Overcurent Very Inverse Relay.qcm .

Test Object - Device Settings .


Substation/Bay:
Substation: Bay: Omicron Office Substation address: Bay address:

.
.
Vikaspuri

.
Device:
Name/description: Device type: Serial/model number: Additional info 1: Additional info 2: Overcurrent relay Very Inverse 13OS001/CDG13AF8012MCH

.
Manufacturer: Device address:

.
English Electric

.
Nominal Values:
f nom: V nom (secondary): I nom (secondary): 50.00 Hz 110.0 V 5.000 A

.
Number of phases: V primary: I primary:

.
3 110.0 kV 1.000 kA

.
Residual Voltage/Current Factors:
VLN / VN: 1.732

.
IN / I nom:

.
1.000

.
Limits:
V max: 200.0 V

.
I max:

.
50.00 A

.
Debounce/Deglitch Filters:
Debounce time: 3.000 ms

.
Deglitch time:

.
0.000 s

.
Overload Detection:
Suppression time: 50.00 ms

Hardware Configuration .
Test Equipment
Type CMC256plus Serial Number JJ348B

.
Hardware Check
Performed At 3/7/2012 5:40:19 PM Result Passed

.
Details

.
Analog Outputs
Test Equipment Device Connector CMC256plus I 1 A JJ348B N Test Object Signal Display Name Connection Terminal I L1 9 , 10(Neutral) I L1

.
Binary/Analog Inputs
Test Equipment Device Connector CMC256plus 1+ Test Object Display Name Connection Terminal Binary Input 1 3 & 4 Signal Trip

JJ348B 12+ 23+ 34+ 45+ 56+ 67+ 78+ 89+ 910+ 101 2 N Bin. In. 2 Bin. In. 3 Bin. In. 4 Bin. In. 5 Bin. In. 6 Bin. In. 7 Bin. In. 8 Bin. In. 9 Bin. In. 10 Bin. In. 11 Bin. In. 12

.
Binary Outputs
Test Equipment Device Connector CMC256plus JJ348B 1+ 12+ 23+ 34+ 411 12 13 14 N Test Object Display Name Connection Terminal Bin. out 1 Signal Bin. out 1

Bin. out 2 Bin. out 3 Bin. out 4 Bin. Out 5 Bin. Out 6 Bin. Out 7 Bin. Out 8

Bin. out 2 Bin. out 3 Bin. out 4

.
Test Module
Name: Test Start: User Name: Company: OMICRON QuickCMC 07-Mar-2012 18:08:25 Version: Test End: Manager:

.
2.40 SR 1 07-Mar-2012 18:30:15

Test Results
Title: Test @10A

.
Fault Calculator:
Table Inputmode Direct Parameters (All values are secondary) I L1 10.00 A 0.00 50.000 Hz

Generator Settings
I L1 10.000A 0.00

+ 90

180

I L1 0

10.0 A -90

Binary Inputs
Binary Input 1 0->1 3.830s Overload 1->0 n/a

Analog Inputs
VDCin -0.0000V IDCin 0.0642mA

.
Comment
TMS=1 I pick up= 2.5 Plug Setting Multiplier= Fault Current/I Pickup nameplate PSM(4) corresponds to between 3 & 4 seconds =10/2.5=4 From the Relay

.
Assessment
Passed

.
07-Mar-2012

.
18:05:49

Title: Test @10A

.
Fault Calculator:
Table Inputmode Direct Parameters (All values are secondary) I L1 10.00 A 0.00 50.000 Hz

Generator Settings
I L1 10.000A 0.00

+ 90

180

I L1 0

10.0 A -90

Binary Inputs
Binary Input 1 0->1 3.833s Overload 1->0 n/a

Analog Inputs
VDCin -0.0000V IDCin 0.0642mA

.
Comment
TMS=1 I pick up= 2.5 Plug Setting Multiplier= Fault Current/I Pickup =10/2.5=4 From the Relay nameplate PSM(4) corresponds to between 3 & 4 seconds Conditions: - On trigger Switch off is checked - Binary Inputs/Trigger is checked Observation: - Binary Input 1 LED shows the continuous state. - Initially it was NO - After getting the trip time it is again NO. Conclusion: Since we have checked the On Trigger Switch off box, once the fault current is applied after 3.883s contacts change their state however since after trigger the kit is immediately switched off the momentarily NC state will not be visible

.
Assessment
Passed

.
07-Mar-2012

.
18:26:16

Comment
Summary 2 tests passed, 0 tests failed, 0 tests not assessed Test passed 100.00% passed