Vous êtes sur la page 1sur 16

Clean and compact drive for energy savings

Altivar 1100

Medium-voltage variable speed drive 0.3 to 10 MW

DIA2ED1080701-EN.indd 1

22/07/09 11:36:14

Increase your productivity, make bigger savings

Altivar 1100 is the latest addition to our full range of electrical distribution, motor control and control systems. Reduction in energy costs Protection of motors and equipment Increased competitiveness Reduction in maintenance costs

Power
Fans, pumps

Mines & minerals


Crushers, fans, pumps

Oil and gas


Pumps, compressors, air blowers

Water treatment
Pumps, air blowers

DIA2ED1080701-EN.indd 2

22/07/09 11:36:14

Benefit from innovation in your medium-voltage applications Better technology


Compact design with input transformer integrated in the drive enclosures

Better results
Return on investments Reduction in installation costs Rapid commissioning Increased productivity Lower production and maintenance costs Enhanced reliability and continuity of operation No disturbance of the motor or driving load Improved motor durability Maximum machine efficiency without risk Compatibility with new or existing motors Extended cable length between motor and drive permitted Perfect integration in the line supply Energy losses minimized No malfunctions or interference with the environment Easy to operate Saves time during use Ease of maintenance A range of high-quality services A one-stop-shop available throughout the installations service life Advice and follow-up services, from specifying requirements right through to after-sales International coverage

Durable components Optimum sizing Proven control

Best in class multilevel technology: - perfect sine wave output current without the need for a filter - no harmonics, no stress on the motor, cable and driven load

36 pulse diode rectifier: - constant optimized input power factor - perfect sine wave input current better than the values required by all the standards : IEC 61000-2-4, IEEE 519, G5/4, etc. User-friendly interface Easy remote access to the device parameters

A comprehensive offer: - medium and low-voltage drives, motor, electrical distribution, control systems, installation - relevant expertise (energy efficiency, line supply study, etc.)

DIA2ED1080701-EN.indd 3

22/07/09 11:36:15

Air cooling for a standalone installation


Example of a 2 MV drive

Inverter cell
Reliability and easy maintenance reduced number of cells thanks to single phase 3-level inverter design easy to replace Motor-friendly up to 17 level PWM control minimizes switching surge on motor

Control
Easy access & compactness integrated high speed control

Integrated transformer
Compactness fewer cables and less commissioning work required Clean power 36-pulse operation

DIA2ED1080701-EN.indd 4

22/07/09 11:36:15

Compact and environmentally friendly


Clean power and friendly to motors The multi-level topology shown below, featuring a 36-pulse diode rectifier, is associated with the kind of low-voltage IGBTs that have proven successful in practice and are found in a wide range of applications. It also features: Harmonics-free input current with high power factor No pulse torque Quasi sine wave for motor and supply currents (negligible harmonic current content) Intrinsic safety: current switched off instantaneously in the event of a fault Minimum losses since the IGBT does not need a snubber and requires little switching power Main circuit configuration for 3.3 kV drive type

Ed

Ed = DC voltage

3-level output voltage of an inverter cell

Inverter cell

3-phase input supply

Input voltage (green) and current waveform (orange) on supply side

Output voltage (green) and current waveform (orange) on motor side

~97%
Compact size: Up to 1.5 MVA per meter of enclosure (drive only) efficiency including transformer
DIA2ED1080701-EN.indd 5

> 40,000 h
MTBF: more than 4 fault-free years
22/07/09 11:36:15

Make your life easier with complete solutions


Altivar 1100 is open to most networks, and can be integrated in any medium or low-voltage architecture. With the Altivar 1100, Schneider Electric has created a comprehensive, safe, and consistent offer for: Controlling and supplying equipment Improving performance Schneider Electric, a world leader in electrical distribution and control systems, presents a range of products, solutions and services for: Transforming and routing energy Automating machines and processes, in complete safety Controlling, supplying and making equipment safe.
The Altivar 1100 solution is based on a transformer, drive and medium-voltage electric motor assembly. Schneider Electric can provide a turnkey solution complete with drive and associated equipment (electrical distribution, control systems). For more information, please contact our project teams.

