Vous êtes sur la page 1sur 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

FOREWORD

This document supersedes and replaces all of Energy Networks previous 11kV and 33kV bare
wire overhead line specifications including:OHL-03-006 Issue 1 L10 (Aug 1994)
OHL-03-007 Issue 1 L15 (Apr 1996)
OHL-03-008 Issue 1 L20 (Feb 1996)
OHL-03-018 Issue 1 L25 (May 1996)
OHL-03-019 Issue 1 L27 (Mar 1996)
OHL-03-025 Issue 1 Genu 3 (D) (Jun 1973)
OHL-03-083 Issue 1 L33 (Aug 2002)
OHL-03-090 Issue 2 L35 (Aug 2005)
OHL-03-093 Issue 1 L36 (Aug 2005)
72/0850/16 Issue 1 Manweb 33kVOverhead Line Design (Oct 1994)
2

SCOPE

Specification for 11kV and 33kV overhead power lines of unearthed construction employing
AAAC Conductors, supported on single and H type wood pole supports.
3

ISSUE RECORD

This is a controlled document.


All copies printed via the Intranet or photocopied will be deemed uncontrolled.
Issue Date
May 2007
4

Issue No
1

Author
L Campbell

Amendment Details
Initial Issue

ISSUE AUTHORITY

Author

Owner

Issue Authority

L Campbell
Senior Project Engineer

A Graham
Policy and Standards
Section Head

C Woodman
Engineering Services
Manager

REVIEW

This Specification will be subject to review following implementation and in any case no later
than three years after publication.
___________________________________________________________________________
SP Power Systems Ltd

Page 1 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

CONTENTS

FOREWORD ............................................................................................................................1

SCOPE .......................................................................................................................................1

ISSUE RECORD.......................................................................................................................1

ISSUE AUTHORITY ...............................................................................................................1

REVIEW....................................................................................................................................1

CONTENTS ..............................................................................................................................2

DEFINITIONS ........................................................................................................................17

REFERENCES........................................................................................................................19

INTRODUCTION ..................................................................................................................22

10

DESIGN DATA..............................................................................................................23

10.1

Design Basis ............................................................................................................23

10.2

Conductors ..............................................................................................................23

10.3

Crossarms ................................................................................................................23

10.4

Supports...................................................................................................................24

10.5

Stays.........................................................................................................................24

11

MATERIALS .................................................................................................................24

12

TECHNICAL REQUIREMENTS FOR THE ERECTION OF LINES...................25

12.1

Structure Type and Capabilities .............................................................................25

12.2

Wood Poles ..............................................................................................................25


12.2.1 Section, Section Angle and Terminal Supports ...................................................25
12.2.2 Supports ...............................................................................................................26

12.3

Pole Strut Loadings.................................................................................................27

12.4

Windspan and Foundation Requirements .............................................................27

___________________________________________________________________________
SP Power Systems Ltd

Page 2 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

12.5

Failure Containment Requirements.......................................................................29

12.6

Steelwork and Bolts.................................................................................................30

12.7

Stays.........................................................................................................................31

12.8

Line Conductors......................................................................................................32
12.8.1 Line jumpers ........................................................................................................32
12.8.2 Down Dropper Jumpers .......................................................................................32

12.9

Insulators and Conductor Fittings .........................................................................33

12.10

Span Lengths...........................................................................................................34

12.11

Section Lengths .......................................................................................................34

12.12

Conductor Design/Erection Sags and Tensions ....................................................35

12.13
Conductor Spacing and Clearances .......................................................................36
12.13.1 Minimum Height of Line Conductors..................................................................36
12.13.2 Summary of Statutory Ground Clearances ..........................................................36
12.13.3 Clearances to Obstacles .......................................................................................37
12.13.4 Clearances to other Power Lines..........................................................................37
12.13.5 Railway and Canal Crossings ..............................................................................37
12.13.6 Telecommunications Crossings ...........................................................................37
12.13.7 Road / Motorway Crossings.................................................................................37
12.14

Safety Signs and Number Plates ............................................................................38

12.15

Anti-climbing Devices .............................................................................................38

12.16
Bonding and Earthing ............................................................................................39
12.16.1 Neutral Earths ......................................................................................................40
12.17

11kV Transformers .................................................................................................40

12.18

Switchgear ...............................................................................................................41

12.19

Air Break Switch Disconnectors.............................................................................41

12.20

HV Cable Terminations ..........................................................................................42

12.21

Surge Arresters........................................................................................................43

12.22

Insulated Shrouding ...............................................................................................43

Appendices......................................................................................................................................44

___________________________________________________________________________
SP Power Systems Ltd

Page 3 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 1 11KV Non Severe Weather Area 50mm2 AAAC Hazel Conductor (L10) .......45
Table 1- Support Types and Duties Table for 50mm2 HAZEL AAAC ................................46
Table 2- Conductor Design Table for 50mm HAZEL AAAC ..............................................47
Table 3- Conductor Pre-Tension Table for 50mm2 HAZEL AAAC.....................................48
Table 4- Conductor Erection Table for 50mm2 HAZEL AAAC...........................................48
Table 5-Maximum Angle of Deviation for Single Poles for 50mm2 HAZEL AAAC...........49
Table 6-Maximum Angle of Deviation for H Poles for 50mm2 HAZEL AAAC .............49
Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 50mm2 HAZEL AAAC
..........................................................................................................................................................50
Table 8-Strut Load in H Poles with Two or Three Stays (kgf) for 50mm2 HAZEL AAAC
..........................................................................................................................................................51
Table 9- Strut Load in Single Pole Double Terminal Structures with Four Stays (kgf) for
50mm2 HAZEL AAAC ..............................................................................................................52
Table 10-Strut Loading in Single Pole Construction Terminals (kgf) for 50mm2 HAZEL
AAAC ..............................................................................................................................................52
Table 11-Stayed Pole Strut Capabilities for 50mm2 HAZEL AAAC....................................53
Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 50mm2 HAZEL
AAAC ..............................................................................................................................................54

___________________________________________________________________________
SP Power Systems Ltd

Page 4 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 2 11kV Severe Weather Area.100mm2 AAAC Oak Conductor (L27) ................55
Table 1- Support Types and Duties Table for 100mm2 OAK AAAC (Severe Weather Area)
..........................................................................................................................................................56
Table 2- Conductor Design Table for 100mm OAK AAAC (Severe Weather Area).........57
Table 3- Conductor Pre-Tension Table for 100mm2 OAK AAAC (Severe Weather Area)58
Table 4- Conductor Erection Table for 100mm2 OAK AAAC (Severe Weather Area) .....58
Table 5-Maximum Angle of Deviation for Single Poles for 100mm2 OAK AAAC (Severe
Weather Area)................................................................................................................................59
Table 6-Maximum Angle of Deviation for H Poles for 100mm2 OAK AAAC (Severe
Weather Area)................................................................................................................................59
Table 7- Strut Load in Single Poles with One or Two Stays (kgf) for 100mm2 OAK AAAC
(Severe Weather Area) ..................................................................................................................60
Table 8- Strut Load in H Poles with Three Stays (kgf) for 100mm2 OAK AAAC (Severe
Weather Area)................................................................................................................................61
Table 8- Strut Load in H Poles with Three Stays (kgf) for 100mm2 OAK AAAC (Severe
Weather Area) (Cont)....................................................................................................................62
Table 9 Strut Loading in Single Pole Construction Terminals (kgf) FOR 100mm2 OAK
AAAC (Severe Weather Area)......................................................................................................62
Table 10-Stayed Pole Strut Capabilities for 100mm2 OAK AAAC (Severe Weather Area)
..........................................................................................................................................................63
Table 10Stayed Pole Strut Capabilities for 100mm2 OAK AAAC (Severe Weather Area)
(cont.)...............................................................................................................................................64
Table 11- Pole Sizing for Single Pole Intermediate and Section Poles for 100mm2 OAK
AAAC ..............................................................................................................................................65

___________________________________________________________________________
SP Power Systems Ltd

Page 5 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 3 33kV Non Severe Weather Area 150mm2 AAAC ASH Conductor (L27) .......66
Table 1- Support Types and Duties Table for 150mm2 ASHAAAC (Non Severe Weather
Area)................................................................................................................................................67
Table 2- Conductor Design Table for 150mm ASH AAAC (Non Severe Weather Area) .68
Table 3- Conductor Pre-Tension Table for 150mm2 ASHAAAC (Non Severe Weather
Area)................................................................................................................................................69
Table 4- Conductor Erection Table for 150mm2 ASHAAAC (Non Severe Weather Area)69
Table 5-Maximum Angle of Deviation for Single Poles for 150mm2 ASHAAAC (Non
Severe Weather Area)....................................................................................................................70
Table 6-Maximum Angle of Deviation for H Poles for 150mm2 ASH AAAC (Non Severe
Weather Area)................................................................................................................................70
Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 150mm2 ASHAAAC
(Non Severe Weather Area) ..........................................................................................................71
Table 8-Strut Load in H Poles with Three Stays (kgf) for 150mm2 ASHAAAC (Non
Severe Weather Area)....................................................................................................................72
Table-9 Strut Load in H Pole Structures with Four Stays (kgf) for 150mm2 ASHAAAC
(Non Severe Weather Area) ..........................................................................................................73
Table 10 Strut Loading in Single Pole Construction Terminals (kgf) for 150mm2
ASHAAAC (Non Severe Weather Area) .................................................................................74
Table 11-Stayed Pole Strut Capabilities for 150mm2 ASHAAAC (Non Severe Weather
Area)................................................................................................................................................75
Table 11 Stayed Pole Strut Capabilities for 150mm2 ASHAAAC (Non Severe Weather
Area) (cont.)....................................................................................................................................76
Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 150mm2
ASHAAAC (Non Severe Weather Area) .................................................................................77

___________________________________________________________________________
SP Power Systems Ltd

Page 6 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 4 33kV Non Severe Weather Area.200mm2 AAAC POPLAR Conductor (L33)78
Table 1- Support Types and Duties Table for 200mm2 POPLARAAAC (Non Severe
Weather Area)................................................................................................................................79
Table 2- Conductor Design Table for 200mm POPLARAAAC (Non Severe Weather
Area)................................................................................................................................................80
Table 3- Conductor Pre-Tension Table for 200mm2 POPLARAAAC (Non Severe Weather
Area)................................................................................................................................................81
Table 4- Conductor Erection Table for 200mm2 POPLARAAAC (Non Severe Weather
Area)................................................................................................................................................81
Table 5-Maximum Angle of Deviation for Single Poles for 200mm2 POPLARAAAC (Non
Severe Weather Area)....................................................................................................................82
Table 6-Maximum Angle of Deviation for H Poles for 200mm2 POPLARAAAC (Non
Severe Weather Area)....................................................................................................................82
Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 200mm2
POPLARAAAC (Non Severe Weather Area) .........................................................................83
Table 8-Strut Load in H Poles with Three Stays (kgf) for 200mm2 POPLARAAAC (Non
Severe Weather Area)....................................................................................................................84
Table-9 Strut load in H Poles with Four Stays (kgf) for 200mm2 POPLARAAAC (Non
Severe Weather Area)....................................................................................................................85
Table 10 Strut Loading in Single Pole Construction Terminals (kgf) for 200mm2
POPLARAAAC (Non Severe Weather Area) .........................................................................85
Table 11-Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Non Severe
Weather Area)................................................................................................................................86
Table 11 Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Non Severe
Weather Area) (cont.)....................................................................................................................87
Table 12-Pole Sizing for Intermediate and Section Poles for 200mm2 POPLARAAAC (Non
Severe Weather Area)....................................................................................................................88

___________________________________________________________________________
SP Power Systems Ltd

Page 7 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 5 33kV Severe Weather Area 200mm2 AAAC POPLAR Conductor (L33) .......89
Table 1- Support Types and Duties Table for 200mm2 POPLARAAAC (Severe Weather
Area)................................................................................................................................................90
Table 2- Conductor Design Table for 200mm POPLAR AAAC (Severe Weather Area) .91
Table 3- Conductor Pre-Tension Table for 200mm2 POPLARAAAC (Severe Weather
Area)................................................................................................................................................92
Table 4- Conductor Erection Table for 200mm2 POPLARAAAC (Severe Weather Area)92
Table 5-Maximum Angle of Deviation for Single Poles for 200mm2 POPLARAAAC
(Severe Weather Area) ..................................................................................................................93
Table 6-Maximum Angle of Deviation for H Poles for 200mm2 POPLARAAAC (Severe
Weather Area)................................................................................................................................93
Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 200mm2
POPLARAAAC (Severe Weather Area) .................................................................................94
Table 8-Strut Load in H Poles with Three Stays (kgf) for 200mm2 POPLARAAAC
(Severe Weather Area) ..................................................................................................................95
Table 9-Strut Load in H Poles with Four Stays (kgf) for 200mm2POPLARAAAC
(Severe Weather Area) ..................................................................................................................96
Table 10Strut Loading in Single Pole Construction Terminals (kgf) for 200mm2
POPLARAAAC (Severe Weather Area) .................................................................................96
Table 11-Stayed Pole Strut Capabilities for 200mm2 POPLAR AAAC (Severe Weather
Area)................................................................................................................................................97
Table 11Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Severe Weather
Area) (cont.)....................................................................................................................................98
Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 200mm2
POPLARAAAC (Severe Weather Area) .................................................................................99

___________________________________________________________________________
SP Power Systems Ltd

Page 8 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 6 33kV Severe Weather Area 300mm2 AAAC UPAS Conductor (L35) ...........100
Table 1- Support Types and Duties Table for 300mm2 UPASAAAC (Severe Weather
Area)..............................................................................................................................................101
Table 2- Conductor Design Table for 300mm UPASAAAC (Severe Weather Area) ......102
Table 3- Conductor Pre-Tension Table for 300mm2 UPASAAAC (Severe Weather Area)
........................................................................................................................................................103
Table 4- Conductor Erection Table for 300mm2 UPASAAAC (Severe Weather Area) ...103
Table 5-Maximum Angle of Deviation for Single Poles for 300mm2 UPASAAAC (Severe
Weather Area)..............................................................................................................................104
Table 6-Maximum Angle of Deviation for H Poles for 300mm2 UPASAAAC (Severe
Weather Area)..............................................................................................................................104
Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 300mm2 UPASAAAC
(Severe Weather Area) ................................................................................................................105
Table 8-Strut Load in H Poles with Three Stays (kgf) for 300mm2 UPASAAAC (Severe
Weather Area)..............................................................................................................................106
Table 10Strut Loading in Single Pole Construction Terminals (kgf) for 300mm2
UPASAAAC (Severe Weather Area) .....................................................................................107
Table 11-Stayed Pole Strut Capabilities for 300mm2 UPASAAAC (Severe Weather Area)
........................................................................................................................................................108
Table 11Stayed Pole Strut Capabilities for 300mm2 UPASAAAC (Severe Weather Area)
(cont.).............................................................................................................................................109
Table 12- Pole Sizing for Intermediate and section Poles for 300mm2 UPASAAAC (Severe
Weather Area)..............................................................................................................................110

___________________________________________________________________________
SP Power Systems Ltd

Page 9 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 7 Installation requirements for Conductors incorporating Optical Fibres ..........111


13

INTRODUCTION........................................................................................................111

13.1

General ..................................................................................................................111
13.1.1 Optical Phase Conductors ..................................................................................111
13.1.2 Crossarms, Supports and Stays ..........................................................................111

13.2

Materials................................................................................................................112
13.2.1 Optical Phase Conductors (OPPC) ....................................................................112
13.2.2 Vibration Damper ..............................................................................................112
13.2.3 Suspension Components ....................................................................................112
13.2.4 UPAS Equivalent OPPC Tension String Components ......................................113
13.2.5 POPLAR Equivalent OPPC Tension String Components .................................114

13.3

Optical Splice Enclosures .....................................................................................115


13.3.1 Electrical Connections .......................................................................................115

13.4

Earthing.................................................................................................................116

13.5

Optical Fibre Cable Connections .........................................................................116

Poplar Equivalent Optical Conductor (Non Severe Weather Area) (L34) ............................118
Table 1 200mm2 AAAC Poplar Equivalent OPPC Conductor (Non Severe Weather Area)
........................................................................................................................................................118
Table 2 Conductor Design Table for 200mm POPLAR Equivalent OPPC AAAC (Non
Severe Weather Area)..................................................................................................................119
Table 3- Conductor Pre-Tension Table for 200mm POPLAR Equivalent OPPC AAAC
(Non Severe Weather Area) ........................................................................................................120
Table 4- Conductor Erection Table for 200mm POPLAR Equivalent OPPC AAAC (Non
Severe Weather Area)..................................................................................................................120
Poplar Equivalent Optical Conductor (Severe Weather Area) (L34).....................................121
Table 1 200mm2 AAAC Poplar Equivalent OPPC Conductor (Severe Weather Area) ...121
Table 2- Conductor Design Table for 200mm POPLAR Equivalent OPPC AAAC (Severe
Weather Area)..............................................................................................................................122

___________________________________________________________________________
SP Power Systems Ltd

Page 10 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 200mm POPLAR Equivalent OPPC AAAC

(Severe Weather Area) ................................................................................................................123


Table 4- Conductor Erection Table for 200mm POPLAR Equivalent OPPC AAAC (Severe

Weather Area)..............................................................................................................................123
UPAS Equivalent optical conductor (Severe Weather Area) (L36)........................................124
Table 1 300mm2 AAAC UPAS Equivalent OPPC Conductor (Severe Weather Area) ....124
Table 2 Conductor Design Table for 300mm UPAS Equivalent OPPC AAAC (Severe
Weather Area)..............................................................................................................................125
Table 3- Conductor Pre-Tension Table for 300mm2 UPAS Equivalent OPPCAAAC
(Severe Weather Area) ................................................................................................................126
Table 4- Conductor Erection Table for 300mm2 UPAS Equivalent OPPCAAAC (Severe
Weather Area)..............................................................................................................................126

___________________________________________________________________________
SP Power Systems Ltd

Page 11 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 8 Installation Requirements for Horse OPGW .......................................................127


14

General..........................................................................................................................127
14.1.1 Optical Ground Wire..........................................................................................127
14.1.2 Supports and Stays.............................................................................................127

14.2

Materials................................................................................................................128
14.2.1 Optical Ground Wire (OPGW) ..........................................................................128
14.2.2 Vibration Damper ..............................................................................................128
14.2.3 Suspension Components ....................................................................................128
14.2.4 Horse Equivalent Tension String Components..................................................129
14.2.5 Connection to Splice Enclosures .......................................................................130

14.3

Conductor Design/Erection Sags and Tensions ..................................................130

14.4

Location of OPGW Attachment Points on Structures.........................................131


14.4.1 Straight Section, Intermediate and Pin Angle Structures...................................131
14.4.2 Angle Section and Terminal Structures .............................................................131

14.5

Bonding and Earthing of OPGW and Components ............................................131

Horse Equivalent OPGW Conductor (80m basic span).......................................................132


Table 1 70mm2 AACSR Horse Equivalent OPGW Conductor (80m basic span) .............132
Table 2 Conductor Design table for 70mm HORSE Equivalent OPGW AACSR (80m
Basic Span) ...................................................................................................................................133
Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (80m
Basic Span) ...................................................................................................................................134
Horse EQUIVALENT OPGW Conductor (100m basic span).............................................135
Table 1 70mm2 ACSR Horse Equivalent OPGW Conductor (100m basic span) ..............135
Table 2 Conductor Design Table for 70mm HORSE Equivalent OPGW AACSR (100m
Basic Span) ...................................................................................................................................136
Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (100m
Basic Span) ...................................................................................................................................137
Horse Equivalent OPGW Conductor (120m basic span).....................................................138

___________________________________________________________________________
SP Power Systems Ltd

Page 12 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 1 70mm2 AACSR Horse Equivalent OPGW Conductor (120m basic span) ...........138
Table 2 Conductor Design Table for 70mm HORSE Equivalent OPGW AACSR (120m
Basic Span) ...................................................................................................................................139
Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (120m
Basic Span) ...................................................................................................................................140

___________________________________________________________________________
SP Power Systems Ltd

Page 13 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Drawings and Component Listings ............................................................................................141

Figure 1 11Kv Single Pole Member Drilling, Scarfing and Marking........................................................................................ 144
Figure 2 11Kv H Pole Member Drilling, Scarfing and Marking ............................................................................................... 145
Figure 3 33Kv Light Construction Single Pole Member Drilling, Scarfing and Marking ...................................................... 146
Figure 4 33Kv Light Construction H Pole Member Drilling, Scarfing and Marking.............................................................. 147
Figure 5 33Kv Heavy Construction Single Pole Member Drilling, Scarfing and Marking..................................................... 148
Figure 6 33Kv Heavy Construction H Pole Member Drilling, Scarfing and Marking ............................................................ 149
Figure 7 Delta H Pole Drilling Scarfing and Marking................................................................................................................ 150
Figure 8 Single Pole Intermediate or Pin Angle (Drawing SP2147473) .................................................................................... 151
Figure 9 Single Pole Intermediate or Pin Angle (Drawing SP4018552) .................................................................................... 153
Figure 10 H Pole Intermediate Long Span (Drawing SP4019155) ........................................................................................ 155
Figure 11 Single Pole Straight Line or Angle Section (Drawing SP2147476)........................................................................... 157
Figure 12 Single Pole Straight Line or Angle Section (Drawing SP4018548)........................................................................... 159
Figure 13 H Pole Straight Line or Angle Section (Drawing SP4019003) .............................................................................. 161
Figure 14 Long Span H Pole Straight Line or Angle Section (Drawing SP2147486)........................................................... 163
Figure 15 Delta H Pole Section or Section Angle (Drawing SP2059611) .............................................................................. 165
Figure 16 Delta Long Span H Pole Section or Section Angle (Drawing SP2059372) ........................................................... 167
Figure 17 Single Pole Terminal (Drawing SP2147474)............................................................................................................... 169
Figure 18 H Pole Terminal (Drawing 2147485)....................................................................................................................... 171
Figure 19 Single Pole Double Terminal (Drawing SP4000578) ................................................................................................. 173
Figure 20 General Arrangement Intermediate Crossarm (Drawing SP4018402).................................................................... 175
Figure 21 General Arrangement Section Crossarm (Drawing SP4018433) ............................................................................. 176
Figure 22 General Arrangement Terminal Crossarm (Drawing SP4018401).......................................................................... 177
Figure 23 General Arrangement Long Span Crossarm (Drawing SP4017663) ....................................................................... 178
Figure 24 General Arrangement Crossarm Strut (Drawing SP4017649) ................................................................................. 179
Figure 25 General Arrangement Long Crossarm Strut (Drawing SP4017635) ....................................................................... 180

___________________________________________________________________________
SP Power Systems Ltd

Page 14 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Figure 26 General Arrangement Long Span Delta Crossarm Strut (Drawing SP2143987).................................................... 181
Figure 27 General Arrangement Terminal Strap (Drawing SP4017664) ................................................................................. 182
Figure 28 General Arrangement Section Strap (Drawing SP4017666)..................................................................................... 183
Figure 29 General Arrangement Insulator Bracket (Drawing SP4018449) ............................................................................. 184
Figure 30 General Arrangement Insulator Plate (Drawing SP4017637) .................................................................................. 185
Figure 31 General Arrangement Foundation Brace Steelwork H Pole 1830mm Centres (Drawing 4017651).................. 186
Figure 32 General Arrangement Foundation Brace Steelwork H Pole 2500mm Centres (Drawing SP4017652) ............. 187
Figure 33 General Arrangement Stay and Foundation Blocks (Drawing SP4019020)............................................................ 188
Figure 34 General Arrangement Wood Brace Block Type 1 H Pole 1830mm Centres (Drawing SP4019036) ................. 189
Figure 35 General Arrangement Wood Brace Block Type 2 H Pole 2500mm Centres (Drawing SP4019037) ................. 190
Figure 36 General Arrangement H Pole Carryover Support Steelwork (Drawing SP4008885)......................................... 191
Figure 37 General Arrangement H Pole Cable Cleat / Coffin Support Steelwork (Drawing SP2143955)......................... 192
Figure 38 General Arrangement H Pole Crucifix Support Steelwork (Drawing SP2143957) ............................................ 193
Figure 39 General Arrangement Single Pole Fuse Steelwork (Drawing SP2059590) .............................................................. 194
Figure 40 General Arrangement Single Pole Fuse Outrigger Steelwork (Drawing SP2143963) ............................................ 195
Figure 41 General Arrangement H Pole Fuse Steelwork (Drawing SP2143487) ................................................................. 196
Figure 42 General Arrangement Surge Arrester Support Steelwork (Drawing SP2143956) ................................................. 197
Figure 43 General Arrangement Delta H Section Strap (Drawing SP2146143)................................................................... 198
Figure 44 General Arrangement Terminal Bracing Strap (Drawing SP4015138)................................................................... 199
Figure 45 General Arrangement Terminal Bracing Strap (Drawing SP4020576)................................................................... 200
Figure 46 General Arrangement Long Section Strap For Long Span Delta H Pole (Drawing SP4019183) ...................... 201
Figure 47 General Arrangement Heavy Construction Stay Attachment Plates (Drawing SP4009774)................................. 202
Figure 48 General Arrangement Heavy Construction Stay Attachment (Drawing SP4009862) ............................................ 203
Figure 49 General Arrangement Transformer Platform Steelwork for a Single Pole (Drawing SP4020579)....................... 204
Figure 50 General Assembly Transformer Platform Steelwork for a Single Pole (Drawing SP4020581) ............................. 205
Figure 51 General Arrangement Transformer Platform Steelwork for an H Pole (Drawing SP4020578)........................ 206
Figure 52 General Assembly Transformer Platform Steelwork for an H Pole (Drawing SP4020580) .............................. 207

___________________________________________________________________________
SP Power Systems Ltd

Page 15 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Figure 53 General Arrangement Single Pole Bog Shoe (Drawing SP2146665) ........................................................................ 208
Figure 54 General Arrangement H Pole Bog Shoe (Drawing SP........................................................................................... 209
Figure 55 General Arrangement Bog Shoe Strut (Drawing SP2146662) .................................................................................. 210
Figure 56 General Arrangement 300 Angle Bracket................................................................................................................... 211
Figure 57 General Arrangement Wind Stay Attachment .......................................................................................................... 212

___________________________________________________________________________
SP Power Systems Ltd

Page 16 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

DEFINITIONS

For the purpose of this Specification the following definitions apply:


AAAC :

All Aluminium Alloy Conductor.

