1. Application...........................................................3 2. Available functions...............................................9 3. Differential protection.........................................17 4. Impedance protection........................................19 5. Current protection..............................................21 6. Voltage protection..............................................24 7. Frequency protection.........................................26 8. Multipurpose protection.....................................27 9. Secondary system supervision..........................28 10. Control...............................................................28 11. Logic..................................................................30 12. Monitoring.........................................................30 13. Metering............................................................33 14. Basic IED functions...........................................33 15. Human machine interface.................................33 16. Station communication ....................................34 17. Remote communication....................................35 18. Hardware description........................................36 19. Connection diagrams........................................39 20. Technical data...................................................52 21. Ordering..........................................................108
Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility for any errors that may appear in this document. Copyright 2011 ABB AB. All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
ABB
1MRK 502 031-BEN A Issued: September 2011 Revision: A possibilities to protect more than one object in one IED. It is possible to have protection for an auxiliary power transformer integrated in the same IED having main protections for the generator. The concept thus enables very cost effective solutions. The REG670 also enables valuable monitoring possibilities as many of the process values can be transferred to an operator HMI. The wide application flexibility makes this product an excellent choice for both new installations and for refurbishment in existing power plants. Serial data communication is via optical connections to ensure immunity against disturbances. The wide application flexibility makes this product an excellent choice for both new installations and the refurbishment of existing installations. By using patented algorithm REG670 (or any other product from 670 series) can track the power system frequency in quite wide range from 9Hz to 95Hz. In order to do that preferably the three-phase voltage signal from the generator terminals shall be connected to the IED. Then IED can adopt its filtering algorithm in order to properly measure phasors of all current and voltage signals connected to the IED. This feature is essential for proper operation of the protection during generator start-up and shutdown procedure.
1. Application
The REG670 is used for protection, control and monitoring of generators and generatortransformer blocks from relatively small units up to the largest generating units. The IED has a comprehensive function library, covering the requirements for most generator applications. The large number of analog inputs available enables, together with the large functional library, integration of many functions in one IED. In typical applications two units can provide total functionality, also providing a high degree of redundancy. REG670 can as well be used for protection and control of shunt reactors. Stator earth fault protection, both traditional 95% as well as 100% injection and 3rd harmonic based are included. When the injection based protection is used, 100% of the machine stator winding, including the star point, is protected under all operating modes. The 3rd harmonic based 100% stator earth fault protection uses 3rd harmonic differential voltage principle. Injection based 100% stator earth fault protection can operate even when machine is at standstill. Well proven algorithms for pole slip, underexcitation, rotor earth fault, negative sequence current protections, and so on, are included in the IED. The generator differential protection in the REG670 adapted to operate correctly for generator applications where factors as long DC time constants and requirement on short trip time have been considered. As many of the protection functions can be used as multiple instances there are
ABB
59N
3Uo>
STTI PHIZ Y
D
Y
81
f<
SA PTUF
SA PTOF 78 Ucos
VT
OC4 PTOC
ZMH PDIS 32 P
U U
64R
GEN PDIF
ROV2 PTOV
NS2 PTOC
TR PTTR
59N
UN>
ROV2 PTOV
Figure 1. Generator protection application with generator differential, 100% stator earth fault and back-up protection
ABB
59N
3Uo>
STTI PHIZ
D
Y
VT
OC4 PTOC
AEG GAPC
ZMH PDIS 32 P
U U
64R
GEN PDIF
LEX PDIS
ROV2 PTOV
S
64W IN>
Figure 2. Generator protection application for generator with split winding including generator phase differential, 100% stator earth fault and back-up protection
ABB
Meter. Y
D
Y
VT
OC4 PTOC
AEG GAPC
ZMH PDIS 32 P
U U
64R
GEN PDIF
LEX PDIS
ROV2 PTOV
S
64W IN> 87W 3Id/I
EF4 PTOC
VT
59N
UN>
ROV2 PTOV
64S
RSE<
STTI PHIZ
IEC11000206 V1 EN
Figure 3. Generator protection application for generator with split winding including generator phase differential, generator split-phase differential, 100% stator earth fault and back-up protection
ABB
50/51
3I>
OC4 PTOC
T3W PDIF
Y
Unit Trafo
50/51
3I>
OC4 PTOC Y
D
Y
59N
3Uo>
ROV2 PTOV
Excitation Trafo
Auxiliary Trafo
D
Y
81
f<
81
f>
SA PTUF
SA PTOF 78 Ucos
ZMH PDIS 32 P
U U
64R
GEN PDIF
ROV2 PTOV
Grounding Transformer
ROV2 PTOV
64S
RSE<
STTI PHIZ
IEC11000202 V1 EN
Figure 4. Unit protection application with overall differential, generator differential, 100% stator earth fault and back-up protection. Stator winding grounded via grounding transformer.
ABB
87N
IdN/I
50/51
3I>
49
Ith
Meter. CV MMXU
REF PDIF
OC4 PTOC
TR PTTR
T2W PDIF
50N/51N
IN>
87O
3Id/I
Unit Trafo
EF4 PTOC
T3W PDIF
Y D
50/51 3I>
OC4 PTOC
D
Y 59N 3Uo> ROV2 PTOV 60FL SDD RFUF 51/67 3I-> 81 f< 78 Ucos
D
Y
OC4 PTOC
ZMH PDIS 32 P
U U
64R
GEN PDIF
SA PTOF
NS2 PTOC
TR PTTR
VT
59N
UN>
ROV2 PTOV
STTI PHIZ
Figure 5. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and back-up protection. Ungrounded stator winding.
ABB
87N
IdN/I
50/51
3I>
49
Ith
Meter. CV MMXU
REF PDIF
OC4 PTOC
TR PTTR
T2W PDIF
50N/51N
IN>
87O
3Id/I
Unit Trafo
EF4 PTOC
T3W PDIF
Y D
D
Y
50/51
3I>
ROV2 PTOV
D
Y
VT
81
f<
78
Ucos
OC4 PTOC
ZMH PDIS 32 P
U U
64R
GEN PDIF
SA PTOF
NS2 PTOC
TR PTTR
REG 670*1.2
IEC11000207-1-en.vsd
IEC11000207 V1 EN
Figure 6. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and back-up protection. Stator winding grounded via primary resistor.
ABB
2. Available functions
Main protection functions
2 0-3 = number of basic instances = option quantities
IEC 61850
Generator REG670
Differential protection T2WPDIF T3WPDIF HZPDIF GENDIF REFPDIF 87T 87T 87 87G 87N Transformer differential protection, two winding Transformer differential protection, three winding 1Ph high impedance differential protection Generator differential protection Restricted earth fault protection, low impedance 0-2 0-2 0-6 0-2 0-3
Impedance protection ZMHPDIS ZDMRDIR PSPPPAM LEXPDIS ROTIPHIZ STTIPHIZ 21 21D 78 40 64R 64S Full-scheme distance protection, mho characteristic Directional impedance element for mho characteristic Pole slip/out-of-step protection Loss of excitation Sensitive rotor earth fault protection, injection based 100% stator earth fault protection, injection based 0-4 0-2 0-1 0-2 0-1 0-1
10
ABB
Voltage protection UV2PTUV OV2PTOV ROV2PTOV OEXPVPH VDCPTOV STEFPHIZ 27 59 59N 24 60 59TH D Two step undervoltage protection Two step overvoltage protection Two step residual overvoltage protection Overexcitation protection Voltage differential protection 100% stator earth fault protection, 3rd harmonic based 0-2 0-2 0-3 0-2 0-2 0-1
Frequency protection SAPTUF SAPTOP SAPFRC 81 81 81 Underfrequency protection Overfrequency protection Rate-of-change frequency protection 0-6 0-6 0-3
ABB
11
IEC 61850
ANSI
Function description
Generator REG670
Multipurpose protection CVGAPC 64R General current and voltage protection Rotor earth fault 1-12 1
12
ABB
ABB
13
IEC 61850
Generator REG670
B16IFCVI IB16 IB16FVCB Monitoring CVMMXN CNTGGIO Event DRPRDRE SPGGIO SP16GGIO MVGGIO BSStart Report RANGE_XP Metering PCGGIO ETPMMTR
Boolean 16 to Integer conversion with Logic Node representation Integer to Boolean 16 conversion Integer to Boolean 16 conversion with Logic Node representation
16 16 16
Measurements Event counter Event function Disturbance report IEC61850 generic communication I/O functions IEC61850 generic communication I/O functions 16 inputs IEC61850 generic communication I/O functions Logical signal status report Measured value expander block
6 5 20 1 64 16 24 3 66
16 6
14
ABB
Designed to communicate
IEC 61850 ANSI Function description Generator REG670 Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication protocol Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485 communication protocol DNP3.0 fault records for TCP/IP and EIA-485 communication protocol Redundant station bus communication IEC61850-8-1, PRP Parameter setting function for IEC61850 IntlReceive Horizontal communication via GOOSE for interlocking Goose binary receive Multiple command and transmit Ethernet configuration of links DUODRV Duo driver configuration 1 1 20/1 1 1 1 1 1 59 10 60/10 1 0-1
Remote communication Binary signal transfer receive/transmit Transmission of analog data from LDCM Receive binary status from remote LDCM 6/36 1 6/3/3
ABB
15
Basic functions included in all products IntErrorSig TIME TimeSynch ActiveGroup Test ChangeLock TerminalID Productinfo MiscBaseCommon IEDRuntimeComp RatedFreq SMBI SMBO SMMI SMAI Sum3Ph LocalHMI LocalHMI AuthStatus AuthorityCheck AccessFTP SPACommMap DOSFRNT DOSOEMAB DOSOEMCD Self supervision with internal event list Time and synchronization error Time synchronization Parameter setting groups Test mode functionality Change lock function IED identifiers Product information Misc Base Common IED Runtime Comp Rated system frequency Signal Matrix for binary inputs Signal Matrix for binary outputs Signal Matrix for mA inputs Signal Matrix for analog inputs Summation block 3 phase Parameter setting function for HMI in PCM600 Local HMI signals Authority status Authority check FTP access with password SPA communication mapping Denial of service, frame rate control for front port Denial of service, frame rate control for OEM port AB Denial of service, frame rate control for OEM port CD 1 1 1 1 1 1 1 1 1 1 1 40 40 4 36 18 1 1 1 1 1 1 1 1 1
16
ABB
3. Differential protection
Generator differential protection GENPDIF
Short circuit between the phases of the stator windings causes normally very large fault currents. The short circuit gives risk of damages on insulation, windings and stator iron core. The large short circuit currents cause large forces, which can cause damage even to other components in the power plant, such as turbine and generator-turbine shaft. To limit the damage due to stator winding short circuits, the fault clearance must be as fast as possible (instantaneous). If the generator block is connected to the power system close to other generating blocks, the fast fault clearance is essential to maintain the transient stability of the non-faulted generators. Normally, the short circuit fault current is very large, that is, significantly larger than the generator rated current. There is a risk that a short circuit can occur between phases close to the neutral point of the generator, thus causing a relatively small fault current. The fault current can also be limited due to low excitation of the generator. Therefore, it is desired that the detection of generator phaseto-phase short circuits shall be relatively sensitive, detecting small fault currents. It is also of great importance that the generator differential protection does not trip for external faults, with large fault currents flowing from the generator. To combine fast fault clearance, as well as sensitivity and selectivity, the generator differential protection is normally the best choice for phase-to-phase generator short circuits. Generator differential protection GENPDIF is also well suited to generate fast, sensitive and selective fault clearance, if used to protect shunt reactors or small busbars.
