1 1120 1 1 2 2 24 24 8034 7950 3 3 27 27 2 2 1110 1110

Face Finned Rows Ship. Oper. Holding Area Length High (in.) 18.7 23.8 23.8 90 96 96 30 36 36 365 435 510 360 430 505 1-12 2-4 2-4

*. These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48 frame. . These condenser coils have 2 rows of 3/8 OD copper tubes and 16 aluminum fins per inch. . When viewing the shaft end of the motor. **. Includes matched indoor blower unit but no piping. . Add an additional 1 lb. charge when used with KEU120 (10 ton) indoor units.

Unitary Products Group

036-21083-007-A-0404

TABLE 4: ELECTRICAL DATA


COMPRESSOR MODEL (HCE) VOLTAGE CODE POWER SUPPLY RLA LRA CONDENSER FAN MOTOR POWER SUPPLY HP QTY FLA UNIT AMPACITY (AMPS) MAX. FUSE SIZE* (AMPS)

25 090 46 58 25 46 58 25 150 46 58

208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60

25.6 12.8 10.2 42.0 19.2 13.8 41.4 20.0 16.4

190 95 75 239 125 80 312 150 108

208/230-1-60 460-1-60 575-1-60 208/230-1-60 460-1-60 460-1-60 208/230-1-60 460-1-60 460-1-60

3/4 3/4 3/4 1/2 1/2 1/2 1/2 1/2 1/2

1 1 1 2 2 2 2 2 2

3.03 1.60 1.8 2.7 1.6 1.3 3.0 1.8 1.8

35.1 17.6 14.6 51.8 24.7 18.0 52.6 26.1 21.3

60 30 20 70 35 25 70 35 30

120

*. Dual element. . Unit includes a 575 to 460-volt transformer.

TABLE 5: UNIT COOLING CAPACITIES AND POWER REQUIREMENTS


Suction Press. & Corresponding Temp. @ Saturation PSIG F MBH Temperature of Air on Condenser Coil, F 65 KW* MBH 75 KW
*

Model HCE

85 MBH KW* MBH

95 KW* MBH

105 KW* MBH

115 KW*

090

61.6 68.5 76.0 84.0 61.6 68.5 76.0 84.0 61.6 68.5 76.0 84.0

35 40 45 50 35 40 45 50 35 40 45 50

90 101 110 120 123 134 145 156 140 151 165 178

6.1 6.3 6.5 6.6 7.7 8.0 8.2 8.4 9.4 9.6 9.9 10.2

88 96 109 115 117 128 139 150 133 144 156 169

6.7 6.8 7.0 7.2 8.4 8.6 8.8 9.1 10.4 10.6 10.9 11.2

81 91 101 109 112 122 132 143 127 137 148 159

7.2 7.4 7.6 7.8 9.1 9.3 9.5 9.8 11.3 11.5 11.8 12.1

77 87 95 104 106 116 126 136 119 129 140 151

7.9 8.1 8.4 8.6 9.9 10.1 10.4 10.6 12.6 12.8 13.1 13.4

74 82 90 99 100 110 120 129 112 122 132 142

8.6 8.9 9.1 9.4 10.8 11.0 11.3 11.5 13.8 14.1 14.4 14.8

68 77 85 93 95 104 113 123 105 114 124 134

9.5 9.7 10.0 10.3 11.8 12.1 12.3 12.5 15.1 15.4 15.8 16.1

120

150

*.

Includes compressor and condenser fan motor(s).

