DC Busbar Protection Overview

Protection zone
IdCH IdLH UdH IacY

UsumY

3 3 3
UsumD

DCFilter

Protection zone
IacD Uac IdCN UdN HSGS HSNBS IdLN MRTB Idee2 Idee1

IdSG IdLN_op HSNBS

MRS IdMRS

Other Pole

Page 2

April 2009

E T PS EN21

Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

DC C&P Training DC-Protection Functions DC Busbar Protection


HV DC Busbar Differential Protection (87HV)

IdCH

IdLH

UdH IacY

UsumY

3 3 3
UsumD

DCFilter

IacD Uac IdCN UdN HSGS HSNBS IdLN MRTB Idee2 Idee1

IdSG IdLN_op HSNBS

MRS IdMRS

Other Pole

Page 3

April 2009

E T PS EN21

Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

DC C&P Training DC-Protection Functions DC Busbar Protection


HV DC Busbar Differential Protection (87HV)

Protection Task

Faults to ground or neutral within protection zone

Evaluation Principle Abs(IdLH IdCH) > threshold

Initiated Sequences At rectifier: Converter Block to Pole Control At inverter: Converter Block to Pole Control, Bypass Pair Firing Inhibit Retarded Protection Task for both stations if firing pulses are blocked: Opening of HSNBS ESOF to Pole Control Typical settings Threshold = 0.25 p.u. Delay time = 10 ms
Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

Page 4

April 2009

E T PS EN21

DC C&P Training DC-Protection Functions DC Busbar Protection


Neutral DC Busbar Differential Protection (87LV)

IdCH

IdLH

UdH IacY

UsumY

3 3 3
UsumD

DCFilter

IacD Uac IdCN UdN HSGS HSNBS IdLN MRTB Idee2 Idee1

IdSG IdLN_op HSNBS

MRS IdMRS

Other Pole

Page 5

April 2009

E T PS EN21

Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

DC C&P Training DC-Protection Functions DC Busbar Protection


Neutral DC Busbar Differential Protection (87LV)

Protection Task

Faults to ground or high voltage within protection zone

Evaluation Principle Abs(IdLN IdCN) > threshold, (2 stages) Initiated Sequences ESOF to Pole Control Open AC circuit breaker Opening of HSNBS 1st stage: Threshold = 0.25 p.u.; Delay time = 50 ms 2nd stage: Threshold = 0.07 p.u.; Delay time = 500 ms

Typical settings

Page 6

April 2009

E T PS EN21

Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

DC C&P Training DC-Protection Functions DC Busbar Protection


DC Differential Back-Up Protection (87DCB)

IdCH

IdLH

UdH IacY

UsumY

3 3 3
UsumD

DCFilter

IacD Uac IdCN UdN HSGS HSNBS IdLN MRTB Idee2 Idee1

IdSG IdLN_op HSNBS

MRS IdMRS

Other Pole

Page 7

April 2009

E T PS EN21

Copyright Siemens AG 2008. All rights reserved. Energy Sector - Power Transmission Solutions

DC C&P Training DC-Protection Functions DC Busbar Protection


DC Differential Back-Up Protection (87DCB)

Protection Task

Earth faults at HV or Neutral DC busbars or pole equipment

Evaluation Principle Abs(IdLH IdLN) > threshold, (2 stages) Initiated Sequences ESOF to Pole Control Open AC circuit breaker Opening of HSNBS 1st stage: Threshold = 0.25 p.u.; Delay time = 200 ms 2nd stage: Threshold = 0.07 p.u.; Delay time = 1000 ms

Typical settings