Approvals Engineer:

Energy Networks representative appointed by the Engineering


Services Manager with authority for Energy Networks
approvals.

Approved:

Equipment approved in accordance with Energy Networks


Equipment Approvals Procedure, and which is considered
suitable for installation on The Companys networks.

Auxiliary Equipment:

Equipment other than that forming part of the line design


which may be placed on supports such as transformers, fuse
gear etc.

Average Span:

The arithmetic average of a number of spans in a line or


section of line.

Basic Span:

The span length adopted for sag/tension calculations.

Conductor Creep:

Permanent long term elongation of the conductor.

Conductor Downpull:

The vertical loading imposed by the conductors corresponding


to a gradient measured between adjacent pole tops.

Construction Terminal:

A support at which the line may be terminated temporarily on


one side of the Crossarm only on tension insulator sets.

Crossarm Assembly:

A descriptive term used to include all pole top Crossarm


components and fixings.

Energy Networks:

SP SP Power Systems Ltd, operator of network assets on


behalf of the company.

Engineer:

Energy Networks nominated representative having authority


over technical matters contained in this specification.

Intermediate Support:

A support in a straight run of line on which the conductors are


supported on pin or post Insulators.

Maximum Conductor Weight (MCW):

The likely maximum vertical component of


applied conductor load.

___________________________________________________________________________
SP Power Systems Ltd

Page 17 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

Maximum Span:

OHL-03-099
Issue 1

The maximum permitted length of any span.

Maximum Working Tension (MWT):

The conductor tension assessed at -5.6C with


wind and ice loading, which may be limited by
vibration considerations.

Non Severe Weather Environment

As defined in Energy Networks Document


OHL-01-008
Construction
Policy
for
Distribution Overhead Lines

OPGW:

Optical Ground Wire

OPPC:

Optical Phase Conductor

Over tensioning:

Excess tension applied above normal tension at time of erection


to compensate for conductor creep.

Recommended Span:

The average span length in any section to which the line should
be planned.

Sag:

The vertical distance, under any system of conductor loading,


between the conductor and a straight line joining adjacent
supporting points, measured at mid-span.

Section Angle Support:

A support at which a line deviates and the conductors are made


off on either side of the Crossarm on tension insulators.

Section Support:

A support in a straight run of line on which the conductors are


made off on either side of the Crossarm on tension insulators.

Severe Weather Environment

As defined in Energy Networks Document OHL-01-008


Construction Policy for Distribution Overhead Lines

Span:

The horizontal distance between adjacent supports. Individual


spans will normally be within 20% of the basic span.

The Company:

Refers to SP Distribution Limited, SP Transmission Limited


and SP Manweb plc.

Uplift

When a line profile indicates a conductor attachment point is


below the -5.6C curve when strung between two adjacent
supports.

Wind Loading Span:

Half the sum of the spans adjacent to the support.

___________________________________________________________________________
SP Power Systems Ltd

Page 18 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

REFERENCES

When designing or constructing overhead lines in accordance with this specification it is


essential that the appropriate persons be in possession of the latest versions of the following
documents.
Statutory Legislation
ESQCR
NRSWA

Electricity Safety, Quality and Continuity Regulations 2002 SI 2665


The New Road and Street Works Act 1991

British Standards (BS)


BS 144
Specification for coal tar creosotes for wood preservation.
BS 183
Specification for General Purpose Galvanised Steel Wire Strand
BS EN ISO 898-1
Mechanical properties of fasteners made of carbon steel and alloy steel,
Bolts, Screws and Studs.
BS EN ISO 1461
Hot dip galvanised coatings on fabricated iron and steel articles
BS 1494-1
Fixings for Sheet, Roof and Wall Coverings
BS 1990 Part 1
Wood poles for overhead lines (Power and Telecoms. lines).
BS 3288
Insulator and conductor fittings for overhead power lines.
BS 4102
Steel Wire for General Fencing Purposes
BS 5950 Part 1
Structural Use of Steelwork in building. Code of Practice
BS EN 20898-1
Mechanical Properties of Fasteners Bolts, Screws and Studs
BS EN 10244-2
Non-ferrous metallic coatings on steel wire - Part 2: Zinc or zinc alloy
coatings on steel wire.
BS EN 61284
Overhead Lines-Requirements and Tests for Fittings.

Continued on next page.

___________________________________________________________________________
SP Power Systems Ltd

Page 19 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Continued from previous page.


Energy Networks Documents
EPS-01-004

Policy for Signing and Guarding of Electrical Networks Apparatus.

OHL-14-005
OHL-03-095
OHL-03-096

Wood Pole Overhead line Clearances.


Specification for Overhead Line Conductor.
Specification for Overhead Line Conductor Incorporating Optical Fibres.

DOC-00-313

Wood Pole Overhead Line Manual.

OHL-18-017
OHL-18-018
OHL-18-019
OHL-18-022
OHL-21-003
OHL-21-004
OHL-21-016
OHL-22-003
OHL-22-004
OHL-22-005
OHL-22-010
OHL-22-012
OHL-22-013
OHL-22-023
OHL-22-026
OHL-22-027
OHL-22-028
OHL-22-029
OHL-22-030
OHL-23-001
OHL-23-002
OHL-25-002
OHL-25-007

Termination of 11kV Cables on Single Poles.


Termination of 11kV Cables on H Poles.
Termination of 33kV Cables on a Crucifix.
Erection of Optical Phase Conductors.
Power Installed Screw Anchors (Sheer Pine Method).
Power Installed Screw Anchors (Torque Method).
Rock Anchors.
Transformer Erection Single Bolt Fixing.
Transformer Erection Single Pole Platform.
Transformer Erection H Pole (2 Tirfor Method).
Installation of Air Break Switch Disconnector.
Installation of Novexia Auguste Switch.
Installation of Pole Mounted Auto Reclosers.
Installation of 15kV Trisec Air Break Sectionalisers.
Installation of 11kV Fuse Mounts on Single Poles.
Installation of 11kV Fuse Mounts With Outrigger Brackets.
Installation of 11kV Fuse Mounts on Spur Poles.
Installation of 11kV Fuse Mounts on H Poles.
Transformer Erection H Pole (1 Tirfor Method).
Labelling of Wood Pole Apparatus in SP Distribution Ltd
Network Area & SP Transmission Ltd Network Area.
Labelling of Wood Pole Apparatus in SP Manweb plc
Network Area.
LV Neutral Earths.
Overhead Line Equipment Earth Systems.

Continued on next page.

___________________________________________________________________________
SP Power Systems Ltd

Page 20 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Continued from previous page.


Electricity Association Technical Specifications (ENATS)
ENATS 43-8
ENATS 43-40

Overhead Line Clearances


Specification for Single Circuit Overhead Lines on Wood Poles for use at
High Voltage Up To and including 33kV.
ENATS 43-88 Selection and treatment of wood poles and associated timber
for overhead lines.
ENATS 43-90 Anti-Climbing Devices and Safety Signs for HV Lines up to and including
400kV.
ENATS 43-91 Stay strands and stay fittings for overhead lines.
ENATS 43-92 Overhead Line Fittings.
ENATS 43-93 Line Insulators.
ENATS 43-95 Steelwork for overhead lines.
ENATS 43-96 Fasteners and washers for wood pole overhead lines.
ENATS 43-119 Designs and Use of Temporary Scaffold Guards
Electricity Networks Association Engineering Recommendations (ER)
ER-P27
ER-PO5

Current Rating Guide for High Voltage Overhead Lines Operating In the
UK Distribution System.
Protection of Telecommunication Lines from High Voltage Power Lines.

___________________________________________________________________________
SP Power Systems Ltd

Page 21 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

INTRODUCTION

It is Asset Strategys aspiration that all Overhead networks will be suitably storm resilient,
lines constructed to this specification will fulfil those requirements providing reliable and
economical network performance.
This Specification has been prepared to provide a design of 11kV and 33kV overhead lines
suitable for application within the companies licensed areas. They incorporate features of
previously proven company specifications, particularly with regard to conductors, maximum
working tensions, span lengths and factors of safety.
All overhead lines erected after 31st January 2003 are required to comply with the Electricity
Safety, Quality and Continuity Regulations. Overhead lines designed and constructed in
accordance with this Specification are deemed to comply with ESQCR 2002 SI 2665.
Any overhead line or part of an overhead line, not complying with this Specification shall, in
each case, be subject to Approval by the Engineering Services Manager or nominated
representative.
Approval will normally be sought when the line is being planned.

___________________________________________________________________________
SP Power Systems Ltd

Page 22 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

10 DESIGN DATA
10.1

Design Basis

The design basis for this specification mirrors that in ENA TS 43-40, utilising an empirical
approach.
10.2

Conductors

The tension of any line conductor at a temperature of -5.6 Celsius and subjected to a design
wind and ice loading appropriate to the environment in which the line will be situated, shall
ensure that the conductor will have a minimum factor of safety of 2.5 over the rated breaking
strength of the conductor.
The basic span length is specific to the conductor and environment in which the line will be
situated and will be specified in the relevant appendix.
10.3

Crossarms

The minimum factor of safety on all Crossarm assemblies and associated steelwork is 2.5 in a
Non Severe Weather Environment and up to 3.5 in a Severe Weather Environment on the
yield stress of the steel.

___________________________________________________________________________
SP Power Systems Ltd

Page 23 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

10.4

OHL-03-099
Issue 1

Supports

The strength of supports is derived from formulae contained in BS 1990 part 1.


The stresses created in intermediate supports are bending stresses due to windage on
conductors, the loading point being 230mm above pole tops. All in-line intermediate and
section poles have a minimum factor of safety of 3.5 in all Weather Environments.
The stresses created in stayed supports are crippling stresses due to stay tension, steelwork
and vertical conductor loads acting at the pole top. All angle and terminal poles have a
minimum factor of safety of 2.5 in a Non Severe Weather Environment and up to 3.5 in a
Severe Weather Environment.
Pole top horizontal loading has also to be maintained within specified limits to prevent pole
top splitting. Poles shall be of a sufficient diameter to withstand the above-mentioned
stresses. Therefore the minimum pole grade allowable in Appendix 1 only shall be
Medium, all other Appendices require a minimum pole grade of Stout to BS 1990 Part 1
for the purpose of this Specification. In addition a minimum pole top diameter is specified in
Table 11 of appendix 1 or Table 10 in all other appendices, this pole top diameter may exceed
the minimum pole top diameter quoted in BS 1990 Part 1. This more onerous requirement
should be taken into account when selecting poles.
For Pinus Sylvestris, the average ultimate extreme fibre stress value used is in all pole
calculations is 53.3N/mm.the average modulus of elasticity fibre stress is 10054N/mm.
In all cases, the appropriate pole strength has been calculated using a maximum taper of
11.25mm/m.
10.5

Stays

The minimum factor of safety on stay assemblies is 2.5 in a Non Severe Weather
Environment and up to 3.5 in a Severe Weather Environment based on the minimum failing
load of the assembly.
11 MATERIALS
Except where otherwise specified all materials used in the construction of lines to this
Specification shall comply with current British Standards and ENA Technical Specifications
as appropriate. Only Energy Networks Approved materials shall be used.

___________________________________________________________________________
SP Power Systems Ltd

Page 24 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

12 TECHNICAL REQUIREMENTS FOR THE ERECTION OF LINES


12.1

Structure Type and Capabilities

Table 1 of appendices 1 to 6 contained within this specification provides details of the


various structure types, limiting span length and angle of deviation detailed under gradient
conditions as applicable, together with the appropriate Energy Networks drawing reference
numbers. The maximum span lengths indicated take account of conductor clashing and
steelwork strength limitations.
Poles, which are subject to Uplift at 5.6C, shall be sectioned.
12.2

Wood Poles

Wooden poles shall be of the species Scots Pine (Pinus Sylvestris) and shall be imported
from a Nordic Country and grown at latitude greater than 6000'00"N.
Poles shall be creosoted to BS144 using the Rueping empty cell process. In all circumstances
poles shall comply with BS 1990 Part 1 and ENATS 43-88 Parts 1 and 2. They shall be
supplied drilled and scarfed. Pole blocks shall be fabricated to ENATS 43-91 drawing
439103 Type 2 and drawing 439112 Type 1 & 2 as required.
12.2.1

Section, Section Angle and Terminal Supports

The gradient limitations quoted in Table 1 of appendices 1 to 6 are derived from the
conductor vertical load, which can be accommodated by the Crossarms and is expressed as a
Downpull gradient, which is measured between adjacent pole tops.
The gradient limitations quoted in Table 1 refer to Downpull gradients on each side of the
support and therefore it is acceptable to summate gradients. The gradients limitations quoted
in Table 1 are therefore permitted on both sides of the supports. Terminal supports are
designed to allow for the appropriate value on one side of the structure only.
The Uplift limits on section, section angle and terminal structures shall be taken as being the
same as for Downpull detailed in Table 1 of the relevant appendices.

___________________________________________________________________________
SP Power Systems Ltd

Page 25 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.2.2

OHL-03-099
Issue 1

Supports

For Section and intermediate structures the maximum Downpull shall be no greater than an
equivalent gradient of 1:10 to the horizontal plane on either side of the structure.
1910

1:10*

1:10*

For hillside applications, the maximum gradient quoted in Table 1 of appendices 1 to 6 for
intermediate supports is limited by the method of conductor attachment and is permitted only
where angle 1660 and where angle 1910 where these limitations cannot be satisfied a
section structure should be employed.
1910

1:4

1660

For Terminal structures the maximum Downpull shall be equivalent to a gradient of 1:5 to the
horizontal plane on one side of the structure only.
Any structure not complying with the requirements set out above shall be subject to approval.
Approval will normally be sought when the line is being planned.

___________________________________________________________________________
SP Power Systems Ltd

Page 26 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.3

OHL-03-099
Issue 1

Pole Strut Loadings

The strut loading imposed on poles due to vertical components of stay and conductor tensions
including any auxiliary equipment at specified angles of line deviation and ground slope
conditions are specified in the Tables 7, 8 & 9 of appendices 1 to 6.
For all single pole 11kV structures an allowance of 600kg has been included for the
attachment of auxiliary equipment.
During construction, section poles may be utilised as temporary terminals. Where a single
pole section structure is required for this situation, the pole must be graded such that it is
capable of a terminal load condition as detailed in pole strut loading tables of the relevant
appendices.
Temporary terminal stays will be fitted in accordance with Energy Networks Approved
staying methods and placed at the ends of the crossarm and the stay anchors positioned no
closer to the pole than two pole lengths, this may require to be increased significantly where
conductors in excess of 100mm2 are employed to limit the loading applied to the pole and
crossarm assembly.
12.4

Windspan and Foundation Requirements

Pole foundations shall be designed to withstand the overturning moment due to windage on
conductors, poles and insulators. Foundation design shall also take account of the rupturing
capacity of the ground. In excavating foundation holes, the minimum amount of soil shall be
disturbed in order to take advantage of the load bearing value of the virgin ground as far as
possible. Back-filled soil shall be compacted using hand or mechanical compaction methods,
not more than 150mm of loose soil shall be returned between each ramming operation.
All structures shall have a minimum of one foundation block fitted at a minimum of 500mm
below ground level. Where an angle of deviation exists the top foundation block shall be on
the inside of the angle.
Where the quality of backfill material is unsuitable it will be necessary to replace the
excavated material with a suitable imported backfill, however an Energy Networks approved
soil additive, e.g. Permasoil, may be used to improve the quality of poor soil.

___________________________________________________________________________
SP Power Systems Ltd

Page 27 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

The Engineer shall inspect holes and, where deemed necessary, additional kicking blocks or
bog shoes as detailed in Energy Networks Drawings Reference SP2146665 (Single Pole Bog
Shoe) or SP2146682 H Pole Bog Shoe shall be installed.
In addition it may be necessary to install wind stays in accordance with Energy Networks
Drawing Reference SP4000336 to exposed sections of line where directed by the Engineer.
All Foundations shall have a minimum factor of safety of 2.5 in a Non Severe Weather
Environment and up to 3.5 in a Severe Weather Environment.
The values for Windspan capabilities for Unstayed Intermediate and Section structures
quoted in Table 11 or 12 as applicable of the appendices have been calculated using a soil
bearing capacity of 314 (kN/m)
Table 10 of appendix 1 and Table 11 of appendices 2 to 6 also detail the planting depths
appropriate to the various pole lengths.

___________________________________________________________________________
SP Power Systems Ltd

Page 28 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.5

OHL-03-099
Issue 1

Failure Containment Requirements

All lines shall include supports, designed to contain a cascade failure, separated by not more
than 1000m. Supports, which are considered adequate to provide failure containment, are: (i)

Any Section Structure. (Minimum Grade Stout as defined in BS 1990)

(ii)

Any H Pole Section Structure.

(iii) Any section angle structure, which requires to be fitted with twin-splayed, stays,
with a stay slope of 45.
(iv) Any H Pole section angle structure in excess of 30o fitted with splayed stays with
a stay slope of 45.
(v)

Any H Pole section, section angle structure fitted with twin splayed stays with a
stay slope of 45o employed on both sides of the structure in the plane of the line.

(vi) A Terminal Structure.

Conductor

Acceptable Failure Containment Options


(i)

(ii)

(iii)

(iv)

(v)

(vi)

Hazel

Oak

--

Ash

--

Poplar

--

--

Upas

--

--

--

Note:- The following table indicates the minimum requirements to satisfy option (iv) for the
various conductor types.
Conductor Type
Hazel
Oak
Ash
Poplar

Angle of deviation on a
Single Pole
>45o
>40o
>29o
>15o

___________________________________________________________________________
SP Power Systems Ltd

Page 29 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.6

OHL-03-099
Issue 1

Steelwork and Bolts

The steelwork for the structure types included in this Specification has been designed using
BS 5950 Part 1 and shall generally conform to the requirements of ENATS 43-95.
All intermediate, section, section angle and terminal supports shall have anti-split bolts fitted
above and below the Crossarm steelwork.
Bolts shall generally conform to ENATS 43-96 and BS EN ISO 898-1
Terminal Bracing Straps Drawing reference SP4020576 for L33 construction and Drawing
Reference SP4015138 for L35 or L36 construction shall be substituted for item 9 in the H
Pole Terminal Structure general assembly Drawing reference SP2147485.
M20 High Yield Steel Pole Bolts (Stamped 8.8) are required for all structures for all
applications.

___________________________________________________________________________
SP Power Systems Ltd

Page 30 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.7

OHL-03-099
Issue 1

Stays

Stays shall be Energy Networks Approved and comply with ENATS 43-91, design
calculations have been based on galvanised steel stranding of 7/4.00mm, Grade 1150 to BS
183. Stay wires shall generally be made off with helical fittings at the pole top, insulator
positions and on the stay rods. Where conductors in excess of 200mm2 are employed, Stay
attachment at pole tops shall be as shown in Energy Networks Drawing ref SP4009862
Thimbles used for making off stay wire to stay rods shall conform to ENATS 43-91. Drawing
439109 Type 1 for 7 /4.00mm stays
Stay blocks shall be cut from sawn timber to produce rectangular sections and shall conform
to ENATS 43-91 as shown in Energy Networks Drawing ref SP4010920 for 7/4.00mm stays
and shall be creosoted to BS 144 using the Rueping Empty Cell Process.
Stay rods shall be adjustable and in accordance with ENATS 43-91 drawing 439101 Type 2
for 7/4.00mm stays.
Tables 7 and 8 of the appendices detail the maximum angles of deviation allowable for the
varying stay slopes relative to a number of stays. Terminal supports shall be stayed in
accordance with the requirements for a 60 angle of deviation.
Where two stays are required, they can be installed either splayed or in tandem. When
splayed, they shall be a minimum of 3m apart at ground level. When in tandem, the stay
blocks shall be in separate holes with at least 3m undisturbed ground between them. Tandem
Stays are not permitted when the structure is designated as a failure containment structure as
defined in 11.5
All stays are to be installed such that the stay wire is left tight under normal working
conditions, with the stay load equally proportioned between the stays where multiple stays
are employed.
Stay insulators shall be as detailed with ENATS 43-91 drawing 439101 Type 1 for use at
11kV and for 33kV two Type 2 insulators in an insulator link assembly drawing 439108 shall
be used. Insulators shall be inserted in every stay wire in such a position that, with the stay
hanging down in a vertical position, the insulator shall be below the lowest bare conductor
but in no circumstance less than 3m above ground. On multiple stayed poles, insulators shall
be staggered to avoid clashing.
The method of installation of stays is detailed in Energy Networks Document OHL-21-002
Rock stays and their method of installation will be of an Energy Networks Approved type the
method of installation is detailed in as detailed in Energy Networks Document OHL-21-016.

___________________________________________________________________________
SP Power Systems Ltd

Page 31 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Only Energy Networks Approved power installed screw anchors may be used and may only
be installed with the agreement of the Engineer The method of installation is detailed in
Energy Networks Documents OHL-21-003 & OHL-21-004.
12.8

Line Conductors

The line conductors shall conform to Energy Networks Specification for Overhead Line
Conductor (OHL-03-095) or (OHL-03-096) as applicable.
The use of PVC covered conductor for line conductor applications is not recommended and
reference should be made to the Engineering Services Manager when considering any use of
covered conductors.
12.8.1

Line jumpers

Line jumpers on section and tapping poles shall be formed in the same AAAC Conductor as
the line conductors. These jumpers shall be directly connected to the line conductor by
Energy Networks Approved Compression connectors.
12.8.2

Down Dropper Jumpers

Where there is a requirement to connect an item of 11kV plant or apparatus to the overhead
line, the associated connecting jumpers shall be formed in covered copper flexible jumpers.
These jumpers shall not be connected to the overhead line conductor directly, a pre fabricated
Energy Networks approved wedge type live line bail shall be connected to the overhead line
conductor, the flexible jumper shall then be connected to the live line bail using a Energy
Networks Approved flexible jumper kit.
The method of installation of down dropper jumpers is detailed in Energy Networks
Document OHL-22-006.

___________________________________________________________________________
SP Power Systems Ltd

Page 32 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.9

OHL-03-099
Issue 1

Insulators and Conductor Fittings

Only Energy Networks Approved polymeric tension insulator sets shall be used at section
and terminal positions, these shall comply with ENATS 43-93.
Where the conductors cross sectional area is in excess of 200mm2 the tension string crossarm
attachment components shall comprise of a BS3288 Shackle Ref 28/29 and a BS 3288 Ball
End Link Ref 28/30. These components shall be substituted for item 15 of the structure
general assembly drawings. All components in the tension string including the tension
insulator shall be rated at a minimum value of 125kN. Where required Sag Adjuster Plates
BS3288 Ref 28/100 and an additional BS3288 Shackle Ref 28/29 may be installed as shown
in Appendix 7 in Energy Networks Drawing Ref SP4022218
For non-tension insulators, only Energy Networks Approved Porcelain Insulators shall be
used on intermediate structures, and for conductor support, unless otherwise specified. These
shall comply with ENATS 43-93, Drawing Reference 439301 for 11kV and Drawing
Reference 439302 for 33kV.
Where the conductor cross sectional area is in excess of 200mm2 only Energy Networks
approved polymeric post type insulators complying with ENATS 43-93 with a separate
armour grip suspension clamp top complying with BS EN 61284 shall provide support at
intermediate structures. These may also be employed as support insulators at terminal and
section structures. These post insulators shall be substituted for items 11 & 12 of the structure
general assembly drawings.
At Earthed Poles Energy Networks Approved Polymeric Insulators shall be used for all line
insulation applications.
All Insulator and Conductor fittings shall comply with BS 3288.
Arcing horns shall not normally be fitted to tension insulator sets.
Energy Networks Approved Tension dead-ends can be either of the compression or helical
type depending on the conductor type. These shall meet the requirements of ENATS 43-92.
Full tension mid-span joints shall only be used in exceptional circumstances when agreed by
the Engineer and any such joint shall be located at least 1 metre from any conductor deadend, or conductor fitting. Non-tension joints shall be of the compression type meeting the
requirements of ENATS 43-92.

___________________________________________________________________________
SP Power Systems Ltd

Page 33 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.10

OHL-03-099
Issue 1

Span Lengths

The basic span length adopted by this specification is dependant on the chosen conductor and
the environment in which the line will be situated and as such is specified in the appropriate
conductor appendices. Individual spans will normally be within 20% of the chosen basic
span.
The average span length of every kilometre of line (not necessarily between section supports)
shall not be greater than the basic span.
In extreme circumstances an occasional Maximum span shall be permitted. In such cases the
maximum span length for individual structures is given in Table 1 of appendices 1 to 6.
No more than two adjacent maximum spans shall be permitted as detailed in Table 1 of
appendices 1 to 6
Where Long Span H Pole Structures are employed, in line stays shall be installed against
the long spans to reduce the effect of out of balance tensions on the adjacent spans.
12.11

Section Lengths

Section lengths, defined as the length between two section supports, shall not exceed 1000m.