ABB
17
Two-winding applications two-winding power transformer two-winding power transformer with unconnected delta tertiary winding
IEC05000053 V1 EN
xx05000048.vsd
IEC05000048 V1 EN
three-winding power transformer with two circuit breakers and two xx05000053.vsd CT-sets on one side Autotransformer with two circuit breakers and two CT-sets on two out of three sides
xx05000057.vsd
xx05000049.vsd
IEC05000049 V1 EN
IEC05000050 V1 EN
two-winding power xx05000050.vsd transformer with two circuit breakers on one side two-winding power transformer with two circuit breakers and two CT-sets on both sides
IEC05000057 V1 EN
Figure 7. CT group arrangement for differential protection and other protections The setting facilities cover the applications of the differential protection to all types of power transformers and auto-transformers with or without load tap changer as well as for shunt reactors or and local feeders within the station. An adaptive stabilizing feature is included for heavy through-faults.By introducing the load tap changer position, the differential protection pick-up can be set to optimum sensitivity thus covering internal faults with low fault level. Stabilization is included for inrush currents as well as for overexcitation conditions. Adaptive stabilization is also included for system recovery inrush and CT saturation for external faults. A high set unrestrained differential current protection is included for a very high speed tripping at a high internal fault currents. An innovative sensitive differential protection feature, based on the theory of symmetrical components, offers the best possible coverage for power transformer winding turnto-turn faults.
xx05000051.vsd
IEC05000051 V1 EN
Three-winding applications three-winding power transformer with all three windings connected
xx05000052.vsd
IEC05000052 V1 EN
18
ABB
up detection of short circuit and earth faults. The four zones have fully independent measuring and settings, which gives high flexibility for all types of lines. The function can be used as under impedance back-up protection for transformers and generators.
4. Impedance protection
Full-scheme distance measuring, Mho characteristic ZMHPDIS
The numerical mho line distance protection is a four zone full scheme protection for backABB
generator-transformer block. If the centre of pole slip is outside in the power grid, the first action should be to split the network into two parts, after line protection action. If this fails there should be operation of the generator PSPPPAM in zone 2, to prevent further damages to the generator, shaft and turbine.
resistance value is then compared with the preset fault resistance alarm and trip levels. The protection function can detect earth faults in the entire rotor winding and associated connections. Requires injection unit REX060 and a coupling capacitor unit REX061 for correct operation.
20
ABB
circuit breakers, excitation transformer and so on. The measuring principle used is not influenced by the generator operating mode and is fully functional even with the generator at standstill. It is still required to have a standard 95% stator earth-fault protection, based on the neutral point fundamental frequency displacement voltage, operating in parallel with the 100% stator earth-fault protection function. Requires injection unit REX060 and optional shunt resistor unit REX062 for correct operation.
the use for instantaneous earth-fault protection, with the reach limited to less than the typical eighty percent of the line at minimum source impedance. EFPIOC can be configured to measure the residual current from the three-phase current inputs or the current from a separate current input. EFPIOC can be blocked by activating the input BLOCK.
5. Current protection
Instantaneous phase overcurrent protection PHPIOC
The instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow use as a high set short-circuit protection function.
21
ABB
CCRBRF function can be programmed to give a single- or three-phase re-trip of the own breaker to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to mistakes during testing.
By using optional metering class CT inputs accuracy of 0,5% can be achieved for steam turbine applications.
t K
NS2PTOC has a wide range of K settings and the sensitivity and capability of detecting and tripping for negative sequence currents down to the continuous capability of a generator. A separate output is available as an alarm feature to warn the operator of a potentially dangerous situation.
23
ABB
Two step overvoltage protection (OV2PTOV) function can be used to detect open line ends, normally then combined with a directional reactive over-power function to supervise the system voltage. When triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks. OV2PTOV has two voltage steps, each of them with inverse or definite time delayed. OV2PTOV has an extremely high reset ratio to allow settings close to system service voltage.
6. Voltage protection
Two step undervoltage protection UV2PTUV
Undervoltages can occur in the power system during faults or abnormal conditions. Two step undervoltage protection (UV2PTUV) function can be used to open circuit breakers to prepare for system restoration at power outages or as long-time delayed back-up to primary protection. UV2PTUV has two voltage steps, each with inverse or definite time delay.
24
ABB
three phase sets of voltage transformers and has one sensitive alarm step and one trip step.
95% and 100% Stator earth fault protection based on 3rd harmonic STEFPHIZ
Stator earth fault is a fault type having relatively high fault rate. The generator systems normally have high impedance earthing, that is, earthing via a neutral point resistor. This resistor is normally dimensioned to give an earth fault current in the range 3 15 A at a solid earth-fault directly at the generator high voltage terminal. The relatively small earth fault currents give much less thermal and mechanical stress on the generator, compared to the short circuit case, which is between conductors of two phases. Anyhow, the earth faults in the generator have to be detected and the generator has to be tripped, even if longer fault time compared to internal short circuits, can be allowed. In normal non-faulted operation of the generating unit the neutral point voltage is close to zero, and there is no zero sequence current flow in the generator. When a phaseto-earth fault occurs the neutral point voltage will increase and there will be a current flow through the neutral point resistor. To detect an earth fault on the windings of a generating unit one may use a neutral point
overvoltage protection, a neutral point overcurrent protection, a zero sequence overvoltage protection or a residual differential protection. These protections are simple and have served well during many years. However, at best these simple schemes protect only 95% of the stator winding. They leave 5% close to the neutral end unprotected. Under unfavorable conditions the blind zone may extend up to 20% from the neutral. The 95% stator earth fault protection measures the fundamental frequency voltage component in the generator star point and it operates when it exceeds the preset value. By applying this principle approximately 95% of the stator winding can be protected. In order to protect the last 5% of the stator winding close to the neutral end the 3rd harmonic voltage measurement can be performed. In 100% Stator E/F 3rd harmonic protection either the 3rd harmonic voltage differential principle, the neutral point 3rd harmonic undervoltage principle or the terminal side 3rd harmonic overvoltage principle can be applied. However, differential principle is strongly recommended. Combination of these two measuring principles provides coverage for entire stator winding against earth faults.
ABB
25
RN
Rf
Transformer
uN
Samples of the neutral voltage from which the fundamental and 3rd harmonic voltages are filtered out
1- x 1 or 100 %
Neutral point fundamental frequency over-voltage protection 5% - 100%
uT
Samples of the terminal voltage from which the 3rd harmonic voltage is filtered out
IEC10000202-1-en.vsd
7. Frequency protection
Underfrequency protection SAPTUF
Underfrequency occurs as a result of lack of generation in the network. Underfrequency protection SAPTUF is used for load shedding systems, remedial action schemes, gas turbine startup and so on. SAPTUF is provided with an undervoltage blocking. The operation is based on positive sequence voltage measurement and requires two phasephase or three phase-neutral voltages to be connected. For information about how to connect analog inputs, refer to Application manual/IED application/Analog inputs/ Setting guidelines
detection of high fundamental power system frequency is needed. Overfrequency occurs at sudden load drops or shunt faults in the power network. Close to the generating plant, generator governor problems can also cause over frequency. SAPTOF is used mainly for generation shedding and remedial action schemes. It is also used as a frequency stage initiating load restoring. SAPTOF is provided with an undervoltage blocking. The operation is based on positive sequence voltage measurement and requires two phasephase or three phase-neutral voltages to be connected. For information about how to connect analog inputs, refer to Application manual/IED application/Analog inputs/ Setting guidelines
or inverse time characteristic, are available within each function. The general function suits applications with underimpedance and voltage controlled overcurrent solutions. The general function can also be utilized for generator transformer protection applications where positive, negative or zero sequence components of current and voltage quantities are typically required. Additionally, generator applications such as loss of field, inadvertent energizing, stator or rotor overload, circuit breaker head flashover and open phase detection are just a few of possible protection arrangements with these functions.
8. Multipurpose protection
General current and voltage protection CVGAPC
The protection module is recommended as a general backup protection with many possible application areas due to its flexible measuring and setting facilities. The built-in overcurrent protection feature has two settable current levels. Both of them can be used either with definite time or inverse time characteristic. The overcurrent protection steps can be made directional with selectable voltage polarizing quantity. Additionally they can be voltage and/or current controlled/restrained. 2nd harmonic restraining facility is available as well. At too low polarizing voltage the overcurrent feature can be either blocked, made non directional or ordered to use voltage memory in accordance with a parameter setting. Additionally two overvoltage and two undervoltage steps, either with definite time
ABB
voltage. If a rotor earth fault occurs, this condition will be detected by the rotor earth fault protection. Depending on the generator owner philosophy this operational state will be alarmed and/or the generator will be tripped. An injection unit is required for rotor earth fault protection (RXTTE4) and a protective resistor on plate for correct operation.
The fuse failure supervision function basically has three different algorithms, negative sequence and zero sequence based algorithms and an additional delta voltage and delta current algorithm. The negative sequence detection algorithm is recommended for IEDs used in isolated or high-impedance earthed networks. It is based on the negative-sequence measuring quantities, a high value of voltage 3U2 without the presence of the negativesequence current 3I2. The zero sequence detection algorithm is recommended for IEDs used in directly or low impedance earthed networks. It is based on the zero sequence measuring quantities, a high value of voltage 3U0 without the presence of the residual current 3I0. For better adaptation to system requirements, an operation mode setting has been introduced which makes it possible to select the operating conditions for negative sequence and zero sequence based function. The selection of different operation modes makes it possible to choose different interaction possibilities between the negative sequence and zero sequence based algorithm. A criterion based on delta current and delta voltage measurements can be added to the fuse failure supervision function in order to detect a three phase fuse failure, which in practice is more associated with voltage transformer switching during station operations.
10. Control
Synchrocheck, energizing check, and synchronizing SESRSYN
The Synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability.
28
ABB
Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that closing can be done safely. SESRSYN function includes a built-in voltage selection scheme for double bus and 1 breaker or ring busbar arrangements. Manual closing as well as automatic reclosing can be checked by the function and can have different settings. For systems which are running asynchronous a synchronizing function is provided. The main purpose of the synchronizing function is to provide controlled closing of circuit breakers when two asynchronous systems are going to be connected. It is used for slip frequencies that are larger than those for synchrocheck and lower than a set maximum level for the synchronizing function. However this function can not be used to automatically synchronize the generator to the network.
Overriding of synchrocheck Operation counter Suppression of Mid position Two types of command models can be used: Direct with normal security SBO (Select-Before-Operate) with enhanced security In normal security, the command is processed and the resulting position is not supervised. However with enhanced security, the command is processed and the resulting position is supervised. Normal security means that only the command is evaluated and the resulting position is not supervised. Enhanced security means that the command is evaluated with an additional supervision of the status value of the control object. The command security with enhanced security is always terminated by a CommandTermination service primitive. Control operation can be performed from the local HMI under authority control if so defined.
Logic rotating switch for function selection and LHMI presentation SLGGIO
The logic rotating switch for function selection and LHMI presentation function (SLGGIO) (or the selector switch function block) is used to get a selector switch functionality similar to the one provided by a hardware selector switch. Hardware selector switches are used extensively by utilities, in
29
ABB
order to have different functions operating on pre-set values. Hardware switches are however sources for maintenance issues, lower system reliability and an extended purchase portfolio. The logic selector switches eliminate all these problems.
the tripping of the fault. It provides pulse prolongation to ensure a trip pulse of sufficient length, as well as all functionality necessary for correct co-operation with autoreclosing functions. The trip function block includes functionality for evolving faults and breaker lock-out.
12. Monitoring
Measurements CVMMXN, CMMXU, VNMMXU, VMMXU, CMSQI, VMSQI
The measurement functions are used to get online information from the IED. These service values make it possible to display on-line information on the local HMI and on the Substation automation system about: measured voltages, currents, frequency, active, reactive and apparent power and power factor primary and secondary phasors positive, negative and zero sequence currents and voltages mA, input currents pulse counters
11. Logic
Tripping logic SMPPTRC
A function block for protection tripping is provided for each circuit breaker involved in
30
ABB
pre-fault time to the end of post-fault time will be included in the recording. Every disturbance report recording is saved in the IED in the standard Comtrade format. The same applies to all events, which are continuously saved in a ring-buffer. The local HMI is used to get information about the recordings. The disturbance report files may be uploaded to PCM600 for further analysis using the disturbance handling tool.
Indications DRPRDRE
To get fast, condensed and reliable information about disturbances in the primary and/or in the secondary system it is important to know, for example binary signals that have changed status during a disturbance. This information is used in the short perspective to get information via the local HMI in a straightforward way. There are three LEDs on the local HMI (green, yellow and red), which will display status information about the IED and the Disturbance report function (trigged). The Indication list function shows all selected binary input signals connected to the Disturbance report function that have changed status during a disturbance.
