CIM Standard for Substation Automation System


Praga, Monday, May 09, 2011
Prof. Veronika Brundula (Universidad Simn Bolvar) Janko Blatnik (GDB d.o.o.)

What role are having Substations inside the Smart Grid?

Universidad Simn Bolvar

To achieve the Smart Grid vision of nearreal time information, a transformation of the power grid communication infrastructure is needed, particularly in transmission and distribution substations. The existing supervisory control and data acquisition (SCADA) remote terminal unit (RTU) systems located inside the substation cannot scale and evolve to support next generation intelligence. New substation automation SCADA system is based on flexible IEC 61850 standards for communication and integration of new smart IED and IEC 61970/61968 for the integration into the control center.
2

What role are having Substations inside the Smart Grid?

Universidad Simn Bolvar

The migration towards this future smart substation is taking place because of: the need to reduce the operational costs to bring more intelligence and automation into the future power grid to comply with new regulatory requirements like NERC-CIP (North American Electric Reliability Corporation - Critical Infrastructure Protection) or UCTE - Operation Handbook

What are CIM and IEC 61850?

Universidad Simn Bolvar

CIM Common Information Model is the set of IEC 61970 and IEC 61968 standards for control center data. It enables interoperability and operation of the interconnected power systems IEC 61850 standard for substation data. It enables interoperability at substation level. Both standards use XML for data presentation. Both standards are under the jurisdiction of IEC TC57 working groups (http://cimug.ucaiug.org ). That gives them the same logic and makes then compatible.
4

How to design and build a new smart substation or renew an existing one to make it Smart Grid ready?

Universidad Simn Bolvar

IP communications Open standards like CIM and IEC 61850 Interoperability between different vendors Full redundancy Components are having integrated communication devices GOOSE messaging IEC 61850 station bus IEC 61850 process bus And with CIM we get Unified data model

How to design and build a new smart substation or renew an existing one to make it Smart Grid ready?

Universidad Simn Bolvar

SAS architecture

Universidad Simn Bolvar

CIM XML
Power system model importer/exporter

WEB Editor
Power system model Browser/Editor

WEB Reporting Services & WEB SCADA

WEB Work Flow (WWF)

GDA CIB (CIM Integration Bus) Syncronizer

HSDA

RDBMS

Technologies to use for SAS

Universidad Simn Bolvar

CIM integration Bus (CIB), is message bus based on OpenESB or WCF (Windows Communication Foundation). GID (Generic Interface Definition) are public APIs for CIB. GDA-Generic Data Access (IEC 61970-403) HSDA-High Speed Data Access (IEC 61970-404). CIB also supports N+1 redundancy of the system

Generic Data Acces GDA (IEC 61970-403)

Universidad Simn Bolvar

IEC 61970-403 Generic Data Access (GDA) defines services that are needed to access public entity objects for the power system domain that are defined in the IEC 61970-3xx series: Common Information Model (CIM). GDA permits a client to access data maintained by another component (either an application or database) or system without any knowledge of the logical schema used for internal storage of the data

Data flow (GDA)

Universidad Simn Bolvar

CIM XML File XML Parser

WEB Visual Editor XML Parser

SCADA Broker

AMI Broker XML Parser GDA Client

XML Parser

GDA Client

GDA Client

GDA Client

GDA CIB

10

High Speed Data Acces HSDA (IEC 61970-404)

Universidad Simn Bolvar

IEC 61970-404 specifies an interface for the efficient transfer of data in a distributed environment. Small amounts of data are transferred with short delay but also large amounts of data are transferred in short time but with possibly longer delay. This is a typical requirement for a SCADA system that acts as a real time data provider to other sub-systems. Other systems than SCADA may also benefit from the characteristics of HSDA. When short delay times as well as bulk data transfer is required, HSDA is a good fit.

11

Data flow (HSDA)

Universidad Simn Bolvar

Visual Editor XML Parser HSDA Client

SCADA Broker XML Parser

AMI Broker
XML Parser HSDA Client

HSDA Client

HSDA OpenESB

12

Benifits of suppoted technologies

Universidad Simn Bolvar

SOA architecture Open standards Integrated support for HTTP and web services Imata vgrajena komponente, ki omogoajo avtomatino transformacijo in povezovanje. OpenESB supports BPEL WCF has integrated the WWF

13

Performances

Universidad Simn Bolvar

Measurement
Performance Data flow

Resutls
<2s for average request Up to 500 requests per one 4 CPUserver

14

Redundancy

Universidad Simn Bolvar

WCF supports N+1 redundancy

15

Redundancy

Universidad Simn Bolvar

16

Security

Universidad Simn Bolvar

Encripted and compresed messages Avtentification based on username/passowrd or X.509 certificate

17

Interoperability

Universidad Simn Bolvar

WCF is based on web services, defined in WS-*. WS-* standards have been developed by different vendors like Microsoft, IBM, SUN... And today they are under the OASIS jurisdiction.

