Académique Documents
Professionnel Documents
Culture Documents
Instrument Transformers
24 oct 2007
gva
PRESENTAION BY
G.V.Akre Director Production Hivoltrans Electricals Private Limited Halol, Gujarat,India
INTRODUCTION
-Instrument transformers play vital role in power system and their operational reliability is very important. -There are frequent cases of catastrophic failure of Instrument Transformers. -Explosive failure may cause damages to adjoining equipments causing considerable loss of asset & injuries (sometimes fatal) to the personnel. -Failure of ITs leads to malfunctioning of system protection, controls, instrumentation and costly power outage. Explosive failure is caused as the result of sudden pressure and heat developed due to huge arc formation, burning and vaporisation of oil/paper in small confined space.
24 oct 2007
gva
INTRODUCTION
Large population of equipments commissioned during last 2 to 3 decades are ageing out which is cause of concern as the failure of aged CTs is not predictable. -Looking at the consequences of failure, the focus has now changed from Conventional Maintenance to Condition Based Monitoring.
24 oct 2007
gva
BATHTUB CURVE
24 oct 2007
gva
BATHTUB CURVE
The curve is a general representation of failure pattern of electrical equipments from the initial years of commissioning to the end of operating life. Failure during first few years are usually due to manufacturing defects,transit damages,installation problems,leakages etc as explained in detail ahead. Random failure mode includes failures due to service condition,system switching serges,lightening impulses,ineffective maintenance etc.The rate of failure during this period is quite low. Wearout failures includes natural aging process resulting into dielectric degradation. Failures during this period are sudden and unpredictable.
The failure rate during this period is quite high.This period as experienced by utilities starts after two oct 2007 gva 24 decades.
L1
CATASTROPHIC FAILURE
24 oct 2007
gva
Failure
24 oct 2007
gva
24 oct 2007
gva
24 oct 2007
gva
10
Factors responsible for failure -Life of IT is expected to be around 20-25 years. -Early failures due to manufacturing defects are low compared to aged out transformers. - Failure of aged out transformers is often sudden and catastrophic. -State of deterioration in such equipments has to be properly diagnosed and timely action be taken. Following factors are some of the main causes responsible for degradation ofoct 2007 gva insulation. 24
11
Factors responsible for failure Manufacturing defects Residual Moisture-inadequate drying of insulation Over stressing- electrical stress Partial Discharges Dielectric loss overheating of insulation Selection of R.M. Improper insulation design Overheating due to I2R loss in primary Poor quality control Poor hermetic sealing -moisture ingression -air ingression
24 oct 2007 gva 12
Service Condition Mishandling and damage during transit/installation Contacts of terminal connectors Unattended leakages-moisture ingress Leakage of N2 gas Leakages through aged out pressure release device Old installation, frequent interruption / overcurrents Lightening and switching surges Ferroresonance Polluted atmosphere Poor maintenance program
24 oct 2007
gva
13
Natural Ageing thermal, mechanical and chemical are continuously acting on paper and oil insulation. -The stresses cause the natural aging process of degradation of insulation.
DEGRADATION PROCESS OF INSULATION Oil impregnated paper (OIP) is standard and proven insulation system used in design of HV equipments. The combination has much more better insulation strength. Insulation paper is made from cellulose fibre. Paper is very hygroscopic by nature & readily absorbs moisture from the surrounding. Aging is influenced by degradation of cellulose and oil as the result of different stresses. Aging accelerate in presence of oxygen and moisture.
24 oct 2007 gva 15
DEGRADATION PROCESS OF INSULATION Thermal degradation causes oxidation & reduces strength of paper (degree of polymerization). Degrdetion process produces mainly H2, CO2, CO, Methane (CH4), H2O, acids and sludge. Water formed acts as catalyst to accelerate further degradation Oxygen mainly affects the oil causing oxidation
24 oct 2007 gva 16
Effects Production of components like H2, CO2, CO, methane, H2O,sludge and acids Reduces tensile strength of paper (degree of polymerization) Affects resistivity & insulation properties of oil & paper Increases tan delta, which in turn increases dielectric heating Tan delta of 0.5% produces 20 watts in 245 kV insulation & 100 watts in 420 kV CT insulation as dielectric loss(heat loss)
24 oct 2007 gva 17
With low dissipation rate of heat, there may be thermal breakdown of insulation. Thus, it can be seen that presence of moisture and O2 can cause speedy degradation of insulation. A poorly dried transformer with higher moisture content and gas (particularly O2) drastically reduces life expectancy. Initial moisture and O2 causes early degradation reducing life expectancy. A well-dried but leaking transformer can easily absorb moisture & O2 from atmosphere.