ABB
The event recorder logs all selected binary input signals connected to the Disturbance report function. Each recording can contain up to 150 time-tagged events. The event recorder information is available for the disturbances locally in the IED. The event recording information is an integrated part of the disturbance record (Comtrade file).
protection functions. Up to ten seconds of data before the trigger instant can be saved in the disturbance file. The disturbance recorder information for up to 100 disturbances are saved in the IED and the local HMI is used to view the list of recordings.
Event function
When using a Substation Automation system with LON or SPA communication, timetagged events can be sent at change or cyclically from the IED to the station level. These events are created from any available signal in the IED that is connected to the Event function (EVENT). The event function block is used for LON and SPA communication. Analog and double indication values are also transferred through EVENT function.
settable limits: low-low limit, low limit, high limit and high-high limit. The measure value expander block (RANGE_XP) has been introduced to enable translating the integer output signal from the measuring functions to 5 binary signals: below low-low limit, below low limit, normal, above high-high limit or above high limit. The output signals can be used as conditions in the configurable logic or for alarming purpose.
compare event- and disturbance data between all IEDs in a station automation system possible.
13. Metering
Pulse counter logic PCGGIO
Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values. The pulses are captured by the binary input module and then read by the function. A scaled service value is available over the station bus. The special Binary input module with enhanced pulse counting capabilities must be ordered to achieve this functionality.
ABB
33
Existing stations with ABB station bus LON can be extended with use of the optical LON interface. This allows full SA functionality including peer-to-peer messaging and cooperation between existing ABB IED's and the new IED 670.
34
ABB
of simple substation automation systems but the main use is for Substation Monitoring Systems SMS.
ABB
35
mA input module MIM The milli-ampere input module is used to interface transducer signals in the 20 to +20 mA range from for example OLTC position, temperature or pressure transducers. The module has six independent, galvanically separated channels. Optical ethernet module OEM The optical fast-ethernet module is used to connect an IED to the communication buses (like the station bus) that use the IEC 61850-8-1 protocol (port A, B). The module has one or two optical ports with ST connectors. Serial and LON communication module SLM, supports SPA/IEC 60870-5-103, LON and DNP 3.0 The serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103, DNP3 and LON communication. The module has two optical communication ports for plastic/plastic, plastic/glass or glass/glass. One port is used for serial communication (SPA, IEC 60870-5-103 and DNP3 port or dedicated IEC 60870-5-103 port depending on ordered SLM module) and one port is dedicated for LON communication. Line data communication module LDCM Each module has one optical port, one for each remote end to which the IED communicates. Alternative cards for Medium range (1310 nm single mode) and Short range (850 nm multi mode) are available. Galvanic RS485 serial communication module The Galvanic RS485 communication module (RS485) is used for DNP3.0 communication. The module has one RS485 communication port. The RS485 is a balanced serial communication that can be used either in 2wire or 4-wire connections. A 2-wire connection uses the same signal for RX and TX and is a multidrop communication with
ABB
36
no dedicated Master or slave. This variant requires however a control of the output. The 4-wire connection has separated signals for RX and TX multidrop communication with a dedicated Master and the rest are slaves. No special control signal is needed in this case. GPS time synchronization module GTM This module includes a GPS receiver used for time synchronization. The GPS has one SMA contact for connection to an antenna. It also includes an optical PPS ST-connector output. IRIG-B Time synchronizing module The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from a station clock. Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support. Transformer input module TRM The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The module has twelve inputs in different combinations of currents and voltage inputs. Either protection class or metering class CT inputs are available. Alternative connectors of Ring lug or Compression type can be ordered. High impedance resistor unit The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent resistor, is available in a single phase unit and a three phase unit. Both are mounted on a 1/1 19 inch apparatus plate with compression type terminals.
E A
C D
xx05000003.vsd
IEC05000003 V1 EN
ABB
37
xx05000004.vsd
IEC05000004 V1 EN
Figure 12. Side-by-side mounting Case size 6U, 1/2 x 19 6U, 3/4 x 19 6U, 1/1 x 19 A 265.9 265.9 265.9 B 223.7 336.0 448.1 C D E 252.9 252.9 252.9 F 205.7 318.0 430.3 (mm)
Mounting alternatives The following mounting alternatives are available (IP40 protection from the front): 19 rack mounting kit Wall mounting kit
Stator injection module SIM The SIM module is installed into the REX060 enclosure. The SIM module generates a square wave voltage signal for injection into the stator circuit via the neutral point resistor or VT/DT. The SIM module measures the voltage and current from the injected signal and the IED consecutively calculates the stator to earth impedance. If the calculated impedance is lower than the preset value an ALARM and/or TRIP output is set.
38
ABB
Rotor injection module RIM The RIM module is installed into the REX060 enclosure. The RIM module generates a square wave voltage signal for injection into the rotor circuit via a capacitor unit REX061 for isolation. The RIM module measures the voltage and current from the injected signal and the IED consecutively calculates the rotor to earth impedance. If the calculated impedance is lower than the preset value an ALARM and/or TRIP output is set.
Coupling capacitor unit REX061 REX061 isolates the injection circuit from the rotor exciter voltage. The REX061 coupling capacitor unit grounding point and grounding brush of the rotor shaft should be properly interconnected. Shunt resistor unit REX062 REX062 is typically used when injection is done via a grounding transformer.
ABB
39
40
ABB
ABB
41
42
ABB
ABB
43
12I, 1A 12I, 5A 9I+3U, 1A 9I+3U, 5A 5I, 1A +4I, 5A +3U 7I+5U, 1A 7I+5U, 5A 6I, 5A +1I, 1A +5U 3I, 5A +4I, 1A +5U 3IM, 1A +4IP, 1A+5U 3IM, 5A +4IP, 5A+5U 6I+6U, 1A 6I+6U, 5A
1A 5A 1A 5A 1A
1A 5A 1A 5A 1A
1A 5A 1A 5A 1A
1A 5A 1A 5A 1A
1A 5A 1A 5A 1A
1A 5A 1A 5A 5A
1A 5A 1A 5A 5A
1A 5A 1A 5A 5A
1A 5A 1A 5A 5A
1A 5A 5A
1A 5A 5A
1A 5A 5A
1A 5A 5A
1A 5A 5A
1A 5A 5A
1A 5A 1A
5A
5A
5A
1A
1A
1A
1A
110-220V
110-220V
110-220V
110-220V
110-220V
1AM *) 5AM *) 1A 5A
1AM *) 5AM *) 1A 5A
1AM *) 5AM *) 1A 5A
1A
1A
1A
1A
110-220V
110-220V
110-220V
110-220V
110-220V
5A
5A
5A
5A
110-220V
110-220V
110-220V
110-220V
110-220V
1A 5A
1A 5A
1A 5A
110-220V 110-220V
110-220V 110-220V
110-220V 110-220V
110-220V 110-220V
110-220V 110-220V
110-220V 110-220V
44
ABB
5A
5A
5A
1A
1A
1A
110-220V
110-220V
110-220V
110-220V
110-220V
110-220V
1A 5A
1A 5A
1A 5A
1A 5A
1A 5A
1A 5A
*) Metering Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI preprocessing function blocks.
Figure 14. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
ABB
45
46
ABB
Figure 18. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
ABB
47
Figure 20. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
1MRK002501-BA 2 PG V1 EN
48
ABB
1MRK002501-BA 3 PG V1 EN
1MRK002501-BA 4 PG V1 EN
ABB
49
1MRK002501-BA 5 PG V1 EN
1MRK002551-BA 1 PG V1 EN
50
ABB
1MRK002551-BA 2 PG V1 EN
1MRK002556-BA 1 PG V1 EN
ABB
51
1MRK002556-BA 2 PG V1 EN
52
ABB
< 150 mVA at Ir = 5 A < 20 mVA at Ir = 1 A Ur = 110 V (0340) V 420 V cont. 450 V 10 s < 20 mVA at 110 V fr = 50/60 Hz 5% 0.5288 V
ABB
53
Table 7. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Current Permissive overload Rated value Ir = 1 or 5 A 1.1 Ir cont. 1.8 Ir for 30 min at Ir = 1A 1.6 Ir for 30 min at Ir = 5A < 350 mVA at Ir = 5 A < 200 mVA at Ir = 1 A Ur = 110 V (0340) V 420 V cont. 450 V 10 s < 20 mVA at 110 V fr = 50/60 Hz 5% 0.5288 V Nominal range (0-1.8) Irat Ir = 1 A (0-1.6) Irat Ir = 5 A
Burden Ac voltage Operative range Permissive overload Burden Frequency Table 8. MIM - mA input module Quantity: Input resistance Input range Power consumption each mA-board each mA input
Rated value: Rin = 194 Ohm 5, 10, 20mA 0-5, 0-10, 0-20, 4-20mA 2W 0.1 W
Nominal range: -
Table 9. OEM - Optical ethernet module Quantity Number of channels Standard Type of fiber Wave length Optical connector Communication speed Rated value 1 or 2 IEEE 802.3u 100BASE-FX 62.5/125 mm multimode fibre 1300 nm Type ST Fast Ethernet 100 MB
54
ABB
Auxiliary DC voltage Table 10. PSM - Power supply module Quantity Auxiliary dc voltage, EL (input) Power consumption Auxiliary DC power in-rush Binary inputs and outputs Table 11. BIM - Binary input module Quantity Binary inputs DC voltage, RL Rated value 16 24/30 V 48/60 V 110/125 V 220/250 V Nominal range RL RL RL RL 20% 20% 20% 20% Rated value EL = (24 - 60) V EL = (90 - 250) V 50 W typically < 5 A during 0.1 s Nominal range EL 20% EL 20% -
Power consumption 24/30 V 48/60 V 110/125 V 220/250 V Counter input frequency Oscillating signal discriminator
ABB
55
Table 12. BIM - Binary input module with enhanced pulse counting capabilities Quantity Binary inputs DC voltage, RL Rated value 16 24/30 V 48/60 V 110/125 V 220/250 V Nominal range RL RL RL RL 20% 20% 20% 20%
Power consumption 24/30 V 48/60 V 110/125 V 220/250 V Counter input frequency Balanced counter input frequency Oscillating signal discriminator
10 pulses/s max 40 pulses/s max Blocking settable 140 Hz Release settable 130 Hz
Table 13. IOM - Binary input/output module Quantity Binary inputs DC voltage, RL Rated value 8 24/30 V 48/60 V 110/125 V 220/250 V Nominal range RL RL RL RL max. max. max. max. 0.05 W/input 0.1 W/input 0.2 W/input 0.4 W/input 20% 20% 20% 20%
56
ABB
Table 14. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Binary outputs Max system voltage Trip and signal relays 10 250 V AC, DC Fast signal relays (parallel reed relay) 2 250 V AC, DC 800 V DC 8A 10 A
Test voltage across open contact, 1 min 1000 V rms Current carrying capacity Continuous 1s Making capacity at inductive load with L/R>10 ms 0.2 s 1.0 s Breaking capacity for AC, cos > 0.4 8A 10 A
30 A 10 A 250 V/8.0 A
0.4 A 0.4 A 250 V/8.0 A 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A 10 nF
