Certain standards produced by the Telecommunications Industry Association, International Organization for Standardization and Institute of Electrical and Electronics Engineers significantly affect the design, installation and performance of structured cabling systems, and frequently inter-relate with each other. This Cabling Installation & Maintenance editorial guide includes information on some of their most recently introduced standards and some that are still in development.

sponsored by:

TIA-1179 addresses cabling in healthcare

The revised TIA-942 Data Center standard

18 Extend your cablings


capabilities

24 De-Mystifying Cabling
Specifications

TIA-1179 addresses cabling in healthcare facilities


Specifications in the new standard are game-changers for pathways and work areas in healthcare environments.
By Brian Ensign, RCDD, NTS, OSP, CSI and Carol Everett Oliver, RCDD, ESS

Healthcare Infrastructure Standard is the culmination of work that took place within the TIA TR-42 Engineering Committee. It is an example of the newer generation of standards from the TIA that address cabling infrastructure within specific areas or environments. A healthcare facility has different types of workspaces, including labs, patient rooms and other spaces in addition to areas that resemble more-traditional workspace environments. While the TIA-568 series of standards effectively addresses cabling in traditional premises environments, the connectivity needs of healthcare facilities are far more complex than commercial buildings, and can be optimized only through a standard that recognizes their particular and often unique requirements. TIA1179 does just that. In fact the standard was initiated by a group of healthcarefacility end-users who approached the TIA and stated that although they liked the then-current TIA-568-B standard, healthcare facilities had design, installation and construction considerations that 568-B did not address. Approximately half the members of the group that drafted and ultimately approved the TIA-1179 standard were healthcare-facility users.

atified in auGust 2010, the ANSI/TIA-1179

The standard can be described as a game-changer in how designers, installers and users of structured cabling systems look at the spaces in those systems. Cabling Installation & Maintenance :: EDITORIAL GUIDE

TIA-1179 addresses cabling in healthcare facilities

Market drivers A combination of market, technical and regulatory drivers has brought healthcare facilities to the forefront, from a business standpoint, for the cabling industry. For more than a decade some provisions in the Health Insurance Portability and Accountability Act (enacted in 1996) have driven the electronic capture and storage of patient medical records. More recently the Health Information Technology for Economic and Clinical Health (HITECH) Act reinforced and even expanded security provisions of HIPAA, and further prompted healthcare facilities of all kinds to store medical records electronically. With a significant amount of patient data now available electronically, medical professionals have been finding ways to use this data to conduct trend analysis and data mining while maintaining the mandated privacy and confidentiality of HIPAA and HITECH. Medical researchers are now able to aggregate patient data to assist in their diagnosis and prevention efforts. The idea of patient data as a tool for medical research comes with the need for storage networks in which this data is housed. Another growing trend in the medical-research field that is also driving the need for more robust networks is long-distance collaboration. A prime example is a surgical procedure being transmitted via video. Today when a patient is undergoing surgery, the on-site surgeon may be accompanied by a consulting surgeon who is at a remote location but can view the surgical procedure via video. pathways in focus The TIA-1179 standard specifies requirements for telecommunications infrastructure intended to support a wide range of healthcare facilities and systems to include cabling, topology, pathways and work areas, and the devices attached to it. As mentioned earlier, pathways and work-area spaces within healthcare facilities are significantly different from those found in commercial buildings, and the 1179 standard addresses this reality. The standard recommends a minimum of two diverse pathways from the entrance facility to the equipment room. Doing so allows the user to segregate more-traditional network-type applications such as voice and data from other critical applications that are more specific to healthcare, such as imaging and diagnostic communications. Additionally, this type of pathway redundancy is Cabling Installation & Maintenance :: EDITORIAL GUIDE

TIA-1179 addresses cabling in healthcare facilities

crucial because in these healthcare environments, the network supports not only data or information flow, but often it quite literally supports the life and health of hospital patients. The TIA-1179 standard also recommends larger equipment rooms and telecommunications rooms (TRs) than were used to seeing. The standard recommendation allows for 100 percent growth when planning these spaces. That may initially sound excessive, but a significant consideration behind this recommendation is to prevent future disruption of rooms, hallways and other areas within a hospital. Hand-in-hand with this consideration is the standard guideline that the cabling-system pathways should not compromise the facilitys operation. Infection control requirements (ICRs) are a key factor in how much, or how little, access cabling-system technicians and managers will have to pathways in healthcare facilities. Consequently the 1179 standard advises that users may want to implement enclosed pathways, especially in air-handling spaces, to meet these ICRs. In general cabling-system designers are accustomed to using these open plenum spaces in which to route cables. In many cases they will find themselves without that luxury in healthcare facilities, challenging these design professionals to develop alternative system designs. Another recommendation in the standard is to segregate cables for different networks and applications due to safety protocols. In practice this means keeping cables separate in accordance with the networks the cables are serving, the specific part of the network theyre serving, or the work-area classification. redefining the work area Perhaps the most significant difference between a healthcare facility and a commercial office buildingand, not coincidentally, a major difference between TIA-1179 and the TIA-568 series of standardsis the treatment of work area spaces. Very much in contrast to the work area of a commercial office building, in which a communications outlet might service a computer, phone, printer and perhaps another user-administered device, a work area in a healthcare facility can take many forms. TIA-1179 addresses this reality by defining 11 work-area classifications. Each of those 11 classifications is further broken down into subgroups, and in total there are 75 work-area types defined in the standard. Cabling Installation & Maintenance :: EDITORIAL GUIDE

TIA-1179 addresses cabling in healthcare facilities

The 11 work-area classifications defined in TIA-1179 are: Patient Services, Surgery/ Procedure/Operating Rooms, Emergency, Ambulatory Care, Womens Health, Diagnostic and Treatment, Caregiver, Service/Support, Facilities, Operations, and Critical Care. Each of these 11 work-area classifications and the subgroup work areas within them is characterized in the standard as a low-, medium- or high-density work area. The standard calls for 2 to 6 outlets, or ports, in a low-density work area; 6 to 12 outlets in medium-density work areas; and more than 14 outlets in highdensity work areas. For several high-density work areas, the need for redundancy is a driving force behind the number of outlets recommended. At the same time, many of these workarea spaces must be equipped to handle multiple temporary connections, such as test apparatus. Picture, for example, a patient room in which tests are conducted on the patient a handful of times per day. The diagnostic equipment used to conduct these tests travels from patient to patient and is plugged in only for the duration of the test being conducted. It is then unplugged and moved to another patient room. Yet the communications outlet must be available and ready at all times. The redundancy inherent in some of these high-density work areas helps to ensure that network connectivity contributes to, rather than detracting from, patient care. Conversations with healtchcare-facility end users have confirmed that many of them have been planning high outlet counts in their most-critical work areas for these and other reasons. The many users who have faced this situation for some time now have in TIA-1179 a standard to which they can refer as an industry-agreed-upon figure for the number of outlets in these areas. Of the 75 total work-area types recognized in the standard, 45 percent are designated as low-density, 25 percent are designated as medium-density and 30 percent are designated as high-density. putting the standard into practice Many real-life examples exist of the principles in TIA-1179 being put into practice in a hospital or other healthcare facility. One example is Johns Hopkins Hospital in Baltimore, MD. Cabling Installation & Maintenance :: EDITORIAL GUIDE

