BUS BARS AND TERMINALS Following factors must be considered while selecting the busbars Permissible temperatures of bus bar and equipments at rated currents and at short circuit conditions. Max.temperature for bus bar joints permissible as per DIN 43673 is 120C Permissible temperature rise for external connection as per IEC 694-1 is 60C for Cu and 70C for Silver plated terminal.
The current carrying capacity of bus bars can be calculated by equating the power loss in the busbar by the current to the heat loss due to convection and radiation.
Power loss =Heat loss due to convection + Heat loss due to radiation. IR = 2.74(T-T0)1.25 X h+b/ h1/4 XL+ 5.669 X 10-8 X 2(h+b) (T4 T04) XL R- Resistance at TC = R40(1+ aXTC), T 0 = Ambient temp in K(273 +40) T = End temperature of bus bar in K(273 + TC) R35= L/a = receptivity of conducting material (0.0265 for Al,0.0178 for Cu) a.= coefficient of resistively (0.0043 for Al, 0.00393 for Cu) = emissivity (0.216 for Al,0.0921 for Cu) L = length of bus bar(in m) h = width of bus bar (in m) b= Thickness of bus bar (in m) Note:- The calculated value of current is in open air, actual value will be less as the heat loss is not higher in the enclosed panel. Actual capacity is to be checked on a sample panel to know the correction factor to be applied for the particular design of panel.
Current carrying capacity for Al bus bars can be determined from DIN 43670 Ambient of 35C and operating temperature of 65C
Current carrying capacity for Cu bus bars can be determined from DIN 43671 Ambient 35C and operating temperature of 65C