Breaking capacity for DC with L/R < 40 48 V/1 A ms 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Maximum capacitive load -
ABB
57
Table 15. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Rated voltage Number of outputs Impedance open state Test voltage across open contact, 1 min Current carrying capacity: Continuous 1.0s Making capacity at capacitive load with the maximum capacitance of 0.2 F : 0.2s 1.0s 30A 10A 30A 10A 110V / 0.4A 125V / 0.35A 220V / 0.2A 250V / 0.15A Operating time <1ms <1ms 5A 10A 5A 10A Static binary output trip 48 - 60 VDC 6 ~300 k No galvanic separation 110 - 250 VDC 6 ~810 k No galvanic separation
58
ABB
Table 16. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Max system voltage Number of outputs Test voltage across open contact, 1 min Current carrying capacity: Continuous 1.0s Making capacity at capacitive load with the maximum capacitance of 0.2 F: 0.2s 1.0s Breaking capacity for DC with L/R 40ms 30A 10A 48V / 1A 110V / 0.4A 125V / 0,35A 220V / 0,2A 250V / 0.15A Table 17. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Binary outputs Max system voltage Test voltage across open contact, 1 min Current carrying capacity Continuous 1s Making capacity at inductive load with L/R>10 ms 0.2 s 1.0 s Breaking capacity for AC, cos j>0.4 Breaking capacity for DC with L/R < 40 ms Trip and Signal relays 24 250 V AC, DC 1000 V rms 8A 10 A 30 A 10 A 250 V/8.0 A 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A 8A 10A Trip and signal relays 250V AC/DC 6 1000V rms
ABB
59
Influencing factors Table 18. Temperature and humidity influence Parameter Ambient temperature, operate value Relative humidity Operative range Storage temperature Reference value +20 C Nominal range -10 C to +55 C Influence 0.02% /C
10%-90% -
Table 19. Auxiliary DC supply voltage influence on functionality during operation Dependence on Ripple, in DC auxiliary voltage Operative range Auxiliary voltage dependence, operate value Interrupted auxiliary DC voltage Interruption interval 050 ms 0 s Restart time Table 20. Frequency influence (reference standard: IEC 602551) Dependence on Frequency dependence, operate value Harmonic frequency dependence (20% content) Harmonic frequency dependence for high impedance differential protection (10% content) Within nominal range fr 2.5 Hz for 50 Hz fr 3.0 Hz for 60 Hz 2nd, 3rd and 5th harmonic of fr 2nd, 3rd and 5th harmonic of fr Influence 1.0% / Hz 1.0% 5.0% Reference value max. 2% Full wave rectified Within nominal range 15% of EL Influence 0.01% /%
0.01% /%
60
ABB
IEC 60255-22-4, Class A IEC 60255-22-5 IEC 60255-22-7, Class A IEC 61000-4-16, Class IV IEC 61000-4-8, Class V IEC 61000-4-10, Class V IEC 60255-22-3
Power frequency magnetic field test 1000 A/m, 3 s 100 A/m, cont. Damped oscillatory magnetic field test Radiated electromagnetic field disturbance Radiated electromagnetic field disturbance Conducted electromagnetic field disturbance Radiated emission Conducted emission 100 A/m 20 V/m, 80-1000 MHz 1.4-2.7 GHz 35 V/m 26-1000 MHz 10 V, 0.15-80 MHz 30-1000 MHz 0.15-30 MHz
ABB
61
Table 22. Insulation Test Dielectric test Impulse voltage test Insulation resistance Table 23. Environmental tests Test Cold test Storage test Dry heat test Damp heat test, steady state Damp heat test, cyclic Type test value Test Ad for 16 h at -25C Test Ad for 16 h at -40C Test Bd for 16 h at +70C Test Ca for 4 days at +40 C and humidity 93% Test Db for 6 cycles at +25 to +55 C and humidity 93 to 95% (1 cycle = 24 hours) Reference standard IEC 60068-2-1 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-78 IEC 60068-2-30 Type test values 2.0 kV AC, 1 min. 5 kV, 1.2/50 ms, 0.5 J >100 MW at 500 VDC Reference standard IEC 60255-5
Table 24. CE compliance Test Immunity Emissivity Low voltage directive Table 25. Mechanical tests Test Vibration response test Vibration endurance test Shock response test Shock withstand test Bump test Seismic test Type test values Class II Class I Class II Class I Class I Class II Reference standards IEC 60255-21-1 IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-2 IEC 60255-21-2 IEC 60255-21-3 According to EN 50263 EN 50263 EN 50178
62
ABB
Injection equipment
Table 26. Electromagnetic compatibility tests Test 1 MHz burst disturbance 100 kHz slow damped oscillatory wave immunity test Surge withstand capability test Electrostatic discharge Direct application Indirect application Electrostatic discharge Direct application Indirect application Fast transient disturbance test Surge immunity test Type test values 2.5 kV 2.5 kV 2.5 kV, oscillatory 4.0 kV, fast transient 15 kV air discharge 8 kV contact discharge 8 kV contact discharge 15 kV air discharge 8 kV contact discharge 8 kV contact discharge 4 kV 1-2 kV, and 2-4 kV, 1.2/50 s High energy 150-300 V, 50 Hz Reference standards IEC 60255-22-1 IEC 61000-4-18, Class III IEEE/ANSI C37.90.1 IEC 60255-22-2, Class IV IEC 61000-4-2, Class IV IEEE/ANSI C37.90.3
IEC 60255-22-7, Class A IEC 61000-4-8, Class 5 IEC 60255-22-3 IEEE/ANSI C37.90.2 IEC 60255-22-6 IEC 60255-11
Power frequency magnetic field test 1000 A/m, 3 s 100 A/m, cont. Radiated electromagnetic field disturbance test Radiated electromagnetic field disturbance test Conducted electromagnetic field disturbance test 20 V/m, 80-1000 MHz 1.4-2.7 GHz 20 V/m, 80-1000 MHz 10 V, 0.15-80 MHz
Voltage dips and short interruptions Dips: 40% /200 ms 70% /500 ms Interruptions: 0-50 ms: No restart 0 s: Correct behaviour at power down Radiated emission Conducted emission 30-1000 MHz 0.15-30 MHz
ABB
63
Table 27. Insulation tests, REX060, REX062 and REG670 Test Dielectric test Impulse voltage test Insulation resistance Table 28. Insulation tests, REX061 Test Dielectric test Type test values 7.48 kV DC, 1min (connections to rotor) 2.8 kV DC, 1 min Impulse voltage test Reference standard IEEE 421.3 Type test values 2.0 kV AC, 1 min 5.0 kV, 1.2/50 s, 0.5 J >100 M at 500V DC Reference standard IEC 60255-5 IEC 60255-5 IEC 60255-5
IEC 60255-5
12.0 kV, 1.2/50 s, 0.5 IEC 60664-1 J (connections to rotor) 5.0 kV, 1.2/50 s, 0.5 J IEC 60255-5
Insulation resistance Table 29. Mechanical tests Test Vibration response test Vibration endurance test REG670 and REX060 REX061 and REX062 Shock response test Shock withstand test REG670 and REX060 REX061 and REX062 Bump test REG670 and REX060 REX061 and REX062 Seismic test REG670 and REX060 REX061 and REX062
>100 M at 500V DC
IEC 60255-5
64
ABB
Table 30. Environmental tests Test Cold test operation storage Dry heat test operation storage Damp heat test steady state cyclic Type test value 16 h at -25C 16 h at -40C IEC 60068-2-2 16 h at +70C 16 h at +85C 240 h at +40C humidity 93% 6 cycles at +25 to +55C humidity 93-95% IEC 60068-2-78 IEC 60068-2-30 Reference standard IEC 60068-2-1
Table 31. Auxiliary DC supply voltage influence Test Auxiliary voltage dependence, operate value Ripple in DC auxiliary voltage, operate value Type test values 20% of EL 15% of EL Influence 0.01% /C 0.01% /C
Table 32. Temperature influence Test Ambient temperature, operate value Storage temperature Type test values -25 C to +55C -40 C to +85C Influence 0.01% /C -
Table 33. Degree of protection Description REX060 Front side Panel mounted, front Rear side, connection terminals REX061 and REX062 Front and side Bottom side Values IP40 IP54 IP20 IP41 IP20
ABB
65
Differential protection
Table 34. Generator differential protection GENPDIF Function Reset ratio Unrestrained differential current limit Base sensitivity function Negative sequence current level Operate time, restrained function Reset time, restrained function Operate time, unrestrained function Reset time, unrestrained function Operate time, negative sequence unrestrained function Range or value > 95% (1-50)p.u. of IBase (0.051.00)p.u. of IBase (0.020.2)p.u. of IBase 25 ms typically at 0 to 2 x set level 20 ms typically at 2 to 0 x set level 12 ms typically at 0 to 5 x set level 25 ms typically at 5 to 0 x set level 15 ms typically at 0 to 5 x set level Accuracy 2.0% of set value 2.0% of Ir 1.0% of Ir -
66
ABB
Table 35. Transformer differential protection T2WPDIF, T3WPDIF Function Operating characteristic Reset ratio Unrestrained differential current limit Base sensitivity function Second harmonic blocking Range or value Adaptable >95% (100-5000)% ofIBase on high voltage winding (10-60)% of IBase Accuracy 1.0% of Ir for I < Ir 1.0% of Ir for I > Ir 1.0% of set value
1.0% of Ir
(5.0-100.0)% of 2.0% of Ir fundamental differential current (5.0-100.0)% of 5.0% of Ir fundamental differential current Y or D 011 -
Connection type for each of the windings Phase displacement between high voltage winding, W1 and each of the windings, W2 and W3. Hour notation Operate time, restrained function Reset time, restrained function Operate time, unrestrained function Reset time, unrestrained function Critical impulse time
ABB
67
Table 36. Restricted earth fault protection, low impedance REFPDIF Function Operate characteristic Reset ratio Base sensitivity function Directional characteristic Range or value Adaptable >95% (4.0-100.0)% of IBase Accuracy 1.0% of Ir for I < IBase 1.0% of I for I > IBase 1.0% of Ir
Operate time, trip function 20 ms typically at 0 to 10 x IdMin Reset time, trip function 25 ms typically at 10 to 0 x IdMin
Table 37. 1Ph High impedance differential protection HZPDIF Function Operate voltage Reset ratio Range or value (20-400) V I=U/R >95% Accuracy 1.0% of Ir -
Maximum continuous voltage U>Trip2/series resistor 200 W Operate time Reset time Critical impulse time 10 ms typically at 0 to 10 x Ud 90 ms typically at 10 to 0 x Ud 2 ms typically at 0 to 10 x Ud
68
ABB
Impedance protection
Table 38. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Number of zones with selectable directions Minimum operate current Positive sequence impedance, phase-toearth loop Positive sequence impedance angle, phaseto-earth loop Reverse reach, phase-toearth loop (Magnitude) Magnitude of earth return compensation factor KN Angle for earth compensation factor KN Dynamic overreach Range or value 4 with selectable direction (1030)% of IBase (0.0053000.000) W/ phase (1090) degrees Accuracy 2.0% static accuracy Conditions: Voltage range: (0.1-1.1) x Ur Current range: (0.5-30) x Ir Angle: at 0 degrees and 85 degrees
(0.0053000.000) / phase (0.003.00) (-180180) degrees <5% at 85 degrees measured with CVTs and 0.5<SIR<30 (0.000-60.000) s 20 ms typically (with static outputs) 105% typically 30 ms typically -
0.5% 10 ms -
Table 39. Pole slip protection PSPPPAM Function Impedance reach Characteristic angle Start and trip angles Zone 1 and Zone 2 trip counters Range or value (0.001000.00)% of Zbase (72.0090.00) degrees (0.0180.0) degrees (1-20) Accuracy 2.0% of Ur/Ir 5.0 degrees 5.0 degrees -
ABB
69
Table 40. Loss of excitation LEXPDIS Function X offset of Mho top point Diameter of Mho circle Timers Range or value (1000.001000.00)% of ZBase (0.003000.00)% of ZBase (0.006000.00) s Accuracy 2.0% of Ur/Ir 2.0% of Ur/Ir 0.5% 10 ms