TIA-1179 addresses cabling in healthcare facilities

Many new hospitals can have more than two dozen different low-voltage systems and while not all of those systems are necessarily Internet Protocol (IP)-based at the current time, convergence is rapidly taking place. Many facilities are being cabled today to support the eventual transition of these low-voltage systems to IP. The new TIA healthcare infrastructure standard recommends a minimum of Category 6 copper cabling for horizontal runs, as well as 50-micron multimode fiber-optic cabling for high-bandwidth transmissions such as computed tomography (CT) scans and magnetic resonance imaging (MRI) exams. For backbones, the standard recommends multimode and singlemode fiber-optic cabling. As mentioned earlier, these backbones should be redundant. Several factors make retrofitting a healthcare facility a difficult prospect, including the aforementioned ICRs and the TIA-1179 recommendation to use enclosed pathways to name just a couple. With these and other contributing factors in mind, as well as the bandwidth requirements and mission-critical nature of communications within healthcare facilities, it is recommended to design cabling systems to support the longest possible lifecycle. While retrofitting is a difficult task, it is the reality for the many facilities that do not have the luxury of building a new system with the proverbial blank canvas. The TIA-1179 standard recommends the use of multi-user telecommunications outlet assemblies (MUTOAs) to provide the flexibility of adding up to 24 additional outlets to a work area. One important fact to keep in mind is that although MUTOAs provide flexibility, they also represent an additional potential point of failure in a system. So installers must take care when retrofitting a workspace with MUTOAs as the standard does not recommend this practice for new facilities. Also, notably, the TIA-1179 standard does not recommend the use of consolidation points (CPs) to add outlets to a work area. Power over Ethernet (PoE) is also a consideration to make when cabling healthcare work areas. As mentioned earlier, some of the low-voltage applications used in healthcare facilities today are not IP-based but may transition to IP in the future. The ability to power these devices using the copper conductors of an unshielded twisted-pair cable, or the copper conductors within a composite copper/fiber cable construction, allows a facility to accommodate any PoE-enabled applications deployed Cabling Installation & Maintenance :: EDITORIAL GUIDE

TIA-1179 addresses cabling in healthcare facilities

today and provides the infrastructure needed for future PoE-enabled applications. Because of the critical nature of this environment, backup power via redundant uninterruptible power supply systems is recommended for all PoE injection systems. Some other best-practice recommendations that are likely to apply in healthcare facilities include considering multifiber cable, preferably preterminated, in highdensity work areas. These cable constructions will be cost-effective, reliable and the least disruptive in sensitive environments. Also, cables installed in hospitals will be subject to high levels of electromagnetic interference (EMI), temperature swings from area to area, and the possibility of contact with chemicals and other gases. These considerations may affect your choice of cables and may affect the manner in which those cables are installed. Exposure to chemicals and other gases once again brings up the issue of pathways. The pathways in which these exposures may happen are crowded with specialized air and gas-delivery systems as well as more-traditional HVAC and other systems. Cables installed in these pathways must be able to withstand these environments without degradation. One of TIA-1179s recommendations, mentioned earlier, is to segregate cables based on the applications or services they are supporting. One practical way to accomplish this is to color-code cables and connectors so they can be identified easily. While the TIA-1179 standard recommends color-coding cable, the standard does not specifically designate certain colors for services or applications. Finally, as with all cabling installations, those that take place in hospitals must meet approval by the local authority having jurisdiction (AHJ). It is certainly in the best interest of everyone involved to research state, regional and local safety codes.

Brian Ensign is director of training and technology with Legrand Ortronics and Carol Everett Oliver is market analyst with Berk-Tek.

7
Cabling Installation & Maintenance :: EDITORIAL GUIDE

Were Not Going Green.

We Already Are.

At Siemon, weve worked hard to be the most green and sustainable network infrastructure company in the world, so that our customers can deploy environmentally responsible cabling systems without sacrificing performance.

Just a few of Siemons Green Achievements:


300% Carbon-Negative Operations Zero-Landfill Recycling/Waste Management 217 KW Solar Power Plant Forestland Conservation ISO 14001 Environmental Management RoHS Compliance

We also help our customers build more sustainable infrastructures though green technology, design strategies and recommendations for:
Future-Proof Infrastructures Resource Management/Maximization Reducing Power Consumption Thermal Efficiency Cabling Abatement/Recycling Planning

To find out more about Siemons Environmental Sustainablity Achievements, visit: www.siemon.com/green

W W W

S I E M O N

C O M

What will be in the revised version of the TIA-942 Data Center standard?
Five years after initial publication, revisions are underway for the TIAs data center cabling specification.
By Jonathan Jew

(TIA) best-selling standards, is undergoing revision. All American National Standards Institute (ANSI) standards must be reaffirmed, withdrawn, or revised every five years. Since ANSI/TIA-942 was published in 2005, it was readily apparent that it needed to be revised. The revision to TIA-942 will be named TIA-942-A. new tia cabling standards scheme Because TIA-942 was published after the restructuring of the TIA-568 series cabling standards, TIA-942 needed to be modified to fit into the new TIA premises telecommunications cabling standards scheme. In this new scheme, common information that applies to multiple types of premises is in common standards, and information specific to a particular type of premises is in premises standards such as TIA-942. Component standards deal with the specification of components and are intended primarily for component manufacturers. This scheme is meant to improve ease of use, efficiency, and ensure consistency between standards. Some of the changes that will be made in TIA-942-A to incorporate it into the new scheme include the following: :: Reference the generic telecommunications cabling topology, terms, and

nsi/tia-942, one of the Telecommunications Industry Associations

environmental classifications described in TIA-568-C.0.

Cabling Installation & Maintenance :: EDITORIAL GUIDE

What will be in the revised version of the TIA-942 Data Center standard?

ANSI/TIA-942-A will be a Premises Standard (middle column) in TIAs new standard scheme. That means information that applies to multiple types of premises including data centers will be found in Common Standards (left column), while information specific to data centers will be found in 942-A.

:: Move content regarding bonding and grounding into the draft TIA-607-B standard, which provides much more information regarding telecommunications grounding and bonding. Because bonding and grounding areimportant for all premises, it is appropriate for this content to be in a generic rather than a premises standard. :: Remove content regarding labeling in computer rooms and instead refer to TIA-606-A Addendum 1, which was published in late 2008 and deals specifically with computer room and equipment room administration. Eventually, TIA606-A will be superseded by TIA-606-B, which will incorporate the addendum Cabling Installation & Maintenance :: EDITORIAL GUIDE

10

What will be in the revised version of the TIA-942 Data Center standard?

In an early draft, TIA-942-A includes the addition of the intermediate distribution area (IDA) and intermediate crossconnect (IC) to serve the needs of larger data centers.

11

and extend the concepts in TIA-606-A to administration outside computer rooms and equipment rooms. Cabling Installation & Maintenance :: EDITORIAL GUIDE

What will be in the revised version of the TIA-942 Data Center standard?

:: Move content regarding racks and cabinets to the draft TIA-569-C standard (because cabinets and racks are used in all types of premises). :: Replace power and telecommunications cabling separation distances with a reference to the more-detailed information being developed for TIA-569-C. :: Move content regarding outside plant pathways to the draft TIA-758-B outside plant standard. incorporating tia-942 addenda TIA-942-A will incorporate the contents of two addenda to TIA-942. TIA-942-1 Data center coaxial cabling specifications and application distances. Addendum 1, published in 2008, provides additional specifications for coaxial cable connectors used for T-3, E-1, and E-3 circuits. It permits longer horizontal cabling from the main distribution area (MDA) for coaxial cable used for these circuits, and provides revised circuit distance guidelines for T-1, T-3, E-1, and E-3 circuits in data centers using the new component specifications. TIA-942-2 Additional guidelines for data centers. Addendum 2, which was approved in late 2009 and should be available now, provides additional guidelines on a wide variety of subjects, the most important of which are revisions to improve energy efficiency. The addendum accomplished the following: :: Specified a wider range of temperatures and humidity in data centers based on revised guidelines published in 2008 by the American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE). :: Specified a three-level lighting protocol to reduce energy usage. :: Added Category 6A to supported media and specified it as the recommended media for balanced twisted-pair cable. :: Added guidance to check with equipment manufacturers regarding radio sources (wireless LANs, cellular telephones, handheld radios, etc.) in computer rooms and entrance rooms. :: Updated data center Tiering reference guide.

12
Cabling Installation & Maintenance :: EDITORIAL GUIDE

What will be in the revised version of the TIA-942 Data Center standard?