24 oct 2007 gva 18
- Moisture present in CT is absorbed by paper and oil in a proportion depending on temperature - There is always equilibrium between moisture in cellulose of paper and oil in an insulation system at any given constant temperature. - With change in temp, the equilibrium is disturbed and transition of moisture takes place between oil & paper. - At higher temperature, the water absorption in oil increases and that of paper reduces
24 oct 2007 gva 19
- As temperature reduces moisture migrates from oil to paper. - It is also established that oil to paper migration is faster than that from paper to oil - During sunny days with higher loads, temp is high and migration of water takes place from paper to oil - During cool nights the reverse takes place & moisture migrates from oil to paper - With high variations in the temperature the concentration of the moisture in any of the media may become critical and break down may take place.
24 oct 2007 gva 20
24 oct 2007
gva
21
MOISTURE TRANSITION
contd.
Illustration from the experimental graph. - At 60C with moisture of 20 ppm in oil, the paper contains 2.5% moisture by weight - At 20C with moisture of 20 ppm in oil, the paper cancontain 7% of moisture by weight. - The paper with higher percentage of total moisture present in CT may cause reduction of dielectric strength significantly and leads to insulation breakdown. - Above experimental finding is also experienced by fact that max failures are taking place during cool nights of hot summers in India,when max variation in temp takes place.
24 oct 2007 gva 22
- In new transformers,the the paper and oil must be perfectly dried to minimise the initial moisture content. (preferably 5 ppm in oil and max 0.5% in paper.) The moisture accelerate the degradation process during initial years. - ITs are minimum oil equipment and oil is not changed during its lifetime,hence the must be hermetically sealed,preferably with metallic bellows. - If nitrogen cushioned sealing is provided, the required pressure should be monitored and maintained during operating life. - Leakages must be attended immediately. Even minor leakage can absorb substantial moisture and O2 from atmosphere in course of time. - With above precautions, the risk of absorption of external moisture will be minimum. 24 oct 2007 gva 23
Condition monitoring may be defined as a process of monitoring the characteristics during operation of equipment and find out the changes and trends of the characteristics of the insulation system which can be used to predict the need for maintenance before serious deterioration occurs.
Thus it determines the health of the equipment and routine maintenance can be rescheduled as required.This reduces the unnecessary cost of maintenance.
24 oct 2007 gva 24
Electrical Diagnostic Tests Test for Insulation Resistance Polarization Index Tan Delta and Capacitance Measurement Resistivity, tan and BDV of oil Partial Discharge Test on site Chemical Analysis
Diagnostic tests
Other Tests and Inspection Infrared Thermograph Visual inspection for leaks, polluted insulators, corona discharges.
24 oct 2007 gva 25
(A) -Test for Water content -Dissolved Gas Analysis (DGA) -IFT (B) -Degree of Polymerization (DP) -Furan Analysis
Insulation Resistance Test Initial screening test for equipments. To use high range 1000,000 m, 5 to 10 kV IR tester Test during fair weather condition. Frequency of test may be high for better results. Gives initial warning to engineers to decide further investigation. Normally useful for medium and low voltage trans upto72.5 kV. Polarization Index
Ratio of IR values at end of 600 seconds and 60 seconds. Possible only with high range meggar. Value of 1.3 to 2.0 indicates good insulation for instrument transformers.
24 oct 2007 gva 26
Tan and capacitance Test One of the best diagnostic test to monitor insulation condition. Concept of tan can be explained by considering insulation as capacitor. An ideal capacitor carries only capacitive current (Ic) which leads the voltage by 90. But actual capacitor formed by transformer insulation conducts resistive current (Ir) due to moisture and impurities. The resultant current (I) is vectorial sum of Ic and Ir and leads voltage by slightly less than 90. The angle between Ic and I is called loss angle and tangent called tan .