Table 41. ROTIPHIZ technical data Function Fault resistance sensitivity Range or value Can be reached Typically Injection frequency Trip limit of fault resistance (75.000 - 250.000) Hz (100 - 100000) Accuracy 500 k 50 k 0.1 Hz 5% of 1 k at Rf 1 k 5% of set value at 1 k < Rf 20 k 10% of set value at Rf > 20 k 5% of 1 k at Rf 1 k 5% of 10 k at 1 k < Rf 20 k 10% of set value at 20 k < Rf 200 k 0.5% 10 ms
70
ABB
Table 42. STTIPHIZ technical data Function Fault resistance sensitivity Range or value Can be reached at steady state operating condition of the machine Typically Injection frequency Trip limit of fault resistance (50.000 - 250.000) Hz (100 - 10000) Accuracy 50 k
10 k 0.1 Hz 5% of 1 k at Rf 1 k 10% of set value at Rf > 1 k 5% of 1 k at Rf 1 k 10% of 10 k at 1 k < Rf 10 k 50% of set value at Rf > 10 k 0.5% 10 ms
ABB
71
Current protection
Table 43. Instantaneous phase overcurrent protection PHPIOC Function Operate current Range or value (1-2500)% of lBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio Operate time Reset time Critical impulse time Operate time Reset time Critical impulse time Dynamic overreach > 95% 25 ms typically at 0 to 2 x Iset 25 ms typically at 2 to 0 x Iset 10 ms typically at 0 to 2 x Iset 10 ms typically at 0 to 10 x Iset 35 ms typically at 10 to 0 x Iset 2 ms typically at 0 to 10 x Iset < 5% at t = 100 ms -
72
ABB
Table 44. Four step phase overcurrent protection OC4PTOC Function Operate current Setting range (1-2500)% of lBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio Min. operating current > 95% (1-100)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir Relay characteristic angle (RCA) Maximum forward angle Minimum forward angle 2nd harmonic blocking Independent time delay Minimum operate time Inverse characteristics, see table 105, table 106 and table 107 Operate time, start function Reset time, start function Critical impulse time Impulse margin time (-70.0 -50.0) degrees (40.070.0) degrees (75.090.0) degrees (5100)% of fundamental (0.000-60.000) s (0.000-60.000) s 19 curve types 2.0 degrees 2.0 degrees 2.0 degrees 2.0% of Ir 0.5% 10 ms 0.5% 10 ms See table 105, table 106 and table 107 -
ABB
73
Table 45. Instantaneous residual overcurrent protection EFPIOC Function Operate current Range or value (1-2500)% of lBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio Operate time Reset time Critical impulse time Operate time Reset time Critical impulse time Dynamic overreach > 95% 25 ms typically at 0 to 2 x Iset 25 ms typically at 2 to 0 x Iset 10 ms typically at 0 to 2 x Iset 10 ms typically at 0 to 10 x Iset 35 ms typically at 10 to 0 x Iset 2 ms typically at 0 to 10 x Iset < 5% at t = 100 ms -
74
ABB
Table 46. Four step residual overcurrent protection EF4PTOC Function Operate current Range or value (1-2500)% of lBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio Operate current for directional comparison Timers Inverse characteristics, see table 105, table 106 and table 107 Second harmonic restrain operation Relay characteristic angle Minimum polarizing voltage Minimum polarizing current Real part of source Z used for current polarization Imaginary part of source Z used for current polarization Operate time, start function Reset time, start function Critical impulse time Impulse margin time > 95% (1100)% of lBase (0.000-60.000) s 18 curve types 1.0% of Ir 0.5% 10 ms See table 105, table 106 and table 107 2.0% of Ir 2.0 degrees 0.5% of Ur 0.25% of Ir -
(5100)% of fundamental (-180 to 180) degrees (1100)% of UBase (1-30)% of IBase (0.50-1000.00) W/phase
(0.503000.00) W/phase
ABB
75
Table 47. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir 0.5% 10 ms See table 105, table 106 and table 107 1.0% of Ir at I < Ir 1.0% of I at I > Ir 1.0% of Ir
Operate value, negative (1-2500)% of lBase sequence current, step 1-4 Reset ratio Timers Inverse characteristics, see table 105, table 106 and table 107 Minimum operate current for step 1 - 4 Operate value, negative current for directional release Relay characteristic angle Minimum polarizing voltage Minimum polarizing current Real part of negative sequence source impedance used for current polarization Imaginary part of negative sequence source impedance used for current polarization Operate time, start function Reset time, start function > 95% (0.000-60.000) s 18 curve types
(0.503000.00) W/phase
Critical impulse time, start 10 ms typically at 0 to 2 x Iset function Impulse margin time, start function Transient overreach 15 ms typically <10% at = 100 ms
76
ABB
Table 48. Sensitive directional residual overcurrent and power protection SDEPSDE Function Operate level for 3I0cosj directional residual overcurrent Range or value (0.25-200.00)% of lBase At low setting: (2.5-10) mA (10-50) mA (0.25-200.00)% of SBase At low setting: (0.25-5.00)% of SBase (0.25-200.00)% of lBase At low setting: (2.5-10) mA (10-50) mA (1.00-400.00)% of lBase At low setting: (10-50) mA Operate level for nondirectional residual overvoltage Residual release current for all directional modes (1.00-200.00)% of UBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir 0.5 mA 1.0 mA 1.0% of Sr at S Sr 1.0% of S at S > Sr 10% of set value 1.0% of Ir at Ir 1.0% of I at I > Ir 0.5 mA 1.0 mA 1.0% of Ir at I Ir 1.0% of I at I > Ir 1.0 mA 0.5% of Ur at UUr 0.5% of U at U > Ur (0.25-200.00)% of lBase At low setting: (2.5-10) mA (10-50) mA Residual release voltage for all directional modes Reset ratio Timers Inverse characteristics, see table 105, table 106 and table 107 Relay characteristic angle RCA Relay open angle ROA (0.01-200.00)% of UBase 1.0% of Ir at I Ir 1.0% of I at I > Ir 0.5 mA 1.0 mA 0.5% of Ur at UUr 0.5% of U at U > Ur > 95% (0.000-60.000) s 19 curve types 0.5% 10 ms See table 105, table 106 and table 107 2.0 degrees 2.0 degrees
Operate level for 3I03U0 cosj directional residual power Operate level for 3I0 and j residual overcurrent
ABB
77
Table 48. Sensitive directional residual overcurrent and power protection SDEPSDE, continued Function Operate time, nondirectional residual over current Reset time, nondirectional residual over current Operate time, start function Reset time, start function Range or value 60 ms typically at 0 to 2 x Iset Accuracy -
60 ms typically at 2 to 0 x Iset
Table 49. Thermal overload protection, two time constants TRPTTR Function Base current 1 and 2 Operate time:
I 2 - I p2 t = t ln 2 I - Ib 2
EQUATION1356 V1 EN
Range or value (30250)% of IBase Ip = load current before overload occurs Time constant = (1500) minutes
(Equation 1)
I = Imeasured Alarm level 1 and 2 Operate current Reset level temperature (5099)% of heat content trip value (50250)% of IBase (1095)% of heat content trip 2.0% of heat content trip 1.0% of Ir 2.0% of heat content trip
78
ABB
Table 50. Breaker failure protection CCRBRF Function Operate phase current Range or value (5-200)% of lBase Accuracy 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio, phase current Operate residual current > 95% (2-200)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir Reset ratio, residual current Phase current level for blocking of contact function Reset ratio Timers Operate time for current detection Reset time for current detection > 95% (5-200)% of lBase 1.0% of Ir at I Ir 1.0% of I at I > Ir > 95% (0.000-60.000) s 10 ms typically 15 ms maximum 0.5% 10 ms -
Table 51. Pole discordance protection CCRPLD Function Operate current Time delay Range or value (0100)% of IBase (0.000-60.000) s Accuracy 1.0% of Ir 0.5% 10 ms
Table 52. Directional underpower protection GUPPDUP Function Power level Range or value (0.0500.0)% of SBase At low setting: (0.5-2.0)% of SBase (2.0-10)% of SBase Characteristic angle Timers (-180.0180.0) degrees (0.00-6000.00) s Accuracy 1.0% of Sr at S < Sr 1.0% of S at S > Sr < 50% of set value < 20% of set value 2 degrees 0.5% 10 ms
ABB
79
Table 53. Directional overpower protection GOPPDOP Function Power level Range or value (0.0500.0)% of Sbase At low setting: (0.5-2.0)% of Sbase (2.0-10)% of Sbase Characteristic angle Timers (-180.0180.0) degrees (0.00-6000.00) s Accuracy 1.0% of Sr at S < Sr 1.0% of S at S > Sr < 50% of set value < 20% of set value 2 degrees 0.5% 10 ms
Table 54. Negative sequence time overcurrent protection for machines NS2PTOC Function Operate value, step 1 and 2, negative sequence overcurrent Reset ratio, step 1 and 2 Operate time, start Reset time, start Time characteristics Inverse time characteristic step 1, I 2 t = K Reset time, inverse characteristic step 1, K=0.01-20.00 Class 10 + 40 ms
2
>95% 20 ms typically at 0 to 2 x Iset 15 ms typically at 0 to 10 x Iset 30 ms typically at 2 to 0 x Iset Definite or Inverse K=1.0-99.0
I 22t = K
Maximum trip delay, step 1 IDMT Minimum trip delay, step 1 IDMT Timers (0.00-6000.00) s (0.000-60.000) s (0.00-6000.00) s 0.5% 10 ms 0.5% 10 ms 0.5% 10 ms
80
ABB
Table 55. Accidental energizing protection for synchronous generator AEGGAPC Function Operate value, overcurrent Reset ratio, overcurrent Transient overreach, overcurrent function Critical impulse time, overcurrent Impulse margin time, overcurrent Operate value, undervoltage Critical impulse time, undervoltage Impulse margin time, undervoltage Operate value, overvoltage Timers Range or value (2-900)% of IBase >95% <10% at = 100 ms 10 ms typically at 0 to 2 x Iset 10 ms typically (2-200)% of UBase 10 ms typically at 2 to 0 x Uset 15 ms typically (2-200)% of UBase (0.000-60.000) s Accuracy 1,0% of Ir at I<Ir 1.0% of I at I>Ir 0.5% of Ur at U<Ur 0.5% of U at U>Ur 0.5% of Ur at U<Ur 0.5% of U at U>Ur 0.5% 10 ms
ABB
81
Voltage protection
Table 56. Two step undervoltage protection UV2PTUV Function Operate voltage, low and high step Absolute hysteresis Internal blocking level, low and high step Inverse time characteristics for low and high step, see table 109 Definite time delays Minimum operate time, inverse characteristics Operate time, start function Reset time, start function Critical impulse time Impulse margin time Range or value (1100)% of UBase (0100)% of UBase (1100)% of UBase Accuracy 0.5% of Ur 0.5% of Ur 0.5% of Ur See table 109
0.5% 10 ms 0.5% 10 ms -
Table 57. Two step overvoltage protection OV2PTOV Function Operate voltage, low and high step Absolute hysteresis Inverse time characteristics for low and high step, see table 108 Definite time delays Minimum operate time, Inverse characteristics Operate time, start function Reset time, start function Critical impulse time Impulse margin time Range or value (1-200)% of UBase (0100)% of UBase Accuracy 0.5% of Ur at U < Ur 0.5% of U at U > Ur 0.5% of Ur at U < Ur 0.5% of U at U > Ur See table 108
0.5% 10 ms 0.5% 10 ms -
82
ABB
Table 58. Two step residual overvoltage protection ROV2PTOV Function Operate voltage, low and high step Absolute hysteresis Inverse time characteristics for low and high step, see table 110 Definite time setting Minimum operate time Operate time, start function Reset time, start function Critical impulse time Impulse margin time Range or value (1-200)% of UBase (0100)% of UBase Accuracy 0.5% of Ur at U < Ur 1.0% of U at U > Ur 0.5% of Ur at U < Ur 1.0% of U at U > Ur See table 110
