Vous êtes sur la page 1sur 8

Take a Test Article Library CEEJ Home Submit an Article

Contact CEEJ

Article # 0005 Burner Management Systems


By Tom Cox, P.E.

Introduction
The following paragraphs outline a general method for implementing a typical boiler Burner Management System (BMS). Several general guidelines to implement operation strategies for such a system are also provided. This document is intended for use by the control systems designer as a guide for basic design. Final and detailed BMS design is required per the applicable design specifications. This narrative contains provisions required for compliance with the NFPA 8501 Standard for Single Burner Operation. The control systems designer is responsible for compliance with this standard, and all other applicable federal, state and local standards and regulations.

General
The Burner Management System must be designed to ensure a safe, orderly operating sequence in the start-up and shutdown of fuel firing equipment and to reduce possible errors by following the operating procedure. The system is intended to protect against malfunction of fuel firing equipment and associated systems. The safety features of the system shall be designed to provide protection in most common emergency situations, however, the system cannot replace an intelligent operators reasonable judgment in all situations. In some phases of operation, the BMS shall provide permissive interlocks only to insure safe startup of equipment. Once the equipment is in service, the operator must follow acceptable safe operating practices. It is essential that all parts of the BMS are in good working order and in service whenever the burner is in service if the system is to provide the protection for which it is designed. Regular maintenance and inspection of the system and its associated hardware is essential for its continued safe operation. This narrative gives a description of a typical BMS as it relates to the various operating phases and the operation of the fuel firing equipment and associated systems.

BMS Functions
The BMS shall be designed to perform the following functions: 1. Prevent firing unless a satisfactory furnace purge has first been completed.

2. Prohibit start-up of the equipment unless certain permissive interlocks have first been completed. 3. Monitor and control the correct component sequencing during start-up and shut-down of the equipment. 4. Conditionally allow the continued operation of the equipment only while certain safety interlocks remaining satisfied. 5. Provide component condition feedback to the operator and, if so equipped, to the plant control systems and/or data loggers. 6. Provide automatic supervision when the equipment is in service and provide means to make a Master Fuel Trip (MFT) should certain unacceptable firing conditions occur. 7. Execute a MFT upon certain adverse unit operating conditions.

Operation
Per NFPA 8501, section 2-1.3(b), a common cause of furnace explosions is Fuel leakage into an idle furnace and the ignition of the accumulation by a spark or other source of ignition. Proper attention to the design of the interlocks and trip system to provide a safe light up of the boiler furnace is required.

Furnace Purge
Before any fuel firing is permitted, either initially or after a boiler trip, a satisfactory furnace purge cycle must be completed. Prior to starting a furnace purge cycle, the operator must ensure that the following purge requirements are satisfied[i]: 1. Drum level within operating range (not high, not low) 2. Instrument air header pressure within operating range 3. Fan is in service 4. Purge airflow capable of a minimum of 70% of the full load airflow established through the unit[ii]. 5. All flame scanners reading "No Flame" 6. Natural gas block valves are proven closed 7. Fuel oil block valves are proven closed 8. Air dampers are in the fully open position 9. Natural gas, or fuel oil, header pressure upstream of block valve is satisfactory 10. Pilot gas header pressure is satisfactory 11. Burner Control System is energized 12. A "No Master Fuel Trip condition" condition is established As each of the above conditions is reached, their respective indicator lights[iii] shall illuminate as "PURGE PERMISSIVES" on the operator control console. Once all of the above conditions are satisfied, the "PURGE AVAILABLE" light shall illuminate indicating that the START PURGE switch is enabled by the system logic. Activating the START PURGE control, when the "PURGE AVAILABLE" light is illuminated, will begin a timed furnace purge cycle as indicated by a "PURGE IN PROGRESS" light illuminating. As indicated in NFPA 8501, section 6-2.4.1(i), the purge shall be ...sufficient for at least eight air changes of the furnace.