___________________________________________________________________________
SP Power Systems Ltd

Page 34 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.12

OHL-03-099
Issue 1

Conductor Design/Erection Sags and Tensions

Ordinates for plotting uplift curves are based on conductor design tensions.
Ordinates for plotting ground clearance curves assume the use of new conductor and include
an allowance for long-term creep over a period of 25 years.
Conductor design sags / tensions are given in Table 2 of appendices 1 to 6.
Erection sags and tensions are given in Table 4 of appendices 1 to 6 and are based on the
conductor design tensions, but have been subject to a 10% over tension to accommodate the
long-term stretch of the conductor during the life of the line.
The conductors shall be pre-tensioned for a minimum time of 60 minutes. At 15-minute
intervals during this period, the tension or sag shall be adjusted in order to maintain the
correct value.
Conductor Pre-Tension sags / tensions are given in Table 3 of appendices 1 to 6.
The erection sags given in Table 4 of appendices 1 to 6 have been calculated from the
conductor design tensions.

___________________________________________________________________________
SP Power Systems Ltd

Page 35 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.13

OHL-03-099
Issue 1

Conductor Spacing and Clearances

The mid span conductor phase spacing generally limits the maximum span lengths detailed in
Table 1of appendices 1 to 6. The following values have been used to establish the values in
Table 1.
The standard conductor spacing is 1.2m on intermediate and terminal supports
The conductor spacing for section angle supports 600 is 1.21m.
The conductor spacing for section angle supports 600 750 is 1.11m.
The conductor spacing for long span H section angle supports 300 1.93m.
The likely maximum conductor temperature for the purpose of assessing clearances is
specific to the chosen conductor and is specified in the relevant appendices.
The minimum electrical clearance between any energised unsupported conductor and an
insulator support, steelwork; stay wire (earthed or unearthed) or stay-bonding device shall not
be less than 400 mm.
The minimum electrical clearance between energised unsupported conductors shall not be
less than 600 mm.
12.13.1 Minimum Height of Line Conductors
The height above ground of any line conductor, or any wire or cable attached to a pole
carrying any line conductor, shall not, at its likely maximum temperature be less than the
value specified in Energy Networks Document OHL-14-005 at any point. In order to
calculate the height above ground of a line conductor, the appropriate sag for the span length
and maximum operating temperature must first be selected from Table 2 of the appropriate
appendix.
12.13.2 Summary of Statutory Ground Clearances
Road Crossing
5.8m

Ground Not Over Road


5.2m

Connecting Jumpers
4.3m

To ensure compliance with the above Statutory Clearances an additional 450mm shall be
allowed on the profile ground clearance at maximum still air sag condition to allow for minor
variations in ground level due to farming activities.

___________________________________________________________________________
SP Power Systems Ltd

Page 36 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

12.13.3 Clearances to Obstacles


With the line conductors at the likely maximum temperature in still air or deflected at any
angle up to 45 from the vertical, the minimum clearances detailed in Energy Networks
Document OHL-14-005 shall be achieved.
12.13.4 Clearances to other Power Lines
Where power lines cross over or are in proximity to one another, the voltage of the power line
with the higher system voltage as detailed in Energy Networks Document OHL-14-005 shall
determine clearances.
12.13.5 Railway and Canal Crossings
When an overhead line is erected along, or across, a railway, canal or navigable river it shall
comply with such arrangements as may be prescribed, or as may be agreed with the
authorities concerned to meet local or special conditions as detailed in Energy Networks
Document OHL-14-005.
12.13.6 Telecommunications Crossings
Where an overhead line to this Specification crosses or is in proximity to a
telecommunications line, precautions shall be taken to prevent contact between the two lines
as detailed in ER-PO5
.
12.13.7 Road / Motorway Crossings
Where a line to this Specification crosses a motorway or other designated 6.1m high load
route road, the minimum height of the conductors at the likely maximum conductor
temperature must be at least 6.9m above the carriageway surface as detailed in Energy
Networks Document OHL-14-005. Where it is necessary to employ a sky cradle during
erection or maintenance works, a clearance of 8.2m must be provided between the line
conductor and carriageway surface. Where a sky cradle cannot be used, scaffolding should
be employed over a motorway. In such instance, a clearance of 14m should be ensured
between the line conductor and the surface of a normal 3-lane motorway. Details of the
design and use of temporary scaffold guards can be found in ENATS 43-119.

___________________________________________________________________________
SP Power Systems Ltd

Page 37 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.14

OHL-03-099
Issue 1

Safety Signs and Number Plates

Safety signs shall be fitted to all supports in accordance with Energy Networks policy EPS01-004.
All poles shall be labelled in accordance with Energy Networks Documents OHL-23-001 or
OHL-23-002 as appropriate.
12.15

Anti-climbing Devices

Anti-climbing devices in accordance with ENATS 43-90 shall be fitted to supports in


accordance with Energy Networks policy EPS-01-004.
Anti-climbing devices shall be fitted to all stays.
Out-rigger brackets shall conform to ENATS 43-95 drawing 439516. The minimum quality
of barbed wire shall be to BS 4102 Section 4 (galvanised steel) with barbs of 85mm spacing.
Similar wire but with the spacing of the barbs set at 50mm is commonly used. In areas where
there is the possibility of severe corrosion stainless steel barbed wire is recommended. Wire
staples shall comply with BS 1494-1. They shall be of sufficient size to firmly hold the wire
in place and be galvanised to BS EN 10244-2.

___________________________________________________________________________
SP Power Systems Ltd

Page 38 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.16

OHL-03-099
Issue 1

Bonding and Earthing

Steelwork on poles shall NOT be earthed except where transformers, ground-operated


switchgear; cable terminations or surge arresters are to be fitted. At such positions all
steelwork and other supporting metalwork mounted on the pole above the anti climbing
device shall be bonded and earthed in accordance with the requirements specified hereunder,
where the pole is not earthed all steelwork above the anti climbing device shall be bonded
together. Steelwork below the anti climbing device shall not be bonded or earthed unless
ground operated switchgear operating handles are installed below the anti climber.
The Earthing and bonding conductor shall be stranded copper conductors of a minimum cross
sectional area of 35mm for 11kV and 70mm for 33kV, the Earthing and bonding conductor
shall be green/yellow PVC, covered.
The top section of stays shall always be bonded to the adjacent steelwork, regardless of
whether the steelwork itself is earthed.
The Earthing conductor shall be connected to one or more Energy Networks Approved earth
rods at a minimum depth of 600mm to establish an earth electrode with a maximum
resistance value of 40 ohms. The first earth rod shall be positioned as close as possible to the
base of the pole.
Where appropriate, deep driving of earth rods can be employed as an alternative to a multirod installation.
The Earthing conductor shall be protected from the bottom of the pole to above the anti
climbing device by an insulated 3.0m long cable guard buried in the ground to a depth of 150
mm.
The method of installation of Earthing for switchgear is detailed in Energy Networks
Document OHL-25-007.

___________________________________________________________________________
SP Power Systems Ltd

Page 39 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

12.16.1 Neutral Earths


Where there is a requirement to install a LV Neutral Earth on any structure the method of
installation is detailed in Energy Networks Document OHL-25-002.
The Neutral Earth Conductor up to the first earth rod shall be shall be 35mm copper
conductor for transformers up to and including 100kVA and 70mm copper conductor for
200kVA transformers, The neutral earth conductor up to the first earth rod shall be black in
colour and PVC covered.
12.17

11kV Transformers

Transformers in excess of 25kVA and up to and including 100kVA may be mounted on


single poles structures on the ENATS 43-95 Transformer Platform arrangement Drawing
Reference SP4020581.
Transformers in excess of 100kVA shall only be mounted on H Poles on the ENATS 43-95
Transformer Platform arrangement Drawing Reference SP4020580.
An alternative to an H Pole may be a single pole and lay leg structure. Where a lay leg is the
preferred method of installation these poles should be obtained at the required length from the
pole supplier, under no circumstances is it acceptable to cut a pole on site to the required
length.
At such positions all steelwork and other supporting metalwork mounted on the pole above
the anti climbing device shall be bonded and earthed in accordance with the requirements
specified in 12.16.
The down dropper jumpers shall be installed in accordance with the requirements specified in
12.8.2.
The methods of installation of Transformers are detailed in Energy Networks Documents
OHL-22-03, OHL-22-04, OHL-22-05, and OHL-22-30.
The Transformer LV Neutral Earth shall be installed in accordance with the requirements
specified in 12.16.1.

___________________________________________________________________________
SP Power Systems Ltd

Page 40 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.18

OHL-03-099
Issue 1

Switchgear

All switchgear with the exception of those of the un-earthed Hook Stick or Long Stick
method of operation shall be installed on Earthed poles in accordance with the requirements
specified in 12.16. They shall be erected at the pole top below the line conductors.

Surge arresters shall be installed as directed by the Engineer and shall be fitted in accordance
with Clause 12.21.
For 11kV applications the down dropper jumpers shall be installed in accordance with the
requirements specified in Energy Networks Document OHL-22-006.
The methods of installation of Pole Mounted Switchgear are detailed in Energy Networks
Documents OHL-22-012, OHL-22-013, OHL-22-023, OHL-22-026, OHL-22-027,
OHL-22-028 and OHL-22-029.
12.19

Air Break Switch Disconnectors

Air Break Switch Disconnectors shall not be installed on Earthed poles. They shall be of an
un-earthed hook stick operated type, erected in a horizontal position at the pole top below the
line conductors
At such positions all steelwork and other supporting metalwork mounted on the pole above
the anti climbing device if fitted shall be bonded in accordance with the requirements
specified in 12.16.
For 11kV applications the down dropper jumpers shall be installed in accordance with the
requirements specified in Energy Networks Document OHL-22-006.
The method of installation of ABSD is detailed in Energy Networks Document OHL-22-010.

___________________________________________________________________________
SP Power Systems Ltd

Page 41 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.20

OHL-03-099
Issue 1

HV Cable Terminations

All HV cables shall be terminated on Energy Networks Approved terminations on poles


below the conductors in accordance with Energy Networks documents
OHL-18-17, OHL-18-18 or OHL-18-19 as appropriate.
The jumpers shall be formed in the same conductor as the line conductors and connected to
the main line with Energy Networks Approved compression connectors and terminating in an
Energy Networks Approved Bi Metallic connector on the cable termination. All connectors
shall satisfy the requirements of ENATS 43-92.
The HV cable shall be secured from 200mm below ground level up to the termination and it
shall be protected from the bottom of the pole to above the anti climbing device by an
insulated 3.0m long cable guard buried in the ground to a depth of 150 mm. Cognisance
should be taken of the requirements of Energy Networks document OHL-025-007 when
considering the routing of the cable and associated earthing system.
All metalwork on the pole including the cable termination associated mounting steelwork and
metallic cable sheath/screen above the Anti Climbing Device shall be bonded and earthed in
accordance with Clause 12.16.
Surge arresters shall normally be incorporated in the cable termination and shall be fitted in
accordance with Clause 12.21.

___________________________________________________________________________
SP Power Systems Ltd

Page 42 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

12.21

OHL-03-099
Issue 1

Surge Arresters

Energy Networks Approved surge arresters shall be fitted to protect cables and elsewhere,
where directed by the Engineer.
Where surge arrestors are to be erected on a pole, whether incorporated in a cable termination
or directly mounted on an item of plant, they shall be connected directly in the current path as
close to the plant or cable termination lugs as possible. One continuous 70mm copper
conductor which shall be green/yellow PVC covered, shall be installed directly from the
apparatus Earthing terminal or the outer surge arrester to the first earth rod which shall be
positioned as close as possible to the base of the pole. The metallic cable sheath/screen of
underground cables shall be connected to the crucifix star point, which shall then be
connected to the surge arrestor earth by a 70mm copper conductor, which shall also be
green/yellow PVC covered.
All other metalwork on the pole including the cable termination associated mounting
steelwork above the Anti Climbing Device shall be bonded to the surge arrestor earth by a
35mm Copper conductor for 11kV and a 70mm Copper conductor for 33kV applications.
The Bonding conductor shall be green/yellow PVC covered in accordance with Clause 12.16.
The earth electrode shall have a maximum resistance value of 10 Ohms.
12.22

Insulated Shrouding

Insulated Shrouding shall be fitted to all 11kV plant and equipment as directed by the
engineer.

___________________________________________________________________________
SP Power Systems Ltd

Page 43 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendices
Appendix 1

11KV Non Severe Weather Area 50mm2 AAAC Hazel Conductor (L10)

Appendix 2

11kV Severe Weather Area.100mm2 AAAC Oak Conductor (L27)

Appendix 3

33kV Non Severe Weather Area 150mm2 AAAC ASH Conductor (L27)

Appendix 4

33kV Non Severe Weather Area.200mm2 AAAC POPLAR Conductor (L33)

Appendix 5

33kV Severe Weather Area 200mm2 AAAC POPLAR Conductor (L33)

Appendix 6

33kV Severe Weather Area 300mm2 AAAC UPAS Conductor (L35)

Appendix 7

Installation requirements for Conductors incorporating Optical Fibres


(L34 & L36)

Appendix 8

Installation Requirements for Horse OPGW

___________________________________________________________________________
SP Power Systems Ltd

Page 44 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 1 11KV Non Severe Weather Area 50mm2 AAAC Hazel Conductor (L10)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC
Equipment Weight

HAZEL
0.1648
59.9
9.9
0.000023
6016.3257
1800.8
100
380
5
913
720.3
-5.6
360.2
5
666.2
0.378
0.771
396.2
600Kg

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

50oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

3.5
2.5
2.5
2.5
2.5
2.5

___________________________________________________________________________
SP Power Systems Ltd

Page 45 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 1- Support Types and Duties Table for 50mm2 HAZEL AAAC
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

114

1: 10

90

1: 5*

Single Pole

100

1:10

10

SP2147473

Single Pole

115

1:10

SP2147476

H Pole

115

1:10

SP4019003

H Pole (Long Span)

130

1:10

SP2147486

Single Pole

110

1:10

60

SP2147476

Single Pole

100

1:10

75

SP2147476

H Pole

110

1:10

75

SP4019003

H Pole (Long Span)

130

1:10

30

SP2147486

Single Pole

100

1:10

1000

SP4000578

Single Pole

114

1:5

SP2147474

H Pole

114

1:5

SP2147485

Structure Type
Intermediate
Pin Angle

Straight Section

Single Pole

Energy Networks
Drawing Reference
SP2147473

Angle Section

Double Terminal
Terminal

Note 1 * See 11.2.2 for guidance on hillside applications.

SP Power Systems Ltd

Page 46 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 2- Conductor Design Table for 50mm HAZEL AAAC


Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
440.9
396.2
360.2
325.7
293.3
263.2
236.1
212.1
191.4
173.7
158.8
146.3
135.7
126.7
119.1
112.5
106.7
101.7

SP Power Systems Ltd

50
0.12
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.27
0.30
0.32
0.35
0.38
0.41
0.43
0.46
0.48
0.51

60
0.17
0.19
0.21
0.23
0.25
0.28
0.31
0.35
0.39
0.43
0.47
0.51
0.55
0.59
0.62
0.66
0.70
0.73

70
0.23
0.25
0.28
0.31
0.34
0.38
0.43
0.48
0.53
0.58
0.64
0.69
0.74
0.80
0.85
0.90
0.95
0.99

Sag (m) for Span (m)


80
90
100
0.30
0.38
0.47
0.33
0.42
0.52
0.37
0.46
0.57
0.40
0.51
0.63
0.45
0.57
0.70
0.50
0.63
0.78
0.56
0.71
0.87
0.62
0.79
0.97
0.69
0.87
1.08
0.76
0.96
1.19
0.83
1.05
1.30
0.90
1.14
1.41
0.97
1.23
1.52
1.04
1.32
1.63
1.11
1.40
1.73
1.17
1.48
1.83
1.24
1.56
1.93
1.30
1.64
2.03

Page 47 of 212

110
0.57
0.63
0.69
0.77
0.85
0.95
1.06
1.18
1.30
1.43
1.57
1.70
1.84
1.97
2.09
2.22
2.34
2.45

120
0.67
0.75
0.82
0.91
1.01
1.13
1.26
1.40
1.55
1.71
1.87
2.03
2.19
2.34
2.49
2.64
2.78
2.92

130
0.79
0.88
0.97
1.07
1.19
1.32
1.47
1.64
1.82
2.00
2.19
2.38
2.57
2.75
2.92
3.10
3.26
3.42

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 50mm2 HAZEL AAAC


Pre-tension
at all temperatures
(Kgf)

495 kgf

50
0.10

60
0.15

70
0.20

Sag (m) for Span (m)


80
90
100
0.27
0.34
0.42

110
0.50

120
0.60

130
0.70

Sag (m) for Span (m)


80
90
100
0.28
0.35
0.43
0.31
0.39
0.48
0.34
0.42
0.52
0.37
0.47
0.58
0.41
0.52
0.64
0.45
0.57
0.71
0.51
0.64
0.79
0.56
0.71
0.88
0.63
0.79
0.98
0.70
0.88
1.09
0.77
0.97
1.20
0.84
1.06
1.31
0.91
1.15
1.42
0.98
1.24
1.53
1.05
1.32
1.64
1.11
1.41
1.74
1.18
1.49
1.84
1.24
1.57
1.94

110
0.52
0.58
0.63
0.70
0.77
0.86
0.96
1.07
1.19
1.31
1.45
1.58
1.72
1.85
1.98
2.11
2.23
2.35

120
0.62
0.69
0.76
0.83
0.92
1.02
1.14
1.27
1.41
1.56
1.72
1.88
2.04
2.20
2.35
2.51
2.65
2.79

130
0.73
0.81
0.89
0.98
1.08
1.20
1.34
1.49
1.66
1.84
2.02
2.21
2.40
2.58
2.76
2.94
3.11
3.28

Table 4- Conductor Erection Table for 50mm2 HAZEL AAAC


Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
475.5
429.8
392.7
356.9
322.6
290.3
260.6
233.7
210.1
189.6
172.2
157.6
145.2
134.8
126.0
118.4
111.9
106.2

SP Power Systems Ltd

50
0.11
0.12
0.13
0.14
0.16
0.18
0.20
0.22
0.25
0.27
0.30
0.33
0.35
0.38
0.41
0.43
0.46
0.48

60
0.16
0.17
0.19
0.21
0.23
0.26
0.28
0.32
0.35
0.39
0.43
0.47
0.51
0.55
0.59
0.63
0.66
0.70

70
0.21
0.23
0.26
0.28
0.31
0.35
0.39
0.43
0.48
0.53
0.59
0.64
0.70
0.75
0.80
0.85
0.90
0.95

Page 48 of 212

Uncontrolled Copy

OHL-03-099
Issue 1

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

Table 5-Maximum Angle of Deviation for Single Poles for 50mm2 HAZEL AAAC
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/4.00mm
2 x 7/4.00mm
25
35
40
45

45
55
65
75

Table 6-Maximum Angle of Deviation for H Poles for 50mm2 HAZEL AAAC
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


2 x 7/ 4.00mm
3 x 7/4.00mm
75
75
75
75

90
90
90
90

Note:
The minimum grade of pole for angles in excess of 50 shall be Stout as defined in BS1990.
For single pole angles between 750 and 1000 a double terminal structure drawing reference
SP4000578 shall be used.
Where a Double terminal structure is employed it shall be fitted with 4 splayed stays.
Where two stays are installed on an H pole structure they shall both be fitted to the outer
limb.

__________________________________________________________________________
Page 49 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 50mm2 HAZEL AAAC
LINE ANGLE

Level Conditions

Downpull 1: 10

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75

4196
4950
5700
6445
7184
7915
8636
9347
10046
10732
11403
12058
12696
13315
13915
14494
5190
5944
6694
7439
8909
8909
9631
10341
11040
11726
12397
13052
13690
14310
14910
15489

3925
4547
5166
5780
6389
6992
7587
8173
8749
9315
9868
10408
10934
11445
11939
12417
4920
5541
6160
6774
7986
7986
8581
9167
9744
10309
10862
11402
11928
12439
12934
13411

3715
4234
4750
5263
5771
6274
6770
7260
7740
8212
8674
9125
9563
9990
10403
10801
4709
5228
5744
6257
7268
7268
7765
8254
8735
9207
9668
10119
10558
10984
11397
11796

45

3544
3980
4413
4843
5270
5692
6108
6519
6922
7318
7705
8084
8452
8810
9156
9490
4539
4974
5407
5837
6686
6686
7102
7513
7916
8312
8700
9078
9446
9804
10150
10485

Note: * Denotes value for selection of Terminal pole at specified Gradient.

__________________________________________________________________________
Page 50 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 8-Strut Load in H Poles with Two or Three Stays (kgf) for 50mm2 HAZEL AAAC
LINE ANGLE

Level Conditions

Downpull 1: 10

30
0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90
0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90
65
70
75
80
85
90

2369
2821
3271
3718
4161
4600
5033
5459
5879
6290
6693
7086
7469
7840
8200
8548
8882
9203
9510
2866
3318
3768
4215
4659
5097
5530
5957
6376
6787
7190
7583
7966
8337
8697
9045
9380
9700
10007
8820
9180
9528
9862
10183
10490

Stay Angle
35
40
Strut Load (kgf)

2186
2559
2930
3299
3664
4026
4383
4734
5080
5419
5751
6075
6391
6698
6994
7281
7557
7821
8074
2683
3056
3427
3796
4161
4523
4880
5232
5577
5917
6249
6573
6888
7195
7492
7778
8054
8318
8571
7677
7974
8261
8537
8801
9054

2044
2355
2665
2972
3277
3579
3877
4171
4459
4742
5019
5290
5553
5809
6056
6296
6526
6746
6957
2541
2852
3162
3470
3775
4076
4374
4668
4956
5239
5516
5787
6050
6306
6554
6793
7023
7244
7454
6789
7036
7275
7506
7726
7937

45
1929
2190
2450
2708
2964
3217
3467
3713
3955
4193
4425
4652
4873
5088
5295
5496
5689
5874
6051
2426
2687
2947
3205
3461
3714
3964
4210
4452
4690
4922
5149
5370
5585
5793
5993
6186
6372
6549
6068
6275
6476
6669
6854
7031

Note: * Denotes value for selection of Terminal pole at specified Gradient.

__________________________________________________________________________
Page 51 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 9- Strut Load in Single Pole Double Terminal Structures with Four Stays (kgf) for
50mm2 HAZEL AAAC
LINE ANGLE

Level Conditions

Downpull 1: 10

75
80
85
90
95
100
75
80
85
90
95
100

Stay Angle
35
40
Strut Load (kgf)

30
14494
15052
15587
16097
16583
17043
15489
16046
16581
17092
17578
18038

12417
12877
13318
13739
14139
14519
13411
13871
14312
14733
15134
15513

10801
11185
11553
11904
12238
12555
11796
12179
12547
12898
13233
13549

45
9490
9812
10121
10416
10696
10962
10485
10807
11115
11410
11691
11956

Table 10-Strut Loading in Single Pole Construction Terminals (kgf) for 50mm2 HAZEL
AAAC
LINE ANGLE
Level Conditions
Downpull 1: 10

Structure

Back Stay Angle (640)

Construction Terminal

5622 kgf

Construction Terminal

6617 kgf

__________________________________________________________________________
Page 52 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 11-Stayed Pole Strut Capabilities for 50mm2 HAZEL AAAC


Pole
(m)
8.5
9
9.5
10
10
10.5
10.5
11
11
11.5
11.5
12
12
12
13
13
13
14
14
14
15
15
15
16
16
16
17
17
17
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
190
190
190
209
190
209
190
208
190
208
190
207
227
195
211
231
195
214
234
195
218
238
200
222
242
200
221
241
200
224
244
200
227
247
200
224
244

265
275
280
285
305
290
310
295
315
300
320
305
325
345
320
340
360
335
355
375
350
370
390
365
385
405
375
395
415
390
410
430
415
435
455
435
455
475

Taper (mm/m)
10.71
11.33
11.25
11.18
11.25
11.11
11.25
11.05
11.25
11.00
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25
11.48
11.25
11.25
11.38
11.25
11.25
11.29
11.25
11.25
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
1800
1800
1800
1800
1800
1800
1800
1800
1800
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400
2400
2400
2400

19916
18368
16546
15030
21022
13750
19061
12662
17397
12069
16448
11213
15148
20664
10683
14105
19073
9761
13308
17846
9200
12946
17238
9034
12430
16428
8271
11202
14770
7946
11093
14533
7070
9998
12984
6282
8620
11147

__________________________________________________________________________
Page 53 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL-03-099
Issue 1

Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 50mm2 HAZEL AAAC
Pole Length (m)

8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

50

60

70

235
240
245
250
255
260
265
270
280
295
310
325
340
350
380
400

235
240
245
250
255
260
265
270
280
295
310
325
340
350
380
400

235
240
245
250
255
260
265
270
280
295
310
325
340
350
380
400

Maximum Wind Span Length (m)


80
90
100
Diameter of Pole 1.5m from Butt (mm)
235
235
235
240
240
240
245
245
245
250
250
250
255
255
255
260
260
260
265
265
265
270
270
270
280
280
280
295
295
295
310
310
310
325
325
325
340
340
340
350
350
350
380
380
380
400
400
400

Note:- Pole sizes marked * shall have two blocks fitted

SP Power Systems Ltd

Pole Length (m)

Foundation Depth (m)

8.5 -11.0 inc.