0.5% 10 ms 0.5% 10 ms -
Table 59. Overexcitation protection OEXPVPH Function Operate value, start Operate value, alarm Operate value, high level Curve type Range or value (100180)% of (UBase/frated) (50120)% of start level (100200)% of (UBase/frated) IEEE or customer defined
IEEE : t = (0.18 k ) ( M - 1) 2
EQUATION1319 V1 EN
(Equation 2)
where M = (E/f)/(Ur/fr) Minimum time delay for inverse function Maximum time delay for inverse function Alarm time delay (0.00060.000) s (0.009000.00) s (0.00060.000) s 0.5% 10 ms 0.5% 10 ms 0.5% 10 ms
ABB
83
Table 60. Voltage differential protection VDCPTOV Function Voltage difference for alarm and trip Under voltage level Timers Range or value (0.0100.0) % of UBase (0.0100.0) % of UBase (0.00060.000)s Accuracy 0.5 % of Ur 0.5% of Ur 0.5% 10 ms
Table 61. 100% Stator E/F 3rd harmonic STEFPHIZ Function Fundamental frequency level UN (95% Stator EF) Third harmonic differential level Third harmonic differential block level Timers Filter characteristic: Fundamental Third harmonic Range or value (1.050.0)% of UBase (0.510.0)% of UBase (0.110.0)% of UBase (0.02060.000) s Reject third harmonic by 140 Reject fundamental harmonic by 140 Accuracy 0.5% of Ur 0.5% of Ur 0.5% of Ur 0.5% 10 ms -
84
ABB
Frequency protection
Table 62. Underfrequency protection SAPTUF Function Operate value, start function Operate time, start function Reset time, start function Operate time, definite time function Reset time, definite time function Voltage dependent time delay Range or value (35.00-75.00) Hz 100 ms typically 100 ms typically (0.000-60.000)s (0.000-60.000)s Accuracy 2.0 mHz 0.5% 10 ms 0.5% 10 ms Class 5 + 200 ms
Settings: UNom=(50-150)% of Exponent U - UMin Ubase t= ( tMax - tMin ) + tMin UNom - UMin UMin=(50-150)% of Ubase (Equation 3) Exponent=0.0-5.0 tMax=(0.000-60.000)s U=Umeasured tMin=(0.000-60.000)s
EQUATION1182 V1 EN
Table 63. Overfrequency protection SAPTOF Function Operate value, start function Range or value (35.00-75.00) Hz Accuracy 2.0 mHz at symmetrical three-phase voltage 0.5% 10 ms 0.5% 10 ms
Operate time, definite time function (0.000-60.000)s Reset time, definite time function (0.000-60.000)s
Table 64. Rate-of-change frequency protection SAPFRC Function Operate value, start function Operate value, internal blocking level Operate time, start function Range or value (-10.00-10.00) Hz/s (0-100)% of UBase 100 ms typically Accuracy 10.0 mHz/s 0.5% of Ur -
ABB
85
Multipurpose protection
Table 65. General current and voltage protection CVGAPC Function Measuring current input Range or value phase1, phase2, phase3, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph (1 - 99999) A phase1, phase2, phase3, PosSeq, -NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph (0.05 - 2000.00) kV Accuracy -
Base voltage
1.0% of Ir for I<Ir 1.0% of I for I>Ir 1.0% of Ir for I<Ir 1.0% of I for I>Ir 0.5% 10 ms See table 105 and table 106
Start overcurrent, step 1 and 2 (2 - 5000)% of IBase Start undercurrent, step 1 and 2 Definite time delay Operate time start overcurrent Reset time start overcurrent Operate time start undercurrent Reset time start undercurrent See table 105 and table 106 (2 - 150)% of IBase (0.00 - 6000.00) s 25 ms typically at 0 to 2 x Iset 25 ms typically at 2 to 0 x Iset 25 ms typically at 2 to 0 x Iset 25 ms typically at 0 to 2 x Iset Parameter ranges for customer defined characteristic no 17: k: 0.05 - 999.00 A: 0.0000 - 999.0000 B: 0.0000 - 99.0000 C: 0.0000 - 1.0000 P: 0.0001 - 10.0000 PR: 0.005 - 3.000 TR: 0.005 - 600.000 CR: 0.1 - 10.0
86
ABB
Table 65. General current and voltage protection CVGAPC , continued Function Voltage level where voltage memory takes over Range or value (0.0 - 5.0)% of UBase Accuracy 0.5% of Ur 0.5% of Ur for U<Ur 0.5% of U for U>Ur 0.5% of Ur for U<Ur 0.5% of U for U>Ur 1.0% of Ur for U<Ur 1.0% of U for U>Ur 2.0 degrees 2.0 degrees -
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of UBase Start undervoltage, step 1 and 2 Operate time, start overvoltage Reset time, start overvoltage Operate time start undervoltage Reset time start undervoltage High and low voltage limit, voltage dependent operation Directional function Relay characteristic angle Relay operate angle Reset ratio, overcurrent Reset ratio, undercurrent Reset ratio, overvoltage Reset ratio, undervoltage Overcurrent: Critical impulse time Impulse margin time Undercurrent: Critical impulse time Impulse margin time Overvoltage: Critical impulse time Impulse margin time 10 ms typically at 0 to 2 x Uset 15 ms typically 10 ms typically at 2 to 0 x Iset 15 ms typically 10 ms typically at 0 to 2 x Iset 15 ms typically (2.0 - 150.0)% of UBase 25 ms typically at 0 to 2 x Uset 25 ms typically at 2 to 0 x Uset 25 ms typically 2 to 0 x Uset 25 ms typically at 0 to 2 x Uset (1.0 - 200.0)% of UBase Settable: NonDir, forward and reverse (-180 to +180) degrees (1 to 90) degrees > 95% < 105% > 95% < 105%
ABB
87
Table 65. General current and voltage protection CVGAPC , continued Function Undervoltage: Critical impulse time Impulse margin time 10 ms typically at 2 to 0 x Uset 15 ms typically Range or value Accuracy
Table 66. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4 Function For machines with: rated field voltage up to 350 V DC static exciter with rated supply voltage up to Supply voltage 120 or 230 V Operate earth fault resistance value Influence of harmonics in the DC field voltage Permitted leakage capacitance Permitted shaft earthing resistance Protective resistor 700 V 50/60 Hz Range or value Accuracy
88
ABB
ABB
89
Control
Table 69. Synchronizing, synchrocheck and energizing check SESRSYN Function Phase shift, jline - jbus Voltage ratio, Ubus/Uline Range or value (-180 to 180) degrees (0.40-25.000) % of UBaseBus and UBaseLIne Accuracy 0.5% of Ur at U Ur 0.5% of U at U >Ur 2.0 mHz 2.0 degrees 0.5% of Ur 0.5% 10 ms 0.5% of Ur at U Ur 0.5% of U at U >Ur 0.5% of Ur 0.5% of Ur at U Ur 0.5% of U at U >Ur 0.5% 10 ms -
Voltage high limit for synchronizing (50.0-120.0)% of and synchrocheck UBaseBus and UBaseLIne Reset ratio, synchrocheck Frequency difference limit between bus and line Phase angle difference limit between bus and line Voltage difference limit between bus and line > 95% (0.003-1.000) Hz (5.0-90.0) degrees (0.02-0.5) p.u
Time delay output for synchrocheck (0.000-60.000) s Voltage high limit for energizing check Reset ratio, voltage high limit Voltage low limit for energizing check Reset ratio, voltage low limit Maximum voltage for energizing (50.0-120.0)% of UBaseBus and UBaseLIne > 95% (10.0-80.0)% of UBase < 105% (50.0-180.0)% of UBaseBus and/or UBaseLIne (0.000-60.000) s 160 ms typically
Time delay for energizing check Operate time for synchrocheck function
90
ABB
Logic
Table 70. Tripping logic SMPPTRC Function Trip action Range or value 3-ph, 1/3-ph, 1/2/3-ph Accuracy 0.5% 10 ms 0.5% 10 ms
Table 71. Configurable logic blocks Logic block Quantity with cycle time fast LogicAND LogicOR LogicXOR LogicInverter LogicSRMemory LogicRSMemory LogicGate LogicTimer LogicPulseTimer LogicTimerSet LogicLoopDelay 60 60 10 30 10 10 10 10 10 10 10 medium 60 60 10 30 10 10 10 10 10 10 10 6 4 4 normal 160 160 20 80 20 20 20 20 20 20 20 8 8 (0.00090000.000) s (0.00090000.000) s (0.00090000.000) s (0.00090000.000) s 0.5% 10 ms 0.5% 10 ms 0.5% 10 ms 0.5% 10 ms Range or value Accuracy
Trip Matrix Logic 6 Boolean 16 to Integer Boolean 16 to integer with Logic Node Integer to Boolean 16 Integer to Boolean 16 with Logic Node 4 4
4 4
4 4
8 8
ABB
91
Monitoring
Table 72. Measurements CVMMXN Function Frequency Voltage Range or value (0.95-1.05) fr (0.1-1.5) Ur (0.2-4.0) Ir 0.1 x Ur< U < 1.5 x Ur 0.2 x Ir < I < 4.0 x Ir 0.1 x Ur< U < 1.5 x Ur 0.2 x Ir < I < 4.0 x Ir 0.1 x Ur < U < 1.5 x Ur 0.2 x Ir< I < 4.0 x Ir 0.1 x Ur < U < 1.5 x Ur 0.2 x Ir< I < 4.0 x Ir 0.02 Accuracy 2.0 mHz 0.5% of Ur at UUr 0.5% of U at U > Ur Connected current 0.5% of Ir at I Ir 0.5% of I at I > Ir Active power, P Reactive power, Q Apparent power, S 1.0% of Sr at S Sr 1.0% of S at S > Sr Conditions: 0.8 x Ur < U < 1.2 Ur 0.2 x Ir < I < 1.2 Ir
Table 73. Supervision of mA input signals Function mA measuring function Max current of transducer to input Min current of transducer to input Alarm level for input Warning level for input Alarm hysteresis for input Range or value 5, 10, 20 mA 0-5, 0-10, 0-20, 4-20 mA (-20.00 to +20.00) mA (-20.00 to +20.00) mA (-20.00 to +20.00) mA (-20.00 to +20.00) mA (0.0-20.0) mA Accuracy 0.1 % of set value 0.005 mA
Table 74. Event counter CNTGGIO Function Counter value Max. count up speed Range or value 0-10000 10 pulses/s Accuracy -
92
ABB
Table 75. Disturbance report DRPRDRE Function Pre-fault time Post-fault time Limit time Maximum number of recordings Time tagging resolution Maximum number of analog inputs Maximum number of binary inputs Maximum number of phasors in the Trip Value recorder per recording Maximum number of indications in a disturbance report Maximum number of events in the Event recording per recording Maximum number of events in the Event list Maximum total recording time (3.4 s recording time and maximum number of channels, typical value) Sampling rate Recording bandwidth Table 76. Event list Function Buffer capacity Resolution Accuracy Maximum number of events in the list Value 1000 1 ms Depending on time synchronizing Range or value (0.059.90) s (0.110.0) s (0.510.0) s 100, first in - first out 1 ms 30 + 10 (external + internally derived) 96 30 96 150 1000, first in - first out 340 seconds (100 recordings) at 50 Hz, 280 seconds (80 recordings) at 60 Hz 1 kHz at 50 Hz 1.2 kHz at 60 Hz (5-300) Hz Accuracy See table 101 -
ABB
93
Table 77. Indications Function Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances Table 78. Event recorder Function Buffer capacity Value Maximum number of events in disturbance report 150 Maximum number of disturbance reports Resolution Accuracy 100 1 ms Depending on time synchronizing Value 96 100
Table 79. Trip value recorder Function Buffer capacity Maximum number of analog inputs Maximum number of disturbance reports Table 80. Disturbance recorder Function Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Value 40 96 Value 30 100
Maximum number of disturbance reports 100 Maximum total recording time (3.4 s recording time and maximum number of channels, typical value) 340 seconds (100 recordings) at 50 Hz 280 seconds (80 recordings) at 60 Hz
94
ABB
Metering
Table 81. Pulse counter PCGGIO Function Input frequency Cycle time for report of counter value Setting range See Binary Input Module (BIM) (13600) s Accuracy -
Table 82. Energy metering ETPMMTR Function Energy metering Range or value kWh Export/Import, kvarh Export/Import Accuracy Input from MMXU. No extra error at steady load