24 oct 2007
gva
27
24 oct 2007
gva
28
Tan-delta Test Higher tan indicates degraded insulation. Comparison between periodic measurements reveal trend in deterioration of insulation. Increase in tan may be due to Moisture, contaminated oil, internal PDs etc. Rise in tan with rise in voltage indicates high moisture /deterioration and steeper rise indicates major defects. Higher tan increase dielectric losses producing losses and heat, thus causing more degradation. Normal value for new CTs can be 0.15 % to 0.4%
24 oct 2007
gva
29
Tan-delta Test --cont.. Old equipment with more than 0.8% should be closely monitored. Higher tan produces higher dielectric loss and if paper-oil insulation do not dissipate the heat it will lead to thermal breakdown. Partial Discharge Test at Site More advanced site testoff line or online. -Direct online method receives signals from PF terminal of CT. -Signals are mixed with unwanted external discharges. -Special filters and microprocessor base instruments for separating internal discharges from external. -Identifies fault in insulation.
24 oct 2007 gva 30
Resistivity, tan and BDV ,IFT,Acid Number of oil Tan-delta increase indicates oxidation,contamination and suspended water particals. Low BDV indicates moisture, contamination due to oxidation. Low resistivity indicates presence of suspended water, acidic oxidation etc. -Decrease in Resistivity with increase in tan indicates soluble contaminants and aging. -Satisfactory resistivity at 90 compared with low resistivity at ambient temperature indicates moisure. IFT detects contaminants and oxidation products in insulating oils.
24 oct 2007 gva 31
Water Content Test water content in oil should be less than 10 ppm, target to be 5ppm. High content results into lower BDV and higher tan and conductivity. Moisture in oil may provide some information about moister content in paper insulation, but it may not be always true.Temperature at which samples taken is important due toTransition Theory of mosture Above tests in addition to DGA and Furan can give more reliable information about insulation condition.
24 oct 2007 gva 32
-- cont
IEC 60599, IEEE C. 57.104 and other standards provides method to establish nature of faults on basis of gasses generated. By taking periodic tests, trend in degradation of insulation can be determined. In hermetically sealed ITs,the oil movement is very slow and the dissolve gas may move to sample collection point after several days. Hence the test results may not give the status of present insulation condition.
24 oct 2007 gva 34
Degree of Polymerization Measurement (IEC 450) DP Determines thermal aging of solid cellulose insulation. Quality of cellulose is measured in DP. Measures indicate tensile strength of paper. New Kraft paper has DP = 1000 to 1500. With long service DP maybe = 200 to 250. DP value of 150 to 200 indicates mechanical strength of only 20% of initial strength and is considered to be the end of insulation life. Most accurate test, but sample of paper must be obtained which is impossible for IT. Use to verify remaining life of the equipment. May be performed to establish cause of failure in failed equipments.
24 oct 2007 gva 35
Furan Analysis Furans form as degradation product of solid insulation and are soluble in oil. Furan analysis is performed by drawing sample from oil from operating transformer. Easy test as compared to DP test as transformer is not required to be opened. Interpretation of results are not as reliable as DP. No universal correlation established between DP and Furan yet. Furan analysis, DGA Test & DP Test combined offers very reliable conclusion.
24 oct 2007
gva
36
MAINTENANCE PROGRAM
1.
2. 3.
4.
A simple program may be devised for condition monitoring by users as under: Regular measurement of IR, PI, Tan, and capacitance be made at suitable intervals in fair dry weather and recorded.Their correlation can be determined. The variations from each periodical test be recorded in a computerized database and the trend of deterioration determined. If the trend is indicative of progressive deterioration, then oil sample should be drawn for Moisture content,IFT,Acid numbers, DGA and Furan test. If oil tests confirm the deterioration, the instrument transformer should be removed from services as early as possible to avoid catastrophic failure. 24 oct 2007 gva 37
For small and medium voltage equipments where population is in thousands, IR, PI, Tan tests may be taken as indicator to replace them. The transformer up to 145 kV may be sent for reconditioning to departmental workshop. The transformers of 245 kV and above should be sent for further investigations to manufacturer of instrument transformers where Partial Discharge test and tan-delta at operating voltage can be performed. The transformer may be re-processed only if there is reasonable remaining life left. For 420 kV class transformers, where population is not high comparatively, should be regularly tested on-site for Moisture, DGA and Furan along with electrical tests listed in step 1.