While harmonization between TIA and international standards is an ideal, one should not expect all the terminology used in the ISO/IEC 24764 and CENELEC EN 50173-5 standards to be included in TIA-942-A.

international standard influence The recently approved ISO/IEC 24764 international data center telecommunications cabling standard will likely influence some of the changes that will be made in TIA-942-A because it is desirable to harmonize with international standards. The ISO/IEC standard may have an impact on several aspects of TIACabling Installation & Maintenance :: EDITORIAL GUIDE

13

What will be in the revised version of the TIA-942 Data Center standard?

942-A, including terminology, maximum horizontal cabling lengths, cabling types, and connectors. Terminology. The ISO/IEC 24764 standard, published by the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC), only deals with telecommunications cabling and is primarily based on the European data center cabling standard CENELEC EN 50173-5, which was published in 2007. Both the ISO/IEC and CENELEC standards use terminology that is different from that found in TIA-942. For example, what TIA-942 calls the horizontal crossconnect (HC) located in the horizontal distribution area (HDA), the ISO/IEC and CENELEC standards call the zone distributor (ZD). Because ISO/ IEC 24764 does not deal with spaces, there is no equivalent in that standard for spaces such as the MDA or HDA. It is unlikely that TIA-942 terms will be changed to match the ISO/IEC terminology. However, it is expected that terms for parts of the infrastructure not named in TIA-942 will be adopted in TIA-942-A. Examples are the equipment outlet (EO) and external network interface (ENI). Maximum horizontal cabling lengths. The ISO/IEC and CENELEC data center standards permit various maximum cabling lengths for zone distribution cabling (horizontal cabling) based on the type of cabling employed. Balanced-pair zone distribution cabling is limited to a maximum of 100 meters, but optical-fiber cabling lengths are only dependent on the channel-length restrictions for the cabled optical fiber category used (i.e., 300 meters for OF-300 channels, 500 meters for OF-500 channels, and 2,000 meters for OF-2,000 channels). TIA-942 has only two exceptions to the normal rule that horizontal cabling is limited to 100 meters, as follows. 1. 1Up to 300-meter horizontal optical-fiber cabling originating from the MDA in data centers where no HDA is present. 2. Up to 300 meters horizontal 75-ohm coaxial cabling originating from the MDA.

14

TIA-942-A will probably remove horizontal cabling distance restrictions for optical fiber other than the application-dependent restrictions specified in TIA-568-C.0. Cabling Installation & Maintenance :: EDITORIAL GUIDE

What will be in the revised version of the TIA-942 Data Center standard?

Removing such restrictions will permit more flexibility in designing optical-fiber networks such as storage area networks. Cabling. ISO/IEC 24764 specifies a minimum of Class EA (Category 6A) for all balanced-pair except network access cablingcabling originating from the entrance room. TIA-942 permits the use of Category 3 through 6A for both backbone and horizontal cabling, but recommends Category 6A. TIA-942-A will probably eliminate the use of one or more of the lower Categories of cables for balanced twisted-pair horizontal cabling. ISO/IEC 24764 specifies a minimum of OM3 (50/125-micron 850-nanometer laseroptimized multimode fiber) for all multimode optical fiber in data centers. Connectors. Unlike TIA-942, which specifies no particular connectors, ISO/IEC 24764 specifies the following connectors. LC and MPO for multimode fiber at the EO and ENI; LC and MPO for singlemode fiber EO; Angled LC connector for singlemode fiber at the ENI. TIA will probably recommend but not require the use of LC and MPO connectors. other new content TIA-942-A will include a new section on energy-efficient design, including recommendations regarding the design of telecommunications cabling, pathways, and spaces to improve energy efficiency. This content will be in addition to the energy-saving measures provided in TIA-942 Addendum 2. To handle large data center topologies, TIA-942-A will add a new space named the intermediate distribution area (IDA), containing a new second-level backbone distributor named the intermediate crossconnect (IC). Practical experience has shown that very large data centers may require this second-level distributor. For example, a large data center could include several computer rooms, each of which could have one or more IDAs to act as central points of administration for the room. For an example data center using this setup, see the figure titled Draft TIA942-A Example Data Center Topology on page 11.

15

The potential changes described in this article are being considered by TIA TR-42.1, the subcommittee responsible for TIA-942-A. Please note, though, Cabling Installation & Maintenance :: EDITORIAL GUIDE

What will be in the revised version of the TIA-942 Data Center standard?

that many of them may not make it into the final publication. Also, there will be other modifications to TIA-942 that were not described here. Because we are at the beginning stages of the revision, it is difficult to tell what those modifications will be. If all goes well, TIA-942-A could be published sometime in 2011.

Jonathan Jew is president of J&M Consultants (www.j-and-m.com).

16
Cabling Installation & Maintenance :: EDITORIAL GUIDE

the RJ-45 Barrier!

Highest level of category 6A margin in the


industry for both UTP and shielded

Siemons Z-MAX 6A

Simple termination process combines Bestin-Class 60-second termination time with high performance consistency

Patented PCB-based Smart Plug technology


Siemons Z-MAX is an optimized end-to-end category 6A UTP and shielded system developed from the ground up to shatter the limitations of the RJ-45 as we know it today.

brings unsurpassed performance optimization into the patch cord

Patented/patent-pending Zero-Cross outlets

eliminate pair crossing/splitting to minimize crosstalk

Ultra High-Density 48-port , 1U Patch Panels


in both UTP and shielded

Exclusive hybrid flat/angled outlet design


To learn more about other Z-MAX innovations, attend a Z-MAX webinar or view real time termination videos visit: www.siemon.com/go/zmax

allows flat or angled mounting orientation with one outlet

W W W

S I E M O N

C O M

Extend your cablings capabilities with four-pair PoE


802.11n wireless LANs and IP surveillance systems are requiring more power than ever before.
By Sani Ronen

communications networks. Now with the advent of Power over Ethernet (PoE) technology, it also has become the electricity backbone, fueling a growing variety of digital devices from Wi-Fi wireless access points and notebook computers to video surveillance cameras. The ratification of the IEEE 802.3at standard in September 2009 enabled PoE to deliver 30 watts of safe power over a single Ethernet cable to an even broader range of gear including access control systems, pan/tilt/zoom (PTZ) cameras, outdoor cameras and even full outdoor solutions that include a heater. The growing use of 802.11n WiFi technology has been one of high-power PoEs drivers. The

thernet Cable has become the universal backbone for

18

The latest IEEE 802.3at standard enables PoE to power a much broader range of powered devices, from 802.11n wireless access points, 802.16 subscriber stations and 3G/LTE femtocells, to perimeter security equipment, videoconferencing and telephony products and thin clients.

Cabling Installation & Maintenance :: EDITORIAL GUIDE

Extend your cablings capabilities with four-pair PoE

multiple-input/multiple-output (MIMO) architecture used by 802.11n technology inherently requires more power than previous technologies, like 802.11a and 802.11b/g. And 802.11n brings about bigger operating ranges that transform it into a better candidate for mesh networks for physical security, in which the wireless local area network (LAN) access points are always connected in tandem with a network camera, and is expected to power it. These two trends make IEEE 802.3at2009 PoE Plus capabilities crucial for the efficient deployment of 802.11n in its full splendor. A key way that PoE system developers are addressing these challenges is by employing the option to implement PoE functionality over all four pairs of the Ethernet cable. This option opens the door for safely delivering 60 watts of direct current (DC) power over a single Ethernet cable, using current levels of 600 milliamp (mA) rather than the 1.2 Amp level of two-pair 60W midspans. With the latest four-pair 802.3at solutions, cabling professionals can go well beyond the 25.5W of two-pair solutions to support powered device (PD) power consumption of 51W, using fully compliant industry-standard 60W PoE technology at the source. And because it is backed by IEEE standards, todays 802.3at-compliant technology incorporates all necessary PD PoE compliance detection features for safe powering as well as safe PD disconnection in overload, short-circuit or under-load conditions. how four-pair powering works The original, standard-power 802.3af specified that a PoE switch or midspan will deliver up to 15.4W. It also defined consumption of up to 12.95W by the powered device, which may be installed up to 100 meters from the switch. This power limitation prevented high power devices that required up to 30W, such as PTZ cameras and advanced access control solutions, to be supported via the industrystandard PoE solution.