ABB
95
Station communication
Table 83. IEC 61850-8-1 communication protocol Function Protocol Communication speed for the IEDs Table 84. LON communication protocol Function Protocol Communication speed Table 85. SPA communication protocol Function Protocol Communication speed Slave number Value SPA 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd 1 to 899 Value LON 1.25 Mbit/s Value IEC 61850-8-1 100BASE-FX
Table 86. IEC60870-5-103 communication protocol Function Protocol Communication speed Table 87. SLM LON port Quantity Optical connector Fibre, optical budget Fibre diameter Range or value Glass fibre: type ST Plastic fibre: type HFBR snap-in Glass fibre: 11 dB (1000 m typically *) Plastic fibre: 7 dB (10 m typically *) Glass fibre: 62.5/125 mm Plastic fibre: 1 mm Value IEC 60870-5-103 9600, 19200 Bd
96
ABB
Table 88. SLM SPA/IEC 60870-5-103/DNP3 port Quantity Optical connector Fibre, optical budget Fibre diameter Range or value Glass fibre: type ST Plastic fibre: type HFBR snap-in Glass fibre: 11 dB (3000ft/1000 m typically *) Plastic fibre: 7 dB (80ft/25 m typically *) Glass fibre: 62.5/125 mm Plastic fibre: 1 mm
*) depending on optical budget calculation Table 89. Galvanic RS485 communication module Quantity Communication speed External connectors Range or value 240019200 bauds RS-485 6-pole connector Soft ground 2-pole connector
Table 90. Duo driver configuration DUODRV Function Protocol Communication speed Value IEC 61850-8-1 100 Base-FX
ABB
97
Remote communication
Table 91. Line data communication module Characteristic Type of LDCM Type of fibre Range or value Short range (SR) Graded-index multimode 62.5/125 m or 50/125 m 850 nm 13 dB (typical distance about 3 km *) 9 dB (typical distance about 2 km *) Medium range (MR) Singlemode 9/125 m Long range (LR) Singlemode 9/125 m
1310 nm
1550 nm
Type ST C37.94
Data transmission
Synchronous
Synchronous
Transmission rate / Data rate 2 Mb/s / 64 kbit/s Clock source Internal or derived from received signal
2 Mb/s / 64 kbit/ 2 Mb/s / 64 kbit/s s Internal or derived from received signal Internal or derived from received signal
*) depending on optical budget calculation **) C37.94 originally defined just for multimode; using same header, configuration and data format as C37.94
98
ABB
Hardware
IED Table 92. Case Material Front plate Surface treatment Finish Steel sheet Steel sheet profile with cut-out for HMI Aluzink preplated steel Light grey (RAL 7035)
Table 93. Water and dust protection level according to IEC 60529 Front Rear, sides, top and bottom Table 94. Weight Case size 6U, 1/2 x 19 6U, 3/4 x 19 6U, 1/1 x 19 Connection system Table 95. CT and VT circuit connectors Connector type Screw compression type Terminal blocks suitable for ring lug terminals Rated voltage and current 250 V AC, 20 A 250 V AC, 20 A Maximum conductor area 4 mm2 (AWG12) 2 x 2.5 mm2 (2 x AWG14) 4 mm2 (AWG12) Weight 10 kg 15 kg 18 kg IP40 (IP54 with sealing strip) IP20
Table 96. Binary I/O connection system Connector type Screw compression type Terminal blocks suitable for ring lug terminals Rated voltage 250 V AC 300 V AC Maximum conductor area 2.5 mm2 (AWG14) 2 1 mm2 (2 x AWG18) 3 mm2 (AWG14)
ABB
99
Injection equipment hardware Table 97. Injection unit REX060 Specifications Case size Weight Firmware Table 98. Coupling capacitor unit REX061 Function For machines with: rated field voltage up to static exciter with rated supply voltage up to Specifications Case size Weight Assembling Table 99. Shunt resistor unit REX062 Specifications Case size Weight Assembling Values 218 x 150 x 243 mm (W x D x H) 4.5 kg 6 x 5 mm screws (3 at bottom and 3 at top) 800 V DC 1600 V 50/60 Hz Range or values Accuracy Values 6U, 1/2 19; 223.7 x 245 x 267 mm (W x D x H) 8.0 kg 1p0r00, loaded in the HMI & Logic module
100
ABB
Table 101. Time synchronization, time tagging Function Time tagging resolution, events and sampled measurement values Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled measurement values Time tagging error with SNTP synchronization, sampled measurement values Table 102. GPS time synchronization module (GTM) Function Receiver Time to reliable time reference with antenna in new position or after power loss longer than 1 month Time to reliable time reference after a power loss longer than 48 hours Time to reliable time reference after a power loss shorter than 48 hours Table 103. GPS Antenna and cable Function Max antenna cable attenuation Antenna cable impedance Lightning protection Antenna cable connector Value 26 db @ 1.6 GHz 50 ohm Must be provided externally SMA in receiver end TNC in antenna end Range or value <30 minutes Accuracy 1s relative UTC Value 1 ms 1.0 ms typically 1.0 ms typically
ABB
101
Table 104. IRIG-B Quantity Number of channels IRIG-B Number of channels PPS Electrical connector IRIG-B Optical connector PPS and IRIG-B Type of fibre Pulse-width modulated Amplitude modulated low level high level Rated value 1 1 BNC Type ST 62.5/125 m multimode fibre 5 Vpp 1-3 Vpp 3 x low level, max 9 Vpp
102
ABB
Inverse characteristic
Table 105. ANSI Inverse time characteristics Function Operating characteristic:
t =
Accuracy -
A P ( I - 1)
+ B k
EQUATION1249-SMALL V1 EN
Reset characteristic:
t =
(I
tr
2
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset ANSI Extremely Inverse ANSI Very inverse ANSI Normal Inverse ANSI Moderately Inverse ANSI Long Time Extremely Inverse ANSI Long Time Very Inverse ANSI Long Time Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1 A=19.61, B=0.491, P=2.0 , tr=21.6 A=0.0086, B=0.0185, P=0.02, tr=0.46 A=0.0515, B=0.1140, P=0.02, tr=4.85 A=64.07, B=0.250, P=2.0, tr=30 A=28.55, B=0.712, P=2.0, tr=13.46 k=(0.05-999) in steps of 0.01 A=0.086, B=0.185, P=0.02, tr=4.6 ANSI/IEEE C37.112, class 5 + 40 ms
ABB
103
Accuracy -
A P k ( I - 1)
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset Time delay to reset, IEC inverse time IEC Normal Inverse IEC Very inverse IEC Inverse IEC Extremely inverse IEC Short time inverse IEC Long time inverse Programmable characteristic Operate characteristic:
t =
(0.000-60.000) s A=0.14, P=0.02 A=13.5, P=1.0 A=0.14, P=0.02 A=80.0, P=2.0 A=0.05, P=0.04 A=120, P=1.0
A P (I - C )
+ B k
EQUATION1370-SMALL V1 EN
Reset characteristic:
t =
k = (0.05-999) in steps of 0.01 IEC 60255, class 5 + A=(0.005-200.000) in steps of 0.001 40 ms B=(0.00-20.00) in steps of 0.01 C=(0.1-10.0) in steps of 0.1 P=(0.005-3.000) in steps of 0.001 TR=(0.005-100.000) in steps of 0.001 CR=(0.1-10.0) in steps of 0.1 PR=(0.005-3.000) in steps of 0.001
(I
TR
PR
- CR
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
104
ABB
Table 107. RI and RD type inverse time characteristics Function RI type inverse characteristic
t = 1 k
0.339 -
0.236 I
EQUATION1137-SMALL V1 EN
I k
I = Imeasured/Iset
ABB
105
Table 108. Inverse time characteristics for overvoltage protection Function Type A curve:
t =
U -U > U>
EQUATION1436-SMALL V1 EN
k 480
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k 480
- 0.035
EQUATION1438-SMALL V1 EN
Programmable curve:
t = kA +D
U -U > U >
-C
EQUATION1439-SMALL V1 EN
k = (0.05-1.10) in steps of 0.01 unless otherwise stated A = (0.005-200.000) in steps of 0.001 B = (0.50-100.00) in steps of 0.01 C = (0.0-1.0) in steps of 0.1 D = (0.000-60.000) in steps of 0.001 P = (0.000-3.000) in steps of 0.001
106
ABB
Table 109. Inverse time characteristics for undervoltage protection Function Type A curve:
t = k
U < -U
U<
EQUATION1431-SMALL V1 EN
EQUATION1432-SMALL V1 EN
+D
k = (0.05-1.10) in steps of 0.01 unless otherwise stated A = (0.005-200.000) in steps of 0.001 B = (0.50-100.00) in steps of 0.01 C = (0.0-1.0) in steps of 0.1 D = (0.000-60.000) in steps of 0.001 P = (0.000-3.000) in steps of 0.001
ABB
107
Table 110. Inverse time characteristics for residual overvoltage protection Function Type A curve:
t =
U -U > U>
EQUATION1436-SMALL V1 EN
k 480
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k 480
- 0.035
EQUATION1438-SMALL V1 EN
Programmable curve:
t = kA +D
B U - U > U >
-C
EQUATION1439-SMALL V1 EN
k = (0.05-1.10) in steps of 0.01 A = (0.005-200.000) in steps of 0.001 B = (0.50-100.00) in steps of 0.01 C = (0.0-1.0) in steps of 0.1 D = (0.000-60.000) in steps of 0.001 P = (0.000-3.000) in steps of 0.001
108
ABB
21. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Please refer to the available functions table for included application functions.
Product specification
Basic IED 670 platform and common functions housed in selected casing REG670 Quantity: 1MRK 002 826-AC
Default: The IED connect CD contains configuration alternative. Use the PCM600 to create or modify the configuration. The PCM600 can also be used for adaptation of an included example configuration. Option: Customer specific configuration On request
Logic
Rule: One Tripping logic must be ordered Tripping logic (SMPPTRC) Qty:
1 2 3 4 5 6
Optional functions
ABB
109
Differential protection
Transformer differential protection, two winding (T2WPDIF) Qty:
1 2
Qty:
Qty:
1
Qty:
Impedance protection
Rule: If one of ZMHPDIS or ZDMRDIR is ordered, both functions must be ordered Full scheme distance protection, mho characteristic (ZMHPDIS) Directional impedance element for mho characteristic (ZDMRDIR)
Qty:
Qty:
Qty:
1 2
Qty:
Note: If ROTIPHIZ or STTIPHIZ is ordered, Injection equipment is also required, see section Accessories, "Injection equipment" Sensitive rotor earth fault protection, injection based (ROTIPHIZ) 100% stator earth fault protection, injection based (STTIPHIZ) Qty: Qty: 1MRK 002 908-YA 1MRK 002 908-ZA
110
ABB
Current protection
Instantaneous phase overcurrent protection (PHPIOC) Qty:
1 2
Qty:
Qty:
1 2 3 4
Qty:
Four step directional negative phase sequence overcurrent protection (NS4PTOC) Sensitive directional residual overcurrent and power protection (SDEPSDE) Thermal overload protection, two time constants (TRPTTR) Breaker failure protection (CCRBRF)
Qty:
Qty:
1
Qty:
1
Qty
Qty:
Qty:
Qty:
Negative sequence time overcurrent protection for machines (NS2PTOC) Accidental energizing protection for synchronous generator (AEGGAPC)
Qty:
Qty:
ABB
111
Voltage protection
Two step undervoltage protection (UV2PTUV) Qty:
1 2
Qty:
1
Qty:
Qty:
Voltage differential protection (VDCPTOV) 100% Stator E/F 3rd harmonic (STEFPHIZ)
Qty: Qty:
Frequency protection
Underfrequency protection (SAPTUF) Qty:
1 2 3 4 5 6
Qty:
Qty:
Multipurpose protection
General current and voltage protection (CVGAPC) Qty:
1 7 2 8 3 9 4 5 6
10 11 12
Qty:
112
ABB
Control
Synchrocheck, energizing check and synchronizing (SESRSYN) Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking Tap changer control and supervision, 6 binary inputs, coded binary (Binary, BCD, Gray) (TCMYLTC) Tap changer control and supervision, 32 binary inputs, one per position (TCLYLTC) Qty:
1 2 3 4
Qty:
Qty:
Station communication
Duo driver configuration (DUODRV) 1MRK 002 924-YA
Optional hardware
Human machine hardware interface
Rule: One must be ordered.
