Industrial Communication

Chapter 2: Modbus Serial

Modbus Serial Features

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Introduction
Modbus = Modicon Bus (1979)
is an application layer messaging protocol for client/server communication between devices connected on the bus. Independent from the other layers Openly published and royalty-free Relatively easy industrial network to deploy It moves raw bits or words without placing many restrictions on vendors

Various versions
Modbus RTU (Serial), Modbus ASCII, Modbus Ethernet TCP/IP, Modbus Plus (Proprietary of =S=)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Layers Used in ISO Model


3 Layers used for Modbus Serial
APPLICATION PRESENTATION SESSION TRANSPORT NETWORK DATALINK PHYSICAL Modbus Protocol Not used Not used Not used Not used Master / Slave, Transmission RTU / ASCII RS485, RS422, Fiber Optic, Radio, Cellular,

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Physical Layer
RS485 2 wire RS485 4 wire
Required
Multi-point and point-to-point To integrate into an existing installation without modification Point-to-point mode 15 meter max.

Optional

RS232 Transmission speeds:

Optional

9600 bps and 19200 bps required with 19.2 Kbps by default
Other speeds: 1200, 2400, 4800, 38400, 56 Kbps, 115 Kbps optional

RS485 is the most common physical layer used on Modbus. 32 devices included the master can be connected on the bus.
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010 5

Modbus RS485 4 wire installation


Topology: bus type
Master
T R 5V 650 ohms

Slave pair
650 ohms

120 ohms 1 nF

5V

120 ohms 1 nF

Master pair
120 ohms 1 nF

Common PG
T R T R

120 ohms 1 nF

Slave 1

Slave n

Max. number of devices: 32 including master without a repeater Max. length: Main segment: 1,000 m at 19,200 bits/s Drops: 40 m in total (20 m for one tap link)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Modbus RS485 2 wire installation


Master
T R 5V 650 ohms

Balanced pair
120 ohms 1 nF

Common PG
T R T R

650 ohms

120 ohms 1 nF

Slave 1

Slave n

Max. number of devices: 32 including master without a repeater Max. length: Main segment: 1,000 m at 19,200 bits/s Drops: 40 m in total (20 m for one tap link)

Topology: bus type


Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Data Transmission
Method of accessing the medium
Master slave

Transmission method:
Client / Server

Max. useful data size:


120 words

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Unicast Addressing Mode


Address = 1 to 247
Request 5
Funct. Code Request data CRC

Adr 1

Adr 2

Adr 3

Adr 4

Adr 5

Adr n

Response 5
Funct. Code Response data CRC

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

Broadcast Addressing Mode


Address = 0
Request 0
Funct. Code Request data CRC

Adr 1

Adr 2

Adr 3

Adr 4

Adr 5

Adr n

No response from slaves Used only with write functions

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

10

Transmission Modes
ASCII transmission mode
Every data item is encoded in two ASCII characters (7 bits) allows time intervals of up to 1 second to occur between characters without causing an error. Used with Modem / Barcodes

RTU transmission mode


Every data item is encoded in one byte (8 bits) Achieves higher throughput & reliability Used with PLC / SCADA

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

11

Modbus Serial Frame


Modbus PDU

PDU = Protocol Data Unit

Address

Function Code

Data

CRC or LRC

= 0 to 247 Identifies the addressee

= 1 to 127 Action to perform

Additional data depending on the Function Code

Validity check

Two addressing modes:

Unicast Broadcast

Address field = 1 to 247 Address field = 0 (used in write only mode)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

12

Address Field
Address Function Data Checksum

Valid device addresses : 0 to 247 decimal. Value 0 reserved for broadcast message (no reponse)

Request
A master addresses a slave by placing the slave address in the address field of the message.

Response
When the slave sends its response, it places its own address in this address field of the response to let the master know which slave is responding.

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

13

Function Field
Address Function Data Checksum

Valid codes are in the range of 1 to 255 decimal.

Request
The function code field tells the slave what kind of action to perform.

Response
For a normal response, the slave simply echoes the original function code. For an exception response, the slave returns a code that is equivalent to the original function code with its most significant bit set to a logic 1.
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

14

Data Field
Address Function Data Checksum

Request
The data field contains additional information which the slave must use to take the action defined by the function code. This can include items like register addresses, quantity of items to be handled, etc...

Response
If no error occurs, the data field contains the data requested. If an error occurs, the field contains an exception code that the master. Application used to determine the next action to be taken.

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

15

Checksum Field
Address Function Data Checksum

Modbus RTU uses CRC


Cyclical Redundancy Check (2 bytes)

Modbus ASCII uses LRC


Longitudinal Redundancy Check (1 byte)

Request
The checksum is calculated by the master and sends to the slave.

