Vous êtes sur la page 1sur 38

HRSGInspectionTasks

PresentedBy: BryanF.Craig,P.E HRSTInc.

8/10/2009 Columbus, OH

AEP / BRO Forum

HRSGInspection
Goals:
1. Documentconditionofequipment 2. Identifyitemsthatneedimmediate maintenance 3. Identifyitemsthatneedbudgetingand planningformaintenancenextyear yp y, g 4. Identifyproblemsearly,allowingtimefor scrutinyandanalysis 5. Duediligence..showstakeholdersyouhave proactiveapproach.
8/10/2009 Columbus, OH AEP / BRO Forum 2

HRSGInspection
KeyElements 1. Dedicatedinspectors
Goodinspectionstakedaysnothours! Good inspections take days not hours! Photos,measurements,notes Everyfactshouldbeaccuratelylinkedtoaspecificlocation. Thickness(UT),Gapdistance,cracklength GasPath Steam/WaterSide Exterior
AEP / BRO Forum 3

2. Recordingobservations(facts) 3. Organizefactslogically 4. Measurementsatcriticalareas 5. Threelocationtypes

8/10/2009 Columbus, OH

HRSGInspection
GasSideInspectionAreas

AccessLanes(inletduct,firingduct,SCR, lanesbetweentubebundles,stack) l b t t b b dl t k) Crawlspacesunderandabovetube headers Importanttodocumentlocationsclearlyfor futurereference future reference Besttoprepareinadvance,ratherthan identifyproblemlocationsonthefly
8/10/2009 Columbus, OH AEP / BRO Forum 4

8/10/2009 Columbus, OH

AEP / BRO Forum

GasSideTasks
InletDuctItems:* 1. LinerSystem 1 Liner System
Looseplates,spinningwashers,exposedinsulation, failedstuds.

2. Flowdistributionplatesorvanes 3. Tubes&Fins
corrosion,warping,vibrationwear corrosion warping vibration wear vibrationdamage,wear,expansioninterferences,weld cracks.
AEP / BRO Forum 6

4. Baffles&TubeTies

8/10/2009 Columbus, OH

InletDuctLiner
Loose&brokencomponents

8/10/2009 Columbus, OH

AEP / BRO Forum

InletDuctLiner
SpinningWashers

8/10/2009 Columbus, OH

AEP / BRO Forum

InletDuctLiner
LinerGaps,ExposedInsulation

8/10/2009 Columbus, OH

AEP / BRO Forum

FlowDistributionGrid

8/10/2009 Columbus, OH

AEP / BRO Forum

10

TubeTies

Tube & fin wear at tube tie

8/10/2009 Columbus, OH

AEP / BRO Forum

11

FailedTubeTies

8/10/2009 Columbus, OH

AEP / BRO Forum

12

GasSideTasks
FiringDuctChecklist 1. LinerSystem(sameasinletduct,pluslookforoxidized components) p ) 2. DuctBurner:
Saginelementsorbaffles Nozzleplugging Cokebuildup Burnerwingcondition Evidenceofflameimpingementorlocalhotspots Evidence of flame impingement or local hotspots

3. 4. 5.

Tubes&Fins(sameasinletduct,plus)

Baffles&Supports Locationoffiringductthermocouples

8/10/2009 Columbus, OH

AEP / BRO Forum

13

Reheater upstream of duct burner


8/10/2009 Columbus, OH AEP / BRO Forum 14

BurnerBaffleFailures
Coen baffle weld seam cracks & failures

Coen fix for baffle weld seam cracks & failures. May not be enough, some cracking still being found.
8/10/2009 Columbus, OH AEP / BRO Forum 15

8/10/2009 Columbus, OH

AEP / BRO Forum

16

CarbonBuildup

Carbon inside gas pipe. Build up has fractured the gas pipe.

Coking: Usually due to olefins in refinery gas. Sometimes coking occurs with natural gas due to poor air/fuel mixing at burner.
8/10/2009 Columbus, OH AEP / BRO Forum 17

OxidizedLinerComponents

8/10/2009 Columbus, OH

AEP / BRO Forum

18

LocalBurnerHotspots

8/10/2009 Columbus, OH

AEP / BRO Forum

19

GasSideTasks
TubeBundleAccessLaneChecklist: 1. LinerSystem(samechecksasinlet&firing y ( g ducts,problemslessprevalent) 2. Tubes&Fins:corrosion,warping 3. Baffles&Supports(sameasprevious) 4. Catalyst
Fouling g Gasbypassaroundperimeter Packingbetweenblocks