19
Cabling Installation & Maintenance :: EDITORIAL GUIDE

Extend your cablings capabilities with four-pair PoE

The new high-power 802.3at standard roughly doubled what power sourcing equipment (PSE) can deliver and what PDs can receiveto 30W and 25.5W, respectively. It also increased PSE output voltage to between 50 and 57V, and boosted maximum ongoing current to 600mA. One of the most important benefits of the IEEE 802.3at standard was that it relied on the field-proven detection and protection concepts of the existing 802.3af standard, thus enabling fast and safe adoption of the new standard. Even more importantly, the IEEE 802.3at-2009 standard changed the definition of a PD, compared to the previous IEEE 802.3-2008 Clause 33. The new standard considers the PD to be the powered interface, as opposed to the entire device being powered. This means that one can have two power interfaces, each taking 25.5W, inside the same box. Nothing precludes these to be connectedone over the two pairs using lines 1, 2, 3 and 6 and the other over the two pairs using lines 4, 5, 7 and 8. This is what makes it possible to double the standard 802.3at-2009 maximum of 25W and go up to 51W while fully complying with the standard. The primary applications for 51W PoE power delivery are full systems that include an IP camera with additional power-consuming accessories such as a heater. In the access control market, a full system that includes a controller, a reader and a few door locks can easily consume 45W of power or more. Powering over all four pairs of Ethernet cable not only boosts power delivery to PDs but also improves efficiency compared to two-pair solutions. Rather than delivering 51W over twisted-pair cable via a four-pair solution, this same four-pair configuration can be used to power two-pair devices with 30W of power, while dissipating up to half the power and consuming almost 15% less energy than conventional two-pair solutions. This translates into savings of approximately $25 per year per powered device, assuming energy costs of $0.10 per kilowatt hour. Finally, the four-pair configuration offers the opportunity to extend cabling lengths. Type 1 devices assume the same legacy cabling infrastructure (Category 3) that was the minimum required for 802.3af. So if Type 1 devices are used with worst-case Category 5 cables, the cables could actually be 60% longer. The resistance of the Category 5 cables is equivalent to Category 3 cables, or 480 feet. Of course, this scheme would only work if the physical layer (PHY) device being used to transmit data could also support these long distances. Cabling Installation & Maintenance :: EDITORIAL GUIDE

20

Extend your cablings capabilities with four-pair PoE

switch vs. midspan Cabling professionals can deploy the latest high-power PoE technology in the cabling infrastructure either by upgrading the switch or by adding midspans to the existing switch infrastructure. Typically the most flexible, scalable, manageable and energy-efficient way to deploy PoE is by using midspans, especially in first-time PoE deployments. They require no changes to the existing switch or cabling, and are generally compatible with any Ethernet switch. One major advantage of midspansreliabilityis especially apparent with the higher power standards. The mean time between failure (MTBF) of PoE switches is considerably lower, when compared with their non-PoE counterparts. This is due to the concentration of high-power dissipation from the PoE section and the highly sensitive data section into a single box. For example, Ciscos 3750X-48T (non-PoE) product has 171,846 hours of MTBF, while the 3750X-48P (its PoE counterpart) product has an MBTF of 139,913 hoursan almost 20% smaller lifetime. Even worse, once there is an issue, one pays for both data and power again, instead of dealing only with the section where the issue exists. Another advantage of midspans is that they are more flexible and scalable than switches. They enable PoE ports to be added, incrementally, only as needed rather than having to invest in advance for future growth at the time of installation. The inclusion of an interlocking feature enables the power infrastructure to be expanded in one-port midspan increments as the new PDs are added. Flexibility is further enhanced with midspans through the inclusion of a gigabit interface so they can more easily support high-power PTZ cameras and thin clients. Other options that enhance flexibility include the ability to use DC inputs with external power supplies for incremental power capacity or redundancy, and flexible powering from alternating current (AC), DC or another midspan. Interconnected midspans can also back each other up. Once deployed, a midspan-based PoE infrastructure is also easier to manage and maintain than one driven by a PoE-capable switch. Midspans deliver remote power-management capabilities that support both IPv4 and IPv6/addressing, which allows simple and efficient monitoring and control of powered devices. This increases in importance with network size and complexity. Remote power management also enables unit scheduling uninterruptible power supply (UPS) Cabling Installation & Maintenance :: EDITORIAL GUIDE

21

Extend your cablings capabilities with four-pair PoE

Safe PoE powering is ensured by first performing PD detection, followed by PD classification to determine a PDs consume power level prior to its ignition. Gradual startup avoids high-frequency data interference; real-time protection and power management during operation ensure system safety. Any PD disconnection is followed by a fast power shutdown.

power monitoring and Web-based monitoring. Malfunctioning remote devices can be reset, eliminating an expensive service call. Midspans also enable centralized control of multi-site or multi-building installations, with support for immediate alert (e.g. E911) and response if IP phone status changes. When the midspan is integrated with a UPS system, the remote power-off/power-on capability also enables low-priority ports to be disconnected during power failures. Remote power management must be performed in a secure fashion, so SNMPv3 management is recommended to prevent malefic agents from interfering with network operations. Finally, midspan-based PoE solutions also significantly improve energy efficiency. The remote-management features alone provide an easy way to power selected ports up or down during the day, which can reduce power consumption by 70%. Each devices power consumption can be measured and its average power consumption can be actively reduced. A typical 1U 24-port midspan that has 24 x 15.4W, or 370W of total power to manage, may only have real-time power needs of Cabling Installation & Maintenance :: EDITORIAL GUIDE

22

Extend your cablings capabilities with four-pair PoE

just over half that amount for the various PDs on the network. Additionally, todays enterprise-grade PoE midspans use a distributed power architecture, augmenting smaller, more-economical internal default power supplies with external power supplies either for incremental additional power or for redundancy. This further improves midspans already excellent system efficiency, and reduces cooling costs because smaller supplies require smaller and/or lower-speed fans. As mentioned earlier, this approach also enables midspans to back each other up, with additional power supply serving the highest-priority system ports. protecting outdoor gear Another key consideration for cabling professionals is whether their powering solution can support the environmental requirements of outdoor PDs such as IP cameras. Until recently PoE could only be deployed safely if it were paired with a surge-protection unit to prevent direct or nearby lightning strikes from damaging or destroying both the PDs and their network switch. Without lightning protection, surges also can move quickly along the Ethernet cable to damage expensive indoor network switches. Because surge- and lightning-protection units can cost anywhere from $250 to $400, many cabling professionals consider them to be a discretionary item. Unfortunately, nearby lightning strikes are much more common than most people think, and even at a mile away can induce a voltage level capable of damaging outdoor devices. A midspan with integrated surge protection reduces lightning-protection costs by as much as 80% compared to using standalone surge-protection equipment. Todays latest midspans provide higher power delivery and improved energy efficiency, while offering a significantly more flexible and scalable alternative to PoE-enabled switches. Cabling professionals can optimize their PoE deployment by choosing midspans that are capable of industry-standard powering on spare pairs in compliance with IEEE 802.3at standards, and that also feature such capabilities as lightning protection that are critical for network gear deployed outdoors.