Schneider Electric global solution offer

Power management and monitoring

Electric substation

GIS switchboard

MV/MV power transformer

AIS 12 MV switchboard

MV motor and drive

MV motor starter control

AIS MV switchboard

MV/MV transformer

Secondary electric substation

LV switchboard

LV motor control switchboard

LV variable speed drive

DIA2ED1080701-EN.indd 6

22/07/09 11:36:16

Ensure the reliability of your installations with a simple open architecture


An innovative control system based on the latest generation of 32-bit microprocessors. eamless integration into a control system architecture. S dvanced control functions that are simple to implement: A - Simple sensorless vector control. - Diagnostics and maintenance can be carried out locally (via terminal or PC) and remotely.
Straightforward programming The drive has advanced parameter-setting and diagnostic functions. It is possible to access the machine status with the key values signature (current, voltage, etc. in real time).

Operator stations

Information
Servers

Ethernet

Control

Fieldbus

PLCs

Equipment

Altivar 1100

Medium-voltage switchboard

DIA2ED1080701-EN.indd 7

22/07/09 11:36:18

Setup and support as benefits of an international group


By applying our industrialization skills to our services, we can ensure your success.
Schneider Electrics expertise Service experts are on hand to help you: get maximum return from your investments optimize the value of your installations throughout their life cycle

A wide range of associated services

Audit and consultancy:

- line supply consultancy (compensation, filtering, harmonics, etc.) - shaft line study (torsional analysis, etc.) - energy efficiency, enabling the best drive solution to be determined

Installation

and startup with:

- assistance and troubleshooting - specific maintenance contract (possibly including remote access and reconditioning)

Bespoke project
management

Customized training Rapid, flexible service


provision

Factory tests at maximum

power with or without motor

DIA2ED1080701-EN.indd 8

22/07/09 11:36:20

Make the most of your energy

DIA2ED1080701-EN.indd 9

22/07/09 11:36:20

Altivar 1100: technical specifications


General characteristics Converter type Input Output Input voltage 36-pulse diode bridge Multi-level PWM inverter. Each inverter cell is a 3-level NPC low-voltage IGBT Standard: 3.3 kV, 6 kV, 6.6 kV Option: 10 kV or any other medium voltage Variation: standard 10% Option up to -20% (10sec with UPS) 50/60 Hz 5% > 0.96 Asynchronous motor Standard: 0 .. 3,300 V - 0 .. 6,000 V - 0 .. 6,600 V Normal: 0.2 .. 50/60 Hz, Extended: 0.2 .. 120 Hz Integrated in the converter, dry type Standard: 380 V 3-phase, 50 Hz Other voltages available as an option 220 V single-phase, 50 Hz. UPS available as an option IP31 RAL 7032 Air-cooled IEC EN 61800-3, IEC EN 61800-4, IEC EN 61800-5-1, IEC EN 60204-11, IEC EN 60529, IEEE 519 Others available as an option

Input frequency Power factor Type of motor supplied Motor connection 3-phase output voltage Output frequency Input transformer Auxiliary voltage Degree of protection Paintwork Cooling Reference standards Standards Power specifications
Voltage classes (kV) Rated capacity (kVA) Voltage classes (kV) Rated capacity (kVA) Rated current (A) (*1) Max.current (A) at overload Applicable max. motor output (kW) (*2) Capacity of auxiliary control supply (kVA) Capacity of fan power power supply (kVA) Overload capability 470 41 49 370 1.5 3 420

Efficiency at nominal power 0.97 for drives and input transformer

6 500 600 700 860 1000 1200 1400 1600 1800 2100 2360 2700 6.6 570 50 60 450 1.5 3 670 59 70 530 1.5 3 780 960 1120 1320 1540 1750 2000 2300 2600 3000 68 84 98 103 115 138 134 141 153 183 173 207 202 212 227 272 262 275 3500 4400 5200 7000 10500 306 321 385 462 459 482 612 643 918 964 3200 4000 4700 6400 9500

72 100 630 760 1.5 3 2.5 3

900 1050 1200 1400 1600 1850 2000 2400 2.5 3 2.5 3 2.5 3 3.5 6 3.5 6 3.5 6 4.5 6 4.5 6

2800 3500 4160 5500 8300 5.5 9 7.5 12 7.5 12 9.5 15 14.5 27

105% for 60 sec - Other overload available as an option

DIA2ED1080701-EN.indd 10

22/07/09 11:36:20

Voltage classes (kV) Rated capacity (kVA) Rated current (A) (*1) Max.current (A) at overload Applicable max. motor output (kW) (*2) Capacity of auxiliary control supply (kVA) Capacity of fan power power supply (kVA) Overload capability 390 68 72 315 1.5 1.5 560 98 103 450 1.5 1.5

3,3 770 1150 1500 1750 134 141 610 1.5 3.0 202 212 262 275 306 321 2600 459 482 2100 4.5 6.0 3500 612 643 2800 5.5 7.5 5200 918 964 4200 7.5 13.5

