Académique Documents
Professionnel Documents
Culture Documents
UNIT - I
INTRODUCTION TO POWER QUALITY Terms and definitions Overloading Under voltage Sustained interruption-Sags and Swells Waveform distortion Total Harmonic Distortion (THD) Computer Business Equipment
ENERGY
ENERGY CAN NEITHER BE CREATED NOR BE DESTROYED BUT IT CAN BE CONVERTED FROM ONE FORM TO ANOTHER FORM.
ELECTRICAL ENERGY
GENERATION OF ELECTRICAL ENERGY IS NOTHING BUT THE CONVERSION OF VARIOUS OTHER FORMS OF ENERGY INTO AN ELECTRICAL ENERGY.
POWER QUALITY = VOLTAGE QUALITY Any Power Problem manifested in Voltage, Current, (or) frequency deviations that results in failure (or) mis-operation of customer equipment . It is related to hardware, software (or) control system malfunctions.
WHY WE ARE CONCERNED ABOUT POWER QUALITY ? The Main reasons behind the growing concern about PQ are:
North American industries lose Tens-of-Billions of Dollars every year in downtime due to power quality problems. (Electrical Business Magazine) Load non-linearities in rising and is expected to reach 50 to 70% in the year 2005 (Electric Power Research Institute) [Computers, UPS, fax machines, printers, fluorescent lighting, ASD, industrial rectifiers, DC drives, arc welders, etc).
WHY WE ARE CONCERNED ABOUT POWER QUALITY ? Economic impacts on utilities, their customers, and suppliers of load equipment. Meeting Customer Expectations Customers : 1. Industrial 2. Domestic 3. Commercial
POWER QUALITY ISSUE AND PROBLEMS Power Quality issues can be roughly broken into a number of sub-categories: Harmonics (sub, super and inter-harmonics); Voltage swells, sags, fluctuations, flicker, and transients Voltage magnitude and frequency deviation, voltage imbalance (3ph sys.) Hot grounding loops and ground potential rise (GPR)Safety & Fire Hazards Monitoring and measurement.
BLOCK DIAGRAM
GENERATION TRANSMISSION & DISTRIBUTION CUSTOMERS
INDUSTRIAL CUSTOMERS
RESIDENTIAL CUSTOMERS
COMMERCIAL CUSTOMERS
TRANSIENTS
Used in the analysis of power system variations to denote an event that is undesirable and momentary in nature. Classified in to 2 categories (i) Impulsive Transient (ii) Oscillatory Transient
TYPES OF TRANSIENTS
IMPULSIVE TRANSIENT It is a sudden, nonpower frequency change in the steady state condition of voltage, current (or) both that is unidirectional in polarity. They are normally characterized by their rise and decay times, which can also be OSCILLATORY TRANSIENT It is a sudden, nonpower frequency change in the steady state condition of voltage, current or both, that includes both positive & negative polarity. Example : Capacitor Bank Energization.
OVERVOLTAGE
An overvoltage is an increase in the r.m.s. ac voltage greater than 110 % at the power frequency for a duration longer than 1 min. It is a result of load switching. Eg : Switching OFF a Large load Energizing a capacitor bank
UNDERVOLTAGE
An undervoltage is a decrease in the rms ac voltage to less than 90 % at the power frequency for a duration longer than 1 min. Example : Load Switching Capacitor Bank Switching off
INTERRUPTIONS
An interruption occurs when the supply voltage or load current decreases to less than 1p.u for a period of time not exceeding 1 min. It can be the result of power system faults, equipment failures and control malfunctions.
VOLTAGE SAG
A sag is a decrease to between 0.1 and 0.9 p.u in r.m.s voltage or current at the power frequency for durations from 0.5 cycle to 1 min.
VOLTAGE SAG
VOLTAGE SWELL
A swell is defined as an increase 1.1 and 1.8 p.u in r.m.s voltage or current at the power frequency for durations from 0.5 cycle to 1 min.
VOLTAGE IMBALANCE
Also called Voltage Unbalance Maximum deviation from the average of the three phase voltages (or) currents.
SYSTEM MODEL
E l e c t r ic U t i l it y T ra n s fo rm e r S y s te m + T ra n s fo rm e r+ F e e d e r E le c t r ic E q u iv a le n t ( P la n t) L o a d Load B us
N o n l in e a r L o a d ( N L L )
S w itc h e d /M o d u la te d P o w e r F ilte r o r S ta tic C a p a c ito r C o m p e n s a to r * S m a r t- c o n tr o lle rs a r e b a s e d o n s p e c ifie d c o n tro l o b je c tiv e s C o n tro l S ig n a ls C o n v e rte r T y p e A rc T y p e D y n a m ic C y c lic a l R ip p le In r u s h T e m p o ra l M o to r iz e d o n /o ff SM PS ASD S a tu r a tio n T y p e
Y F(s )
SM PF D if f e r e n t T o p o lo g ie s
o n /o ff o r PW M
is Vs Ps
S m a rt C o n tr o lle r *
N L L
N o n lin e a r Load
e ig h t d e s ig n s (D r. A .M . S h a r a f)
Y F ( T A F , C - T y p e , H P D F , S p e c ia l T o p o lo g y )
WAVEFORM DISTORTION
Steady-state deviation from an ideal sine wave of power frequency principally characterized by the spectral content of the deviation. 5 types of waveform distortion 1. DC offset 2. Harmonics 3. Inter-Harmonics 4. Notching
ITI CURVE
ITI Curve ---- Information Technology Industry Council Curve A set of curves published by ITI representing the withstand capabilities of computers connected to power systems in terms of magnitude and duration of the voltage disturbance.
CBEMA CURVE
CBEMA ---- Computer Business Equipment Manufacturers Association. A set of curves representing the withstand capabilities of computers in terms of the magnitude and duration of the voltage disturbance. Standard for measuring the performance of all types of equipment and power systems.
CBEMA CURVE