If the operator is starting the boiler from the cold condition, or restarting after a Master Fuel Trip event, the procedure outlined in the following paragraphs is required. If the boiler is recycling or otherwise starting from a warm condition, the MFT circuit will reset automatically and the procedure will skip directly to the main flame light off sequence. At the end of the purge cycle, and providing that the purge requirements remained satisfied, the damper control shall position the inlet damper for light-off, approximately 10% to 30% airflow, depending on burner design, required turn-down, etc. The "PURGE COMPLETE" light will illuminate and the boiler trip circuit shall be ready for reset, and so indicated by a "MFT RESET" light. Provided the start-up permissives remain satisfied, the system shall initiate a burner startup period timer set for no more than 10 minutes. If the operator does not initiate a start-up within this time, the boiler control system will exit the PURGE COMPLETE condition and the operator must begin again with the pre-purge cycle. If the MFT has been reset, the boiler control system will trip the MFT when leaving the PURGE COMPLETE condition. Upon completing a satisfactory purge, the operator must press the RESET MFT pushbutton. The boiler control system will indicate that the MFT has been reset with a steady on MFT RESET light. At this point, the boiler control system is ready to allow the main flame start-up sequence.

Main Flame Start-Up Sequence


The main flame start-up sequence, from the lighting the of the pilot flame through main flame light-off, is an automated sequence. Once the start-up sequence has begun, only the BOILER STOP switch and the EMERGENCY STOP will interrupt the startup sequence. Any interruption of the start-up sequence requires a post-fire purge prior to attempting to start the boiler again. To initiate the start-up sequence, the operator activates the START BOILER switch.

Pilot Flame Light-Off


Before the burner can be started, satisfactory light-off conditions for the pilot and main burners must be met. This is accomplished when the following conditions are satisfied: For the pilot igniter: 1. MFT relay reset 2. Pilot gas header pressure normal For natural gas: 1. All of the above mentioned for the pilot igniter 2. Natural gas pressure normal 3. Natural gas control valve is in light-off position For fuel oil: 1. All of the above mentioned for the pilot igniter 2. Oil gun is in place in the burner

3. 4. 5. 6.

Oil pressure is normal Fuel oil atomizing interlocks are satisfied Fuel oil atomizing medium is provided to the burner Oil control valve is in light-off position

Other Conditions: 1. No MFT condition after purge 2. All flame scanners report no flame 3. All natural gas, or all fuel oil, block valves shown closed 4. All air dampers are in light-off position Failure to meet any of these conditions shall prevent the burner light-off operation. To light the pilot flame, the pilot header vent valve, and, for natural gas fuel, the natural gas vent valve shall be closed by the boiler control system. Then, sequentially, the igniter transformer is energized, the pilot gas block valves are open and a 10 second pilot ignition timer starts counting down. When ignition timer cycle is completed, the igniter transformer is de-energized and the pilot flame scanner is checked by the control system. If the pilot flame is present, the main flame light-off sequence continues. If the pilot flame fails, the boiler control system initiates a pilot flame failure shutdown. Additional attempts of pilot light-off are permissible provided a successful pilot light-off is made within 10 minutes after the furnace purge. Note that if the pilot flame continues to fail after several attempts, the boiler should be inspected to determine the fault and the condition corrected.

Main Flame Light-Off


Once the pilot flame is made, the boiler control system opens the header block valves for the selected fuel. A main flame light-off timer begins a 15 second countdown for natural gas, or 20 seconds for fuel oil, to establish and stabilize the main flame. At 5 seconds before time out, the boiler control system closes the pilot block valves and opens the pilot vent valve. The remaining 5 seconds are used to detect the main flame. For the typical dual flame scanner design, a main flame failure shutdown is initiated if both flame scanners return a no flame signal to the burner control system. This will generate a boiler trip, and another furnace purge will be required. Once the burner is lit, the system is in the NORMAL RUN CONDITION and combustion controls should be released to modulation control.

Shutdown
Per NFPA 8501, section 6-2.4.5, The normal shutdown cycle for the boiler shall accomplish the following in the order listed: (a) Shut off fuel supply to the main burner. (b) Interrupt spark and shut off fuel supply to igniter, if in operation. (c) For oil: 1. Where used, open the recirculating valve. 2. Shut off atomizing medium, if desired. (d) For gas, vent piping between safety shutoff valves to atmosphere.

(e) Perform a post purge of the boiler furnace enclosure. (f) Shut down fan, if desired. For a safety shutdown, a manual reset is also required.

Normal Boiler Shutdown


A normal shutdown is initiated by operating BOILER SHUTDOWN switch. This will initiate the shut down sequence listed above.

Boiler Master Fuel Trip


Any of the following conditions shall cause a boiler trip to occur. This results in the shutdown of all fuel and requires another furnace purge cycle before any attempt at relighting. For fuel oil: 1. Excessive steam pressure. 2. Low water level. 3. Low fuel pressure. 4. Low oil temperature. 5. Loss of combustion air supply. 6. Loss of flame. 7. Loss of control system power. 8. Loss of atomizing medium, if used. For natural gas: 1. Excessive steam pressure or water temperature. 2. Low water level. 3. High or low gas pressure. 4. Loss of combustion air supply. 5. Loss of flame. 6. Loss of control system power.