8/10/2009 Columbus, OH

AEP / BRO Forum

20

10

Tube&FinFouling

8/10/2009 Columbus, OH

AEP / BRO Forum

21

Tubes&Fins
TubeBuckling Superheaters&Economizers

8/10/2009 Columbus, OH

AEP / BRO Forum

22

11

Tubes&Fins
Cracking HPSHTube

8/10/2009 Columbus, OH

AEP / BRO Forum

23

Exhaust flow into page

GasBaffles

Sidewall Baffles Upper Header Center (Laning) Baffles

Tubes

Lower Header Header (Bulkhead) Baffles

8/10/2009 Columbus, OH

AEP / BRO Forum

24

12

BaffleFailures

8/10/2009 Columbus, OH

AEP / BRO Forum

25

BaffleGapsDecreasePerformance

8/10/2009 Columbus, OH

AEP / BRO Forum

26

13

CatalystFouling

CatalystGasBypass

8/10/2009 Columbus, OH

AEP / BRO Forum

28

14

GasSideTasks
CrawlSpaceChecklist: 1. Waterfromtubeleaks? 2. Floordebris 3. Linercondition 4. Linerfituparoundpipingandhanger penetrations 5. Baffles 6. Bentpiping 6 Bent piping 7. Headercorrosion 8. Tube/headerjointcondition(ifvisible)

8/10/2009 Columbus, OH

AEP / BRO Forum

29

Spray pattern is a leak indication

15

Fin scale debris on crawlspace floor

Oxidized carbon steel debris on crawlspace floor

16

Accelerated corrosion near penetrations, probably caused by rain water leaking past penetration seal.
8/10/2009 Columbus, OH

Roof debris blocks drainage holes, trapping rainwater.

AEP / BRO Forum

34

17

BulkheadGasBypass

Hot Exh

8/10/2009 Columbus, OH

AEP / BRO Forum

35

Gap between baffle and floor is too large, allows gas bypass, decreasing performance.

8/10/2009 Columbus, OH

AEP / BRO Forum

36

18

BentDrainsIndicateStress

8/10/2009 Columbus, OH

AEP / BRO Forum

37

ExteriorTasks
ExteriorInspectionChecklist Exterior Inspection Checklist 1. Casinghotspots,cracks 2. Pipingpenetrationseals 3. Accessdoorcondition 4. 4 Foundations

8/10/2009 Columbus, OH

AEP / BRO Forum

38

19

Casing
AccessDoors HotSpot

8/10/2009 Columbus, OH

AEP / BRO Forum

39

PenetrationSeals

Bellows cracks can be difficult to see. Tight cracks, bellows are compressed when off line. Look for hot spots, and nearby insulation fur.
8/10/2009 Columbus, OH AEP / BRO Forum 40

20

These bellow cracks were easy to see! However, it took some extra effort to climb up on the roof casing to inspect.
8/10/2009 Columbus, OH AEP / BRO Forum 41

HRST Upgraded Pipe Penetration Seal

PROBLEM: Tears in Fabric T i F bi Cracks in Bellows Delay box

SOLUTION: HRST Pipe Penetration Seals

8/10/2009 Columbus, OH

AEP / BRO Forum

42

21

Casing Stress & Cracks

Expansion

Stress Points (Typ)


8/10/2009 Columbus, OH AEP / BRO Forum 43

Casing Stress & Cracks

22

Casing Crack

Hotspots

23

HRSGInspection
Water/SteamSideTasks

SteamDrumsaretheonlynonintrusiveaccess y tothewater/steamsideinamodernHRSG. Drumsareoftenalsoinspectedbythewater chemistrydeptandinsuranceinspector.

8/10/2009 Columbus, OH

AEP / BRO Forum

47

Water/SteamSideInspectionTasks
SteamDrumChecklist 1. Drumsurfacecondition 2. Signsofdistressonsteamseparation equipment&bellypan 3. Thicknessofbellyplatesandsteam separators 4. MechanicalIntegrity g y 5. Approximatewaterlinevs.drawing 6. Debris
8/10/2009 Columbus, OH AEP / BRO Forum 48

24

DrumSurfaceCondition
1. Drumsurfacedetails(color,condition,pits)
Color
Redisgoodinanoxidizingenvironment Redisbadinareducingenvironment Keeptrackofsurfacedefectsfrommanufacture Trackwhethersmoothness(roughness)ischanging Doyouhavethem? Whatdotheylooklikeunderneath?

Condition

Pits Pits

8/10/2009 Columbus, OH

AEP / BRO Forum

49

OxygenAttackinSteamDrum Offline

25

HPDrumCondition

Surface defects in an HP drum from rolling steel NOT a significant issue 8/10/2009 Columbus, OH AEP / BRO Forum

51

SignsofDistress
2. Signsofdistressonsteamseparation equipment&bellypan equipment & belly pan
Cracksinthebellypan Cracksinthefinalseparatorcorners Weldseamsintheshellandshelltohead Downcomerindications

8/10/2009 Columbus, OH

AEP / BRO Forum

52

26

SignsofDistress
Cracks?

Baffle Cracks?