Display type
Small, alpha numeric Small, alpha numeric Small, alpha numeric Medium, graphic display Medium, graphic display Medium, graphic display Medium, graphic display Medium, graphic display Medium, graphic display
Keypad symbol
IEC IEC IEC IEC IEC IEC ANSI ANSI ANSI
Case size
1/2 19" 3/4 19" 1/1 19" 1/2 19" 1/1 19" 3/4 19" 1/2 19" 3/4 19" 1/1 19" 1MRK 000 008-HB 1MRK 000 008-PB 1MRK 000 008-KB 1MRK 000 008-LB 1MRK 000 008-MB 1MRK 000 008-NB 1MRK 000 008-LC 1MRK 000 008-NC 1MRK 000 008-MC
ABB
113
Analog system
Rule: One Transformer input module must be ordered Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals 12I, 1A, 50/60 Hz Transformer input module, compression terminals 12I, 5A, 50/60 Hz Transformer input module, compression terminals 9I+3U, 1A, 50/60 Hz Transformer input module, compression terminals 9I+3U, 5A, 50/60 Hz Transformer input module, compression terminals 5I, 1A+4I, 5A+3U, 50/60 Hz Transformer input module, compression terminals 7I+5U, 1A, 50/60 Hz Transformer input module, compression terminals 7I+5U, 5A, 50/60 Hz Transformer input module, compression terminals 6I, 5A+1I, 1A+5U, 50/60 Hz Transformer input module, compression terminals 3I, 5A+4I, 1A+5U, 50/60 Hz Transformer input module, compression terminals 3IM, 1A+4IP, 1A+5U, 50/60 Hz Transformer input module, compression terminals 3IM, 5A+4IP, 5A+5U, 50/60 Hz Transformer input module, compression terminals 6I+6U, 1A, 50/60 Hz Transformer input module, compression terminals 6I+6U, 5A, 50/60 Hz Transformer input module, compression terminals 3I, 5A+3I, 1A+6U, 50/60 Hz Transformer input module, compression terminals 6I, 5A, 50/60 Hz Transformer input module, compression terminals 6I, 1A, 50/60 Hz Qty: Qty: Qty: Qty: Qty: Qty: Qty: Qty: Qty: Qty:
Qty:
Qty:
Qty: Qty:
Qty:
Qty:
114
ABB
Transformer input module, ring lug terminals 12I, 1A, 50/60 Hz Transformer input module, ring lug terminals 12I, 5A, 50/60 Hz Transformer input module, ring lug terminals 9I+3U, 1A, 50/60 Hz Transformer input module, ring lug terminals 9I+3U, 5A, 50/60 Hz Qty: Transformer input module, ring lug terminals 5I, 1A+4I, 5A+3U, 50/60 Hz Transformer input module, ring lug terminals 7I+5U, 1A, 50/60 Hz Transformer input module, ring lug terminals 7I+5U, 5A, 50/60 Hz Qty: Transformer input module, ring lug terminals 6I, 5A+1I, 1A+5U, 50/60 Hz 3I, 5A+4I, 1A+5U, 50/60 Hz 3IM, 1A+4IP, 1A+5U, 50/60 Hz 3IM, 5A+4IP, 5A+5U, 50/60 Hz Qty: Qty: Qty: Qty: Qty:
Qty:
Qty: Qty:
Qty:
Transformer input module, ring lug terminals 6I+6U, 1A, 50/60 Hz Transformer input module, ring lug terminals 6I+6U, 5A, 50/60 Hz Transformer input module, ring lug terminals 3I, 5A+3I, 1A+6U, 50/60 Hz Qty: Qty: Qty:
ABB
115
Transformer input module, ring lug terminals 6I, 1A, 50/60 Hz Transformer input module, ring lug terminals 6I, 5A, 50/60 Hz Qty: Qty:
Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
Case size
When ordering I/O modules, observe the maximum quantities according to tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed. Note: Maximum quantity of I/O modules depends on the type of connection terminals.
Maximum quantity of I/O modules, with ring lug terminals, module limits see above
Case sizes 1/1 x 19, one (1) TRM 1/1 x 19, two (2) TRM 3/4 x 19, one (1) TRM 3/4 x 19, two (2) TRM 1/2 x 19, one (1) TRM Maximum in case 7 5 4 2 1 Possible locations for I/O modules with ringlugs P3, P5, P7, P9, P11, P13, P15 P3, P5, P7, P9, P11 P3, P5, P7, P9 P3, P5 P3 1MRK 000 151-NC 1MRK 000 151-ND 1MRK 000 151-NB 1MRK 000 151-NE 1MRK 000 151-NA
116
ABB
11 12 13 14
RL 48-60 VDC, 30 mA
Qty:
1 8
2 9
3 10
11 12 13 14
RL 110-125 VDC, 30 mA
Qty:
1 8
2 9
3 10
11 12 13 14
RL 220-250 VDC, 30 mA
Qty:
1 8
2 9
3 10
11 12 13 14
RL 24-30 VDC, 50 mA
Qty:
1 8
2 9
3 10
11 12 13 14
RL 48-60 VDC, 50 mA
Qty:
1 8
2 9
3 10
11 12 13 14
RL 110-125 VDC, 50 mA
Qty:
1 8
2 9
3 10
11 12 13 14
ABB
117
RL 220-250 VDC, 50 mA
Qty:
1 8
2 9
3 10
11 12 13 14
Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs RL 24-30 VDC Qty:
1 8 2 9 3 10 4 5 6 7
11 12 13 14
RL 48-60 VDC
Qty:
1 8
2 9
3 10
11 12 13 14
RL 110-125 VDC
Qty:
1 8
2 9
3 10
11 12 13 14
RL 220-250 VDC
Qty:
1 8
2 9
3 10
11 12 13 14
Qty:
RL 110-250 VDC
Qty:
118
ABB
Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased. IOM with 30 mA inrush current is still available. Binary input/output module (IOM) 8 inputs, 10 outputs, 2 high-speed outputs RL 24-30 VDC, 30 mA Qty:
1 2 3 4 5 6
RL 48-60 VDC, 30 mA
Qty:
RL 110-125 VDC, 30 mA
Qty:
RL 220-250 VDC, 30 mA
Qty:
RL 24-30 VDC, 50 mA
Qty:
RL 48-60 VDC, 50 mA
Qty:
RL 110-125 VDC, 50 mA
Qty:
RL 220-250 VDC, 50 mA
Qty:
Binary input/output module (IOM with MOV), 8 inputs, 10 outputs, 2 high-speed outputs RL 24-30 VDC Qty:
1 2 3 4 5 6
RL 48-60 VDC
Qty:
RL 110-125 VDC
Qty:
RL 220-250 VDC
Qty:
Qty:
ABB
119
Qty:
Time synchronization
Rule: Only one Time synchronization can be ordered. GPS Time module (GTM) IRIG-B Time synchronization module 1MRK 002 282-AB 1MRK 002 305-AA
Engineering facilities
19 rack mounting kit for 1/2 x 19 case or 2 x RHGS6 or RHGS12 Quantity: 1MRK 002 420-BB
Quantity:
Quantity:
120
ABB
Note: Wall mounting not recommended with communication modules with fibre connection (SLM, OEM, LDCM) Wall mounting kit for terminal Flush mounting kit for terminal
Quantity:
Quantity:
Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be specified when ordering a terminal.
Quantity:
Accessories
GPS antenna and mounting details
GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA
Quantity:
Quantity:
Quantity:
Test switch The test system COMBITEST intended for use with the IED 670 products is described in 1MRK 512 001-BEN and 1MRK 001024-CA. Please refer to the website: www.abb.com/ substationautomation for detailed information. Due to the high flexibility of our product and the wide variety of applications possible the test switches needs to be selected for each specific application. Select your suitable test switch based on the available contacts arrangements shown in the reference documentation. However our proposals for suitable variants are:
Two winding transformer with internal neutral on current circuits. Two pcs can be used in applications for three winding transformers in single or multi-breaker arrangement (ordering number RK926 215BD) Two winding transformer with external neutral on current circuits. Two pcs can be used in applications for three winding transformers in single or multi-breaker arrangement (ordering number RK926 215BH). Three winding transformer with internal neutral on current circuits (ordering number RK926 215-BX). The normally open "In test mode" contact 29-30 on the RTXP test switches should be connected to the input of the test function
121
ABB
block to allow activation of functions individually during testing. Test switches type RTXP 24 is ordered separately. Please refer to Section "Related documents" for reference to corresponding documents. Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and the on/off switch for dc-supply are ordered separately. Please refer to Section "Related documents" for reference to corresponding documents.
Quantity:
Quantity:
Quantity:
Quantity:
RK795101-MA RK795101-MB
Quantity: Quantity:
RK795101-CB RK795101-DC
122
ABB
Injection equipment
Rule: If ROTIPHIZ or STTIPHIZ is ordered, Injection equipment is required. Injection unit (REX060) Casing 1/2 x 19" rack casing Backplane module (BPM) Human machine interface HMI and logic module (HLM) Injection modules Rule: Stator injection module (SIM) is required if 100% stator earth fault protection, injection based (STTIPHIZ) is selected/ active in REG670 Stator injection module (SIM) Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection, injection based (ROTIPHIZ) is selected/active in REG670 Rotor injection module (RIM) Power supply module Rule: One Power supply module must be specified Power supply module (PSM) 24-60 VDC 90-250 VDC Mounting details with IP40 of protection from the front 19" rack mounting kit Wall mounting kit for terminal Flush mounting kit for terminal Extra IP54 mounting seal + Flush mounting kit for terminal 1MRK 002 420-BB 1MRK 002 420-DA 1MRK 000 020-Y 1MRK 002 420-EA 1MRK 002 239-AB 1MRK 002 239-BB 1MRK 002 544-BA 1MRK 002 544-AA Basic Basic Basic Quantity: 1MRK 002 500-AA
Rule: REX061 requires REX060 and that Rotor injection module (RIM) is selected in REX060 and that Sensitive rotor earth fault protection, injection based (ROTIPHIZ) is selected/active in REG670. Coupling capacitor unit (REX061) Rule: REX062 requires REX060 and that Stator injection module (SIM) is selected in REX060 and that 100% stator earth fault protection, injection based (STTIPHIZ) is selected/active in REG670 Shunt resistor unit (REX062) Quantity: 1MRK 002 555-AA Quantity: 1MRK 002 550-AA
Combiflex
ABB 123
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used. Side-by-side mounting kit Quantity: 1MRK 002 420-Z
Quantity:
Quantity:
RK795102-AD
Quantity:
Quantity:
Manuals
Note: One (1) IED Connect CD containing user documentation (Operators manual, Technical reference manual, Installation and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED. Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
124
ABB
User documentation Rule: Specify the number of printed manuals requested Operators manual IEC Quantity: 1MRK 502 028-UEN
ANSI
Quantity:
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
ANSI
Quantity:
Application manual
IEC
Quantity:
ANSI
Quantity:
Quantity:
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country:
End user:
Station name: Generator manufacturer: Type of prime mover: steam , gas , hydro
ABB
125
Related documents
Documents related to REG670
Operators manual Installation and commissioning manual Technical reference manual Application manual Product guide customized Product guide pre-configured Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670 Connection and Installation components Test system, COMBITEST Accessories for 670 series IEDs 670 series SPA and signal list IEC 61850 Data objects list for 670 series Engineering manual 670 series Buyers guide REG 216 Communication set-up for Relion 670 series More information can be found on www.abb.com/substationautomation.
Identity number
1MRK 502 028-UEN 1MRK 502 029-UEN 1MRK 502 027-UEN 1MRK 502 030-UEN 1MRK 502 031-BEN 1MRK 502 032-BEN 1MRG001910 1MRK 513 003-BEN 1MRK 512 001-BEN 1MRK 514 012-BEN 1MRK 500 092-WEN 1MRK 500 091-WEN 1MRK 511 240-UEN 1MRB520004-BEN 1MRK 505 260-UEN
126
ABB
127
Contact us
ABB AB Substation Automation Products SE-721 59 Vsters, Sweden Phone +46 (0) 21 32 50 00 Fax +46 (0) 21 14 69 18 www.abb.com/substationautomation