Unitary Products Group

036-21083-007-A-0404

TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS


Air On Cooling Coil CFM WB F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 95F Sensible Capacity, MBH Entering Dry Bulb, F 86 80 74 68 75 92 82 91 66 82 80 89 57 71 75 84 84 97 91 91 75 94 89 89 63 80 85 86 95 112 113 113 90 110 110 110 70 88 94 94 101 119 120 120 135 157 157 156 121 144 149 148 53 70 82 88 49 64 78 81 43 57 69 72 59 80 91 91 54 74 88 89 47 64 77 78 69 93 111 113 66 89 106 110 53 70 84 87 74 95 115 119 99 130 147 147 90 117 139 139 32 49 61 67 31 47 61 63 30 43 56 58 34 55 65 66 34 53 68 69 31 48 61 62 43 67 84 87 43 66 83 87 35 53 67 70 46 67 87 91 63 94 125 137 60 87 113 131 27 39 45 29 43 46 30 42 44 30 40 41 33 48 48 32 45 46 40 58 60 20 42 59 64 18 36 50 53 19 40 60 64 57 89 119 56 83 108 Temperature of Air on Condenser 105F Sensible Capacity, MBH Total Power Cap. Input, Entering Dry Bulb, F MBH KW 86 80 74 68 H5CE090/K4EU090 96 9.5 73 52 31 89 9.3 88 68 47 26 81 9.0 81 60 38 81 89 9.0 41 84 63 89 93 9.5 65 48 30 86 9.2 80 63 45 28 78 9.0 78 76 59 41 86 9.0 86 77 60 42 88 9.3 56 42 28 82 9.1 69 55 42 28 74 8.9 74 67 53 40 82 8.8 68 54 41 81 H5CE090/K3EU120 9.5 82 57 9.2 77 92 9.1 84 84 9.1 86 86 9.4 73 53 9.1 91 72 9.0 85 84 9.0 85 85 9.3 62 46 9.1 78 62 8.9 74 79 8.9 74 81 H3CE120/K3EU120 133 12.4 94 68 120 12.3 109 91 109 12.0 108 109 109 12.0 109 109 130 12.5 89 66 117 12.3 106 87 106 12.0 104 106 106 12.0 106 106 112 12.3 69 52 101 12.2 87 70 92 11.9 83 92 92 11.9 85 92 H3CE120/K3EU180 135 12.8 100 72 124 12.5 115 94 115 12.3 113 115 115 12.3 115 115 HCE150/K3EU180 156 15.1 132 96 151 15.0 127 151 151 15.0 141 151 150 15.0 141 150 153 15.0 118 88 144 14.8 141 114 143 14.8 134 143 143 14.8 134 143 97 92 84 86 96 91 84 85 91 86 79 81 32 52 59 61 32 51 64 65 30 47 58 58 42 64 82 83 42 64 81 83 35 52 66 68 45 67 85 88 60 91 122 132 57 84 110 125 27 34 36 31 44 44 31 42 52 38 55 57 19 41 57 60 18 35 49 50 17 39 58 61 115F Sensible Capacity, MBH Entering Dry Bulb, F 86 80 74 68 72 85 80 87 64 79 76 83 54 67 73 78 80 86 78 81 71 87 79 81 60 77 74 76 93 105 106 106 88 102 103 103 69 86 90 90 98 110 112 112 129 145 144 144 115 138 137 137 50 67 80 80 47 62 74 74 41 54 65 64 55 75 78 81 51 70 81 81 44 61 70 71 67 88 106 106 65 86 102 102 52 69 82 82 71 93 112 112 94 124 135 135 85 111 129 129 29 45 58 58 29 44 57 56 27 40 51 51 30 50 53 56 31 49 60 61 28 45 54 55 41 62 79 80 42 62 78 79 35 52 64 65 43 66 83 85 58 89 119 126 55 81 107 120 24 37 37 27 39 39 26 38 37 25 28 31 29 40 41 29 38 39 36 53 53 18 39 55 56 18 34 47 48 16 38 56 57 52 84 113 51 77 102

Total Cap., MBH 100 93 82 91 97 91 80 89 91 86 75 84 104 97 91 91 102 95 89 89 97 91 85 86 137 126 113 113 134 123 110 110 114 104 94 94 140 129 120 120 163 157 157 156 160 150 149 148