8/10/2009 Columbus, OH

AEP / BRO Forum

53

HP BellyPanCracks (orbaffleplate)

8/10/2009 Columbus, OH

AEP / BRO Forum

54

27

Downcomer Indications

8/10/2009 Columbus, OH

AEP / BRO Forum

55

ThicknessofBellyPans andSteamSeparationEquipment
3. UTtest
F/W,Deltak,Vogt,NEM,Aalborg,Alstom,etc
BellyPans Cyclones(F/W=horizontal,others=vertical)

N/EandCerrey
BellyPans(nocyclones)

8/10/2009 Columbus, OH

AEP / BRO Forum

56

28

UltrasonicThicknessMeasurements
Thicknessmeasurementsareausefultoolto documentconditionofdruminternals,tubesand , piping. Bespecificaboutlocations&documentation Mostmeasurementsaresimplethicknessfor generaldocumentationortotrackFlow AcceleratedCorrosion MoresophisticatedUTusedforcrackdetection: h d df kd shearwave,phasedarray

8/10/2009 Columbus, OH

AEP / BRO Forum

57

8/10/2009 Columbus, OH

AEP / BRO Forum

58

29

Cycloneswornthrough fromFAC

8/10/2009 Columbus, OH

AEP / BRO Forum

59

BellyPanThinning UTinLP&IP Check here!

8/10/2009 Columbus, OH

AEP / BRO Forum

60

30

LPBellyPanHole(FAC)

8/10/2009 Columbus, OH

AEP / BRO Forum

61

MechanicalIntegrity
4. IntegrityofInternals i f l
Piping
BrokenUBolts Missingnuts PluggedChemFeedLines

Separators
Failure Plugging Missinghardware

8/10/2009 Columbus, OH

AEP / BRO Forum

62

31

HP FallenChemFeedLine

U bolt broke off

8/10/2009 Columbus, OH

AEP / BRO Forum

63

HPDrum ChemFeedLine

8/10/2009 Columbus, OH

AEP / BRO Forum

64

32

HPDrum brokencycloneattachment

8/10/2009 Columbus, OH

AEP / BRO Forum

65

Deltak PerforatedPlateAbove MeshSeparator

8/10/2009 Columbus, OH

AEP / BRO Forum

66

33

Deltak MeshSeparatorFailure

8/10/2009 Columbus, OH

AEP / BRO Forum

67

ApproximateWaterLine vs.Drawing
5. WaterLineReadings i di
Thewaterlineisoftenfalselyreadinglowdueto proximityofthedowncomerorpumpsuctiontothe leveltransmitters.Thesuctioneffectofthoselarge linespullsonthelevelsensinglines. Pluggingofthelinesisproblematiciftheyare positionedoffthebottomoftheshell. Thenumberonecauseoffaultylevelindicationor controliscalibrationorcompensation
8/10/2009 Columbus, OH AEP / BRO Forum 68

34

LP waterlevel

8/10/2009 Columbus, OH

AEP / BRO Forum

69

LP leveltransmitterproximity topumpsuction

8/10/2009 Columbus, OH

AEP / BRO Forum

70

35

Debrisinleveltap

Lower level tap magnetic debris


8/10/2009 Columbus, OH AEP / BRO Forum 71

DebrisinDrums
6. 6 Debris bi
Amount Color Magnetitevs.Hematite? Flakesvs.Powder?

8/10/2009 Columbus, OH

AEP / BRO Forum

72

36

Debrisindrum

8/10/2009 Columbus, OH

AEP / BRO Forum

73

Summary
GasSide
AccessLanes(inletduct,firingduct,SCR,betweentube Access Lanes (inlet duct, firing duct, SCR, between tube bundles,stack) Crawlspacesunderandabovetubeheaders Casinghotspots,cracks Pipingpenetrationseals Accessdoorcondition Foundations SteamDrumsaretheonlynonintrusiveaccesstothe water/steamsideinmostHRSGs

Exterior

Steam/WaterSide

8/10/2009 Columbus, OH

AEP / BRO Forum

74

37

HRSGInspection
FurtherWork
OnlineorHotInspection
HRSGinspectionwhileunitisoperating Idealforfindinghotspots,casingcracks,penetrationsealfailures g p , g ,p Cancheckhotpositionofspringhangers

ExtendedScopeofflineinspection
Dependingontheage,quantity&severityofcyclesandhistoryofissues, moreintrusiveinspectiontechniquesmaybebesttoquantifycondition. Commontechniques:
1. 2. 3. 4. 5. 6. 7. 8. 9. UTtubesandpipingbeyondspotchecks(AScan,PhasedArray,orShearWave) DyePenetrant orMagneticparticletestingofsuspectareas ConventionalandDigitalXRay(Radiography) EddyCurrentTesting PipingAssessment HardnessandReplication(P91) Desuperheaterremoval&inspection Borescoping Tubesamples

8/10/2009 Columbus, OH

AEP / BRO Forum

75

AnyQuestions?
BryanF.Craig,P.E HRSTInc. bcraig@hrstinc.com 8138554688(office) 6127431009(cell

8/10/2009 Columbus, OH

AEP / BRO Forum

76

38