23

Sani Ronen is Product Marketing Manager in Microsemi Corporations analog mixed signal group. Cabling Installation & Maintenance :: EDITORIAL GUIDE

FROM 5e TO 7A

De-Mystifying Cabling Specifications


From 5e to 7A

tructured cabling standards specify generic installation and design topologies that are characterized by a category or class of transmission performance. These cabling standards are subsequently referenced in applications standards, developed by committees such as IEEE and ATM, as a minimum level of performance necessary to ensure application operation. There are many advantages to be realized by specifying standards-compliant structured cabling. These include the assurance of applications operation, the flexibility of cable and connectivity choices that are backward compatible and interoperable, and a structured cabling design and topology that is universally recognized by cabling professionals responsible for managing cabling additions, upgrades, and changes.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

The Telecommunications Industry Association (TIA) and International Standard for Organization (ISO) committees are the leaders in the development of structured cabling standards. Committee members work hand-in-hand with applications development committees to ensure that new grades of cabling will support the latest innovations in signal transmission technology. TIA Standards are often specified by North American end-users, while ISO Standards are more commonly referred to in the global marketplace. In addition to TIA and ISO, there are often regional cabling standards groups such as JSA/JSI (Japanese Standards Association), CSA (Canadian Standards Association), and CENELEC (European Committee for Electrotechnical Standardization) developing local specifications. These regional cabling standards groups contribute actively to their countrys ISO technical advisory committees and the contents of their Standards are usually very much in harmony with TIA and ISO requirements. While the technical requirements of TIA and ISO are very similar for various grades of cabling, the terminology for the level of performance within each committees Standards can cause confusion. In TIA Standards, cabling components (e.g. cables, connecting hardware, and patch cords) are characterized by a performance category and are mated to form a permanent link or channel that is also described by a performance category. In ISO, components are characterized by a performance category and permanent links and channels are described by a performance class. TIA and ISO equivalent grades of performance are characterized by their frequency bandwidth and are shown in table 1.

TABLE 1: TIA AND ISO EQUIVALENT CLASSIFICATIONS


FREQUENCY BANDWIDTH 1 100 MHz 1 250 MHz 1 500 MHz 1 600 MHz 1 1,000 MHz TIA COMPONENTS) Category 5e Category 6 Category 6A n/s n/s TIA (CABLING) Category 5e Category 6 Category 6A n/s n/s ISO (COMPONENTS) Category 5e Category 6 Category 6A Category 7 Category 7A ISO (CABLING) Class D Class E Class EA Class F Class FA

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

When faced with the daunting task of upgrading an existing network or designing a new building facility, cabling experts are encouraged to look to the Standards for guidance on performance and lifecycle considerations. Both TIA and ISO state that the cabling systems specified in their Standards are intended to have a useful life in excess of 10 years. Since applications, such as Ethernet, typically have a useful life of 5 years, it is recommended practice to specify cabling systems that will support two generations of network applications. For most commercial building end-users, this means specifying a cabling plant that is capable of supporting 1000BASE-T (Gigabit Ethernet) today and a planned upgrade to 10GBASE-T in 5 years. TIA categories and ISO classes of structured cabling that are recognized for the support of data-speed applications are specified in the Standards listed in Table 2.

TABLE 2: TIA AND ISO STANDARDS REFERENCES


TIA CABLING STANDARDS Category 5e Category 6 Category 6A ANSI/TIA-568-C.2, Balanced Twisted-Pair Telecommunications Cabling and Components Standard, 2009 ANSI/TIA-568-C.2, Balanced Twisted-Pair Telecommunications Cabling and Components Standard, 2009 ANSI/TIA-568-C.2, Balanced Twisted-Pair Telecommunications Cabling and Components Standard, 2009

ISO CABLING STANDARDS Class D Class E Class EA Class F Class FA ISO/IEC 11801, 2nd Ed., Information technology Generic Cabling for Customer Premises, 2002 ISO/IEC 11801, 2nd Ed., Information technology Generic Cabling for Customer Premises, 2002 Amendment 1 to ISO/IEC 11801, 2nd Ed., Information technology Generic Cabling for Customer Premises, ISO/IEC 11801, 2nd Ed., Information technology Generic Cabling for Customer Premises, 2002 Amendment 1 to ISO/IEC 11801, 2nd Ed., Information technology Generic Cabling for Customer Premises,

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

CATEGORY 5E/CLASS D Category 5e/class D cabling requirements were first published in 2000 in order to address the additional transmission performance characterization required by applications such as 1000BASE-T that utilize bi-directional and full four-pair transmission schemes. The Standard added headroom to category 5 performance limits and characterized several new transmission criteria that were required for support of Gigabit Ethernet over a worst case four-connector channel (the 1000BASE-T application was originally targeted for operation over category 5 channels having just two-connectors). To ensure that additional performance margins were satisfied, category 5e/class D specifications added headroom to the parameters of NEXT loss, ELFEXT loss, and return loss and introduced the characterization of crosstalk using power summation, which approximates the total crosstalk present when all pairs are energized as in a four-pair transmission scheme. Although no longer recognized by the Standards for new installations, a substantial number of installed category 5 channels are likely to support the 1000BASE-T application. Information on the qualification of legacy category 5 installations for this application can be found in annex M of ANSI/TIA-568-C.2.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

CATEGORY 6/CLASS E The majority of structured cabling specified for new buildings in the past 5 years has been category 6/class E rated because it provided the maximum performance headroom and return-on-investment. Category 6/class E cabling delivered double the signal-to noise margin (attenuation-to-crosstalk margin is positive to 200 MHz) of category 5e/class D cabling and provided the performance headroom desired by end-users to ensure that their cabling plant could withstand the rigors of the cabling environment and still support 1000BASE-T when it was time for an application upgrade. The category 6/class E cabling specification development process also brought to light the need to limit the conversion of differential mode signals to common mode signals and vice versa through the characterization of component balance, resulting in cabling systems with improved electromagnetic compatibility (EMC) performance. Although, category 6/class E cabling was primarily targeted to support 100BASE-T and 1000BASE-T applications, the good news is that some of the installed base of category 6/class E cabling can support the 10GBASE-T application. The TIA TSB-155-A and ISO/IEC 24750 technical bulletins identify the additional performance headroom, as well as applicable field qualification test requirements and procedures, which must be satisfied by the installed base of category 6/class E cabling in order to support the 10GBASE-T application. Since the digital signal processing (DSP) capabilities of the 10GBASE-T application result in full internal pair-to-pair crosstalk cancellation, this application is particularly sensitive to undesired signal coupling between adjacent components and cabling. This coupling is called alien crosstalk and the characterization of alien crosstalk in the installed category 6/class E cabling plant is the main focus of the TIA TSB-155-A and ISO/IEC 24750 technical bulletins. Because the alien crosstalk in category 6/class E UTP cabling is extremely dependent upon installation practices (e.g. bundling, the use of tie-wraps, and pathway fill), performance values were developed based upon a typical worst case environment meaning that 10GBASET should operate over category 6/class E UTP channel lengths of up to 37 meters and may operate over channel lengths of 37 to 55 meters of category 6/class E UTP cabling depending upon the actual alien crosstalk levels present. Since the overall foil in category 6/class E F/UTP cabling designs significantly reduces alien crosstalk, these length limitations are not applicable to F/UTP cabling.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

TIA TSB-155 and ISO/IEC 24750 also specify recommended mitigation practices in the event that an installed category 6/class E channel does not satisfy the minimum alien crosstalk levels. Mitigation techniques include using non-adjacent patch panel ports to support the 10GBASE-T application, separating or using improved equipment cords, using F/UTP equipment cords, unbundling cables, reconfiguring cross-connects as interconnects, and replacing category 6/class E components with category 6A/class EA components. Category 6/class E cabling is not recommended for new installations targeted for support of the 10GBASE-T application. The reason for this is that, while field test devices for determining compliance to the new PSANEXT loss and PSAACRF (previously known as PSAELFEXT loss) parameters are just now being introduced to the market, the test methodology remains extremely time-consuming, overly onerous to implement, and may not be fully conclusive. Furthermore, in a majority of installations, alien crosstalk mitigation will be required. Often, the recognized mitigation methods cannot be easily implemented due to existing pathway fill restrictions and the potential need to replace components. In addition, there is no guidance on qualification procedures for large installations or future MAC work. Since the category 6/class E Standard was published in 2002, it is more than halfway through its targeted 10-year lifecycle. Todays cabling specifiers are looking to even higher performing grades of cabling to ensure maximum performance and return-on-investment. CATEGORY 6A/CLASS EA Category 6A/class EA cabling requirements are nearing finalization and were initially developed to address the extended frequency bandwidth and alien crosstalk headroom required to support 10GBASE-T over 100 meters of cabling containing up to four-connectors. Category 6A/class EA cabling delivers positive signal-to-alien crosstalk margin up to 500 MHz and is recommended as the minimum grade of cabling capable of withstanding the rigors the cabling environment and supporting 10GBASE-T when it is time for an application upgrade. Balance requirements for channels and permanent links are also specified for the first time, thereby ensuring better electromagnetic compatibility (EMC) performance than any previous generation of cabling. Performance headroom has been incorporated into all transmission parameters, including power sum alien crosstalk, and both laboratory and field test qualification methods are specified for category 6A/class EA cabling. Average power sum alien crosstalk across all four-pairs is specified for use by the IEEE committee in their channel capacity modeling. It is interesting to note that the term equal level far-end crosstalk loss (or ELFEXT loss) previously used in TIA specifications has been replaced by attenuation to crosstalk ratio, far-end (or ACRF). The intent of this change is for TIA to harmonize with the ISO terminology and more accurately describe the actual test measurement configuration. Category 6A/class EAcabling provides the maximum return-on-investment when the calculations are performed using a 10-year lifecycle.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