Power Input, KW 8.5 8.3 8.0 8.1 8.5 8.2 8.0 8.0 8.4 8.1 7.9 7.9 8.5 8.3 8.2 8.2 8.4 8.2 8.1 8.1 8.4 8.2 8.0 8.1 11.1 11.1 10.7 10.7 11.3 11.3 10.9 10.9 11.1 11.0 10.7 10.7 11.7 11.4 11.2 11.2 13.7 13.5 13.5 13.5 13.6 13.3 13.3 13.3

Total Cap., MBH 93 85 80 87 88 81 76 83 85 78 73 80 90 86 78 81 91 87 79 81 85 81 74 76 129 114 106 106 125 111 103 103 110 98 90 90 129 119 112 112 149 145 144 144 145 138 137 137

Power Input, KW 10.4 10.2 10.0 9.9 10.5 10.2 10.1 9.9 10.3 10.0 9.9 9.7 10.4 10.2 10.0 10.0 10.3 10.1 9.9 9.9 10.2 10.0 9.9 9.8 13.6 13.4 13.2 13.2 13.6 13.4 13.2 13.2 13.6 13.4 13.2 13.2 13.9 13.6 13.4 13.4 16.8 16.7 16.7 16.7 16.7 16.5 16.5 16.5

3600

3000

2400

4200

3500

2800

4400

4000

3000

4700

6250

5000

55 87 116 53 80 105

All Sensible Capacity Blower Motor KW x 3.415 MBH KW

Nominal Rating = Blower Motor (MBH)

Note: These capacities are gross ratings. For net capacities, determine the KW requirement of the supply air blower motor per the published BLOWER PERFORMANCE data. Convert KW to MBH per the following equation and deduct this equivalent heat from the gross cooling ratings.

The KW input ratings listed above include the compressor and condenser fan motor(s).

Unitary Products Group

036-21083-007-A-0404

Sequence of Operation
UNIT OPERATION - 7-1/2, 10 & 12-1/2 TON When the external control calls for cooling at terminal Y1: The system controller (SC) is energized. The system control- ler starts the compressors and enables the condenser fans by energizing contactor 1M (2M on the 10 and 12-1/2 ton, 208/230 volt models). The single condenser fan is energized with the compressor on the 7-1/2 ton models. Condenser fan motor #1 is energized with the compressors on the 10 and 12-1/2 ton models while fan #2 is enabled with compressor operation. Fan motor #2 operation is controlled through the Ambient Temperature Switch (ATS) which will de-energize the motor when the ambient temperature falls below 70F Safety Lockout: The system controller (SC) has a lockout cir- cuit to prevent compressor short-cycling on a safety control

with automatic reset. If the high or low refrigerant pressure switches (HP or LP) open, the SC will enter lockout mode. SC provides a 90 second bypass of the low pressure switch LP to prevent nuisance lockouts during unit start-up. A malfunction light (24V, 2 A max. resistive load) can be energized through SC, by connecting the light between termi- nals X and B on TB1. NOTE: To reset the unit after a lockout: a. Turn the system switch on the thermostat to the OFF position and back to the COOL position. OR b. Increase the set point of the room thermostat above the temperature in the conditioned space and return it to its original setting. If the unit continues to be shut down by one of its safety controls, a service man should be called to determine the cause of the problem. Repeated reset- ting of the lockout circuit may damage the unit.

Unitary Products Group

036-21083-007-A-0404

NOTE: USE COPPER CONDUCTORS ONLY


SIZE POWER WIRING DICONNECT SWITCH, AND FUSING PER ELECTRICAL DATA TABLE

NOTE: Use thermostat 2HT04701424 if the blower unit is equipped with a 2-stage electric heat accessory. Use thermostat 2TH07701024 if the blower unit is equipped with a hot water coil, a steam coil or a 1-stage electric heat accessory. The field wiring connected to these dummy terminals on TB1 can be
routed directly from the condensing

Y1

FACTORY - MOUNTED PIGTAILS ON TERMINAL COMPRESSOR CONTACTOR 1M

unit to the thermostat if desired.

