When power fails, the automatic transfer switch follows user-set time delays to start the generator, transfer the load to the generator, reconnect to utility power and shut down the generator after generator cool down.
ASCO Series 300 Power Transfer Load Center rated two pole, 400 amperes with optional transient voltage surge suppression on utility and generator sources.
Features
! !
Power Transfer Load Center is Service Entrance Rated and listed to UL 67 Automatic Transfer Switch is listed to UL 1008, the standard for Transfer Switch Equipment, and meets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) articles 700, 701 and 702. Also CSA certified to CSA 22.2 No. 178-1978 True double-throw contacts eliminate simultaneous connection to utility and generator Adjustable close differential voltage sensing on the normal source
! ! ! ! !
Automatic engine exerciser to test the generator with or without loads Pre-wired and factory tested for easy installation Space saving modular design provides easy access and serviceability Convenient terminals for connecting neutral and ground conductors Available in Type 1 (indoor) or Type 3R (outdoor) enclosures
! !
Product Specifications
Control and Display Panel
Provides LED indicators for Transfer Switch position and source availability. The panel also includes engine generator exerciser test and time delay bypass pushbuttons.
Load Center
Service disconnect breakers (Utility and Generator Sources) 200 amps 400 amps UL 67 Listed Branch circuit breaker positions Forty-two (42) Branch circuit breaker type Square D plug-on type Square D bolt-on type Fully rated solid neutral Ground connection
300
All Units
L4 2 200 F 1 X C
Poles 2 3
Optional Accessories 11BG = Programmable Engine Exerciser and Source Availability Contacts 14AA/14BA = Auxiliary Contacts* 44G = Strip Heater with Thermostat 72A = Communications Interface Module 73 = Transient Voltage Surge Suppression (see chart) * Auxiliary contacts indicate position of main contacts. Two (2) for normal and two (2) for emergency position (one set is standard).
General Data
Service voltage 240/120 VAC, 60 hz single phase, 3 wire 208/120 VAC, 60 hz three phase, 4 wire Short circuit rating 22 kA for 200 amp 42 kA for 400 amp Enclosure dimensions (WxHxD) 200 ampere Type 1 enclosure 30 x 78 x 7.25 inches Type 3R enclosure 30 x 84 x 10 inches 400 ampere Type 1 enclosure 35 x 78 x 7.25 inches Type 3R enclosure 36 x 84 x 10 inches UL certification UL 67 Listed UL 1008 Listed (ATS) UL 1449 2nd Edition (TVSS)
50
Publication 3109R1