CLASS F Class F requirements were published in 2002 and describe performance criteria for a fully shielded media type (i.e. cabling with an overall shield and individually shielded pairs). Category F cabling delivers positive attenuation-to-crosstalk margin up to 600 MHz and offers unsurpassed electromagnetic capability (EMC) performance because of its shielded construction. Due to its ease of use, performance headroom, ability to support multiple applications under one sheath, and its specification as the recommended category 7 interface in the ISO 15018 Standard, the non-RJ style plug and socket interface specified in IEC 61076-3-104:2002 is the most commonly specified category 7 connector. This interface is commercially available from multiple manufacturers whose products are interoperable. There is significant evidence that the cabling industry and applications developers are ready to adopt fullyshielded cabling. For example, class F cabling was identified as the copper media of choice in one IEEE new application call-for-interest and the published ISO/IEC 14165-114 application Standard, entitled, A Full Duplex Ethernet Physical Layer Specification for 1000 Mbit/s operating over balanced channels Class F (Category 7 twisted pair cabling), specifies operation over a minimally rated class F channel. It is interesting to note that, although TIA is not actively developing a standard for category 7 at this time, it is acceptable to specify class F cabling in North American markets. The rationale for this is that, in addition to being recognized by BICSI, NEMA, IEEE, and other standards organizations, class F is simply a superset of TIA category 6A requirements. Field test requirements and adapters for class F cabling qualification have been commercially available since 2002. The advantage that class F has over other grades of cabling is that it is targeted for support of next generation applications beyond 10GBASE-T. Class F cabling is the only media to have a 15-year lifecycle and class F cabling provides the maximum return-on-investment when calculations are performed using a 15-year lifecycle. CLASS FA Class FA requirements are based upon the existing class F cabling requirements and category 7 non-RJ style plug and socket interface. The significant enhancement in class FA specifications is the extension of the frequency bandwidth of characterization from 600 MHz to 1,000 MHz. This enhancement allows class FA cabling to be uniquely capable of supporting all channels of broadband video (e.g. CATV) that operate up to 862 MHz. It is likely that all fully-shielded cabling solutions specified in the near future will be class FA.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A
APPLICATIONS SUPPORT Table 3 summarizes cabling types capable of supporting commonly specified applications over 100-meter, four-connector topologies. TABLE 3: APPLICATIONS CHART
CATEGORY/5E CLASS D 4/16 MBPS TOKEN RING 10BASE-T 100BASE-T4 155 MBPS ATM 1000BASE-T TIA/EIA-854 10GBASE-T ISO/IEC 14165-144 BROADBAND CATV CATEGORY 6/CLASS E CATEGORY 6A/CLASS EA CLASS F CLASS FA

l l l l l

l l l l l l

l l l l l l l

l l l l l l l l

l l l l l l l l l

PERFORMANCE COMPARISON CHART: Table 4 provides comparative channel performance data at 100 MHz for category 5e/class D, category 6/class E, category 6A/class EA, class F, and class FA channels. Where there is a slight difference between TIA and ISO performance limits, ISO performance limits are indicated in parenthesis. TABLE 4: INDUSTRY STANDARDS PERFORMANCE COMPARISON AT 100 MHZ FOR CHANNELS
Category 5e/Class D Category 6/Class E Frequency Range (MHz) Insertion Loss (dB) NEXT Loss (dB) PSNEXT Loss (dB) ACR (dB) PSACR (dB) ACRF 1 (dB) PSACRF 2 (dB) Return Loss (dB) PSANEXT Loss (dB) PSAACRF (dB) TCL (dB) ELTCTL 3 (dB) Propagation Delay (ns) Delay Skew (ns)
1 2 3

Category 6A/Class EA 1 - 500 20.9 39.9 37.1 18.6 15.8 23.3/25.5 20.3/22.5 12.0 60.0 37.0 20.3 0.5/0 548 50

Class F 1 - 600 20.8 62.9 59.9 42.1 39.1 44.4 41.4 12.0 n/s n/s 20.3 0 548 30

Class FA 1 1,000 20.3 65.0 62.0 46.1 41.7 47.4 44.4 12.0 67.0 52.0 20.3 0 548 30

1 100 24.0 30.1 27.1 6.1 3.1 17.4 14.4 10.0 n/s n/s n/s n/s 548 50

1 - 250 21.3/21.7 39.9 37.1 18.6 15.8 23.3 20.3 12.0 n/s n/s n/s n/s 548 50

Specified as ELFEXT loss for category 5e/class D and category 6/class E. Specified as PSELFEXT loss for category 5e/class D and category 6/class E. ELTCTL is specified at 30 MHz.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

D AT A C E N T E R C A B L I N G

Why Category 6 Should Not be Specified for 10Gb/s

A recent report1 by the industry market research firm IDC provided the recordduring the 2nd quarter of 2010. A likely bet is that the majority of these switches becomes increasing available, data center decision makers will want to take ing 10 Gb/s technology over balanced twisted-pair copper cabling. While it is advantage of the cost savings, convenience, and flexibility provided by deployare being deployed in the data center. As 10GBASE-T network equipment breaking news: more than one million 10 Gigabit Ethernet ports were shipped

specify category 6A or higher cabling in a new 10 Gb/s-ready data center.

environments, the reality is that there are some very compelling reasons to

true that category 6 cabling can provide limited support of 10GBASE-T in some

8 Standards recognize category 6A as the minimum grade of cabling for data centers

TIA, ISO/IEC, and other telecommunications Standards organizations have developed Standards that address cabling system design and installation in the data center environment. The message of these Standards is clear: the minimum grade of cabling to be deployed in the data center is category 6A. The working draft of ANSI/TIA-942-A2 states that category 6A is the recommended grade of horizontal and backbone cabling to install in new data centers. ISO/IEC 247643 explicitly states that main distribution and zone distribution cabling systems supporting data centers shall be designed to provide a minimum of class EA (equivalent to TIA category 6A) channel performance.

8 Category 6 support of 10GBASE-T is uncertain

Several published industry guidelines (e.g. TIA TSB-155-A4 and ISO/IEC TR 247505) are available to assist in qualifying the capability of an existing category 6 cabling plant to support 10GBASE-T. These guidelines were not intended for newly-installed cabling. According to guidelines, category 6 cabling less than 37 meters (121 feet) should support the 10GBASE-T application and cabling between 37 meters and 55 meters (180 feet) should support the application depending upon the alien crosstalk environment. However, there is no 10GBASE-T application support assurance over short runs of category 6 because alien crosstalk is highly dependent on cable density.

The only way to ensure compliance to guidelines such as TSB-155-A and ISO/IEC TR 24750 is to perform complicated alien crosstalk field tests on every channel. This testing can be extremely time-consuming and may not be fully conclusive. In a majority of data center installations, alien crosstalk mitigation will likely be required. The recognized mitigation methods cannot be easily implemented due to existing pathway fill restrictions and the potential need to replace links or components. Finally, there is no guidance on qualification procedures for large installations or future MAC (moves, adds, and changes) work. The added cost and uncertainty associated with alien crosstalk qualification testing of category 6 cabling makes category 6A systems a much more desirable solution for new 10 Gb/s-ready data centers.