TERMINALS ON BLOCK TB1 OF BLOWER UNIT

24 VOLT

53

60

66

G
WIRE IN ACCORDANCE WITH ALL LOCAL AND NATIONAL ELECTRICAL CODES

THERMOS TAT 2TH08701024

FIGURE 1 - TYPICAL FIELD WIRING WITH AIR HANDLER

HCE090

HCE120 & 150

UNIT 090 120 150

4-POINT LOAD (lbs) Total 360 430 510 A 60 90 111 B 70 114 152 C 124 127 143 D 106 99 104

FIGURE 2 - 4 POINT LOADS

Unitary Products Group

036-21083-007-A-0404

FIELD-INSTALLED ACCESSORIES - 0 FLOW AMBIENT KITS - An auto-transformer and temperature control maintain stable system operation by reducing the speed of the condenser fan motor.

FIGURE 3 - TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE

Unitary Products Group

036-21083-007-A-0404

CLEARANCES
CONTROL BOX ACCESS

HCE090 (7-1/2 Ton)


31-3/4 42-3/4

Overhead (Top)* Front (Piping and Access Panels) Left Side Right Side Rear Bottom

120 30 24 24 24 0
32-1/2 5

AIR OUT

AIR IN

7/8" DIA. CONTROL WIRING ENTRY

*. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge. . Adequate snow clearance must be provided if winter operation.

4-1/8 5

2 GUAGE LINE ACCESS

1-3/8" DIA. POWER WIRING ENTRY 7/8" KNO CKOUT ACCESSORY WIRING ENTRY 1-1/8" OD SUCTION LINE 4-1/2 10-1/8 2-1/2

25-3/4

CENTER OF GRAVITY

COMPRESSOR AND CONDENSER FAN MOTOR ACCESS

1/2" OD LIQUID LINE

UNIT 7-1/2 TON 10 TON 12-1/2 TON

DIM (IN.) A 42-3/4 70-1/8 70-1/8 B 31-3/4 32 32 C 19-3/4 30-3/4 29-5/8 D 11-1/2 15-1/8 16 -1/2

HCE120 (10 Ton) HCE150 (12-1/2 Ton)

AIR OUT

AIR OUT

CONTROL BOX ACCESS

SERVICE PORT LOCATION AIR IN

39

1-1/8 OD (10 TON) 1-3/8 OD (12-1/2 TON) SUCTION LINE 5/8 OD LIQUID LINE

15-3/4 2-3/4 7-3/4

8-3/4

5-3/8 7/8 DIA CONTROL WIRING ENTRY

6-3/4

32 2-1/4
7/8" KNOCKOUT ACCESSORY WIRING ENTRY CONDENSER FAN MOTOR ACCESS

5-7/8 32-1/2 70-1/2 1-3/8 DIA. POWER WIRING ENTRY

COMPRESSOR AND CONDENSER FAN MOTOR ACCESS

FIGURE 4 - UNIT DIMENSIONS & CLEARANCES - HCE090, 120 & 150

Unitary Products Group

036-21083-007-A-0404

TABLE 7: NOMINAL EVAPORATOR DATA FOR G2FD090S35 W/HCE090

10

Unitary Products Group

036-21083-007-A-0404

GUIDE SPECIFICATION
Furnish and install YORK Sunline air-cooled condensing units or equivalent, suitable for ground or roof mounting. Units shall have capacities and efficiencies as outlined in the schedules shown on the plans and shall be installed in accor- dance with all applicable national and local codes. c. Fan motors shall be totally enclosed with permanently lubricated ball-bearings for longer wear during start and stop cycles. Fan motors shall have inherent overload protection. Coil shall be constructed of rifled copper tubing mechanically expanded and bonded to louvered aluminum fins. Coil shall include an integral subcooler.

d. e.