24 oct 2007 gva 38
As a result of compelling need felt by many utilities, online monitoring systems have been developed for transformers in more advanced countries to avoid unexpected failures. On-line monitoring of critical network assets provides information previously unavailable. This in turn allows better asset management. It is fast maturing into a serious and reliable network tool. Normally dissipation factor and partial discharge tests are conducted on line using specially developed instruments. Technique of on-line monitoring of DGA and evolved gases is also developed, however it is mostly used for very costly equipments like power transformers presently.
24 oct 2007 gva 39
The key advantages are: 1. Relevant data collected and made visible on network. 2. Major help in delaying routine maintenance as long as possible hence driving down costs. 3. Costly and not easy to replace equipments are prime candidates for on-line monitoring. 4. Damage to the asset is minimized. 5. Equipment need not be taken out of service
24 oct 2007 gva 40
Infrared systems can measure temperature of exposed parts of equipment online. Can be used on routine basis by maintenance engineers. Infrared thermal imaging system is a technique involving infrared camera, software and computer. Camera senses infrared radiation from heated components of equipment in yard. A computer processes this information and displays the images of components with different colors depending upon the temperatures. By comparing the difference in similar parts in the equally loaded CTs in different phases, abnormally heated component is pointed out. Further investigation, corrective action is taken avoiding further damages.
24 oct 2007 gva 41
INFRARED THERMOGRAPHY
24 oct 2007
gva
42
24 oct 2007
gva
43
24 oct 2007
gva
44
24 oct 2007
gva
45
CONCLUSIONS The degradation and subsequent failure of transformers is the result of aging of cellulose from paper insulation at elevated temperatures. Use of proper material and best manufacturing practice is the first step to minimize the degradation of insulation. However, for the instrument transformer to live its full life of 25-30 years, it is important to adopt efficient maintenance management by monitoring the condition of insulation at site by the user.
24 oct 2007 gva 46
Conclusions
In our country, very few utilities may be using some or all of the diagnostic techniques. Therefore, increased awareness and adoption of these essential techniques is highly desirable Effective condition-based maintenance practices for substation plant assets will result in reduced controllable operating costs and improved utility performance. Proper investigations and analysis of failure of the equipments, carried out worldwide has resulted into improvement in electrical equipment design. It has also revised systems and developed new equipments for health monitoring.
24 oct 2007 gva 47
CONTD Presently On-line monitoring is becoming main focus area for utilities mainly in developed countries to evolve new techniques for reliable operation of power equipments.
It is highly desirable that the utilities and equipment manufacturers in our country have collaborative efforts in bringing together the resources in form of their experiences/data on failures, ideas, personnel, skill and fund to have common guidelines on the subject of condition monitoring.
24 oct 2007
gva
48
HIVOLTRANS
THANK YOU
G.V.AKRE
HIVOLTRANS ELECTRICALS PRIVATE LIMITED, GUJARAT,INDIA.
24 oct 2007
gva
49
RATIO TEST
24 oct 2007
gva
50
Processinfg of Insulation MOISTURE IN PAPER AND OIL 1) Paper = 3 - 7 % Moisture After drying - < 0.5% Moisture. 2)Raw Oil = 30 - 55 ppm Moisture After Processing- < 10 ppm of moisture. 3)Processed Oil BDV = 65-70kV. Oil from Inst trans. = 45 - 55 kV. 4)Gas in Oil apprx.10% to 12 % After Processing and Degassing - 0.1% Gas Content. 24 oct 2007 gva
51
These special class metering CTs require the stipulated accuracy limits to be maintained upto 1% of the operating primary current. Normal CTs require this limit to 5% of primary current. IS 2705, 1992 specifies these CTs for 5 Amps secondary current and ratios of 25/5, 50/5, 100/5 & their decimal multiples. However, IEC in their amendment in 2002,included 1.0 Amp CT but with observation that there is uncertainty in accuracy measurement at low current.
24 oct 2007 gva 52
Voltage Factor
The voltage factor is dependent upon the system earthing condition. To achieve high VF core flux density has to be reduced substantially, which increases the cost. Adequate VF must be provided OR there is danger of failure during fault on the system which produce transients of high voltage nature. VTs with low VF are prone to Ferro-resonance under favorable conditions. Under fault conditions in isolated neutral system, the voltage appearing across open delta winding is 3 times the rated sec voltage.
