Assembly Instructions

Operating values

8. Operating values
The operating values in this instruction apply to SF6 circuit-breaker LTB 72,5-245E1 with operating mechanism BLK 222.

8.1 Times

Closing times Opening time coil I Opening time coil II Close-Open time(1)

< 28 ms 17 2 ms 17 2 ms 26 3 ms

(1) The Close-Open time refers to the time the main contacts are closed during a closing operation when a tripping pulse is simultaneously connected via the auxiliary contact.

8.2 Motor and control circuits

Charging time for motor Operating voltage opening coil I Operating voltage opening coil II Operating voltage closing coil I Operating voltage closing coil II

max 15 s V (according to the rated data plate) V (according to the rated data plate) V (according to the rated data plate) V (according to the rated data plate)

8.3 Resistance
Main circuit resistance per pole max 49 .

8.4 Contact stroke


Main contact stroke is 160 3 mm.

1HYB800001-044 Rev.B

31