Response
The checksum is re-calculated by the slave and compared to the value sent by the master. If a difference is detected, the slave will not construct a response to the master.
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

16

Function Codes
Code 01 02 03 04 05 06 07 08 15 16 23 43 (0x01) (0x02) (0x03) (0x04) (0x05) (0x06) (0x07) (0x08) (0x0F) (0x10) (0x17) (0x2B) Function Read n consecutive output bits Read n consecutive input bits Read n consecutive output words Read n consecutive input words Write 1 output bit Write 1 output word Read exception status Access diagnostic counters Write n output bits Write n output words Read/Write n output words Read identification

http://www.modbus.org
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010 17

Example of Read Request


Request
1 byte 1 byte 2 bytes 2 bytes 2 bytes

Slave Function Address code = 3

First word address

Number of words to read

CRC16

Response
1 byte 1 byte 2 bytes 2 bytes 2 bytes 2 bytes

Slave Function Address code = 3

Number of bytes read

Value of the first word

Value of the last word

CRC16

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

18

Registers & Index


Registers
Memory variable located in a device Word, Bit, Byte, etc Can be reached thanks to its Index

Inputs Registers: read only (status) Outputs Registers: read / write (commands)
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010 19

Programming Modbus with Unity Pro

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

20

1 Platform, 3 Target
3 PLC Targets
M340, Premium, Quantum

Same Philosophy Different Function Blocks

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

21

BMXNOM0200
Safety screw (1) Display block with 4 LEDs: (2)
RUN (green) and ERR (red): Module status SER COM (green): Activity on the serial link (lit) or fault (flashing).

Channel 0 (3a & 3b)


RS 232C connection, marked COM Port 0 RS232 RS 485 connection, marked COM Port 0 RS485

Channel 1 (4)
RS 485 connection, marked COM Port 1 RS485

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

22

BMXNOM0200 Configuration

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

23

Request Programming
Dedicated Function Blocks for M340
ADDM Address Conversion READ_VAR Execute a read request WRITE_VAR Execute a write request DATA_EXCH Execute a user defined request OUT_IN_MBUS Change from Slave to Master mode
Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010 24

ADDM FB
IN:
String variable: r.m.c.e.MBS

Out
Converted table of words, to be used in the others FB

r.m.c.e.MBS
r = the rack number where the Modbus module is located, m = the slot number of the Modbus module, c = the channel used e = the equipment address (slave address) of the target MBS = used to indicates to use Modbus Serial (optional)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

25

READ_VAR FB

IN:
ADR: to be linked to the output of the ADDM block. OBJ: defining object to read (in the case of Modbus register: %MW) NUM: starting register to read NB: number of consecutive register to read

OUT
RECP: reception zone of the block, delivering the value read (table of words)

IN/OUT
GEST: table of 4 words to manage the communication block (errors, timeout, length, etc..)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

26

WRITE_VAR FB

IN:
ADR: to be linked to the output of the ADDM block. OBJ: defining object to read (in the case of Modbus register: %MW) NUM: starting register to read EMIS: source table to write from the PLC

IN/OUT
GEST: table of 4 words to manage the communication block (errors, timeout, length, etc..)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

27

GEST Variable
Structured Variable
Table of 4 words
Most Significant Byte GEST[1] Exchange number (updated each time the request is executed) Operation report Timeout Length Least Significant Byte Activity bit: 1 = exchange in progress, 0 = exchange terminated. Communication Report

GEST[2] GEST[3] GEST[4]

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

28

Exercise
Add & Configure Modbus Module (p 2-13) Add a module Configure the channel Set the Modbus Slave Insert the ADDM block Create the READ_VAR request Test the application

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

29

Optimizing Communication
Beware of Communication Buffer Overload Usage of the Activity Bit (GEST[1].X0)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

30

Optimizing Communication (Example)


Conditioning with the Activity Bit
Avoid buffer overload Ensure that the next block is send when the previous is finished.

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

31

Optimizing Communication (Cont.)


Device Timeout
Mean to know if the Master is lost After a defined time without receiving request, Slave goes to fallback mode
Allo, anybody still there?

Fallback Mode
Mode activated when communication is lost Behaviour to define (start a motor, stop a process, switch off outputs..)
No answers great, lets go party!

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

32

Exercise
Optimizing the Communication (2-16) Insert the Activity Bit as condition Insert the WRITE_VAR function Test the communication Testing the TimeOut (2-20) Use WRITE_VAR to change the Timeout parameter Test the communication

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010

33

Modbus Serial RTU


Main Features Reminder:
Up to 1200m whatever the baud rate value Performance: Depends on the PLC application and how its managed. Up to 32 Slaves Baudrates: 1,2kbit/s... 19,2kbit/s max 240 bytes per telegram No separate ground wire Good error detection (CRC)

Industrial Communication Course with Unity Pro - Modbus Schneider Electric | Industry Business | Training | E. Pauchet V5.0 May 2010