11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

1.8
2.0
2.2
2.4

Page 54 of 212

110

120

130

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

2 x 235
2 x 240
2 x 245
2 x 250
2 x 255
2 x 260
2 x 265
2 x 270
2 x 280
2 x 295
2 x 310
2 x 325
2 x 340
2 x 350
2 x 380
2 x 400

2 x 235
2 x 240
2 x 245
2 x 250
2 x 255
2 x 260
2 x 265
2 x 270
2 x 280
2 x 295
2 x 310
2 x 325
2 x 340
2 x 350
2 x 380
2 x 400

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 2 11kV Severe Weather Area.100mm2 AAAC Oak Conductor (L27)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC
Equipment Weight

OAK
0.3273
118.9
14
0.000023
6016.3257
3576.1
90
380
9.5
913
1151.0
-5.6
715.2
5
1151.0
0.968
1.279
651.2
600Kg

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

50oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

3.5
2.5
2.5
2.5
2.5
2.5

___________________________________________________________________________
SP Power Systems Ltd

Page 55 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL-03-099
Issue 1

Table 1- Support Types and Duties Table for 100mm2 OAK AAAC (Severe Weather Area)
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

105

1:10

00

90

1:5*

00

Single Pole

110

1:10

00

SP2147476

H Pole

110

1:10

00

SP4019003

H Pole (Long Span)

130

1:10

00

SP2147486

Single Pole

100

1:10

600

SP2147476

H Pole

100

1:10

750

SP4019003

H Pole (Long Span)

130

1:10

300

SP2147486

Single Pole

105

1:10

00

SP2147474

H Pole

105

1:5

00

SP2147485

Structure Type
Intermediate

Straight Section

Angle Section

Single Pole

Terminal

Energy Networks
Drawing Reference
SP2147473

Note 1 * See 11.2.2 for guidance on hillside applications.

_____________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 56 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL-03-099
Issue 1

Table 2- Conductor Design Table for 100mm OAK AAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
736.6
651.2
583.9
521.0
463.7
412.9
368.9
331.7
300.6
274.7
253.2
235.2
219.9
207.0
195.8
186.0
177.5
169.9

50
0.14
0.16
0.18
0.20
0.22
0.25
0.28
0.31
0.34
0.37
0.40
0.43
0.47
0.49
0.52
0.55
0.58
0.60

60
0.20
0.23
0.25
0.28
0.32
0.36
0.40
0.44
0.49
0.54
0.58
0.63
0.67
0.71
0.75
0.79
0.83
0.87

70
0.27
0.31
0.34
0.38
0.43
0.49
0.54
0.60
0.67
0.73
0.79
0.85
0.91
0.97
1.02
1.08
1.13
1.18

Sag (m) for Span (m)


80
90
100
0.36
0.45
0.56
0.40
0.51
0.63
0.45
0.57
0.70
0.50
0.64
0.79
0.56
0.71
0.88
0.63
0.80
0.99
0.71
0.90
1.11
0.79
1.00
1.23
0.87
1.10
1.36
0.95
1.21
1.49
1.03
1.31
1.62
1.11
1.41
1.74
1.19
1.51
1.86
1.27
1.60
1.98
1.34
1.69
2.09
1.41
1.78
2.20
1.48
1.87
2.31
1.54
1.95
2.41

110
0.67
0.76
0.85
0.95
1.07
1.20
1.34
1.49
1.65
1.80
1.95
2.10
2.25
2.39
2.53
2.66
2.79
2.91

120
0.80
0.90
1.01
1.13
1.27
1.43
1.60
1.78
1.96
2.14
2.33
2.50
2.68
2.85
3.01
3.17
3.32
3.47

130
0.94
1.06
1.18
1.33
1.49
1.67
1.87
2.08
2.30
2.52
2.73
2.94
3.14
3.34
3.53
3.72
3.90
4.07

_____________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 57 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL-03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 100mm2 OAK AAAC (Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

50

60

70

80

90

100

110

120

130

828

0.12

0.18

0.24

0.32

0.40

0.49

0.60

0.71

0.83

Sag (m) for Span (m)

Table 4- Conductor Erection Table for 100mm OAK AAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
796.9
709.0
638.6
572.0
510.1
453.9
404.4
361.7
325.6
295.5
270.5
249.7
232.2
217.4
204.8
193.9
184.4
176.0

50
0.13
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.31
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.55
0.58

60
0.18
0.21
0.23
0.26
0.29
0.32
0.36
0.41
0.45
0.50
0.54
0.59
0.63
0.68
0.72
0.76
0.80
0.84

70
0.25
0.28
0.31
0.35
0.39
0.44
0.50
0.55
0.62
0.68
0.74
0.80
0.86
0.92
0.98
1.03
1.09
1.14

Sag (m) for Span (m)


80
90
100
0.33
0.42
0.51
0.37
0.47
0.58
0.41
0.52
0.64
0.46
0.58
0.72
0.51
0.65
0.80
0.58
0.73
0.90
0.65
0.82
1.01
0.72
0.92
1.13
0.80
1.02
1.26
0.89
1.12
1.38
0.97
1.23
1.51
1.05
1.33
1.64
1.13
1.43
1.76
1.20
1.52
1.88
1.28
1.62
2.00
1.35
1.71
2.11
1.42
1.80
2.22
1.49
1.88
2.32

110
0.62
0.70
0.78
0.87
0.97
1.09
1.22
1.37
1.52
1.68
1.83
1.98
2.13
2.28
2.42
2.55
2.69
2.81

120
0.74
0.83
0.92
1.03
1.15
1.30
1.46
1.63
1.81
1.99
2.18
2.36
2.54
2.71
2.88
3.04
3.20
3.35

130
0.87
0.98
1.08
1.21
1.36
1.52
1.71
1.91
2.12
2.34
2.56
2.77
2.98
3.18
3.38
3.57
3.75
3.93

_____________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 58 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 5-Maximum Angle of Deviation for Single Poles for 100mm2 OAK AAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/ 4.00
25
30
35
40

2 x 7/ 4.00
30
45
50
60

Table 6-Maximum Angle of Deviation for H Poles for 100mm2 OAK AAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


3 x 7/ 4.00mm
4 x 7/ 4.00mm
75
90
75
90
75
90
75
90

__________________________________________________________________________
Page 59 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 7- Strut Load in Single Poles with One or Two Stays (kgf) for 100mm2 OAK AAAC
(Severe Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

Downpull 1:5

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
25
30
35
40
45
50
55
60
0
5
10
15
20
25
30
35
40
45
50
55
60
0
5
10
15
20
25
30
35
40
45
50
55
60

5462
6765
8061
9349
10626
11889
13137
14366
15575
16760
17921
19054
20158
7180
8483
9779
11067
13607
13607
14855
16084
17293
18478
19639
20772
21876
8848
10151
11447
12735
15275
15275
16523
17752
18961
20146
21307
22440
23544

5059
6133
7202
8264
9316
10358
11387
12400
13397
14375
15332
16266
17176
6777
7851
8920
9982
12076
12076
13105
14118
15115
16093
17050
17984
18894
8445
9519
10588
11650
13744
13744
14773
15786
16783
17761
18718
19652
20562

4745
5641
6533
7419
8298
9167
10025
10871
11703
12519
13317
14097
14857*
6463
7359
8251
9137
10885
10885
11743
12589
13421
14237
15035
15815
16575*
8131
9027
9919
10805
12553
12553
13411
14257
15089
15905
16703
17483
18243

45

4490
5242
5991
6734
7472
8201
8921
9631
10329
11013
11683
12338
12975*
6208
6960
7709
8452
9919
9919
10639
11349
12047
12731
13401
14056
14693*
7876
8628
9377
10120
11587
11587
12307
13017
13715
14399
15069
15724
16361*

Note: * Denotes value for selection of Terminal pole at specified Gradient.

__________________________________________________________________________
Page 60 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 8- Strut Load in H Poles with Three Stays (kgf) for 100mm2 OAK AAAC (Severe
Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90
0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90

3078
3859
4637
5410
6176
6934
7682
8420
9145
9857
10553
11233
11895
12539
13162
13763
14343
14898
15429
3937
4718
5496
6269
7035
7793
8541
9279
10004
10716
11412
12092
12754
13397
14021
14622
15202
15757
16288

2815
3460
4101
4738
5370
5995
6612
7220
7818
8405
8979
9540
10086
10616
11130
11626
12104
12562
12999
3674
4318
4960
5597
6229
6854
7471
8079
8677
9264
9838
10398
10945
11475
11989
12485
12962
13421
13858

2611
3149
3684
4216
4743
5264
5779
6287
6786
7275
7754
8222
8678
9121
9549
9963
10362
10744
11109
3470
4008
4543
5075
5602
6123
6638
7146
7645
8134
8613
9081
9537
9980
10408
10822
11221
11603
11968

45

2445
2896
3346
3792
4234
4672
5104
5530
5948
6359
6761
7154
7536
7908
8267
8615
8949
9270
9576
3304
3755
4205
4651
5093
5531
5963
6389
6807
7218
7620
8013
8395
8766
9126
9474
9808
10129
10435

Note: * Denotes value for selection of Terminal pole at specified Gradient.

__________________________________________________________________________
Page 61 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 8- Strut Load in H Poles with Three Stays (kgf) for 100mm2 OAK AAAC (Severe
Weather Area) (Cont)
LINE ANGLE

Downpull 1:5

30

0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90

4771
5552
6330
7103
7869
8627
9375
10113
10838
11550
12246
12926
13588
14231
14855
15456
16036
16591
17122

Stay Angle
35
40
Strut Load (kgf)
4508
4304
5152
4842
5794
5377
6431
5909
7063
6436
7688
6957
8305
7472
8913
7980
9511
8479
10098
8968
10672
9447
11232
9915
11779
10371
12309
10814
12823
11242
13319
11656
13796
12055
14255
12437
14692
12802

45
4138
4589
5039
5485
5927
6365
6797
7223
7641
8052
8454
8847
9229
9600
9960
10308
10642
10963
11269

Note: * Denotes value for selection of Terminal pole at specified Gradient

Table 9 Strut Loading in Single Pole Construction Terminals (kgf) FOR 100mm2 OAK
AAAC (Severe Weather Area)
LINE ANGLE
Level Conditions
Downpull 1: 5

Structure

Back Stay Angle (640)

Construction Terminal

8191 kgf

Construction Terminal

11577 kgf

__________________________________________________________________________
Page 62 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 10-Stayed Pole Strut Capabilities for 100mm2 OAK AAAC (Severe Weather Area)
Pole
(m)
8.5
8.5
9
9
9.5
9.5
10
10
10.5
10.5
11
11
11.5
11.5
12
12
12
13
13
13
14
14
14
15
15
15
16
16
16
17
17
17

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
206
191
211
190
210
190
209
190
209
190
208
190
208
190
207
227
195
211
231
195
214
234
195
218
238
200
222
242
200
221
241

265
285
275
295
280
300
285
305
290
310
295
315
300
320
305
325
345
320
340
360
335
355
375
350
370
390
365
385
405
375
395
415

Taper (mm/m)
10.71
11.25
11.25
11.25
11.25
11.25
11.18
11.25
11.11
11.25
11.05
11.25
11.00
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25
11.48
11.25
11.25
11.38
11.25
11.25
11.29
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400
2400
2400
2400

20881
28533
19310
27338
17206
24314
15581
21815
14217
19725
13060
17958
12431
16956
11527
15583
21276
10949
14461
19572
9973
13606
18262
9376
13212
17606
9192
12660
16744
8402
11388
15026

__________________________________________________________________________
Page 63 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Table 10Stayed Pole Strut Capabilities for 100mm2 OAK AAAC (Severe Weather Area)
(cont.)
Pole
(m)
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
200
224
244
200
227
247
200
224
244

390
410
430
415
435
455
435
455
475

Taper (mm/m)
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2800
2800
2800
2800
2800
2800
2800
2800
2800

8175
11441
15010
7236
10258
13339
6404
8805
11401

__________________________________________________________________________
Page 64 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL-03-099
Issue 1

Table 11- Pole Sizing for Single Pole Intermediate and Section Poles for 100mm2 OAK AAAC
Pole Length (m)

8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

50

60

70

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

Maximum Wind Span Length (m)


80
90
100
Diameter of Pole 1.5m from Butt (mm)
265
265
285
275
275
295
280
280
300
285
285
305
290
290
310
295
295
315
300
300
320
305
305
325
320
320
340
335
335
355
350
350
350
365
365
365
375
375
375*
390
390
390
415
415
415
435
435
435

Note:- Pole sizes marked * shall have two blocks fitted

SP Power Systems Ltd

Pole Length (m)

Foundation Depth (m)

8.5 -11.0 inc.


11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

2.0
2.2
2.4
2.8

Page 65 of 212

110

120

130

285*
295*
300*
305*
310*
315*
320*
325*
340*
355*
370*
385*
395*
410*
415*
455*

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL-03-099
Issue 1

Appendix 3 33kV Non Severe Weather Area 150mm2 AAAC ASH Conductor (L27)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC
Equipment Weight

ASH
0.5071
180.7
17.4
0.000023
5700
5436.1071
90
380
9.5
913
1532.0
-5.6
1087.2214
5
1532.0
1.240
1.410
971.6
600Kg

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

50oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

SP Power Systems Ltd

3.5
2.5
2.5
2.5
2.5
2.5

Page 66 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 1- Support Types and Duties Table for 150mm2 ASHAAAC (Non Severe Weather Area)
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

100

1:10

00

90

1:5*

00

Single Pole

110

1:10

00

SP2147476

H Pole

110

1:10

00

SP4019003

H Pole (Long Span)

130

1:10

00

SP2147486

Single Pole

100

1:10

450

SP4018548

H Pole

100

1:10

750

SP4019003

H Pole

90

1:10

900

SP4019003

H Pole (Long Span)

120

1:10

150

SP2147486

H Pole

110

1:10

00

SP2147485

Structure Type
Intermediate

Straight Section

Single Pole

Angle Section

Terminal

Note 1 * See 11.2.2 for guidance on hillside applications.

SP Power Systems Ltd

Page 67 of 212

Energy Networks
Drawing Reference
SP2147473

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2- Conductor Design Table for 150mm ASH AAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1093.8
971.6
875.2
785.1
702.6
629.0
564.8
510.0
463.6
424.8
392.2
364.7
341.3
321.3
304.0
289.0
275.8
264.0

SP Power Systems Ltd

50
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.52
0.55
0.57
0.60

60
0.21
0.23
0.26
0.29
0.32
0.36
0.40
0.45
0.49
0.54
0.58
0.63
0.67
0.71
0.75
0.79
0.83
0.86

70
0.28
0.32
0.35
0.40
0.44
0.49
0.55
0.61
0.67
0.73
0.79
0.85
0.91
0.97
1.02
1.07
1.13
1.18

Page 68 of 212

80
0.37
0.42
0.46
0.52
0.58
0.64
0.72
0.80
0.88
0.96
1.03
1.11
1.19
1.26
1.33
1.40
1.47
1.54

Sag (m) for Span (m)


90
100
0.47
0.58
0.53
0.65
0.59
0.72
0.65
0.81
0.73
0.90
0.82
1.01
0.91
1.12
1.01
1.24
1.11
1.37
1.21
1.49
1.31
1.62
1.41
1.74
1.50
1.86
1.60
1.97
1.69
2.08
1.78
2.19
1.86
2.30
1.94
2.40

110
0.70
0.79
0.88
0.98
1.09
1.22
1.36
1.50
1.65
1.81
1.96
2.10
2.25
2.39
2.52
2.65
2.78
2.90

120
0.83
0.94
1.04
1.16
1.30
1.45
1.62
1.79
1.97
2.15
2.33
2.50
2.67
2.84
3.00
3.16
3.31
3.46

130
0.98
1.10
1.22
1.36
1.52
1.70
1.90
2.10
2.31
2.52
2.73
2.94
3.14
3.33
3.52
3.71
3.88
4.06

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 150mm2 ASHAAAC (Non Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

50

60

70

80

90

100

110

120

130

1231

0.13

0.19

0.25

0.33

0.42

0.51

0.62

0.74

0.87

Sag (m) for Span (m)

Table 4- Conductor Erection Table for 150mm2 ASHAAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1184.5
1058.4
957.6
862.0
772.9
691.7
619.4
556.5
502.9
457.7
419.8
388.0
361.1
338.3
318.7
301.8
287.0
274.0

SP Power Systems Ltd

50
0.13
0.15
0.17
0.18
0.21
0.23
0.26
0.28
0.32
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.55
0.58

60
0.19
0.22
0.24
0.26
0.30
0.33
0.37
0.41
0.45
0.50
0.54
0.59
0.63
0.67
0.72
0.76
0.80
0.83

70
0.26
0.29
0.32
0.36
0.40
0.45
0.50
0.56
0.62
0.68
0.74
0.80
0.86
0.92
0.97
1.03
1.08
1.13

Page 69 of 212

80
0.34
0.38
0.42
0.47
0.52
0.59
0.65
0.73
0.81
0.89
0.97
1.05
1.12
1.20
1.27
1.34
1.41
1.48

Sag (m) for Span (m)


90
100
0.43
0.54
0.49
0.60
0.54
0.66
0.60
0.74
0.66
0.82
0.74
0.92
0.83
1.02
0.92
1.14
1.02
1.26
1.12
1.38
1.22
1.51
1.32
1.63
1.42
1.76
1.52
1.87
1.61
1.99
1.70
2.10
1.79
2.21
1.87
2.31

110
0.65
0.72
0.80
0.89
0.99
1.11
1.24
1.38
1.53
1.68
1.83
1.98
2.12
2.27
2.41
2.54
2.67
2.80

120
0.77
0.86
0.95
1.06
1.18
1.32
1.47
1.64
1.82
1.99
2.17
2.35
2.53
2.70
2.86
3.02
3.18
3.33

130
0.90
1.01
1.12
1.24
1.39
1.55
1.73
1.92
2.13
2.34
2.55
2.76
2.97
3.17
3.36
3.55
3.73
3.91

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 5-Maximum Angle of Deviation for Single Poles for 150mm2 ASHAAAC (Non Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/ 4.00mm
2 x 7/ 4.00mm
18
31
22
40
26
45
29
45

Table 6-Maximum Angle of Deviation for H Poles for 150mm2 ASH AAAC (Non Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


3 x 7/ 4.00mm
4 x 7/ 4.00mm
74
90
90
90
90
90
90
90

__________________________________________________________________________
Page 70 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 150mm2 ASHAAAC
(Non Severe Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1: 10

30
0
5
10
15
20
25
30
35
40
45
0
5
10
15
20
25
30
35
40
45

5894
7628
9355
11071
12774
14459
16124
17765
19380
20965
8180
9915
11641
13358
15060
16745
18410
20052
21667
23252

Stay Angle
35
40
Strut Load (kgf)
5456
5115
6886
6308
8310
7497
9725
8678
11128
9849
12518
11008
13891
12154
15244
13283
16576
14395
17883
15485
7743
7402
9172
8595
10596
9783
12011
10964
13415
12135
14805
13295
16177
14441
17531
15570
18862
16681
20170
17772

45
4839
5840
6837
7828
8811
9784
10745
11693
12625
13540
7126
8127
9124
10115
11097
12070
13032
13979
14912
15827

__________________________________________________________________________
Page 71 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 8-Strut Load in H Poles with Three Stays (kgf) for 150mm2 ASHAAAC (Non Severe
Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1: 10

30
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90

3313
4354
5390
6420
7441
8452
9451
10436
11405
12356
13288
14198
15085
15947
16782
17590
18368
19115
19830
4457
5497
6533
7563
8584
9595
10594
11579
12548
13499
14431
15341
16228
17090
17926
18733
19511
20258
20973

Stay Angle
35
40
Strut Load (kgf)
3030
2810
3888
3526
4742
4238
5591
4947
6433
5650
7267
6346
8091
7033
8903
7711
9702
8377
10486
9032
11254
9673
12005
10299
12736
10909
13447
11502
14136
12077
14802
12633
15443
13168
16059
13682
16649
14174
4173
3953
5031
4669
5886
5382
6735
6090
7577
6793
8411
7489
9234
8176
10046
8854
10845
9521
11629
10175
12398
10816
13148
11442
13879
12052
14590
12646
15279
13221
15945
13776
16587
14312
17203
14826
17792
15317

45
2631
3232
3830
4424
5014
5598
6175
6743
7303
7852
8390
8915
9427
9925
10407
10874
11323
11754
12167
3774
4375
4973
5568
6157
6741
7318
7887
8446
8995
9533
10058
10570
11068
11551
12017
12466
12898
13310

__________________________________________________________________________
Page 72 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table-9 Strut Load in H Pole Structures with Four Stays (kgf) for 150mm2 ASHAAAC
(Non Severe Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1: 10

0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90
0
5
10
15
20
25
30
35
40
45
50
55
60*
65
70
75
80
85
90

Stay Angle
35
40
Strut Load (kgf)

30
3044
3911
4775
5633
6484
7327
8159
8980
9787
10580
11356
12115
12854
13572
14269
14942
15590
16212
16808
4187
5055
5918
6776
7627
8470
9302
10123
10931
11723
12499
13258
13997
14715
15412
16085
16733
17356
17951

2808
3523
4235
4943
5644
6339
7026
7702
8368
9022
9662
10287
10896
11489
12063
12618
13153
13666
14157
3951
4666
5378
6086
6788
7482
8169
8846
9511
10165
10805
11430
12040
12632
13206
13761
14296
14809
15300

2625
3221
3815
4406
4991
5571
6144
6709
7264
7810
8344
8865
9374
9868
10348
10811
11257
11685
12095
3768
4364
4959
5549
6135
6714
7287
7852
8407
8953
9487
10009
10517
11012
11491
11954
12400
12828
13238

45
2476
2976
3475
3970
4462
4948
5429
5903
6369
6826
7274
7712
8139
8554
8956
9345
9719
10078
10422
3619
4120
4618
5113
5605
6091
6572
7046
7512
7970
8418
8856
9282
9697
10099
10488
10862
11222
11565

Note: * Denotes value for selection of Terminal pole at specified Gradient


__________________________________________________________________________
Page 73 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 10 Strut Loading in Single Pole Construction Terminals (kgf) for 150mm2 ASHAAAC
(Non Severe Weather Area)
LINE ANGLE
Level Conditions
Downpull 1: 10

Structure

Back Stay Angle (640)

Construction Terminal

9625

Construction Terminal

11496

__________________________________________________________________________
Page 74 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11-Stayed Pole Strut Capabilities for 150mm2 ASHAAAC (Non Severe Weather Area)
Pole
(m)
8.5
8.5
9
9
9.5
9.5
10
10
10
10.5
10.5
10.5
11
11
11
11.5
11.5
11.5
12
12
12
13
13
13
14
14
14
15
15
15
16
16
16

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
206
191
211
190
210
190
209
229
190
209
229
190
208
228
190
208
228
190
207
227
195
211
231
195
214
234
195
218
238
200
222
242

265
285
275
295
280
300
285
305
325
290
310
330
295
315
335
300
320
340
305
325
345
320
340
360
335
355
375
350
370
390
365
385
405

Taper (mm/m)
10.71
11.25
11.25
11.25
11.25
11.25
11.18
11.25
11.25
11.11
11.25
11.25
11.05
11.25
11.25
11.00
11.25
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25
11.48
11.25
11.25
11.38
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400

20881
28533
19310
27338
17206
24314
15581
21815
29943
14217
19725
27032
13060
17958
24572
12431
16956
23186
11527
15583
21276
10949
14461
19572
9973
13606
18262
9376
13212
17606
9192
12660
16744

__________________________________________________________________________
Page 75 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11 Stayed Pole Strut Capabilities for 150mm2 ASHAAAC (Non Severe Weather
Area) (cont.)
Pole
(m)
17
17
17
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
200
221
241
200
224
244
200
227
247
200
224
244

375
395
415
390
410
430
415
435
455
435
455
475

Taper (mm/m)
11.29
11.25
11.25
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2400
2400
2400
2800
2800
2800
2800
2800
2800
2800
2800
2800

8402
11388
15026
8175
11441
15010
7236
10258
13339
6404
8805
11401

__________________________________________________________________________
Page 76 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 150mm2 ASHAAAC (Non Severe Weather Area)
Pole Length (m)

8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

50

60

70

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

Maximum Wind Span Length (m)


80
90
100
Diameter of Pole 1.5m from Butt (mm)
265
265
285
275
275
295
280
280
300
285
285
305
290
290
310
295
295
315
300
300
320
305
305
325
320
320
340
335
335
355
350
350
350
365
365
365
375
375
375*
390
390
390
415
415
415
435
435
435

110

120

130

285*
295*
300*
305*
310*
315*
320*
325*
340*
355*
370*
385*
395*
410*
415*
455*

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

Note:- Pole sizes marked * shall have two blocks fitted

Pole Length (m)


8.5 -11.0 inc.
11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

Foundation Depth (m)


2.0
2.2
2.4
2.8

___________________________________________________________________________________________________________________
Page 77 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Appendix 4 33kV Non Severe Weather Area.200mm2 AAAC POPLAR Conductor (L33)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC

POPLAR
0.6812
239.4
20.09
0.000023
5700
7200
90
380
9.5
913
1897.2
-5.6
1368.2
5
1897.2
1.487
1.515
1276.0

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

65oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

3.5
2.5
3.0
3.5
3.0
2.5

____________________________________________________________________________
Page 78 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 1- Support Types and Duties Table for 200mm2 POPLARAAAC (Non Severe Weather Area)
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

100

1:10

00

90

1:5*

00

H Pole (Long Span)

130

1:10

00

SP4019155

Single Pole

110

1:10

00

SP4018548

H Pole

110

1:10

00

SP4019003

H Pole (Long Span)

130

1:10

00

SP2147486

H Pole (Delta)

100

1:5

00

SP2059611

Single Pole

110

1:10

300

SP4018548

H Pole

100

1:10

600

SP4019003

H Pole (Long Span)

130

1:10

100

SP2147486

H Pole

110

1:5

00

SP2147485

Structure Type
Single Pole
Intermediate

Straight Section

Angle Section

Terminal

Energy Networks
Drawing Reference
SP4018552

Note 1 * See 11.2.2 for guidance on hillside applications.