920 1200 1400 2.5 3.0 2.5 3.0 3.5 6.0

105% for 60 sec - Other overload availabe as an option

Control Characteristics Motor control modes Number of quadrants Steady state operation Protection Interface V/f type control, sensorless flux vector control Catch on the fly, suppression of critical speeds 2 Speed accuracy in steady state: 0.5% Overcurrent, main circuit fuse blown, overvoltage, undervoltage, CPU fault, cooling fan stop Graphic keypad for local operation Wired and networked remote communication Option: > HMI : large LCD touch panel > Operation & Maintenance tool via PC (DDC loader) Standard: Profibus, Modbus Options: Ethernet, CANopen, DeviceNet, etc.

Communication

Environmental characteristics Storage temperature Operating temperature Cooling method Relative humidity Altitude Vibration Noise level Options Input isolation switch with grounding Output isolation switch with grounding UPS Inverter + battery charger Cable entry from the top
(*1) When Inverter output frequency is less than 25Hz,Inverter output current is decreased. (output current will be 70% at 0.2Hz) (*2) The applicable motor output is the reference value of standard 3.3 and 6.6kV, 4-pole motors

-10 to 60 C. (Transportation temperature: -10 C to 70 C / (60 C to 70 C for 24 h) 0 to 40 C Forced air cooling 85% RH max. (no condensation). Option: up to 95%. < 1000 m above sea-level Acceleration: 4.9m/s2 acceptable (10 to 50Hz) 85 dB(A). Option: 80 dB(A)

Identification code

ATV1100_xx
Name of range Nominal power (Rated capacity, kVA) Cooling: A (air)

A 33
Output voltage 33 : 3300 V 60 : 6000 V 66 : 6600 V

DIA2ED1080701-EN.indd 11

22/07/09 11:36:20

Altivar 1100: typical dimensions


3.3 kV Capacity (kVA) Outline drawing Dimension (mm) A B C D (Full width) (Transformer (Converter (Control panel) panel) output panel) 390 560 770 1150 1500 1750 2600 3500 5200 Fig.1 Fig.1 Fig.1 Fig.2 Fig.2 Fig.2 Fig.4 Fig.6 Fig.8 2000 2300 2300 3000 3400 3500 3600 6800 10900 _ _ _ 2100 2300 2300 2200 2300 5200 1500 1800 1800 900 1100 1200 1400 3600 4800 500 500 500 _ _ _ _ 900 900 E (Fan) 548 548 605 542 542 542 542 542 600 F (Depth) 1000 1100 1200 1300 1400 1400 1400 1400 1900 G (Maintenance space) 1300 1300 1300 1300 1300 1300 1500 1500 1800 2000 3000 4100 4500 6200 7000 8100 12300 26000 Approx. mass. (kg)

(*1) The outline dimensions of the panel represent the maximum dimensions of a standard-capacity model. They may differ depending on the applicable motor capacity. (*2) The structure is for maintenance from the front. Be sure to allow at least the maintenance space listed in column G of the above table.

(*3) A wiring duct is installed on the panel in Figs. 8 and 9 (height: 600mm). (*4) A cooling fan is mounted on the panel. To assure maintainability and cooling performance, allow a clearance of at least 500mm between the top of the fan and the ceiling.

Front maintenance structure


Fig.1 3.3 kV: 390, 560, 770 kVA Fig.2 3.3 kV: 1150, 1500, 1750 kVA 6.6 kV: 470, 570, 680, 960, 1120 kVA Fig.3 6.6 kV: 1320, 1540, 1750, 2000, 2300, 2600, 3000, 3500 kVA