I. General
a. b. c. d. e. Units shall be manufactured in a facility registered under the ISO 9002 manufacturing quality standard. Units shall be CSA approved. Unit shall be packaged to allow outdoor storage. Hermetic compressors shall be covered by a five year limited warranty. All other unit parts shall be covered by a full year limited warranty.

V. Refrigeration Components
a. b. c. d. e. Refrigeration system contains both high and low pressure cut-outs. Service valves to ease installation and recovery of refrigerant. External ports to accommodate gauge lines, allowing for easy servicing of the unit. Each unit ships with a filter drier for field installation. Holding charge of R-22.

II. Unit Cabinet


a. Cabinet shall be constructed of 18 gauge, zinc-coated steel, finished with a powder paint process capable of withstanding a minimum of 500 salt spray hours accord- ing to ASTM B117. Cabinet screws shall comply with the ASTM B117 salt spray test for a minimum of 750 hours. Panels shall be removable for easy access to all internal components during maintenance and service. Cabinet shall feature a separate access panel for the controls so that unit airflow need not be disturbed during servicing. Permanently attached base rails shall have 3-way fork access and installation. lifting holes for ease of

VI. Controls
a. b. c. d. e. Each unit is equipped with 24 volt control circuit with terminal blocks. Color-coded wiring for easy service and trouble shooting. Independent line break thermal protection for the condenser fans. 5 minute anti-short cycle timer to protect the compressor from frequent cycling. Unit safety lockouts which automatically reset from the thermostat once the anti-short cycle timer is satisfied. Safety lockouts will also generate a 24 volt signal to the "X" terminal, allowing notification to the user via the thermostat fault light (if present). These safety lockouts shall include:

b. c. d.

e. lift

III. Compressor
a. b. Compressor shall be scroll compressors with integral motor overload protection. Compressors for HCE090, 120 have crankcase heaters to keep refrigerant from diluting the compressor oil in the sump. Crankcase heater shall be field replaceable with- out removal of the charge. Compressor shall be mounted on isolators to limit the transmission of sound and vibration.

c.

IV. Condenser and Fans


a. Fan motors shall be single phase, direct-drive with propeller-type condenser fans which discharge air vertically upward. Units with more than one condenser fan motor shall be wired to distribute the single phase motor loads across the 3 phase power supply, thus minimizing phase imbal- ance on multiple unit installations.

High refrigerant pressure. Low refrigerant pressure (low refrigerant pressure shall be bypassed for the first 90 seconds of operation to eliminate nuisance trips). Compressor motor protection to automatically shutdown the unit in the event of motor overcurrent or excessive tem- perature conditions. Unit shall automatically restart after the line break protector cools. Low ambient operation down to 45F (7C) without a low ambient kit. (Operation down to 0F with the optional low ambient kit.)

VII. Electrical
a. b. c. Units shall be volts, 3 phase, with a single power point connection. Unit control circuit shall have a 24 volt transformer, sized sufficiently to operate the indoor fan. All condenser fan motors and the secondary of each transformer shall be grounded.

b.

Unitary Products Group

11

VIII. Accessories and Options


a. Head Pressure Control - Shall include an auto transformer to slow the speed of the condenser fan at low ambient temperatures, allowing operation of the con- densing unit down to 0F. Coil Guard - Field installed decorative grille shall be placed on the units to provide further coil protection. Phenolic Coating on Condenser Coil - Condenser coils shall be dipped in a four-coat phenolic coating process to provide longer life in corrosive conditions.

b. c.

Subject to change without notice. Printed in U.S.A. Copyright 2004 by Unitary Products Group. All rights reserved. Unitary Products Group 5005 York Drive

036-21083-007-A-0404 Supersedes: 036-21083-006-B-0903 Norman OK 73069