System OK Indicator
Flashing green System OK LEDs indicate that the controller is operating normally
Schneider Electric < DA> <08/10/2009> 4
Panel On
Trip Key
Opened state indicator
Close Key
Closed state indicator
Trip Key
Opened state indicator
Close Key
Closed state indicator
An audible tone will sound and an alert message appears on the display even if its off at the time. Trip/Close
Circuit Isolation
Operation of these switches creates a physical break in the Trip or Close circuit.
Located below Interface
Enabled
Disabled
10
Quick Keys
The controller has four user configurable keys that provide the capability for the operator to quickly access commonly used settings without having to navigate to the relevant panel page. The default configuration of these keys in the setVUE interface can be changed by the user. WSOS or the Operator Interface can be used to assign the function to each key. A set of stick-on labels is provided to change the text of the quick keys to match the new function.
Schneider Electric < DA> <08/10/2009> 11
12
Menu Navigation
HATCH OPEN
SYSTEM STATUS
MENU
EVENT LOG
MENU
MEASUREMENT
MENU
MENU
COMMUNICATION
MENU
AUTOMATION
MENU
PROTECTION
The setVUE menu is organized into logical groups called Display Groups. Within each display group are a number of pages.
The key moves to the next display group in tern. The keys scroll through the screens within a display group. All display groups are circular.
Schneider Electric < DA> <08/10/2009> 13
14
Custom Menu
The Custom Menu key gives access to the custom menu which was configured using WSOS5. Where a Custom Menu has been configured, an operator should only need to press the Custom Menu key to step through view the selected screens. Alternatively the display may have been configured to scroll automatically when the panel is on. Pressing the Custom Menu key will have no effect if it has not been configured.
15
Custom Menu
HATCH OPEN
SYSTEM STATUS
MENU
EVENT LOG
MENU
MEASUREMENT
MENU
MENU
HATCH OPEN
MENU
COMMUNICATION
MENU
AUTOMATION
MENU
PROTECTION
CUSTOM MENU
The main menu can be accessed by pressing the key. Return to the custom menu by pressing the key.
CUSTOM MENU
16
17
----------------------------------------- EVENT LOG --------------------------------- E 01 / 06 / 09 01 / 06 / 09 01 / 06 / 09 09:48:31:47 09:51:28:00 09:51:59:27 Panel Close Request Seq Reset Time 20 s Phase Set 100 Amp
----------------------------------------- EVENT LOG --------------------------------- E OCP WSOS A: Protection WSOS A: Protection Panel Close Request Seq Reset Time 20 s Phase Set 100 Amp
18
The display area consists of four lines, each forty characters long.
To the right of the title is a code, indicating the display group to which the page belongs: S E M P A C System Status Display Group Event Log Measurement Display Group Protection Display Group Automation Display Group Communications Setup
19
---------- PASSWORD ENTRY ---------A AAAA ---Active Protection Setting Has Changed
3. Protection Settings
1. Phase Fault Trip Setting 2. Earth Fault Trip Setting
When this message appears, press Menu or Enter to put the changed setting into service. Otherwise continue changing settings.
CHANGED ACTIVE PROTECTION SETTINGS The changed active PROTECTION SETTINGS Are now in service. Select the MENU or The ENTER key to continue.
20
21