In the event of an MFT, the control system shall initiate the following: 1. Execute a shut down as listed above. 2. Illuminate the appropriate indicator lights and alarms. 3. Return the system to the pre-purge state Boiler restart will be inhibited until all pre-purge requirements are satisfied.

Alarms
The following is a list of recommended alarm conditions: 1. 2. 3. Any boiler or burner trip signal High or low water level High furnace pressure

4. Partial Loss of flame (For the typical two scanner system, one indicates no flame) 5. Main fuel shutoff valves closed 6. Loss of control system power 7. Unsuccessful burner shutdown

Interface with the Combustion Control System (CCS)


The following list, at a minimum, of signals should be sent to the Combustion Control System: 1. Controls to purge position 2. Controls to light-off position 3. Normal run condition: release controls to modulation 4. Main natural gas block valve open: permissive to place gas control valve in automatic. 5. Master fuel trip: run boiler load to zero and place combustion controls in manual. 6. Oil recirculation signal Under the provisions of NFPA 8501, section 6-5.2.3, for a single burner boiler, the BMS and CCS may reside in the same processor. This option can to reduce the integration complexity and increase the BMS to CCS interface reliability.

Operator Interface
The above describes a traditional operator interface using discrete switches and indicator lights. The control designer is encouraged to incorporate a graphical user interface or similar options in order to enhance the ease of use and readability of the boiler control system operator interface.

Endnotes:
[i] Prepurge permissives condition checks and furnace purge are to be initiated by the operator from the local BMS panel (see NFPA 8501, Chapter 5 for detailed guidelines on cold starting using fuel oil, Chapter 6 for cold starting using natural gas). [ii] Purge air flow (NFPA 8501, section 6-2.4.1(h): The total furnace airflow shall not be reduced below the purge rate airflow (70% of the maximum continuous airflow capacity). Reducing airflow below these limits will lead to a MFT, and a new furnace purge will be required. [iii] Suggested color design: Purge Permissives indicating lights: Purge Available indicating light: Purge in progress indicating light:

white green amber

Purge complete indicating light: MFT reset indicating light:

white red

Article # 0005

TEST QUESTIONS:

1. The Burner Management System must be designed to ...? a. provide a safe and orderly evacuation procedure b. ensure a safe and orderly operating sequence c. eliminate all possible errors by the operator d. All of the above 2. The BMS shall provide protection against most common emergencies but cannot replace ...? a. an intelligent operators reasonable judgment b. a fully integrated plant control system c. a properly wired and located emergency shutdown switch. d. All of the above 3. What condition(s) must be satisfied prior to starting a furnace purge cycle? a. The fuel valves must be proven closed b. Air dampers are in the fully open position c. All flame scanners reading "No Flame" d. All of the above 4. What may be used to interrupt the main flame start-up sequence after it has begun? a. Activating the "Boiler Stop" or the "Emergency Stop" switch. b. Blowing out the pilot light. c. A call from the Governor or the President. d. All of the above 5. What must be completed before any fuel firing is permitted? a. The boiler must be drained and filled with fresh water. b. A pre-fire inspection by the local fire department. c. A Certificate of Inspection must be issued by the state boiler inspector. d. A satisfactory furnace purge cycle. 6. Which of the following conditions will cause a boiler trip (MFT) to occur? a. Excessive steam pressure b. Loss of combustion air supply c. Low water level d. All of the above 7. The Boiler Management System shall be designed to...? a. monitor and control the correct component sequencing during start-up and shut-down b. allow for the unattended start-up and shut-down of the boiler

c. allow firing the boiler without a furnace purge being completed d. All of the above 8. The burner startup period timer is set for ...? a. no more than 10 minutes b. no less than 10 minutes c. 30 seconds d. to between 20 and 40 minutes at the discretion of the operator 9. As indicated in NFPA 8501, section 6-2.4.1(i), the purge shall be ...sufficient for at least ____ air changes of the furnace. a. eight b. six c. five d. two 10. Which of the following is a recommended alarm condition? a. High furnace pressure b. A boiler trip signal c. loss of control system power d. All of the above

Vous aimerez peut-être aussi