_____________________________________________________________________________________________________________________
Page 79 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2- Conductor Design Table for 200mm POPLARAAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1436.6
1276.0
1149.5
1031.6
924.1
828.4
745.0
673.8
613.7
563.1
520.7
484.8
454.2
428.0
405.3
385.5
368.1
352.6

50
0.15
0.17
0.19
0.21
0.23
0.26
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.55
0.58
0.60

60
0.21
0.24
0.27
0.30
0.33
0.37
0.41
0.45
0.50
0.54
0.59
0.63
0.67
0.72
0.76
0.80
0.83
0.87

70
0.29
0.33
0.36
0.40
0.45
0.50
0.56
0.62
0.68
0.74
0.80
0.86
0.92
0.97
1.03
1.08
1.13
1.18

80
0.38
0.43
0.47
0.53
0.59
0.66
0.73
0.81
0.89
0.97
1.05
1.12
1.20
1.27
1.34
1.41
1.48
1.55

Sag (m) for Span (m)


90
100
0.48
0.59
0.54
0.67
0.60
0.74
0.67
0.83
0.75
0.92
0.83
1.03
0.93
1.14
1.02
1.26
1.12
1.39
1.22
1.51
1.32
1.64
1.42
1.76
1.52
1.87
1.61
1.99
1.70
2.10
1.79
2.21
1.87
2.31
1.96
2.41

110
0.72
0.81
0.90
1.00
1.11
1.24
1.38
1.53
1.68
1.83
1.98
2.13
2.27
2.41
2.54
2.67
2.80
2.92

120
0.85
0.96
1.07
1.19
1.33
1.48
1.65
1.82
2.00
2.18
2.35
2.53
2.70
2.86
3.02
3.18
3.33
3.48

130
1.00
1.13
1.25
1.39
1.56
1.74
1.93
2.14
2.34
2.56
2.76
2.97
3.17
3.36
3.55
3.73
3.91
4.08

_____________________________________________________________________________________________________________________
Page 80 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 200mm2 POPLARAAAC (Non Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

50

60

70

80

90

100

110

120

130

1619 kgf

0.13

0.19

0.26

0.34

0.43

0.53

0.64

0.76

0.89

Sag (m) for Span (m)

Table 4- Conductor Erection Table for 200mm2 POPLARAAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1557.0
1390.9
1258.5
1133.1
1016.5
910.5
816.5
734.8
665.1
606.3
557.0
515.5
480.4
450.5
424.8
402.5
383.1
365.9

50
0.14
0.15
0.17
0.19
0.21
0.23
0.26
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.58

60
0.20
0.22
0.24
0.27
0.30
0.34
0.38
0.42
0.46
0.51
0.55
0.59
0.64
0.68
0.72
0.76
0.80
0.84

70
0.27
0.30
0.33
0.37
0.41
0.46
0.51
0.57
0.63
0.69
0.75
0.81
0.87
0.93
0.98
1.04
1.09
1.14

80
0.35
0.39
0.43
0.48
0.54
0.60
0.67
0.74
0.82
0.90
0.98
1.06
1.13
1.21
1.28
1.35
1.42
1.49

Sag (m) for Span (m)


90
0.44
0.50
0.55
0.61
0.68
0.76
0.84
0.94
1.04
1.14
1.24
1.34
1.44
1.53
1.62
1.71
1.80
1.88

100
0.55
0.61
0.68
0.75
0.84
0.94
1.04
1.16
1.28
1.40
1.53
1.65
1.77
1.89
2.00
2.12
2.22
2.33

110
0.66
0.74
0.82
0.91
1.01
1.13
1.26
1.40
1.55
1.70
1.85
2.00
2.14
2.29
2.43
2.56
2.69
2.82

120
0.79
0.88
0.97
1.08
1.21
1.35
1.50
1.67
1.84
2.02
2.20
2.38
2.55
2.72
2.89
3.05
3.20
3.35

130
0.92
1.03
1.14
1.27
1.42
1.58
1.76
1.96
2.16
2.37
2.58
2.79
3.00
3.19
3.39
3.58
3.76
3.93

_____________________________________________________________________________________________________________________
Page 81 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 5-Maximum Angle of Deviation for Single Poles for 200mm2 POPLARAAAC (Non
Severe Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/ 4.00mm
2 x 7/ 4.00mm
8
22
11
27
13
30
15
30

Table 6-Maximum Angle of Deviation for H Poles for 200mm2 POPLARAAAC (Non
Severe Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


3 x 7/ 4.00mm
4 x 7/ 4.00mm
38
53
45
60
52
60
59
60

__________________________________________________________________________
Page 82 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 200mm2 POPLARAAAC
(Non Severe Weather Area)
Stay Angle
LINE ANGLE

Level Conditions

Downpull 1: 10

30
0
5
10
15
20
25
30
35
0
5
10
15
20
25
30
35

5531
8108
10676
13229
15762
18271
20751
23197
8929
11506
14074
16627
19160
21669
24149
26595

35
40
Strut Load (kgf)
4993
4575
7118
6348
9235
8115
11340
9872
13429
11615
15498
13341
17543
15047
19559
16730
8391
7973
10516
9746
12633
11513
14739
13270
16827
15013
18896
16739
20941
18445
22957
20128

45
4236
5724
7206
8680
10143
11591
13023
14435
7634
9122
10604
12078
13541
14989
16421
17833

__________________________________________________________________________
Page 83 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 8-Strut Load in H Poles with Three Stays (kgf) for 200mm2 POPLARAAAC (Non
Severe Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

30
0
5
10
15
20
25
30
35
40
45
50
55
60
0
5
10
15
20
25
30
35
40
45
50
55
60

3212
4758
6299
7831
9351
10856
12344
13811
15256
16674
18064
19423
20748
4911
6457
7998
9530
11050
12555
14043
15510
16955
18373
19763
21122
22447

Stay Angle
35
40
Strut Load (kgf)
2865
2595
4140
3659
5410
4719
6673
5773
7926
6819
9168
7854
10394
8878
11604
9888
12795
10882
13965
11858
15111
12814
16231
13749
17324
14660
4564
4294
5839
5358
7109
6418
8372
7472
9625
8518
10867
9553
12093
10577
13303
11587
14494
12581
15664
13557
16810
14513
17930
15448
19023
16359

45
2376
3268
4158
5042
5920
6789
7648
8495
9329
10148
10951
11735
12500
4075
4967
5857
6741
7619
8488
9347
10194
11028
11847
12650
13434
14199

__________________________________________________________________________
Page 84 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table-9 Strut load in H Poles with Four Stays (kgf) for 200mm2 POPLARAAAC (Non
Severe Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

30

0
5
10
15
20
25
30
35
40
45
50
55
60*
0
5
10
15
20
25
30
35
40
45
50
55
60*

2882
4171
5455
6731
7998
9252
10492
11715
12919
14101
15259
16391
17495
4581
5870
7154
8430
9697
10951
12191
13414
14618
15800
16958
18090
19194

Stay Angle
35
40
Strut Load (kgf)
2593
2368
3655
3254
4714
4138
5766
5016
6811
5888
7845
6751
8868
7604
9876
8445
10868
9274
11843
10087
12798
10884
13732
11663
14642
12422
4292
4067
5354
4953
6413
5837
7465
6715
8510
7587
9544
8450
10567
9303
11575
10144
12567
10973
13542
11786
14497
12583
15431
13362
16341
14121

45
2185
2929
3670
4407
5139
5863
6579
7285
7980
8662
9331
9985
10622
3884
4628
5369
6106
6838
7562
8278
8984
9679
10361
11030
11684
12321

Note: * Denotes value for selection of Terminal pole

Table 10 Strut Loading in Single Pole Construction Terminals (kgf) for 200mm2
POPLARAAAC (Non Severe Weather Area)
LINE ANGLE
Level Conditions
Downpull 1: 10

Structure

Back Stay Angle (640)

Construction Terminal

11559 kgf

Construction Terminal

14957 kgf

__________________________________________________________________________
Page 85 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11-Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Non Severe Weather
Area)
Pole
(m)
8.5
8.5
8.5
9
9
9
9.5
9.5
9.5
10
10
10
10.5
10.5
10.5
11
11
11
11.5
11.5
11.5
12
12
12
13
13
13
14
14
14
15
15
15

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
206
226
191
211
231
190
210
230
190
209
229
190
209
229
190
208
228
190
208
228
190
207
227
195
211
231
195
214
234
195
218
238

265
285
305
275
295
315
280
300
320
285
305
325
290
310
330
295
315
335
300
320
340
305
325
345
320
340
360
335
355
375
350
370
390

Taper (mm/m)
10.71
11.25
11.25
11.25
11.25
11.25
11.25
11.25
11.25
11.18
11.25
11.25
11.11
11.25
11.25
11.05
11.25
11.25
11.00
11.25
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25
11.48
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400

20881
28533
39611
19310
27338
37642
17206
24314
33425
15581
21815
29943
14217
19725
27032
13060
17958
24572
12431
16956
23186
11527
15583
21276
10949
14461
19572
9973
13606
18262
9376
13212
17606

__________________________________________________________________________
Page 86 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11 Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Non Severe Weather
Area) (cont.)
Pole
(m)
16
16
16
17
17
17
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
200
222
242
200
221
241
200
224
244
200
227
247
200
224
244

365
385
405
375
395
415
390
410
430
415
435
455
435
455
475

Taper (mm/m)
11.38
11.25
11.25
11.29
11.25
11.25
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2400
2400
2400
2400
2400
2400
2800
2800
2800
2800
2800
2800
2800
2800
2800

9192
12660
16744
8402
11388
15026
8175
11441
15010
7236
10258
13339
6404
8805
11401

__________________________________________________________________________
Page 87 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 12-Pole Sizing for Intermediate and Section Poles for 200mm2 POPLARAAAC (Non Severe Weather Area)
Pole
Length
(m)
8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

50

60

70

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

Maximum Wind Span Length (m)


80
90
100
Diameter of Pole 1.5m from Butt (mm)
265
285
285
275
295
295*
280
300*
300*
285
305*
305*
290*
310*
310*
295*
315*
315*
300
320
340*
305
325
345*
320
340*
340*
335*
355*
355*
350
370
370*
365
365*
385*
375*
395*
395*
390
410*
410*
415
415*
435*
435
435*
455*

110

120

130

305*
315*
320*
325*
330*
335*
340*
345*
360*
375*
390*
385*
395*
410*
435*
455*

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

Note:- Pole sizes marked * shall have two ENATS 439103 Type 2 blocks fitted

Pole Length (m)


8.5 -11.0 inc.
11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

Foundation Depth (m)


2.0
2.2
2.4
2.8

____________________________________________________________________________________________________________________
Page 88 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Appendix 5 33kV Severe Weather Area 200mm2 AAAC POPLAR Conductor (L33)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC

POPLAR
0.6812
239.4
20.09
0.000023
5700
7200
80
380
9.5
913
2200.0
-5.6
1440
5
1897.2
1.487
1.515
1357.4

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

65oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

3.5
3.5
3.5
3.5
3.5
3.5

Page 89 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 1- Support Types and Duties Table for 200mm2 POPLARAAAC (Severe Weather Area)
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

Energy Networks
Drawing Reference

Single Pole

100

1:10

00

SP4018552

Single Pole

80

1:5*

00

SP4018552

H Pole (Long Span)

130

1:10

00

SP4019155

Single Pole

100

1:10

00

SP4018548

H Pole

130

1:10

00

SP4019003

H Pole (Long Span)

100

1:10

00

SP2147486

H Pole (Delta)

100

1:5

00

SP2059611

Single Pole

100

1:10

300

SP4018548

H Pole

130

1:10

600

SP4019003

H Pole (Long Span)

100

1:10

100

SP2147486

H Pole

100

1:5

00

SP2147485

Structure Type

Intermediate

Straight Section

Angle Section

Terminal

Note 1 * See 11.2.2 for guidance on hillside applications.

_____________________________________________________________________________________________________________________
Page 90 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2- Conductor Design Table for 200mm POPLAR AAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1512.7
1344.1
1209.2
1081.2
962.2
854.3
759.1
677.2
608.4
551.1
503.7
464.4
431.5
403.7
380.0
359.6
341.8
326.2

50
0.14
0.16
0.18
0.20
0.22
0.25
0.28
0.31
0.35
0.39
0.42
0.46
0.49
0.53
0.56
0.59
0.62
0.65

60
0.20
0.23
0.25
0.28
0.32
0.36
0.40
0.45
0.50
0.56
0.61
0.66
0.71
0.76
0.81
0.85
0.90
0.94

70
0.28
0.31
0.35
0.39
0.43
0.49
0.55
0.62
0.69
0.76
0.83
0.90
0.97
1.03
1.10
1.16
1.22
1.28

80
0.36
0.41
0.45
0.50
0.57
0.64
0.72
0.80
0.90
0.99
1.08
1.17
1.26
1.35
1.43
1.52
1.59
1.67

Sag (m) for Span (m)


90
100
0.46
0.56
0.51
0.63
0.57
0.70
0.64
0.79
0.72
0.88
0.81
1.00
0.91
1.12
1.02
1.26
1.13
1.40
1.25
1.55
1.37
1.69
1.49
1.83
1.60
1.97
1.71
2.11
1.82
2.24
1.92
2.37
2.02
2.49
2.11
2.61

110
0.68
0.77
0.85
0.95
1.07
1.21
1.36
1.52
1.69
1.87
2.05
2.22
2.39
2.55
2.71
2.87
3.01
3.16

120
0.81
0.91
1.01
1.13
1.27
1.44
1.62
1.81
2.02
2.22
2.43
2.64
2.84
3.04
3.23
3.41
3.59
3.76

130
0.95
1.07
1.19
1.33
1.50
1.68
1.90
2.12
2.37
2.61
2.86
3.10
3.34
3.56
3.79
4.00
4.21
4.41

_____________________________________________________________________________________________________________________
Page 91 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 200mm2 POPLARAAAC (Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

1695

Sag (m) for Span (m)


50
0.13

60
0.19

70
0.26

80
0.33

90
0.42

100
0.52

110
0.63

120
0.75

130
0.88

Table 4- Conductor Erection Table for 200mm2 POPLARAAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1630.3
1457.9
1318.7
1184.9
1058.4
941.3
835.7
742.9
663.5
596.9
541.7
495.9
457.8
426.0
399.0
376.0
356.1
338.8

50
0.13
0.15
0.16
0.18
0.20
0.23
0.25
0.29
0.32
0.36
0.39
0.43
0.46
0.50
0.53
0.57
0.60
0.63

60
0.19
0.21
0.23
0.26
0.29
0.33
0.37
0.41
0.46
0.51
0.57
0.62
0.67
0.72
0.77
0.82
0.86
0.90

70
0.26
0.29
0.32
0.35
0.39
0.44
0.50
0.56
0.63
0.70
0.77
0.84
0.91
0.98
1.05
1.11
1.17
1.23

80
0.33
0.37
0.41
0.46
0.51
0.58
0.65
0.73
0.82
0.91
1.01
1.10
1.19
1.28
1.37
1.45
1.53
1.61

Sag (m) for Span (m)


90
100
0.42
0.52
0.47
0.58
0.52
0.65
0.58
0.72
0.65
0.80
0.73
0.90
0.83
1.02
0.93
1.15
1.04
1.28
1.16
1.43
1.27
1.57
1.39
1.72
1.51
1.86
1.62
2.00
1.73
2.13
1.83
2.26
1.94
2.39
2.04
2.51

110
0.63
0.71
0.78
0.87
0.97
1.09
1.23
1.39
1.55
1.73
1.90
2.08
2.25
2.42
2.58
2.74
2.89
3.04

120
0.75
0.84
0.93
1.03
1.16
1.30
1.47
1.65
1.85
2.05
2.26
2.47
2.68
2.88
3.07
3.26
3.44
3.62

130
0.88
0.99
1.09
1.21
1.36
1.53
1.72
1.94
2.17
2.41
2.66
2.90
3.14
3.38
3.61
3.83
4.04
4.25

_____________________________________________________________________________________________________________________
Page 92 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 5-Maximum Angle of Deviation for Single Poles for 200mm2 POPLARAAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/ 4.00mm
2 x 7/ 4.00mm
9
26
11
30
14
30
16
30

Table 6-Maximum Angle of Deviation for H Poles for 200mm2 POPLARAAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


3 x 7/ 4.00mm
4 x 7/ 4.00mm
44
60
54
60
60
60
60
60

__________________________________________________________________________
Page 93 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 200mm2 POPLARAAAC
(Severe Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1:10

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
25
30
0
5
10
15
20
25
30

6683
9172
11650
14111
16551
18965
21348
9966
12456
14934
17395
19835
22249
24632

5923
7976
10019
12048
14060
16051
18016
9207
11260
13303
15332
17344
19334
21299

5332
7045
8750
10444
12122
13783
15423
8616
10329
12034
13727
15406
17067
18707

45

4853
6291
7721
9142
10551
11944
13321
8137
9574
11005
12426
13834
15228
16604

__________________________________________________________________________
Page 94 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 8-Strut Load in H Poles with Three Stays (kgf) for 200mm2 POPLARAAAC (Severe
Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
25
30
35
40
45
50
55
60
0
5
10
15
20
25
30
35
40
45
50
55
60

3949
5443
6930
8406
9870
11319
12749
14158
15543
16902
18232
19531
20795
5591
7085
8571
10048
11512
12960
14390
15800
17185
18544
19874
21173
22437

3463
4694
5920
7138
8345
9539
10718
11880
13022
14143
15240
16310
17353
5105
6336
7562
8780
9987
11181
12360
13522
14664
15785
16882
17952
18995

3084
4112
5135
6151
7158
8155
9139
10109
11062
11997
12912
13806
14676
4726
5754
6777
7793
8800
9797
10781
11750
12704
13639
14554
15447
16317

45

2778
3640
4498
5351
6196
7032
7858
8671
9471
10256
11024
11774
12504
4419
5282
6140
6993
7838
8674
9500
10313
11113
11898
12666
13415
14146

__________________________________________________________________________
Page 95 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 9-Strut Load in H Poles with Four Stays (kgf) for 200mm2POPLARAAAC (Severe
Weather Area)
LINE ANGLE

Stay Angle
35
40

30

45

Strut Load (kgf)

Level Conditions

Downpull 1: 10

0
5
10
15
20
25
30
35
40
45
50
55
60*
0
5
10
15
20
25
30
35
40
45
50
55
60*

3487
4732
5971
7201
8421
9628
10820
11994
13149
14281
15390
16472
17526
5129
6374
7613
8843
10063
11270
12462
13636
14791
15923
17031
18114
19168

3082
4108
5130
6144
7150
8146
9128
10096
11048
11982
12896
13788
14657
4724
5750
6772
7786
8792
9787
10770
11738
12690
13624
14538
15430
16299

2767
3623
4475
5322
6162
6992
7812
8620
9414
10194
10956
11701
12426
4408
5265
6117
6964
7803
8634
9454
10262
11056
11835
12598
13343
14068

2511
3230
3945
4655
5360
6056
6744
7422
8089
8743
9383
10008
10616
4153
4871
5587
6297
7001
7698
8386
9064
9731
10385
11025
11649
12258

Note: * Denotes value for selection of Terminal pole at specified Gradient

Table 10Strut Loading in Single Pole Construction Terminals (kgf) for 200mm2
POPLARAAAC (Severe Weather Area)
LINE ANGLE
Level Conditions
Downpull 1: 10

Structure

Back Stay Angle (640)

Construction Terminal

11479

Construction Terminal

14763

__________________________________________________________________________
Page 96 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11-Stayed Pole Strut Capabilities for 200mm2 POPLAR AAAC (Severe Weather Area)
Pole
(m)
8.5
8.5
8.5
9
9
9
9.5
9.5
9.5
10
10
10
10.5
10.5
10.5
11
11
11
11.5
11.5
11.5
12
12
12
13
13
13
14
14
14
15
15
15

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
206
226
190
211
231
190
210
230
189
209
229
190
209
234
190
213
233
190
208
238
190
212
237
195
211
241
195
214
234
195
218
238

265
285
305
275
295
315
280
300
320
285
305
325
290
310
335
295
320
340
300
320
350
305
330
355
320
340
370
335
355
375
350
370
390

Taper (mm/m)
10.71
11.25
11.25
11.33
11.25
11.25
11.25
11.25
11.25
11.25
11.25
11.25
11.11
11.25
11.25
11.05
11.25
11.25
11.00
11.25
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25
11.48
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2800
2800
2800

21937
29985
41670
20034
28609
39431
17917
25347
34878
16052
22666
31140
14715
20434
30221
13483
20120
27389
12817
17494
27769
11860
17385
25408
11227
14836
23197
10192
13919
18696
9755
13780
18392

__________________________________________________________________________
Page 97 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11Stayed Pole Strut Capabilities for 200mm2 POPLARAAAC (Severe Weather Area)
(cont.)
Pole
(m)
16
16
16
17
17
17
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
200
222
242
200
221
241
200
224
244
200
227
247
200
224
244

365
385
405
375
395
415
390
410
430
415
435
455
435
455
475

Taper (mm/m)
11.38
11.25
11.25
11.29
11.25
11.25
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2800
2800
2800
2800
2800
2800
3000
3000
3000
3000
3000
3000
3000
3000
3000

9528
13149
17417
8676
11782
15567
8298
11625
15262
7323
10394
13525
6468
8902
11533

__________________________________________________________________________
Page 98 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 12-Pole Sizing for Single Pole Intermediate and Section Poles for 200mm2 POPLARAAAC (Severe Weather Area)
Pole
Length (m)

50

60

70

8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

285
295
300
305
310
315
320
325
340
355
370
385
395
410
435
455

Maximum Wind Span Length (m)


80
90
100
Diameter of Pole 1.5m from Butt (mm)
285*
305*
305*
295*
315*
315*
300*
320*
320*
305*
325*
325*
310*
330*
330*
315*
335*
335*
320*
340*
340*
325*
345*
345*
340*
360*
360*
355*
375*
375*
370*
390*
390*
385*
405*
405*
395*
415*
415*
410*
430*
430*
435*
455*
455*
455*
475*
475*

110

120

130

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

Note:- Pole sizes marked * shall have two blocks fitted


Pole Length (m)

Foundation Depth (m)

8.5 -11.0 inc.


11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

2.2
2.4
2.8
3.0

____________________________________________________________________________________________________________________
Page 99 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Appendix 6 33kV Severe Weather Area 300mm2 AAAC UPAS Conductor (L35)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC
Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

UPAS
1.031
342.54
24.71
2.30E-05
5810
10348.1
80
380
9.5
913
2350.0
-5.6
2069.6
5
2350.0
1.963
1.694
1653.8
65oC

Factors of Safety
Unstayed Poles
Pole Foundations
Stayed Poles
Stays
Steelwork
Pin Insulators

3.5
3.5
3.5
3.5
3.5
3.5

Page 100 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 1- Support Types and Duties Table for 300mm2 UPASAAAC (Severe Weather Area)
Max Span Length
(m)

Max Gradient

Angle of Line
Deviation

100

1:10

00

80

1:5*

00

Single Pole

100

1:10

00

SP4018548

H Pole (Delta Long


Span)

130

1:10

00

SP2059372

H Pole (Delta)

80

1:5

00

SP2059611

Single Pole

100

1:10

220

SP4018548

H Pole

100

1:10

600

SP4019003

H Pole (Delta Long


Span)

110

1:10

100

SP2059372

H Pole

100

1:5

00

SP2147485

Structure Type
Intermediate

Straight Section

Angle Section

Terminal

Single Pole

Note 1 * See 11.2.2 for guidance on hillside applications.