24 oct 2007 gva 54
Life may be increased by reprocess if life of insulation is not over. Purpose clean insulation of carbon particles, wax, etc. Replace components like gaskets, pitted terminals, explosion vents, secondary terminals. Remove moisture, replace degraded oil. Improve IR, Oil Resistivity, etc. Process Remove all oil, dismantle and reassemble with parts as above. Heat the trans in oven for 24 hours at around 80-90 dgree under vacuum. Fill fresh treated hot oil (65-75 deg.cent)under vacuum so as to penetrate the bulk of insulation. After 24 hrs, remove this oil which washes out trapped oil in insulation. Repeat the process twice or thrice by observing drained oil for color, BDV. Treat the washed equipment in oven under vacuum at 70 80 C for sufficient time depending upon voltage class.(3 to 7 days for 33 kv to 220 kV) Remove finally the oil residue before filling finally with dry hot oil.
24 oct 2007 gva 57
A)ELECTRICAL POWER RESEARCH INST. (EPRI-1) EPRI has sponsored extensive research targeted at understanding the dynamic behavior and effects of moisture in transformer insulation systems. High Voltage Instrument Transformers & Bushings A project has been completed to monitor a large number of HVCTs and bushings in laboratories and in service, including on-line tan delta, partial discharge (pd) and other available monitoring methods. Units were tested to failure to evaluate failure modes, sensitivity of monitoring and to develop "end-of-life" criteria for interpretation of field monitoring data.
24 oct 2007 gva 59
EPRI-4
About the Electric Power Research Institute The Electric Power Research Institute (EPRI), with major locations in Palo Alto, California, and Charlotte, North Carolina, was established in 1973 as an independent, nonprofit center for public interest energy and environmental research. EPRI brings together members, participants, the Institute's scientists and engineers, and other leading experts to work collaboratively on solutions to the challenges of electric power. These solutions span nearly every area of electricity generation, delivery, and use, including health, safety, and environment. EPRI's members represent over 90% of the electricity generated in the United States. International participation represents nearly 15% of EPRI's total research, development, and demonstration program.
24 oct 2007 gva 60
24 oct 2007
gva
61
24 oct 2007
gva
62
24 oct 2007
gva
63
From www.sayedsaad.com /highvoltage/- In practical applications liquids are normally used at voltage stresses of about 5060 kV/cm when the equipment is continuously operated. On the other hand, in applications like high voltage bushings, where the liquid only fills up the voids in the solid dielectric, it can be used at stresses as high as 100200 kV/cm.
24 oct 2007
gva
64
From http://www.usbr.gov/power/data/fist/fist3_30/fist3_30.pdf
It should be noted that small amounts of H2, CH4, and CO are produced by normal aging. Thermal decomposition of oil-impregnated cellulose produces CO, CO2 , H2, CH4, and O2. Decomposition of cellulose insulation begins at only about 100 C or less. Therefore, operation of transformers at no more than 90 C is imperative. Faults will produce internal hot spots of far higher temperatures than these, and the resultant gases show up in the DGA.
24 oct 2007
gva
65
http://www.usbr.gov/power/data/fist/fist3_30/fist3_30.pdf
a)4.6.2 Interfacial Tension (IFT). This test (ASTM D-791-91) [21], is used by DGA laboratories to determine the interfacial tension between the oil sample and distilled water. The oil sample is put into a beaker of distilled
water at a temperature of 25 C. The oil should float because its specific gravity is less than that of water, which is one. There should be a distinct line between the two liquids. The IFT number is the amount of force (dynes) required to pull a small wire ring upward a distance of 1 centimeter through the water/oil interface. (A dyne is a very small unit of force equal to 0.000002247 pound.) Good clean oil will make a very distinct line on top of the water and give an IFT number of 40 to 50 dynes per centimeter of travel of the wire ring. -As the oil ages, it is contaminated by tiny particles (oxidation products) of the oil and paper insulation. These particles extend across the water/oil interface line and weaken the tension between the two liquids. The more particles, the weaker the interfacial tension and the lower the IFT number. The IFT and acid numbers together are an excellent indication of when the oil needs to be reclaimed. It is recommended the oil be reclaimed when the IFT number falls to 25 dynes per centimeter. At this level, the oil is very contaminated and must be reclaimed to prevent sludging, which begins around 22 dynes per centimeter. See FIST 3-5 [20]. -If oil is not reclaimed, sludge will settle on windings, insulation, etc., and cause loading and cooling problems discussed in an earlier section. This will greatly shorten transformer life.