8Category 6 running 10Gb/s should not be used in the same pathways as category 6A UTP

Emerging industry guidance on pathway separation (e.g. TIA TSB-1906) unequivocally states that category 6 UTP cabling transmitting 10GBASE-T signals should not be placed unbundled, in adjacent bundles, or in the same bundle as category 6A UTP cabling transmitting 10GBASE-T signals. TIA TSB-190 also reaffirms TIAs position that category 6A cabling should be used for all new installations targeted for support of 10GBASE-T.

8There are no applications under development for category 6

Both TIA and ISO state that the cabling systems specified in their Standards are intended to have a useful life in excess of 10 years. Since the category 6 and class E cabling Standards were published in 2002, these systems are already beyond the halfway point of their targeted lifecycle. Furthermore, applications development groups such as IEEE 802.3 or ATM are not investigating the development of new Ethernet or other data transmission solutions for deployment over category 6 cabling.

www.siemon.com

Why Category 6 Should Not be Specified for 10Gb/s

D AT A C E N T E R C A B L I N G

8Category 6 UTP cannot support a full 100 meter 10GBASE-T channel, limiting design flexibility
Category 6A and 7A can support a full 100 meter channel and potentially longer. Siemon is working with Aquantia, a leading 10GBASE-T chip manufacturer to test their shielded 6A and 7A cabling systems in extended channel distances beyond 100 meters7 - instead of using category 6 UTP and shortening it. Shortening channels to use category 6 for 10GBASE-T may restrict equipment placement and require the addition of patching zones or switches, resulting in added connectivity, equipment and power cost.

8Category 6 UTP cannot support power-saving short reach mode (aka data center mode)
Short reach mode, per the IEEE 10GBASE-T standard can reduce power consumption by approximately 1W per port when using shorter (30m or less) category 6A or higher cabling channels. Category 6 cabling cannot take advantage of this power savings mode, therefore making it a higher cost and less environmentally friendly option.

8Cables with reduced diameter conductors cannot dissipate heat as well as category 6Aor higher systems
Data center temperatures are increasing. ASHRAE recommendations are up to 81F/27C. Cable insertion loss increases as cabling temperature increases. In data centers, the majority of cabling is at the rear of server cabinets where the heat is the greatest. The increased current levels of evolving PoE+ applications also generate more heat, further compounding these temperature issues. TIA and ISO specify a temperature dependent de-rating factor used in determining horizontal cable length at temperatures above 20C (68F). Horizontal cables having reduced diameter conductors will be further limited in distance due to a higher temperature de-rating factor compared to category 6A and especially compared to shielded category 6A and higher cabling.

References
1- Worldwide Ethernet Switch and Router 2Q10 Market Share Update, Doc # 224735, IDC, August 2010 2 - ANSI/TIA-942-A, Telecommunications Infrastructure Standard for Data Centers, draft 2.0, pending publication 3 - ISO/IEC 24764, Ed. 1.0, Information technology Generic cabling for data centers, April 2010 4 - TIA TSB-155-A, Guidelines for the Assessment and Mitigation of Installed Category 6 Cabling to Support 10GBASE-T, March 2010 5 - ISO/IEC TR 24750, Information technology Assessment and Mitigation of Installed Category 6 Cabling to Support 10GBASE-T, July 2007 6 - TIA TSB-190, Guidelines on Shared Pathways and Shared Sheaths, draft 2.0, pending publication 7 - Aquantia Press Release, July 2010 - http://www.aquantia.com/pdf/AQ_120m_Reach_Release_FINAL.pdf 8 - ASHRAE 72-74 (22-23C)

Siemon Asia Pacific Headquarters Shanghai, China Tel: (86) 21 6390 6778

Siemon CASA Headquarters Central & South America Bogota, Colombia Tel: (571) 317 2121

Siemon EMEA Headquarters Europe, Middle East & Africa Chertsey Surrey, England Tel: (44) (0) 1932 571771

Siemon Brazil Sao Paulo, Brazil Tel: (55) 11 3831 5552

Siemon North America Headquarters Watertown, Connecticut Tel: (1) 866-548-5814

FLR_No_10G_Cat6 9/10

Visit our website at www.siemon.com for detailed global office contact information

www.siemon.com

Short Length 26 AWG Data Center Solutions Equal Long Term Risks

Convergence, virtualization, and an improving economy are fueling tremendous data center growth. As would be expected, the increasing number of ports and congestion in todays data centers presents a new set of cabling challenges including: Managing air flow for optimum thermal performance Maintaining proper pathway fill requirements Supporting advanced applications such as 10GBASE-T and PoE Plus
Unfortunately, a recent trend in the industry is to respond to these challenges by deploying twisted-pair cables constructed from 26 AWG conductors over a restricted length channel topology. The trend is based on the idea that these cables reduced outside jacket diameter will help alleviate thermal and pathway fill issues. The primary concern with this practice is the fact that these reduced-length systems are not Standards compliant. Cables with 26 AWG conductors do not comply with any TIA or ISO/IEC Standard for horizontal cable requirements, all of which specify a minimum of 24 AWG (0.5mm) conductors. Any claim that these cables are category 6A, 6, or 5e compliant is a violation of the Uniform Commercial Code. As a result of the deficiencies imparted by the use of these smaller diameter conductors, the length of channels must be shortened (typically to 70 meters) to satisfy maximum channel insertion loss requirements. While this approach is commonly justified by the rationale that 100 meter topologies are not often deployed in data centers, there are multiple long term risks associated with specifying a cabling system that fails to meet one of the most fundamental mechanical construction requirements.

8 Risk: Support of Future Applications is Unknown


Should a future application be developed for operation over category 6A cabling, there is no assurance that channels constructed from 26 AWG horizontal cables will support it.

8 Risk: Power Delivery Applications Generate Excessive Heat


Horizontal cables constructed from 26 AWG conductors have significantly higher per unit length direct current or dc loop resistance than the maximum 0.25 per meter requirement specified by TIA and ISO Standards. These cables can exhibit dc loop resistance as high as 0.29 per meter. Depending upon bundle size, this increased resistance may result in a temperature rise in excess of the maximum 10 C allowed by IEEE 802.3at for PoE Plus deployment; calling into question the ability of these solutions to adequately support power delivery. Excessive heat not only adversely affects the operation of electronic equipment, but can result in premature aging of the dielectric materials that are used in the cable jacket and conductor insulation. As targets for future power delivery applications increase from the PoE Plus level of 30 watts to proposed values as high as 100 watts, compliance to TIA and ISO Standards requirements for per unit length dc loop resistance becomes extremely critical to avoid excessive heat generation.

8Risk: Reduced Flexibility for Future Growth:


The challenges that data centers are facing today are fueled by growth, but short length channel topologies ultimately restrict flexibility to accommodate data center expansion in the future. This is counterintuitive. Standards specified cabling topologies provide the most flexibility for growth and support of new applications.