Page 101 of 212

Energy Networks
Drawing Reference
SP4018552

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2- Conductor Design Table for 300mm UPASAAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1866.0
1653.9
1477.2
1315.7
1171.8
1046.9
940.7
851.8
777.9
716.3
664.7
621.1
584.0
552.1
524.3
500.0
478.5
459.3

50
0.17
0.19
0.22
0.24
0.27
0.31
0.34
0.38
0.41
0.45
0.48
0.52
0.55
0.58
0.61
0.64
0.67
0.70

60
0.25
0.28
0.31
0.35
0.40
0.44
0.49
0.54
0.60
0.65
0.70
0.75
0.79
0.84
0.88
0.93
0.97
1.01

70
0.34
0.38
0.43
0.48
0.54
0.60
0.67
0.74
0.81
0.88
0.95
1.02
1.08
1.14
1.20
1.26
1.32
1.37

80
0.44
0.50
0.56
0.63
0.70
0.79
0.88
0.97
1.06
1.15
1.24
1.33
1.41
1.49
1.57
1.65
1.72
1.80

Page 102 of 212

Sag (m) for Span (m)


90
100
0.56
0.69
0.63
0.78
0.71
0.87
0.79
0.98
0.89
1.10
1.00
1.23
1.11
1.37
1.23
1.51
1.34
1.66
1.46
1.80
1.57
1.94
1.68
2.07
1.79
2.21
1.89
2.33
1.99
2.46
2.09
2.58
2.18
2.69
2.27
2.81

110
0.84
0.94
1.06
1.19
1.33
1.49
1.66
1.83
2.00
2.18
2.35
2.51
2.67
2.82
2.97
3.12
3.26
3.39

120
0.99
1.12
1.26
1.41
1.58
1.77
1.97
2.18
2.39
2.59
2.79
2.99
3.18
3.36
3.54
3.71
3.88
4.04

130
1.17
1.32
1.47
1.66
1.86
2.08
2.32
2.56
2.80
3.04
3.28
3.51
3.73
3.95
4.15
4.36
4.55
4.74

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 300mm2 UPASAAAC (Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

1950

Sag (m) for Span (m)


50
0.17

60
0.24

70
0.32

80
0.42

90
0.54

100
0.66

110
0.80

120
0.95

130
1.12

Table 4- Conductor Erection Table for 300mm2 UPASAAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
2029.4
1808.6
1621.7
1447.6
1289.0
1148.4
1026.8
923.8
837.8
766.2
706.5
656.5
614.2
578.0
546.9
519.8
496.0
475.0

50
0.16
0.18
0.20
0.22
0.25
0.28
0.31
0.35
0.38
0.42
0.46
0.49
0.52
0.56
0.59
0.62
0.65
0.68

60
0.23
0.26
0.29
0.32
0.36
0.40
0.45
0.50
0.55
0.61
0.66
0.71
0.76
0.80
0.85
0.89
0.94
0.98

70
0.31
0.35
0.39
0.44
0.49
0.55
0.61
0.68
0.75
0.82
0.89
0.96
1.03
1.09
1.15
1.21
1.27
1.33

80
0.40
0.46
0.51
0.57
0.64
0.72
0.80
0.89
0.98
1.08
1.17
1.26
1.34
1.43
1.51
1.59
1.66
1.74

Page 103 of 212

Sag (m) for Span (m)


90
100
0.51
0.63
0.58
0.71
0.64
0.79
0.72
0.89
0.81
1.00
0.91
1.12
1.02
1.25
1.13
1.39
1.25
1.54
1.36
1.68
1.48
1.82
1.59
1.96
1.70
2.10
1.81
2.23
1.91
2.36
2.01
2.48
2.10
2.60
2.20
2.71

110
0.76
0.86
0.96
1.08
1.21
1.36
1.52
1.69
1.86
2.03
2.21
2.38
2.54
2.70
2.85
3.00
3.14
3.28

120
0.91
1.03
1.14
1.28
1.44
1.62
1.81
2.01
2.21
2.42
2.63
2.83
3.02
3.21
3.39
3.57
3.74
3.91

130
1.06
1.20
1.34
1.50
1.69
1.90
2.12
2.36
2.60
2.84
3.08
3.32
3.55
3.77
3.98
4.19
4.39
4.59

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 5-Maximum Angle of Deviation for Single Poles for 300mm2 UPASAAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


1 x 7/ 4.00mm
7
8
10
12

2 x 7/ 4.00mm
11
14
18
22

Table 6-Maximum Angle of Deviation for H Poles for 300mm2 UPASAAAC (Severe
Weather Area)
Angle of Stay
Slope
30
35
40
45

Grade 1150 Stay Wire


3 x 7/ 4.00mm
4 x 7/ 4.00mm
30
38
36
48
41
58
45
60

__________________________________________________________________________
Page 104 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 7-Strut Load in Single Poles with One or Two Stays (kgf) for 300mm2 UPASAAAC
(Severe Weather Area)
LINE ANGLE

Level Conditions

Downpull 1: 10

Stay Angle
35
40
Strut Load (kgf)

30

0
5
10
15
20
22
0
5
10
15
20
22

7360
11085
14797
18488
22151
23607
12270
15996
19707
23398
27062
28518

6670
9741
12802
15845
18866
20067
11580
14652
17712
20756
23776
24977

6133
8696
11250
13790
16310
17312
11044
13607
16161
18700
21221
22223

45

5698
7848
9991
12122
14238
15078
10608
12759
14902
17033
19148
19989

__________________________________________________________________________
Page 105 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 8-Strut Load in H Poles with Three Stays (kgf) for 300mm2 UPASAAAC (Severe
Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1: 10

0
5
10
15
20
25
30
35
40
45
0
5
10
15
20
25
30
35
40
45

Stay Angle
35
40
Strut Load (kgf)

30

3948
6184
8411
10627
12826
15005
17159
19285
21378
23434
6404
8639
10867
13082
15281
17460
19614
21740
23833
25889

3538
5381
7218
9045
10858
12655
14431
16184
17909
19605
5993
7837
9673
11500
13313
15110
16886
18639
20365
22060

3219
4757
6290
7814
9327
10827
12309
13771
15211
16626
5674
7212
8745
10269
11783
13282
14764
16227
17667
19082

45

2960
4251
5537
6816
8086
9344
10587
11815
13023
14210
5415
6706
7992
9271
10541
11799
13043
14270
15478
16665

__________________________________________________________________________
Page 106 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table-9 Strut Load in H Pole Structures with Four Stays (kgf) For 300mm2
UPASAAAC (Severe Weather Area)
LINE ANGLE

Level
Conditions

Downpull 1:10

0
5
10
15
20
25
30
35
40
45
50
55
60*
0
5
10
15
20
25
30
35
40
45
50
55
60*

Stay Angle
35
40
Strut Load (kgf)

30

3559
5421
7278
9124
10957
12772
14568
16339
18083
19797
21476
23119
24722
6014
7877
9733
11579
13412
15228
17023
18794
20538
22252
23932
25574
27177

3217
4753
6283
7806
9317
10814
12294
13755
15193
16606
17991
19345
20666
5672
7208
8739
10261
11772
13269
14749
16210
17648
19061
20446
21800
23122

2951
4233
5510
6780
8041
9291
10526
11745
12945
14124
15279
16410
17512
5406
6688
7965
9235
10496
11746
12981
14200
15400
16579
17735
18865
19967

45

2735
3811
4882
5948
7006
8055
9091
10114
11121
12110
13080
14028
14954
5190
6266
7338
8404
9462
10510
11546
12569
13576
14565
15535
16484
17409

Note: * Denotes value for selection of Terminal pole at specified gradient

Table 10Strut Loading in Single Pole Construction Terminals (kgf) for 300mm2
UPASAAAC (Severe Weather Area)
LINE ANGLE
Level Conditions
Downpull 1: 10

Structure

Back Stay Angle (650)

Construction Terminal

10411

Construction Terminal

15321

__________________________________________________________________________
Page 107 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11-Stayed Pole Strut Capabilities for 300mm2 UPASAAAC (Severe Weather Area)
Pole
(m)
8.5
8.5
8.5
9
9
9
9.5
9.5
9.5
10
10
10
10.5
10.5
10.5
11
11
11
11.5
11.5
11.5
12
12
12
13
13
13
14
14
14

Pole Top Dia. 1.5m


Dia. (mm) from Butt
190
206
226
190
211
231
190
210
230
190
209
229
190
209
229
190
208
228
190
208
228
190
207
227
195
211
231
195
214
234

265
285
305
275
295
315
280
300
320
285
305
325
290
310
330
295
315
335
300
320
340
305
325
345
320
340
360
335
355
375

Taper (mm/m)
10.71
11.25
11.25
11.33
11.25
11.25
11.25
11.25
11.25
11.18
11.25
11.25
11.11
11.25
11.25
11.05
11.25
11.25
11.00
11.25
11.25
10.95
11.25
11.25
10.87
11.25
11.25
11.20
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400

21937
29985
41670
20034
28609
39431
17917
25347
34878
16174
22666
31140
14715
20434
28030
13483
18555
25412
12817
17494
23944
11860
16042
21924
11227
14836
20096
10192
13919
18696

Note:- The minimum pole top diameter for single poles of angles in excess of 130 shall
be 215mm.
The minimum pole top diameter for H poles of angles in excess of 310 shall be
225mm.

__________________________________________________________________________
Page 108 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Table 11Stayed Pole Strut Capabilities for 300mm2 UPASAAAC (Severe Weather Area)
(cont.)
Pole
(m)
15
15
15
16
16
16
17
17
17
18
18
18
20
20
20
22
22
22

Pole Top Dia. 1.5m


Dia. (mm) from Butt
195
218
238
200
222
242
200
221
241
200
224
244
200
227
247
200
224
244

350
370
390
365
385
405
375
395
415
390
410
430
415
435
455
435
455
475

Taper (mm/m)
11.48
11.25
11.25
11.38
11.25
11.25
11.29
11.25
11.25
11.52
11.25
11.25
11.62
11.25
11.25
11.46
11.25
11.25

Planting
Pole Strut Strength
Depth (mm)
(kgf)
2800
2800
2800
2800
2800
2800
2800
2800
2800
3000
3000
3000
3000
3000
3000
3000
3000
3000

9755
13780
18392
9528
13149
17417
8676
11782
15567
8298
11625
15262
7323
10394
13525
6468
8902
11533

Note:- The minimum pole top diameter for single poles of angles in excess of 130 shall
be 215mm.
Note:- The minimum pole top diameter for H poles of angles in excess of 310 shall be
225mm.

__________________________________________________________________________
Page 109 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 12- Pole Sizing for Intermediate and section Poles for 300mm2 UPASAAAC (Severe Weather Area)
Pole Length
(m)

50

60

8.5
9
9.5
10
10.5
11
11.5
12
13
14
15
16
17
18
20
22

265
275
280
285
290
295
300
305
320
335
350
365
375
390
415
435

265
275
280
285
290
295
300
305
320
335*
350
365
375
390
415
435

Maximum Wind Span Length (m)


70
80
90
Diameter of Pole 1.5m from Butt (mm)
265
285*
285*
275
295*
295*
280*
300*
300*
285*
305*
325*
290*
310*
330*
315*
315*
335*
320*
320*
340*
325*
325*
345*
340*
340*
360*
335*
355*
2 x 335
350
370*
370*
365
365*
385*
375
395*
395*
390
390*
410*
415
415*
435*
435
435*
455*

100

115

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

2 x 265
2 x 275
2 x 280
2 x 285
2 x 290
2 x 295
2 x 300
2 x 305
2 x 320
2 x 335
2 x 350
2 x 365
2 x 375
2 x 390
2 x 415
2 x 435

Note:- Pole sizes marked * shall have two blocks fitted


Pole Length (m)

Foundation Depth (m)

8.5 -11.0 inc.


11.5 14.0 inc.
15.0 17.0 inc.
18.0 22.0 inc

2.2
2.4
2.8
3.0

____________________________________________________________________________________________________________________
Page 110 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Appendix 7 Installation requirements for Conductors incorporating Optical Fibres


13 INTRODUCTION
This Appendix has been prepared to provide a design for 33kV overhead lines suitable for
installation on the companies network, utilising optical fibre communication cores embedded
within the phase conductors.
The optical fibres are enclosed within two separate stainless steel tubes in a phase conductor.
This appendix is complementary to the equivalent standard conductor installation
requirements, and should be read in conjunction with it.
This appendix details the specific stringing requirements for: 200mm AAAC POPLAR Equivalent OPPC (L34)
300mm AAAC UPAS Equivalent OPPC (L36).
13.1

General

When compared to a standard overhead line construction, lines incorporating optical fibres
shall have the centre phase conductors substituted with an equivalent optical phase conductor
(OPPC).
All overhead line components and design parameters shall comply with the requirements of the
standard conductor as specified in the relevant appendix with the exception of those specified
in the following clauses.
There are specific installation techniques, which require to be employed when installing lines
incorporating optical fibres within the conductors; these are documented in Energy Networks
document OHL-18-022.
13.1.1

Optical Phase Conductors

The maximum working tension of an equivalent OPPC is designed to be the same as for a
standard AAAC conductor. However, due to the difference in physical construction of the
OPPC when compared with standard conductor, the maximum sag of the OPPC will be
marginally less than standard conductor, therefore the maximum design sag for the standard
conductor should be used when profiling as indicated in Table 2 of the relevant appendix.
13.1.2

Crossarms, Supports and Stays

As the loadings for the equivalent OPPC are almost identical to the standard conductor,
structure sizing, stay strength and their deployment, and Crossarm sizing shall all be as
detailed in the relevant standard conductor appendix.

____________________________________________________________________________
Page 111 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

13.2

OHL03-099
Issue 1

Materials

Except where otherwise specified, all materials used in the construction of lines to this
Appendix shall comply with current British Standards, ENA Technical Specifications and
international standards where appropriate. Only Energy Networks Approved materials shall be
used.
13.2.1

Optical Phase Conductors (OPPC)

The optical conductors physical and electrical parameters considered by this specification are
detailed in Energy Networks document OHL-03-96, each conductor shall incorporate two
stainless steel buffer tubes each containing a minimum of 12 single mode optical fibres.
13.2.2

Vibration Damper

As for standard 33kV line construction, no vibration dampers are normally required to be
employed on the OPPC.
13.2.3

Suspension Components

33kV polymeric post insulators and armour grip suspension clamps shall be used at all
intermediate insulator positions; the proposed suspension arrangements are not designed to
take any uplift load. Where the structure is deemed to be in uplift, the line should be sectioned
and tension support components employed in accordance with Section 11.1.

____________________________________________________________________________
Page 112 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

13.2.4

OHL03-099
Issue 1

UPAS Equivalent OPPC Tension String Components

From termination strap on the Crossarm, the following components are required for
termination of the OPPC:

____________________________________________________________________________
Page 113 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

13.2.5

OHL03-099
Issue 1

POPLAR Equivalent OPPC Tension String Components

From termination strap on the Crossarm, the following components are required for the OPPC:

____________________________________________________________________________
Page 114 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

13.3

OHL03-099
Issue 1

Optical Splice Enclosures

At OPPC in-line splice and terminal positions, only Energy Networks Approved fibre optic
splice enclosures may be installed. These fitting comprise of a rigid stand off composite
insulator and one or two fibre optic splice chambers where appropriate.
At Terminal positions these will be mounted on two H Pole Carry Over Channels as detailed in
Energy Networks Drawing Reference SP4008885 and secured using two transformer-clamping
plates as detailed in ENATS drawing reference 439529.
At in-line splice positions, on H Pole section structures the unit will be mounted on the
centre phase conductor section strap, on Single pole section structures the unit will be mounted
on the outside of the angle on the section crossarm this component shall be substituted for
items 11 & 13 of the general assembly drawings
They will be located on section and terminal structures as indicated on Energy Networks
drawing reference SP4019865.
In order to prevent damage to the stainless steel buffer tubes containing the Optical Fibres the
line conductor should be dressed directly from the dead end fitting directly to the splice
enclosures and should be installed in such a manner to ensure the minimum-bending radius of
the conductor is not compromised. Only Energy Networks Approved persons shall carryout the
splicing of the optical fibres.
13.3.1

Electrical Connections

At terminal positions where a load carrying electrical connection is required for example to a
cable termination these should be connected to the Splice enclosure jumper by one or two 3bolt parallel groove clamps. (See also general arrangement drawings and associated component
listings). Parallel Groove clamps should be used for all electrical connection associated with
the OPPC.
It is essential that all conductors are thoroughly cleaned using a suitable wire brush and a
Energy Networks approved conductive paste should be applied to the conductor prior to the
application of the parallel groove clamps; the clamps should be tightened with a suitable torque
wrench to the manufacturers recommended torque. Compression fittings must not be applied to
the OPPC conductor. At Splice Enclosures, the termination connecting rod should be cleaned
using 150-grade abrasive paper and an Energy Networks approved conductive paste should be
applied to the conductor and connecting rod prior to the application of the parallel groove
clamp(s).

____________________________________________________________________________
Page 115 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

13.4

OHL03-099
Issue 1

Earthing

As is normal practise all metalwork including Optical Splice Enclosures on all structures shall
be bonded and or earthed in accordance with Energy Networks document OHL-25-01.
A connection hole is provided on the base plate of the Optical Termination Unit to which the
earth-bonding lug should be connected.
13.5

Optical Fibre Cable Connections

The Fibre Optic underground cables shall secured every 500mm down the pole and protected
at the bottom of the pole by cable guards 3.0m long sunk 150mm into the ground
.

____________________________________________________________________________
Page 116 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

General Arrangement OPPC Splice Enclosures

____________________________________________________________________________
Page 117 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Poplar Equivalent Optical Conductor (Non Severe Weather Area) (L34)


Table 1 200mm2 AAAC Poplar Equivalent OPPC Conductor (Non Severe Weather Area)

Design Parameters
Conductor Code name

POPLAR OPPC

Greased Conductor Weight (kg/m)

0.678

Cross Sectional Area of Conductor (mm)

226.42

Conductor Overall Diameter (mm)

20.09

Coefficient of Linear Expansion (/Degree C)

0.000023

Modulus of Elasticity (kg/mm)

5700

Rated Breaking Strength of Conductor (kgf)

6808

Basic / Recommended Span (m)

90

Wind Pressure on Conductor (N/m)

380

Radial Ice Thickness (mm)

9.5

Ice Density (kg/m)

913

Absolute Maximum Working Tension (MWT) Limit (kgf)

1897.2

Temperature at MWT Limit (Degrees C)

-5.6

Maximum "Everyday" Tension (EDT) Limit (kgf)

1368.2

Temperature at EDT Limit (Degrees C)

5
o

Maximum Conductor Tension (MCT) (kgf) @ 5.6 C

1897.2

Maximum Conductor Weight (MCW) (kg/m)

1.484

Maximum Conductor Pressure (MCP) (kg/m)

1.515

Freezing Point Tension (FPT) (kgf) @ 0 C

1304.4

____________________________________________________________________________
Page 118 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2 Conductor Design Table for 200mm POPLAR Equivalent OPPC AAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1458.9
1304.4
1181.7
1066.1
959.1
862.3
776.6
702.2
638.7
584.8
539.3
500.8
468.1
440.0
415.7
394.6
376.1
359.7

50
0.15
0.16
0.18
0.20
0.22
0.25
0.27
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.51
0.54
0.56
0.59

60
0.21
0.23
0.26
0.29
0.32
0.35
0.39
0.43
0.48
0.52
0.57
0.61
0.65
0.69
0.73
0.77
0.81
0.85

70
0.28
0.32
0.35
0.39
0.43
0.48
0.53
0.59
0.65
0.71
0.77
0.83
0.89
0.94
1.00
1.05
1.10
1.15

Sag (m) for Span (m)


80
90
0.37
0.47
0.42
0.53
0.46
0.58
0.51
0.64
0.57
0.72
0.63
0.80
0.70
0.88
0.77
0.98
0.85
1.07
0.93
1.17
1.01
1.27
1.08
1.37
1.16
1.47
1.23
1.56
1.30
1.65
1.37
1.74
1.44
1.83
1.51
1.91

100
0.58
0.65
0.72
0.79
0.88
0.98
1.09
1.21
1.33
1.45
1.57
1.69
1.81
1.93
2.04
2.15
2.25
2.36

110
0.70
0.79
0.87
0.96
1.07
1.19
1.32
1.46
1.61
1.75
1.90
2.05
2.19
2.33
2.47
2.60
2.73
2.85

120
0.84
0.94
1.03
1.14
1.27
1.42
1.57
1.74
1.91
2.09
2.26
2.44
2.61
2.77
2.94
3.09
3.25
3.39

____________________________________________________________________________________________________________________
Page 119 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 200mm POPLAR Equivalent OPPC AAAC (Non Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

1642

50
0.13

60
0.19

70
0.25

Sag (m) for Span (m)


80
90
100
0.33
0.42
0.52

110
0.62

120
0.74

130
0.87

Table 4- Conductor Erection Table for 200mm POPLAR Equivalent OPPC AAAC (Non Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1578.8
1419.7
1291.9
1169.9
1055.0
949.0
853.3
768.7
695.5
632.9
579.9
535.2
497.3
465.1
437.4
413.5
392.7
374.4

50
0.13
0.15
0.16
0.18
0.20
0.22
0.25
0.28
0.30
0.33
0.37
0.40
0.43
0.46
0.48
0.51
0.54
0.57

60
0.19
0.21
0.24
0.26
0.29
0.32
0.36
0.40
0.44
0.48
0.53
0.57
0.61
0.66
0.70
0.74
0.78
0.81

70
0.26
0.29
0.32
0.35
0.39
0.44
0.49
0.54
0.60
0.66
0.72
0.78
0.84
0.89
0.95
1.00
1.06
1.11

Sag (m) for Span (m)


80
90
0.34
0.43
0.38
0.48
0.42
0.53
0.46
0.59
0.51
0.65
0.57
0.72
0.64
0.80
0.71
0.89
0.78
0.99
0.86
1.08
0.94
1.18
1.01
1.28
1.09
1.38
1.17
1.48
1.24
1.57
1.31
1.66
1.38
1.75
1.45
1.83

100
0.54
0.60
0.66
0.72
0.80
0.89
0.99
1.10
1.22
1.34
1.46
1.58
1.70
1.82
1.94
2.05
2.16
2.26

110
0.65
0.72
0.79
0.88
0.97
1.08
1.20
1.33
1.47
1.62
1.77
1.92
2.06
2.20
2.34
2.48
2.61
2.74

120
0.77
0.86
0.94
1.04
1.16
1.29
1.43
1.59
1.75
1.93
2.10
2.28
2.45
2.62
2.79
2.95
3.11
3.26

____________________________________________________________________________________________________________________
Page 120 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Poplar Equivalent Optical Conductor (Severe Weather Area) (L34)


Table 1 200mm2 AAAC Poplar Equivalent OPPC Conductor (Severe Weather Area)

Design Parameters
Conductor Code name

POPLAR OPPC

Greased Conductor Weight (kg/m)

0.678

Cross Sectional Area of Conductor (mm)

226.42

Conductor Overall Diameter (mm)

20.09

Coefficient of Linear Expansion (/Degree C)

0.000023

Modulus of Elasticity (kg/mm)

5700

Rated Breaking Strength of Conductor (kgf)

6808

Basic / Recommended Span (m)

80

Wind Pressure on Conductor (N/m)

380

Radial Ice Thickness (mm)

9.5

Ice Density (kg/m)

913

Absolute Maximum Working Tension (MWT) Limit (kgf)

1897.2

Temperature at MWT Limit (Degrees C)

-5.6

Maximum "Everyday" Tension (EDT) Limit (kgf)

1440

Temperature at EDT Limit (Degrees C)

5
o

Maximum Conductor Tension (MCT) (kgf) @ 5.6 C

1825.5

Maximum Conductor Weight (MCW) (kg/m)

1.484

Maximum Conductor Pressure (MCP) (kg/m)

1.515

Freezing Point Tension (FPT) (kgf) @ 0 C

1383.6

____________________________________________________________________________
Page 121 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2- Conductor Design Table for 200mm POPLAR Equivalent OPPC AAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1545.3
1383.6
1253.3
1128.4
1010.6
901.8
803.7
717.6
643.8
581.5
529.5
486.1
449.9
419.4
393.5
371.2
351.9
335.1

50
0.14
0.15
0.17
0.19
0.21
0.23
0.26
0.30
0.33
0.36
0.40
0.44
0.47
0.51
0.54
0.57
0.60
0.63

60
0.20
0.22
0.24
0.27
0.30
0.34
0.38
0.43
0.47
0.52
0.58
0.63
0.68
0.73
0.78
0.82
0.87
0.91

70
0.27
0.30
0.33
0.37
0.41
0.46
0.52
0.58
0.65
0.71
0.78
0.85
0.92
0.99
1.06
1.12
1.18
1.24

Sag (m) for Span (m)


80
90
0.35
0.44
0.39
0.50
0.43
0.55
0.48
0.61
0.54
0.68
0.60
0.76
0.67
0.85
0.76
0.96
0.84
1.07
0.93
1.18
1.02
1.30
1.12
1.41
1.21
1.53
1.29
1.64
1.38
1.74
1.46
1.85
1.54
1.95
1.62
2.05

100
0.55
0.61
0.68
0.75
0.84
0.94
1.05
1.18
1.32
1.46
1.60
1.74
1.88
2.02
2.15
2.28
2.41
2.53

110
0.66
0.74
0.82
0.91
1.01
1.14
1.28
1.43
1.59
1.76
1.94
2.11
2.28
2.45
2.61
2.76
2.91
3.06

120
0.79
0.88
0.97
1.08
1.21
1.35
1.52
1.70
1.90
2.10
2.30
2.51
2.71
2.91
3.10
3.29
3.47
3.64

___________________________________________________________________________________________________________________
Page 122 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 200mm POPLAR Equivalent OPPC AAAC (Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

1625

Sag (m) for Span (m)


50
0.13

60
0.19

70
0.26

80
0.33

90
0.42

100
0.52

110
0.63

120
0.75

130
0.88

Table 4- Conductor Erection Table for 200mm POPLAR Equivalent OPPC AAAC (Severe Weather Area)

Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1664.1
1499.3
1365.3
1235.7
1111.7
995.0
887.6
791.1
706.7
634.5
573.7
523.0
480.8
445.4
415.6
390.2
368.4
349.5

50
0.13
0.14
0.16
0.17
0.19
0.21
0.24
0.27
0.30
0.33
0.37
0.41
0.44
0.48
0.51
0.54
0.58
0.61

60
0.18
0.20
0.22
0.25
0.27
0.31
0.34
0.39
0.43
0.48
0.53
0.58
0.63
0.69
0.73
0.78
0.83
0.87

70
0.25
0.28
0.30
0.34
0.37
0.42
0.47
0.52
0.59
0.65
0.72
0.79
0.86
0.93
1.00
1.06
1.13
1.19

Sag (m) for Span (m)


80
90
0.33
0.41
0.36
0.46
0.40
0.50
0.44
0.56
0.49
0.62
0.55
0.69
0.61
0.77
0.69
0.87
0.77
0.97
0.85
1.08
0.95
1.20
1.04
1.31
1.13
1.43
1.22
1.54
1.31
1.65
1.39
1.76
1.47
1.86
1.55
1.96

100
0.51
0.57
0.62
0.69
0.76
0.85
0.95
1.07
1.20
1.34
1.48
1.62
1.76
1.90
2.04
2.17
2.30
2.43

110
0.62
0.68
0.75
0.83
0.92
1.03
1.16
1.30
1.45
1.62
1.79
1.96
2.13
2.30
2.47
2.63
2.78
2.93

120
0.73
0.81
0.89
0.99
1.10
1.23
1.37
1.54
1.73
1.92
2.13
2.33
2.54
2.74
2.94
3.13
3.31
3.49

___________________________________________________________________________________________________________________
Page 123 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

UPAS Equivalent optical conductor (Severe Weather Area) (L36)


Table 1 300mm2 AAAC UPAS Equivalent OPPC Conductor (Severe Weather Area)

Design Parameters
Conductor Code name

UPAS OPPC

Greased Conductor Weight (kg/m)

1.022

Cross Sectional Area of Conductor (mm)

342.54

Conductor Overall Diameter (mm)

24.71

Coefficient of Linear Expansion (/Degree C)

2.30E-05

Modulus of Elasticity (kg/mm)

5810

Rated Breaking Strength of Conductor (kgf)

10300.7

Basic / Recommended Span (m)

80

Wind Pressure on Conductor (N/m)

380

Radial Ice Thickness (mm)

9.5

Ice Density (kg/m)

913

Absolute Maximum Working Tension (MWT) Limit (kgf)

2350.0

Temperature at MWT Limit (Degrees C)

-5.6

Maximum "Everyday" Tension (EDT) Limit (kgf)

2060.1

Temperature at EDT Limit (Degrees C)

5
o

Maximum Conductor Tension (MCT) (kgf) @ 5.6 C

2350.0

Maximum Conductor Weight (MCW) (kg/m)

1.954

Maximum Conductor Pressure (MCP) (kg/m)

1.694

Freezing Point Tension (FPT) (kgf) @ 0 C

1653.7

____________________________________________________________________________
Page 124 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2 Conductor Design Table for 300mm UPAS Equivalent OPPC AAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1866.5
1653.7
1476.4
1314.2
1169.6
1044.1
937.4
848.2
774.1
712.4
660.8
617.2
580.2
548.3
520.6
496.4
475.0
455.9

50
0.17
0.19
0.22
0.24
0.27
0.31
0.34
0.38
0.41
0.45
0.48
0.52
0.55
0.58
0.61
0.64
0.67
0.70

60
0.25
0.28
0.31
0.35
0.39
0.44
0.49
0.54
0.59
0.65
0.70
0.75
0.79
0.84
0.88
0.93
0.97
1.01

70
0.34
0.38
0.42
0.48
0.54
0.60
0.67
0.74
0.81
0.88
0.95
1.01
1.08
1.14
1.20
1.26
1.32
1.37

Sag (m) for Span (m)


80
90
0.44
0.55
0.49
0.63
0.55
0.70
0.62
0.79
0.70
0.88
0.78
0.99
0.87
1.10
0.96
1.22
1.06
1.34
1.15
1.45
1.24
1.57
1.32
1.68
1.41
1.78
1.49
1.89
1.57
1.99
1.65
2.08
1.72
2.18
1.79
2.27

100
0.68
0.77
0.87
0.97
1.09
1.22
1.36
1.51
1.65
1.79
1.93
2.07
2.20
2.33
2.45
2.57
2.69
2.80

110
0.83
0.93
1.05
1.18
1.32
1.48
1.65
1.82
2.00
2.17
2.34
2.50
2.66
2.82
2.97
3.11
3.25
3.39

120
0.99
1.11
1.25
1.40
1.57
1.76
1.96
2.17
2.38
2.58
2.78
2.98
3.17
3.36
3.53
3.71
3.87
4.03

____________________________________________________________________________________________________________________
Page 125 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3- Conductor Pre-Tension Table for 300mm2 UPAS Equivalent OPPCAAAC (Severe Weather Area)
Pre-tension
at all temperatures
(Kgf)

2127

Sag (m) for Span (m)


50
0.15

60
0.22

70
0.29

80
0.38

90
0.49

100
0.60

110
0.73

120
0.86

130
1.01

Table 4- Conductor Erection Table for 300mm2 UPAS Equivalent OPPCAAAC (Severe Weather Area)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
2029.2
1807.9
1620.5
1445.8
1286.6
1145.4
1023.3
920.0
833.7
762.0
702.3
652.3
610.1
574.0
543.0
516.0
492.3
471.4

50
0.16
0.18
0.20
0.22
0.25
0.28
0.31
0.35
0.38
0.42
0.45
0.49
0.52
0.56
0.59
0.62
0.65
0.68

60
0.23
0.25
0.28
0.32
0.36
0.40
0.45
0.50
0.55
0.60
0.65
0.71
0.75
0.80
0.85
0.89
0.93
0.98

70
0.31
0.35
0.39
0.43
0.49
0.55
0.61
0.68
0.75
0.82
0.89
0.96
1.03
1.09
1.15
1.21
1.27
1.33

Sag (m) for Span (m)


80
90
0.40
0.51
0.45
0.57
0.50
0.64
0.57
0.72
0.64
0.80
0.71
0.90
0.80
1.01
0.89
1.12
0.98
1.24
1.07
1.36
1.16
1.47
1.25
1.59
1.34
1.70
1.42
1.80
1.51
1.91
1.58
2.01
1.66
2.10
1.73
2.20

100
0.63
0.71
0.79
0.88
0.99
1.12
1.25
1.39
1.53
1.68
1.82
1.96
2.09
2.23
2.35
2.48
2.59
2.71

110
0.76
0.86
0.95
1.07
1.20
1.35
1.51
1.68
1.85
2.03
2.20
2.37
2.53
2.69
2.85
3.00
3.14
3.28

120
0.91
1.02
1.14
1.27
1.43
1.61
1.80
2.00
2.21
2.41
2.62
2.82
3.02
3.20
3.39
3.57
3.74
3.90

____________________________________________________________________________________________________________________
Page 126 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Appendix 8 Installation Requirements for Horse OPGW


This Appendix has been prepared to provide a design for a OPGW conductor to replace the
existing Hardex communication network on existing 33kV overhead lines structures
This appendix details the specific stringing requirements for a 70mm ACSR Horse Equivalent
OPGW
14 General
Where there is a requirement to modernise the existing Hardex communication network an
Optical Ground wire may be employed in accordance with the following requirements.
There are specific installation techniques, which require to be employed when installing
conductors incorporating optical fibres; these are documented in Energy Networks document
OHL-18-022.
14.1.1

Optical Ground Wire

The maximum working tension of an equivalent OPGW is designed to be the same as for a
standard AACSR conductor. However, due to the difference in physical construction of the
OPGW when compared with standard conductor, the maximum sag of the OPGW will be
marginally less than standard conductor, therefore the maximum design sag for the OPGW
conductor may be used when profiling as indicated in Table 2 of this Appendix.
See Section 12.13.1 for guidance on minimum height of conductors.
Note:- Land usage may have changed since the original line was profiled and obstacles may
have been erected which could infringe on the basic requirements set out in section 11.13.1
therefore it is recommended this is given full consideration.
14.1.2

Supports and Stays

As the loadings for the OPGW are not significantly greater than the Hardex Communication
cable there are no requirements to alter existing structures.

____________________________________________________________________________
Page 127 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

14.2

OHL03-099
Issue 1

Materials

Except where otherwise specified, all materials used in the construction of lines to this
Appendix shall comply with current British Standards, ENA Technical Specifications and
international standards where appropriate. Only Energy Networks Approved materials shall be
used.
14.2.1

Optical Ground Wire (OPGW)

The optical Ground Wire considered by this Appendix is detailed in Energy Networks
document OHL-03-96; each conductor shall incorporate two stainless steel buffer tubes each
containing a minimum of 12 single mode optical fibres.
14.2.2

Vibration Damper

No vibration dampers are normally required to be employed on the OPGW


.
14.2.3

Suspension Components

The OPGW shall be supported at all intermediate positions using a standard pole outrigger
bracket (ENATS Drawing Reference 431403) in conjunction with a galvanised steel
suspension link connected to an Armour Grip Suspension Clamp.
The pole bolt securing the outrigger bracket should be positioned 225mm above the profiled
OPGW position to allow for the suspension components.
The proposed suspension arrangements are not designed to take any uplift load. Where the
structure is deemed to be in uplift, the line should be sectioned and tension support
components employed in accordance with Section 12.1.

____________________________________________________________________________
Page 128 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

14.2.4

OHL03-099
Issue 1

Horse Equivalent Tension String Components

From the BS3288 Ref 14/88 eyebolt on the structure the following components are required for
termination of the OPGW:
1.
2.
3.
4.
5.
6.

Ball/ Hook (BS Ref. 15/ 32).


Socket/ clevis (BS Ref.15/ 84).
Single Link (length 400mm)
Thimble/clevis (BS Ref. 15/86)
Protection Rods
Helical dead-end

Items 4 - 7 are generally supplied in a kit.


Item
1
2
3
4

Part name

Q'ty
1
1
1
1

Protection rods
Dead end
Thimble
400 mm Link

Load Rating
70 kN
70 kN
100 kN
70 kN

1
2

Cable

____________________________________________________________________________
Page 129 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

14.2.5

OHL03-099
Issue 1

Connection to Splice Enclosures

At OPGW intermediate and terminal splice positions an optical fibre splice enclosure is
required to facilitate the splicing of the optical fibres.
The optical splice enclosure shall be fixed above anti climber level and secured using two
10mm x 75mm galvanised coach bolts.
At terminal positions the Fibre Optic underground cables shall be secured every 500mm down
the pole and protected at the bottom of the pole by cable guards 3.0m long sunk 150mm into
the ground.
14.3

Conductor Design/Erection Sags and Tensions

Conductor design Sags and tension are given in Tables 2 & 3 of this appendix. The original
lines incorporating Hardex Communications cables were profiled using a Wolf Sag
template (normally 500C) The design sag of the Horse OPGW replacement at an Assumed
maximum ambient temperature of 450C whilst greater than the Hardex is equal to or slightly
less than the Wolf Profile used when the line was originally planned and hence the Horse
OPGW may be strung as a direct replacement for the Hardex communications cable.
The erection tensions given in Tables 3 of this appendix are based on the conductor design
tension, but have been subjected to an over tension equivalent to a -130C temperature shift to
allow for bedding in of the strands and long term creep of the conductor during the life of the
line. No pre-tensioning or other adjustments is necessary during the erection of the line

____________________________________________________________________________
Page 130 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

14.4

OHL03-099
Issue 1

Location of OPGW Attachment Points on Structures.

The Attachment positions for OPGW on all structures will be as follows:14.4.1

Straight Section, Intermediate and Pin Angle Structures

The Outrigger Bracket (ENATS Drawing Reference 431403) shall be installed


1365mm below phase conductors for spans up to 107m.
1675mm below phase conductors for spans up to 152m.
14.4.2

Angle Section and Terminal Structures

The Eye Bolt (ENATS Drawing Reference 439603) shall be installed


1520mm below phase conductors for spans up to 107m.
1830mm below phase conductors for spans up to 152m
14.5

Bonding and Earthing of OPGW and Components

As is common with all metalwork on structures constructed to this specification At Optical


Splice enclosure positions the splice enclosure will be required to be bonded in accordance
with section 12.16.
The OPGW shall also be bonded to all steelwork on the structure in addition it shall be earthed
at intervals of approximately 400m in accordance with section 11.16.

____________________________________________________________________________
Page 131 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Horse Equivalent OPGW Conductor (80m basic span)


Table 1 70mm2 AACSR Horse Equivalent OPGW Conductor (80m basic span)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC

Horse OPGW
0.445
103.93
13.95
0.0000177
9177
5948
80
380
9.5
913
1217.6
-5.6
1189.0
5
1217.6
1.084
1.277
742.4

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

450C

____________________________________________________________________________
Page 132 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2 Conductor Design table for 70mm HORSE Equivalent OPGW AACSR (80m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
812.6
735.0
669.6
608.8
553.1
503.1
458.9
420.3
387.1
358.5
333.9
312.7
294.4
278.4
264.5
252.2
241.2
231.4

80
0.44
0.48
0.53
0.58
0.64
0.71
0.78
0.85
0.92
0.99
1.07
1.14
1.21
1.28
1.35
1.41
1.48
1.54

90
0.55
0.61
0.67
0.74
0.81
0.90
0.98
1.07
1.16
1.26
1.35
1.44
1.53
1.62
1.70
1.79
1.87
1.95

100
0.68
0.76
0.83
0.91
1.01
1.11
1.21
1.32
1.44
1.55
1.67
1.78
1.89
2.00
2.10
2.21
2.31
2.40

Sag (m) for Span (m)


110
120
0.83
0.99
0.92
1.09
1.01
1.20
1.11
1.32
1.22
1.45
1.34
1.59
1.47
1.75
1.60
1.91
1.74
2.07
1.88
2.23
2.02
2.40
2.15
2.56
2.29
2.72
2.42
2.88
2.54
3.03
2.67
3.18
2.79
3.32
2.91
3.46

130
1.16
1.28
1.40
1.54
1.70
1.87
2.05
2.24
2.43
2.62
2.82
3.01
3.19
3.38
3.55
3.73
3.90
4.06

140
1.34
1.48
1.63
1.79
1.97
2.17
2.38
2.59
2.82
3.04
3.27
3.49
3.70
3.92
4.12
4.32
4.52
4.71

150
1.54
1.70
1.87
2.06
2.26
2.49
2.73
2.98
3.23
3.49
3.75
4.00
4.25
4.49
4.73
4.96
5.19
5.41

____________________________________________________________________________________________________________________
Page 133 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (80m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
1009.3
925.7
853.1
783.1
716.1
652.8
594.1
540.5
492.4
449.9
412.8
380.8
353.3
329.5
309.1
291.3
275.8
262.2

80
0.35
0.38
0.42
0.45
0.50
0.55
0.60
0.66
0.72
0.79
0.86
0.93
1.01
1.08
1.15
1.22
1.29
1.36

90
0.45
0.49
0.53
0.58
0.63
0.69
0.76
0.83
0.92
1.00
1.09
1.18
1.28
1.37
1.46
1.55
1.63
1.72

100
0.55
0.60
0.65
0.71
0.78
0.85
0.94
1.03
1.13
1.24
1.35
1.46
1.57
1.69
1.80
1.91
2.02
2.12

Sag (m) for Span (m)


110
120
0.67
0.79
0.73
0.87
0.79
0.94
0.86
1.02
0.94
1.12
1.03
1.23
1.13
1.35
1.25
1.48
1.37
1.63
1.50
1.78
1.63
1.94
1.77
2.10
1.91
2.27
2.04
2.43
2.18
2.59
2.31
2.75
2.44
2.90
2.57
3.06

130
0.93
1.02
1.10
1.20
1.31
1.44
1.58
1.74
1.91
2.09
2.28
2.47
2.66
2.85
3.04
3.23
3.41
3.59

140
1.08
1.18
1.28
1.39
1.52
1.67
1.84
2.02
2.21
2.42
2.64
2.86
3.09
3.31
3.53
3.74
3.95
4.16

150
1.24
1.35
1.47
1.60
1.75
1.92
2.11
2.32
2.54
2.78
3.03
3.29
3.54
3.80
4.05
4.30
4.54
4.77

____________________________________________________________________________________________________________________
Page 134 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Horse EQUIVALENT OPGW Conductor (100m basic span)


Table 1 70mm2 ACSR Horse Equivalent OPGW Conductor (100m basic span)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC

Horse OPGW
0.445
103.93
13.95
0.0000177
9000
5945.0
100
380
9.5
913
1253.6
-5.6
1189.0
5
1253.6
1.084
1.277
648.7

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

45oC

____________________________________________________________________________
Page 135 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2 Conductor Design Table for 70mm HORSE Equivalent OPGW AACSR (100m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
710.8
648.7
598.2
552.5
511.7
475.5
443.6
415.6
390.9
369.2
350.1
333.1
318.0
304.5
292.3
281.4
271.4
262.3

80
0.50
0.55
0.60
0.64
0.70
0.75
0.80
0.86
0.91
0.96
1.02
1.07
1.12
1.17
1.22
1.27
1.31
1.36

90
0.63
0.69
0.75
0.82
0.88
0.95
1.02
1.08
1.15
1.22
1.29
1.35
1.42
1.48
1.54
1.60
1.66
1.72

100
0.78
0.86
0.93
1.01
1.09
1.17
1.25
1.34
1.42
1.51
1.59
1.67
1.75
1.83
1.90
1.98
2.05
2.12

Sag (m) for Span (m)


110
120
0.95
1.13
1.04
1.23
1.13
1.34
1.22
1.45
1.32
1.57
1.42
1.68
1.52
1.81
1.62
1.93
1.72
2.05
1.82
2.17
1.92
2.29
2.02
2.40
2.12
2.52
2.21
2.63
2.30
2.74
2.39
2.85
2.48
2.95
2.57
3.05

130
1.32
1.45
1.57
1.70
1.84
1.98
2.12
2.26
2.40
2.55
2.69
2.82
2.96
3.09
3.22
3.34
3.46
3.58

140
1.53
1.68
1.82
1.97
2.13
2.29
2.46
2.62
2.79
2.95
3.11
3.27
3.43
3.58
3.73
3.88
4.02
4.16

150
1.76
1.93
2.09
2.27
2.45
2.63
2.82
3.01
3.20
3.39
3.58
3.76
3.94
4.11
4.28
4.45
4.61
4.77

____________________________________________________________________________________________________________________
Page 136 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (100m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
874.2
800.9
739.0
681.3
627.9
579.3
535.6
496.7
462.3
431.9
405.3
381.9
361.3
343.0
326.8
312.4
299.5
287.8

80
0.41
0.44
0.48
0.52
0.57
0.61
0.66
0.72
0.77
0.82
0.88
0.93
0.99
1.04
1.09
1.14
1.19
1.24

90
0.52
0.56
0.61
0.66
0.72
0.78
0.84
0.91
0.97
1.04
1.11
1.18
1.25
1.31
1.38
1.44
1.50
1.57

100
0.64
0.69
0.75
0.82
0.89
0.96
1.04
1.12
1.20
1.29
1.37
1.46
1.54
1.62
1.70
1.78
1.86
1.93

Sag (m) for Span (m)


110
120
0.77
0.92
0.84
1.00
0.91
1.08
0.99
1.18
1.07
1.28
1.16
1.38
1.26
1.50
1.36
1.61
1.46
1.73
1.56
1.85
1.66
1.98
1.76
2.10
1.86
2.22
1.96
2.34
2.06
2.45
2.15
2.56
2.25
2.67
2.34
2.78

130
1.08
1.17
1.27
1.38
1.50
1.62
1.76
1.89
2.03
2.18
2.32
2.46
2.60
2.74
2.88
3.01
3.14
3.27

140
1.25
1.36
1.48
1.60
1.74
1.88
2.04
2.20
2.36
2.52
2.69
2.85
3.02
3.18
3.34
3.49
3.64
3.79

150
1.43
1.56
1.69
1.84
1.99
2.16
2.34
2.52
2.71
2.90
3.09
3.28
3.46
3.65
3.83
4.01
4.18
4.35

____________________________________________________________________________________________________________________
Page 137 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead


Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Horse Equivalent OPGW Conductor (120m basic span)


Table 1 70mm2 AACSR Horse Equivalent OPGW Conductor (120m basic span)

Design Parameters
Conductor Code name
Greased Conductor Weight (kg/m)
Cross Sectional Area of Conductor (mm)
Conductor Overall Diameter (mm)
Coefficient of Linear Expansion (/Degree C)
Modulus of Elasticity (kg/mm)
Rated Breaking Strength of Conductor (kgf)
Basic / Recommended Span (m)
Wind Pressure on Conductor (N/m)
Radial Ice Thickness (mm)
Ice Density (kg/m)
Absolute Maximum Working Tension (MWT) Limit (kgf)
Temperature at MWT Limit (Degrees C)
Maximum "Everyday" Tension (EDT) Limit (kgf)
Temperature at EDT Limit (Degrees C)
Maximum Conductor Tension (MCT) (kgf) @ 5.6oC
Maximum Conductor Weight (MCW) (kg/m)
Maximum Conductor Pressure (MCP) (kg/m)
Freezing Point Tension (FPT) (kgf) @ 0oC

Horse OPGW
0.445
103.93
13.95
0.0000177
9000
5945.0
120
380
9.5
913
1284.7
-5.6
1189.0
5
1284.7
1.084
1.277
574.7

Design Temperature
Maximum Conductor Temperature For Assessing Ground Clearances

45oC

____________________________________________________________________________
Page 138 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 2 Conductor Design Table for 70mm HORSE Equivalent OPGW AACSR (120m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
620.0
574.7
538.6
506.3
477.4
451.7
428.8
408.3
389.9
373.3
358.4
344.9
332.5
321.3
311.0
301.5
292.8
284.7

80
0.57
0.62
0.66
0.70
0.75
0.79
0.83
0.87
0.91
0.95
0.99
1.03
1.07
1.11
1.14
1.18
1.22
1.25

90
0.73
0.78
0.84
0.89
0.94
1.00
1.05
1.10
1.16
1.21
1.26
1.31
1.35
1.40
1.45
1.49
1.54
1.58

100
0.90
0.97
1.03
1.10
1.17
1.23
1.30
1.36
1.43
1.49
1.55
1.61
1.67
1.73
1.79
1.84
1.90
1.95

Sag (m) for Span (m)


110
120
1.09
1.29
1.17
1.39
1.25
1.49
1.33
1.58
1.41
1.68
1.49
1.77
1.57
1.87
1.65
1.96
1.73
2.05
1.80
2.15
1.88
2.23
1.95
2.32
2.02
2.41
2.09
2.49
2.16
2.58
2.23
2.66
2.30
2.74
2.36
2.81

130
1.52
1.64
1.75
1.86
1.97
2.08
2.19
2.30
2.41
2.52
2.62
2.73
2.83
2.93
3.02
3.12
3.21
3.30

140
1.76
1.90
2.02
2.15
2.28
2.41
2.54
2.67
2.80
2.92
3.04
3.16
3.28
3.39
3.51
3.62
3.72
3.83

150
2.02
2.18
2.32
2.47
2.62
2.77
2.92
3.07
3.21
3.35
3.49
3.63
3.76
3.90
4.02
4.15
4.27
4.40

____________________________________________________________________________________________________________________
Page 139 of 212

Uncontrolled Copy

Specification for 11kV And 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

Table 3 Conductor Erection Table for 70mm HORSE Equivalent OPGW AACSR (120m Basic Span)
Temp.
(Deg. C)
-6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80

Tension
(Kgf)
745.9
688.1
641.1
598.3
559.8
525.2
494.3
466.8
442.2
420.3
400.7
383.0
367.2
352.8
339.8
327.9
317.1
307.1

80
0.48
0.52
0.56
0.60
0.64
0.68
0.72
0.76
0.81
0.85
0.89
0.93
0.97
1.01
1.05
1.09
1.12
1.16

90
0.60
0.65
0.70
0.75
0.80
0.86
0.91
0.97
1.02
1.07
1.12
1.18
1.23
1.28
1.33
1.37
1.42
1.47

100
0.75
0.81
0.87
0.93
0.99
1.06
1.13
1.19
1.26
1.32
1.39
1.45
1.51
1.58
1.64
1.70
1.75
1.81

Sag (m) for Span (m)


110
120
0.90
1.07
0.98
1.16
1.05
1.25
1.12
1.34
1.20
1.43
1.28
1.53
1.36
1.62
1.44
1.72
1.52
1.81
1.60
1.91
1.68
2.00
1.76
2.09
1.83
2.18
1.91
2.27
1.98
2.36
2.05
2.44
2.12
2.53
2.19
2.61

130
1.26
1.37
1.47
1.57
1.68
1.79
1.90
2.01
2.13
2.24
2.35
2.45
2.56
2.66
2.77
2.87
2.96
3.06

140
1.46
1.58
1.70
1.82
1.95
2.08
2.21
2.34
2.47
2.59
2.72
2.85
2.97
3.09
3.21
3.32
3.44
3.55

150
1.68
1.82
1.95
2.09
2.24
2.38
2.53
2.68
2.83
2.98
3.12
3.27
3.41
3.55
3.68
3.82
3.95
4.08

____________________________________________________________________________________________________________________
Page 140 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Drawings and Component Listings


Drawing.