18

Interoperability

Universidad Simn Bolvar

19

Interoperability

Universidad Simn Bolvar

Metadata: The Web Services Description Language (WSDL) defines a standard language for specifying services and various aspects of how those services can be used. WS-Policy allows specification of more dynamic aspects of a service's behaviour that cannot be expressed in WSDL, such as a preferred security option. WS-MetadataExchange allows a client to request descriptive information about a service, such as its WSDL and its policies, via SOAP. Beginning with the .NET Framework 4 release, WCF also supports WSDiscovery. This broadcastbased protocol lets an application find services available elsewhere on its local network. Reliability: WS-ReliableMessaging defines additions to the SOAP header that allow reliable end-to-end communication, even when one or more SOAP intermediaries must be traversed.
20

Interoperability

Universidad Simn Bolvar

Transactions: Built on WS-Coordination, WS-AtomicTransaction allows using two-phase commit transactions with SOAP-based exchanges.

21

Integration mechanism and data flow of IEC 61850 and CIM

Universidad Simn Bolvar

22

Integration mechanism and data flow of IEC 61850 and CIM

Universidad Simn Bolvar

To be able to use CIM and IEC 61850 together we need to design mapping rules between CIM and IEC 61850. As we can see IEC 61850 and CIM representation the mapping is not too complicated: The breaker elements are the same in both standards Logical node associated with breaker is analogous to the CIM Discrete Value object The terminals associated with breaker are the same in both standards The Connectivity Node, Terminal of Busbar and the Busbar elements of the CIM standard are mapped to the Connectivity node of the IEC61850 standard. When we established the mapping rule we have a very good base for the integral solution.

23

Integration of IEC 61850 and CIM

Universidad Simn Bolvar

24

Integration of IEC 61850 and CIM

Universidad Simn Bolvar

As we can see, the integration of both standards gives us integral solution of Substation Automation System and Control Center. Each parameter can be entered into the system exactly once. The CID configuration files from IEDs are imported into the SAS. That import procedure builds up the SAS model. SAS model is exported as CIM-XML file and imported into the CIM compliant control center. That import builds up the power network model in control center. That can be also achieved automatically (on event) if the SAS and control center supports GDA API interface defined in IEC 61970-403. Real-time data between IEDs and SAS uses the IEC 61850 standard. For the communication between control center and SAS many standards can be used. Most commonly used standards are DNP 3.0 and IEC 60870-5-104. In the future we can expect that either IEC 61850 or HSDA defined in IEC 61970-404 will be used on that level.

25

Plug & Play Substation

Universidad Simn Bolvar

Integration of IEC 61850 and CIM (IEC 61970/61968) gives us Plug & Play substation automation system
26

Distributed control center

Universidad Simn Bolvar

That solution gives us so called Distributed control center solution. Every substation automation controller is part of the cluster connected with CIM based middleware
27

Benefits of Smart Substation

Universidad Simn Bolvar

New smart substations have fully redundant design. All components are having integrated communication devices. Instead of old fashion hard wire solution between secondary and primary equipment, a new IEC 61850 IP based process bus is taking its place. Instead of serial point to point communication IEC 61850 IP based station bus is taking its place. Instead of hard wire for inter IED communication (interlocking ), IEC 61850 GOOSE messaging is used. The configuration of IEDs is standardized with IEC 61850 and can be imported into the station controller as CID file for each IED. Most of the hard wires in substations are replaced with IP communication. Adding new smart primary equipment is simply adding a new IP device into the IP network, same as with secondary equipment. The complete model of a substation can be transferred into the control center as CIM-XML file or through GDA-Generic Data Access API using the CIM standards IEC 61970/61968. GDA even supports that every change in the configuration of station controller is automatically transferred to the control center.
28

CIM Client

Universidad Simn Bolvar

29

WEB Scada

Universidad Simn Bolvar

30

CIM based enterprise solution


SCADA/DMS AMR Klicni Center

Universidad Simn Bolvar

WEB.SCADA

WEB.AMI

CIM Integration Platform


GDB.DAQ

Open Meter API, Google Meter API

PROCESS LAN WEB Services (Proprietary)


DC
S-FSK PLC

HSDA, GDA
WEB.DC

CIM Integration Bus IEC 101, 104 DNP 3.0 WEB.SAS IEC 101, 104 GDA, CIM-XML, IEC 61850, 101, 103 HSDA DNP 3.0
WEB.SAS SAS
IEC 61850, 101, 103 IEC 61850, 101, 103

S-FSK PLC

G3-PLC, ZigBee

DLMS

DLMS

31
IP Meter

Conclusion

Universidad Simn Bolvar

CIM and IEC 61850 offer us an open cost effective solution. Both standards has been worldwide accepted by different utilities and manufactures. Both standards, each for its level, offers interoperability, free configuration, cost effectiveness, scalability and reliability.
The integration of both levels, substation and control center is indispensable. Both standards are becoming the facts as the utilities are migrating to the open and network solution for their SAS and control centers.

32

Universidad Simn Bolvar

Universidad Simn Bolvar Sartenejas, Baruta, Edo. Miranda Apartado 89000 Caracas Venezuela Tel: +58 412 9800 358 vbrundula@usb.ve

THANKS

GDB d.o.o. Tehnoloki park 24 1000 Ljubljana Slovenia-EU

Tel: +386 59 0322 45 Fax: +386 59 0322 46 E-mail: cim@gdb.si www.gdb.si

33

Vous aimerez peut-être aussi