C A

B A

B A

Fig.4 3.3 kV: 2600 kVA

Fig.5 6.6 kV: 4400, 5200 kVA


E

Ceiling Upper maintenance clearance

2300

2360

60

D A

Min. G

Front maintenance clearance

Front/rear maintenance structure


Fig.6 3.3 kV: 3500 kVA
Ceiling Upper maintenance clearance

B A

Min. G

600

Front maintenance Rear maintenance clearance clearance

DIA2ED1080701-EN.indd 12

Min. 500

Min. 500
22/07/09 11:36:21

6.6 kV Capacity (kVA) Outline drawing Dimension (mm) A B C D (Full width) (Transformer (Converter (Control panel) panel) output panel) 470,570, 670, 780 960,1120 1320, 1540 1750, 2000, 2300 2600, 3000 3500 4400, 5200 7000 10500 Fig.2 Fig.2 Fig.3 Fig.3 Fig.3 Fig.3 Fig.5 Fig.7 Fig.9 2900 3000 3400 4300 4800 4800 8400 12900 21800 1900 2000 2000 2400 2400 2400 2300 2400 5600 1000 1000 1400 1900 2400 2400 1400 3600 4800 _ _ _ _ _ _ 1000 900 1000 E (Fan) 372 372 372 542 542 542 542 542 600 Approx. mass. (kg) F G (Depth) (Maintenance space) 1300 1300 1300 1400 1400 1400 1400 1400 1900 1300 1300 1300 1300 1300 1300 1500 1500 1800 4500 4900 6400 8400 10200 11200 17900 24500 51000

(*5) The standard front face of the panel is a covered type (except for the control output panel). A door type can also be manufactured. (*6) In the case of the 6.6kV type with a capacity of 5,200kVA and above, back to back installation (front/rear maintenance structure) reduces the

panel width by approximately half. Contact us for the dimensions of this type. (*7) The outline dimensions of the panel may be changed without notice. Contact us for details.

Front/rear maintenance structure


Fig.7 6.6 kV: 7000 kVA

Ceiling Upper maintenance clearance

2300

2360

Min. G 60 B C D C B

Front maintenance clearance

Rear maintenance clearance

Fig.8 3.3 kV: 5200 kVA

Wiring duct

Ceiling Upper maintenance clearance

C A

B
Min. G F 1200
Rear maintenance clearance Front maintenance clearance

Fig.9 6.6 kV: 10500 kVA


Wiring duct

D A

DIA2ED1080701-EN.indd 13

Min. 1100

Min. 500 600

22/07/09 11:36:21

DIA2ED1080701-EN.indd 14

22/07/09 11:36:23

Prepare your quote


Date Company Project name Market segment Application End user Standards & Certifications Customer specifications Project status Purchasing time frame Scope of supply Quantity of MV drives Scope of supply Drive Input switch/breaker Motor Supply data Power supply Auxiliary supply Control supply Motor parameters Type of motor Induction Rated power Maximum power Rated speed Rated frequency Rated current Maximum torque Excitation current Ventilation Load parameters Type of load Gear Variable torque Reduction ratio Starting time Overtorque Acceleration time Braking Installation Temperature (C) Relative humidity Drive Input transformer Distance Interface No. of analog inputs No. of digital inputs Communication Ethernet 24 VDC 4~20mA No. of digital outputs Modbus Profibus DeviceNet No. of analog outputs 24V VDC Dry contact Other 4~20mA Indoor: Altitude Indoor Air cooling Dry type min. Outdoor Oil filled max. Outdoor: Other 12-pulse input IP 00 24-pulse input IP54 Other Other min. max. less than 1000 m Water cooling Indoor Outdoor Drive to motor Regenerative Reverse speed Resistance 110% 60 s every 10 min. 150% 60 s every 10 min. kW Other Cycle Deceleration time Braking power Constant torque Inertia J (GD2/4) Constant power kNm kgm2 Other pu Breakaway torque (at 0 rpm) rpm Hz A % A Efficiency DOL starting current Inertia J (GD2/4) Excitation voltage Force-ventilated Synchronous kW kW Maximum speed % A kgm2 V New hp hp rpm Power factor pu Existing (retrofit) Number of poles Voltage Short circuit power Voltage UPS (Y/N) kV % (MVA) max: V % No. of phases Frequency min: Frequency V Hz % HV cable length Hz % Hz Input transformer Output switch/breaker Other By-pass Budget estimate less than 6 months RFQ phase between 6 & 12 months between 12 & 18 months more than 18 months Other Pump EPC IEC ANSI Fan Compressor OEM IEE Extruder SI UL Other Other Name Position/Organization Country Water & Wastewater Oil & Gas Power generation Mining & Minerals Metals Phone E-mail

Other informationScope of supply

Self-ventilated

Inside container Rectifier

Transformer to drive

DIA2ED1080701-EN.indd 15

22/07/09 11:36:24

Schneider Electric Industries S.A.S.


Head Office 35 rue Joseph Monier 92500 Rueil-Malmaison FRANCE www.schneider-electric.com ART : 837452 Date : 07/2009 Due to possible changes in standards and equipment, the features described in this document in the form of text and images are subject to confirmation by Schneider Electric. Designed and created by: Gavrinis Photos: Schneider Electric - Shutterstock

DIA2ED1080701-EN.indd 16

22/07/09 11:36:24

DIA2ED1090803EN - Imprimierie xxx