Page No.

Figure 1 11Kv Single Pole Member Drilling, Scarfing and Marking............................................................................. 144
Figure 2 11Kv H Pole Member Drilling, Scarfing and Marking..................................................................................... 145
Figure 3 33Kv Light Construction Single Pole Member Drilling, Scarfing and Marking ........................................ 146
Figure 4 33Kv Light Construction H Pole Member Drilling, Scarfing and Marking ................................................ 147
Figure 5 33Kv Heavy Construction Single Pole Member Drilling, Scarfing and Marking ...................................... 148
Figure 6 33Kv Heavy Construction H Pole Member Drilling, Scarfing and Marking .............................................. 149
Figure 7 Delta H Pole Drilling Scarfing and Marking ....................................................................................................... 150
Figure 8 Single Pole Intermediate or Pin Angle (Drawing SP2147473) ........................................................................ 151
Figure 9 Single Pole Intermediate or Pin Angle (Drawing SP4018552) ........................................................................ 153
Figure 10 H Pole Intermediate Long Span (Drawing SP4019155) ............................................................................. 155
Figure 11 Single Pole Straight Line or Angle Section (Drawing SP2147476) .............................................................. 157
Figure 12 Single Pole Straight Line or Angle Section (Drawing SP4018548)........................................................................... 159
Figure 13 H Pole Straight Line or Angle Section (Drawing SP4019003) .............................................................................. 161
Figure 14 Long Span H Pole Straight Line or Angle Section (Drawing SP2147486)........................................................... 163
Figure 15 Delta H Pole Section or Section Angle (Drawing SP2059611) .............................................................................. 165
Figure 16 Delta Long Span H Pole Section or Section Angle (Drawing SP2059372) ........................................................... 167
Figure 17 Single Pole Terminal (Drawing SP2147474)............................................................................................................... 169
Figure 18 H Pole Terminal (Drawing 2147485)....................................................................................................................... 171
Figure 19 Single Pole Double Terminal (Drawing SP4000578) ................................................................................................. 173
Figure 20 General Arrangement Intermediate Crossarm (Drawing SP4018402).................................................................... 175
Figure 21 General Arrangement Section Crossarm (Drawing SP4018433) ............................................................................. 176
Figure 22 General Arrangement Terminal Crossarm (Drawing SP4018401).......................................................................... 177
Figure 23 General Arrangement Long Span Crossarm (Drawing SP4017663) ....................................................................... 178

___________________________________________________________________________
SP Power Systems Ltd

Page 141 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 24 General Arrangement Crossarm Strut (Drawing SP4017649) ................................................................................. 179


Figure 25 General Arrangement Long Crossarm Strut (Drawing SP4017635) ....................................................................... 180
Figure 26 General Arrangement Long Span Delta Crossarm Strut (Drawing SP2143987).................................................... 181
Figure 27 General Arrangement Terminal Strap (Drawing SP4017664) ................................................................................. 182
Figure 28 General Arrangement Section Strap (Drawing SP4017666)..................................................................................... 183
Figure 29 General Arrangement Insulator Bracket (Drawing SP4018449) ............................................................................. 184
Figure 30 General Arrangement Insulator Plate (Drawing SP4017637) .................................................................................. 185
Figure 31 General Arrangement Foundation Brace Steelwork H Pole 1830mm Centres (Drawing 4017651).................. 186
Figure 32 General Arrangement Foundation Brace Steelwork H Pole 2500mm Centres (Drawing SP4017652) ............. 187
Figure 33 General Arrangement Stay and Foundation Blocks (Drawing SP4019020)............................................................ 188
Figure 34 General Arrangement Wood Brace Block Type 1 H Pole 1830mm Centres (Drawing SP4019036) ................. 189
Figure 35 General Arrangement Wood Brace Block Type 2 H Pole 2500mm Centres (Drawing SP4019037) ................. 190
Figure 36 General Arrangement H Pole Carryover Support Steelwork (Drawing SP4008885)......................................... 191
Figure 37 General Arrangement H Pole Cable Cleat / Coffin Support Steelwork (Drawing SP2143955)......................... 192
Figure 38 General Arrangement H Pole Crucifix Support Steelwork (Drawing SP2143957) ............................................ 193
Figure 39 General Arrangement Single Pole Fuse Steelwork (Drawing SP2059590) .............................................................. 194
Figure 40 General Arrangement Single Pole Fuse Outrigger Steelwork (Drawing SP2143963) ............................................ 195
Figure 41 General Arrangement H Pole Fuse Steelwork (Drawing SP2143487) ................................................................. 196
Figure 42 General Arrangement Surge Arrester Support Steelwork (Drawing SP2143956) ................................................. 197
Figure 43 General Arrangement Delta H Section Strap (Drawing SP2146143)................................................................... 198
Figure 44 General Arrangement Terminal Bracing Strap (Drawing SP4015138)................................................................... 199
Figure 45 General Arrangement Terminal Bracing Strap (Drawing SP4020576)................................................................... 200
Figure 46 General Arrangement Long Section Strap For Long Span Delta H Pole (Drawing SP4019183) ...................... 201
Figure 47 General Arrangement Heavy Construction Stay Attachment Plates (Drawing SP4009774)................................. 202
Figure 48 General Arrangement Heavy Construction Stay Attachment (Drawing SP4009862) ............................................ 203
Figure 49 General Arrangement Transformer Platform Steelwork for a Single Pole (Drawing SP4020579)....................... 204
Figure 50 General Assembly Transformer Platform Steelwork for a Single Pole (Drawing SP4020581) ............................. 205
Figure 51 General Arrangement Transformer Platform Steelwork for an H Pole (Drawing SP4020578)........................ 206

___________________________________________________________________________
SP Power Systems Ltd

Page 142 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 52 General Assembly Transformer Platform Steelwork for an H Pole (Drawing SP4020580) .............................. 207
Figure 53 General Arrangement Single Pole Bog Shoe (Drawing SP2146665) ........................................................................ 208
Figure 54 General Arrangement H Pole Bog Shoe (Drawing SP........................................................................................... 209
Figure 55 General Arrangement Bog Shoe Strut (Drawing SP2146662) .................................................................................. 210
Figure 56 General Arrangement 300 Angle Bracket................................................................................................................... 211
Figure 57 General Arrangement Wind Stay Attachment .......................................................................................................... 212

___________________________________________________________________________
SP Power Systems Ltd

Page 143 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 1 11Kv Single Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 144 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 2 11Kv H Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 145 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 3 33Kv Light Construction Single Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 146 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 4 33Kv Light Construction H Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 147 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 5 33Kv Heavy Construction Single Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 148 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 6 33Kv Heavy Construction H Pole Member Drilling, Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 149 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 7 Delta H Pole Drilling Scarfing and Marking

___________________________________________________________________________
SP Power Systems Ltd

Page 150 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 8 Single Pole Intermediate or Pin Angle (Drawing SP2147473)

___________________________________________________________________________
SP Power Systems Ltd

Page 151 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement Single Pole Intermediate (Drawing SP2147473)
ITEM

NUMBER

01
02
03
07
11
12
14

1
1 or 2
1
2
3
3
3

19

3 or 4

21
22
23

4
1 or 2
3 or 4

24

1 or 2

25
26

As Required
1
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Intermediate Crossarm Member
ENATS 439519
SP4018402
Crossarm Strut
ENATS 439526
SP4017649
Insulator
ENATS 43-93
Insulator Pin
BS3288 Fig 4, Ref 29
Helical Ties
ENATS 43-15
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign - English
- Bilingual
Pole Numbers
Insulator Bracket
ENATS 439518
SP4018449
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811075
C43811070
C43270037
C43602072
C43602025
C43602050
C06294004
C06293900
C43811071
-

____________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 152 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 9 Single Pole Intermediate or Pin Angle (Drawing SP4018552)

___________________________________________________________________________
SP Power Systems Ltd

Page 153 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement Single Pole Intermediate or Pin Angle (Drawing SP4018552)
ITEM

NUMBER

01
02
03
07
11
12
14

1
1 or 2
2
4
3
3
3

19

3 or 4

21
22
23

10
1 or 2
1 or 2

24

1 or 2

25
26
27

As Required
1
2
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Intermediate Crossarm Member
ENATS 439519
SP4018402
Crossarm Strut
ENATS 439526
SP4017649
Insulator
ENATS 43-93
Insulator Pin
BS3288 Fig 4, Ref 29
Helical Ties
ENATS 43-15
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Insulator Bracket
ENATS 439518
SP4018449
Insulator Plate
SP4017637
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811075
C43811070
C43270037
Codes depend on
bolt length
C43602072
C43602025
C43602050
C06294004
C06293900
C43811071
C43500930
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 154 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 10 H Pole Intermediate Long Span (Drawing SP4019155)

___________________________________________________________________________
SP Power Systems Ltd

Page 155 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement H Pole Intermediate Long Span (Drawing SP4019155)

ITEM

NUMBER

01
02
06
11
12
14

2
2 or 4
2
3
3
3

19

8 or 10

20
21
22
23

4
6
6 or 8
4 or 6

24

2 or 4

25
27
30
31

As Required
3
2
1
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Long Span Crossarm Member
ENATS 439521
SP4017663
Insulator
ENATS 43-93
Insulator Pin
BS3288 Fig 4, Ref 29
Helical Ties
ENATS 43-15
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Insulator Plate
SP4017637
Foundation Brace Steelwork 2500mm centres
ENATS 439559
SP4017652
Foundation Brace Block
ENATS 439112 Type 2
SP4019037
Hardwood Plugs
ENATS 439516

COMMODITY
CODE NO.
C43810342
C43811079
C43270037
Codes depend on
bolt length
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
C43500930
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 156 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 11 Single Pole Straight Line or Angle Section (Drawing SP2147476)

___________________________________________________________________________
SP Power Systems Ltd

Page 157 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement Single Pole Straight Line or Angle Section (Drawing reference SP2147476)
ITEM

NUMBER

01
02
04
07
09
10
11
13
14
15
16
17
18

1
1 or 2
2
4
2
2
2
2
2
6
6
6
3

19

3 or 4

20
21
22
23

2
12
1 or 2
1 or 2

24

1 or 2

25

As Required
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Section Crossarm Member
ENATS 439520
SP4018433
Crossarm Strut
ENATS 439526
SP4017649
Terminal Strap
ENATS 439528
SP4017664
Section Strap
ENATS 439525
SP4017666
Pin Insulator
ENATS 43-93
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
Helical Ties
ENATS 43-15
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811077
C43811070
C43811074
C43811072
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 158 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 12 Single Pole Straight Line or Angle Section (Drawing SP4018548)

___________________________________________________________________________
SP Power Systems Ltd

Page 159 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement Single Pole Straight Line or Angle Section (Drawing reference SP4018548)
ITEM

NUMBER

01
02
04
08
09
10
11
13
14
15
16
17
18

1
1 or 2
2
4
2
2
2
2
2
6
6
6
3

19

3 or 4

20
21
22
23

2 or 4
12
1 or 2
1 or 2

24

1 or 2

25

As Required
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Section Crossarm Member
ENATS 439520
SP4018433
Long Crossarm Strut
SP4017635
Terminal Strap
ENATS 439528
SP4017664
Section Strap
ENATS 439525
SP4017666
Pin Insulator
ENATS 43-93
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
Helical Ties
ENATS 43-15
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811077
C43500940
C43811074
C43811072
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 160 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 13 H Pole Straight Line or Angle Section (Drawing SP4019003)

___________________________________________________________________________
SP Power Systems Ltd

Page 161 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Arrangement H Pole Straight Line or Angle Section (Drawing SP4019003)
ITEM

NUMBER

01
02
04
10
11
13
14
15
16
17
18

2
2 or 4
2
3
2
2
2
6
6
6
3

19

8 or 10

20
21
22
23

4
6
6 or 8
4 or 6

24

2 or 4

25
28
29

As Required
2
1
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Section Crossarm Member
ENATS 439520
SP4018433
Section Strap
ENATS 439525
SP4017666
Pin Insulator
ENATS 43-93
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
Helical Ties
ENATS 43-15
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Foundation Brace Steelwork 1830mm centres
ENATS 439558
SP4017651
Foundation Brace Block
ENATS 439112 Type 1
SP4019036
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811077
C43811072
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
C43500935
C43811796
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 162 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 14 Long Span H Pole Straight Line or Angle Section (Drawing SP2147486)

___________________________________________________________________________
SP Power Systems Ltd

Page 163 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Long Span H Pole Straight Line or Angle Section (Drawing SP2147486)
ITEM

NUMBER

01
02
06
10
11
13
14
15
16
17
18

2
2 or 4
2
3
2
2
2
6
6
6
3

19

8 or 10

20
21
22
23

4
6
6 or 8
4 or 6

24

2 or 4

25
30
31

As Required
2
1
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Long Span Crossarm Member
ENATS 439521
SP4017663
Section Strap
ENATS 439525
SP4017666
Pin Insulator
ENATS 43-93
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
Helical Ties
ENATS 43-15
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Foundation Brace Steelwork 2500mm centres
ENATS 439559
SP4017652
Foundation Brace Block
ENATS 439112 Type 2
SP4019037
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811079
C43811072
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 164 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 15 Delta H Pole Section or Section Angle (Drawing SP2059611)

___________________________________________________________________________
SP Power Systems Ltd

Page 165 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Delta H Pole Section or Section Angle (Drawing SP2059611)

ITEM

NUMBER

01
02
05
09
11
13
14
15
16
17
18

2
2 or 4
2
2
2
2
3
6
6
6
3

19

10 or 12

20
21
22
23

7
12
6 or 8
4 or 6

24

2 or 4

25
28
29
32
42

As Required
2
1
2
2
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Terminal Crossarm Member
ENATS 439522
SP4018401
Terminal Strap
ENATS 439528
SP4017664
Pin Insulator
ENATS 43-93
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
Helical Ties
ENATS 43-15
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Foundation Brace Steelwork 1830mm centres
ENATS 439558
SP4017651
Foundation Brace Block
ENATS 439112 Type 1
SP4019036
Delta H Section Strap
SP2146143
30 Degree Angle Bracket
SP4018951
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811080
C43811074
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
C43500935
C43811796
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 166 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 16 Delta Long Span H Pole Section or Section Angle (Drawing SP2059372)

___________________________________________________________________________
SP Power Systems Ltd

Page 167 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Delta Long Span H Pole Section or Section Angle (Drawing SP2059372)
ITEM
NUMBER
DESCRIPTION
ENATS, BS or OTHER DRAWING
REFERENCE
NUMBER
01
2
Wood Pole
ENATS 434001
02
2 or 4
Pole Block
ENATS 439103 Type 2
SP4019020
05
2
Terminal Crossarm Member
ENATS 439522
SP4018401
06
2
Long Span Crossarm Member
ENATS 439521
SP4017663
09
2
Terminal Strap
ENATS 439528
SP4017664
11
2
Pin Insulator
ENATS 43-93
13
2
Pilot Pin 50mm Shank
BS3288 Fig 5, Ref 50
14
2
Helical Ties
ENATS 43-15
15
6
Ball End Hook
BS3288 Fig 12 Ref 15/32
16
6
Tension Insulator
ENATS 43-93
17
6
Helical Dead End Assembly
ENATS 43-92
18
3
Non Tension Joint
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
19
8 or 10
diameter
(Grade 8.8 HYS)
20
9
M20 Tie Rods
ENATS 439608 Type 2 or 3
21
8
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
22
6 or 8
M20 Square Curved Washer
ENATS 439605
23
4 or 6
M20 Square Flat Washer
ENATS 439604
Safety Sign English
24
2 or 4
Bilingual
25
As Required
Pole Numbers
28
2
Foundation Brace Steelwork 1830mm centres
ENATS 439558
SP4017651
29
1
Foundation Brace Block
ENATS 439112 Type 1
SP4019036
32
2
Long Section Strap For Long Span Delta H Pole
SP4019183
41
4
Long Span Delta Crossarm Strut
SP2143987
As Required
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811080
C43811079
C43811074
C43270177
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
C43500935
C43811796
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 168 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 17 Single Pole Terminal (Drawing SP2147474)

___________________________________________________________________________
SP Power Systems Ltd

Page 169 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly Single Pole Terminal (Drawing 2147474)
ITEM

NUMBER

01
02
05
07
09
15
16
17

1
1 or 2
2
4
3
3
3
3

19

3 or 4

20
21
22
23

4
8
1 or 2
1 or 2

24

1 or 2

25

As Required
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Terminal Crossarm Member
ENATS 439522
SP4018401
Crossarm Strut
ENATS 439526
SP4017649
Terminal Strap
ENATS 439528
SP4017664
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811080
C43811070
C43811074
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 170 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 18 H Pole Terminal (Drawing 2147485)

___________________________________________________________________________
SP Power Systems Ltd

Page 171 of 212

Uncontrolled Copy

Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single


and H Type Wood Poles.

OHL03-099
Issue 1

____________________________________________________________________________________________________________________
General Assembly H Pole Terminal (Drawing SP2147485)

ITEM

NUMBER

01
02
05
15
16
17

2
2 or 4
2
3
3
3

19

8 or 10

20
21
22
23

5
6
6 or 8
4 or 6

24

2 or 4

25
28
29

As Required
2
1
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Terminal Crossarm Member
ENATS 439522
SP4018401
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Foundation Brace Steelwork 1830mm centres
ENATS 439558
SP4017651
Foundation Brace Block
ENATS 439112 Type 1
SP4019036
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811080
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
C43500935
C43811796
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 172 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 19 Single Pole Double Terminal (Drawing SP4000578)

___________________________________________________________________________
_
SP Power Systems Ltd

Page 173 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead Lines of Unearthed Construction on Single
and H Type Wood Poles.

OHL03-099
Issue 1

General Assembly Single Pole Double Terminal (Drawing SP4000578)

ITEM

NUMBER

01
02
05
07
09
15
16
17

1
1 or 2
4
8
6
6
6
6

19

5 or 6

20
21
22
23

8
20
1 or 2
1 or 2

24

1 or 2

25

As Required
As Required

DESCRIPTION

ENATS, BS or OTHER DRAWING


REFERENCE
NUMBER
Wood Pole
ENATS 434001
Pole Block
ENATS 439103 Type 2
SP4019020
Terminal Crossarm Member
ENATS 439522
SP4018401
Crossarm Strut
ENATS 439526
SP4017649
Terminal Strap
ENATS 439528
SP4017664
Ball End Hook
BS3288 Fig 12 Ref 15/32
Tension Insulator
ENATS 43-93
Helical Dead End Assembly
ENATS 43-92
M20 Pole Bolt (HYS) and Nut. Length to suit Pole ENATS 43- 96 Clause 4.2
diameter
(Grade 8.8 HYS)
M20 Tie Rods
ENATS 439608 Type 2 or 3
M20 x 60mm Assembly Bolt and Nut
ENATS 43- 96 Clause 4.2
M20 Square Curved Washer
ENATS 439605
M20 Square Flat Washer
ENATS 439604
Safety Sign English
Bilingual
Pole Numbers
Hardwood Plugs
ENATS 439516
-

COMMODITY
CODE NO.
C43810342
C43811080
C43811070
C43811074
C43238026
C43200548
C43811060
C43602072
C43602025
C43602050
C06294004
C06293900
-

___________________________________________________________________________________________________________________
SP Power Systems Ltd

Page 174 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 20 General Arrangement Intermediate Crossarm (Drawing SP4018402)

___________________________________________________________________________
SP Power Systems Ltd

Page 175 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 21 General Arrangement Section Crossarm (Drawing SP4018433)

___________________________________________________________________________
SP Power Systems Ltd

Page 176 of 212

Uncontrolled Copy
Specification for 11kVAnd 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 22 General Arrangement Terminal Crossarm (Drawing SP4018401)

___________________________________________________________________________
SP Power Systems Ltd

Page 177 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 23 General Arrangement Long Span Crossarm (Drawing SP4017663)

___________________________________________________________________________
SP Power Systems Ltd

Page 178 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 24 General Arrangement Crossarm Strut (Drawing SP4017649)

___________________________________________________________________________
SP Power Systems Ltd

Page 179 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 25 General Arrangement Long Crossarm Strut (Drawing SP4017635)

___________________________________________________________________________
SP Power Systems Ltd

Page 180 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 26 General Arrangement Long Span Delta Crossarm Strut (Drawing SP2143987)

___________________________________________________________________________
SP Power Systems Ltd

Page 181 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 27 General Arrangement Terminal Strap (Drawing SP4017664)

___________________________________________________________________________
SP Power Systems Ltd

Page 182 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 28 General Arrangement Section Strap (Drawing SP4017666)

___________________________________________________________________________
SP Power Systems Ltd

Page 183 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 29 General Arrangement Insulator Bracket (Drawing SP4018449)

___________________________________________________________________________
SP Power Systems Ltd

Page 184 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 30 General Arrangement Insulator Plate (Drawing SP4017637)

___________________________________________________________________________
SP Power Systems Ltd

Page 185 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 31 General Arrangement Foundation Brace Steelwork H Pole 1830mm Centres (Drawing 4017651)

___________________________________________________________________________
SP Power Systems Ltd

Page 186 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 32 General Arrangement Foundation Brace Steelwork H Pole 2500mm Centres (Drawing SP4017652)

___________________________________________________________________________
SP Power Systems Ltd

Page 187 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 33 General Arrangement Stay and Foundation Blocks (Drawing SP4019020)

___________________________________________________________________________
SP Power Systems Ltd

Page 188 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 34 General Arrangement Wood Brace Block Type 1 H Pole 1830mm Centres (Drawing SP4019036)

___________________________________________________________________________
SP Power Systems Ltd

Page 189 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 35 General Arrangement Wood Brace Block Type 2 H Pole 2500mm Centres (Drawing
SP4019037)

___________________________________________________________________________
SP Power Systems Ltd

Page 190 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 36 General Arrangement H Pole Carryover Support Steelwork (Drawing SP4008885)

___________________________________________________________________________
SP Power Systems Ltd

Page 191 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 37 General Arrangement H Pole Cable Cleat / Coffin Support Steelwork (Drawing SP2143955)

___________________________________________________________________________
SP Power Systems Ltd

Page 192 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 38 General Arrangement H Pole Crucifix Support Steelwork (Drawing SP2143957)

___________________________________________________________________________
SP Power Systems Ltd

Page 193 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 39 General Arrangement Single Pole Fuse Steelwork (Drawing SP2059590)

___________________________________________________________________________
SP Power Systems Ltd

Page 194 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 40 General Arrangement Single Pole Fuse Outrigger Steelwork (Drawing SP2143963)

___________________________________________________________________________
SP Power Systems Ltd

Page 195 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 41 General Arrangement H Pole Fuse Steelwork (Drawing SP2143487)

___________________________________________________________________________
SP Power Systems Ltd

Page 196 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 42 General Arrangement Surge Arrester Support Steelwork (Drawing SP2143956)

___________________________________________________________________________
SP Power Systems Ltd

Page 197 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 43 General Arrangement Delta H Section Strap (Drawing SP2146143)

___________________________________________________________________________
SP Power Systems Ltd

Page 198 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 44 General Arrangement Terminal Bracing Strap (Drawing SP4015138)

___________________________________________________________________________
SP Power Systems Ltd

Page 199 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 45 General Arrangement Terminal Bracing Strap (Drawing SP4020576)

___________________________________________________________________________
SP Power Systems Ltd

Page 200 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 46 General Arrangement Long Section Strap For Long Span Delta H Pole (Drawing SP4019183)

___________________________________________________________________________
SP Power Systems Ltd

Page 201 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 47 General Arrangement Heavy Construction Stay Attachment Plates (Drawing SP4009774)

___________________________________________________________________________
SP Power Systems Ltd

Page 202 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 48 General Arrangement Heavy Construction Stay Attachment (Drawing SP4009862)

___________________________________________________________________________
SP Power Systems Ltd

Page 203 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 49 General Arrangement Transformer Platform Steelwork for a Single Pole (Drawing SP4020579)

___________________________________________________________________________
SP Power Systems Ltd

Page 204 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 50 General Assembly Transformer Platform Steelwork for a Single Pole (Drawing SP4020581)

___________________________________________________________________________
SP Power Systems Ltd

Page 205 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 51 General Arrangement Transformer Platform Steelwork for an H Pole (Drawing SP4020578)

___________________________________________________________________________
SP Power Systems Ltd

Page 206 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 52 General Assembly Transformer Platform Steelwork for an H Pole (Drawing SP4020580)

___________________________________________________________________________
SP Power Systems Ltd

Page 207 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 53 General Arrangement Single Pole Bog Shoe (Drawing SP2146665)

___________________________________________________________________________
SP Power Systems Ltd

Page 208 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 54 General Arrangement H Pole Bog Shoe (Drawing SP

___________________________________________________________________________
SP Power Systems Ltd

Page 209 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 55 General Arrangement Bog Shoe Strut (Drawing SP2146662)

___________________________________________________________________________
SP Power Systems Ltd

Page 210 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 56 General Arrangement 300 Angle Bracket

___________________________________________________________________________
SP Power Systems Ltd

Page 211 of 212

Uncontrolled Copy
Specification for 11kV And 33kV Overhead
Lines of Unearthed Construction on Single and
H Type Wood Poles.

OHL03-099
Issue 1

Figure 57 General Arrangement Wind Stay Attachment

___________________________________________________________________________
SP Power Systems Ltd

Page 212 of 212

Vous aimerez peut-être aussi