DVR2000E/EC Hardware Installation


- IOM Reference -

This section will discuss the installation of the DVR2000E/EC hardware. This is discussed in detail in the DVR2000E Installation, Operation, and Maintenance (IOM) Manual (GPN019 03/06), Pages 26 36.

DVR2000E/EC Hardware Installation


- Mounting -

The DVR2000E Installation, Operation, and Maintenance (IOM) Manual (GPN019 03/06), Pages 26 - 28 provides you the information necessary to mount the DVR2000E/EC voltage regulator. Please refer to this information for: Size evaluation,

A cutout template, and


Drilling dimensions.
Ref: IOM, Page 26 3

DVR2000E/EC Hardware Installation


- Connections -

The DVR2000E Installation, Operation, and Maintenance (IOM) Manual (GPN019 03/06), Pages 29-32 provides you the information necessary to connect the DVR2000E/EC voltage regulator to your generator. Please refer to this information for detailed instructions and definitions of each terminal.
NOTE: Be sure that the DVR2000E/EC is hard-wired to earth with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case.

Ref: IOM, Page 26

DVR2000E/EC Hardware Installation


- Typical Connection Diagram Three Phase Sensing

Ref: IOM, Page 33

DVR2000E/EC Hardware Installation


- Typical Connection Diagram Single Phase Sensing

Ref: IOM, Page 34

DVR2000E/EC Hardware Installation


- Electrical Connection Notes -

1. In order to parallel with the DVR2000E/EC, a current transformer (CT) MUST be installed in the B-phase of the generator and connected to the CT1 and CT2 inputs of the regulator.

2. If installing a CT, always confirm that the dotside is towards the generator as shown in the connection diagrams.
Ref: IOM, Page 33 7

DVR2000E/EC Hardware Installation


- Electrical Connection Notes (Contd) -

3. To disable the droop circuit (Parallel Control), you MUST SHORT Terminals 52L and 52M. This will be necessary to run the generator as a stand-alone unit. 4. To disable the VAR/PF Control (available on DVR2000EC only), you MUST SHORT Terminals 52J and 52K. This will be necessary to run the generator as a stand-alone unit if using a DVR2000EC regulator.
Ref: IOM, Page 33 8

DVR2000E/EC Hardware Installation


- Typical Cross-Current Connections Connection of (2) Generators

Ref: IOM, Page 36

DVR2000E/EC Hardware Installation


- Typical Cross-Current Connections Connection of (3+) Generators

Ref: IOM, Page 36

10

DVR2000E/EC Hardware Installation


- Electrical Connection Notes (Contd) -

5. The suggested 0.1 Ohm resistor shown for the cross-current (reactive differential) connections may need to vary. This burden resistor should have a value approximately (10) times the cross current loop resistance for proper differential operation. The volt-ampere (VA) capacity of the paralleling current transformers should be considered after sizing the burden resistor.
Ref: IOM, Page 32 11

DVR2000E/EC Hardware Installation


- Install Protective Cover -

NOTE: It is highly recommended that the protective cover be installed on the DVR2000E / DVR2000EC whenever power is applied to the DVR2000E / DVR2000EC as the heat sinks on the rear-side of the DVR2000E / DVR2000EC are live when power is applied. Ref: IOM, Page 27 12

DVR2000E/EC Hardware Installation


- End of Section -