The PRF1/PRF1 Master surge arrester range is suitable for use with all earthing systems: TT, TNS, TNC, IT. Type 1 surge arresters are tested with a 10/350 s current wave.
PRF1/PRF1 Master
The Type 1 PRF1/PRF1 Master surge arrester protects electrical installations against direct lightning strokes. It is recommended for electrical installations in tertiary and industrial buildings protected by a lightning conductor or by a meshed cage. It is used to run to earth a direct lightning current propagated through the live conductors and the earth conductor. It must be installed with an upstream fuse type or circuit-breaker type protection (disconnection) device whose breaking capacity must be at least equal to the maximum prospective short-circuit current at the installation point.
DB108607
Product solution
1P+N 3P+N
PRF1 16621 + 16623 16625 3 x 16621 + 16624 16628 PRF1 combined PRF1 Master 16626 16629
PB101094-30
PB101095-30
PB101096-30
16621
PB101101-35
16622
PB101106-37
16623
PB101097-30
16624
16626
16629
90271E_Ver2.1.indd/2
21 mars 2007
DB108608
Earthing system
2P 3P
3 x 16621 16627
Disconnection circuit-breaker
Technical data Cat. no.
D125 cat. no.: 18533 D125 cat. no.: 18533 D125 cat. no.: 18532 D125 cat. no.: 18532 D125 cat. no.: 18534 D125 cat. no.: 18534 Integrated NS160N TM160D cat. no.: 30620 NS160N TM160D cat. no.: 30630 NS160N TM160D cat. no.: 30650
4P
TNC TNC, IT non-distributed neutral TT, TNS TT, TNS, IT distributed neutral TT, TNS TT, TNS, IT distributed neutral TT, TNS TT, TNS 16643 16641
125 A D curve
TT, TNS, IT (1) distributed neutral TT, TNS, IT (1) distributed neutral (1) Without led version.
16643 16645
160 A D curve
PB101102-30
PB101099-30
16625
PB101956-50
16627
PB101104-30
16628
16630
21 mars 2007
90271E_Ver2.1.indd/3
In - kA
Nominal discharge current
Up - kV
Un - V Uc - V
Cat. no.
Voltage Rated Maximum protection voltage continuous level network operating voltage
Operating frequency Biconnect Degree of protection Response time End-of-life indication: PRF1: 16621, Combi PRF1: 16626, 16629, 16630 with led breaking capacity (with protection device) connection by tunnel terminal :
Green Off PRF1 PRF1 Master PRF1, combis PRF1 PRF1 Master
50/60 Hz by fork type comb busbar front panel: IP40 terminals: IP20 y 1 s correct operation at end of life 6 kA / 230 V, 3 kA / 400 V 36 kA / 230 V, 8 kA / 400 V Rigid cable: 10...25 mm Flexible cable: 10...25 mm Rigid cable: 10...50 mm Flexible cable: 10...35 mm -40 C... +85 C IEC 61643-1 T1 , EN 61643-11 Type 1
90271E_Ver2.1.indd/4
21 mars 2007
PB101107-15
Accessories
Type
2P Wiring comb busbars 3P Wiring comb busbars 16641 4P Wiring comb busbars 6P Wiring comb busbars 8P Wiring comb busbars
Number of poles
2 3 4 6 8
Cat. no.
16641 16642 16643 16644 16645 16646
PB101100-30
This circuit-breaker is tested in conjunction with the PRF1 surge arrester with a 10/350 waveform. It is used specifically for the protection of surge arresters from the PRF1 range. The assembly conforms to IEC 61643-1 and EN 61643-11 standards. Type Number of poles
2 3 4
Rating (A)
125 125 125
Curve
Width in 9 mm modules
4 6 8
Cat. no.
D125 18532
D D D
PB101108-30
PB100626-30
Cat. no.
This circuit-breaker is tested in conjunction with the PRF1 Master surge arrester with a 10/350 wave form. The assembly conforms to IEC 61643-1 and EN 61643-11 standards. Type
NS160N TM160D
Number of poles
2 3 4
Rating (A)
160 160 160
Curve
D D D
Cat. no.
30620 30630 30650
21 mars 2007
90271E_Ver2.1.indd/5