24 oct 2007 gva 66
Fault processes such as arcing, pyrolysis and partial discharge differ tremendously in their energy content. Partial discharge is the lowest energy process and will characteristically produce significant amounts of only hydrogen. Thermal processes (pyrolysis) will produce methane, ethane, ethylene, as well as hydrogen. Arcing will produce all of the fault gases. It is the only fault process that will produce acetylene.
24 oct 2007
gva
67
IFT
IFT Significance: The magnitude of the IFT is inversely related to the concentration of the hydrophilic degradation products from the deterioration of the oil. Since the hydrophilic materials are usually highly polar and thus not very soluble in the non-polar oil, the presence of these species can result in sludge formation. These materials that remain dissolved in the oil can affect the desired electrical properties of the oil. They will reduce the dielectric strength and increase the dissipation factor of the oil. Sludge buildup can also affect the heat transfer characteristics of the oil by slowing or perhaps even blocking circulation of the oil.
24 oct 2007 gva 68
IFT There is usually an inverse relationship between the neutralization number of an oil and its IFT. As an oil sample undergoes oxidative degradation, its neutralization number will increase while its IFT value will decrease. It should also be recognized that a decrease in the IFT does not imply that the acidity must also be high, since there are other non-acidic contaminants that could be present in the oil that are hydrophilic and will lower the IFT but not raise the acidity. An example of such a situation might be that of a free breathing transformer near salt water where a salt water mist might be able to enter the unit. Such an event will not affect the acidity but would markedly affect the IFT and dielectric strength of the oil.
24 oct 2007 gva 69
1. 2. 3. 4. 5. 6. 7. 8. 9.
24 oct 2007
gva
70
- Cross section selected considering rated thermal current and short time current requirement - Example : Ratio = 150 / 1, STC = 40 KA / 1.0 Sec Cross Section for 150 A = 150 / 1.65 = 91 mm2 Cross Section for 40 KA / 1.0 sec = 40000/180 = 223 mm2 Thus, Primary Winding section required = 223 mm2 - Heat generated (I2R) due to passage of STC is not dissipated stored as latent heat - Temp is increased momentarily before dissipation - Design should absorb such heat shocks - STC current peaks are approx 2.5 times RMS value - Peak current (say 100 KA) develops high mechanical forces inside primary winding - Primary must be reinforced to withstand such dynamic 71 24 oct 2007 gva forces
PRIMARY WINDING OF CT
REFERENCES-1
References: Internal Insulation Failure Mechanism of HV Equipment under Service Condition GIGRE, Session 2002, by A.K. Lakhanin, V.V.Sokolov. IEEE Guide for Interpretation of Gases Generated in oil immersed transformers. Std. C.57.104-1991 Review of Modern Diagnostic Techniques for Assessing Insulation Condition of Aged Transformers. By Tapan K. Saha. Diagnostics of Paper and Oil CT Insulation CIGRE International Conference on large H.V. Electrical Systems 1998. Live Assessment of Transformers By M.J. Patel, ERDA. B.Buereschaper, O.Kleboth - Lugova and T.Leibfried. The electrical strength of transformer oil in a transformer board-oil system during moisture non-equilibrium. Terry Krieg, ElectraNet SA, Jeff Benach, AVO International.
24 oct 2007 gva 72
REFERENCES-2
Managing High voltage current Transformers and Bushings using On-Line Insulation Monitoring Technique. The AVO SOS system is designed to provide continuous online monitoring of insulation condition by comparative measurement of insulation capacitance and dielectric dissipation factor. Powerlink Queensland, Australias research and development (R&D) team developed innovative condition-monitoring techniques. Initially, the team produced the Instrument Transformer Testing Device (ITTD), which led to the development of the continuous online monitoring system in the early 1990s. LCMSEA- Life Cycle Management of Substation Equipment and Apparatus Interest Group of CEA Technologies Inc (CEATI). CEATI is focused on coordinating research and cost-sharing efforts among electrical utilities. It has published research report on Instrument Transformer Condition Assessment and Diagnostics. The interest group has sponsored the report which consists of literature review and worldwide survey of utilities to identify the best practice) http:// www.ceatech.ca/psearch.php.
24 oct 2007 gva 73