8Solution:
FLR_LngTerm Risk_B 11/10

Reducing overall cable diameter is not the only way, nor the best way, to manage airflow and maintain proper pathway fill in the data center. These issues can be effectively addressed without the specification of noncompliant, reduced-length cabling systems that compromise applications support and future growth. Data center products such as Siemons VersaPOD cabinet and cable management solution maximize air flow through specialized design features that include perforated front and rear doors, open base construction, air flow management between cabinets, and provisions for roof mounted cooling fans and additional accessories such as brush guards, blanking panels, and grommets that promote proper air flow and temperature control. VersaPOD also features an array of integrated horizontal and vertical cable management options that support high cable capacity in addition to a concealable pathway for cable routing and slack management. With so many smart and flexible options available, it just doesnt make sense to take on the long term risks associated with short length cabling.
Siemon Asia Pacific Headquarters Shanghai, China Tel: (86) 21 6390 6778 Siemon CASA Headquarters Central & South America Bogota, Colombia Tel: (571) 317 2121 Siemon EMEA Headquarters Europe, Middle East & Africa Chertsey Surrey, England Tel: (44) (0) 1932 571771 Siemon Brazil Sao Paulo, Brazil Tel: (55) 11 3831 5552 Siemon North America Headquarters Watertown, Connecticut Tel: (1) 866-548-5814

www.siemon.com

FROM 5e TO 7A

CONCLUSION: When designing and installing structured cabling systems, chose the strongest foundation to support your present and future network applications needs. To ensure support of emerging technologies that utilize the latest advances in signaling schemes, it is critical to be as informed as possible. Trust the TIA and ISO standards developmental groups to specify complete cabling criteria capable of providing applications assurance for tomorrow's technologies today. IMPORTANT DEFINITIONS Alien Crosstalk Unwanted signal coupling from one component, channel, or permanent link to another is defined as alien crosstalk. Since alien crosstalk is an indicator of differential (or balanced) signal coupling, alien crosstalk cannot be adversely impacted by common mode noise (e.g. noise from motors or florescent lights) that is present in the environment. Alien crosstalk is only specified by the Standards as a power sum parameter for components and cabling to approximate the energy present when all pairs are energized. Power sum alien crosstalk measured at the near-end is called power sum alien near-end crosstalk loss (PSANEXT loss) and power sum alien crosstalk measured at the far-end is called power sum alien attenuation to crosstalk ratio, far-end (PSAACRF). High power sum alien crosstalk levels can compromise the operation of the 10GBASE-T application. Attenuation to Crosstalk Ratio, Far-End (ACRF) (previously know as ELEFXT loss) Pair-to-pair far-end crosstalk (FEXT) loss quantifies undesired signal coupling between adjacent pairs at the far-end (the opposite end of the transmit-end) of cabling or a component. ACRF is calculated by subtracting the measured insertion loss from the measured far-end crosstalk loss and yields a normalized value that can be used to compare cable and cabling performance independent of length. Poor ACRF levels can result in increased bit error rates and/or undeliverable signal packets. Note that NEXT loss margin alone is not sufficient to ensure proper ACRF performance. Attenuation to Crosstalk Ratio (ACR) A critical consideration in determining the capability of a cabling system is the difference between insertion loss and near-end crosstalk (NEXT) loss. This difference is known as the attenuation to crosstalk ratio (ACR). Positive ACR calculations mean that transmitted signal strength is stronger than that of near-end crosstalk. ACR can be used to define a signal bandwidth (i.e. 200 MHz for category 6) where signal to noise ratios are sufficient to support certain applications. It is interesting to note that digital signal processing (DSP) technology can perform crosstalk cancellation allowing some applications to expand useable bandwidth up to and beyond the point at which calculated ACR equals zero. Even so, the maximum frequency for which positive ACR is assured provides a benchmark to assess the useable bandwidth of twisted-pair cabling systems. Balance Twisted-pair transmission relies on signal symmetry or "balance" between the two conductors in a pair. Maintaining proper balance ensures that cabling systems and components do not emit unwanted electromagnetic radiation and are not susceptible to electrical noise. Component balance requirements are specified for category 6/class E cabling. Component and cabling balance requirements are specified for category 6A/class EA and higher grades of cabling. Balance may be characterized by longitudinal conversion loss (LCL), longitudinal conversion transfer loss (LCTL), transverse conversion loss (TCL), or equal level transverse converse transfer loss (ELTCTL).

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

Equal Level Far-End Crosstalk (ELFEXT) Loss See definition for Attenuation to Crosstalk Ratio, Far-End. Insertion Loss (Attenuation) Insertion loss is a measure of the decrease in signal strength along the length of a transmission line. Ensuring minimal signal attenuation is critical because digital signal processing (DSP) technology can not compensate for excessive signal loss. Near-End Crosstalk (NEXT) Loss Pair-to-pair near-end crosstalk (NEXT) loss quantifies undesired signal coupling between adjacent pairs at the near-end (the same end as the transmit-end) of cabling or a component. Excessive NEXT loss can be detrimental to applications that do not employ crosstalk cancellation digital signal processing (DSP) technology. Power Sum All pair-to-pair crosstalk parameters can be expressed as a power summation, which approximates the level of undesired internal signal coupling present when all pairs are energized. Power sum NEXT loss, ACRF, ANEXT loss, and AACRF characterization confirms that the cabling is significantly robust to minimize crosstalk from multiple disturbers. This type of characterization is necessary to ensure cabling compatibility with applications that utilize all four pairs for transmitting and receiving signals simultaneously such as 1000BASE-T and applications that are sensitive to alien crosstalk such as 10GBASE-T. Propagation Delay & Delay Skew Propagation delay is the amount of time that passes between when a signal is transmitted and when it is received at the opposite end of a cabling channel. The effect is akin to the delay in time between when lightning strikes and thunder is heard - except that electrical signals travel much faster than sound. Delay skew is the difference between the arrival times of the pair with the least delay and the pair with the most delay. Transmission errors that are associated with excessive delay and delay skew include increased jitter and bit error rates. Return Loss Return loss is a measure of the signal reflections occurring along a transmission line and is related to impedance mismatches that are present throughout a cabling channel. Because emerging applications such as 1000BASE-T and 10GBASE-T rely on full duplex transmission encoding schemes (transmit and receive signals are superimposed over the same conductor pair), they are sensitive to errors that may result from marginal return loss performance. Transfer Impedance Shield effectiveness characterizes the ability of screened (F/UTP) and fully shielded (S/FTP) cables and connecting hardware to maximize immunity from outside noise sources and minimize radiated emissions. Transfer impedance is a measure of shield effectiveness; lower transfer impedance values correlate to better shield effectiveness

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

FROM 5e TO 7A

ABOUT THE AUTHOR Valerie Maguire holds the position of Global Sales Engineer at The Siemon Company. Valerie received her B.S.E.E. degree from the University of Connecticut and actively participates in the development and publication of IEEE 802.3 Ethernet and ANSI/TIA telecommunications standards. She has edited many TIA Standards, including ANSI/TIA-568-B.2-10 (category 6A) and newly published ANSI/TIA-568-C.2 (copper cabling). Valerie is Vice Chair of the TIA TR-42 Telecommunications Cabling Systems Engineering Committee, Vice Chair of the TIA TR-42.7 Copper Cabling Subcommittee, TIA TR-42 appointed liaison to IEEE 802.3, and Treasurer of IEEE 802.3. In addition, Valerie is a frequent speaker at industry conferences. She has authored over 45 technical articles and engineering papers, holds one U.S. Patent, and received the 2008 Harry J. Pfister Award for Excellence in Telecommunications.

CONNECTING THE WORLD TO A HIGHER STANDARD


W W W

S I E M O N

C O M

About Siemon:
Established in 1903, Siemon is an industry leader specializing in the manufacture and innovation of high quality, high-performance network cabling solutions. Headquartered in Connecticut, USA, with global offices, manufacturing and service partners throughout the world, Siemon offers the most comprehensive suite of copper (unshielded and shielded twisted-pair) category 5e, category 6 (Class E), category 6A(Class EA) and category 7/7A (Class F/FA), and multimode and singlemode fiber cabling systems available. With over 400 patents specific to structured cabling, from patch cords to patch panels, Siemon Labs invests heavily in R&D and development of industry standards, underlining the companys long-term commitment to its customers and the industry. www.siemon.com
links:

Shielded Copper Cabling Resource Center Explores Benefits, Advantages and Myths about Shielded Cabling Siemon Offers Free Online Continuing Education Course for AIA/BiCSI Credits Achieve Faster Mechanical Splice Terminations with Siemon XLR8 Free Data Center E-Book from Siemon and Intel: Deploying, Managing and Securing an Efficient Physical Infrastructure Siemon ConvergeIT - Smarter, Greener Buildings